Test Asset Test Conditions
Substation MAIN SUBSTATION Reason MAINTENANCE  

Position TX NO.2 Weather SUNNY DAY  

Job # Ambient
30 °C
Temperature
Asset ID Humidity 80.00 %

Date 28/09/2021  

Tester AKMAL, FAUZI  

Power Transformer Information


Manufacturer THAI TRAFO Core design Core

Serial # 000468 Tank type Sealed

Year 2000 Class ONAN/ONAF

Vector group Dyn11 Coolant Mineral oil

Phases 3
D yn11
Frequency 50
H2 X2
Weight 17200 kg
X0 X3 BIL / Lightning Impulse 75 kV
H1 H3 Impedance HVLV 8.98 %
X1
Impedance HVTV %

Impedance LVTV %

Oil volume 3700 GAL

Oil temp. 35 °C

Transformer windings
Voltage Changer Tap changer Winding
Winding kVA Rated I # Taps Nominal Tap setting
(kV) type Model material

Primary 33.00 12 500 5 3 DETC Cu

Secondary 11.00 12 500 1 Cu

Comment:

localhost:59721/?fileport=63054#%2520&ui-state=dialog 1/5
9/29/21, 4:10 PM TRAX - Test report

Test results

Tan Delta - Power Transformer


Corr.
P eq
%TD at 34 Corr. %TD
Designation f (Hz) U C at 34 I eq
°C Factor to
°C
20°C
CHG + CHL 50.00 10.00 kV 6.704 nF 0.676 --- --- 1.424 W 21.06 mA

CHG 50.00 9.995 kV 2.204 nF 0.674 --- --- 467.0 mW 6.924 mA

CHL 50.00 9.997 kV 4.507 nF 0.677 --- --- 958.8 mW 14.16 mA

CLG + CLH 50.00 6.351 kV 10.03 nF 0.711 --- --- 2.241 W 31.51 mA

CLG 50.00 6.354 kV 5.531 nF 0.741 --- --- 1.288 W 17.38 mA

CLH 50.00 6.350 kV 4.500 nF 0.675 --- --- 953.7 mW 14.14 mA

Comment:
GOOD CONDITION (EXPECTED < 1.0%)
Turns ratio measurements
Measured
Connection Tap (P) Tap Voltage (V) U TTR Error I Exc Phase
TTR
H1-H2 / X1-X0 1 34 650 --- 5.456 --- --- --- ---

H2-H3 / X2-X0 1 34 650 --- 5.456 --- --- --- ---

H3-H1 / X3-X0 1 34 650 --- 5.456 --- --- --- ---

H1-H2 / X1-X0 2 33 825 --- 5.326 --- --- --- ---

H2-H3 / X2-X0 2 33 825 --- 5.326 --- --- --- ---

H3-H1 / X3-X0 2 33 825 --- 5.326 --- --- --- ---

H1-H2 / X1-X0 3 33 000 80.00 V 5.196 5.195 -0.02 % 2.679 mA 0.0 °

H2-H3 / X2-X0 3 33 000 80.00 V 5.196 5.196 -0.01 % 2.302 mA 0.0 °

H3-H1 / X3-X0 3 33 000 79.96 V 5.196 5.196 -0.00 % 3.666 mA 0.0 °

H1-H2 / X1-X0 4 32 175 --- 5.066 --- --- --- ---

H2-H3 / X2-X0 4 32 175 --- 5.066 --- --- --- ---

H3-H1 / X3-X0 4 32 175 --- 5.066 --- --- --- ---

H1-H2 / X1-X0 5 31 350 --- 4.936 --- --- --- ---

H2-H3 / X2-X0 5 31 350 --- 4.936 --- --- --- ---

H3-H1 / X3-X0 5 31 350 --- 4.936 --- --- --- ---

Comment:
GOOD CONDITION (EXPECTED ERROR <0.5%)

localhost:59721/?fileport=63054#%2520&ui-state=dialog 2/5
9/29/21, 4:10 PM TRAX - Test report

Winding resistance measurements


34°C
Connection Tap (P) Current Stability Variation
Resistance
H1-H2 5 --- --- --- ---

H2-H3 5 --- --- --- ---

H3-H1 5 --- --- --- ---

H1-H2 4 --- --- --- ---

H2-H3 4 --- --- --- ---

H3-H1 4 --- --- --- ---

H1-H2 3 10.00 A 462.0 mΩ 99.32 % ---

H2-H3 3 10.00 A 456.8 mΩ 99.15 % ---

H3-H1 3 10.01 A 456.4 mΩ 98.69 % 1.21 %

H1-H2 2 --- --- --- ---

H2-H3 2 --- --- --- ---

H3-H1 2 --- --- --- ---

H1-H2 1 --- --- --- ---

H2-H3 1 --- --- --- ---

H3-H1 1 --- --- --- ---

Comment:
GOOD CONDITION (EXPECTED ERROR <5.0%)

localhost:59721/?fileport=63054#%2520&ui-state=dialog 3/5
9/29/21, 4:10 PM TRAX - Test report

Demag measurements
Remanence before Remanence after
Designation Current Time
demag demag
H2-H1 0.000 A 31.04 s 28.55 % <1 %

Comment:
N/A
Winding resistance measurements
34°C
Connection Tap (S) Current Stability Variation
Resistance
X1-X0 1 10.00 A 461.4 mΩ 99.47 % ---

X2-X0 1 10.00 A 461.0 mΩ 99.51 % ---

X3-X0 1 10.05 A 459.1 mΩ 99.72 % 0.50 %

Comment:
GOOD CONDITION (EXPECTED ERROR < 0.50%)

localhost:59721/?fileport=63054#%2520&ui-state=dialog 4/5
9/29/21, 4:10 PM TRAX - Test report

Demag measurements
Remanence before Remanence after
Designation Current Time
demag demag
H2-H1 0.000 A 27.59 s 70.38 % <1 %

Comment:
N/A

localhost:59721/?fileport=63054#%2520&ui-state=dialog 5/5