MODEL 206-F-TYPE 4 Modulating Float Valve: Key Features
MODEL 206-F-TYPE 4 Modulating Float Valve: Key Features
MODEL 206-F-TYPE 4
MODULATING FLOAT VALVE
KEY FEATURES
• Maintains relatively constant level
• Automatic compensation for level draw-down
• Standard integral damping reduces hunting
• Drip-tight at high level shut-off
• Low supply pressure options
PRODUCT OVERVIEW
The Singer model 206-F-Type 4 modulating float valves are based on the 206-PG main valve. They are ideal for
balancing the inflow and outflow demand into the reservoir and maintaining level at the designated maximum.
The valve closes drip-tight at the maximum level and modulates to maintain the tank level. The float pilot is
remotely installed at the high level in the reservoir tank. Pilot connections to the main valve are connected in the
field. As the reservoir level drops the main valve is opened proportionally to increase the filling rate. Movement
of the main stem alters the size of the closing restriction, interrupting the tendency of the valve to hunt.
TYPICAL APPLICATION
R400 pilot
Singer 206-F-Type 4
ORDERING INSTRUCTIONS
Refer to page 244 for the order form and ordering
instructions.
Additionally, include the following information for this
product:
Single chamber (206)
MODEL 206-F-TYPE 4
MODULATING FLOAT VALVE
206-F-Type 4 Flow Capacity (See 206-PG in Main Valve section for other valve data)
Size (inches) 3 in 4 in 6 in 8 in 10 in 12 in 16 in 18 in 20 in
Size (mm) 80 mm 100 mm 150 mm 200 mm 250 mm 300 mm 400 mm 450 mm 500 mm
Maximum Continuous (USGPM) 300 580 1025 2300 4100 6400 9230 16500 16500
Pressure Drop (Bar) 1.3 1.0 1.2 1.4 1.2 1.2 1.2 1.6 1.5
206-F-Type 4 Flow Capacity (See 206-PG in Main Valve section for other valve data)
Size (inches) 24 x 16 in 24 x 20 in 28 in 30 in 32 in 36 in 40 in
Size (mm) 600 x 400 mm 600 x 500 mm 700 mm 750 mm 800 mm 900 mm 1000 mm
Maximum Continuous (USGPM) 16500 21700 33600 33650 33700 33800 55470
Maximum Continuous (L/s) 1040 1370 2120 2123 2126 2132 3500
Pressure Drop (Bar) 1.4 1.4 1.2 1.2 1.2 1.2 1.2
Globe Style
Flat Diaphragm 'E'
Flow
'E' 'E'
'E'
'E' Flange
Flow
'C' Diameter
'F' 'C'
'D' 'F' 'D' 'D' Dim
'D'
Flange Feet'A'
'A' 'A' 'B' 'B' for Safety and Standard Opposite
Convenience