DB Hawells Catalogue
MINI 24
Isolator 28
Changeover Switch 32
Residual Current Circuit Breaker with Overload and Short Circuit Protection (RCBO) 48
Distribution Board 54
2
Miniature Circuit Breaker
Range
6A to 40A - ‘B’ Curve
0.5A to 63A - ‘C’ Curve
0.5A to 63A - ‘D’ Curve
0.5A to 63A for DC Application
Execution
Single Pole (1P)
Single Pole & Neutral (1P+N)
Double Pole (2P)
Three Pole (3P)
Three Pole & Neutral (3P+N)
Four Pole (4P)
Specification
IS 8828 / IEC 60898 / EN 60898
Features
s 0RECISE HAMMER ACTION
s 0LATES !RC #HUTE FOR EFFECTIVE ARC QUENCHING
s ,ONGER ELECTRICAL LIFE
s 7IDE RANGE
s 6ALUE FOR MONEY
s ,OW POWER CONSUMPTION THUS COST EFFECTIVE
Energy saving
Accessories - Auxiliary Switch
- Shunt Trip
3
MIN IA TU RE C IRC U IT B R EAKER
CONSTRUCTION
Miniature Circuit Breakers have precisely formed moulded case & cover of flame retardant high strength thermo-plastic material having high melting
point, low water absorption, high dielectric strength and temperature with stand.
The Switching Mechanism is independent, manual and trip free, i.e., the breaker trips internally even if the operating knob is held in ON position.
The Contact Mechanism comprises of fixed & moving contacts specially designed for reliability, long life and anti-weld properties.
The Arc Extinguishing Device comprises of 15 plates arc chute. The arc under the influence of the magnetic field and arc guide is moved into the
arc chute where it is rapidly split and quenched.
Thermal Operation
The thermal operation provides protection from moderate overloads. Under overload condition, a thermo-metallic element (bimetallic strip) deflects
until it operates a latching mechanism allowing the main contacts to open.
Magnetic Operation
In magnetic operation, large overloads or short circuit current actuates a solenoid causing a plunger to strike the latching mechanism rapidly opening
the main contacts.
INTERNAL VIEW
Outgoing Terminal
Bimetal Carrier
Bimetal Strip
Latch
Arc-chutes Holder
Solenoid
Arc-chutes
Knob / Dolly
Arc-runner
Incoming Terminal
(Dual Termination)
4
MINIA T URE CIRCUI T B R E A KE R
TECHNICAL INFORMATION
Type / Series B C D
Vibration g 3
** 1P Single Pole
1P+N Single Pole Neutral
* Current Ratings - 0.5, 1, 2, 3, 4, 5, 6, 8, 10, 13, 16, 2P Double Pole
20, 25, 32, 40, 50, 63 3P Three Pole
3P+N Three Pole Neutral
4P Four Pole
5
MIN IA TU RE C IRC U IT B R EAKER
CHARACTERISTICS CURVES
TRIPPING CHARACTERISTICS
Based on the Tripping Characteristics, MCBs are available in ‘B’, ‘C’ and ‘D’ curve to suit different types of applications.
‘B’ Curve: for protection of electrical circuits with equipment that does not cause surge current (lighting and distribution circuits). Short circuit release is set to
(3 - 5) In
‘C’ Curve: for protection of electrical circuits with equipment that causes surge current (inductive loads and motor circuits).
‘D’ Curve: for protection of electrical circuits which causes high inrush current, typically 12-15 times the thermal rated current (transformers, X-ray machines
etc.) Short circuit release is set to (10 - 20) In
In a current limiting breaker, the tripping & arc control mechanism are so designed that
under short circuit conditions, the contacts are physically separated and the
electrodynamic forces set up by fault current, assist the extinction in less than half
cycle.
6
MINIA T URE CIRCUI T B R E A KE R
Current Limiting design in itself may not fulfill the requirement of quick breaking
(instantaneous action) mainly due to inertia of the Latch mechanism and
interconnected sequence of operations.
A Hammer directly connected to the plunger strikes the moving contact arm
with a force proportional to the peak current there by forcibly separating the
moving contact from the fixed contact much before the latch mechanism
operates. This further reduces the opening time of the circuit breaker.
Plunger
Hammer
Graph 1 Graph 2
Calculation In / switch = K1 x K2 x In
Example 4 MCBs with In = 10A, and the amb. temp. is 50oC kept with no gap in between
Solution K1 =0.89 (from graph 1)
K2 =0.78 (from graph 2)
In / pole = 0.89 x 0.78 x 10 = 6.94 A
These can be used on different frequencies in supply from 16 2/ 3 - 60 Hz without any deration.
For higher frequencies, normal MCBs can be used with a multiplication factor which shall only affect its magnetic trip current.
Supply AC DC
Frequency 100Hz 200Hz 400Hz
Multiplication Factor 1.1 1.2 1.5 1.5
7
MIN IA TU RE C IRC U IT B R EAKER
L E T T H R O U G H E N E R G Y I 2T
COLD RESISTANCE The power loss value declared are at rated current.
& POWER LOSS DETAILS Rated Current Cold Resistance Power Loss per Pole
IN (A) RI (m) Pv (W)
1 1178.00 1.3
2 281.00 1.5
4 92.00 2.2
6 16.55 0.7
10 11.68 1.4
13 10.10 1.7
16 8.00 2.2
20 5.25 2.5
25 3.78 3.1
32 2.57 3.4
40 1.94 3.9
63 1.40 7.3
8
MINIA T URE CIRCUI T B R E A KE R
DC APPLICATION
MCBs for DC application are specially designed to meet tough arc quenching
conditions. While selecting circuit breaker for DC applications following parameters
have to be taken into consideration.
The rating and normal running temperature of the MCB are unaffected by DC. The MCB
can be selected using the thermal section of the standard time / current curves .
Vb
Isc =
Rb
The time constant is usually given in milliseconds (ms.). Ideally, DC circuits would be mainly resistive (i.e. a low number), as inductive circuits produce a back
emf when the current suddenly falls. This in turn tends to prolong arcing during switching operations, and so reduce contact life.
Circuit Voltage
The voltage of the circuit is dependent upon the power supply. The lower the voltage the easier switching operations will be, but the voltage makes no difference
to the running of the MCBs.
Contact life can be significantly increased by reducing the voltage, drop accross each pole. This can be achieved by wiring poles in series.
MCBs have been successfully tested on DC and can be used under the following conditions :
Voltage 12-130V
9
MIN IA TU RE C IRC U IT B R EAKER
ACCESSORIES
AUXILIARY CONTACT
SHUNT TRIP
Attachment used for remote tripping.
Outgoing
D1 1. To trip the Circuit Breaker through Shunt Trip Coil, 70% to 110% of the rated voltage is
to be applied across D1 & D2
2. The Shunt Trip coil is short time rated and it trips the breaker instantaneously.
S.T. (i.e., continuous duty not required)
240V
Incoming Connection
10
MINIA T URE CIRCUI T B R E A KE R
DISCRIMINATION DATA
MCB MCB Upstream C Curves
Downstream
C curve 10A 13A 16A 20A 25A 32A 40A 50A 63A
0.5 to 5A 50 65 80 100 125 160 200 250 315
6A 65 80 100 125 160 200 250 315
10A 100 125 160 200 250 315
13A 125 160 200 250 315
16A 160 200 250 315
20A 200 250 315
25A 250 315
32A 315
40A
50A
MCB MCCBs
Downstream Upstream
C curve 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A 160A 200 250A 320A 400A 500A 630A 800A 1000A 1250A 1600A
0.5 to 6A 1100 1200 1400 1700 2000 2500 3400 4800 5800 6700 T T T T T T T T T T T
10A - 1100 1200 1400 1700 2100 2500 3000 3500 4300 T T T T T T T T T T T
16A - - - 1300 1600 1900 2100 2400 2700 3200 8300 T T T T T T T T T T
20A - - - - 1600 1900 2100 2400 2700 2500 8300 T T T T T T T T T T
25A - - - - - 1700 1800 2000 2200 2500 5400 8700 T T T T T T T T T
32A - - - - - - 1800 2000 2200 2500 5400 8700 T T T T T T T T T
40A - - - - - - - 1500 1700 2000 4300 7000 T T T T T T T T T
50A - - - - - - - - 1300 1500 3600 5900 9000 T T T T T T T T
63A - - - - - - - - - 1100 2800 5200 8200 T T T T T T T T
Prospective Fault Levels to which selectivity is achieved ( T = Total Selectivity )
11
MIN IA TU RE C IRC U IT B R EAKER
SELECTION CHART
For Household Applications Rating of MCBs for specified no. of fittings
(“B” Series MCBs)
Lamp Number of Lamps Rating (A)
Appliances Capacity / Current Rating Type of MCB
watt (Load) of MCB (Watt)
(240V~ 1ph)
20W 8 1
Air Conditioner 1.0 tonnes 10A “C” series
1.5 tonnes 16A “C” series 12 1.5
2.0 tonnes 20A “C” series
40W 2 0.5
Refrigerator 165 litres 3A “C” series
350 litres 4A “C” series 10 2
12 2.5
Oven cum Griller 4500W 32A “B” series
1750W 10A “B” series
60W 1 0.5
Oven only 750W 6A “B” series 4 1.5
Hot Plate only 2000W 10A “B” series
8 3
Room Heater 1000W 6A “B” series
2000W 10A “B” series 12 4
Washing Machine 300W 2A “C” series
80W 1 0.5
Washing Machine
(with heater) 1300W 8A “C” series 2 1
5 2
Water Heater
(storage/instant) 1000W 6A “B” series 8 4
2000W 10A “B” series 12 5
3000W 16A “B” series
6000W 32A “B” series 100W 1 1
Electric iron 750W 6A “B” series 2 1.5
1250W 8A “B” series 4 2.5
Auto Toaster
(2 slices) 1200W 8A “B” series “B” series MCB is used for all Lighting Applications
Electric Kettle 1500W 10A “B” series
3X240V
Note : One lighting circuit can have upto 800W or upto 10 lighting points
One power circuit can have upto 2000W or 1 power points
12
MINIA T URE CIRCUI T B R E A KE R
SINGLE POLE (1P) Current ‘B’ Curve ‘C’ Curve ‘D’ Curve ‘DC’ MCB.*
Rating (A) Cat No. Cat No. Cat No. Cat No.
0.5 DHMCCSPF0x5 DHMCDSPF0x5 DHMCESPF0x50013
1 DHMCCSPF001 DHMCDSPF001 DHMCESPF0010013
2 DHMCCSPF002 DHMCDSPF002 DHMCESPF0020013
3 DHMCCSPF003 DHMCDSPF003 DHMCESPF0030013
4 DHMCCSPF004 DHMCDSPF004 DHMCESPF0040013
5 DHMCCSPF005 DHMCDSPF005 DHMCESPF0050013
6 DHMCBSPF006 DHMCCSPF006 DHMCDSPF006 DHMCESPF0060013
10 DHMCBSPF010 DHMCCSPF010 DHMCDSPF010 DHMCESPF0100013
16 DHMCBSPF016 DHMCCSPF016 DHMCDSPF016 DHMCESPF0160013
20 DHMCBSPF020 DHMCCSPF020 DHMCDSPF020 DHMCESPF0200013
32 DHMCBSPF032 DHMCCSPF032 DHMCDSPF032 DHMCESPF0320013
35 DHMCESPF0350013
40 DHMCBSPF040 DHMCCSPF040 DHMCDSPF040 DHMCESPF0400013
50 DHMCCSPF050 DHMCDSPF050 DHMCESPF0500013
63 DHMCCSPF063 DHMCDSPF063 DHMCESPF0630013
DOUBLE POLE (2P) Current ‘C’ Curve ‘D’ Curve ‘DC’ MCB.*
Rating (A) Cat No. Cat No. Cat No.
0.5 DHMCCDPF0x5 DHMCDDPF0x5 DHMCEDPF0x50013
1 DHMCCDPF001 DHMCDDPF001 DHMCRDPF0010013
2 DHMCCDPF002 DHMCDDPF002 DHMCRDPF0020013
3 DHMCCDPF003 DHMCDDPF003 DHMCRDPF0030013
4 DHMCCDPF004 DHMCDDPF004 DHMCRDPF0040013
5 DHMCCDPF005 DHMCDDPF005 DHMCRDPF0050013
6 DHMCCDPF006 DHMCDDPF006 DHMCRDPF0060013
10 DHMCCDPF010 DHMCDDPF010 DHMCRDPF0100013
16 DHMCCDPF016 DHMCDDPF016 DHMCRDPF0160013
20 DHMCCDPF020 DHMCDDPF020 DHMCRDPF0200013
32 DHMCCDPF032 DHMCDDPF032 DHMCRDPF0320013
35 DHMCRDPF0350013
40 DHMCCDPF040 DHMCDDPF040 DHMCRDPF0400013
50 DHMCCDPF050 DHMCDDPF050 DHMCRDPF0500013
63 DHMCCDPF063 DHMCDDPF063 DHMCRDPF0630013
*MCB suitable for DC application.
13
MIN IA TU RE C IRC U IT B R EAKER
THREE POLE (3P) Current ‘B’ Curve ‘C’ Curve ‘D’ Curve ‘DC’ MCB.*
Rating (A) Cat No. Cat No. Cat No. Cat No.
0.5 DHMCCTPF0x5 DHMCDTPF0x5 DHMCDTPF0x5
1 DHMCCTPF001 DHMCDTPF001 DHMCDTPF001
2 DHMCCTPF002 DHMCDTPF002 DHMCDTPF002
3 DHMCCTPF003 DHMCDTPF003 DHMCDTPF003
4 DHMCCTPF004 DHMCDTPF004 DHMCDTPF004
5 DHMCCTPF005 DHMCDTPF005 DHMCDTPF005
6 DHMCCTPF006 DHMCDTPF006 DHMCDTPF006
10 DHMCCTPF010 DHMCDTPF010 DHMCDTPF010
16 DHMCCTPF016 DHMCDTPF016 DHMCDTPF016
20 DHMCCTPF020 DHMCDTPF020 DHMCDTPF020
32 DHMCCTPF032 DHMCDTPF032 DHMCDTPF032
35
40 DHMCCTPF040 DHMCDTPF040 DHMCDTPF040
50 DHMCCTPF050 DHMCDTPF050 DHMCDTPF050
63 DHMCCTPF063 DHMCDTPF063 DHMCDTPF063
14
MINIA T URE CIRCUI T B R E A KE R
RAILWAY MCB
ACCESSORIES
SHUNT TRIP
AUXILIARY CONTACT
15
MIN IA TU RE C IRC U IT B R EAKER
INDICATOR LIGHTS
Havells Indicator Light is a new addition to the product range and can be used in both building and industrial installations. Indicator lights are designed for signaling
the incoming supply.
Volts Colour Cat. No. Colour Lens Cat. No. Neon Bulb Cat. No.
240 V Red DHMCYSPX000 Red DCPTMMCX043 DCELDMCL001
240 V Amber DHMCXSPX000 Amber DCPTMMCX051 DCELDMCL001
240 V Blue DHMCVSPX000 Blue DCPTMMCX049 DCELDMCL001
240 V Green DHMCZSPX000 Green DCPTMMCX050 DCELDMCL001
240 V Clear DHMCWSPX000 Clear DCPTMMCX052 DCELDMCL001
APPLICATIONS
z Distribution Box
z Kiosks
z Load Line DB
z Meter Boxes
z Testing Panels
z Switch Boards
z MIMIC Panels
z Control panels
FEATURES
z Modular Design enables Indicator Lamp replacement with lens of different varieties
16
MINIA T URE CIRCUI T B R E A KE R
TECHNICAL INFORMATION
IEC 60947-5-1
Frequency 50 Hz
Light Permanent
Degree of Protection IP 20
z Colour Cap
z Old Lamp
17
18
Miniature Circuit Breaker
(80 - 125)
Execution
Single Pole (1P)
Three Pole (3P)
Three Pole & Neutral (3P+N)
Specification
IS 8828-1996 / IEC 60898 - 2002
Features
s 5NIFORM K! BREAKING CAPACITY FOR THE ENTIRE RANGE
s #ONTROL LEVER COLOUR UNAMBIGUOUSLY INDICATES THE
rated current In of the device
In (A) Colour
80 (Silver)
100 (Red)
125 (Yellow)
s 0OSITION INDICATING DEVICE OPTICALLY THE OPERATING
status of the device Indicator colour device status
(Red) ON
(Green) OFF
s 4EST BUTTON FOR VERIlCATION OF THE TIPPING MECHANISM
function
19
MIN IA TU RE C IRC U IT B R EAKER
(80- 125A MCB )
TECHNICAL INFORMATION
Type/Series C
Vibration g 3
20
MINIA T URE CIRCU I T B R E A K E R
(8 0-125A M CB)
21
MIN IA TU RE C IRC U IT B R EAKER
(80- 125A MCB )
TECHNICAL INFORMATION
SHUNT TRIP Attachment used for Remote Tripping Voltage Cat. No.
Standard conformity : IS: 13947 - 1: 93 24 ac M0AST024
Rated Current (ln) A : 80 - 125 48 ac M0AST048
Rated Voltage : 110 ac M0AST110
ac : 24, 48, 110, 230, 400 230 ac M0AST230
dc : 24, 48, 110, 220, 440 400 ac M0AST400
Frequency Hz : 50 24 dc M0DST024
Operating Voltage : 70% - 110% of rated voltage 48 dc M0DST048
Impulse Voltage kV : 4 110 dc M0DST110
Electrical endurance : 10000 operations 220 dc M0DST220
Terminal Capacity mm2 : max 2.5 440 dc
M0DST440
Protection Class : IP-20 as per IS-2147 / IEC-60529
Mounting : To be coupled on Left side of MCB
Impulse Voltage kV : 4
22
MINIA T URE CIRCU I T B R E A K E R
(8 0-125A M CB)
ACCESSORIES INSTALLATION
1. Switch on both the block and the device. 1. Switch on both the block and the device.
2. Insert metallic shaft from the right onto the device in such a control 2. Insert metallic shaft from the right onto the device in such a control lever and
lever and the plastic shaft into the block switching system hole. the plastic shaft into the block switching system hole.
3. Slide the block from the right onto the device in such a way that one 3. Slide the block from the right onto the device in such a way that one shaft
shaft interconnects control levers and the other interconnects the interconnects control levers and the other interconnects the switching
switching systems. systems.
4. Press the block to the device and click the side fixing latches of the 4. Press the block to the device and click the side fixing latches of the block in
block in the device recess. the device recess.
5. Check correct function by switching. 5. Check correct function by switching.
TRIPPING CHARACTERISTICS
‘C’ Curve : for protection of electric circuits with equipment that causes surge current (inductive and motor circuits)
Short circuit release is set to 5 - 10 ln
23
24
Mini MCB
Range
6A, 10A, 16A, 20A, 25A, 32A
Execution
Single Pole (1P)
Specification
IS 8828-1996
Features
s 0ROTECTION AGAINST OVERLOAD SHORT CIRCUIT IN SWITCH
board itself
s 3UITABLE FOR BOTH $%3"