Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Executive Order G-70-150-AD

Exhibit 1

VaporVac System Equipment List


State Fire Marshal
Component Manufacturer/Model Identification Number

Nozzle OPW 11VAI-xx (Figure 1A) 005:008:050


without vapor valve
xx = 22 (15/16" OD spout, hold open latch (HOL))
27 (13/16" OD spout, HOL)
42 (15/16" OD spout, no HOL)
47 (13/16" OD spout, no HOL)

Husky V3 6201xxx (Figure 1B) 005:021:011


without vapor valve
xxx= 039 (leaded spout, hold open latch (HOL))
xxx= 049 (unleaded spout, HOL)
xxx= 079 (leaded spout, no HOL)
xxx= 089 (unleaded spout, no HOL)

Emco Wheaton A4500-xx (Figure 1C) 005:007:042


xx = 051 (15/16" OD spout, hold open latch (HOL))
052 (13/16" OD spout, HOL)
053 (15/16" OD spout, no HOL)
054 (13/16" OD spout, no HOL)

Saber N11110, N12110, N21110, N22110 005:051:001


(Refer to the appropriate revision of Executive Order G-70-159)

Splash Guards Splash guards are optional but, if used, must be the guards listed
for use with the nozzle. Local districts may require splash guards.
See Figure 1A or 1B or 1C for their location on the nozzle.

Inverted Coaxial Hose Catlow Vapor Mate 005:033:005


Dayco 7282 Superflex 2000 005:033:005
Dayco 7292 Superflex 4000 005:033:006
Goodyear Flexsteel 005:036:002
Thermoid Hi-Vac 005:037:003
Thermoid Hi-Vac S 005:037:004
VST VSTaflex 005:052:001
OR
Any inverted coaxial hose which is CARB-certified
for use with the VaporVac system.
Executive Order G-70-150-AD, Exhibit 1, Page 2

Breakaway Couplings Without A Vapor Poppet


Catlow
AV200 005:030:005
AV200-1 005:030:005
Emco Wheaton A5019-001 005:030:005
OPW 66CI 005:030:005
Richards Industries
VA-51 (reconnectable) 005:031:007
VA-61 005:031:009

With A Vapor Poppet


Catlow
AV2001 (reconnectable) 005:030:006
AVR200S (reconnectable) 005:030:010
Emco Wheaton A5219-001 (reconnectable)005:030:010
Husky 4034 (reconnectable) 005:021:009
OPW 66CIP (reconnectable) 005:030:010
Richards Industries
VA-50 (reconnectable) 005:031:007
VA-60 005:031:009
OR
Any inverted coaxial breakaway which is CARB-certified
for use with the VaporVac system.

Swivels Richards Industries


MFVA 005:031:015
STVA (includes a breakaway with a
vapor poppet) 005:031:016
STVA1 (includes a breakaway) 005:031:016

Pressure/Vacuum Valve OPW 523LP, 523LPS 005:008:051


(settings as specified below)
Hazlett H-PVB-1 Gold label 005:017:004
(settings as specified below)
Morrison Brothers 749CRB0600 AV 005:041:001
(settings as specified below)
OR
Any CARB-certified valve with the following pressure
and vacuum settings, in inches water column (wc):

Pressure: three plus or minus one-half inches


(3.0 + 0.5") water column.
Vacuum: eight plus or minus two inches
(8 + 2") water column.

Note: For systems installed before June 7, 1994, a valve with the
following settings may be used until July 7, 1998. Local districts
may require earlier replacement of these valves.
Executive Order G-70-150-AD, Exhibit 1, Page 3

Pressure: at least one and not exceeding three and one-half


inches (1 - 3.5") water column.
Vacuum: at least one-half ounce/inch2 (0.87") water column.

Vapor Pump Blackmer VGR 3/4


Dispensers Gilbarco Advantage Series B"XY"
("X" may be 0 through 9 or A
"Y" may be 0 through 9, A through P)

Schlumberger 4000 Series


4"ABC"-"YZ"-"S"-VG
("A" may be 1 through 4 and designates the number of
products on the front side
"B" may be 0 through 4 and designates the number of
products on the back side
"C" may be 0 through 3 and designates the number of hoses
per side
"Y" may be 2 through 7 and designates computer options
"Z" may be A; D; or none and designates computer options
"S" may be B; L; R; -B-L; -B-R; -L-R; -B-L-R; or no characters
and designates optional features
VG designates the Gilbarco VaporVac system)

VaporVac Retrofit CV00"XY"-"ZZ"


Assemblies ("X" may be 0 through 3
(for the Advantage Series "Y" may be 0 through 9
and MPD-1, 2/C, and 3) "Z" may be 0 through 9 and designates cosmetic features
such as color)

Phase I Adaptors Any CARB-certified device which prevents loosening or


overtightening of the Phase I product and vapor adaptors.

Note: For systems installed before two CARB-certified devices


which prevent loosening or overtightening of the Phase I product
and vapor adaptors are available, or within sixty days after that
date, any CARB-certified Phase I product adaptor may be used for
a period not to exceed four years from the date the second device
was certified. Local districts may require earlier conversion to such
devices.

You might also like