Address:
Cseresznyefa u. 60/3 Examination of ESD MUF_07_05_01D-5
Tel/Fax: 06/34 744-642
Mobil 1: 06/30 216-4583 properties under Page 1/1
Mobil 2: 06/30 335-6586 Revised 04
E-mail: [email protected] laboratory conditions Date of issue 2013.09.01
Introductory data
QUALIFICATION DATA SHEET: Description of the sample, brief introduction and summary
ANNEX I. Measurement results obtained during the certification of the sample
Important! The qualification report is complete and valid only in the presence of all attachments.
Notes
Introductory
Refference data
documents
IEC 61340-5-1:2016 - Electrostatics – Part 5-1: Protection of electronic devices from electrostatic
phenomena – General requirements
ANSI-ESD S20.20:2014 - For the Development of an Electrostatic Discharge Control Program for –
Protection of Electrical and Electronic Parts, Assemblies and Equipment (Excluding Electrically
Initiated Explosive Devices)
Summary
Based on qualification measurements carried out under normal environmental conditions, it can be concluded that the
flooring samples coated with the Dr Schutz ESD Sealers meet the requirements of IEC 61340-5-1:2016 and ANSI/ESD
20.20 International ESD standards. From the measurements made with the copper grounding electrode it can be stated that
from the ESD point of view, the surface treatment with Dr Schutz coatings improves the homogeneity of the floors
independently of the layer system,so that floors properly ground the mobile devices like wagons, charts, chairs, etc. The
results also show that the test surfaces coated with Dr Schutz ESD coatings improve the suitability of floor and human
system resistance.
Type of ESD floor for tests Required measurement results Comparison of measured results
Mesurement 1 Measurement 2 Measurement 3
Measuremen
Limits
number
Sample
t types
Date: 2017.09.12. Date: 2017.--.--. Date: 2017.--.--. Notes
Floor type Measured points
Measured Measured Measured
Low High value
Unit Compliance
value
Unit Compliance
value
Unit Compliance
Material: between points 1 and 2 Rp-p 1.0×104 Ω 1.0×109 Ω 173 kΩ OK - - - - - - Original floor
STO POX KU
615 between points 3 and 4 Rp-p 1.0×104 Ω 1.0×109 Ω 298 kΩ OK - - - - - -
(original Coated floor
flooring) between points 5 and 6 Rp-p 1.0×104 Ω 1.0×109 Ω 278 kΩ OK - - - - - -
Relation between the original and the
Dr. Schutz between points 9 and 7 Rp-p 1.0×104 Ω 1.0×109 Ω 111 kΩ OK - - - - - -
coated floor surface
Sample 2017_01
material
between point 9 and grounding Rgp 1.0×104 Ω 1.0×109 Ω 98.4 kΩ OK - - - - - - Original floor
layout: ESD
Color Base 2 between point 7 and grounding Rgp 1.0×104 Ω 1.0×109 Ω 879 kΩ OK - - - - - - Coated floor
coats
between point 9 and grounding
ESD TopCoat Rgp 1.0×104 Ω 1.0×109 Ω 100 GΩ NOK - - - - - - Original floor
(copper earth electrode)
1 coat
between point 7 and grounding 4 9
(copper earth electrode)
Rgp 1.0×10 Ω 1.0×10 Ω 9.41 MΩ OK - - - - - - Coated floor
System measurement to
original floor
Rsys. - 1.0×109 Ω 13.8 MΩ OK - - - - - - Original floor
System measurement to
coated floor
Rsys. - 1.0×109 Ω 6.36 MΩ OK - - - - - - Coated floor
Material: between points 1 and 2 Rp-p 1.0×104 Ω 1.0×109 Ω 157 kΩ OK - - - - - - Original floor
STO POX KU
611 between points 3 and 4 Rp-p 1.0×104 Ω 1.0×109 Ω 324 kΩ OK - - - - - -
(original Coated floor
4 9
flooring) between points 5 and 6 Rp-p 1.0×10 Ω 1.0×10 Ω 900 kΩ OK - - - - - -
Relation between the original and the
Dr. Schutz between points 9 and 7 Rp-p 1.0×104 Ω 1.0×109 Ω 110 kΩ OK - - - - - -
Sample 2017_02
Type of ESD floor for tests Required measurement results Comparison of measured results
Mesurement 1 Measurement 2 Measurement 3
Measuremen
Limits
number
Sample
t types
Date: 2017.09.12. Date: 2017.--.--. Date: 2017.--.--. Notes
Floor type Measured points
Measured Measured Measured
Low High value
Unit Compliance
value
Unit Compliance
value
Unit Compliance
Material: between points 1 and 2 Rp-p 1.0×104 Ω 1.0×109 Ω 1.73 MΩ OK - - - - - - Original floor
STO POX KU
613 between points 3 and 4 Rp-p 1.0×104 Ω 1.0×109 Ω 275 kΩ OK - - - - - -
(original Coated floor
flooring) between points 5 and 6 Rp-p 1.0×104 Ω 1.0×109 Ω 660 kΩ OK - - - - - -
Relation between the original and the
Dr. Schutz between points 9 and 7 Rp-p 1.0×104 Ω 1.0×109 Ω 674 kΩ OK - - - - - -
Sample 2017_03
Type of ESD floor for tests Required measurement results Comparison of measured results
Mesurement 1 Measurement 2 Measurement 3
Measuremen
Limits
number
Sample
t types
Date: 2017.09.12. Date: 2017.--.--. Date: 2017.--.--. Notes
Floor type Measured points
Measured Measured Measured
Low High value
Unit Compliance
value
Unit Compliance
value
Unit Compliance
Material: between points 1 and 2 Rp-p 1.0×104 Ω 1.0×109 Ω 10.5 MΩ OK - - - - - - Original floor
Graboplast
ESD PVC between points 3 and 4 Rp-p 1.0×104 Ω 1.0×109 Ω 384 kΩ OK - - - - - -
(original Coated floor
flooring) between points 5 and 6 Rp-p 1.0×104 Ω 1.0×109 Ω 333 kΩ OK - - - - - -
Relation between the original and the
Dr. Schutz between points 9 and 7 Rp-p 1.0×104 Ω 1.0×109 Ω 1.48 MΩ OK - - - - - -
Sample 2017_05
Type of ESD floor for tests Required measurement results Comparison of measured results
Mesurement 1 Measurement 2 Measurement 3
Measuremen
Limits
number
Sample
t types
Date: 2017.09.12. Date: 2017.--.--. Date: 2017.--.--. Notes
Floor type Measured points
Measured Measured Measured
Low High value
Unit Compliance
value
Unit Compliance
value
Unit Compliance
Material: between points 1 and 2 Rp-p 1.0×104 Ω 1.0×109 Ω 170 kΩ OK - - - - - - Original floor
STO POX KU
611 between points 3 and 4 Rp-p 1.0×104 Ω 1.0×109 Ω 190 kΩ OK - - - - - -
(original Coated floor
flooring) between points 5 and 6 Rp-p 1.0×104 Ω 1.0×109 Ω 120 kΩ OK - - - - - -
Relation between the original and the
Dr. Schutz between points 9 and 7 Rp-p 1.0×104 Ω 1.0×109 Ω 100 kΩ OK - - - - - -
Sample 2017_07
Type of ESD floor for tests Required measurement results Comparison of measured results
Mesurement 1 Measurement 2 Measurement 3
Measuremen
Limits
number
Sample
t types
Date: 2017.09.12. Date: 2017.--.--. Date: 2017.--.--. Notes
Floor type Measured points
Measured Measured Measured
Low High value
Unit Compliance
value
Unit Compliance
value
Unit Compliance
Material: between points 1 and 2 Rp-p 1.0×104 Ω 1.0×109 Ω 139 MΩ OK - - - - - - Original floor
Tarkett TORO
(original between points 3 and 4 Rp-p 1.0×104 Ω 1.0×109 Ω 538 kΩ OK - - - - - -
flooring) Coated floor
between points 5 and 6 Rp-p 1.0×104 Ω 1.0×109 Ω 486 MΩ OK - - - - - -
Dr. Schutz Relation between the original and the
material between points 9 and 7 Rp-p 1.0×104 Ω 1.0×109 Ω 84.4 MΩ OK - - - - - -
Sample 2017_09
Type of ESD floor for tests Required measurement results Comparison of measured results
Mesurement 1 Measurement 2 Measurement 3
Measuremen
Limits
number
Sample
t types
Date: 2017.09.12. Date: 2017.--.--. Date: 2017.--.--. Notes
Floor type Measured points
Measured Measured Measured
Low High value
Unit Compliance
value
Unit Compliance
value
Unit Compliance
Material: between points 1 and 2 Rp-p 1.0×104 Ω 1.0×109 Ω 150 kΩ OK - - - - - - Original floor
STO POX KU
611 between points 3 and 4 Rp-p 1.0×104 Ω 1.0×109 Ω 2.12 MΩ OK - - - - - -
(original Coated floor
flooring) between points 5 and 6 Rp-p 1.0×104 Ω 1.0×109 Ω 762 kΩ OK - - - - - -
Relation between the original and the
Dr. Schutz between points 9 and 7 Rp-p 1.0×104 Ω 1.0×109 Ω 150 kΩ OK - - - - - -
Sample 2017_11
Type of ESD floor for tests Required measurement results Comparison of measured results
Mesurement 1 Measurement 2 Measurement 3
Measuremen
Limits
number
Sample
t types
Date: 2017.09.12. Date: 2017.--.--. Date: 2017.--.--. Notes
Floor type Measured points
Measured Measured Measured
Low High value
Unit Compliance
value
Unit Compliance
value
Unit Compliance
Type of ESD floor for tests Required measurement results Comparison of measured results
Mesurement 1 Measurement 2 Measurement 3
Measuremen
Limits
number
Sample
t types
Date: 2017.09.12. Date: 2017.--.--. Date: 2017.--.--. Notes
Floor type Measured points
Measured Measured Measured
Low High value
Unit Compliance
value
Unit Compliance
value
Unit Compliance
Material:
Measurement points
6
Coated surface
3 7 4
Original flooring
1 9 2
Grounding point
2800 Tatabánya Document ID:
Address:
Cseresznyefa u. 60/3
Tel/Fax: 06/34 744-642 Examination of ESD properties under MUF_07_05_01D-5
Mobil 1: 06/30 216-4583 Page: 1/1
Mobil 2: 06/30 335-6586 laboratory conditions Revised: 04
E-mail: [email protected] Date of issue: 2013.09.01
Measurement
Measurement limit
The schematic diagram or photo of the measurements
types
Sample type Notes
Low: High:
Gigaohm meter
Weight electrode
Weight electrode
Flooring
Gigaohm meter
Weight electrode
Measurement points: see Grounding
- Rgp - 1.0×109 Ω
annex I point
Flooring
Flooring
samples coated
with Dr Schutz Gigaohm meter
materials
Flooring
Gigaohm
Man
metter
standing
on an ESD
Floor
Flooring