Professional Documents
Culture Documents
Electrical License Examination Guide: 20210211 - Licensingexaminationguide Checked 20210211
Electrical License Examination Guide: 20210211 - Licensingexaminationguide Checked 20210211
The information in this guide is provided by the Licensing Unit of the Department of Labor and
Industry to ensure that applicants for personal electrician licenses administered by the
department understand basic qualifications, knowledge areas, and examination criteria and
format to enable them to successfully complete requirements to become licensed. Although
this document contains a significant amount of detail, it should not be construed by applicants
to be inclusive of all information necessary to successfully make application, pass a license
examination, and subsequently become licensed by the department. It is the applicant’s
responsibility to adequately prepare to successfully complete the license examination process.
The examination question format, degree of difficulty, and length of examination has been
in effect since January 1, 2021.
The 2020 National Electrical Code® became effective November 17, 2020 and is the code
edition used for the questions in the electrical license examinations.
The Lineman license examination is based on the 2017 National Electrical Safety Code®.
Successfully completing a license examination provides evidence that the applicant possesses the necessary
knowledge and expertise to be licensed in a specific profession or for a specific scope of work within a
profession.
Licensing examinations are designed to assess the applicant’s competence after they have completed their
qualifying education, training and experience. Licensing examinations are designed to assess higher level skills
than academic examinations by assessing the applicant’s ability to apply the competencies they gained from
their education, training and experience in actual practice.
Licensing examinations are intended to assure the public that the person passing an examination is qualified to
practice within the scope of the license without causing harm to the public.
The purpose of this license examination guide is to provide applicants with awareness of knowledge areas
covered by specific license examinations, question and examination format, degree of difficulty for specific
license examinations, length of examination and length of time allowed to complete their examination.
Applicants are encouraged to review this entire guide to ensure their understanding of the examination process
and governing rules.
General
A copy of the National Electrical Code or the National Electrical Safety Code book is provided in the soft-cover
format and does not include tabs or other aids. The edition of the National Electrical Code is the edition adopted
as part of the state building code at the time the examination is administered. The edition of the National
Electrical Safety Code is the most current edition at the time the examination is administered. The electronic
calculator is of the common desk type that includes addition, subtraction, multiplication, division, square root,
and percentage functions. The Laws and Rules Booklet provided for the examination is in the Department’s
current format and represents the laws and rules in effect at the time the examination is administered.
1. Examination instructions are intended to be clear, concise and complete. No questions may be asked of the
examination proctor (test administrator).
2. Applicants should understand the question without having to read the answer selections.
3. Examination questions relate to knowledge areas within the scope of the applicable license.
4. Examination questions reasonably cover the knowledge areas within the scope of the applicable license.
5. Examination questions relate to knowledge areas that are common. The examination knowledge areas are
within the areas of work generally experienced by applicants for, or persons holding, the class of the
applicable license.
6. Applicants are allowed to use the National Electrical Code or National Electrical Safety Code (used only for
the lineman examination), a Laws and Rules Booklet, and an electronic calculator during their entire
examination. Unless code references are specifically required by an individual question, no code references
are required as part of any answer. All reference materials and a calculator are provided by the Department.
No other materials or electronic devices, including cell phones, are allowed in the building. Although
reference materials are available for the entire examination, applicants should be adequately prepared and
not rely on provided reference materials to answer all questions. The majority of questions are intended to
be answered without the applicant needing to refer to reference materials.
Question Format
1. Examination questions are formatted in a manner that requires the applicant to demonstrate mastery of the
knowledge area.
2. Variables in a question ensure that the appropriate knowledge area(s) or code rule(s) must be applied to
arrive at the correct answer.
3. Multiple-choice answer selections for knowledge areas with multiple conditions or requirements are worded
in a manner that requires the applicant to demonstrate knowledge of the subject matter and minimize the
applicant’s opportunity to select a correct answer(s) based on key words.
4. Questions with a negative-response format such as “which of the following does NOT apply,” are only used in
limited instances. This is a companion format to the multiple-correct answer format identified in 3 above.
5. Incorrect multiple-choice answer selections are “plausible.”
6. Questions may include extraneous information.
7. Unless stated otherwise in specific questions, all questions and related answers assume a “unity” power
factor.
8. Some questions relate to code violations repeatedly made by installers of electrical wiring. Practical
experience must be augmented by quality training to ensure the applicant’s complete and accurate
understanding of electrical code and theory.
Degree of Difficulty
1. Each examination question is assigned a degree of difficulty rating from 1 to 5, with 5 being the most
difficult. “Degree of difficulty” as used in administration of the department’s license examinations has
no relationship to academic “grade point average” achievement.
2. Questions rated least difficult (lowest) are those that relate to a single knowledge area, such as
definitions or those requiring the application of a single code rule, or do not require complex
mathematical calculations.
3. Questions rated most difficult (highest) are those that require the application of multiple code rules or
require multiple or complex mathematical calculations.
4. Each examination is assigned a degree of difficulty range that is commensurate with the responsibility
or authority of the applicable license.
5. Approximately 50% of specific license examination questions have a degree of difficulty within the
overall “degree of difficulty” range for the license type.
1. The license examinations for the Class A master electrician and the Class A journeyworker electrician
consists of 80 questions.
2. The license examination for the power limited technician consists of 80 questions.
3. The license examinations for the maintenance electrician consists of 70 questions, and lineman consist
of 50 questions.
4. The license examination for the Class B and satellite system installer licenses consist of 25 questions.
5. Unless stated otherwise, all examination questions have the same point value. Partial points are not
given - either full point credit or zero point credit is awarded for each question.
6. The passing score for all examination is 70 percent.
7. The time allowed to complete all examinations is 5½ hours.
Examination Results
1. Examination results are e-mailed and mailed to applicants generally within two weeks of the examination.
Examination results are not provided to applicants by telephone.
2. Examination result letters mailed to applicants who passed their examinations will contain directions on
how to obtain their license.
3. Examination result letters mailed to applicants who failed their examinations will contain directions on
how to make subsequent application.
Examination Review or Appeal
1. Examinations with scores within five (5) percentage points of passing are rechecked to ensure accuracy.
2. Written or oral reviews of individual examinations are not available to applicants. Applicants may
provide written comment to the Department’s licensing unit on specific examination questions.
3. Applicants who fail any examination may submit an application to retake the examination 30 days after
notification that they failed their examination.
1) Which one of the following conditions apply where Type NM cables are permitted to enter a
panelboard through a nonflexible raceway without the cables being secured to the panelboard?
A The raceway extends directly above the enclosure without penetrating the structural
ceiling.
B Because the cables are not secured to the enclosure with a fitting, they shall be
strapped within 24-inches, measured along the cable sheath, of the outer end of the
raceway.
C The raceway shall be at least 18-inches, but not more than 130-inches long.
D The number of cables installed in the raceway is not limited where the raceway length is
not more than 24-inches.
2) Which of the four statements listed below does NOT correctly state code requirements pertaining
to the installation of receptacle outlets installed to serve countertop surfaces in the kitchen of a
dwelling unit located in a multifamily dwelling?
A A receptacle outlet shall be installed at each wall counter space that is 12-inches or
wider.
B The required receptacle outlets shall be supplied by not less than two small-appliance
branch circuits.
C If located above, the receptacle outlets shall not be located more than 20-inches above
the counter top.
D Only receptacle outlets installed within 6-inches of the outside edge of the sink(s) shall be
required to be provided with ground-fault circuit-interrupter protection for personnel.
3) A feeder supplies three 460-volt, three-phase, 1740 RPM, Design B, alternating-current motors.
The motors have the following nameplate ratings: 25 horsepower, 28.4 amperes; 15 horsepower,
18.2 amperes; and 10 horsepower, 11.3 amperes. Assuming all the motors are operating under
continuous duty, what minimum size XHHW-2 copper feeder circuit conductors are required to
supply the motor load? The conductor terminations are rated at 75°C.
A 2 AWG
B 3 AWG
C 4 AWG
D 6 AWG
Units of Measurement:
The measurement system of preference for the National Electrical Code (Code) is now metric units in
accordance with the modernized metric system known as the International System of Units (SI). The SI units
appear first, followed by the inch-pound units in parentheses. This same system also applies to the Tables in
Chapter 9 and the Annexes.
Compliance with the numbers shown in either the SI system or the inch-pound system constitutes compliance
with the Code. Because most applicants are more familiar with the inch-pound units, all questions and answers
in department license examinations use the inch-pound unit system. Answers for “absolute answer” format
questions may be provided in either SI units or in inch-pound units.
Electrical codes often give exact specifications based on exact criteria, then require that these specifications be
adjusted if the circumstances differ from the criteria which the exact specifications were based on. In many
cases, the original specified value is to be adjusted by a percentage. An example would be the ampacity
adjustment factors for conductors. In other cases, the Code gives the applicable percentage to be used in design
calculations. Examples of this would be applying demand factors, adjusting for continuous load or selecting
overcurrent protection for motors or transformers. A percentage is defined as a ratio of a whole number to 100.
The number value, including any decimal of this ratio, is multiplied by 100 and assigned the % sign.
• The percentage amount is divided by 100 to obtain the decimal equivalent: (70 ÷ 100 = .70)
• 140 is multiplied by .70 (140 x .70 = 98)
• Answer: 70% of 140 = 98
A ratio is defined as a fixed comparison or proportion between two similar values, such as primary
compared to secondary or input compared to output.
1) A single-phase transformer has a nameplate voltage rating of 480/120. What is the ratio of the
primary voltage to the secondary voltage?
Formulas used in code and theory calculations are in the form of equations. An equation is a statement
of equality of two quantities of variables, such as A x B = C. While it is important to remember the
definition of an equation, it is more important to know how to transpose an equation that is not
expressed as being equal to the variable that is unknown. As an example, Ohm’s law and Watt’s law
contain three variables that can be transposed into 10 other equations. Equations (formulas) can be
transposed by one or more of the following operations performed equally on each side of the equal sign
(=): addition, subtraction, multiplication or division.
1) If A x B = C. Solve for A.
Ohm’s law expresses the relationship of three variables, E, I and R. The electromotive force in volts is
represented by the letter E, the current in amperes is represented by the letter I, and the resistance in
ohms is represented by the letter R.
In certain alternating current circuits, the term impedance is used rather than resistance. Impedance is a
combination of resistance and reactance and is represented by the letter Z.
1) In a series circuit, the voltage dropped across a 30 Ω resistor is 75-volts. What is the current of the
circuit?
• If E = I x R, then I = E÷ R
• I = 75 ÷ 30
• Answer: I = 2.5 amperes
Watt’s Law (P = E x I)
Watt’s law expresses the relationship of three variables, P, E, and I. The power of an electrical circuit in
watts is represented by the letter P, the electromotive force in volts is represented by the letter E, and
the current in amperes is represented by the letter I. Watts is the term for the true power being used in
an electrical circuit. True power is only produced when the voltage and current sine waves are both
either positive or negative, referred to as a unity power factor. The product of E x I must be a positive
number for watts to be produced. A positive number times a negative number results in a negative
number. As an example: (pos x pos = pos), neg x neg = pos), (neg x pos = neg)
1) An electric baseboard heater is rated 1500 watts at 240-volts. What is the current drawn by the
heater?
• If P = E X I, then I = P ÷ E
• I = 1500 ÷ 240
• Answer: I = 6.25 amperes
For the purposes of this discussion of resistance, direct current circuits and alternating circuits that do
not contain inductive or capacitive loads (unity power factor) are used.
In a series circuit, the current is the same at any point in the circuit, the total resistance is the sum of the
individual resistors, and the applied voltage is equal to the sum of the voltage dropped across all the
resistors.
1) A series circuit, consists of three resistors valued at 20 Ω, 40 Ω, and 60 Ω respectively. If the current
of the circuit is 2 amperes, what is the source voltage?
• If E = I x R
• R total = R1 + R2 + R3
• R total = 20 + 40 + 60 then R total = 120 Ω
• E = 2 x 120
• Answer: E = 240 volts
There are three methods of determining the total resistance in a parallel circuit.
1) When resistors of equal value are connected in parallel, the total resistance is equal to the value of
the resistance of the resistor divided by the number of resistors.
• R total = R ÷ N
• R total = 15 ÷ 3
• Answer: RT = 5Ω
2) The product over sum method can be used for two different resistance values. In a circuit with more
than two resistors or branches, the product over sum method can be used sequentially until only
one pair of resistors is left. For example: RT = (R1 x R2) ÷ (R1 + R2)
3) The third method is the reciprocal method. The total resistance of a parallel circuit is equal to the
reciprocal of the sum of the reciprocals of the resistor values.
1 = 1 + 1 + 1
RT R1 R2 R3
1 = 1 + 1 + 1
RT 2 4 8
1 = .5 + .25 + .125
RT
1 = .875
RT
RT = 1
.875
Answer: RT = 1.143 Ω
For single- phase loads, the volt-amperes are simply the product of multiplying the voltage times the
current. In most cases the Code uses the term volt-amperes in lieu of watts. “Watts” generally is the
volt-amperes multiplied by the power factor of the circuit because it takes into account that current and
voltage may not always be in-phase or in unity. A power factor for other than resistive loads is normally
less than unity or 100% and will result in less usable power or energy. The volt-ampere load of an
alternating current circuit is also called “apparent power,” as it appears the circuit is producing power
equal to the volts times the amperes. Since this number can be quite large, the term KVA is sometimes
used. One KVA is equal to 1000 volt-amperes.
For three-phase calculations, the volt-amperes are multiplied by 1.732 (square root of 3).
While the Code does not mandate a specific allowable amount of voltage drop on feeders and branch
circuits, it does recommend that the total voltage drop not exceed five percent for reasonable efficiency
of operation. In addition, the recommendation states that the feeders and branch circuit should have a
maximum of three percent. If the feeder circuit had two percent, the branch circuit could have three
percent or if the branch circuit had two percent, the feeder could have three percent. The voltage drop
calculation is an application of Ohm’s law. The voltage drop is equal to the current times the resistance
of the circuit. Determining the resistance of the circuit is the problematic part of the equation. The size,
material, and length of the circuit conductors determine the total resistance.
Each set of parallel conductors must be considered as one conductor when calculating voltage drop. The
voltage drop calculations presented here result in an approximate voltage drop for alternating current
circuits. Skin-effect, power factor, and harmonics are factors not taken into consideration in these
examples. The formulas described below should not be relied on for the design of large feeders or
feeders for inductive or harmonic loads.
Single-phase formulas:
1) What is the voltage drop on a 240-volt, single-phase circuit, that is 150 feet from the
panelboard, has a current of 28 amperes and No.8 THWN copper conductors?
• Use K = 12.8
• VD 1Ø = (2 x K x I x L) ÷ CM
• VD 1Ø = (2 x 12.8 x 28 x 150) ÷ 16510
• VD 1Ø = 107520 ÷ 16510
• Answer: VD 1Ø = 6.5 –volts
2) What is the voltage drop on a 208-volt, three-phase branch circuit, that is 205 feet from the
panelboard, has a current of 33 amperes, and the conductors have a resistance of .510 Ω
per 1000 feet?
• VD 3Ø = (1.732 x R x I x L) ÷ 1000
• VD 3Ø = (1.732 x .510 x 33 x 205) ÷ 1000
• VD 3Ø = 5976 ÷ 1000
• Answer: VD 3Ø = 5.98 volts
1) What is the percentage of voltage drop on a 480 volt, three-phase, feeder circuit, that is 280 feet
from the service equipment to the panelboard, has a current of 135 amperes, and 250 kcmil XHHW-
2 aluminum conductors?
• Use K = 21.1
• VD 3Ø = (1.732 x K x I x L) ÷ CM
• VD 3Ø = (1.732 x 21.1 x 135 x 280) ÷ 250,000
• VD 3Ø = (1,381,409 ÷ 250,000)
• VD 3Ø = 5.53 volts
• Percent of VD = VD ÷ EL-L x 100
• Percent of VD = 5.53 ÷ 480 x 100
• Percent of VD = .01152 x 100
• Answer: Percent of VD = 1.15%
Transformer Ratings
Transformers are commonly rated in KVA. The term KVA is a measure of apparent power in units of
1000 volt-amperes. The term KVA is not to be confused with KW (kilo-watts). KW is a measure of true
power units of 1000 watts. Even though there are some losses associated with transformers, for general
calculations the KVA of the primary is considered equal to the KVA of the secondary. The nameplate of
the transformer generally includes the KVA rating, primary and secondary voltages or combinations, the
manufacturer’s name, temperature rise, percent of impedance and if it is single- or three-phase.
• 1Ø KVA = (E x I) ÷1000
• I = (KVA x 1000) ÷ E
• I = (25 X 1000) ÷ 480
• I = 25000 ÷ 480
• Answer: I = 52 amperes
2) Three-Phase Example: For three-phase loads the KVA rating is equal the voltage times the current
times 1.732. A three-phase, 750 KVA transformer is rated at 4160-208/120 volts. What is the full
load, secondary current rating?
The available short-circuit fault current value must be known to properly select equipment ratings.
Although there are a number of factors that will affect the available short-circuit fault current at any
point on an electrical system, most calculations begin with determining the maximum available short-
circuit fault current at the load terminals of a transformer under a bolted short circuit condition without
any short-circuit or overcurrent protection and assuming an infinite primary source. Only transformer
short-circuit fault current calculations are demonstrated by the following examples. The formula for
maximum available fault current for a transformer is:
Short-circuit current [SC] = transformer secondary full-load amperes [FLA] x the multiplier
The transformer multiplier is equal to 100 divided by the transformer impedance expressed as a
percentage. The transformer impedance is generally marked on the nameplate of the transformer and is
identified by the letter “Z”.
1) What is the maximum available short-circuit fault current for a transformer with the following
secondary nameplate rating: 75 kva, 120/240 volt, single- phase, 2.5% Z?
2) What is the maximum available short-circuit fault current for a transformer with the following
secondary nameplate rating: 45 kva, 120/208 volt, three- phase wye, 1.2% Z?
The examples illustrated above are for line-to-line faults. Line-to-neutral or line-to-ground faults
will generally result in 10 to 15% higher available short-circuit fault currents.
Not considering any reduction based on circuit impedance or increase from motor load
contribution, the equipment connected to the load side of the transformers in the illustrations
above must have a short-circuit or interrupt rating not less than the calculated available short-
circuit fault current for each question.
Annex C of the National Electrical Code contains the Tables for conduit and tubing fill for conductors and
fixture wires of the same size. Every type of conduit, flexible conduit or tubing in which conductors are
field installed has two tables listing the maximum number of any given wire size (gauge) and type
(insulation). These Tables apply to raceways longer than 24-inches.
1) How many No.10 AWG, Type THWN conductors may be installed in trade size 1½, Schedule 80,
Polyvinyl Chloride Conduit?
When a conduit or tubing contains several different size conductors or contains conductors with
different types of insulation, a more complex procedure is to be followed. In general, this procedure
involves three steps. First, determine the combined square inch area of all the conductors. Second,
determine the percent of cross sectional area allowed for conductors based on the number of
conductors to be installed in the conduit. Third, select the size conduit or tubing that has a “percent of
area” determined in step one that exceeds the square inch area required for the conductors determined
in step two. This information is found in the tables in NEC Chapter 9. Where conduit or tubing nipples
not longer than 24-inches are installed between boxes, cabinets or similar enclosures, the nipples shall
be permitted to be filled to 60 percent of their total cross sectional area.
• Using NEC Chapter 9, Table 1 it is determined that 40% of the cross sectional area of the rigid
metal conduit may be used for conductor fill because it will contain over 2 conductors.
• From NEC Chapter 9, Table 5, determine the square inch area of all the conductors, based on
their size and insulation type.
o No.3 THW - 0.1134 sq. in. times 6 conductors = 0.6804 sq. in.
o No.6 THWN - 0.0507 sq. in. times 6 conductors = 0.3042 sq. in.
o No.8 THWN - 0.0366 sq. in. times 1 conductor = 0.0366 sq. in.
o No.14 XHHW - 0.0139 sq. in. times 12 conductors = 0.1668 sq. in.
o The total cross-section area of the conductors is 1.1880 sq. in
• Using NEC Chapter 9, Table 4 under the heading of Rigid Metal Conduit, determine from the
40% column, the minimum size conduit that exceeds 1.1880 square inches.
• Answer: trade size 2
Conductor Ampacity
NEC Table 310.16 lists the allowable ampacities of conductors rated 0–2000 volts, 60°C through 90°C,
based on an ambient temperature of 30°C and not more than three current-carrying conductors in a
raceway, cable or directly buried in the earth. When conductors are used within these specific criteria it
is simply a matter of selecting the ampacity from the table based on the conductor size, insulation type
and material. These criteria limit the amount of heat generated by the current flowing through the
conductor to a safe level. Conductors used outside of these criteria must have their ampacities adjusted
accordingly.
There are two variables that may need to be considered: ambient temperatures and the numbers of
conductors in a raceway.
Ambient Temperature:
On occasion, conductors are used in environments that are warmer than an ambient temperature of
30°C (86°F). The higher temperature environments limit a conductor’s ability to safely dissipate the heat
generated by the conductor, so the ampacity must be reduced. NEC Table 310.15(B)(1) includes
correction factors for ambient temperatures other than 30°C (86°F). To correct the conductor ampacity
based on ambient temperature, multiply the allowable ampacities by the appropriate factor of the
ambient in which the conductor will operate. In addition, the temperature limitations equipment
terminations described in NEC section 110.14 must be applied when conductor ampacity/overcurrent
rating is determined.
1) What is the allowable ampacity of a No.1/0 THWN copper conductor when installed in an ambient
temperature of 107° F?
• NEC Table 310.16 lists the allowable ampacity of No.1/0 THWN copper, a 75°C rated
conductor as 150 amperes
• The correction factor is .82
• 150 x .82 = 123 amperes
• Answer: 123 amperes
Often more than three current-carrying conductors are installed in a single raceway.
Once again the allowable ampacity of the conductors must be reduced to prevent overheating and
damage to conductor insulation.
NEC Table 310.15(C)(1) specifies the percentage of adjustment required based on the number of
current-carrying conductors in the raceway or cable.
The percentages given in NEC Table 310.15(C)(1) are applied to the allowable ampacities of Tables
310.16 through 310.21 after any correction for ambient temperature has been made.
1) A trade size 1¼ conduit contains three, 3-phase motor circuits and an equipment grounding
conductor. The motors run at the same time and the conductors are No.8 THHN copper. What is the
allowable ampacity of these conductors?
• From NEC Table 310.16, the allowable ampacity of a No.8 THHN copper conductor is 55
amperes.
• The 55 ampere rating is based on not more than three current-carrying conductors in the
raceway and an ambient temperature of 30°C.
• Because a different ambient temperature is not stated, no correction for ambient temperature
is required, the percentages given in NEC Table 310.15(C)(1) to the ampacity listed in the table
are applied
• In this case it is 70% based on the nine current-carrying conductors.
• Note: NEC section 310.15(F) provides that the equipment grounding conductor is not counted
when applying the provisions of section 310.15(C)(1).
• 55 x .70 = 38.5 Amperes
• Answer: 38.5 Amperes
The Code requires that boxes and conduit bodies be of sufficient size to provide ample free space for
conductors, connections and where applicable, wiring devices. These requirements are found in NEC
section 314.16.
1) What is the maximum number of No.10 AWG THHN conductors that may be installed in a 4 x 2⅛
square metal box?
This answer can be taken directly from NEC Table 314.16(A) as there are no other volume
allowances required. Answer: 12 conductors
2) What is the maximum number of No.12 AWG conductors that may be installed in a box that is
marked with a volume of 60 cubic inches?
• NEC Table 314.16(B) gives the volume allowance required per conductor
• In this case, 2.25 cubic inches are required for each No.12 AWG conductor
• Divide the volume of the box by the volume allowance of the conductor
• Do not round up!
• 60 cubic inches ÷ 2.25 cubic inches = N
• N = 26.67
• Answer: 26 conductors
3) A 2-gang, nonmetallic box is to be used for a 3-way switch and duplex receptacle outlet. Type NM
cable is used as the wiring method. The box contains a 14-2 and a 14-3 cable for the lighting circuit
and two, 12-2 cables for the outlet circuit. The box has internal cable clamps to secure the cables.
What is the minimum cubic inch volume of the box?
Determine the volume required for the conductors. Do not count the equipment grounding
conductors at this time.
With limited exception, conductors that supply motor branch circuits shall be sized at 125% of the full-
load current rating of the motor based on the values in NEC Tables 430.247 through 430.250, rather
than that of the motor nameplate. NEC section 430.6(A)(1) requires these tables also be used to
determine the ampere rating of switches and the branch-circuit short-circuit and ground-fault
protection. The motor nameplate current rating is to be used only to size the overload protection.
1) What is the minimum size THWN copper, branch circuit conductors that may be used to supply a
40 HP, 230-volt, 3Ø alternating current motor with a nameplate current of 97.6 amperes?
• As previously stated, the nameplate current is not to be used to size the branch circuit
conductors, rather the value given in NEC Table 430.250 shall be used.
• The full-load current rating of a 40 HP, 230-volt, 3Ø motor is 104 amperes.
• In accordance with NEC section 430.22, the ampere rating of the branch circuit
conductors shall be 125% of the rating found in Table 430.250.
• 104 X 1.25 = 130 amperes.
• From the 75°C column of Table 310.16, select a copper conductor with an ampacity that
equals or exceeds 130 amperes.
• Answer: No.1 AWG
2) A motor control center serves the following 3Ø, 460-volt, AC motors: 1 – 100 HP; 6 – 15 HP; and
2 –HP. What is the minimum ampacity of the feeder conductors that supply the motor control
center?
• NEC section 430.24 requires conductors supplying several motors to have an ampacity
at least equal to the sum of the full-load current ratings as determined by section
430.6(A)(1), plus 25% of the highest motor in the group.
• 124 + (124 x .25) + (6 x 21) + (2 x 11) = 303 amperes
• Answer: 303 amperes
3) Dual element, time-delay fuses are used to provide motor branch-circuit, short-circuit and
ground-fault protection for a 75 HP, 230-volt, 3Ø, Squirrel cage, Design B, three-phase motor. In
general, what is the maximum size fuse that may be installed?
• The Percentages of Full-Load Current found in NEC Table 430.52 are applied to the Full-
Load Current, Three-Phase Alternating-Current Motors of Table 430.250.
• A 75 HP, 230-volt, three-phase motor has a full-load current rating of 192 amperes.
• From the Dual Element (Time Delay) Fuse column of NEC Table 430.52, the maximum
fuse is 175% of 192 amperes. 192 x 1.75 = 336 amperes.
• Because 336 amperes is not a standard fuse rating as listed in 240.6, NEC section
430.52(C)(1) Exception No. 2, allows the next largest standard rating to be used as long
as it does not exceed 225%, in this case, 350 amperes.
• Answer: 350 amperes
The Department of Labor and Industry offers these study suggestions for the types of license examinations
indicated. This study guide must not be construed to indicate that all questions will be from the knowledge
areas indicated below or that all knowledge areas will be included on individual examinations. License
applicants are expected to be familiar with all Code requirements that apply to the scope of the license they
are applying for.
The examinations administered by the Department are identified by the following abbreviations:
Lineman license examinations are based on general electrical theory and requirements found in the 2017
edition of the National Electrical Safety Code as published by the Institute of Electrical and Electronics
Engineers, Inc., and the Laws and Rules Regulating Licensing of Electricians and Inspection of Electrical
Installations.
Chapter 1 General
Definitions X X X X X X X X
Approval, listing and labeling of electrical equipment required X X X X X X X X
Interrupting rating of electrical equipment X X
Mechanical execution of work X X X X X X X X
Electrical connections, terminals, splices and temperature X X X X X X X
limitations of equipment
Identification of disconnecting means X X X X X X
Working space about electrical equipment and dedicated X X X X X X X
equipment space
Working space about electrical equipment and dedicated X X
equipment space over 1000 volts
Chapter 9 Tables
Notes to tables: percent of cross section of raceways for X X X X X X X
conductors; use Annex C for conductors all the same size and
insulation type; dimensions and percent area of conduit and
tubing; dimensions of insulated conductors
Notes to tables: conductor properties; alternating-current X X X X X
resistance; Annex D, examples of branch-circuit, feeder,
service, and motor circuit calculations; Annex E, types of
construction
Notes to tables: class 2 and 3 alternating-current power X X X
source limitations
WHO IS COVERED?
The ADA provides comprehensive civil rights protection for “qualified individuals with disabilities.” An
“individual with a disability” is a person who: 1) has a physical or mental impairment that substantially
limits a “major life activity,” 2) has a record of such an impairment, or 3) is regarded as having such an
impairment. “Major life activities” include functions such as caring for oneself, performing manual tasks,
walking, seeing, hearing, speaking, breathing, learning, and working.
Individuals who currently engage in the illegal use of drugs are not protected by the ADA when an action is
taken on the basis of their current illegal use of drugs.
A “qualified” individual with a disability is one who meets the essential eligibility requirements for the
examination. The Department is not required to take any action that would result in a fundamental
alteration in the nature of the examination or an undue financial and administrative burden. However, the
Department must take any other action, if available, that would not result in a fundamental alteration or
undue burdens but would ensure that individuals with disabilities receive the benefits or services.
WHAT IS REQUIRED?
The Department is required to make reasonable modifications in any policies, practices, and procedures
that deny equal access to individuals with disabilities, unless a fundamental alteration in the examination
would result. To do so, it must furnish auxiliary aids and services when necessary to ensure effective
communication, unless an undue burden or fundamental alteration would result. The Department may not
place special charges on individuals with disabilities to cover the costs of measures necessary to ensure
nondiscriminatory treatment, such as making modifications required to provide program accessibility or
providing qualified interpreters. Finally, it must operate the examination so that, when viewed in its
entirety, it is readily accessible to and usable by individuals with disabilities.
Integration of individuals with disabilities into the mainstream of society is fundamental to the purposes of
the ADA. The Department may not provide the examination to individuals with disabilities through
programs that are separate or different, unless the separate programs are necessary to ensure that the
benefits and services are equally effective. Even when separate programs are permitted, an individual with
a disability still has the right to choose to participate in the regular program. The Department cannot
require an individual with a disability to accept a special accommodation or benefit if the individual
chooses not to accept it.
QUESTIONS?
If you have any questions about the ADA we encourage you to contact the United States Department of
Justice which as an ADA information line, at https://www.ada.gov/infoline.htm
GENERAL INFORMATION
If you are a person with a disability, you have certain rights under the Americans with Disabilities Act
(“ADA”). A brief summary of these rights is on the back of this sheet. It is not meant to be complete. If you
have any questions about the ADA we encourage you to contact the United States Department of Justice
which as an ADA information line, at https://www.ada.gov/infoline.htm
Examinations are held weekly, generally every Saturday, at the Department of Labor and Industry Building
located at 443 Lafayette Road North, Saint Paul, just north of the intersection of Interstate 94 and US
Highway 52 (Lafayette Road North), on the northeast edge of downtown Saint Paul. The building is
accessible to persons with physical disabilities.
Specify instructions for scheduling and appearing for an examination are included in the letter that is sent
to approved applicants.
ALTERNATIVE ARRANGEMENTS
The ADA requires this agency to make “reasonable accommodations” for applicants with disabilities in
giving the examinations. If you are a person with a disability which may affect your ability to enter the
examination facility or to take any portion of the examination, the ADA may require the agency to provide
alternative examination arrangements. We are not required to do so if we are unaware of your need for
alternatives. Based on the above description of the examination facilities and the examination itself, we
ask that you inform us of any alternative arrangements you may require to take the examination. Please
describe in detail:
SIGNATURE DATE
IF YOU ARE REQUESTING ALTERNATIVE ARRANGEMENTS BASED ON A DISABILITY, PLEASE SUBMIT THIS
FORM WITH YOUR APPLICATION FOR EXAMINATION FORM.
Dates scheduled by individuals without written approval of their application will be rejected and not
scheduled. Individuals retesting after a failed examination must apply for another examination date.
Detailed examination dates, location and scheduling information can be accessed at:
http://www.dli.mn.gov/business/get-licenses-and-permits/license-exam-schedule
Applicants must schedule their examinations ahead of time. Walk-ins are not permitted to take an
examination. Applicants may reschedule their examination one time. Applicants that fail to appear for a
rescheduled examination as well as applicants that fail their examination must submit a new application
and examination fee before being approved for examination or reexamination.
All examination types administered at the St. Paul office begin at 8:15 a.m. and end at 1:45.
All examination types are allotted 5½ hours for completion. All applicants should arrive at the
examination site not later than 30 minutes before their scheduled starting time. A picture ID must be
presented by all applicants when they appear for examination.
Note: Food and drink are permitted during the exam. Use of restrooms is permitted. However, applicants
are not allowed to leave the building once the examination has started.
The Department of Labor and Industry Building located at 443 Lafayette Road North, Saint Paul, just north
of the intersection of Interstate 94 and US Highway 52 (Lafayette Road North), on the northeast edge of
downtown Saint Paul.
http://www.mapquest.com/maps/map.adp?country=US&addtohistory=&formtype=address&searchtyp
e=address&cat=&address=443%20Lafayette%20Rd%20N&city=Saint%20Paul&state=MN&zipcode=
55155%2d4301
Specific instructions concerning the examinations in St. Paul are sent as a part of the “Approved for
Examination” letter and specific instructions for out-state sites are sent to persons who schedule at those
sites.
Applicants who have received a Bachelor’s degree in Electrical Engineering from an accredited university or
college qualify for the Class A master electrician and power limited technician examinations without being
required to have any practical installation experience. “Engineer” applicants should include a copy of their
transcript or diploma with their application.
Applicants for Class A journeyworker electrician, maintenance electrician, power limited technician, and
Class B installer who have successfully completed a two-year technical college program approved by the
Department receive 12-month’s experience credit toward the experience required for the class of license
applied for.
Applicants for a power limited technician license who have completed other technical training approved by
the Department receive up to 12-month’s experience credit toward the 36 month experience requirement.
Technical training credit is only granted for successful completion of programs approved by the Department
prior to completion by the applicant. Technical training credit is not approved on an individual applicant
basis.
Military Experience
Applicants may receive experience credit for performing electrical work in the military. Applicants with
military experience should include a copy of their DD214 discharge documents with their application.
Minnesota Rule 3800.3520 identifies allowable experience credit, situations under which experience is
acceptable to the Department, and experience requirements for all license categories. Applicants are
encouraged to review these requirements prior to submitting an application.
Application/examination fees for applicants that do not qualify for examination are not refundable.
Applicants for a satellite system installer license are not required to have any practical experience, rather
are required to have successfully completed the National Standards and Testing Program for satellite
system installers sponsored by the Satellite Broadcasting and Communications Association of America, Inc.
or other program approved by the Board of Electricity.
Minnesota has agreements at the journeyworker electrician level with the following states: Alaska,
Arkansas, Colorado, Iowa, Montana, Nebraska, North Dakota, South Dakota, and Wyoming. In addition,
Minnesota, Iowa, North Dakota, Nebraska, and South Dakota have reciprocal agreements at the master
electrician license level.
1. The applicant must meet the qualifications for license examination in the state they are making
application.
2. The applicant must not have failed the same or greater class of license examination in the state
application is made.
3. The applicant must have obtained the same or greater class of license in the first state by
examination at the state level (the license must not have been obtained through a reciprocal
agreement or grandfather clause with a city or other political subdivision).
4. The applicant must have received an examination score equal to or greater than required in the
state application is made.
5. The applicant must have held the license for at least one year in the first state.
6. The applicant’s license must be current and in good standing in the first state.
7. The applicant must not be under any order to deny, suspend, or revoke any class of electrical
license in Minnesota.
8. The applicant must submit an application and examination fee with the application.
9. Upon approval, the applicant must submit the required license fee to be issued the license applied
for.
10. Upon obtaining the license, the applicant (licensee) must meet all continuing education and
renewal requirements to maintain the license.
Except for power limited technician licenses, all other personal licenses require the license holder to earn a
minimum of 16 hours of continuing education credit prior to renewal. Of these 16 hours, at least 12 hours
must be on the National Electrical Code, and up to 4 hours may be on related technical subjects or the
Minnesota Electrical Act and Minnesota Rules Chapters 3800 and 3801.
Power limited technicians are required to earn 16 hours of continuing education credit, 4 hours of which
must be on the National Electrical Code and up to 12 hours may be on related technical subjects or the
Minnesota Electrical Act and Minnesota Rules Chapters 3800 and 3801.
Satellite system installers are required to earn 4 hours of continuing education credit.
Holders of master electrician licenses, which have fixed terms, are not required to meet any continuing
education requirements in their first pro-rated term, but must earn 16 hours in all subsequent terms.
Continuing education credits may be used for renewal of more than one class of license, but may only be
used once for each class of license. Continuing education credits in excess of those required for renewal
and earned prior to expiration of a license do not carry over to the next license term.
Continuing education credit is only received for verified attendance/completion of programs granted
Department approval. Continuing education credit may be received by attending programs approved in
other states where the programs meet Department requirements.
Continuing education requirements are found in Minnesota Rule 3800.3600-3603. Lists of Department
approved continuing education providers are available under “continuing education” at:
http://www.dli.mn.gov/workers/electrician-or-electrical-installer/continuing-education-electrical
Laws and Rules Regulating Licensing of Electricians and Inspection of Electrical Installations
A copy of the Minnesota Electrical Act and Minnesota Rules Chapter 3800 and 3801 are included
in the hard- copy packet or may be downloaded from the Department’s website at:
http://www.dli.mn.gov/business/electrical-contractors/electrical-laws-and-rules