Sulphur Hexafluoride SF: Power Transmission and Distribution
Sulphur Hexafluoride SF: Power Transmission and Distribution
Sulphur Hexafluoride SF: Power Transmission and Distribution
Copyright© Siemens AG
Power Transmission and Distribution / High Voltage
Sulphur Hexafluoride, SF6
Copyright© Siemens AG
Seite 2 Sep-06 Autor Power Transmission and Distribution / High Voltage
Electrical properties
50 Hz breakdown voltage of SF6 in a homogeneous field as a function of the
distance between electrodes
kV
Öl
200
vacuum
SF6, 1 bar
150
100
air, 1 bar
50
Copyright© Siemens AG
Seite 3 Sep-06 Autor Power Transmission and Distribution / High Voltage
SF6-Füllkurve und Ansprechwerte des Dichtewächters
SF6 filling curve and operating values of density monitor
SF6 filling and operating values of density monitor
Beispiel / Example:
LS / CB
Fülldruck / Filling
Pressure:
6,0 bar / 20°C
6,0+0,3
5,2-0,2
0,2+0,15
Copyright© Siemens AG
Seite 4 Sep-06 Autor Power Transmission and Distribution / High Voltage
Density monitor, cross section
at 20°C
1 Signal 1: 5,0 bar
Microswitches 2 Signal 2: 5,0 bar
3 Signal 3: 5,2 bar
SF6-Referencevolume
6 bar at 20°C
Bellows
SF6-Gas breaker
Body
Copyright© Siemens AG
Seite 5 Sep-06 Autor Power Transmission and Distribution / High Voltage
Density monitor, cross section
Ambient Indoor
Copyright© Siemens AG