Features: 83 Series - Modular Timers 12 - 16 A
Features: 83 Series - Modular Timers 12 - 16 A
SERIES
Contact specification
Contact configuration 1 CO (SPDT) 1 CO (SPDT) 1 CO (SPDT)
Rated current/Maximum peak current A 16/30 16/30 16/30
Rated voltage/Maximum switching voltage V AC 250/400 250/400 250/400
Rated load AC1 VA 4,000 4,000 4,000
Rated load AC15 (230 V AC) VA 750 750 750
Single phase motor rating (230 V AC) kW 0.5 0.5 0.5
Breaking capacity DC1: 30/110/220 V A 16/0.3/0.12 16/0.3/0.12 16/0.3/0.12
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi AgNi
Supply specification
Nominal voltage (UN) V AC (50/60 Hz) 24...240 24...240 24...240
V DC 24...240 24...240 24...240
Rated power AC/DC VA (50 Hz)/W < 1.5 / < 2 < 1.5 / < 2 < 1.5 / < 2
Operating range V AC 16.8...265 16.8...265 16.8...265
V DC 16.8...265 16.8...265 16.8...265
Technical data
Specified time range (0.05…1)s, (0.5…10)s, (0.05…1)min, (0.5...10)min, (0.05...1)h, (0.5...10)h, (0.05...1)d, (0.5...10)d
Repeatability % ±1 ±1 ±1
Recovery time ms 200 200 200
Minimum control impulse ms — — 50
X-2013, www.findernet.com
Wiring diagram
(without control signal)
8 3 . 0 1 . 0 . 2 4 0 . 0 0 0 0
Series Versions
Type 0000 = Standard
0 = Multi-function (AI, DI, GI, SW, BE, CE, DE, WD) Supply voltage
1 = On-delay (AI) 240 = (24 ... 240)V AC/DC
2 = Interval (DI) Supply version
4 = Off-delay with control signal (BE) 0 = AC (50/60 Hz)/DC
6 = Power off-delay (True off-delay) (BI)
8 = Star-delta (SD) No. of poles
9 = Asymmetrical flasher (LI, LE, PI, PE) 1 = 1 CO (SPDT)
2 = 2 CO (DPDT) for 83.02 and 83.62
2 = 2 NO (DPST-NO) for 83.82
Technical data
Insulation
Dielectric strength between input and output circuit V AC 4,000
between open contacts V AC 1,000
Insulation (1.2/50 μs) between input and output kV 6
EMC specifications
Type of test Reference standard 83.01/02/11/21/41/82/91 83.62
Electrostatic discharge contact discharge EN 61000-4-2 4 kV 4 kV
air discharge EN 61000-4-2 8 kV 8 kV
Radio-frequency electromagnetic field (80 ÷ 1,000 MHz) EN 61000-4-3 10 V/m 10 V/m
(1,000 ÷ 2,700 MHz) EN 61000-4-3 3 V/m 3 V/m
Fast transients (burst) (5-50 ns, 5 and 100 kHz) on Supply terminals EN 61000-4-4 7 kV 6 kV
on control signal terminal (B1) EN 61000-4-4 7 kV 6 kV
Surges (1.2/50 μs) on Supply terminals common mode EN 61000-4-5 6 kV 6 kV
Timers and Monitoring relays
4
83
SERIES
83.11 83.21
Screw terminal Screw terminal
83.82 83.91
Screw terminal Screw terminal
X-2013, www.findernet.com
5
83
SERIES
Accessories
Sheet of marker tags, for types 83.01/11/21/41/62/82, plastic, 72 tags, 6x12 mm 060.72
060.72
087.02.2
Z1 Z2
15 - 18 15 - 16
OFF Open 25 - 28 25 - 26
15 - 18 15 - 16
ON Open 25 - 28 25 - 26
Open 15 - 18 15 - 16
ON (Timing in Progress) 25 - 28 25 - 26
15 - 16 15 - 18
ON Closed 25 - 26 25 - 28
* The LED on type 83.62 is illuminated when supply voltage is supplied to timer.
• Possible to control an external load, such as another relay coil or timer, connected to the control signal terminal B1.
** ** A voltage other than the supply voltage can be applied to the control signal (B1), example:
A1 - A2 = 230 V AC
B1 - A2 = 12 V DC
6
83
SERIES
Functions
Wiring diagram U = Supply voltage S = Signal switch = Output contact
Multi-function Type (AI) On-delay.
without control signal 83.01 Apply power to timer. Output contacts transfer after preset
83.02 time has elapsed. Reset occurs when power is removed.
(DI) Interval.
Apply power to timer. Output contacts transfer immediately.
After the preset time has elapsed, contacts reset.
83.01
(GI) Pulse delayed.
Apply power to timer. Output contacts transfer after preset
time has elapsed. Reset occurs after a fixed time of 0.5s.
83.02 type
Contact mode selector Functions without control signal (example: AI) Functions with control signal (example: BE)
2 timed contacts
Both output contacts (15-18 and 25-28) Both output contacts (15-18 and 25-28)
follow the timing function follow the timing function
Both output contacts [15-18 and 25(21)-28(24)] Both output contacts [15-18 and 25(21)-28(24)]
stay permanently open stay permanently open
1 timed +
1 instantaneous contact
X-2013, www.findernet.com
The output contact 15-18 follows the timing function The output contact 15-18 follows the timing function
The output contact 21-24 follows the power supply (U) The output contact 21-24 follows the control signal (S)
7
83
SERIES
with control signal (S) 83.41 (BE) Off-delay with control signal.
Power is permenently applied to the timer.
The output contacts transfer immediately on closure of the
control signal (S). Opening the control signal initiates the
preset delay, after which time the output contacts reset.
83.41
Asymmetrical recycler 83.91 (LI) Asymmetrical flasher (starting pulse on)- (Z1-Z2 open).
without control signal Apply power to timer. Output contacts transfer immediately
and cycle between ON and OFF for as long as power is
applied. The ON and OFF times are independently
Timers and Monitoring relays
adjustable.