Low Frequency AC Transmission For Offshore Wind Power
Low Frequency AC Transmission For Offshore Wind Power
Low Frequency AC Transmission For Offshore Wind Power
1179
K. NAGAMANI, et al., International Journal of Emerging Trends in Engineering Research, 9(8), August 2021, 1179 – 1184
FILTER DESIGN
Fig. 3. shows Receiving-end cycloconverter control At the sending end, the 12-pulse inverter produces harmonics of
order 1, 2, … and can be represented as a
2.SYSTEM DESIGN
source of harmonic currents (in Fig. 7). These current
harmonics are filtered by two single-tuned filters for the 11th
MAIN POWER COMPONENTS
and 13th harmonic, and one damped filter for higher order
The main power components are selected based on a harmonics ( 23rd). Generally, the filter design is dependent
steady state analysis of the LFAC transmission system shown on the reactive power supplied at fundamental frequency (also
in Fig. 1, under the following assumptions: known as the filter size) and the required quality factor. The
• Only fundamental components of voltages and currents are total reactive power requirement of these filters can be
considered. The receiving end is modeled as a 20Hz estimated. Here, it is assumed that the total reactive power
voltage source of nominal magnitude. requirement is divided equally among the three filters. The
• The power losses of the reactor, thyristors, filters, and quality factor for each filtercan be determined using the method
transformers are ignored. presented. A High-Quality Factor 100) is used for the
• The resistances and leakage inductances of transformers single tuned filters, and a Low- Quality Factor is used for the
are neglected. high pass damped filter. Finally, with the capacitance and
• The ac filters are represented by an equivalent capacitance quality factor known, the inductance and resistance of each
corresponding to the fundamental frequency. filter can be determined. With such filter design, the 12-pulse-
• The design is based on rated operating conditions (i.e., related current harmonics originating at the sending end are
maximum power output). essentially absent from the transmission line.
At the steady state, the average value of the dc current is equal
At the receiving end, there are two groups of filters, namely,the
to, so the power delivered from the wind turbines.
ac filters at the 60Hz side and the LC filter at the 20Hz side. At
the 60Hz side, if the cycloconverter generates exactly one-third
of the grid frequency, and it can be shown [30, p. 360]that the line
current has only odd harmonic components (3rd, 5th, 7th, etc).
Subharmonic and inter harmonic components are not generated.
Here, three single-tuned filters and one damped filter are used to
prevent these harmonic currents from being injected into the
60Hz power grid. These filters are designed with a procedure
similar to that for the ac filters at the sending end.
1181
K. NAGAMANI, et al., International Journal of Emerging Trends in Engineering Research, 9(8), August 2021, 1179 – 1184
3.SIMULATION RESULTS
To demonstrate the validity of the proposed LFAC system,
simulations have been carried out using MATLAB/Simulink
and the Piecewise Linear Electrical Circuit Simulation
(PLECS)
The wind power plant is rated at 180 MW, and the transmission
distance is 160 km. The system parametersare listed in Table I.
The parameters of the PI controllers in Figs. 2 and 3 are listed in
Table II. The transmission power cable is modeled by cascading
20 identical sections. The ABB 5STP 42U6500 and the ABB
Fig. 6. Shows Equivalent circuit of the LFAC transmission system 5STP 08F6500 thyristors are selected to construct the sending
for harmonic analysis. end inverter and the receiving end cycloconverter, respectively.
Multiple series connected 5 thyristors at the sending end and 30
At the 20Hz side, the line-to-neutral voltage has harmonics of order thyristors at the receiving end are used such that the rated voltage
3, 5, 7, …. Without subharmonic and inter harmonic components of a switch is 150% of the rated blocking voltage.
[30, p. 306]. However, the harmonic components of order equal to Fig. 13 shows the steady state line-to-line voltage and current
integer multiples of three are absent in the line-to-line voltage. waveforms at the sending end, the receiving end, the 20Hz
Therefore, as seen from the 20Hz side, the cycloconverter acts as a side of the cycloconverter, and the 60Hz power grid side under
source of harmonic voltages of orders ( rated power conditions. The 20Hz voltage generated from
in Fig. 6). the cyclo- converter has significant harmonic distortion
(THD is 14.8%). Due to the LC filter, the voltages at the
The design of the LC filter has two objectives:
receiving and sending ends have reduced THD values
1) to decrease the amplitudes of the voltage harmonics generated
(3.9% and 2.2%, respectively).The measured fundamental
by the cycloconverter;
power factor angle at the 20Hz.
2) to increase the equivalent harmonic impedance magnitudes seen
from the receiving end, indicated by in Fig. 6.
The design procedure presented here takes into account the
voltage harmonics of order 5, 7, 11, and 13. For cycloconverters,
the amplitude of the voltage harmonics only depends on the
voltage ratio and the fundamental power factor at the 20Hz side,
under the assumption of sinusoidal output current, which is
sufficient for design purposes. Generally, the voltage harmonics
tend to become worse with decreasing.
Fig. 8 illustrates the relationship between the per unit amplitudes
of the voltage harmonics under consideration and the power factor
angle , computed based on formulas in [30, p. 303]. Apparently,
for the 5th and 7th voltage harmonics, the amplitudes are
symmetric with respect to , and positive (i.e., reactive power
consumption by the cycloconverter) can result in reduced
amplitudes of the 11th and 13th harmonic currents. However, this
value is unacceptably low, so selected (for operation at rated
power).
Fig. 7. Shows Harmonic voltage amplitudes generated by
After has been determined, it follows from (18) and (19) that
the cycloconverter at the20-Hz side.
there is a linear relation between and
, as in , since
1182
K. NAGAMANI, et al., International Journal of Emerging Trends in Engineering Research, 9(8), August 2021, 1179 – 1184
1183
K. NAGAMANI, et al., International Journal of Emerging Trends in Engineering Research, 9(8), August 2021, 1179 – 1184
Fig. 9 depicts the results of a transient simulation where the [7] N. Flourentzou, V. G. Agelidis, and G. D. Demetriades, “VSC-based
power from the wind turbines ramps from 0 to 180 MW, HVDC power transmission systems: An overview,” IEEE Trans.
at a rate of 60 MW/s (perhaps unrealistically fast, but Power Electron., vol. 24, no. 3, pp.
chosen to demonstrate that the system is stable even for this 592–602, Mar. 2009.
large transient). Shown are the transient responses of the dc bus [8] T. Funaki and K. Matsuura, “Feasibility of the lower
voltage at the sending end, the magnitude of the fundamental frequency AC transmission,” in Proc. IEEE Power Eng. Soc.
component of the 20Hz voltage generated by the Winter Meeting, 2000,vol. 4, pp. 2693–2698.
cycloconverter, the active power injected into the 60Hz [9] X. Wang, C. Cao, and Z. Zhou, “Experiment on fractional
power grid, and the transmission efficiency (which reaches frequency transmission system,” IEEE Trans. Power Syst.,
a value of 93.3% at rated power). vol. 21, no. 1, pp. 372–377, Feb. 2006.
[10] N. Qin, S. You, Z. Xu, and V. Akhmatov, “Offshore wind farm
4.CONCLUSION connec- tion with low frequency ac transmission technology,”
presented at the IEEE Power Energy Soc. Gen. Meeting,
A low frequency ac transmission system for offshore wind Calgary, AB, Canada, 2009.
power has been proposed. A method to design the system’s [11] Y. Cho, G. J. Cokkinides, and A. P. Meliopoulos, “Time
components and control strategies has been discussed. The domain sim-ulation of a three-phase cycloconverter for LFAC
use of a low frequency can improve the transmission transmission sys- tems,” presented at the IEEE Power Energy
capability of submarine power cables due to lower cable Soc. Transm. Distrib. Conf. Expo., Orlando, FL, May 2012.
charging current. The proposed LFAC system appears to be
a feasible solution for the integration of offshore wind
power plants over long distances, and it might be a suitable
alternative over HVDC systems in certain cases.
Furthermore, it might be easier to establish an
interconnected low frequency ac network to transmit bulk
power from multiple plants. In order to make better
informed decisions, it is necessary to perform a complete
technical and economic comparison among HVAC,
HVDC, and LFAC, evaluating factors, such as the
transmission efficiency, investment and operating costs, and
the performance under system transients.
REFERENCES
[1] N. B. Negra, J. Todorovic, and T. Ackermann, “Loss
evaluation of HVAC and HVDC transmission solutions for
large offshore wind farms,” Elect. Power Syst. Res., vol. 76,
no. 11, pp. 916–927, Jul. 2006.
[2] S. Bozhko, G. Asher, R. Li, J. Clare, and L. Yao, “Large offshore
DFIG- based wind farm with line-commutated HVDC
connection to the main grid: Engineering studies,” IEEE
Trans. Energy Convers., vol. 23, no. 1, pp. 119–127, Mar.
2008.
[3] O. Gomis-Bellmunt, J. Liang, J. Ekanayake, R. King, and N.
Jenkins, “Topologies of multiterminal HVDC-VSC
transmission for large off-shore wind farms,” Elect. Power Syst.
Res., vol. 81, no. 2, pp. 271–281, Feb. 2011.
[4] P. Bresesti, W. L. Kling, R. L. Hendriks, and R. Vailati,
“HVDC connection of offshore wind farms to the
transmission system,” IEEETrans. Energy Convers., vol. 22,
no. 1, pp. 37–43, Mar. 2007.
[5] S. V. Bozhko, R. Blasco-Giménez, R. Li, J. C. Clare, and G. M.
Asher, “Control of offshore DFIG-based wind farm grid with line-
commutated HVDC connection,” IEEE Trans. Energy
Convers., vol. 22, no. 1, pp.71–78, Mar. 2007.
[6] J. Arrillaga, High Voltage Direct Current Transmission,
2nd ed. London, U.K.: Institution of Electrical Engineers,
1998.
1184