Manual Instrucciones Power One Forza 48 25600pdf
Manual Instrucciones Power One Forza 48 25600pdf
Revision: /
Document number: 037879
Copyright © Power One AS.
All Rights Reserved.
Power-One, AS
Kobbervikdalen 75
P.O.Box 1543
N-3007 Drammen
Unless specifically noted, all addresses, data, characters and persons referenced herein, and all exam-
ples involving names of companies and products, are fictitious examples and are designed solely to il-
lustrate the use of Power One products.
If you find errors or problems with this documentation, please notify Power One. Power One does not
guarantee that this document is error-free. The information in this document is subject to change without
notice.
Originated Hans Andre Dokka Date 23.07.04 Approved Roar Fagerhus Date 23.07.04
Signed Signed
Introduction to the manual
The information contained herein was applicable at the time the manual was ready for printing. Power One
reserves the right to change specifications and designs without notice and without incurring obligation or
liability.
This manual is the work product of Power One and embodies confidential proprietary data in which Power
One retains all rights, including exclusive right of use, reproduction, distribution and sale. It is submitted
under a confidential relationship for a specific purpose, and the recipient agrees by accepting this work
product, not to supply or disclose any information regarding it to any unauthorized person.
Note! The text set off in this manner present an important piece of information that is essential to
highlight.
CAUTION The text set off in this manner provides warning notice that failure to
follow these directions can result in damage to equipment.
WARNING THE TEXT SET OFF IN THIS MANNER PROVIDES WARNING NOTICE
THAT FAILURE TO FOLLOW THESE DIRECTIONS CAN RESULT IN BODILY
HARM OR LOSS OF LIFE AND/OR EXTENSIVE DAMAGE TO EQUIPMENT
Abbreviations
The following abbreviations are used in this manual:
Abbreviation: Description:
PPS P1 Power Supply System
PMP P1 Modular Power
CMP Convection-cooled Modular Power
FMP Fan-cooled Modular Power
PCS P1 Control and Supervision
PCU P1 Control Unit
GMC Galero Modular Controller
PPR P1 Power Rack
PBDU P1 Battery Distribution Unit
PBC P1 Battery Cabinet
PDU P1 Distribution Unit
PPRD P1 Power Rack with DC Distribution
PPC P1 Power Supply Cabinet
PBF P1 Battery Fuse Unit
PCB Printed Circuit Board
LVD Low voltage disconnection
PLD Partial load disconnection
MCB Miniature circuit breaker
MCCB Moulded case circuit breaker
Disclaimer
Power One is not responsible for system problems that are the result of installation or modification of the
instructions provided in this manual.
If you have any problems with your system, e.g. you wonder how to install a new PMP rectifier or you have
some questions regarding messages or alarms on the control module, please see the Troubleshooting
section. If this does not solve your problem, please seek assistance at your local Power One office, or our
head office in Norway. These also concern any indistinctness in the manual.
Contents:
1 System description Forza PPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.2 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1.3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1.4 System description - Forza . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
1.4.1 FMP 32 - Rectifier module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
1.4.2 PCS - Controller system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
1.4.3 PPR 32/4 19"- Subrack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
1.4.4 PBDU, PBF and PDU - Distribution modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
1.4.4.1 Low voltage disconnection (LVD) (Option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
1.4.4.2 Partial load disconnection (PLD) (Option). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.1 Safety - Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.2 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.2.1 Lethal voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.2.2 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.2.3 Precautions for lead acid batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.2.4 Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.2.5 High temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.3 Cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2.3.1 Storage and transportation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2.3.2 Handling electrostatic sensitive devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2.3.3 Traceability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2.3.4 Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
3 Installation guide Forza PPC guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1 Site requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.2 AC Power source requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.3 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.4 Installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.4.1 Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.4.2 Tools required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.4.3 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
3.4.3.1 Connection of mains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
3.4.3.2 DC connections from top. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
3.4.3.3 Connection of Common positive (+) DC cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
3.4.3.4 DC connection from bottom (Only for special made cabinets) . . . . . . . . . . . . . . . . . . . . . . . . 3-7
3.4.3.5 Connection of live DC cables (- 48V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
3.4.3.6 Connection of communication and current share signals. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
3.4.3.7 Connection of expansion cabinet(s) with copper bars. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
3.4.3.8 Connection of expansion cabinet(s) cable to copper rail under floor level . . . . . . . . . . . . . .3-10
3.4.3.9 Connections of fuse alarms between cabinets.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-11
3.4.4 Connection of alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-12
3.4.5 Connection of symmetry measurement and temperature sensor . . . . . . . . . . . . . . . . . . . . . . .3-13
4 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.1 Commissioning overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Table of contents ix
Table of contents
1.1 General
Forza modular DC power cabinet systems are designed to meet rigid telecom applications with very high
reliability and flexibility for future expansion. This cabinet power solutions provide rectification, system
management and power distribution while maintaining high reliability and offering flexibility for future
expansion. The Forza Power Systems are based on hot-swappable rectifier modules (FMP 32.48) output
power available at 3200W per module.
System management is accomplished through messages and alarms displayed on the system controller’s
(PCS) LCD screen and can also be displayed remotely via the PC-based PowCom™1 software package.
Highly scalable PPC range with vertical raiser bars for hot live expansion or rectifier shelf’s and DC
distribution.
Note! Normally rectifier modules are installed in the cabinet at shipment, but in some particular cases
rectifier modules are shipped separately.
POWER ON
MESSAGE
ALARM
POWER ON
MESSAGE CANCEL
CANCEL RS232
ALARM
PBDU 1
PDU 1
PCS
DC distribution
FMP 32
AC F
F
FMP 32
LVD
FB
BATT
Input: -voltage: 230/400 V 3-phase (site configurable)
-current: <2x10A per module
Output: -voltage: 48V DC nominal / 64000W pr cabinet
-current: Max 64A per. module, 48V
-power: Max 3200W pr. module.
Weight: Rectifier: 4,2 kg
Cabinet dim.: Height: 2150 mm
Width: 600 mm
Depth: 600 mm
1.3 Operation
z The Forza 48-64000 is a floor cabinet solution with a built in DC-bus that enables the plug-in
connection of rectifier subracks and battery / load breaker shelves. This system can accommodate
up to 20 rectifier modules, a supervision module (PCS) and DC distribution with a wide range of
plug-in DC load distributions (low and high ohmic). Up to 64000W/48V steady state power per
cabinet. The system is based up on hot swappable 48V/3200W rectifier modules, which are working
in parallel with automatic load sharing.
z The cabinet system is normally configured with N+1 redundancy, with N as the number of rectifier
modules necessary for feeding the load and charging the battery and 1 as the redundant rectifier
module. In normal operation the rectifier modules, FMP 32, are feeding the load and simultaneously
maintain the batteries in a fully charged state.
z During a mains input power failure, the rectifiers are shut down and the batteries deliver the power
required by the load, for a certain backup time. If the battery voltage drops below the pre-set level,
the low voltage disconnection circuit, LVD disconnects the batteries automatically to prevent battery
deep discharge and thus prolong the battery life. When the mains input power is restored, the
rectifiers start up automatically feeding the load, closes LVD circuit and are starting recharge the
batteries.
z The system performance is supervised and controlled from the supervisory unit, PCS. From this unit
output DC voltage is set, alarm thresholds, LVD circuit operation, temperature compensated battery
charging, etc. Any malfunction will be indicated by LED, text in the display and operation of dry
contacts. How ever, PCS is not a single point of failure. In the event of malfunction in the PCS, basic
tasks like feeding the load and charging batteries, will be maintained by the rectifier modules directly
at preset default values.
z The alarm and threshold setting of the Forza can be set locally by use of the PCS push buttons and
menu guided operation or remotely, by use of the PowComTM program.
Load outputs:
Several available load breaker modules based on:
MCCB’s: 1x1500A, 2x600A, 2x384A and 4x384A
MCB’s: 24x2-63A, 16x80-100A, 24x216A High ohmic.
Knife fuses: 5xNH1-3 and 9xNH00
Battery outputs:
Several available battery breaker modules based on:
MCCB’s: 1x1500A, 2x600A and 4x384A
MCB’s: 12x100A.
Knife fuses: 5xNH1-3
See product description PBDU, PBF and PDU for detailed information about the actual module.
The distribution has no special operation other than switching the battery and load breakers on and off. All
DC distribution breakers are supervised by measuring voltage drop across each breaker.
Breakers which are not connected to any load, will not cause breaker alarm even if they are left open.
Due to a small leakage current (2,5-3 mA) through the alarm circuit the voltage measured with a DVM
(Digital Volt Meter) on an open breaker output, will be nearly equal to output rectifier voltage.
If a battery breaker fault occurs or is simulated it might take from 2-10 minutes before the fault is indicated,
depending on the battery condition.
The distribution module has common "+" and breakers in "-" leg. For more information see schematic
drawing in Appendix A.
At a mains outage, PCS will open the PLD contactor when batteries has discharged down to a certain
voltage, or the battery voltage has been under a certain voltage for a predetermined time. The
disconnecting has to be set according to the present load and battery manufacturers discharge tables or
requirements.
The distribution module has common "+" and breakers in "-" leg. For more information see schematic
drawing in Appendix A.
2 Safety
Safety 2-1
Document number: 028580.fm
Revision: A
Safety
The instructions in the Customer Documentation must be followed by properly trained and authorized
personnel when installing, operating, commissioning or maintaining this equipment. Neglecting the
instructions may be dangerous to personnel and equipment. Although the purpose of safety devices,
routines and regulations are meant to take care of the safety of the user, nobody is excused from using
common sense at all times when operating or otherwise handling the equipment.
These above mentioned safety guidelines include Warnings, Cautions and Notes.
2.2 Warnings
All persons who perform any operations on this equipment should be advised of the potential dangers.
Ensure that the following guidelines and cautions are observed, when dealing with high voltage systems
and equipment:
z Potentially lethal voltages are present within the system. Ensure that all power supplies are
completely isolated by setting all power switches to OFF, disconnecting all relevant connectors and
removing all relevant breakers before attempting any maintenance work. Do not rely on switches
alone to isolate a power supply.
z Potentially lethal voltages are present within this system. Ensure that high voltage safety
requirements are implemented before attempting to work on the system with power connected.
z Potentially lethal voltages can be induced if the equipment is not grounded (earthed) correctly.
Ensure that all ground connections are secure.
2.2.2 Grounding
Ensure the following guidelines are observed when dealing with equipment that may contain lead acid
batteries:
z Any attempt to burn these batteries may result in an explosion and the generation of toxic fumes.
z Should a lead acid battery suffer damage, it must be moved into a well-ventilated area. Contact with
the corrosive fluid must be avoided.
z Neutralize any acid corrosion with copious amounts of a solution of baking soda and water. Wipe of
all traces of soda.
z If the lead acid battery is removed from the equipment to which it is fitted, any exposed contact must
be insulated prior to disposal.
z Ensure that protective full-face shields, rubber gloves and aprons are worn and insulated tools are
used when working with the batteries.
2.2.4 Weight
Safety 2-3
Document number: 028580.fm
Revision: A
Safety
2.3 Cautions
CAUTION! During storage and transportation, the units must remain in their
original packages in order to avoid mechanical damage, maintain tracability, and
protect the units against electrostatic discharge.
2.3.3 Traceability
2.3.4 Breakers
Note! Normally rectifier modules are installed in the cabinet at shipment, but in some particular cases
rectifier modules are shipped separately.
3.4.1 Unpacking
Check that the received equipment is in accordance with the packing list. Ensure that the cabinet and the
equipment have not been damaged during transportation.
You must report any parts that are damaged, missing or incorrect. If possible, correct the problem before
continuing.
CAUTION! Care must be taken when installing this system. The units can be
damaged and can cause damage if not handled with care. Pay particular attention
to the order in which units are installed.
1. Pull out all rectifier modules in order to lower the overall weight.
2. Move cabinet to the right place and rise into on upright position.
3. Use a water leveller making sure that cabinet is levelled. Adjust cabinet legs if necessary.
4. If necessary the cabinet can be fixed to the floor through the plinth or towards the wall.
Figure 3-2
Wall bracket
Tapties
M6 Torx 30
Loose the wall bracket located on the upper part on left and right side by unscrewing the two tapties. Drag
the wall bracket up and fasten it to the cabinet again (see Figure 3-2). The cabinet is now ready to be fixed
to the wall.
3.4.3 Connections
See also: Product description PBF
Product description PDU
Product description PBDU
Make input and output connections as described below.
When connecting mains to terminal blocks use, depending on type of cable, either:
z use a cable tie around conductors as close to the terminal block as possible, to prevent a stranded
conductor to come loose and touch any secondary conductive parts on the backplane or,
z remove as little insulation on cable as possible before entering into terminal block, so that the jacket
prevent a stranded conductor to come loose and touch any secondary conductive parts on the
backplane (Note! The insulation on the cable must have a clearing of minimum 1mm in the terminal
blocks).
Plastic tubes
Mains 1 Mains 2
Mains 2 is supplying subrack 2, position 7 and 8, and subrack 3 position 9, 10, 11 and 12
Mains 3: is supplying subrack 4, position 13, 14, 15 and 16, and subrack 5, position 17 and 18
Mains 4 is supplying subrack 5, position 19 and 20, and subrack 6 position 21, 22, 23 and 24
Figure 3-4
2. Remove the horizontal sheet metal, which is mounted in front of the cable glands. (Fixed from top
with 2xM4 screws)
M4 screws
3. Remove all the cable bushings located over the positive copper bus bar except from the one half of
the inner row.
Note! It is important to select the input cable positions systematically, using the inner row first, in order
to take care of future expansion of cables
4. Remove the "knock out" of the bushing by a hammer and screwdriver or similar tool. Fit the two
bushing parts around the cable and if necessary clamp it with the attached screws.
Figure 3-7
5. If the opening is too big compared to size of cable, wind some scotch tape around the cable.
6. When all cable bushings are fitted and mounted, replace all the unused bushings. Secure the
bushings by fitting the sheet horizontal metal and fix it by enclosed M8 washers and nuts.
Connect common positive (+) DC cables according to Figure 3-9, request torque 30 Nm.
Note! Some cabinets will only have the possibility to connect 1-6 cables.
Figure 3-9
The system is made common positive, 0V positive and –48V negative. A grounding terminal, meant for
central earth, is located on the top of the cabinet. Internal grounding of the system may easily be removed
in case a “floating” output voltage is requested. Unscrew the two torx screws shown in and remove the
copper plate. When the output is “floating”, the positive block in the system may be used for grounding.
This way, a grounding cable of max. 240mm2 may be connected to the positive block.
Figure 3-10
2 x Torx
Copper plate
Common positive (+) connected to
the chassis of the cabinet
Technical data
Figure 3-11
Taptites
Connection • M6
point • Torx 30
Nut Washers Copper bars
1. Remove top, top side panels and front panels in that order.
2. Knock out the punch outs for paralleling. (Located on the top side panels).
3. Use attached screws, nuts and washers for mounting of the copper bars. Required torque: 30 Nm.
The copper bars is to be mounted on top of the connection points (see Figure 3-11 and Figure 3-12) With
two (double) copper bars (see Figure 3-13)
Figure 3-12
Figure 3-13
3.4.3.8 Connection of expansion cabinet(s) cable to copper rail under floor level
Only for special made cabinets and if the system consist of more than one cabinet.
Technical data
Cable from U-shaped copper bars to copper rail section under floor level.
Mount cables from rail section in power cabinets on to rail section under floor level.
Figure 3-14
Floor level
+ Copper rail
- Copper rail
Figure 3-15
Previous cabinet
Fuse alarm signal
Next cabinet /
Main cabinet
If the system consists of more than one cabinet, the cabinets fuse alarm must be connected together using
the fuse alarm contact. For this purpose use max a 1.5mm2 cable.
When all cabinets fuse alarm is connected together, connect one cable from cabinet 1 to main cabinet.
Figure 3-16
ALARM 6 18
17
16
ALARM 5 15
14
13
ALARM 4 12
11
10
J13 ALARM 3 9
8
7
ALARM 2 6
5
4
ALARM 1 3
2
1
The green connectors can be easily removed, if desired, for ease in installing the wires to the connector.
Power-One recommends using 22 AWG wires to connect alarms to the alarm output terminals.
2. Determine whether to reference normally closed or normally open with reference to common for
each alarm contact.
3. Strip the wires back approximately 10mm. Stranded wire may be soldered or covered with copper
ferrule if desired.
4. Insert wire into the correct positions in the green connector and tighten screw to clamp wire into
connector.
5. Route the wires through the cable area at the top left of the cabinet.
Note! The number of battery branches to be supervised has to be set in the PCS in order to activate the
symmetry measurement.
It is also possible to add a temperature probe to the system for temperature compensated charging of the
battery bank. Fasten the temperature probe in the middle of the topmost battery bank. The temperature
probe will measure the ambient temperature of a battery bank and the PCS will adjust the float charge
according to the temperature compensation factor set in the PCS. This factor must be set in the PCS
according to the battery manufacturer recommendation.
- Blue 1
T Green 2 J11 Temp. probe
+ Red 3
T -36V Blue 1
-24V Green 1 J4 Batt. sym. 1
-12V Red 3
-36V Blue 4
-24V Green 5 J4 Batt. sym. 2
-12V Red 6
-36V Blue 7
-24V Green 8 J4 Batt. sym. 3
-12V Red
-48V 9
-36V -36V Blue 10
-24V -24V Green 11 J4 Batt. sym. 4
-12V Red 12
-12V
0V
2. Strip the wires back approximately 10mm. Stranded wire may be soldered or covered with copper
ferrule if desired.
3. Insert wire into the correct positions in the green connector and tighten screw to clamp wire into
connector.
The wires are pre-routed with fastener strips on the cabinet sidewall and down to the battery bank.
4 Commissioning
Commissioning 4-1
Document number: 037145.fm
Revision: /
Commissioning
Note! Before starting commissioning read the product description for the individual modules.
If there are any difficulties in increasing the voltage to alarm level, the alarm level can be adjusted to a
lower level.
4.3 Preparation
Check the installation to ensure the following:
z Site is clean and safe
z Grounding: The equipment is correctly grounded. The grounding cable size, color and routing
conform to the requirements.
z Power: The incoming mains AC power is available for this site. The site power switch and circuit
breakers are clearly labelled. The power cables are correctly terminated.
2. Remove covers and check that all connections are made according to the installation drawing. Verify
that all connections are properly tightened with a sufficient torque.
(See Torque table in the Maintenance and troubleshooting chapter)
4. Verify correct mains voltage on input mains terminals in cabinet by measuring each individual phase
voltage towards neutral. Turn off mains voltage after verifying.
10. Green LED on PCS (control unit) should blink for approximately 20 sec.
13. Verify right polarity on battery connection by measuring the voltage drop across battery breaker(s)
(Normally not more than 5V DC)
15. If any alarms are present they should be reset in accordance with “Show alarms” in product
description PCS. No alarms should be present.
16. If the system shows any communication failure from a rectifier position without any rectifier installed.
Select "Accept removed parts" from the Miscellaneous menu on PCS. (For more information see
product description PCS.)
Commissioning 4-3
Document number: 037145.fm
Revision: /
Commissioning
Note! A sealing protects the potentiometer in the subrack. Do not break the seal.
Commissioning 4-5
Document number: 037145.fm
Revision: /
Commissioning
Checked Result
(D)
1. Check that rack is levelled
2. Check that all breakers are turned to “off”
position and that no rectifiers are mounted in
the subrack(s).
3. Connect AC, and measure voltage on the L1-N:………..V AC
mains input connections in the cabinet, Is to L2-N:...............V AC
be 230V AC (Measure 230V from phase to N L3-N:...............V AC
when 400V mains input is used)
4. Mount rest of the rectifiers
5. After connection of battery, verify right
polarity by measuring the voltage drop across
the battery breakers (normally not more than
5V DC).
6. Check float charge, U1, and boost charge,
U2. Is to be adjusted according to the battery U1:……..V DC
manufacture requirements. U2:.........V DC
7. Check temperature compensation. Is to be
adjusted according to the battery Comp. :…….V/10oC
manufacture requirements.
Check temperature read off compare to the Read off:………oC
room temperature.
8. Check symmetry measurement and set
number of battery strings according to Number: ….
actually supervised battery strings in the
Alarm limit:……
system.
9. Check alarm transmission by running an
alarm test.
Table 4-2 Commissioning record
Main Controller
Master unit in the system communicating with all distributed micro controllers. Has LCD display, menu
driven operation, visual alarm indication, RS232 contact for remote operation and RS 485 for internal
communication with 128 addresses. (64 rectifiers and 64 other remote micro controllers).
Internal Power
Alarm Interface
Input for current reading, battery and load breaker monitoring, battery temperature, battery symmetry
measurement. Output for operating two individual contactors (LVD and PLD), 6 potential free alarm
contacts. Five analogue or digital inputs for supervision of miscellaneous signals (ventilation, door open,
etc)
PCS- -Internal
PCS InternalPower
Power
Optional
(BM0500)
(BM0500) RS 485 or
RS 232 (via converter )
PCS- -Alarm
PCS AlarmInterface
Interface
(BM0494)
(BM0494)
RS
485
PMPController
PMP Controller
(PMP 25/50)
(PMP 25 / FMP 32)
In addition PMP 25 and FMP 32 has an internal micro controller communicating with the other units.
1. PowCom - Communication program for remote control (by modem or zero-modem cable) of the power supply system.
z Interface: RS 232 for remote operation via PowCom. RS 485 for internal
communication with 128 addresses (64 rectifiers and 64 sub-
controllers). Optional RS 485 for communication with additional 128
addresses. Overall max. capability is 128 rectifiers and 128
sub-controllers.
z Basic functions: Menu driven operation
Up to 24 pre-defined alarms
16 programmable alarms
Internal clock with battery backup
Multiple language choice
Temperature compensated charging
Boost charging, manually and automatic
LVD control of two contactors, voltage or time controlled
Battery test, manual or automatic with symmetry measurement.
Alarm relay test
Adjustable battery current
Software controlled start up after mains outage and battery test
Enhanced battery monitoring
System LED’s
RS232 Interface
The control unit is equipped with four push buttons: CANCEL, , , and (ENTER).
The arrow keys are used to go up and down in the menu hierarchy, to adjust limits and to select options.
The key is used to go one level deeper to the menu system and to confirm adjustments. The CANCEL
key takes you one level up in the menu hierarchy in addition to cancel the adjustments.
To adjust the alarm limits, use the arrow keys to select "adjust limits". Press to enter the sub menu, and
once more to select "alarm limit". By using the and keys the various alarm limits can be checked. To
adjust a limit: select the correct limit and press . The correct password must be entered before a new
value can be set.
The password is set to 1234 by default, but can be changed. Use the keys to set and to confirm each
digit. CANCEL can be used to correct a digit. When the correct password is entered it stays active for
approximately 2 minutes.
The adjust mode is indicated by a : (colon) in front of the value and a steady cursor behind. Use the
keys to adjust the alarm limit and press to confirm the value or CANCEL to revert to the previous value.
To return to main menu, press the CANCEL button. If the PCS is left unattended the display will return to
main menu automatically after 2 minutes. The backlight will be turned off after 2 minutes without any key
pressed. Pressing any key will turn it back on.
5.5 Connecting to PC
Connect to a PC with PowComTM installed. The BAUD rate in the PowComTM COM port settings must be
set to the same as the PCS is set to (9600 is the default baud rate of the PCS). If modem is to be used,
connect modem before initiation. Push INIT MODEM in the miscellaneous menu.
Pin Function
2 Receive
3 Transmit
5 0V (ground)
5.6 Menus
5.6.1 Show voltage and currents
The control module normally shows system voltage and battery current. Pressing the arrow will show
system voltage and distribution current, pressing once more will show system voltage and rectifier
current.
Module data
This menu shows information from the individual rectifier modules. Use the keys to select the module
number. Press enter to view another page of information. Four pages of information are available for each
module. The information available is communication status, module current, mean current, module
temperature, module measured voltage, Module OVP limit, alarm information, Serial number and module
software version number. Module alarms are indicated by 3 letter flags. The meanings of these are as
follows.
MNS - No input mains.
LOW - Output voltage low
OFF - No operation, caused by no mains or other failure
OVS - Overvoltage shutdown.
FAN - Fan failure, will cause the module to go off and OFF to be set.
CUR - Current sharing fault. Current deviates too much from average.
TMP - Temperature is high, will eventually cause the module to go off and off to be set.
Unit data
This menu shows information from the individual units. Units are I/O parts of the system like alarm interface
cards, distribution cards etc. The information available is communication status, serial number and unit
software version number. The menu is operated as the module data menu.
Temperature
The battery temperature is shown.
Ext. measurements
Up to 8 "external measurements" can be shown. These measurements are not standard measurements.
Both text and inputs are system specific and are defined in the configuration. If there are not configured any
measurements NA will be shown when enter is pressed.
Dist. current
Show the distribution current from individual distributions. Up to 64 distributions can be shown. Require
distributions with Distribution interface (PDU-IF). If no such distributions are available NA will be shown
when enter is pressed.
Symmetry voltage
The symmetry voltage for each battery branch is shown.
z U1 Normal. The U1 reference is shown, press to change U1 (The float charge voltage)
z U2 Boost. The U2 reference is shown, press to change U2 (The boost charge voltage)
z U3 Test. The U3 reference is shown, press to change U3 (The Battery test voltage)
z U4 Spare. The U4 reference is shown, press to change U4 (The spare voltage) (Not normally used)
Alarm limits.
This menu contains High voltage, low voltage, Over voltage shutdown limit, low voltage disconnect, partial
low voltage disconnect limits, load reconnect limit, high load limit, high temperature limit.
Boost parameters.
This menu contains the limits for boost charging control. See section 5.7 Boost charging
Battery test.
This menu contains the limits for battery test. See section 5.8 Battery test
Temperature comp.
This menu turns the temperature compensation on and off, and set the compensation factor.
5.6.7 Miscellaneous
The miscellaneous menu makes it possible to set the date and time, change password, view version
information, initialise modem, and show symmetry voltages and temperature.
Set time
The clock is shown. Press to adjust the clock. The clock is battery backed and will keep the time even if
the PCS is turned off.
Relay test
Press to check the alarm relays. The relays will be activated one and one. Use the keys to select
witch relay should be activated.
Alarm blocking
Allows the alarm relays to be disabled during maintenance. One alarm relay will normally be active as long
as the alarms are blocked.
Version
Show the PCS software version, configuration number and serial number.
Shunt A
The nominal current of the battery shunts.
Shunt mV
The nominal voltage of the battery shunts.
Network address
Several PCS's may be connected together in a multidrop RS232 network. Each module then needs to have
a unique address between 2 and 255. The address may be set here.
Baud rate
Select the baud rate for the RS232 serial port of the PCS. Either 2400 or 9600.
Init modem
Press enter to send a string to init a modem. Additional initiation may be required in beforehand depending
on the modem.
Note! Do not do this if there is an actual communication alarm caused by a fault in a module or unit.
Reset to defaults
Will reset alarm limits etc. to the default value without deleting logged data or system information. It is
recommended to try this instead of Master Reset if a reset is needed. In some cases it might still be
necessary to do a master reset. After a reset always check all limits and adjust them to the desired level.
Master reset
Will completely reset the PCS deleting all stored data. If possible download the data to a PC before doing
this. Use this only if absolutely necessary. After a reset always check all limits and adjust them to the
desired level.
Manually boost charging - Choose U2 boost in the referance menu for activating boost charging. (Return to
float charge manually by choosing "U1", or automatically after a pre-set time.)
Periodic boost charging - after a pre-set period boost charge will be automatically activated for a pre-set
time. Interval and boost time to be programmed (for example 4 hours every 3rd week).
Automatic boost charging - when during a mains failure the battery voltage falls below t1 limit value, a timer
is started. When the mains return, the system will start an automatic boost. This will last a certain time after
the battery voltage reach the t2 limit. This time will be multiplied with a boost factor; K. t1 limit, t2 limit and
the factor can all be set.
Adjustable values:
Note! Most of the manufactures of sealed lead acid batteries do not recommend boost charging. If this
type of battery is used, the boost function should be totally disabled by settings as follows:
Boost time = 0
U2 boost = U1 normal
Parameter settings.
The idea of this feature is to make partial discharges of the battery, approx. 30-40% of the capacity, in order
to discover faults before it actually becomes a problem. The settings should be done according to the
battery manufacturer requirements, but as a rule of thumb the following settings can be used for standard
VR lead batteries:
U3 Test = 1,9 V/cell
End voltage b.test = 1,94V/cell
Batt. test time = 40% of expected backup time
Ah limit for test = 40% of nominal battery capacity
Parameters to be set/adjusted from the "battery test" menu or PC with PowCom installed.
Adjustable values:
Battery test voltage, (U3) 0 - 100 Volts
Symmetry limit 0,0 - 4,0 Volts
End voltage battery test 0 - 100 Volts
Test duration 0 - 20 hours
Ah limit for test 0 - 50000 Ah
Time for test 0 - 23
No of test/year 0-4
No of batteries branches 0 - 12
Battery type 4 blocks, 23 cell-, 23 cell+, 3 blocks or 2 blocks
Number of batteries must be equal to number of symmetry measurements. If symmetry cables are not in
use, number of batteries must be set to 0 (zero).
Enclosure: IP 20
6.3 Operation
FMP 32 has status indicators that is located on the front panel of the module. The output voltage is
adjusted from the Controller.
There are three LEDs situated on the rectifier's front panel, which indicate the operating condition of the
rectifier.
GREEN
Power ON
YELLOW
Current Limit / Thermal protection. Communication
failure (flashing).
RED
Module failure / high output voltage / shutdown.
6.4 Environment
The FMP 32 rectifiers meet the Environmental Standard requirements of:
ETS 300 019-1-3 class 3.1 / 3M1 for Operating (Stationary In-Use)
Temperature Range: -40°C to +65°C (up to 2000m) and -40°C to +55°C (above 2000m)
6.4.1 Storage
ETS 300 019-2-1 Class 1.2.
6.4.2 Transport
ETS 300 019-2-2 Class 2.3.
6.4.3 Operation
ETS 300 019-2-3 Class 3.2.
6.5 Safety
The FMP 32rectifiers fulfil those international and national safety standards for these systems according to
grounding, fire protection and other safety matters as specified in the following standards:
6.6 EMC
The rectifiers' EMC meets the requirements of:
Note! All examples, pictures and drawings in this documentation are based on cabinets with 4 x PPR.
PPR 32/4 is a subrack/rectifier shelf for interconnecting of FMP 32 modules. Each subrack/rectifier shelf
has 4 module positions.
Each subrack/rectifier shelf may be equipped according to present power requirements, and later be
completed with additional FMP 32 modules.
PL4 (COM)
PL6 (COM)
PL3 (CUR)
PL5 (CUR)
Dip switches
PE
N
L Input mains
Note! You can only address 64 modules in one com. channel. If more than 64 modules are used,
module position 65 will have address 0 (Dip switch off). This will also be com. channel 2, new
com. cable from main cabinet.
PL4
PL6
PL3
PL4
PL6
PL3
z Use cable marked with Brown 1 between PL6 in subrack/rectifier shelf 1 to PL4 in subrack/rectifier
shelf 2.
z Use cable marked with Orange 3 between PL5 in subrack/rectifier shelf 1 to PL3 in subrack/rectifier
shelf 2.
z Use cable marked with Brown 1 between PL6 in subrack/rectifier shelf 2 to PL4 in subrack/rectifier
shelf 3.
z Use cable marked with Orange 3 between PL5 in subrack/rectifier shelf 2 to PL3 in subrack/rectifier
shelf 3.
Note! If the system consist of more subracks connect after the same method between subracks as
described above.
F M P 3 2 2 . 8
Product description PPR 32/4 19” Subrack
z Use cable marked with Brown 1 between PL6 in main cabinet to PL4 in extension cabinet1.
z Use cable marked with Orange 3 between PL5 in main cabinet to PL3 in extension cabinet1.
z Use cable marked with Brown 1 between PL6 in extension cabinet1 to PL4 in extension cabinet2.
z Use cable marked with Orange 3 between PL5 in extension cabinet1 to PL3 in extension cabinet2.
Note! If the system consist of more extension cabinets connect after the same method between
cabinets as described above.
7 1 28 1-6 1+2+4+5
8 1 29 1-6 3+4+5
8 1 29 1-6 3+4+5
8 1 30 1-6 1+3+4+5
8 1 30 1-6 1+3+4+5
8 1 31 1-6 2+3+4+5
8 1 31 1-6 2+3+4+5
8 1 32 1-6 1+2+3+4+5
8 1 32 1-6 1+2+3+4+5
9 1 33 1-6 6
9 1 33 1-6 6
9 1 34 1-6 1+6
9 1 34 1-6 1+6
9 1 35 1-6 2+6
9 1 35 1-6 2+6
9 1 36 1-6 1+2+6
9 1 36 1-6 1+2+6
10 1 37 1-6 3+6
10 1 37 1-6 3+6
10 1 38 1-6 1+3+6
10 1 38 1-6 1+3+6
10 1 39 1-6 2+3+6
10 1 39 1-6 2+3+6
10 1 40 1-6 1+2+3+6
10 1 40 1-6 1+2+3+6
11 1 41 1-6 4+6
11 1 41 1-6 4+6
11 1 42 1-6 1+4+6
11 1 42 1-6 1+4+6
11 1 43 1-6 2+4+6
11 1 43 1-6 2+4+6
11 1 44 1-6 1+2+4+6
11 1 44 1-6 1+2+4+6
12 1 45 1-6 3+4+6
12 1 45 1-6 3+4+6
12 1 46 1-6 1+3+4+6
12 1 46 1-6 1+3+4+6
12 1 47 1-6 2+3+4+6
12 1 47 1-6 2+3+4+6
12 1 48 1-6 1+2+3+4+6
12 1 48 1-6 1+2+3+4+6
13 1 49 1-6 5+6
13 1 49 1-6 5+6
13 1 50 1-6 1+5+6
13 1 50 1-6 1+5+6
13 1 51 1-6 2+5+6
13 1 51 1-6 2+5+6
13 1 52 1-6 1+2+5+6
13 1 52 1-6 1+2+5+6
14 1 53 1-6 3+5+6
14 1 53 1-6 3+5+6
14 1 54 1-6 1+3+5+6
14 1 54 1-6 1+3+5+6
14 1 55 1-6 2+3+5+6
14 1 55 1-6 2+3+5+6
14 1 56 1-6 1+2+3+5+6
14 1 56 1-6 1+2+3+5+6
15 1 57 1-6 4+5+6
15 1 57 1-6 4+5+6
Table 7-1 Addressing module positions
15 1 58 1-6 1+4+5+6
15 1 58 1-6 1+4+5+6
15 1 59 1-6 2+4+5+6
15 1 59 1-6 2+4+5+6
15 1 60 1-6 1+2+4+5+6
15 1 60 1-6 1+2+4+5+6
16 1 61 1-6 3+4+5+6
16 1 61 1-6 3+4+5+6
16 1 62 1-6 1+3+4+5+6
16 1 62 1-6 1+3+4+5+6
16 1 63 1-6 2+3+4+5+6
16 1 63 1-6 2+3+4+5+6
16 1 64 1-6 1+2+3+4+5+6
16 1 64 1-6 1+2+3+4+5+6
17 2 65 1-6 Off
17 2 65 1-6 Off
17 2 66 1-6 1
17 2 66 1-6 1
17 2 67 1-6 2
17 2 67 1-6 2
17 2 68 1-6 1+2
17 2 68 1-6 1+2
18 2 69 1-6 3
18 2 69 1-6 3
18 2 70 1-6 1+3
18 2 70 1-6 1+3
18 2 71 1-6 2+3
18 2 71 1-6 2+3
18 2 72 1-6 1+2+3
18 2 72 1-6 1+2+3
19 2 73 1-6 4
19 2 73 1-6 4
19 2 74 1-6 1+4
19 2 74 1-6 1+4
19 2 75 1-6 2+4
19 2 75 1-6 2+4
19 2 76 1-6 1+2+4
19 2 76 1-6 1+2+4
20 2 77 1-6 3+4
20 2 77 1-6 3+4
20 2 78 1-6 1+3+4
20 2 78 1-6 1+3+4
20 2 79 1-6 2+3+4
20 2 79 1-6 2+3+4
20 2 80 1-6 1+2+3+4
20 2 80 1-6 1+2+3+4
21 2 81 1-6 5
21 2 81 1-6 5
21 2 82 1-6 1+5
21 2 82 1-6 1+5
21 2 83 1-6 2+5
21 2 83 1-6 2+5
21 2 84 1-6 1+2+5
21 2 84 1-6 1+2+5
22 2 85 1-6 3+5
22 2 85 1-6 3+5
22 2 86 1-6 1+3+5
22 2 86 1-6 1+3+5
22 2 87 1-6 2+3+5
Table 7-1 Addressing module positions
22 2 87 1-6 2+3+5
22 2 88 1-6 1+2+3+5
22 2 88 1-6 1+2+3+5
23 2 89 1-6 4+5
23 2 89 1-6 4+5
23 2 90 1-6 1+4+5
23 2 90 1-6 1+4+5
23 2 91 1-6 2+4+5
23 2 91 1-6 2+4+5
23 2 92 1-6 1+2+4+5
23 2 92 1-6 1+2+4+5
24 2 93 1-6 3+4+5
24 2 93 1-6 3+4+5
24 2 94 1-6 1+3+4+5
24 2 94 1-6 1+3+4+5
24 2 95 1-6 2+3+4+5
24 2 95 1-6 2+3+4+5
24 2 96 1-6 1+2+3+4+5
24 2 96 1-6 1+2+3+4+5
25 2 97 1-6 6
25 2 97 1-6 6
25 2 98 1-6 1+6
25 2 98 1-6 1+6
25 2 99 1-6 2+6
25 2 99 1-6 2+6
25 2 100 1-6 1+2+6
25 2 100 1-6 1+2+6
26 2 101 1-6 3+6
26 2 101 1-6 3+6
26 2 102 1-6 1+3+6
26 2 102 1-6 1+3+6
26 2 103 1-6 2+3+6
26 2 103 1-6 2+3+6
26 2 104 1-6 1+2+3+6
26 2 104 1-6 1+2+3+6
27 2 105 1-6 4+6
27 2 105 1-6 4+6
27 2 106 1-6 1+4+6
27 2 106 1-6 1+4+6
27 2 107 1-6 2+4+6
27 2 107 1-6 2+4+6
27 2 108 1-6 1+2+4+6
27 2 108 1-6 1+2+4+6
28 2 109 1-6 3+4+6
28 2 109 1-6 3+4+6
28 2 110 1-6 1+3+4+6
28 2 110 1-6 1+3+4+6
28 2 111 1-6 2+3+4+6
28 2 111 1-6 2+3+4+6
28 2 112 1-6 1+2+3+4+6
28 2 112 1-6 1+2+3+4+6
29 2 113 1-6 5+6
29 2 113 1-6 5+6
29 2 114 1-6 1+5+6
29 2 114 1-6 1+5+6
29 2 115 1-6 2+5+6
29 2 115 1-6 2+5+6
29 2 116 1-6 1+2+5+6
29 2 116 1-6 1+2+5+6
Table 7-1 Addressing module positions
8.3 Installation
Cable entry from top of cabinet:
The battery and distribution module is a "plugable" module that connects directly to the systems rail
section. Decide where on the top of cabinet you want the entrance of the negative (-) cables for battery
breaker and distribution breakers (knives 5xNH1-3). Entrance will vary due to cable properties (size and
flexibility). The cable duct (located on the left side of the cabinet) is only accessible for up to 50mm2 cables.
The negative (-) connection is to be done directly on the breakers. (see Figure below)
Cable entry from bottom of cabinet (only for special made cabinets):
The battery and distribution module is a "plugable" module that connects directly to the systems rail
section. Decide where from the bottom of the cabinet you want the entrance of the negative (-) cables for
battery and distribution breakers (knives 5xNH1-3). Entrance will vary due to cable properties (size and
flexibility). The cable duct (located on the left side of the cabinet) is only accessible for up to 50mm2 cables.
The negative (-) connection is to be done directly on the breakers. (see Figure below)
Figure 8-1
8.5 Commissioning
1. Measure voltage drop across battery breaker to make sure battery is correctly polarised. (Normally
not more than 5V DC)
3. Pull out one of the battery breakers and verify battery breaker alarm in the controller
5. Pull out one of the load breakers and verify breaker alarm in the controller
7. Repeat the above mentioned steps for each battery and distribution module.
8.6 Maintenance
The module does not need any special maintenance except for ordinary cleaning.
Figure 9-1
Common “+” connection. Output
connection positive cables
On the top of the distribution there is a horizontal cable duct for fixing output cabling.
9.5 Installation
The distribution module is a “plug able” module that connects directly to the systems rail section. Use cable
duct located on the left side of the cabinet for guiding of cables to the distribution. Positive cables are to be
connected in terminal blocks at the common "+" bar, and negative cables are to be connected directly to
the MCB's. Use torque 2,5 – 3,5 Nm on these connections.
The distribution unit may be delivered with high ohmic resistance wires mounted on the MCB breakers. A
maximum of 6W loss in each wire gives the following:
60 10
30 14
15 20
Table 9-1
9.7 Commissioning
1. Switch on all MCB's in the distribution units.
2. Turn off one of the fuses and verify fuse alarm at PCS
4. Repeat the two above-mentioned steps for one MCB in each distribution module.
9.8 Maintenance
The distribution does not need any special maintenance except for ordinary cleaning.
Figure 10-1
Figure 10-2
10.5 Installation
The distribution module is a "plugable" module that connects directly to the systems rail section. Use cable
duct located on the left side of the cabinet for guiding of cables to the distribution. Positive cables to be
connected to the terminals at the common “+” bar and negative cables to be connected directly to the
MCB’s.
10.6 Commissioning
1. Switch on all MCB's in the distribution unit.
2. Turn off one of the breakers and verify breaker alarm at PCS
4. Repeat the above mentioned steps for one MCB in each distribution module.
10.7 Maintenance
The distribution does not need any special maintenance except for ordinary cleaning.
11.1 General
PCS alarm interface unit consist of PCB0546, which is an alarm board for Power One systems. The unit is
located on the left or backside of the distribution. Access from top of the cabinet.
z 3 x analogue inputs. (J4 pin 10-12) (Pin 12 = Analog 1, Pin 11 = Analog 2 and Pin 10 = Analog 3)
z RS485 interface for communication with plant controller PCS. (J7 and J16)
12V
J9 Ext. transfoshunt 2
3 -12V 1
2 J10 Digital output
1
Distrfuse alarm 2
- Blue 1 J5 Battfuse manual 1
T Green 2 J11 Temp. probe
+ Red 2
3
J3 Digital input
1
T -36V Blue 1
-24V Green -Shunt 2 2
-12V Red
2 J4 Batt. sym. 1 J12 +Shunt 2 1
3
-36V Blue -Shunt 1 2
-24V Green
4 J2 +Shunt 1 1
5 J4 Batt. sym. 2
-12V Red 6 8
-36V Blue 7 J16 Comm. RJ45
-24V Green 8 J4 1
Batt. sym. 3
-12V Red
-48V 9 8
-36V -36V Blue 10 J7 Comm. RJ45
-24V -24V Green 11 J4 Batt. sym. 4 1
-12V Red 12
-12V
0V
11.4 Maintenance
The PCS alarm interface unit does not need any special maintenance.
1. Plug in module.
3. Wait. After 1 minute the yellow LED will start blinking. Wait for max. 4 min.
12.2 Troubleshooting
This guide is a step-by-step recommendation of what to do if problems occur. If first step of
recommendation do not solve the problem continue to the next one. If the problem cannot be solved please
call your local Power - One office for assistance.
Load/battery disconnected:
z If breaker blows once more, there is either a too high load or short circuit at the system
Mains error:
z Check the equipment that is connected to the blown fuse (there may be a reason for this fuse to
blow) and reconnect it.
Battery failure:
Module failure:
z Pull it out.
z Wait for 30 sec. and reinstall it according to 12.1 Installing new modules.
z Check ventilation.
Symmetry fault:
z Check batteries.
High load:
Communication failure:
12.3 Maintenance
The connections on the terminal blocks and circuit breakers must be checked according to the 12.4 Torque
table minimum once a year.
Minimum once a year output voltage should be verified to be within limits. Result of the test should be filed
to see any deviations.
In addition the system needs normal cleaning and verifying of right operation. It is very important to keep air
inlets and outlets free from dust or other materials, which may prevent free air circulation through the
cubical.
Show voltage/
Batt. current
Show voltage/
Distr. current
Show voltage/
Rect. current
Temperature Symmetry
voltage 6
Ext.
measurements Symmetry
voltage 7
U1 normal voltage
Distr. current Symmetry
voltage 8
Select/adjust
U1-U4 U2 boost voltage
Symmetry
Symmetry
voltage 1
voltage 9
U3 test voltage
Symmetry
Symmetry
voltage 2
voltage 10
U4 spare voltage
Symmetry
Symmetry
voltage 3
voltage 11
Reference
Symmetry
Symmetry
voltage 4
voltage 12
Overvolt.
Boost interval
Battery test Symmetry limit Shutdown
set time
Load/battery
Miscellaneous Test end Boost factor disconnect
Relay test Temperature Enable temp. voltage
comp. comp.
Partial
Boost t1
Alarm blocking Test duration disconnect
Enable current Comp. factor
Batt. current limit
Menu language limit
Load/battery
Boost t2
Version Ah- limit reconnect
Batt. current
Syst. specific limit
limits Autoboost
Set new password High load
Time of test enable
Shunt voltage
No of batteries
Network address
Battery type
Baud rate
Init modem
Accept removed
Date: Designer: Control: Approved: Scale:
parts
05.09.2002 ØSK
Reset to defaults Replacement for: Replaced by:
Menu tree
Master reset
Page 1 of 1
PCS ref: Rev:
45
40
POWER ON
MESSAGE
ALARM
POWER ON
MESSAGE CANCEL
CANCEL RS232
ALARM
35
PBDU 1
PDU 1
30
25 PDU 1 PDU 2
20
PDU 2 PDU 3
15
PDU 3 PDU 4
10
5
FMP 32.48 FMP 32.48 FMP 32.48 FMP 32.48 FMP 32.48 FMP 32.48 FMP 32.48 FMP 32.48
0 FMP 32.48 FMP 32.48 FMP 32.48 FMP 32.48 FMP 32.48 FMP 32.48 FMP 32.48 FMP 32.48
WxHxD=600x2150x600mm WxHxD=600x2150x600mm
Page 01 of 01
Cabinet layout
Forza 48-25600 ref: Rev:
037810 /
PE N N N L1 L2 L3 PE N N N L1 L2 L3 PE N N N L1 L2 L3 PE N N N L1 L2 L3
1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7
PE L1 L1 L2 L2 L3 L3 PE L1 L1 L2 L2 L3 L3 PE L1 L1 L2 L2 L3 L3 PE L1 L1 L2 L2 L3 L3
For systems with more than 3 rectifier shelves PCS CANCEL
POWER ON
-48V -48V
+ Red 3
T Green 2 J11 Temp. probe
- Blue
1
T
18
Alarm 6 17 J13
16
15
Alarm 5 14 J13
13
12
Alarm 4 11 J13
10
9
Alarm 3 8 J13
7
6
5 10.05.04 ØSK 1:10
Alarm 2 J13
4
3 Page 01 of 01
Alarm 1 2 J13
General connection drawing
1
Forza 48 Top entry caninet
Alarm contacts are shown in alarm position Alarm contacts are shown in alarm position 037396 /
A-4
A.4 General block diagram Forza main cabinet - 037397 - Rev: B
1
+ Output
1
- Output Quantity of subracks
will vary due to the
actual order
+ BM0635
L
N
8
- PE
L
PL4 COM N
8 PE
OPTION:
8
PL6 COM Subrack for L
N
8 Current share exten.cab.
8
PL3 Current share 4xFMP 32 PE
L
subrack 1
PL5 Current share
N BM0635 PL5
PE
Sub Rack n
OPTION:
8
Communication exten. cab.
subrack 1
BM00635 PL6
PCS - Control unit
8
J6 Com Modem 9
BM0479
with power
8
J7 Com PCS RS 232
J3 Com system 1
8
J4 Com system 2
8
J8 Power PCS
8
8
J8 Power
8
J5 Com 2 BM0500
8
J4 Com 2
8
J2 Com 1
J3 Com1
Main cabinet
1 1
PBF/PBDU 2 2 J1
PL1, Pin1 and 2
PCS 8
J7 Com
BM0546
alarm interface unit J16 Com
PDU 25 0V
Quantity and type of
- Load 1 distributions will vary
due to the actual
- Load n
order
PDU 25 0V
w/PLD
- Load 1
- Load n
PDU 25 - Load 1
- Load n
PBDU 25
- Load 1
- Load n
- Batt. 1
- Batt. n
PBF 25 - Batt. 1
- Batt. n
12.07.04 ØSK
037397 B
1
+ Output
1
Communication - Output Quantity of subracks
from prev. cab. 8
8
PL6 COM Subrack for L
N
Current share
8 8
PL3 Current share 4xFMP 32 PE
L
from prev. cab. PL5 Current share
N
PE
Last subrack Sub Rack 1
BM0635 PL3
+ BM0635
L
N
8
- PE
L
PL4 COM N
8 PE
8
PL6 COM Subrack for L
N
8
PL3 Current share 4xFMP 32 PE
L
N
PL5 Current share PE
Sub Rack 2
+ BM0635
L
N
8
- PE
L
PL4 COM N
8 PE
8
PL6 COM Subrack for L
N
8
PL3 Current share 4xFMP 32 PE
L
N
PL5 Current share PE
Sub Rack n OPTION:
8 Current share exten.cab.
subrack 1
BM0635 PL5
OPTION:
8
Communication exten. cab.
subrack 1
BM00635 PL6
8
J7 Com
PCS 8
J16 Com
BM0546
PDU 25 0V
Quantity and type of
- Load 1 distributions will vary
due to the actual
- Load n
order
PDU 25 0V
w/PLD
- Load 1
- Load n
PDU 25 - Load 1
- Load n
PBDU 25
- Load 1
- Load n
- Batt. 1
- Batt. n
PBF 25 - Batt. 1
- Batt. n
08.07.04 ØSK
037398 A
8
J6 Com Modem 9
8 BM0479 J7 Com PCS
J3 Com system 1
8
J4 Com system 2
8
J8 Power PCS
8
* 8
8
J8 Power
8
J5 Com 2 BM0500
8
J4 Com 2
8
J2 Com 1
J3 Com 1
1
J1
* 2
037400 /
8 8
J7 Com. BM0546
* 8 8
J16 Com. For more details, see
1 + connection drawing
2 - J2 Shunt 1
1 +
Distr. breaker 2 - J12 Shunt 2
alarm signal 1 Distribution fuse
J5
2 Batt. fuse manual
Located in top of
the cabinet
1
12 2
3 J6 Batt. fuse
4
Signal 1 0V
PDU 2 Sys. voltage J14
PL 1
1 J1 Disconnect 1
2
3
1
4 J1 Disconnect 2
5
6
Reconnect 7 J1 Reconnect
6
Signal Disconnect 8
9
PDU w/PLD
PL 1
Quantity and 1
type of 1
2
Digital input 0 J3
Digital input 1
distributions
will vary due to 6
Signal
the actual PDU
order PL 1 1
12
0V
- batt 1
- batt 2
- batt 3
- Load 1
- Load n
12
27.03.2003 RFA
Replacement for: Replaced by:
Schematic diagram
Page 1 of 1
http://esmtier.power.one:7777/files/
PBDU 25 Powec ref:
ref: Rev:
0V
- Load 1
- Load n
BM0660
X1
6 X2
X3
PDU 24xMCB X4
X5
PL1 LED board
1
BM0554
13.07.04 ØSK
Page 1 of 1
Schematic diagram PDU 25 w/LED
Powec ref:
ref: Rev:
037822 /
0V
- Load 1
- Load n
6
PDU 25-max16xMCB
PL1
1
8
PL4
BM0635
PL6
8 PL3
Subrack 1
8 PL5
L
L
+
N
N 1
PE
PE
-
L
L
N
N
PE
2
PE
L
L
N
N
PE
3
PE
L
L
N
7
N
PE
4
PE
6
Mains 1 4
8 PL4
3
8
BM0635
PL6
2
8 PL3
Subrack 2
1 8 PL5
1
L
L
+
N
N 5
PE
PE
-
L
L
N
N
PE
6
PE
L
L
N
N
PE
7
PE
L
L
N
N
PE
8
7
PE
6
Mains 2 4
8 PL4
3
8 PL6
BM0635
2 8 PL3 Subrack 3
1 8 PL5
1 L
L
+
N
N 9
PE
PE
-
L
L
N
N
PE
10
PE
L
L
N
N
PE
11
PE
L
L
N
N
PE
12
PE
10.05.04 ØSK
037407 /
8
PL4
BM0635
PL6
8 PL3
Subrack 4
8 PL5
L
L
+
N
N 13
PE
PE
-
L
L
N
N
PE
14
PE
L
L
N
N
PE
15
PE
L
L
N
7
N
PE
16
PE
6
Mains 3 4
8 PL4
3
8
BM0635
PL6
2
8 PL3
Subrack 5
1 8 PL5
1
L
L
+
N
N 17
PE
PE
-
L
L
N
N
PE
18
PE
L
L
N
N
PE
19
PE
L
L
N
N
PE
20
7
PE
6
Mains 4 4
10.05.04 ØSK
037407 /
-Battery 1
-Battery 2
-Battery 3
- Load
Fuse 6A 10A 16A 20A 25A 32A 40A 50A 200A Char. PLD Type of equipment
F1 X C
F2 X C
F3 X C
F4 X C
F5 X C
F6 X C
F7 X C
F8 X C
F9 X C
F10 X C
F11 X C
F12 X C
F13 X C
F14 X C
F15 X C
F16 X C
F17 X C
F18 X C
F19 X C
F20 X C
F21 X C
F22 X C
F23 X C
F24 X C
+0V Load
-Load
Fuse 6A 10A 16A 20A 25A 32A 40A 50A 200A Char. PLD Type of equipment
F1 X C
F2 X C
F3 X C
F4 X C
F5 X C
F6 X C
F7 X C
F8 X C
F9 X C
F10 X C
F11 X C
F12 X C
F13 X C
F14 X C
F15 X C
F16 X C
F17 X C
F18 X C
F19 X C
F20 X C
F21 X C
F22 X C
F23 X C
F24 X C
+0V Load
-Load
Fuse 6A 10A 16A 20A 25A 32A 40A 50A 200A Char. PLD Type of equipment
F1 X C
F2 X C
F3 X C
F4 X C
F5 X C
F6 X C
F7 X C
F8 X C
F9 X C
F10 X C
F11 X C
F12 X C
F13 X C
F14 X C
F15 X C
F16 X C
F17 X C
F18 X C
F19 X C
F20 X C
F21 X C
F22 X C
F23 X C
F24 X C
+0V Load
-Load
+ LOAD
F1 F2
Fuse 6A 10A 16A 20A 25A 32A 40A 50A 200A Char. PLD Type of equipment
F1 X C
F2 X C
F3 X C
F4 X C
F5 X C
F6 X C
F7 X C
F8 X C
F9 X C
F10 X C
F11 X C
F12 X C
F13 X C
F14 X C
F15 X C
F16 X C
F17 X C
F18 X C
F19 X C
F20 X C
F21 X C
F22 X C
F23 X C
F24 X C
+0V Load
0V 0V
-Load
Fuse 6A 10A 16A 20A 25A 32A 40A 50A 200A Char. PLD Type of equipment
F1 X C
F2 X C
F3 X C
F4 X C
F5 X C
F6 X C
F7 X C
F8 X C
F9 X C
F10 X C
F11 X C
F12 X C
F13 X C
F14 X C
F15 X C
F16 X C
F17 X C
F18 X C
F19 X C
F20 X C
F21 X C
F22 X C
F23 X C
F24 X C
+0V Load
-Load
Fuse 6A 10A 16A 20A 25A 32A 40A 50A 200A Char. PLD Type of equipment
F1 X C
F2 X C
F3 X C
F4 X C
F5 X C
F6 X C
F7 X C
F8 X C
F9 X C
F10 X C
F11 X C
F12 X C
F13 X C
F14 X C
F15 X C
F16 X C
F17 X C
F18 X C
F19 X C
F20 X C
F21 X C
F22 X C
F23 X C
F24 X C
+0V Load
-Load