Download as pdf or txt
Download as pdf or txt
You are on page 1of 114

Emerson FB1200 Flow Computer Instruction Manual

D301782X012
July 2021

Emerson FB1200 Flow Computer


Instruction Manual

Remote Automation Solutions


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Device Safety Considerations


 Reading these Instructions
Before operating the device, read these instructions carefully and understand their safety implications. In some situations,
improperly using this device may result in damage or injury. Keep this manual in a convenient location for future reference.
Note that these instructions may not cover all details or variations in equipment or cover every possible situation regarding
installation, operation, or maintenance. Should problems arise that are not covered sufficiently in the text, immediately
contact Customer Support for further information.

 Protecting Operating Processes


A failure of this device – for whatever reason -- may leave an operating process without appropriate protection and could result
in possible damage to property or injury to persons. To protect against this, you should review the need for additional backup
equipment or provide alternate means of protection (such as alarm devices, output limiting, fail-safe valves, relief valves,
emergency shutoffs, emergency switches, etc.). Contact Remote Automation Solutions for additional information.

 Returning Equipment
If you need to return any equipment to Remote Automation Solutions, it is your responsibility to ensure that the equipment
has been cleaned to safe levels, as defined and/or determined by applicable federal, state and/or local law regulations or
codes. You also agree to indemnify Remote Automation Solutions and hold Remote Automation Solutions harmless from any
liability or damage which Remote Automation Solutions may incur or suffer due to your failure to ensure device cleanliness.

 Grounding Equipment
Ground metal enclosures and exposed metal parts of electrical instruments in accordance with OSHA rules and regulations as
specified in Design Safety Standards for Electrical Systems, 29 CFR, Part 1910, Subpart S, dated: April 16, 1981 (OSHA rulings are
in agreement with the National Electrical Code). You must also ground mechanical or pneumatic instruments that include
electrically operated devices such as lights, switches, relays, alarms, or chart drives.
Important: Complying with the codes and regulations of authorities having jurisdiction is essential to ensuring personnel
safety. The guidelines and recommendations in this manual are intended to meet or exceed applicable codes and regulations.
If differences occur between this manual and the codes and regulations of authorities having jurisdiction, those codes and
regulations must take precedence.

 Protecting from Electrostatic Discharge (ESD)


This device contains sensitive electronic components which be damaged by exposure to an ESD voltage. Depending on the
magnitude and duration of the ESD, it can result in erratic operation or complete failure of the equipment. Ensure that you
correctly care for and handle ESD-sensitive components.

System Training
A well-trained workforce is critical to the success of your operation. Knowing how to correctly install, configure, program,
calibrate, and trouble-shoot your Emerson equipment provides your engineers and technicians with the skills and confidence
to optimize your investment. Remote Automation Solutions offers a variety of ways for your personnel to acquire essential
system expertise. Our full-time professional instructors can conduct classroom training at several of our corporate offices, at
your site, or even at your regional Emerson office. You can also receive the same quality training via our live, interactive
Emerson Virtual Classroom and save on travel costs. For our complete schedule and further information, contact the Remote
Automation Solutions Training Department at 800-338-8158 or email us at [email protected].

Ethernet Connectivity
This automation device is intended to be used in an Ethernet network which does not have public access. The inclusion of this
device in a publicly accessible Ethernet-based network is not recommended.

ii Contents
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Contents
Section 1: Introduction 1
1.1 Safety Labels ........................................................................................................................ 3
1.2 Features ............................................................................................................................... 3
1.3 FB1200 Flow Computer Models ............................................................................................ 4
1.3.1 FB1200 Flow Computer (with Multi-variable or Static Pressure Sensor) ..................... 4
1.3.2 FB1200 Flow Computer (without Integral Sensor) .................................................... 5
1.4 Central Processing Unit (CPU) ............................................................................................... 5
1.4.1 Memory ................................................................................................................... 5
1.5 Explosion-proof Enclosure .................................................................................................... 5
1.5.1 Physical Security ....................................................................................................... 6
1.6 I/O........................................................................................................................................ 7
1.7 Power Options...................................................................................................................... 7
1.8 Communications .................................................................................................................. 8
1.9 Human-Machine Interface (HMI) Module .............................................................................. 8
1.10 FBxWifi™ Communications ........................................................................................ 9
1.11 Software Tools ......................................................................................................... 10
1.12 RoHS2 Compliance .................................................................................................. 10

Section 2: Installation 11
2.1 Hazardous Locations .......................................................................................................... 11
2.2 Environmental Specifications ............................................................................................. 11
2.3 Required Tools ................................................................................................................... 12
2.4 Site Considerations ............................................................................................................ 12
2.5 General Wiring Guidelines .................................................................................................. 15
2.6 Front or Rear End Caps ....................................................................................................... 15
2.6.1 Removing/Replacing Retaining Clamp on End Caps ................................................ 16
2.6.2 Removing the Front or Rear End Caps ..................................................................... 17
2.6.3 Replacing the Front or Rear End Caps...................................................................... 18
2.7 Mounting the Enclosure ..................................................................................................... 18
2.7.1 Bolting Considerations ........................................................................................... 18
2.7.2 O-rings with Flange Adapters.................................................................................. 20
2.7.3 Direct Mount .......................................................................................................... 21
2.7.4 Indirect Mount ....................................................................................................... 21
2.7.5 Rotating the Housing ............................................................................................. 24
2.8 Grounding the Device ........................................................................................................ 26
2.9 Terminal Plate .................................................................................................................... 27
2.10 Power Modes ........................................................................................................... 28
2.10.1 Low Power Mode .................................................................................................. 28
2.10.2 Standard Power Mode .......................................................................................... 30
2.10.3 Notes on Battery Life ............................................................................................ 31
2.11 Connecting Power.................................................................................................... 31
2.11.1 Connecting DC Power .......................................................................................... 32
2.11.2 Connecting Battery Power .................................................................................... 33
2.12 Installing the Optional Solar Panel ............................................................................ 34
2.12.1 Attaching Mounting Hardware to the Solar Panel ................................................. 34
2.12.2 Mounting the Solar Panel (Integral Mount) ........................................................... 36
2.12.3 Mounting the Solar Panel (Remote Mount) ........................................................... 38
2.12.4 Connecting Solar Power ....................................................................................... 39
2.12.5 Adjusting the Optional Solar Panel Tilt Angle ........................................................ 40

Contents iii
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021
2.13 Connecting Communication Ports ........................................................................... 41
2.13.1 Connecting to COM1 ............................................................................................ 41
2.13.2 Connecting to COM2 and COM3 .......................................................................... 44
2.13.3 Ethernet Port ........................................................................................................ 49

Section 3: I/O Configuration and Wiring 51


3.1 Analog Inputs ..................................................................................................................... 55
3.1.1 AI Wiring ................................................................................................................ 55
3.2 Analog Outputs .................................................................................................................. 59
3.2.1 AO Wiring .............................................................................................................. 59
3.3 Digital Inputs ...................................................................................................................... 61
3.3.1 DI Wiring ................................................................................................................ 62
3.4 Digital Outputs ................................................................................................................... 64
3.4.1 DO Wiring .............................................................................................................. 65
3.5 Pulse Inputs ........................................................................................................................ 67
3.5.1 PI Wiring ................................................................................................................ 67
3.6 Connecting the RTD ........................................................................................................... 69
3.7 Connecting a Rosemount 4088B Transmitter for Use in a Second Meter Run ...................... 72

Section 4: Operation 75
4.1 Powering Up/Powering Down the Device ........................................................................... 75
4.2 Establishing Communications ............................................................................................ 75
4.2.1 Communicating with the SCADA Host .................................................................... 75
4.2.2 Communicating with a Laptop Using One of the Serial Ports ................................... 76
4.2.3 Communicating with a Laptop Using Ethernet ........................................................ 76
4.2.4 Communicating with a Laptop Wirelessly with FBxWifi ........................................... 77
4.3 Communicating using the HMI Module .............................................................................. 78

Section 5. Service and Troubleshooting 81


5.1. Returning the Unit for Repairs ............................................................................................ 82
5.2. Interpreting the Status LEDs ............................................................................................... 83
5.3. Switch and Buttons ............................................................................................................ 85
5.4. Removing/Replacing the HMI Module ................................................................................ 85
5.5. Replacing the Main Battery Pack ......................................................................................... 86
5.6. Removing/Replacing the SRAM Battery .............................................................................. 88
5.7. Upgrading System Firmware .............................................................................................. 90

Appendix A: Special Instructions for Class I Division 2 Locations 93

Appendix B: Special Instructions for Class I Division 1 Locations 97

Appendix C: ATEX Non-Sparking Zone 2 Certifications 101

Appendix D: ATEX Flame-Proof Zone 1 Certifications 103

Index 105

iv Contents
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Section 1: Introduction
This section covers the following topics:

 Safety Labels
 Features
 FB1200 Flow Computer Models
 Central Processing Unit (CPU)
 Explosion-proof Enclosure
 I/O
 Power Options
 Communications
 Human-Machine Interface (HMI) Module
 FBxWifi™ Communications
 Software Tools
 RoHS2 Compliance

The Emerson FB1200 Flow Computer supports measurement for one or two meter runs. This
manual describes how to install and configure the Emerson FB1200 Flow Computer hardware.

For information on using the FBxConnect™ configuration software, see the online help that
accompanies FBxConnect.

Introduction 1
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 1-1: FB1200 Flow Computer

1 HMI module
2 Front end cap (cover)
3 Data plate
4 Rear end cap (cover)
5 Conduit fittings
6 Enclosure
7 Sensor module

2 Introduction
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

1.1 Safety Labels


This product may display safety label(s) to identify potential hazards. The same types of notices
appear within the documentation. Whenever you see an exclamation point (!) enclosed within a
triangle (shown to the left), consult the documentation for additional safety information about the
hazard and how to avoid it. The labels used are :

DANGER
MAY CAUSE DEATH
Observe all precautionary signs posted on the equipment.
Failure to do so may result in death or serious injury to personnel.

WARNING
DANGER TO PERSONNEL AND EQUIPMENT
Observe all precautionary signs posted on the equipment.
Failure to do so may result in injury to personnel or cause damage to the equipment.

CAUTION
MAY CAUSE INJURY TO PERSONNEL OR DAMAGE EQUIPMENT
Observe all precautionary signs posted on the equipment.
Failure to do so may result in injury to personnel or cause damage to the equipment.

SAFETY FIRST
General instructions and safety reminders.

1.2 Features
The FB1200 Flow Computer includes the following key features:
 Enclosure suitable for use in Class I Division 1 explosion proof and Ex db Zone 1 flame- proof
environments
 Enclosure suitable for use in Class I Division 2 non-incendive and Ex nA Zone 2 non- sparking
environments
 Integral multi-variable sensor for measurement of Pressure (P) and Differential Pressure (DP)
 Connections for customer-supplied resistance temperature detector (RTD) for measurement
of temperature (T)
 Support for a second meter run through communication with a separate external transmitter
 Base I/O consists of two on-board channels you can individually configure as either digital
input (DI), digital output (DO) or pulse input (PI) and two on-board I/O channels you can
Introduction 3
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021
individually configure as either analog input (AI) or analog output (AO). Optional 6-channel
expansion I/O board available
 Power from a DC power supply, or an optional lead acid battery/solar panel combination
 Serial communication options for RS-232, RS-485 (2-wire), and RS-485/422 (4-wire).
 Ethernet
 HMI module with optional display and back light for local operator interaction
 Optional Wi-Fi® transceiver (802.11 b/g) for field technician to access the flow computer
from a laptop without physical cable connection.
 Application software supports AGA3, AGA8, ISO 5167, ISO 6976, and API 21.1 calculations in
U.S., metric, or other natural gas standard units.
 Application software optionally supports API Chapter 11.1, API Chapter 12.2, API 20.1, and
API 21.2 calculations in U.S., metric, or other hydrocarbon liquid standard units.

1.3 FB1200 Flow Computer Models


You can purchase the FB1200 Flow Computer with or without integrated sensors.

1.3.1 FB1200 Flow Computer (with Multi-variable or Static Pressure


Sensor)
The flow computer with sensors has either a multi-variable sensor module or a static pressure
sensor:

Figure 1-2: FB1200 Flow Computer – Multivariable (Left); Static Pressure (Right)

4 Introduction
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

1.3.2 FB1200 Flow Computer (without Integral Sensor)


The no integral sensor version includes no sensor module. In this case the process variable data
used in flow computer calculations comes from external devices and enters the device through the
serial ports or I/O channels.

Figure 1-3: FB1200 Flow Computer (No Integral Sensor Version)

1.4 Central Processing Unit (CPU)


The flow computer’s CPU is a NXP® Kinetis® K61 series CPU with an ARM® Cortex® M4 processor
that operates at 4 MHz to 60 MHz depending on the power mode. The CPU runs the Micrium
operating system.

1.4.1 Memory
The flow computer includes both static and flash memory.

Table 1-1: Memory

Memory Usage

8 MB SRAM Holds in-use configuration, current state of all variables

Holds firmware image, historical logs, configuration backup (if saved to flash),
128 MB Flash
and the executing program

1.5 Explosion-proof Enclosure


The FB1200 Flow Computer includes an explosion-proof enclosure made of either aluminum or
stainless steel. The enclosure consists of the main housing, two threaded covers, and four conduit
entry points.

Introduction 5
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021
The four conduit entry points are ¾ in NPT pipe threaded holes that permit entry of field conduit
for I/O and communication wiring. ATEX installations use a ¾ in NPT to M20 thread reducer.
Unused apertures shall be closed with suitable blanking elements.

The FB1200 Flow Computer can operate in an unprotected outdoor environment. Wiring for I/O,
communications, and power enters the enclosure through the four conduit fittings with
appropriate protective seals and connects to the terminal plate.

The front end cap (cover) provides a viewing window for the HMI module. You can access the
terminal plate by removing the rear end cap (cover).

The FB1200 Flow Computer has North American certification for Class I Division 1 Groups C and D
(explosion proof) and Class I Division 2 Groups A, B, C and D (non-incendive) hazardous locations or
non-hazardous locations. See Appendix A and Appendix B for more information.

The FB1200 Flow Computer has European certification for EExd Zone 1 (flame proof) and EExd
Zone 2 (non-sparking) hazardous locations or non-hazardous locations. See Appendix C and
Appendix D for more information.

Details on certification information are included on the data plate screwed to the top of the
enclosure.

1.5.1 Physical Security


The flow computer end caps include retaining clamps for ATEX/IEC applications. In addition, if local
regulations require it, you can wire a tamper-resistant seal using the tie holes located in the front
and rear end caps, and in the coupling screws.

Figure 1-4: Retaining Clamps and Tie Holes for Tamper-resistant Seals

1 Retaining clamp (For ATEX & IEC approved products only)


2 Tie holes in end caps
3 Tie holes in coupling screws

6 Introduction
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

1.6 I/O
The flow computer comes with base I/O from both the CPU and the built-in multi-variable (MV)
sensor. Base I/O consists of:
 Pressure (P) input from the MV sensor, differential pressure (DP) input from the MV sensor,
connections for temperature (T) input from a customer-supplied RTD or a single static
pressure sensor.
 Two on-board I/O channels that you can individually configure as digital input (DI), digital
output (DO), or pulse input (PI)
 Two on-board I/O channels that you can individually configure as either analog input (AI) or
analog output (AO)
An optional 6-channel expansion I/O board includes:
 Four I/O channels that you can individually configure as digital inputs (DI), digital outputs
(DO), or pulse inputs (PI)
 Two I/O channels that you can individually configure as either analog inputs (AI), or analog
outputs (AO)

Table 1-2: FB1200 Flow Computer I/O Configurations

FB1200 Flow Computer FB1200 Flow Computer


without optional I/O with optional I/O

MV (P, DP, T) or Static Pressure Sensor MV (P, DP, T) or Static Pressure Sensor

2 DI/DO/PI channels 6 DI/DO/PI channels (4 of these reside on the 6-channel


expansion I/O board)

2 AI/AO channels 4 AI/AO channels (these reside on the 6-channel


expansion I/O board)

1.7 Power Options


You can power the flow computer using an external DC input, an internal battery, or an internal
rechargeable battery connected to a solar panel.

Important
Use only batteries supplied with the flow computer or sold by Emerson Remote Automation
Solutions as spare parts for this flow computer. If you substitute a battery you obtain elsewhere you
void your certification unless it is the identical part from the same manufacturer as that supplied
with the flow computer from Emerson.

Introduction 7
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Table 1-3: Power Options

Option Usage

External DC Power
5.7 Vdc to 30 Vdc external supply (Max power at 10 watts)
Supply

Lead Acid Battery Pack  6.0 Vdc


 4.5Ah
 Not suitable with ATEX or IECEx applications
 Can be optionally charged by a 6-watt solar panel

1.8 Communications
The flow computer includes three serial communication ports and one Ethernet port. The serial
ports allow communication using DNP3, Modbus, BSAP, and ROC protocols. The Ethernet port is an
RJ-45 connector. The Ethernet port supports a maximum of six concurrent TCP connections
(sockets).

Table 1-4: Serial Ports

Port Type Use

COM1  Serial communications RS-232, RS-485 (2-wire), RS-485/422 (4-wire)


 Software-selectable for RS-232, RS- communication to host or other devices. 4-wire
485 (2-wire), RS-485/422 (4-wire) used with external radio.
operation
 4-wire

COM2  Serial communications RS-232 or RS-485 (2-wire) communication to


 Software-selectable for RS-232, or host or other devices.
RS-485 (2-wire) operation
 2-wire

COM3  Serial communications RS-232 or RS-485 (2-wire) communication to


 Software-selectable for RS-232, or host or other devices.
RS-485 (2-wire) operation
 2-wire

1.9 Human-Machine Interface (HMI) Module


The flow computer includes an HMI module with an optional liquid crystal display (LCD) for local
operator access to the device. The LCD, if present, shows a series of menus that sequentially display
the current values of particular process variables. A configuration parameter in FBxConnect
determines whether you must log in first to view the menus. If required, you log in by selecting
alphanumeric characters by scrolling through a list until you select the correct character.

The HMI module includes four LEDs to provide status information. Units with the display include
four infrared (IR) buttons for operator interaction.

8 Introduction
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021
To conserve power, the HMI module enters sleep mode after a period of inactivity. Sleep mode
disables FBxWifi communication. In FBxConnect, you can configure the number of minutes of
inactivity triggering sleep mode through the LCD Sleep Time parameter. Setting this parameter to
0 disables sleep mode which keeps the HMI module on but uses significantly more power.

Figure 1-5: HMI Module with LCD

Figure 1-6: HMI Module without LCD

Note
If your flow computer does not include the LCD option, you still have the status LEDs and a single IR
button for waking up the device (shown in Figure 1-6).

1.10 FBxWifi™ Communications


The flow computer has an optional Wi-Fi® transceiver (FBxWifi) that enables you to connect via a
laptop or tablet from some small distance away.

This capability allows an operator to potentially remain outside the hazardous location and still
communicate with the flow computer. The operator's laptop must have Wi-Fi capability, line-of-
sight access to the HMI module, and must be loaded with FBxConnect configuration software.
Once connected, the operator can view process values, edit configuration parameters, and collect
logs.

Introduction 9
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Note
The FBxWifi electronics reside inside the HMI module. The HMI module must be awake to use
FBxWifi communications You can wake it up manually by holding a finger against the front cover
glass over the Hold to Wake button (the left-most button) for typically from five to ten seconds.

1.11 Software Tools


The FBxConnect configuration software provides a series of wizards that allow you to perform
configuration activities for the flow computer. You connect a PC running the FBxConnect
configuration software to the flow computer using one of the communication ports or through a
wireless connection. You can then:

 Set parameters within your application


 Configure I/O channels
 Specify the serial communication method for a port (RS-232 to RS-485) as needed
 View or collect audit trail information such as alarm, event, or historical logs
 Update system firmware

1.12 RoHS2 Compliance


Device without Integral MVS or SP Sensor:
RoHS (2) EU Directive 2011/65/EU

Device with Integral MVS or SP Sensor:

RoHS (2) EU Directive 2011/65/EU: This product may be considered out-of-scope when used for
the intended design purpose in a Large Scale Fixed Installation (LSFI).

Consult https://www.emerson.com/compliance for up-to-date product information.

10 Introduction
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Section 2: Installation
This section covers the following topics:

 Hazardous Locations
 Environmental Specifications
 Required Tools
 Site Considerations
 General Wiring Guidelines
 Front or Rear End caps
 Mounting the Enclosure
 Grounding the Device
 Terminal Plate
 Power Modes
 Connecting Power
 Installing the Optional Solar Panel
 Connecting Communication Ports

The flow computer ships from the factory fully assembled, except for the optional solar panel
assembly.

2.1 Hazardous Locations


The housing for the FB1200 Flow Computer is an explosion-proof case designed to operate in
hazardous locations.

For North America the FB1200 Flow Computer has certifications for Class I, Division 1 (Groups C &
D) explosion-proof, Class I Division 2 (Groups A, B, C & D) non-incendive, and non-hazardous
locations only. Appendix A contains special information for Class I Division 2 installations; Appendix B
contains special information for Class I Division 1 installations.

For Europe the FB1200 Flow Computer has certifications for Ex db Zone 1 flame-proof and for Ex nA
Zone 2 non-sparking installations and non-hazardous locations only. Appendix C contains special
information for Ex nA Zone 2 installations; Appendix D contains special information for Ex db Zone 1
installations.

All certifications are listed on the data plate located on the top of the device.

2.2 Environmental Specifications


This section summarizes the environmental specifications for the device. For full details, refer to
the product data sheet FB1200 Flow Computer (D301790X012).

Installation 11
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Table 2-1: Environmental Specifications

Specification Range

Ambient Temperature -40°C to +80 °C (-40 °F to +176 °F) - no battery, C1D1/C1D2


-40°C to +80 °C (-40°F to +176 °F) – lead acid battery, C1D1/C1D2
-40°C to +80 °C (-40 °F to +176 °F) – no battery, ATEX/IEC Ex db
-40°C to +80 °C (-40 °F to +176 °F) – no battery, ATEX/IEC Ex nA

Maximum Process
120 °C (248 °F)
Connection Temperature

Humidity 5% to 95% non-condensing

Vibration 2g over 10 to 150 Hz; 1g over 150 to 200 Hz

2.3 Required Tools


Certain tools and equipment are required for installing and servicing the flow computer.

Table 2-2: Required Tools

Tool Use

Torque wrench For bolting/mounting the flow computer

2.5 mm hexagonal wrench For manipulating rotation set screw

3 mm hexagonal wrench For screw for M4 x 0.7 end cap retaining clamp
(ATEX required)

9/16 in hexagonal wrench For installing/removing ¾ in NPT conduit plugs

1 1/16 in combination wrench For installing/removing ¾ in NPT to M20 thread


reducer (ATEX required)

#1 Phillips-head screwdriver For screws on HMI module

#2 Phillips-head screwdriver For screws on other modules and boards

1/8 inch flat-head screwdriver For 5.08 mm pitch terminal block connections

3/32-inch flat head screwdriver For 3.81 mm pitch terminal block connections

Laptop PC running Field Tools with FBxConnect


For software configuration
configuration software

2.4 Site Considerations


The flow computer must reside in an accessible location for configuration and service. Refer to the
dimensional drawings for information on the space required.
 Ensure the installation location provides easy access to the HMI module.

12 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021
 If your unit includes the optional solar panel, ensure the installation location provides
sufficient space to mount the solar panel and adequate sunlight to charge the battery.
 If your unit includes the optional FBxWifi, ensure the installation location provides line-of-
sight access to the transceiver.

Figure 2-1: FB1200 Flow Computer Dimensions – Multivariable Sensor Version (Option F1)

Installation 13
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-2: FB1200 Flow Computer Dimensions – No Integral Sensor Version (Option F0)

14 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-3: FB1200 Flow Computer Dimensions – Static Pressure Sensor (Option F2)

2.5 General Wiring Guidelines


The flow computer’s pluggable terminal blocks use compression-type terminals.

The 5.08 mm pitch terminal blocks accommodate wire between 28 and 12 AWG; the 3.81 mm
pitch terminal blocks accommodate wire between 28 and 14 AWG.
 When making a connection, insert the bare end of the wire (approx. 1/4" max) into the clamp
adjacent to the screw and secure the screw.
 To prevent shorts, ensure that no bare wire is exposed.
 Allow some slack in the wire while making terminal connections. Slack makes the wires more
manageable and helps minimize mechanical strain on the terminal blocks.
 Use twisted pair, shielded and insulated cable for communication and I/O wiring to minimize
signal errors caused by electromagnetic interference (EMI), radio frequency interference
(RFI) and transients. When using shielded cable, ground all shields at only one point in the
appropriate system. This prevents circulating ground current loops that can cause signal
errors.

2.6 Front or Rear End Caps


The flow computer includes two threaded covers (end caps). The front end cap includes a window
for viewing the HMI module; the rear end cap provides access to the terminal plate for power and
I/O wiring.

Installation 15
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

2.6.1 Removing/Replacing Retaining Clamp on End Caps


For flameproof ATEX/IEC applications, each end cap includes a retaining clamp which screws down
to prevent the end cap from being unscrewed.

Figure 2-4: Front End Cap with Retaining Clamp Fitted

1 End Cap
2 Screw
3 Retaining Clamp

Figure 2-5: Retaining Clamp in Place

To loosen or tighten the screw, use a 3mm hexagonal wrench. When tightening, torque to 12 in-lbs
(1.4 N m).

Figure 2-6: Retaining Clamp and Screw

16 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

2.6.2 Removing the Front or Rear End Caps


DANGER
EXPLOSION HAZARD: Never remove end cap(s) in a hazardous location. Removing end cap(s) in a
hazardous location could result in an explosion.

Note
If you need more leverage place a long screwdriver or other appropriate tool across the two
notches in the end cap to act as a pry bar (see Figure 2-7).

Figure 2-7: Removing or Tightening the End Cap with Long Screwdriver

1. Remove the retaining clamp (if present). (See Section 2.6.1)


2. Grasp the end cap (front or rear).

Figure 2-8: Front (left) and Rear (right) End caps

3. Unscrew the end cap turning it counter-clockwise until it comes off. Set it aside in a safe
location.

Installation 17
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-9: Front (left) and Rear (right) End Caps Removal

2.6.3 Replacing the Front or Rear End Caps


DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

1. Grasp the end cap (front or rear).


2. Carefully align the end cap threads with the threads of the enclosure.

Important
When replacing the rear end cap, ensure wires connecting to the terminal plate do not get
crimped or caught between the end cap threads and the enclosure.

3. Screw the end cap clockwise (eight full turns) until it is tightly sealed to the enclosure.
4. Replace the retaining clamp (if required). (See Section 2.6.1)

Note
If you need more leverage place a long screwdriver or other appropriate tool across the two
notches in the end cap to act as a pry bar (see Figure 2-7).

2.7 Mounting the Enclosure


You can mount the flow computer either directly to a manifold on the pipeline or indirectly on a
two-inch pipe or pole.

Direct mount installations use either a traditional mounting kit or a coplanar mounting kit. Indirect
mount installations use an inline mounting kit.

2.7.1 Bolting Considerations


If the flow computer installation requires assembly of a process flange, manifold, or flange
adapters, follow these assembly guidelines to ensure a tight seal for optimal performance
characteristics of the flow computer.

Only use bolts supplied with the flow computer or sold by Emerson Remote Automation Solutions
as spare parts. Refer to the figure for common flow computer assemblies with the bolt length
required for proper flow computer installation.

18 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

Note
For all other manifolds, contact your local Emerson Sales office or Emerson Impact Partner.

Bolts are typically carbon steel or stainless steel. Confirm the material by viewing the markings on
the head of the bolt and referencing the figure. If bolt material is not shown in the figure, contact
your local Emerson Remote Automation Solutions representative for more information.

Figure 2-10: Transmitter with Coplanar Flange

Figure 2-11: Transmitter with Coplanar Flange and Optional Flange Adapters

Figure 2-12: Transmitter with Traditional Flange and Optional Flange Adapters

Use the following bolt installation procedure:

1. Carbon steel bolts do not require lubrication. Stainless steel bolts are factory-coated with a
lubricant to ease installation. Do not apply any additional lubricant when installing either
type of bolt.
2. Finger-tighten the bolts.

Installation 19
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021
3. Torque the bolts to the initial torque value using a crossing pattern. See Table 2-3 for initial
torque value.
4. Torque the bolts to the final torque value using the same crossing pattern. See Table 2-3 for
final torque value.
5. Verify that the flange bolts protrude through the sensor module before applying pressure.
Table 2-3: Torque Values for the Flange and Flange Adapter Bolts

Bolt Material Head markings Initial Torque Final Torque

Carbon 300 in. -lbs. 650 in. -lbs.


Steel (CS) (33.9 N m) (73.4 N m)

Stainless Steel 150 in. -lbs. 300 in. -lbs.


(SST) (16.9 N m) (33.9 N m)

Figure 2-13: Proper Bolt Installation

1 Bolt
2 Sensor module

2.7.2 O-rings with Flange Adapters


DANGER
Failure to install proper flange adapter O-rings may cause process leaks, which can result in death
or serious injury. Only use the O-ring that is designed for its specific flange adapter.

20 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-14: O-rings with Flange Adapters

1 Flange
2 O-ring
3 Square PTFE-based profile
4 Round Elastomer profile

1. Whenever the flange or adapters are removed, visually inspect the O-rings.
2. Replace the O-rings if there are any signs of damage, such as nicks or cuts.
3. If the O-rings are replaced, re-torque the flange bolts and alignment screws after installation
to compensate for seating of the O-rings.

2.7.3 Direct Mount


Direct mount installations use either a traditional mounting kit or a coplanar mounting kit. Mount
the flow computer directly to the pipeline only if the pipeline includes a process manifold.

DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

1. Place taps in the top or side of the line.


2. Mount the flow computer beside or above the taps.

2.7.4 Indirect Mount


You can mount the flow computer to a two-inch pipe or pole. Indirect mount can use the inline,
coplanar, or traditional flange mounting kits.

DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

Installation 21
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-15: Traditional Flange Mounting Kit

1 2.0 in. pipe diam. U-bolt assembly (5/16-18 x 4.0 LG) with (2) nuts (item 3)
2 Mounting bracket
3 Apply Loctite® 222™ Low Strength Purple Threadlocker to nuts. Torque nuts to 30
in-lbs (3.4 N m
4 7/16-20 x .625 cs/zinc cobalt screws (4). Torque to 30 in-lbs (3.4 N m)

22 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-16: Coplanar Mounting Kit

1 Tubular L-shaped bracket


2 3/8-16 x 1 ½ in socket head wire lockable screw (2) – Apply Killark® LUBG-6 Thread
Lubricant to threads. Torque screws to 30 in-lbs (3.4 N m)
3 Split 3/8 lock washer (2)
4 5/16-18 keps nut (2). Apply Loctite 222 Low Strength Purple Threadlocker to nuts. Torque
nuts to 30 in-lbs (3.4 N m)
5 U-bolt bracket
6 2-inch diameter pipe U-bolt

Installation 23
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-17: Inline Mounting Kit

1 Pipe mounting bracket


2 U-bolt 2 ½ inch diam. pipe (5/16-18 x 3.75 long)
3 5/16 flat lock washer (2)
4 5/16-18 300 series hex nut (2) - Apply Loctite 222 Low Strength Purple Threadlocker to
threads. Torque nuts to 30 in-lbs (3.4 N m)
5 U-bolt clamp assembly - Apply Loctite 222 threadlocker to threads. Torque nuts to 30 in-lbs
(3.4 N m)

2.7.5 Rotating the Housing


To improve accessibility to the HMI module or to ease wiring, you can optionally rotate the
housing.

Important
Never rotate the housing more than 180 degrees from its original (as-shipped) position. Over-
rotation can break electronics within the unit.

24 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-18: Housing Rotation Set Screw (1 each side)

1 Set Screw (one each side)

DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

3. Loosen the two housing rotation set screws.


4. Rotate the housing no more than 180 degrees from its original (as-shipped) position.
5. Re-tighten the two housing rotation set screws. Torque to 6 in-lbs. (0.7 N m).

Installation 25
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

2.8 Grounding the Device


The flow computer includes a grounding lug on the terminal plate.

Figure 2-19: Ground Lug

1 Ground Lug

DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

 Once you have installed the unit, run a ground wire between the ground lug and a known
good earth ground. You route the ground wire through one of the conduit fittings.
 Use stranded copper wire to earth ground and keep the length as short as possible.
 Clamp or braze the ground wire to the ground bed conductor (typically a stranded copper
AWG 0000 cable installed vertically or horizontally).
 Run the ground wire so that any routing bend in the cable has a minimum radius of 30.5 cm
(12 inches) below ground and 20.4 cm (8 inches) above ground.
 For more information on grounding or if your installation uses cathodic protection, refer to
Site Considerations for Equipment Installation, Grounding, and Wiring (D301452X012).

26 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

2.9 Terminal Plate


The terminal plate includes the various terminal blocks (TB) for power and I/O connections.

The terminal plate’s appearance varies depending upon whether you have the optional 6-channel
expansion I/O module installed with 3.81 pitch connections; when it is installed there are eight or
nine connections per terminal blocks instead of six 5.08 pitch connections. Compare your device to
the pictures to see which terminal plate you have.

Figure 2-20: Terminal Plate (without Optional I/O with 6 5.08 mm Pitch Connectors)

Installation 27
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021
Terminal Plate (with Optional I/O with 8 3.81 mm Pitch Connectors)

2.10 Power Modes


To keep power consumption to a minimum, especially for remote sites, the flow computer can run
in two different power modes: Low Power Mode (4 or 8 MHz CPU clock speed) or Standard Power
Mode (60 MHz CPU clock speed).

2.10.1 Low Power Mode


The flow computer normally runs in low power mode for typical metering applications. The radio
Power Control function (configurable in FBxConnect) switches the flow computer into standard
power mode at specified times when serial communications are required, then it reverts to low
power mode when the communication period is over. A serial connection to a remote 4088B MVT
can occur in low power mode.

28 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021
The local display (HMI module) with FBxWifi communications and FBxWifi uses additional power.
You can configure it in FBxConnect to shut down after a period of inactivity.

Important
You must disable the Ethernet port (using a jumper) to run in low power mode. See Section 2.13.3.

Table 2-4: Typical Power Usage – Low Power Mode at Room Temperature

Description Power Usage (mW) at 6.1Vdc

Base flow computer with integral multivariable DP and


pressure sensor and temperature measurement for a single
meter run.

47
Historical configuration supports maximum of:
 4 averages
 12 Station 1 history points (Group 4)
 10 User Periodic history points (Group 1)

Base flow computer with integral static pressure sensor and


temperature measurement and a pulsed input for a single
meter run

45
Historical configuration supports maximum of:
 4 averages
 12 Station 1 history points (Group 4)
 10 User Periodic history points (Group 1)

Base flow computer with integral multivariable DP and


pressure sensor and temperature measurement,
communicating to remote 4088B-dual meter run (4088B
externally powered)
82
Historical configuration supports maximum of:
 8 averages
 24 Station 1 & Station 2 history points (Group 4/Group 5)
 10 User Periodic history points (Group 1)

Additional Load Options:

Display and backlight active 292

FBxWifi 315

FBxWifi and display active 337

DO active (1 Hz, 50:50 duty cycle, no load) 1

Important
If you increase the number of history points/averages beyond any of the maximum limits detailed in
Table 2-4, the flow computer cannot operate in low power mode and automatically runs in standard
power mode.

Installation 29
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

2.10.2 Standard Power Mode


When serial communication is active (other than to a remote 4088B MVT) the flow computer
operates in standard power mode. The unit also uses standard power mode when:
 The HMI module display is ON
 FBxWifi is active
 Ethernet port enabled in the flow computer
 Modbus Master communication active
 PIDs, Math/logic Blocks, Action Blocks, Effect blocks enabled
 6-channel expansion I/O board installed and enabled in the flow computer; if board installed
but disabled in FBxConnect, can remain in low power mode
 Power control zone enabled

Table 2-5: Typical Power Usage – Standard Power Mode at room temperature

Power Usage Power Usage Power Usage


Description
(mW) at 6Vdc (mW) at 12Vdc (mW) at 24Vdc

Base flow computer with integral


multivariable DP and pressure sensor and
230 245 287
temperature measurement for a single
meter run

Base flow computer with integral static


pressure sensor and temperature
244 260 305
measurement and a pulsed input for a
single meter run

Base flow computer with integral


multivariable DP and pressure sensor and
temperature measurement, 278 306 373
communicating to remote 4088B - dual
meter run (4088B externally powered)

Additional Load Options:

Display and backlight active 162 168 178

FBxWifi 189 185 200

FBxWifi and display active 204 207 221

DO active (1 Hz, 50:50 duty cycle, no load) 1 1 1

PI active (10 KHz, 50:50 duty square wave) 13 14 15

6-channel expansion I/O board installed 40 49 80

Ethernet enabled 100 Mbit 435 421 462

Ethernet active 100 Mbit 459 443 489

30 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

2.10.3 Notes on Battery Life


Battery life varies based on numerous factors including temperature, communication usage, and
various load options. To achieve the maximum battery life noted in the product data sheet requires
that you:
 Limit use of the display, backlight, and FBxWifi options.
 Limit communication activity.
 Disable power to all I/O (except for the MV or static pressure sensor, or RTD). To do this, click
Configure > I/O Setup > I/O Configuration > Properties and select Disable for each I/O
module.

See the product data sheet FB1200 Flow Computer (D301790X012) for information on the
additional power load of various options.

2.11 Connecting Power


Power can come from an external DC supply, or a lead acid battery pack with a solar panel. See
Section 2.12.4 for information on solar power connections.

Power connections are made through conduit fittings to the terminal plate. Remove the rear end
cap for access to the terminal plate.

Installation 31
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

2.11.1 Connecting DC Power


DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

When power comes from an external DC supply, connect using the +DCIN and –DCIN terminals.
Use standard copper wire (#18 AWG minimum). The device supports both 12V and 24V power
supplies. It accepts DC voltage from 5.7 to 30V; the amount of power required varies depending
upon the options used.

Note
The top portion of Figure 2-21 shows the unit with optional I/O; the bottom portion shows the unit
without optional I/O.

Figure 2-21: DC Power Connections

1 To External power supply

32 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

2.11.2 Connecting Battery Power


DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

Important
If you purchased this device with the rechargeable lead acid battery pack, be aware that the lead
acid battery pack must always be stored in a charged state. If you do not intend to install the flow
computer immediately, make provisions to “top-off” the lead acid battery at six-month intervals.
Failure to do so could sharply reduce battery life or result in a dead battery.

When power comes from an internal battery pack, the battery pack plugs into one of two
connectors.

Figure 2-22: Connecting the Battery Pack

1 Left Battery Connector


2 Right Battery Connector

Restriction
The solar panel and lead acid battery combination cannot be used with ATEX/IECEx applications.

Installation 33
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

2.12 Installing the Optional Solar Panel


If you purchased the lead acid battery/solar panel kit for main power, you need to install the
supplied 6W solar panel. If you purchased the lead acid battery with a solar regulator but you are
supplying your own solar panel, follow the manufacturer’s instructions for remote mounting.

DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

Solar panel installation involves:


 Attaching mounting hardware to the solar panel (if not attached prior to shipment).
 Mounting the solar panel in one of two ways:

• Integral mount (solar panel attaches directly to the flow computer)

• Remote mount (solar panel mounts to a pole)


 Wiring power to the solar panel.
 Setting the tilt angle of the panel for maximum solar exposure.

2.12.1 Attaching Mounting Hardware to the Solar Panel


DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

Attach mounting hardware to the solar panel as shown in Figure 2-23.

 Attach aluminum tilt brackets (Item 2) to solar panel using the provided pan head screws
(Item 3), hex nuts (Item 10 in Figure 2-24), and #10 lock washers (Item 9 in Figure 2-24).

 Apply Loctite® Threadlocker 222 sparingly to threads of hex nuts (Item 6). Attach mounting
bracket to tilt brackets using provided hex nuts (Item 6), hex bolts (Item 5), washers (Item 4),
and spring lock washers (Item 7). The spring lock washer goes between the washer and the
nut. Torque to 30 in-lbs (3.4 N m).

34 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-23: Attaching Mounting Hardware to the Solar Panel

1 6V, 6W solar panel


2 aluminum tilt bracket (2)
3 10-32 x ½ pan head screw (4). Note: Matching hex nuts and washers not visible in this
graphic; see Items 9 and 10 in Figure 2-24
4 5/16 flat washer (4); only two visible in this graphic
5 5/16-18 x .75 LG hex head bolt (2)
6 5/16-18 hex nut (2); only one visible in this graphic
7 5/16 flat spring lock washer (2) only one visible; placed on bolt between washer and nut
8 mounting bracket

Installation 35
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

2.12.2 Mounting the Solar Panel (Integral Mount)


DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

Restriction
The solar panel and lead acid battery combination cannot be used with ATEX/IECEx applications.
The integral mount solar panel cannot be used in a Class I Division 1 area; C1D1 solar panels must
be remote mounted with the solar panel in a safe area.

1. Apply Loctite® 380™ Black Instant Adhesive to threads of elbow pipe (Item 15 in Figure 2-
20). Attach elbow pipe (Item 15) to the flow computer conduit opening (Item 16); torque to
50 in-lbs (5.6 N m).

2. Apply Loctite 380 adhesive sparingly to threads of pipe (Item 14).

3. Attach pipe (Item 14) to elbow pipe (Item 15). Torque to 50 in-lbs (5.6 N m).

4. Attach pipe cap (Item 11) to top of pipe (Item 14). Torque to 50 in-lbs (5.6 N m).

5. Apply Loctite 222 threadlocker sparingly to threads of U-bolt (Item 12).

6. Attach solar panel assembly to pipe (Item 14) using U-bolt (Item 12).

7. Attach a ground wire at the back of the solar panel. For more information on grounding,
refer to Site Considerations for Equipment Installation, Grounding, and Wiring Manual
(D301452X012).

8. Adjust swivel and tilt angle for maximum solar exposure (see Section 2.13.5).

36 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-24: Integral Mounted Solar Panel

1 6V, 6W solar panel


2 aluminum tilt bracket (2)
3 10-32 x ½ pan head screw (4).
4 5/16 flat washer (4); only two visible in this graphic
5 5/16-18 x .75 LG hex head bolt (2)
8 mounting bracket
9 #10 lock washer (4)
10 #10-32 hex nut (4)
11 ¾ NPT pipe cap
12 U-bolt 1 1/8 in. diam. pipe x ¼ -20 x 2-inch-long
13 pipe threads (2)
14 ¾ NPT x 8-inch-long threaded pipe
15 ¾ NPT 90-degree female x male elbow pipe
16 Conduit fitting

Installation 37
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

2.12.3 Mounting the Solar Panel (Remote Mount)


DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

Restriction
Battery power is not allowed in ATEX/IECEx applications.

1. Apply Loctite 222 thread locker sparingly to threads of U-bolt (Item 12).

2. Attach solar panel assembly to pole using U-bolt (Item 12). Torque to 30 in-lbs (3.4 N m).

3. Adjust swivel and tilt angle for maximum solar exposure (see Section 2.13.5).

Figure 2-25: Remote Mounted (pole mounted) Solar Panel

1 6V, 6W solar panel


2 mounting bracket
12 U-bolt 1 1/8 in. diam. pipe x ¼ -20 x 2 inch long
17 pole (customer supplied)

38 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

2.12.4 Connecting Solar Power


DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

When power comes from a solar panel/lead acid battery combination, connect using the +SPIN and
–SPIN terminals and standard copper wire (#18 AWG minimum).

Note
The top portion of Figure 2-26 shows wiring for units with option I/O; the bottom portion shows
wiring for units without optional I/O.

Figure 2-26: Wiring Solar Power

1 To solar panel

Restriction
Battery power is not allowed in ATEX/IECEx applications.

Installation 39
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

2.12.5 Adjusting the Optional Solar Panel Tilt Angle


DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

The mounting brackets allow you to adjust the solar panel for maximum solar exposure. You can
adjust the swivel of the panel by adjusting the U-bolt.

Figure 2-27: Adjusting Solar Panel Tilt Angle

 Point the solar panel surface due south (in the northern hemisphere) or due north (in the
southern hemisphere) at an angle determined by the latitude of the site. Table 2-6 shows the
angle (from horizontal) at which you should install the solar panel to maximize annual energy
output. At most latitudes, you can improve performance by reducing the angle during the
summer and increasing the angle during the winter. If no seasonal adjustments in panel
direction are needed then adjust the position for the worst-case December-February angle.
 Solar insolation is the amount of solar energy in hours received each day by an optimally
tilted panel during the worst month of the year. An insolation rating of one hour means that
the site, on average, would receive one hour of solar energy at the panel's rated power level
(1000W/m2 per day). This rating varies from less than one hour in northern Canada to more
than six hours in the Sahara Desert.

40 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021
Table 2-6: Solar Panel Tilt Angle

Latitude Installation Angle

0 to 4° 10° from horizontal

5 to 20° Add 5° from the local latitude

21 to 45° Add 10° from the local latitude

46 to 65° Add 15° from the local latitude

66 to 75° 80° from horizontal

2.13 Connecting Communication Ports


DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

The communication ports allow you to connect either to a PC or laptop running FBxConnect
software or to other devices. If your application measures two meter runs, you must dedicate a
port for communication to the external transmitter for the second meter run.

Access the three serial communication ports and the Ethernet port on the terminal plate under the
rear end cap. Route communication cables through the conduit fittings and connect the cables on
the terminal plate.

2.13.1 Connecting to COM1


COM1 can be configured for RS-232, RS-485 (2-wire), or RS-485/422 (4-wire) communications.
When connecting COM1 to another device using RS-232, use wiring as shown in Figure 2-28.

Note
The upper portion of Figure 2-28 shows wiring for units with optional I/O; the lower portion shows
wiring for units without optional I/O.

Installation 41
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-28: Connecting a Device to COM1 Using RS-232

1 RS-232 port (COM1) on FB device


2 RS-232 port on external device

When connecting COM1 to another device using RS-485/422 (4-wire), use wiring as shown in
Figure 2-29.

Note
The upper portion of Figure 2-29 shows wiring for units with optional I/O; the lower portion shows
wiring for units without optional I/O.

42 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-29: Connecting a Device to COM1 Using RS-485/422 (4-wire)

1 RS-485/422 (4-wire) port (COM1) on FB device


2 RS-485/422 (4-wire) port on external device

When connecting COM1 to another device using RS-485 (2-wire), use wiring as shown in Figure 2-
30.

Note
The upper portion of Figure 2-30 shows wiring for units with optional I/O; the lower portion shows
wiring for units without optional I/O.

Installation 43
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-30: Connecting a Device to COM1 Using RS-485 (2-wire)

1 RS-485 (2-wire) port (COM1) on FB device


2 RS-485 (2-wire) port on external device

Regardless of the interface standard (RS-232, RS-485 [2-wire or 4-wire]), you must use FBxConnect
to configure the port for proper usage.

2.13.2 Connecting to COM2 and COM3


COM2 and COM3 operate identically. Each can be configured for either RS-232 or RS-485 (2-wire)
communication.

When connecting COM2 or COM3 to an RS-232 port on another device (a PC or another


controller/flow computer) use wiring as shown in Figure 2-31:

44 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-31: Connecting a Device to COM2 or COM3 Using RS-232 (with Optional I/O)

1 RS-232 port (COM2) on FB device


2 RS-232 port (COM3) on FB device
3 RS-232 port on external device

Note
COM3 does not have its own GND terminal. Use either GND terminal on the COM1 terminal block.

Installation 45
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-32: Connecting a Device to COM2 or COM3 Using RS-232 (without optional I/O)

1 RS-232 port (COM2) on FB device


2 RS-232 port on external device
3 RS-232 port (COM3) on FB device

Note
COM2 does not have its own GND terminal. Use either GND terminal on the COM1 terminal block.

When connecting COM2 or COM3 to an RS-485 (2-wire) port on another device (such as a
transmitter), use wiring as shown in Figure 2-33:

46 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-33: Connecting a Device to COM2 or COM3 Using RS-485 (2-wire) (with optional I/O)

1 RS-485 (2-wire) port (COM2) on FB device


2 RS-485 (2-wire) port (COM3) on FB device
3 RS-485 (2-wire) port on external device

Note
COM3 does not have its own GND terminal. Use either GND terminal on the COM1 terminal block.

Installation 47
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-34: Connecting a Device to COM2 or COM3 Using RS-485 (2-wire) (without optional I/O)

1 RS-485 (2-wire) port (COM2) on FB device


2 RS-485 (2-wire) port on external device
3 RS-485 (2-wire) port (COM3) on FB device

Note
Neither COM2 nor COM3 have GND terminals. Use either GND terminal on the COM1 terminal
block when grounding COM2 or COM3.

Regardless of the interface standard (RS-232 or RS-485 2-wire), you must use FBxConnect to
configure the port for proper usage.

48 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

2.13.3 Ethernet Port


The Ethernet port is a standard 8-pin 10/100Base-T RJ-45 modular connector located on the
terminal plate. Connect to the Ethernet port using the appropriate Category 5 shielded patch cable

Note
The default IP address for the Ethernet port is 192.168.1.10; the default port is 20000.

Figure 2-35: Location of Ethernet Port

1 Ethernet Port

Note
If you ordered Ethernet, the unit ships with Ethernet enabled. If you need to operate the device in
lower power mode, you must disable Ethernet. Jumper J10 on the CPU module (see Figure 2-36)
controls whether Ethernet is enabled or disabled (lower power mode). See the CPU Module Field
Replacement Guide (D301802X012) for information on how to open the unit to gain access to the
CPU module.

Installation 49
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 2-36: Ethernet Port jumper

50 Installation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Section 3: I/O Configuration and Wiring


This section covers the following topics:
 Analog Inputs
 Analog Outputs
 Digital Inputs
 Digital Outputs
 Pulse Inputs
 Connecting the RTD
 Connecting a Rosemount 4088B Transmitter For Use in a Second Meter Run

I/O in the flow computer comes from the integrated multivariable sensor and RTD connector, the
CPU board, as well as from the optional 6-channel expansion I/O board.

Note
When using a digital output to drive an inductive load (such as a relay coil), place a suppression diode
across the load. This protects the DO from the reverse Electro-Motive Force (EMF) spike generated
when the inductive load is switched off.

Notes About Power for an External Device Connected to a Flow Computer I/O Point:
If the external device does not include its own integrated power supply, you must provide your own
external supply (30Vdc maximum) for that device.

I/O Configuration and Wiring 51


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 3-1: Base I/O on CPU (with Optional I/O)

A When wiring a 1-5 V Analog Input (AI), use configuration at left


B When wiring a 4-20 mA Analog Input (AI), use configuration at left
1 Field Device
2 Power Supply 30Vdc Max
3 500 mA load max
4 To AGND
5 To AIAOx
6 Dry contact

52 I/O Configuration and Wiring


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 3-2: Base I/O On CPU (without Optional I/O)

A When wiring a 1-5 V Analog Input (AI), use configuration at left


B When wiring a 4-20 mA Analog Input (AI), use configuration at left
1 Field Device
2 Power Supply 30Vdc Max
3 500 mA load max
4 To AGND
5 To AIAOx
6 Dry contact

I/O Configuration and Wiring 53


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 3-3: Optional 6-channel Expansion I/O Module

A When wiring a 1-5 V Analog Input (AI), use configuration at left


B When wiring a 4-20 mA Analog Input (AI), use configuration at left
1 Field Device
2 Power Supply 30Vdc Max
3 500 mA load max
4 To AGND
5 To AIAOx
6 Dry contact

54 I/O Configuration and Wiring


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

3.1 Analog Inputs


The flow computer includes two on-board channels you can individually configure as either analog
inputs (AI) or analog outputs (AO). In addition, if you purchased the optional 6-channel expansion I/O
board, there are two additional channels you can individually configure as either AIs or AOs.

Note
No external resistor is required for a current (mA) device. You can apply a 250 ohm resistor using
analog input configuration selections in FBxConnect.

When configured as analog inputs, the channels have the following characteristics:

Table 3-1: Analog Input Characteristics

Type Number Supported Characteristics

Analog 0 to 4 as follows:  4 to 20 mA range (@24Vdc), or 1 to


Input  1 or 2 non-isolated channels on CPU 5Vdc
(AI) board (AIAO1 and AIAO2) always  Over range for calibration purposes:
present. You can configure one, both, 3.2 to 20.8 mA or 0.8 to 5.2 Vdc
or neither as AIs.  Externally powered
 1 or 2 additional non-isolated channels  Factory calibrated (re-calibration is
on optional 6-channel expansion I/O unnecessary for at least 3 years)
board (AIAO3 and AIAO4). If present  Signal conditioning
you can configure one, both, or neither  When you configure a channel as an
as AIs. AI it cannot be used as an AO

3.1.1 AI Wiring
Wire analog inputs as shown in the following figures.

Note
Figures 3-4 and 3-5 show analog input wiring for AIAO2. AIAO1 and AIAO2 share the same GND
terminal.

I/O Configuration and Wiring 55


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 3-4: 4-20 mA AI Wiring (Base I/O with Optional I/O Module)

1 Field Device
2 Power Supply 30Vdc Max

Figure 3-5: 1-5 V AI Wiring (Base I/O with optional I/O)

1 Field Device

56 I/O Configuration and Wiring


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 3-6: AI Wiring (Base I/O without Optional I/O Module)

A When wiring a 1-5 V Analog Input (AI), use configuration at left


B When wiring a 4-20 mA Analog Input (AI), use configuration at left
1 Field Device
2 Power Supply 30Vdc Max
3 To AGND
4 To AIAOx

Note
Figures 3-7 and 3-8 show analog input wiring for AIAO3. AIAO3 and AIAO4 share the same GND
terminal.

I/O Configuration and Wiring 57


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 3-7: 4-20 mA AI Wiring (with Optional 6-channel Expansion I/O Module).

1 Field Device
2 Power Supply 30Vdc Max

Figure 3-8: 1-5 V Analog Input (AI) Wiring (Optional 6-channel Expansion I/O Module

1 Field Device

58 I/O Configuration and Wiring


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

3.2 Analog Outputs


The flow computer includes two on-board channels you can individually configure as either analog
outputs (AO) or analog inputs. In addition, if you purchased the optional 6-channel expansion I/O
board, there are two additional channels you can individually configure as either AOs or AIs.

When configured as analog outputs, the channels have the following characteristics:

Table 3-2: Analog Output Characteristics

Type Number Supported Characteristics

Analog 0 to 4 as follows:  4 to 20 mA range (@24Vdc)


Output  1 or 2 non-isolated channels on CPU  Externally powered field device
(AO) board (AIAO1 and AIAO2) always (AIAO1/AIAO2)
present. You can configure one, both,  AO provides current to power field
or neither as AOs. Note: If you device (AIAO3/ AIAO4)
configure both as AOs we recommend  AO sinks current to system ground
you provide isolation to avoid ground  Factory calibrated (re-calibration is
loops which could affect readings. unnecessary for at least 3 years)
 1 or 2 additional non-isolated channels  You can configure a fail state so that
on optional 6-channel expansion I/O on power up or if the CPU fails the
board (AIAO3 and AIAO4). If present output drives to 0 µA
you can configure one, both, or neither  When a channel is configured as an
as AOs. AO it cannot be used as an AI

3.2.1 AO Wiring
Wire analog outputs as shown in the following figures.

Note
Figure 3-9 shows analog output wiring for AIAO1. AIAO1 and AIAO2 share the same GND terminal.

I/O Configuration and Wiring 59


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 3-9: AO Wiring (Base I/O with Optional I/O)

1 Field Device
2 Power Supply 30Vdc Max

Figure 3-10: AO Wiring (Base I/O without Optional I/O)

1 Field Device
2 Power Supply 30Vdc Max

60 I/O Configuration and Wiring


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Note
Figure 3-11 shows analog output wiring for AIAO4. AIAO3 and AIAO4 share the same GND terminal.

Figure 3-11: AO Wiring (with Optional 6-channel Expansion I/O Module)

1 Field Device

3.3 Digital Inputs


Depending upon how you ordered it, the flow computer includes either two or six channels you can
individually configure as digital inputs (DI), digital outputs (DO), or pulse inputs (PI).

When configured as digital inputs, the channels have the following characteristics:

Table 3-3: Digital Input Characteristics

Type Number Supported Characteristics

Digital 0 to 6 as follows:  Circuit protection


Input  1 or 2 non-isolated channels on CPU  30ms input filtering
(DI) board (PI/DI/DO1 and PI/DI/DO2). Two  Maximum input frequency of 10 Hz
always present; you can configure one,  Selectable current source of 66 µA or
both, or neither as DIs. 2 mA
 1 to 4 additional non-isolated channels  Either externally driven or internally
on optional 6-channel expansion I/O driven and pulled to ground by dry
board (PI/DI/DO3 through PI/DI/DO6). contact closures or open collector
If present you can con- figure one, devices
two, three, four or none as DIs.  When a channel is configured as a DI
it cannot be used as a DO or PI
channel

I/O Configuration and Wiring 61


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

3.3.1 DI Wiring
The following figures show how to wire digital inputs.

Note
Figure 3-12 shows discrete input wiring for DIDO1. DIDO1 and DIDO2 share the same GND terminal.

Figure 3-12: DI Wiring (Base I/O with Optional I/O)

1 Dry contact

62 I/O Configuration and Wiring


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 3-13: DI Wiring (Base I/O without Optional I/O)

1 Dry contact

Note
Figure 3-14 shows discrete input wiring for DIDO5. DIDO5 and DIDO6 share the same GND terminal.
DIDO3 and DIDO4 share a different GND terminal.

Figure 3-14: DI Wiring - (with Optional 6-channel Expansion I/O Module)

1 Dry contact

I/O Configuration and Wiring 63


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

3.4 Digital Outputs


Depending upon how you ordered it, the flow computer includes two or six channels you can
configure as digital outputs (DO), digital inputs (DI) or pulse inputs (PI).

Note
When using a digital output to drive an inductive load (such as a relay coil), place a suppression diode
across the load. This protects the DO from the reverse Electro-Motive Force (EMF) spike generated
when the inductive load is switched off.

When configured as digital outputs, the channels have the following characteristics:

Table 3-4: Digital Output Characteristics

Type Number Supported Characteristics

Digital 0 to 6 as follows:  DO is a low side switch that sinks


Output  1 or 2 non-isolated channels on CPU current to ground
(DO) board (PI/DI/DO1 and PI/DI/DO2). Two  Current rating of 500 mA
always present; you can configure one,  Maximum operating frequency of 50
both, or neither as DOs. Hz
 1 to 4 additional non-isolated channels  Pulse off/on time can be configurable
on optional 6-channel expansion I/O with a 31 ms minimum on time and a
board (PI/DI/DO3 through PI/DI/DO6). 31 ms minimum off time
If present you can configure one, two,  Can be configured in software with an
three, four or none as DOs. output state for initial power-up and
in the case of a CPU failure
 Software configurable failure mode of
fail open, fail closed, or hold last state
 When a channel is configured as a DO
it cannot be used as a DI or PI channel

64 I/O Configuration and Wiring


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

3.4.1 DO Wiring
The following diagrams show how to wire digital outputs.

Note
Figure 3-15 shows digital output wiring for DIDO2. DIDO1 and DIDO2 share the same GND terminal.
DIDO3 and DIDO4 share a different GND terminal.

Figure 3-15: DO Wiring (Base I/O with Optional I/O)

1 Power Supply 30VDC max


2 500 mA load max

I/O Configuration and Wiring 65


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 3-16: DO Wiring (Base I/O without Optional I/O)

1 Power Supply 30Vdc Max


2 500 mA load max

Note
Figure 3-17 shows digital output wiring for DIDO4. DIDO3 and DIDO4 share the same GND terminal.
DIDO5 and DIDO6 share a different GND terminal.

Figure 3-17: DO Wiring (with Optional 6-channel Mixed I/O Module)

1 Power Supply 30Vdc Max


2 500 mA load max

66 I/O Configuration and Wiring


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

3.5 Pulse Inputs


The flow computer includes two channels that can be individually configured as pulse inputs (PI),
digital inputs (DI), or digital outputs (DO).

When configured as pulse inputs, the PI channels have the following characteristics:

Table 3-5: Pulse Input Characteristics

Type Number Supported Characteristics

Pulse 0 to 6 as follows:  Supports dry contacts and open


Input  1 or 2 non-isolated channels on CPU collector outputs connected to
(PI) board (PI/DI/DO1 and PI/DI/DO2). Two ground and voltage inputs
always present; you can configure one,  Supports single pulse for volume or
both, or neither as PIs. mass
 1 to 4 additional non-isolated channels  Input filtering selectable at 30 µs or 1
on optional 6-channel expansion I/O ms
board (PI/DI/DO3 through PI/DI/DO6).  Frequency range from 0 to10.5 KHz
If present you can con- figure one,  Maximum input frequency for the 1
two, three, four or none as PIs. ms filter is 300 Hz
 When a channel is configured as a PI it
cannot be used as a DI or DO channel
 ON when greater than 3.0V; OFF
when less than 2.0V

3.5.1 PI Wiring
The following diagrams show how to wire the pulse inputs.

Note
Figure 3-18 shows pulse input wiring for PIDIDO1. PIDIDO1 and PIDIDO2 share the same GND
terminal.

I/O Configuration and Wiring 67


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 3-18: PI Wiring (Base I/O with Optional I/O)

Figure 3-19: PI Wiring (Base I/O without Optional I/O)

68 I/O Configuration and Wiring


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Note
Figure 3-20 shows pulse input wiring for PIDIDO5. PIDIDO5 and PIDIDO6 share the same GND
terminal. PIDIDO3 and PIDIDO4 share a different GND terminal.

Figure 3-20: PI Wiring (with Optional I/O Module)

3.6 Connecting the RTD


DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

RTD connections reside on the terminal plate under the rear end cap. The flow computer supports 2-
wire, 3-wire, and 4-wire operation for a PT100 RTD. Route the RTD cable through the conduit fittings
and connect them on the terminal plate (as shown on Figure 3-21 and Figure 3-22).

Note
The device defaults to the 4-wire RTD configuration; you can change this setting in FBxConnect.

I/O Configuration and Wiring 69


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 3-21: Wiring for 2-Wire, 3-Wire, and 4-Wire RTD (Units with Optional I/O)

1 2-Wire RTD
2 3-Wire RTD
3 4-Wire RTD

70 I/O Configuration and Wiring


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 3-22: Wiring for 2-Wire, 3-Wire, and 4-Wire RTD (Units without Optional I/O)

1 2-Wire RTD
2 3-Wire RTD
3 4-Wire RTD

I/O Configuration and Wiring 71


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

3.7 Connecting a Rosemount 4088B Transmitter for Use in


a Second Meter Run
Data for the second run comes from an external transmitter such as the Rosemount 4088B.

Figure 3-23: Connecting a 4088B Transmitter for a Second Meter Run

1 RS-485 bus, twisted pair required


2 Enable AC termination using switches.
3 User-provided power supply (5.4V to 30V)

72 I/O Configuration and Wiring


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

See the Rosemount™ 4088 Multivarible™ Transmitter Reference Manual (00809-0100-4088, Rev CB,
Feb. 2017) for details on installing the 4088B.

1. Using twisted pair wire, connect the RS-485 terminals for COM3 to the RS-485 terminals on
the 4088B as shown in the graphic.
2. Set switches on the 4088B for bus termination or use a 120 ohm resistor.

3. Use FBxConnect software to configure COM3 for RS-485. In particular, enable termination for
the port.

I/O Configuration and Wiring 73


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

74 I/O Configuration and Wiring


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Section 4: Operation
This section covers the following topics:

 Powering Up/Powering Down the Device


 Establishing Communications
 Communicating using the HMI Module

This section describes day-to-day operation of the Emerson FB1200 Flow Computer including how
to turn it on and off and how to communicate with it.

4.1 Powering Up/Powering Down the Device


DANGER
Do not attempt to connect or disconnect power from the unit in a hazardous area. Ensure the
area is non-hazardous. Failure to do so could result in an explosion.

1. Remove the front end cap.

2. Terminal block TB1 includes connections for DC power (+DCIN, -DCIN) and solar power
(+SPIN, -SPIN). Battery power (which is also used with solar power) has its own internal
connections.
 Plug in TB1 to activate DC or solar power. If your device uses an internal battery and it
is not connected, connect it as discussed in 2.12.3 Connecting Battery Power.
 Unplug TB1 to deactivate DC or solar power. If your device uses an internal battery,
disconnect the main battery.
This turns on (or shuts OFF) power from either an external power supply or the battery
pack/solar panel.

Note
When you turn power on, the backlight on the HMI module lights, momentarily turns off and then
remains lit while the INPUT LED blinks. After approximately one minute the initialization process
finishes and the HMI starts to display live data.

4.2 Establishing Communications


The flow computer supports three ways to establish communications: through the host SCADA
system, through a local laptop computer running FBxConnect, or through the HMI module.

4.2.1 Communicating with the SCADA Host


Communication to the flow computer through a SCADA host computer requires configuration of
the host computer software, which varies depending upon whether you are using OpenEnterprise
or another host software package. Much of this configuration is beyond the scope of this topic, but
no matter which host you are using, there are certain steps you must take:
Operation 75
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021
1. Decide how the SCADA host should communicates with the flow computer. This could be
through connection with one of the communication ports. A serial port connection could be
a cable directly connected to the SCADA host or there could be intermediate connections
through a radio or modem. An Ethernet port connection must be through an Ethernet switch
with an appropriate Category 5 shielded patch cable.
2. Decide which communication protocol you will use. This could be DNP3, ROC, or BSAP. See
these documents for more information:
 Emerson FB Flow Computer DNP3 Protocol Specifications Manual (D301806X012)
 ROC Protocol Specifications Manual (for Emerson FBx-series) (D301828X012)
 BSAP Communication Guide for FB1000/FB2000 Series Flow Computers (D301808X012)
3. Provide the SCADA host with information about the various parameters it needs to extract
from the application running in the flow computer. Typically, the SCADA host software
includes a utility that allows you to identify this information so it can be incorporated into the
database at the SCADA host.
4. Using whatever human-machine interface (HMI) tools exist for the SCADA host, create
graphical displays or reports that include the parameters from the application required for
successful operator interaction (setpoints, flow variables and so on).

4.2.2 Communicating with a Laptop Using One of the Serial Ports


 If the flow computer is not awake, you must wake it up first. (See Section 4.3)
 Your laptop must have Field Tools software with FBxConnect software installed.
 You must know a valid username/password combination for the flow computer.

DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

1. Connect a cable between a serial port (or serial/USB adapter) on your laptop and port COM2
on the flow computer.
2. Launch Field Tools and add a new serial connection for this device; this launches FBxConnect
configuration software. (If you already have an existing saved serial connection for this
device in Field Tools, just double-click on it in the Connections list.)
3. Log into the flow computer if prompted.
4. Use the FBxConnect configuration software to view or change any desired parameters.
5. When finished, log off the flow computer and disconnect the cable from its serial port.

4.2.3 Communicating with a Laptop Using Ethernet


Your laptop must have Field Tools software with FBxConnect software installed.

You must know a valid username/password combination for the flow computer.

76 Operation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

1. Connect a Category 5 shielded cable between an Ethernet port on your laptop and an
Ethernet switch for your network.
2. Connect a Category 5 shielded cable between your Ethernet switch and the Ethernet port on
the flow computer.
3. Launch Field Tools and add an IP connection for the device then click Connect to start the
FBxConnect software. (If you already have an existing saved IP connection for this device in
Field Tools, just double-click on it in the Connections list.)
4. Log into the flow computer if prompted.
5. Use the FBxConnect software to view/change any desired parameters.
6. When finished, log off from the flow computer and disconnect the cable.

4.2.4 Communicating with a Laptop Wirelessly with FBxWifi


You must have purchased the flow computer with the optional FBxWifi communcations feature to
connect to a laptop PC wirelessly. Additionally:
®
 Wi-Fi must be configured and working on your laptop PC.
 Your laptop PC must have Field Tools software with FBxConnect installed.
 You must know a valid username/password combination for the flow computer.
 You must know the name of the wireless network and the security key required to connect to
it.
 Your laptop PC must be within line-of-sight with either the front display of the flow computer
or of an external antenna for the FBxWifi communications module.
 If the flow computer is not awake, you must wake it up first. (See Section 4.3)

WARNING
Ensure that you and your laptop PC are in a non-hazardous area.

1. Launch Field Tools software and add a new wireless connection. (If you already have a saved
wireless connection for this device in Field Tools, just double-click on the device in the
Connections list and skip to Step 4.)
2. Select the wireless network to which the flow computer belongs and enter the appropriate
security key.
3. Click Connect to start the FBxConnect software.
4. Log into the flow computer if prompted.
5. Use the FBxConnect software to view or change any desired parameters.
6. When finished, log off the flow computer and disconnect from the wireless network.

Operation 77
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

4.3 Communicating using the HMI Module


You must have purchased the flow computer with the HMI module version that includes the
optional display. Not all models include the display. Units without the display still include a button
to wake up the device and status LEDs.

Notes
 If the device is configured to require logins to view data, you must know a valid
username/password combination for the flow computer.
 To conserve power, the HMI module enters sleep mode after a period of inactivity. Sleep
mode disables FBxWifi communication. In FBxConnect, you can configure the number of
minutes of inactivity triggering sleep mode through the LCD Sleep Time parameter. Setting
this parameter to 0 disables sleep mode which keeps the HMI module on but uses
significantly more power.

The operator “awakens” the device by holding a finger against the front cover glass over the
Hold to Wake button (the left-most button) for typically five to ten seconds. You can also
pre-define a number of automatic wake-up times during the day from the Power Control
screen in FBxConnect.

To temporarily keep the HMI module out of sleep mode, maintain an active FBxConnect
connection. So long as communications remain active, the HMI module does not sleep.

1. Go to the front of the flow computer and touch your finger on the glass above the Hold to
Wake button until the display lights up. (This may take several seconds.)

Figure 4-1: Waking the Display

78 Operation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021
2. If prompted, login using a valid username/password combination. For information on how
the buttons work, see Table 4-1.
3. The display enters Screen Saver Mode where it sequentially presents a series of screens
showing details about the meter run flow rates, totals, and current process variables.

Figure 4-2: Infrared (IR) Button Location

1 Left Infrared (IR) Button


2 Down Infrared (IR) Button
3 Up Infrared (IR) Button
4 Right Infrared (IR) Button

Note
When using the IR buttons, aim your finger at the round spot just below the arrow.

Operation 79
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021
Table 4-1: Infrared (IR) Buttons on HMI Module

Button Mode Use


OR Screen Saver  Tap once to move up or down one item through list
of parameters.
 Hold to stay on current parameter.
Data Entry  Tap (UP) once to move the cursor to the previous
character in the list or (DOWN) once to move the
cursor to the next character in the list.Hold (UP) or
(DOWN) to scroll more quickly through the
character list.
Idle Mode Hold to wake the display (if screen is off)
Screen Saver Log out (if logged on)
Data Entry  Tap once to move the cursor to the left.Hold to
perform action shown on screen (such as “Hold to
Accept”)
Data Entry  Tap once to move the cursor to the right.Hold to
perform action shown on screen (such as “Hold to
Cancel”)

Symbol(s) representing the status of a value may appear in the upper right of the display,
next to the description. Multiple symbols may display. If there are no data quality issues, no
symbols display.
Table 4-2: Symbols on Display

Symbol Meaning

Alarm: The parameter value shown is in an alarm state (such as High Alarm,
Low Alarm, etc.).
Override: The parameter value shown is in override mode (that is, a user-
entered fixed value).
Fault: The parameter value shown is somehow invalid.

Unverified: For parameter values that require additional validation (beyond


simple database min/max range checking), the firmware has not yet validated
the parameter value shown.

80 Operation
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Section 5. Service and Troubleshooting


This section covers the following topics:

 Returning the Unit for Repairs


 Interpreting the Status LEDs
 Switch and Buttons
 Removing/Replacing the HMI Module
 Replacing the Main Battery Pack
 Removing/Replacing the SRAM Battery
 Upgrading System Firmware

To maintain hazardous location certifications, you can only replace components in the field with
the exact same part so that the model string on the data plate remains correct. This means you
cannot add any hardware not reflected in the model string or upgrade a hardware component to a
newer version; any such upgrades are prohibited and void the hazardous location certification.

For a list of user serviceable parts contact your Emerson Remote Automation Solutions sales
representative or Emerson Impact Partner.

This chapter describes the service tasks that everyone needs to know such as replacing batteries or
installing a firmware upgrade. A separate series of field replacement guides covers major field
replaceable components.

Any replacement not covered in this chapter or in the field replacement guides (such as adding or
upgrading hardware or replacing sensors) can only be performed at an Emerson-authorized repair
facility.

Important
Use only batteries supplied with the flow computer or sold by Emerson as spare parts for this flow
computer. If you substitute a battery you obtain elsewhere you will void your certification unless it is
the identical part from the same manufacturer as that supplied with the flow computer from
Emerson.

Service and Troubleshooting 81


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021
Figure 5-1: FB1200 Flow Computer Components

1 Front end cap (cover)


2 HMI module
3 Battery pack
4 Data plate
5 Rear end cap (cover)
6 Threaded ¾ in NPT to M20 x 1.5 conduit fitting (2 of 4 shown)
7 Housing/Enclosure
8 Sensor Module
9 Mounting hardware

5.1. Returning the Unit for Repairs


Only certain field replacement procedures are allowed under warranty and hazardous location
certification. Other types of repairs cannot be performed in the field. In those cases, you must ship
the unit to an Emerson-authorized repair facility. Contact Emerson Remote Automation Solutions
for a return authorization number and instructions for where to ship the unit.

82 Service and Troubleshooting


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

WARNING
International safety regulations restrict the shipment of lithium batteries. If you need to return
the flow computer, remove the lithium battery before you ship the unit. Failure to remove the
lithium battery may delay or prevent shipment of the flow computer.

5.2. Interpreting the Status LEDs


The flow computer display has four (4) status LEDs. The meaning of each LED varies depending
upon the color displayed or whether the LED flashes.

Figure 5-2: LED Locations

1 Input LED
2 Link LED
3 Status LED
4 Alarm LED

Service and Troubleshooting 83


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Table 5-1: LED Descriptions

LED Color/State Meaning

An active wired Ethernet connection exists.


Link LED GREEN
Otherwise it is off. (FB1200/FB2200 only)

GREEN One of the IR buttons is being pressed.

Input LED CPU booting or CPU has not yet recognized


Flashing YELLOW HMI module when HMI first powered on; goes
off when recognized.

OK – Main power battery pack charged or not


GREEN
in use.

Main power battery pack low. Replace/re-


charge lead acid battery pack soon. (If FB1100
Flashing RED
Flow Computer with lithium battery pack–
replace battery pack.)
Status LED
FB1100 Flow Computer with lithium battery
pack only: Unit has switched to C cell battery
Flashing YELLOW
internal to battery pack. Replace battery pack
soon.

Off No power

Flashing GREEN Main power battery pack charging

GREEN No alarms.

HMI firmware update in progress.


Alarm LED Flashing RED

RED Alarms are present.

Table 5-2: Special LED Sequences using Multiple LEDs

LED Sequence Color/State

HMI module failed. Replace with spare or


Link, Input, Status, and Alarm all solid RED
return for repairs.

Link and Alarm alternately flash RED; sequence CPU stuck in boot mode. Contact technical
repeats support.

84 Service and Troubleshooting


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

5.3. Switch and Buttons


A momentary switch and two push buttons on the HMI module provide trouble-shooting options
for the flow computer.

DANGER
EXPLOSION HAZARD: Never remove end cap(s) in a hazardous location. Removing end cap(s) in a
hazardous location could result in an explosion.

Table 5-3: Switch and Buttons

Button Name Purpose Procedure

SYSTEM RESET Resets power. This momentary switch Move the SYSTEM RESET switch
interrupts power to the flow either up or down. Unit powers off
computer to reset it. Used if system is and then restarts.
powered on but is non-functional; this
attempts a reboot.

A Clears memory (SRAM). The SRAM 1. Press and hold the A button.
memory holds current data values and 2. While continuing to hold the A
pending alarm messages. If unit has button, move the SYSTEM RESET
unexpectedly stopped operating, you switch either up or down to
can depress this button on power-up initiate a reset.
to clear that information from 3. Release the A button. The system
memory (hard reset). Try this if a clears SRAM during the power up
SYSTEM RESET alone does not work. sequence.

B Currently undefined None

5.4. Removing/Replacing the HMI Module


You do not need to power down the unit to replace the HMI module.

DANGER
Ensure the flow computer is in a non-hazardous area. Never remove/replace the HMI module in a
hazardous area.

Important
The HMI module includes the FBxWifi transceiver; once you remove the HMI module; Wi-Fi
communication with the flow computer ceases.

1. Remove the retaining clamp from the front end cap (if present). (See Section 2.6.1.)
2. Unscrew the front end cap.
3. Loosen the four captive fastening screws on the HMI module.

Service and Troubleshooting 85


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 5-3: Captive Fastening Screws

4. Grasp the HMI module and remove it by gently pulling it straight out.
5. To replace the HMI module, line up the printed circuit board (PCB) with the slot on the back
and gently press it back on. Tighten the four captive fastening screws.
6. Replace the front end cap. Screw the end cap clockwise (eight full turns) until it is tightly
sealed to the enclosure. Replace the retaining clamp, if applicable (see Section 2.6.1).

5.5. Replacing the Main Battery Pack


Periodically you must replace the main battery pack. FBxConnect provides a battery life indicator to
show the number of days in use.

WARNING
If lead acid battery voltage falls below 4.7V, the battery can no longer be recharged, and the
charging system considers the battery dead. You must replace the battery.

Figure 5-4: Main Battery Pack

The device provides two battery connectors, enabling you to hot-swap the battery pack in a non-
hazardous location. Slide out the first battery pack (leaving it connected), attach the new battery to
86 Service and Troubleshooting
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021
the second (available) connector (so both batteries are connected), and then disconnect the old
battery pack.

DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

DANGER
EXPLOSION HAZARD: Do not disconnect equipment unless power has been removed or the area
is known to be non-hazardous.

DANGER
EXPLOSION HAZARD: Substitution of any components may impair suitability for Class I, Division 1
or Class I, Division 2.

DANGER
EXPLOSION HAZARD: Do not replace batteries unless power has been switched off or the area is
known to be non-hazardous. Batteries must only be changed in an area known to be non-
hazardous.

WARNING
There are no user-serviceable parts inside the battery pack. Do not open the battery pack as you
may damage the battery pack or injure yourself.

Restriction
Battery packs cannot be used with ATEX or IECEx applications.

Keep the replacement battery pack handy during the procedure.

1. Remove the retaining clamp from the front end cap (if present). (See Section 2.6.1.)
2. Remove the front end cap.
3. Loosen the two bottom captive fastening screws on the HMI module. Leave the two top
screws connected to the battery pack.
4. Grasp the HMI module and gently pull it and the battery pack out of the enclosure, leaving
the battery still connected.

Service and Troubleshooting 87


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 5-5: Removing the Battery Pack

5. Connect the new battery to the open connector. Route the wires so they are in the recessed
area. Make sure the wires won’t get caught in the end cap threads.
6. Disconnect the old battery pack’s connector from the unit and set the old battery pack aside.
7. Slide the new battery pack into the unit.
8. Loosen the top captive fastening screws on the HMI module to separate it from the old
battery pack.
9. Align the HMI module with the new battery pack and the tab on the CPU carrier board
(bezel). Gently press the assembly on, being careful not to pinch the battery wires.
Tighten all four screws.
10. Replace the front end cap. Screw the end cap clockwise (eight full turns) until it is tightly
sealed to the enclosure. Replace the retaining clamp, if applicable (see Section 2.6.1).

5.6. Removing/Replacing the SRAM Battery


A lithium coin cell battery provides backup power for the SRAM and the real time clock. The SRAM
backup battery can last for up to 10,000 hours of cumulative operation, and only runs if the main
power system fails. You do not need to power down the unit to replace the SRAM backup battery.

Important
 If the unit is ever powered down without the SRAM battery installed, SRAM data is lost. Always
back up your data before you remove the SRAM battery if you know that main power will also
be off.
 Replacement SRAM backup batteries must be either Rayovac® Model BR2335 or Panasonic®
Model BR2330.

DANGER
Ensure the flow computer is in a non-hazardous area. Never remove end caps in a hazardous area.

88 Service and Troubleshooting


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

DANGER
Do not disconnect equipment unless power has been removed or the area is known to be non-
hazardous.

DANGER
EXPLOSION HAZARD: Substitution of any components may impair suitability for Class I, Division 1
or Class I, Division 2.

DANGER
EXPLOSION HAZARD: Do not replace batteries unless power has been switched off or the area is
known to be non-hazardous. Batteries must only be changed in an area known to be non-
hazardous.

1. Remove the retaining clamp from the front end cap (if present). (See Section 2.6.1.)
2. Remove the front end cap.
3. Remove the HMI module.
4. Grasp the coin cell battery and remove it from its slot.

Figure 5-6: Removing/Replacing the Coin Cell Battery

5. Insert the new coin cell battery in the slot. The positive side (+) must be on top.

CAUTION
When inserting the SRAM coin cell battery, push the battery gently into its slot until it
stops. The battery should slide in easily. Do not use excessive force.

6. Replace the HMI module.


7. Replace the front end cap. Screw the end cap clockwise (eight full turns) until it is tightly
sealed to the enclosure. Replace the retaining clamp, if applicable (see Section 2.6.1.).

Service and Troubleshooting 89


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

5.7. Upgrading System Firmware


Periodically Emerson releases new system firmware for the flow computer to introduce new
features or update system functions.

You must know a valid username/password combination for the flow computer to complete this
process.

DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.

Important
 A power loss occurring during a firmware update to a unit with a dead SRAM coin cell battery
can corrupt SRAM memory and place the flow computer in a continuous boot cycle, requiring
you to return the device to the factory for repairs. To avoid this, be sure to replace the SRAM
coin cell battery when its power is low. To check this in FBxConnect, click Services > System
Power and look at the SRAM Battery Status field on the display.

 When upgrading system firmware version 01.xx.xx.xx to version 2.05.xx.xx or newer, allow
up to 10 minutes to complete the upgrade and do not power cycle the unit.

1. Launch Field Tools and use FBxConnect to connect to the flow computer.
2. Click the Services tab, then click Firmware Update.
3. Click Configuration Save to save the flow computer’s configuration.
4. Click History Collection to save the historical data contained in the flow computer.
5. Click Firmware Update.
6. In the Firmware Update dialog box, click Browse and navigate to the zip file containing your
new system firmware. The grid updates with details of the firmware version currently in the
device, and the firmware version in the zip file.

90 Service and Troubleshooting


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure 5-7: Firmware Update Dialog Box

7. Select the checkbox in the Selected column to choose the firmware. If you are downloading
the same version that is already installed on the device, select Download Even If Unchanged.
8. Select Time Sync device after the download if you want to sychronize the flow computer’s
clock with your PC clock after the download completes.

Click Start to begin the firmware download. Allow the download to proceed to completion. If
you choose to cancel the firmware download before it completes, the system restores the
current version already in the device.

Service and Troubleshooting 91


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Appendix A: Special Instructions for Class I


Division 2 Locations
1. The Emerson FB1200 Flow Computer is listed by Underwriters Laboratories (UL) as non-
incendive and is suitable for use in Class I, Division 2, Groups A, B, C and D hazardous
locations or nonhazardous locations. Read this appendix carefully before installing a non-
incendive Emerson FB1200 Flow Computer. Refer to the other chapters of this manual for
general information. In the event of a conflict between the other chapters of this manual and
this appendix, always follow the instructions in this appendix.
2. The Emerson FB1200 Flow Computer includes both non-incendive and unrated field circuits.
Unless a circuit is specifically identified in this appendix as non-incendive, the circuit is
unrated. Unrated circuits must be wired using wiring methods as specified in Article 501-4(b)
of the National Electrical Code (NEC), NFPA 70 for installations in the United States, or as
specified in Section 18-152 of the Canadian Electrical Code for installation in Canada.
3. All communication ports terminate on the terminal plate within the enclosure. Wiring to the
connectors is unrated. No connections may be made to communication ports unless the
user ensures that the area is known to be nonhazardous. Connections to the "Local Port" are
temporary and must be short in duration to ensure that flammable concentrations do not
accumulate while it is in use.
4. An RTD may be supplied with the Emerson FB1200 Flow Computer. Connection to the RTD is
approved as a non-incendive circuit so that Division 2 wiring methods are not required.
5. I/O connections are unrated and must be wired using Division 2 wiring methods.

DANGER
EXPLOSION HAZARD: Do not disconnect equipment unless power has been removed or the area
is known to be non-hazardous.

DANGER
EXPLOSION HAZARD: Substitution of any components may impair suitability for Class I, Division
1 or Class I, Division 2.

DANGER
EXPLOSION HAZARD: Do not replace batteries unless power has been switched off or the area is
known to be non-hazardous. Batteries must only be changed in an area known to be non-
hazardous.

Special Instructions for Class I Division 2 Locations 93


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure A-1: Data Plate (No Battery) – Class I Division 2 Non-incendive (UL)

94 Special Instructions for Class I Division 2 Locations


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure A-2: Data Plate (Lead Acid Battery) – Class I Division 2 Non-incendive (UL)

Special Instructions for Class I Division 2 Locations 95


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

96 Special Instructions for Class I Division 2 Locations


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Appendix B: Special Instructions for Class I


Division 1 Locations
1. The Emerson FB1200 Flow Computer is listed by Underwriters Laboratories (UL) as explosion
proof and is suitable for use in Class I, Division 1, Groups C and D hazardous locations or
nonhazardous locations. Read this appendix carefully before installing an Emerson FB1200
Flow Computer. Refer to the other chapters of this manual for general information. In the
event of a conflict between the other chapters of this manual and this appendix, always
follow the instructions in this appendix.
2. The Emerson FB1200 Flow Computer includes both non-incendive and unrated field circuits.
Unless a circuit is specifically identified in this appendix as non-incendive, the circuit is
unrated. Unrated circuits must be wired using wiring methods as specified in Article 501-4(b)
of the National Electrical Code (NEC), NFPA 70 for installations in the United States, or as
specified in Section 18-152 of the Canadian Electrical Code for installation in Canada.

DANGER
Though the Emerson FB1200 Flow Computer has a local port for local interrogation, it
should not be accessed with the cover removed in a Class I Division 1 area unless it has first
been verified that no flammable concentrations exist in that area. The local port may be
wired through a conduit, using seals, to an unclassified or Division 2 area.

3. All communication ports terminate on the terminal plate within the enclosure. Wiring to the
connectors is unrated. No connections may be made to communication ports unless the
user ensures that the area is known to be nonhazardous. Connections to the "Local Port" are
temporary and must be short in duration to ensure that flammable concentrations do not
accumulate while it is in use.
4. An RTD may be supplied with the Emerson FB1200 Flow Computer. Connection to the RTD is
approved as a non-incendive circuit.

Note
A bendable RTD (with a plastic bushing, as utilized in Division 2 installations) may not be
used in a Division 1 area as it renders the area non-explosion proof. Use an RTD connection
head and explosion-proof conduit for Division 1 installations.

5. I/O connections are unrated and must be wired using wiring methods as specified in Article
501-4(b) of the National Electrical Code (NEC), NFPA 70 for installations in the United States, or
as specified in Section 18-152 of the Canadian Electrical Code for installation in Canada.

Special Instruction for Class I Division 1 Locations 97


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

DANGER
EXPLOSION HAZARD: Do not disconnect equipment unless power has been removed or the area
is known to be non-hazardous.

DANGER
EXPLOSION HAZARD: Substitution of any components may impair suitability for Class I, Division
1 or Class I, Division 2.

DANGER
EXPLOSION HAZARD: Do not replace batteries unless power has been switched off or the area is
known to be non-hazardous. Batteries must only be changed in an area known to be non-
hazardous.

DANGER
The area must be known to be non-hazardous before servicing the unit and before installing or
removing I/O wiring.

98 Special Instructions for Class I Division 1 Locations


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure B-1: Data Plate (No Battery) – Class I Division 1 Explosion Proof (UL)

Special Instruction for Class I Division 1 Locations 99


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Figure B-2: Data Plate (Lead Acid Battery) – Class I Division 1 Explosion Proof (UL)

100 Special Instructions for Class I Division 1 Locations


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Appendix C: ATEX Non-Sparking Zone 2


Certifications
This appendix includes notes on ATEX certifications. For full details, please refer to the Emerson
FB1200 Flow Computer Safe Use Instructions (D301769X012).

Special Conditions of Use:

 Make provisions to ensure, in the event of transient disturbances, that the rated voltage does
not exceed 140% of the peak rated voltage.

 Impact tests on the display were conducted based on Group II values for the low risk of
mechanical danger, in accordance with Table 13 of both EN 60079-0:2012+A11:2013 and
IEC 60079-0 6th Edition. Install flow computers with displays in areas where the risk of impact
is low.

 Lead Acid Battery, and Solar Panel options are not for use in ATEX/ IECEx applications.

 For Zone 2 installation, take care to install and use the flow computer in such a way that
excludes the danger of electrostatic charge.

 Refer to field replacement guides for replacement of the following parts:

Field Replacement Guide


Replacement Part Kit Number document number
End Caps 399122-01-0 and D301814X012
399123016-KIT
HMI Module Display Assembly 399379-01-0, 621627011- D301816X012
KIT, 399380-01-0,
621627020-KIT
CPU Board 399134018-KIT D301802X012
Termination Board and 399185-01-1, 400216010- D301820X012
Terminal Block KIT, 395791014-KIT
395803000-KIT
6-Channel I/O Expansion 400215-01-0 D301819X012
Board
Sensor Assembly Variable Kit Number D301842X012
Coin Cell Battery 395620-03-1 D301854X012

This device was evaluated according to the following standards:


 IEC 60079-0 6th Edition
 IEC 60079-15 4th Edition
 EN 60079-0 :2012+A11:2013
 EN 60079-15:2010

ATEX Non-Sparking Zone 2Certifications 101


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021
Enclosure Rating: IP66

Terminal blocks for the FB1200 Flow Computer have the following characteristics:
 Terminal blocks can accommodate two conductors per channel.
 Stranded or solid wire allowed.
 Torque values: NM 0.5-0.6
 Wire size: 28-12 AWG (0.08 – 3.3 mm2); (0.32 – 2.05 mm)
Bristol Inc. d.b.a. Remote Automation Solutions
1100 Buckingham Street
Watertown, CT 06795 U.S.A.

Figure C-1: Data Plate – ATEX nA Non-Sparking

102 ATEX Non-Sparking Zone 2 Certifications


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Appendix D: ATEX Flame-Proof Zone 1


Certifications
The data plate and certain conditions of use are shown below. For full details refer to the Emerson
FB1200 Flow Computer Safe Use Instructions (D301769X012).

Figure D-1: Data Plate – ATEX Ex db Flame-proof

ATEX Flame-Proof Zone 1 Certifications 103


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021
Special Conditions of Use / Schedule of Limitations:

 Contact your authorized sales and service representative for any maintenance or repair
beyond the routine maintenance of the FB1200 Flow Computer. Do not alter or disassemble
any of the fireproof joints of the FB1200 Flow Computer.
 The Model 4088 and Model 215 Scalable Pressure Transmitters provided with the FB1200
Flow Computer contain a thin-wall diaphragm. Installation, maintenance, and use must take
into account the environmental conditions to which the diaphragm is subjected. Follow the
manufacturer’s instructions for installation and maintenance to ensure safety during the
device’s lifetime.

 Refer to field replacement guides for replacement of the following parts:

Field Replacement Guide


Replacement Part Kit Number document number:
End Caps 399122-01-0 and D301814X012
399123016-KIT
HMI Module Display Assembly 399379-01-0, 621627011- D301816X012
KIT, 399380-01-0,
621627020-KIT
CPU Board 399134018-KIT D301802X012
Termination Board and 399185-01-1, 400216010- D301820X012
Terminal Block KIT, 395791014-KIT
395803000-KIT
6-Channel I/O Expansion 400215-01-0 D301819X012
Board
Sensor Assembly Variable Kit Number D301842X012
Coin Cell Battery 395620-03-1 D301854X012

This device was evaluated according to the following standards:

 IEC 60079-0, 6th Edition


 IEC 60079-1, 7th Edition
 EN 60079-0:2012+A11:2013
 EN 60079-1:2014

104 ATEX Flame-Proof Zone 1 Certifications


Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Index

4 Ethernet .............................................................. 49
I/O ....................................................................... 51
4088B transmitter ................................................... 72
ports ................................................................... 41
A power .................................................................. 31
Analog Inputs .......................................................... 55 RTD ..................................................................... 69
Analog Outputs ....................................................... 59 solar power ......................................................... 39
ATEX Certification Coplanar mounting kit ............................................ 23
notes about ................................................ 101, 103 Covers
ATEX Zone 1 .......................................................... 103 removing........................................................ 15, 17
ATEX Zone 2 .......................................................... 101 replacing ............................................................. 18
Attaching Mounting Hardware to the Solar Panel ..... 34 D
B Daily operation ....................................................... 75
Battery DC power
connecting ........................................................... 33 connecting .......................................................... 32
Bolting Considerations ............................................. 18 Digital Inputs .......................................................... 61
Digital Outputs ....................................................... 64
C Direct mounting ..................................................... 21
Case
E
rotating ................................................................ 24
Class I Division 1 ....................................................... 97 Enclosure
Class I Division 2 ....................................................... 93 mounting the ...................................................... 18
COM1 End caps
wiring ................................................................... 41 removing........................................................ 15, 17
COM2 replacing ............................................................. 18
wiring ................................................................... 44 Environmental Specifications .................................. 11
COM3 Equipment required for servicing the unit ............... 12
wiring ................................................................... 44 Ethernet
Communication connecting .......................................................... 49
establishing .......................................................... 75 Ethernet communications ....................................... 76
through an Ethernet port...................................... 76 Ethernet Port
to a laptop using a wireless connection................. 77 Location .............................................................. 49
to laptop through a serial port .............................. 76 F
using HMI module ................................................ 78
FBxWifi.................................................................... 77
with SCADA host .................................................. 75
Figures
Communication ports
2-1. FB1200 Flow Computer Dimensions –
connecting ........................................................... 41
Multivariable Sensor Version ............................ 13
Connecting
2-2. FB1200 Flow Computer Dimensions (No
4088B transmitter ................................................ 72
Integral Sensor) ............................................... 14
battery ................................................................. 33
2-3. FB1200 Flow Computer Dimensions (with Static
DC power ............................................................. 32
Pressure Sensor) .............................................. 15
Index 105
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021
2-4. Front End Cap with Retaining Clamp Fitted .... 16 3-4. 4-20 mA AI Wiring (Base I/O with Optional I/O
2-5. Retaining Clamp in Place ............................... 16 Module) ........................................................... 56
2-6. Retaining Clamp and Screw ........................... 16 3-5. 1-5 V AI Wiring (Base I/O with Optional I/O) .. 56
2-7.Removing or Tightening the End Cap with 3-6. AI Wiring (Base I/O without Optional I/O
Prybar ............................................................... 17 Module) ........................................................... 57
2-8. Front (left) and Rear (right) End Caps ............. 17 3-7. 4-20 mA AI Wiring (with Optional 6-channel
2-9. Front (left) and Rear (right) End Caps Removal Expansion I/O Module) ..................................... 58
......................................................................... 18 3-8. 1-5 V Analog Input (AI) Wiring (with Optional 6-
2-10. Transmitter with Coplanar Flange ................ 19 channel Expansion I/O Module) ........................ 58
2-11. Transmitter with Coplanar Flange and 3-9. AO Wiring (Base I/O with Optional I/O) ......... 60
Optional Flange Adapters ................................. 19 3-10. AO Wiring – (Base I/O without Optional I/O) 60
2-12. Transmitter with Traditional Flange and 3-11. AO Wiring (with Optional 6-channel Expansion
Optional Flange Adapters ................................. 19 I/O Module) ..................................................... 61
2-13. Bolt Installation ........................................... 20 3-12. DI Wiring (Base I/O with Optional I/O) ......... 62
2-14. O-rings (w/ Flange Adapters ........................ 21 3-13. DI Wiring (Base I/O -without Optional I/O) .. 63
2-15. Traditional Flange Mounting Kit................... 22 3-14. DI Wiring - (with Optional 6-channel Expansion
2-16. Coplanar Mounting Kit ................................ 23 I/O Module) ..................................................... 63
2-17. Inline Mounting Kit ...................................... 24 3-15. DO Wiring (Base I/O with Optional I/O) ....... 65
2-18. Housing Rotation Set Screws ....................... 25 3-16. DO Wiring (Base I/O without Optional I/O).. 66
2-19. Ground Lug ................................................. 26 3-17. DO Wiring (with Optional 6-channel Mixed I/O
2-20. Terminal Plate ............................................. 27 Module ............................................................ 66
2-21.DC Power Connections ................................. 32 3-18. PI Wiring (Base I/O with Optional I/O) ......... 68
2-22. Connecting the Battery Pack ....................... 33 3-19. PI Wiring (Base I/O without Optional I/O ..... 68
2-23. Attaching Mounting Hardware to the Solar 3-20. PI Wiring (with Optional I/O Module) .......... 69
Panel ................................................................ 35 3-21. Wiring for 2-, 3-, and 4-Wire RTD (Units with
2-24. Integral mounted solar panel....................... 37 Optional I/O).................................................... 70
2-25. Solar panel remote mounted (pole mounted) 3-22. Wiring for 2-Wire, 3-Wire, and 4-Wire RTD
......................................................................... 38 (Units without Optional I/O)............................. 71
2-26. Wiring Solar Power ...................................... 39 3-23. Connecting a 4088B Transmitter for a Second
2-27. Adjusting Solar Panel Tilt Angle ................... 40 Meter Run ........................................................ 72
2-28. Connecting a Device to COM1 Using RS-23242 4-1. Waking the Display ....................................... 78
2-29. Connecting a Device to COM1 Using RS- 4-2. Infrared (IR) Button Location......................... 79
485/422 (4-wire) .............................................. 43 A-1. Data Plate (No Battery) – Class I Div 2 Non-
2-30. Connecting a Device to COM1 Using RS-485 incendive (UL) .................................................. 94
(2-wire) ............................................................ 44 A-2. Data Plate (Lead Acid Battery) – Class I Div 2
2-31. Connecting a Device to COM2 or COM3 Using Non-incendive (UL) .......................................... 95
RS-232 (with Optional I/O) ................................ 45 B-1. Data Plate (No Battery) – Class I Div 1 Explosion
2-32. Connecting a Device to COM2 or COM3 Using Proof (UL) ........................................................ 99
RS-232 (without optional I/O) ........................... 46 B-2. Data Plate (Lead Acid Battery) – Class I Div 1
2-33. Connecting a Device to COM2 or COM3 Using Explosion Proof (UL) ....................................... 100
RS-485 (2-wire) (with optional I/O) ................... 47 C-1. Data Plate – ATEX nA Non-Sparking ............ 102
2-34. Connecting a Device to COM2 or COM3 Using D-1. Data Plate – ATEX Ex db Flame-proof .......... 103
RS-485 (2-wire) (without optional I/O) .............. 48 Flameproof
2-35. Location of Ethernet Port ............................. 49 ATEX Zone 1 certification notes ......................... 103
2-36. Ethernet Jumper .......................................... 50
3-1. Base I/O on CPU (with optional I/O) ............... 52
G
3-2. Base I/O On CPU (without Optional I/O) ......... 53 Grounding .............................................................. 26
3-3. Optional 6-channel Expansion I/O Board ........ 54

106 Index
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

H Pulse Inputs ............................................................ 67


Hazardous locations................................................. 11 R
ATEX Zone 1 ....................................................... 103
Removing/Replacing End Cap Retaining Clamp ....... 16
ATEX Zone 2 ....................................................... 101
Rotating the housing............................................... 24
Class I Division 1 ................................................... 97
RTD
Class I Division 2 ................................................... 93
connecting .......................................................... 69
HMI module ............................................................. 78
Run 2 transmitter
symbols on display ............................................... 80
connecting .......................................................... 72
Housing
rotating ................................................................ 24 S
I Screen Saver Mode .................................................. 79
Second meter run
I/O
connections for ................................................... 72
configuration and wiring ...................................... 51
Serial communications ............................................ 76
Indirect mounting .................................................... 21
Site considerations .................................................. 12
Inline mounting kit................................................... 24
Solar panel
Installation ............................................................... 11
adjusting the tilt angle ......................................... 40
L installing the optional .......................................... 34
integral mounting ............................................... 36
LCD
remote mount (pole mount) ............................... 38
communicating using .......................................... 78
remote mounted (pole) ....................................... 38
Location of Ethernet port ......................................... 49
Solar power
Low Power Mode ..................................................... 28
connecting .......................................................... 39
M Standard Power Mode ............................................. 30
Mounting Symbols
direct ................................................................... 21 on LCD display ..................................................... 80
indirect ................................................................ 21 T
Mounting kit
Tables
coplanar ............................................................... 23
2-1. Environmental Specifications........................ 12
inline .................................................................... 24
2-2. Required Tools ............................................. 12
traditional ............................................................ 22
2-4. Typical Power Usage– Low Power Mode........ 29
N 2-5. Typical Power Usage (Standard Power Mode)30
Non-sparking 2-6. Solar Panel Tilt Angle .................................... 41
ATEX Zone 2 certification notes .......................... 101 2-3. Bolt Torque Values ....................................... 20
Notes on Battery Life ................................................ 31 3-1. AI Characteristics .......................................... 55
3-2. AO Characteristics ........................................ 59
O 3-3. DI Characteristics.......................................... 61
Operation ................................................................ 75 3-4. DO Characteristics ........................................ 64
O-rings .................................................................... 20 3-5. PI Characteristics .......................................... 67
4-1. Infrared (IR) Buttons on HMI Module ............. 80
P 4-2. Symbols on Display ....................................... 80
Ports Terminal plate ......................................................... 27
connecting ........................................................... 41 Tools required ......................................................... 12
Power Traditional flange mounting kit ............................... 22
connecting ........................................................... 31 Transmitter
turning ON or OFF ................................................ 75 connecting for a second meter run ...................... 72
Power Modes ........................................................... 28

Index 107
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

W Z
Wi-Fi ........................................................................ 77 Zone 2
Wiring ATEX certification .............................................. 101
guidelines ............................................................ 15 Zone1
I/O........................................................................ 51 ATEX certification .............................................. 103

108 Index
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

Index 109
Emerson FB1200 Flow Computer Instruction Manual
D301782X012
July 2021

For customer service and technical support,


visit www.Emerson.com/SupportNet
Global Headquarters,
North America, and Latin America:
Emerson Automation Solutions
Remote Automation Solutions
6005 Rogerdale Road
Houston, TX 77072 U.S.A.
T +1 281 879 2699 | F +1 281 988 4445
www.Emerson.com/RemoteAutomation
Europe:
Emerson Automation Solutions
Remote Automation Solutions
Unit 1, Waterfront Business Park
Dudley Road, Brierley Hill
Dudley DY5 1LX UK
T +44 1384 487200
Middle East/Africa:
Emerson Automation Solutions
Remote Automation Solutions
Emerson FZE
P.O. Box 17033 © 2018-2021 Remote Automation Solutions, a business unit of Emerson Automation
Jebel Ali Free Zone – South 2 Solutions. All rights reserved.
Dubai U.A.E.
T +971 4 8118100 | F +971 4 8865465 This publication is for informational purposes only. While every effort has been made to ensure
accuracy, this publication shall not be read to include any warranty or guarantee, express or
Asia-Pacific: implied, including as regards the products or services described or their use or applicability.
Emerson Automation Solutions Remote Automation Solutions (RAS) reserves the right to modify or improve the designs or
Remote Automation Solutions specifications of its products at any time without notice. All sales are governed by RAS terms
1 Pandan Crescent and conditions which are available upon request. RAS accepts no responsibility for proper
Singapore 128461 selection, use or maintenance of any product, which remains solely with the purchaser and/or
T +65 6777 8211| F +65 6777 0947 end-user.

Remote Automation Solutions

You might also like