TECHNICAL SPECIFICATION

FOR

DC STRING CABLES
TECHNICAL SPECIFICATION
For
DC STRING Cables

DOCUMENT CONTROL SHEET

TECHNICAL SPECIFICATION

FOR

DC STRING CABLES

Project: Rev.
Mayfair Renewable Energy Private Limited - 22 Doc. No: LSEPL-032-PV-ELE-751-TS-3007
0
MWac
(22.47 MWdc) - Project in RON district. Date: 20/06/2017 Page 2 of 6
TECHNICAL SPECIFICATION
For
DC STRING Cables

 Interconnecting SPV modules and Module to SMU :-

Vendor
Sr. Particulars Technical Description
No. Compliance
1) Cable Size (Sq.mm) 1C, 4 Sq.mm & 6 Sq. mm.
2) Voltage rating 1100 V (1.8 KV DC)
Electrolytic multi stranded annealed
tinned copper conductor class 5, IEC
3) Conductor 60228

The conductor must be type test passed


Temp. resistance, halogen free, flame
4) Core Insulation
retardant, Electron beam cross linked
Weather resistant, halogen free, flame
retardant, hydrolysis res stant, UV ,temp
5) Outer Sheath (Jacket) resistant , Electron beam cross linked
(Preferably Positive- Red, Negative-
Black)
6) Temp range (°C) -40 to 120 °C
7) Ambient Temp range (°C) -40 to 90 °C
8) Short circuit Temp range (° ) Bidder to submit
9) DC resistance at 20°C (ohm/km) Bidder to submit
10) DC resistance at 70°C (ohm/km) Bidder to submit
11) DC resistance at 90°C (ohm/km) Bidder to submit
12) Current carrying capacity in air (A) Bidder to submit
Current carrying capacity when Bidder to submit
13)
three cable in conduct
14) Max overall diameter (mm) Bidder to submit
15) Minimum bending radius (mm) Bidder to submit
16) Expected Life > 25 Years
Applicable Codes & Standards
UL, TUV 2 PFG 1169/08.2007 Or EN
17) Complying Standards 50618
a UV and Sunlight Resistant HD/605/A1
b Ozone resistant EN 50396
c Halogen free IEC-60754-1/2
d Fire resistant UL, TUV 2 PFG 1169/08.2007
e Smoke emission IEC 61034, EN 61034-1 2
f Shrinkage test EN 60811-1-3
g Pressure test at high temp EN 60811-3-1
h Damp heat test EN 60068
i Acid and alkaline resistance EN 60811-2-1
Construction of Conductor Tinned
j Flexible Copper Conductor IEC 60228 Class 5
Temperature index and service life
k of over 20-25 years IEC 60216

Project:
TECHNICAL SPECIFICATION
For
DC STRING Cables

Notes:
1.1 Outer Sheath of cable must have
i) Manufacturer name, Cable Size and voltage grade
l ii) Word FRNC at every 5 meters
iii) Sequential marking of length of cables in meters at every 1 meter.
2.0 Acceptance test shall be included in the cable price.
3.0 Sampling of the ac eptance test as per IS 7098.

Vendor
Type, Routine, Acceptance tests :
Compliance
Type test, routine, acceptance tests requirements for these cables shall be as per
TUV specification 2 Pfg 1169/08.2007. Charges of routine and acceptance test shall
be deemed to be included in the cable price. Sampling for acceptan e test as will be
as per IS 7098.

 Required Quantity:

Sr. Description Qty.


No
1 1CX6 Sq.mm DC Cable (Tinned Copper Conductor insulated
at inner & outer sheath as per following specifications)
1.1 With Inner Sheath & Outer sheath BLACK for –ve pole cable. 60 Km*
1.2 With Inner sheath & Outer sheath RED for +ve pole cable. 60 Km*
2 1CX4 Sq.mm DC Cable (Tinned Copper Conductor insulated
at inner & outer sheath as per following specifications)
2.1 With Inner Sheath & Outer sheath BLACK for –ve pole cable. 10 Km*

2.2 With Inner sheath & Outer sheath RED for +ve pole cable. 10 Km*

* Actual quantity may vary.

Commissioning of the System:

- All cables to be installed by Lanco team.

Product Warranty:
 The Vendor shall be legally bound to provide a performance guarantee ensuring all the cable
units will be fully functional with desired output for 300 months from the date of
commissioning.

Project: 0
Page 4 of 6
TECHNICAL SPECIFICATION
For
DC STRING Cables

Submission:
Upon securing the project, the Vendor shall submit following documents for the selected cable.
 General Arrangement drawing showing front and rear view, overall dimensions,
installation plan, termination arrangements, packing dimensions and weights.
 Technical literature giving complete specifications and information.
 Installation guide.
 Independent test characteristics.
 Temperature rise type test report.
 Other report specified, if any.

General Technical Parameters for DC String Cables ( 4 & 6 Sqmm.)


S.No. Description Unit Specification
Cable Size sq.mm
Specification
Max. temp at conductor deg. C
1 General
Ambient temperature -- Up to 50 C (minimum
0

Voltage rati g
No. of cores nos.
Material
diameter of wires(max) mm
2 Conductor Type of conductor
Nominal cross section sqmm
No. of strand
Material
Thickness mm
3 Insulation
Colour
Material
Thickness mm
Nominal overall diameter mm
4 Outer sheath Marking on the cable with meter marks
Colour
Approx. cable weight kg/km
Current rating at 60 deg. C - In Air A
Max D.C resistance of conductor @ 20 deg. C ohm
Max. conductor temp. at termination of short ckt. deg. C
5 Electrical Continuous current carrying capacities when A
cable laid in air @ 40 deg. C
Continuous current carrying capacities when
cable laid in ground @ 40 deg. C
6 Packing Packing length meter

Project: 0
Date: 20/06/2017 Page 5 of 6
TECHNICAL SPECIFICATION
For
DC STRING Cables

Type of packing

 Cable drums
(a) Cables shall be supplied in returnable wooden or steel drums of heavy construction. The
surface of the drum and the outer most cable layer shall be covered with water proof cover. Both
the ends of the cables shall be properly sealed with heat shrin able PVC/ rubber caps secured by
'U' nails so as to eliminate ingress of water during transportation, storage and erection. However,
for Single core cables upto 6 Sq. mm size, supplier can do alternative packaging of whole
Drum/Spool to eliminate ingress of water during transportation, storage and erection. Wood
preservative anti-termite treatment shall be applied to the entire drum. Wooden drums shall
comply with IS: 10418.

(b) Each drum shall carry manufacturer's name, purchaser’s n me, address and contract number,
item number and type, size and length of cable and net gross weight stenciled on both sides of
the drum. A tag containing same information shall be attached to the leading end of the cable. An
arrow and suitable accompanying wording shall be marked on one end of the reel indicating the
direction in which it should be rolled.