Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Technical Data

Broadcrown Ltd, Airfield Industrial Estate, Hixon, Stafford. ST18 0PF UK July 2008
Tel: +44 (0)1889 272200 Fax: +44 (0)1889 272220 www.broadcrown.com

Generator
Cummins Newage Stamford Model: BCC 1250P-50
KTA 50 G3 PI 734 Generator
Model: BCC 1400S-50

Power Factor
50 Hz 3-Phase Cos Φ = 0.8

PRIME POWER (PRP) STANDBY POWER (LTP)


RATINGS
BCC 1250P-50 BCC 1400S-50
Voltage kVA kWe kVA kWe Amps
415/240 1250 1000 1400 1120 1948
400/230 1250 1000 1400 1120 2021
380/220 1250 1000 1400 1120 2127

Definition of Ratings & Reference Conditions

Prime Power (PRP) is the nominal output continuously available, where the average load (variable) does not exceed 70% of the prime
power rating during an operating period of 250 hours. The total operating time at 100% prime power must not exceed 500 hours per year.
A 10% overload is available for a maximum of 1 hour in 12 hours of operation and must not exceed a total of 25 hours per year.
Standby Power (LTP) is the maximum output available (at variable load), for up to 200 hours per year. The average load (variable) must
not exceed 80% of the standby power rating, with less than 25 hours per year at the full standby rating. No overload is available. The
genset must not operate, at standby rating, in parallel with the public utility under any circumstances.
Standard Reference Conditions: air temperature 25°C (77°F), barometric pressure 100kPa [110m(361ft) altitude], 30% relative humidity.
Note: The above ratings may be subject to derate at different operating conditions. Please see the Derate Guidelines on the Broadcrown
website.
All power ratings and reference conditions in accordance with ISO 8528-1 and ISO 3046-1.

Key Features:

● Efficient water cooled diesel engine.


● Single bearing Newage Stamford alternator
● Radiator with pressure cap and drain point
● Fully guarded engine-driven fan
● Fully welded steel baseframe with lifting / jacking points
● Various fuel system options
● Heavy duty rubber anti-vibration mountings
● 24V starter batteries and connecting cables
● Separate engine-driven battery charging alternator
● Spin on oil and fuel filters and dry type air filter element
● Industrial silencer(s) supplied loose (optional)
● Auto Start control system with digital instrumentation
● Main line circuit breaker (optional)
● Factory Test Certificate
● Operation & Maintenance Manual
● Wide range of optional extra features available

Overall Dimensions & Weights - Open Set


Length (L) = 5200mm
H
Width (W) = 1795mm
Height (H) = 2340mm

Dry Weight (inc oil) = 9740kg


L W Operating Weight = 10200kg

Typical Open Generator Sound Pressure Level at 1m, Free Field (dB)
Overall dBA 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

111 100 103 105 105 105 104 101 103


All specifications and design are subject to change without notice
BCC 1250P-50
BCC 1400S-50
July 2008

ENGINE & COOLING SYSTEM CUMMINS KTA 50 G3

SI Units PRIME STANDBY

Engine Speed r/min 1500


Performance

Gross Power kWm 1097 1227


Fan Power kWm 20 20
Net Power kWm 1077 1207
Emissions Certification
Altitude Capability m 1700 2200

Cylinders / Type 16 cyl / 60° Vee / 4-stroke


Aspiration / Charge Cooling Turbocharged / JWAC
General

Governing / Engine Management Electronic Governor / ECU


Bore / Stroke mm 159 / 159
Cubic Capacity litres 50.3
BMEP kPa 1737 1943

Fuel Consumption at 100% Power litres/h 261 293


Fuel Consumption at 75% Power litres/h 199 223
Fuel

Fuel Consumption at 50% Power litres/h 139 155


Total fuel flow litres/h 625
Standard Fuel Tank Capacity litres 200

Engine Air Flow m³/s 1.605 1.746


Air

Maximum Air Intake Restriction (used filter) kPa 6.23

Exhaust Gas Flow m³/s 3.73 4.01


Exhaust

Exhaust Gas Temperature °C 520 525


Maximum Exhaust Back Pressure kPa 6.8
Typical Exhaust Pipe Diameter mm 350

Radiator Cooling Air Flow m³/s 23


Max Restriction to Cooling Air Flow Pa 250
Cooling

Max Radiator Air-On Temperature °C 45


Maximum Coolant Temperature °C 104
Coolant Capacity - Engine Only litres 161
Total Coolant Capacity litres 312

Total Oil Capacity incl Filters litres 177


Oil

Typical Oil Pressure at Rated Speed kPa 414


Typical Oil Consumption (>250hrs Operation) litres/h 0.69

Heat Rejection to Engine Cooling Water kW 680 775


Thermal

Heat Rejection to Charge Cooler kW n/a


Heat Radiated From Engine (Typical) kW 130 150

Electrical System Voltage V 24


Elec

Battery Type 4 (Series-Parallel) 623


Battery Capacity SAE CCA A 1730

ALTERNATOR NEWAGE STAMFORD PI 734

SI Units PRIME STANDBY

Manufacturer NEWAGE STAMFORD


Model (may vary with voltage) PI 734 A or B PI 734 B
Operating Temperature °C 40 27
General Data

Coupling / No. of Bearings Direct / Single Bearing


Phase / Poles / Winding Type 3-Phase / 4-Pole / Winding 311
Power Factor Cos Φ = 0.8
Excitation Separately excited by PMG
Insulation System Class H
AVR Type MX 321
Voltage Regulation ± 0.5%
All specifications and design are subject to change without notice
BCC 1250P-50
BCC 1400S-50
July 2008

STANDARD CONTROL SYSTEM - EXPORT PRODUCTS BC 5110 Digital Auto Start

The standard control system for Export products is BC 5110 (photo), based on the
Deep Sea Electronics DSE5110 Digital Auto Start controller.

This provides for the manual and automatic remote start of the generator with a LCD
digital display of :

▪ Coolant Temperature, with integral high temperature protection


▪ Oil Pressure, with integral low pressure protection
▪ Volts, Amps and Frequency
▪ Engine operating hours
▪ Battery volts

Also featuring :

▪ Automatic cool-down timer function


▪ Emergency Stop button
▪ Ample auxillary inputs/outputs for optional features
▪ Optional - battery charger and door mounted illuminated switch.

CONTROL SYSTEM OPTIONS - EXPORT PRODUCTS

BC 5310 & BC 5320 control systems (just the DSE modules shown here)
provide complete power monitoring and protection facilities.
Compared to BC 5110, addition features include :

▪ Pre-alarms for Low Oil Pressure and High Coolant Temperature


▪ Digital display of kW, kVA and Power Factor
▪ Under/Over Volts protection
▪ Over Current Protection
▪ Full RS485 Telemetry implementation

The BC 5320 provides full AMF functionality with integrated mains monitoring
and generator/mains contactor control.

The BC 5510 & BC 5520 control systems provide the same features as
BC 5310 & BC 5320 respectively, plus :

▪ BC 5510 - Set-to-Set Synchronisation


▪ BC 5520 - Single Set-to-Mains Supply Synchronisation with
integrated mains monitoring

For Multi Set-to-Mains synchronisation, each set requires BC 5510 with the addition
of one mains monitoring panel BC 5560 (not illustrated).
See the Synchronisation Guidelines for further details.

CONTROL SYSTEM OPTIONS - X-RANGE

The X-Range of control systems has been developed to suit larger generating sets (>500kVA)
for the UK and Projects market.

The entry level is Remote Start and provides for the manual and automatic remote start of the
generator with LCD digital display all operating paramaters including :

▪ Coolant temperature with high temperature alarm and shutdown


▪ Oil pressure with low pressure alarm and shutdown
▪ Engine operating hours, battery charge volts and amps
▪ Volts, with Under/Over Volts protection
▪ Amps, with Over Current protection
▪ Frequency, kW, kVA, Power Factor

The Automatic Main Fail variant add full AMF functionality with integrated mains monitoring and
generator/mains breaker control.

The Generator Parallel system makes provision for set-to-set synchronisation, whilst the Mains
Parallel version allows single set-to-mains synchronisation with integrated AMF functionality.

By means of the Multi-Set Mains Parallel system (not illustrated) a number of sets can be
synchronised with each other and the mains supply.

All specifications and design are subject to change without notice