Current Ratings

Page 1 of 2

NYY & NYCY unarmoured power cables


These charts relate, to unarmoured power cables with PVC core insulation and PVC outer
sheathing, such as NYY & NYCY. The figures shown are to be considered as guiding values only.

Current Carrying Capacity in Ampere (Amps)


Based on laying in ground with an ambient ground temperature of 20°C

Nominal NYY type (unscreened) NYCY type (screened)


Area 2-3 single core multicore, 3 or one single 2-3 single core multicore, 3 or
(mm²) cables, trefoil 4 loaded cores core cable* cables, trefoil 4 loaded cores
1.5 30 27 41 31 27
2.5 39 36 55 40 36
4.0 50 47 71 51 47
6.0 62 59 90 63 59
10 83 79 124 84 79
16 107 102 160 108 102
25 138 133 208 139 133
35 164 159 250 166 160
50 195 188 296 196 190
70 238 232 365 238 234
95 286 280 438 281 280
120 325 318 501 315 319
150 365 359 563 347 357
185 413 406 639 385 402
240 479 473 746 432 463
300 541 535 848 473 518
400 614 613 975 521 579
500 693 687 1125 574 624
630 777 - 1304 636 -
800 859 - 1507 - -
1000 936 - 1715 - -
* Rated current for direct current systems with a far-distanced return conductor

Conversion factors ≥ 5 core cables, 1.5mm² to 10.0mm², against above table


Loaded Cores: 5 7 10 14 19 24 40 61
Factor: 0.75 0.65 0.55 0.50 0.45 0.40 0.35 0.30

Conversion factors for deviating ambient air temperature


Temperature: 10°C 15°C 20°C 25°C 35°C 40°C 45°C 50°C
Factor: 1.15 1.12 1.08 1.04 0.96 0.91 0.87 0.82

Continued on following page


Current Ratings
Page 2 of 2

NYY & NYCY unarmoured power cables

Continued from previous page:

Current Carrying Capacity in Ampere (Amps)


Based on laying in free air with an ambient air temperature of 30°C
Nominal NYY type (unscreened) NYCY type (screened)
Area 2-3 single core multicore, 3 or one single 2-3 single core multicore, 3 or
(mm²) cables, trefoil 4 loaded cores core cable* cables, trefoil 4 loaded cores
1.5 21 19.5 27 22 19.5
2.5 28 25 35 29 26
4.0 37 34 47 39 34
6.0 47 43 59 49 44
10 64 59 81 67 60
16 84 79 107 89 80
25 114 106 144 119 108
35 139 129 176 146 132
50 169 157 214 177 160
70 213 199 270 221 202
95 264 246 334 270 249
120 307 285 389 310 289
150 352 326 446 350 329
185 406 374 516 399 377
240 483 445 618 462 443
300 557 511 717 519 504
400 646 597 843 583 577
500 747 669 994 657 626
630 858 - 1180 744 -
800 971 - 1396 - -
1000 1078 - 1620 - -
* Rated current for direct current systems with a far-distanced return conductor

Conversion factors ≥ 5 core cables, 1.5mm² to 10.0mm², against above table


Loaded Cores: 5 7 10 14 19 24 40 61
Factor: 0.10 0.60 0.50 0.45 0.40 0.35 0.30 0.25