Test Record
Difference in leakage currents shall not differ by more than 20% for
different phases in same circuit. Further, the test results to be
compared against factory test values and any variation of more than
20% from the factory test results shall be investigated.
11 Ensure all termination box covers and guards are correctly re-fitted
and identified as HV.