Foam Chamber Model - FC
Foam Chamber Model - FC
TECHNICAL DATA :
MODEL FC
PAGE 1 OF 6
a) Number of Foam Chamber
The number of foam chambers required is determined by
the tank diameter. Where two or more foam chambers are
required, they shall be spaced equally around the tank
periphery and each Foam Chamber shall be sized to deliver Selection Of KV Foam Chamber
foam at an approximately same rate. Please refer graph to SIZE OF FOAM K-FACTOR
select the unit that will provide the required minimum foam CHAMBER
solution application rate at the available operating pressure
50 NB 43.4 to 127
of the Foam Chamber. For minimum number of Foam
Chamber requirement, kindly follow the recommendations 65 NB 115.4 to 254
as per NFPA/OISD/TAC or as per the governmental codes 80 NB 230.9 to 508
or ordinances wherever applicable. 100 NB 461.8 to 1016
b) Minimum Foam Solution Application Rate 150 NB 923.6 to1524.2
The minimum foam solution application rate is the rate at
which the water and foam concentrate in correctly
proportioned ratio should be delivered to the surface of a To select the size of the Foam Chamber use the following
storage tank under protection to control and extinguish the formula
fire. For minimum application rate requirement follow the Q=K P
recommendations as per NFPA/OISD/TAC or governmental Q = Total solution flow in litres per minute.
codes or ordinances wherever applicable. K = Constant for Foam Chamber
P = Inlet pressure in kg/sq.cm.
Testing And Maintenance
Qualified and trained person must commission the system. Example
After few initial successful tesst an authorized person must To find K-Factor
be trained to perform inspection and testing of the system. Q = 300 LPM
It is recommended to carry out physical inspection of the P = 3.5 Kg/sq.cm.
system regularly. The system must be fully tested at least K = 300 ÷ 3.5 = 160.35
once in a year or in accordance with applicable NFPA/OISD/
TAC standards or in accordance with standards of the This K-Factor falls within the range of the Foam Chamber
organization having local jurisdiction. having 65 NB size. Hense 65 NB size of Foam Chamber
should be selected.
Do not turn off the system or any valve to make repair or test The Foam Chamber size may also be selected with the
the system, without placing a roving Fire Patrol in the area help of the graph.
covered by the system. The Patrol should continue until the
system is put back in service. Also inform the local security Calculation example
guard and control alarm station, so as to avoid false alarm. Tank type : Fixed roof storage tank
Tank diameter : 40 meters.
Each system is to be flushed properly. The vapour seal must Foam concentrate to be used : AFFF 3%
be replaced if the system has been operated. Normal testing Pressure at inlet of Foam Chamber : 3.5 kg/sq.cm.
of the chamber can be carried out by removing the cover Flash point of liquid stored in tank : - 27°C.
plate from the top of the chamber. This allows the system
Surface area = d2 ÷ 4 = ( 3.14 X 402.) ÷ 4
to draw a sample of the expanded foam without removing
the vapour seal or disconnecting the Foam Chamber from = 1256 Sq. mts.
the tank. a) Foam solution application rate
= *4.1 LPM /Sq. mts. X Surface area
The air screen is to be inspected periodically for the = 4.1 X 1256
obstruction of air inlet holes. If any obstruction is noticed, = 5150 LPM
remove the same and flush if necessary. *4.1 LPM is as per NFPA-11 ( 5 LPM as per OISD
recommendations ) or it should be as per prevailing
It is recommended to have regular maintenance programme rules of local authority having jurisdiction.
to inspect the Vapour Seal Chamber discharge area and
deflector for possible deposit or obstruction. b) Number of Foam Chamber required for 40 metres
diameter tank = 3 nos. minimum (Reference
NOTE NFPA-11)
A PROVISION IS TO BE MADE FOR PRESSURE GAUGE
MOUNTING AT INLET OF FOAM CHAMBER, WHICH CAN Capacity of Foam Chamber required
BE PLUGGED AFTER SUCCESSFUL COMMISSIONING = 5150 ÷ 3
OF THE SYSTEM. THIS WILL HELP TO ANALYSE THE SYS- = 1717 LPM
TEM WHILE COMMISSIONING.
The K-Factor for flow of 1718 LPM at 3.5 kg./sq.cm.
K = Q ÷ P = 1717 ÷ 3.5
= 918.30
PAGE 2 OF 6
The K-Factor (918.30) falls within the K-Factor of 100 NB
size of the Foam Chamber. Hence three numbers of 100
NB Foam Chamber with 1717 LPM capacity at 3.5 kg./sq.cm
inlet pressure are to be selected.
Note
THE ABOVE ARE THEORETICAL CALCULATIONS. IT IS,
THEREFORE, RECOMENDED THAT SYSTEM DESIGNER
CONSIDERS AN APPROPRIATE FACTOR OF SAFETY
3
= 5154 X X 55
100
= 8505 litres.
Add 5% = 8930 litres.
Note
1. It is recommended to select next higher size of Foam
Chamber when the K-Factor is very much close to upper
limit of the model.
2. For the best performance the inlet pressure at the Foam
Chamber should be 2.8 kg/sq.cm. or higher.
PAGE 3 OF 6
FOAM CHAMBER
PAGE 4 OF 6
PRESSURE VS FLOW PERFORMANCE CHARACTERISTIC
400 2600
2200
300
2000
1800
200 1600
1400
1200
100
1000
800
2 3 4 5 6 7 8 2 3 4 5 6 7 8
INLET PRESSURE (KG./SQ.CM.) INLET PRESSURE (KG./SQ.CM.)
3700
800
3400
FOAM SOLUTION FLOW (LPM)
3100
600
2800
2500
400
2200
200 1900
1600
2 3 4 5 6 7 8 2 3 4 5 6 7 8
INLET PRESSURE ((KG/CM
KG/SQCM)) INLET PRESSURE (KG./SQ.CM)
1400
1200
FOAM SOLUTION FLOW (LPM)
1000
800
600
400
2 3 4 5 6 7 8
INLET PRESSURE (KG./SQ.CM)
SIZE 80NB
PAGE 5 OF 6
TYPICAL FOAM CHAMBER INSTALLATION WITH DEFLECTOR
LIMITED WARRANTY
Products manufactured by K.V. FIRE CHEMICALS (I) PVT.LTD.. are warranted against defects in material and workmanship for a period of Two (2) years from the date of shipment.
KV's obligation under this warranty is limited to replace or repair the products or its parts, which are shown to KV's examination to be in a defective condition attributable to KV. No warranty is given for products
or components which have been subject, to misuse, improper installation, corrosion, wear and tear, improper storage, modification or repaired. If the defect attributable to KV cannot be rectified by repair
or replacement, then KV may elect to refund the purchase price of the equipment in complete discharge of its obligation under this Limited Warranty.
IN NO EVENT SHALL K.V. FIRE CHEMICALS (I) PVT. LTD. BE LIABLE IN CONTRACT, STRICT LIABILITY OR ANY OTHER LEGAL THEORY, FOR INCIDENTAL, IN-DIRECT, SPECIAL OR
CONSEQUENTIAL DAMAGES, INCLUDING DAMAGES. FOR INJURY TO PERSON OR DEATH OR DAMAGE TO PROPERTY AND OR PENALTIES RESULTING FROM ANY PRODUCTS
OR COMPONENT MANUFACTURED OR ASSEMBLED BY KV. THIS IS LIMITED WARRANTY ONLY. KV DISCLAIMS WITH RESPECT TO THE PRODUCTS ALL IMPLIED WARRANTIES OF
MERCHANTABILITY AND ALL IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE. THERE IS NO WARRANTY OF ANY NATURE MADE BY KV BEYOND AS STATED ABOVE.
NOTICE :
The equipment presented in this bulletin is to be installed in accordance with the latest publication standards of NFPA or other similar organisations and also with the provision of government codes
or ordinances wherever applicable.
The information provided by us are to the best of our knowledge and belief, and are general guidelines only. Site handling and installation control is beyond our reach. Hence we give no guarantee for result
and take no liability for damages, loss or penalties whatsoever, resulting from our suggestion, information, recommendation or damages due to our product.