Comfortpoint Cp-Expio: Expansion Io Board

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

TM

ComfortPoint
CP-EXPIO
EXPANSION IO BOARD

! Expand point capacity of CP-IPC to maximum 128 I/Os

! Maximum fifteen CP-EXPIO modules per one CP-IPC

! Powerful processor to support faster IO scanning

! Flexible and easy configuration with ComfortPoint Studio

SYSTEM ARCHITECTURE FEATURES

Powerful Processor
Web Browser
http:// or https:// CP-EXPIO Expansion I/O Boards has Powerful processor on-
Management Level

User Interface & Management Tools


EBI board for fast input/output scanning.
Redundant Server
Redun
EBI BACnet client ComfortPoint Studio
udio
o

WAP
Mixed Inputs and Outputs
Internet
CP - EXPIO Comes with a mix of 24 input and outputs to suit any
PDA application requirements.
BACnet IP Network
CP-IPC CP-EXPIO CP-DIO Expandable
CP-IPC
PDA CP-IPC can connect to up to 15 Expansion IO Boards. All the
3 Party BACnet
rd

integration CP - HMI Expansion IO board are connected on the same RS485 bus.
BACnet MS/TP Network
BACnet MS/TP

Programming and Configuration


Modbus

CP - HMI
Energy Meter
ComfortPoint Studio allows user to add/delete/modify expansion
CP - Online Chiller / Boiler
boards and IO Assignment.
CP-SPC
Addressing
Field Level

3rd Party BACnet


integration CP-SPC 32- bit Native Addressing of CP-EXPIO is done via onboard HEX Switch. The
BACnet Solution

CP-DIO PDA
address can be between 1 to 15.
Balancing Tool

CP-VAV
Firmware Upgrade
Firmware on the CP-EXPIO can be easily upgraded using
ComfortPoint online.
Flexible mounting options
DIN-rail or Wall mounting.
BTL Logo, UL Logo & the CE Mark Logo are used to indicate product compliance and/or
conformance to those standards. These Logo/Marks are trademark of the respective Agencies.

Note: The information provided herein are correct and up to date at the time of production. Due
to Product renovation & technology upgrade, the specifications given in this data sheet are
subject to change. Please contact your nearest HBS branch for current updates
SPECIFICATIONS DIMENSIONS

Electrical Data Environmental


Operating Voltage
Temperature
! 24 VAC ± 20%, 50/60 Hz, 15 VA
! 1 “power” LED ! Operation: (0 to 50) 0C
! Storage: (-20 to +70) 0C
Power Consumption: Max. 15 VA,
Ambient Humidity (operation and storage)
Housing Material: ABS Plastic ! 5 to 93% relative humidity, non-
condensing
Mounting Certifications
! DIN rail ! CE
! Wall mounting ! UL 916
Protection Class: IP 20
Models
Integrated I/Os
! CP-EXPIO: 24 points on board
Digital Output
Hardware Interfaces
! 4 DOs, 24 VAC TRIACS with LED indication
RS485C Connection
Digital Input
! Allows to connect CP-IPC and other
! 6 DIs which can be configured as Expansion IO Boards
Potential-free contact or pulse
HEX Switch
counter @ 15 Hz
! For Addressing of EXPIO
! LED Indication, illuminated when
contact close Reset Button
Analogue Output
! 6 AOs, 0-10 Vdc
Analogue Input
! 12 bit A/D resolution
! 8 Universal inputs
! 0/2 -10 Vdc, PT 1000 (-50 to +
150) oC, NTC 20K (-50 to +150) oC

MTBF ( Mean Time Between Failure ) Data


! 100000 Hours or 11.4 Years

Find out more


Contact a Honeywell representative today.
Visit www.honeywell.com/buildingsolutions/offices
for a Honeywell office near you.
Honeywell Building Solutions
North Asia
No. 430 Li Bing Road, Zhang Jiang Hi-Tech Park ComfortPoint™ is a trademark of Honeywell
Pudong New Area. Shanghai 201203, China International Inc.
Tel: +86 21 2894 2000 BACnet® is a registered trademark of American
Society of Heating, Refrigerating
South Asia Pacific and Air-Conditioning Engineers (ASHRAE).
Level 3, 2 Richardson Place
North Ryde NSW 2113 Australia
Tel: +61 2 9353 7000 SL-53-1092 AP
April 2010
www.honeywell.com © 2010 Honeywell International Inc.