PB Manual Call Point Range: Ex De, Ex Ia, Weatherproof
PB Manual Call Point Range: Ex De, Ex Ia, Weatherproof
PB Manual Call Point Range: Ex De, Ex Ia, Weatherproof
Overview Features
These new and improved manual • ATEX certified • Corrosion free GRP construction
alarm call points have been designed • Variety of colours available
for use in hazardous locations and • IECEx certified
harsh environmental conditions. • UL certified for Haz locs • Up to 9 terminals available
The GRP enclosure is suitable for • UL certified for Ord locs • Optional LED – indicates that the
use onshore or offshore where light unit has been operated
weight combined with a high level of • TR CU certified
• Earth continuity option for metal
corrosion resistance is required.
• Chinese (CCC) certified glands
The unit is now supplied with a lift
• Brazilian (INMETRO) certified • 1 or 2 changeover switches
flap that latches firmly in place (not
available for turn and push version). • CCOE certified • Captive cover screws
• DNV type approval (IEC 60945) • Lift flap as standard (not available
for turn and push version)
• SIL 2 certified
• Latching as standard. Self reset
• IP66 and IP67
(momentary) available
Eaton
Unit B, Sutton Parkway
Oddicroft Lane
Sutton in Ashfield
United Kingdom © 2020 Eaton
NG17 5FB All Rights Reserved
Printed in UK Eaton is a registered trademark.
T: +44 (0) 1623 444 400 Publication
www.crouse-hinds.com/hac No.DSMC0031/G All other trademarks are property
[email protected] October 2020 of their respective owners.
All specifications, dimensions, weights and tolerances are nominal (typical) and Eaton reserve the right to vary all data without prior notice.
No liability is accepted for any consequence of use.
Certifications General arrangement drawing (all dimensions in mm)
120 ±2
ATEX Ex de Cert. no. BAS02ATEX2105X. ATEX Approved Ex II 2GD 1 2 3 116 3
Certified to: EN60079-0, EN60079-1, EN60079-7, EN60079-18, EN60079-31 67 2
Ex db eb IIC T6 Gb, Ex tb IIIC T85°C Db (switch only)
Ex db eb mb IIC T6 Gb, Ex tb IIIC T85°C Db (with LED)
Ex db eb mb IIC T4 Gb, Ex tb IIIC T135°C Db (with resistors & diodes)
ATEX Ex ia Cert no. Baseefa 03ATEX0084X. ATEX Approved Ex II 1GD
FIXING CENTRES
Certified to: EN60079-0, EN60079-11
Ex ia IIC T4 Ga , Ex ia IIIC T135ºC Da CERT LABEL
72 1
IECEx Ex de Cert. no. IECEx BAS 18.0100X.
Certified to: IEC60079-0, IEC60079-1, IEC60079-7, IEC60079-18, IEC60079-31
Ex db eb IIC T6 Gb, Ex tb IIIC T85°C Db (switch only)
Ex db eb mb IIC T6 Gb, Ex tb IIIC T85°C Db (with LED)
Ex db eb mb IIC T4 Gb, Ex tb IIIC T135°C Db (with resistors & diodes)
25 1
IECEx Ex ia Cert. no. IECEx BAS 12.0093X GLAND
Certified to: IEC 60079-0, IEC 60079-11 4 5 6 CENTRES
16 16
Ex ia IIC T4 Ga, Ex ia IIIC T135ºC Da 92 1
FIXING HOLES: 6.0 (4 POSITIONS)
ALL DIMENSIONS ARE IN MILLIMETERS
FIXING CENTRES
UL Listing no. E186629
120 ±2
UL listed to Class 1, Div 2. Groups A,B,C & D 1 2 3 116 3
UL listed for Ordinary Locations. Listing no. S8117 67 2
FIXING CENTRES
Russian Fire approved (Must be red and have burning house CERTduty
LABEL label)
126 ±2
72 1
TR CU Ex ia 0Ex ia IIC T4 Ga X, Ex ia IIIC T135°C Da
Russian Fire approved (must be red and have burning house duty label)
INMETRO Ex de Ex db eb IIC T6 Gb, Ex tb IIIC T85°C Db (switch only)
Ex db eb mb IIC T6 Gb, Ex tb IIIC T85°C Db (with LED)
Ex db eb mb IIC T4 Gb, Ex tb IIIC T135°C Db (with resistors & diodes)
25 1
CCC Ex de Ex de IIC T6 (switch only), Ex de mb IIC T4 (other versions) GLAND
4 5 6 CENTRES
CCC Ex ia Ex ia IIC T4 16 16 FIXING HOLES: 6.0 (4 POSITIONS)
92 1 ALL DIMENSIONS ARE IN MILLIMETERS
Type Approvals American Bureau of Shipping type approval (ABS) PBI only FIXING CENTRES
Ordering requirements
The following code is designed to help in selection of the correct unit. Build up the reference number by inserting the code for each component into the appropriate box
Model Certification Entries Labels Voltage Switches Options Terminals Finish
PB
DSMC0031/G 10/20