GCBS Manual
GCBS Manual
FOR
PLC BASED GALLEY CALL BELL SYSTEM
CLIENT : GOA SHIPYARD LIMITED
YARD No. : 1234
P.O.No. : 185281
DATE : 23/10/2017
USER : COAST GUARD
FABRICONS
74, MAROL CO-OP. INDUSTRIAL ESTATE,
www.fabricons.in
Page 2 of 45
11.6 LOC - LO’S CABIN..................................................................................................... 35
11.7 LOC - WARDROOM...................................................................................................36
12. CABLE FLOW DIAGRAM FOR PLC BASED GALLEY CALL BELL SYSTEM... 38
13. EXTERNAL WIRING OF PLC BASED GALLEY CALL BELL SYSTEM..............41
14. PLC ADDRESSING.......................................................................................................44
Page 3 of 45
1. PRODUCT ORDER REFERENCE
1.1 EQUIPMENT
b) XO’s CABIN
c) EO’s CABIN
d) LO’s CABIN.
e) WARD ROOM.
1.2 CLIENT
Page 4 of 45
1.3 INSPECTION AUTHORITY
MANUFACTURE’S QC DEPT.
1.5 MANUFACTURER
FABRICONS
www.fabricons.in
Page 5 of 45
2. UNPACKING, STORAGE & HANDLING
2.1 UNPACKING
2.2 STORAGE
2.3 HANDLING
PLC Based Galley Call Bell System contains parts like PLC, Lamps,
Push Buttons, Hooters & Relays and therefore should be handled
carefully.
Page 6 of 45
3. TECHNICAL MANUAL
3.1 TECHNICAL DESCRIPTION
PURPOSE: -
2. EO’s Cabin
3. LO’s Cabin
4. Ward Room
5. XO’s Cabin
OPERATION
Page 7 of 45
noticed. Once the call is attended, the RESET push button is to be
pressed. This button is also provided in each officer’s cabin.
This ensures that Galley or Pantry staff cannot reset the call
without attending the officer.
Door & gland plate are provided with neoprene rubber gasket all
around. The hinged door of main control panel is provided with
door stopper. The panels in commanding officer room & officers
dining hall have screwed cover.
All tally plates are with black background and white letters, since
the complete system is fabricated using PLC. Each panel is
provided with diagram relevant to respective panel for connection
purpose.
3.3 PAINTING
Page 8 of 45
3.4 DIMENSIONS AND WEIGHT
Total weight of all panels is within 30 kg. The dimensions & weight
are kept minimum without impairing technical requirement. For
details of dimensions, refer following AS MADE drawings:
CABLE GLAND: All cables enter the panels from the bottom
through cable glands. The bottom plate of the panels in Galley and
Pantry are detachable. CO’S Day Cabin, XO’S Cabin, EO’S Cabin,
LO’S Cabin, Ward Room Cabin panel has non-detachable plate.
Page 9 of 45
Type: Weather proof double compression cable glands suitable for
un-armored cables of OD 8mm to 12mm.
Page 10 of 45
4. CPIL / PIL
The PLC Based Galley Call Bell system is manufactured with
ingenuously available components. All components are of good
quality and conveniently available in the market. They can also be
made available by us as and when required. For detailed CPIL/PIL
refer following drawing no.
Page 11 of 45
5. INSTALLATION, OPERATION & USER’S
MANUAL
5.1 INSTALLATION:
5.2 INTERCONNECTIONS
The panel in Galley & Pantry are provided with 24V DC Hooters
with db level approximately 90dB. A call is given from any of the
five places above to either Galley or Pantry or both. An audio-
visual indication will appear at the called place. The visual
indication will also appear from where the call is given. If for any
reason, the given call is to be canceled before attendance, then
call reset push button to be pressed to cancel the call. The call
received at Galley / Pantry need to be acknowledged to put off
the audio alarm and to inform the calling party that call is being
Page 12 of 45
attended. The call can be reset after attendance only form calling
party’s cabin. Thus when the call is received at Galley / Pantry, it
cannot be ignored without attending. For detailed Circuit Diagram
refer following drawing no.
Page 13 of 45
6. MAINTENANCE & FAULT FINDING PROCEDURE
6.1 MAINTENANCE
The PLC Based Galley Call Bell Systems are very simple to operate
and does not require major maintenance. Routine and periodic
cleanliness from dust and tightening of the contacts be done as
part of maintenance.
2. Call from any one - Check the respective PLC I/O terminal
place is not connections.
received at other - Tighten the wiring of respective LED and
place push button contact.
Page 14 of 45
7. HAT / SAT TRAILS
The Galley Call Bell system is of proven performance and very
simple to operate. If the system is installed and interconnected as
per details provided, it will start functioning. The following format
is recommended before carrying out HAT/SAT.
Page 15 of 45
8. AS MADE DRAWINGS
“As built Drawings” are provided for each Galley Call Bell Systems.
The drawings provide essential design data, constructional details,
circuit details etc. for reference, maintenance and fault finding in
emergency.
Page 16 of 45
9. TEST CERTIFICATES
The system is factory tested prior to dispatch. The system is tested
by manufacture’s QC department. Following checks are carried
out:
4) I.R Test.
5) H.V Test.
6) Operational Test.
Page 17 of 45
Page 18 of 45
Page 19 of 45
Page 20 of 45
Page 21 of 45
Page 22 of 45
Page 23 of 45
Page 24 of 45
Page 25 of 45
10. BLOCK DIAGRAM OF PLC BASED GALLEYCALL
BELL SYSTEM
Page 26 of 45
11. CIRCUIT DIAGRAM OF PLC BASED
GALLEY CALL BELL SYSTEM
11.1 LOC - GALLEY
Page 27 of 45
Inter Unit Communication Terminals are as follows:
Page 28 of 45
11.2 LOC - WARDROOM PANTRY
Page 29 of 45
THE PLC I/O LIST& CONTROL TERMINALS LIST OF LOC -
WARDROOM PANTRY IS AS FOLLOWS:
Page 30 of 45
Inter Unit Supply Terminals are as follows:
THE PLC I/O LIST& CONTROL TERMINALS LIST OF LOC - CO’S DAY
CABIN IS AS FOLLOWS:
Page 31 of 45
11.4 LOC - XO’S CABIN
Page 32 of 45
THE PLC I/O LIST& CONTROL TERMINALS LIST OF LOC - XO’S CABIN IS
AS FOLLOWS:
Page 33 of 45
Inter Unit Supply Terminals are as follows:
Page 34 of 45
11.6 LOC - LO’S CABIN
Page 35 of 45
THE PLC I/O LIST& CONTROL TERMINALS LIST OF LOC - EO’S
CABIN IS AS FOLLOWS:
Page 36 of 45
Inter Unit Supply Terminals are as follows:
Page 37 of 45
12. CABLE FLOW DIAGRAM FOR PLC BASED
GALLEY CALL BELL SYSTEM
Page 38 of 45
3. Four wires of size 3 x 1.5 sq.mm. each is supplied to terminals 2 (HI),
3 (SH), 4 (LO) & 6 (NC) of Pantry from terminals 12 (HI), 13 (SH), 14
(LO) & 16 (NC) of Galley respectively.
10. Two wires of size 2 x 2.5 sq.mm. each is supplied to terminals 1 (V+)
& 5 (V-) of LO’S CABIN from terminals 11 (V+) & 15 (V-) of EO’S
CABIN respectively.
11. Four wires of size 3 x 1.5 sq.mm. each is supplied to terminals 2 (HI),
3 (SH), 4 (LO) & 6 (NC) of LO’S CABIN from terminals 12 (HI), 13 (SH),
14 (LO) & 16 (NC) of EO’S DAY CABIN respectively.
Page 39 of 45
12. Two wires of size 2 x 2.5 sq.mm. each is supplied to terminals 1 (V+)
& 5 (V-) of Wardroom from terminals 11 (V+) & 15 (V-) of LO’S CABIN
respectively.
13. Four wires of size 3 x 1.5 sq.mm. each is supplied to terminals 2 (HI),
3 (SH), 4 (LO) & 6 (NC) of Wardroom from terminals 12 (HI), 13 (SH),
14 (LO) & 16 (NC) of LO’S DAY CABIN respectively.
Page 40 of 45
13. EXTERNAL WIRING OF PLC BASED GALLEY CALL BELL SYSTEM
Page 41 of 45
Page 42 of 45
Page 43 of 45
14. PLC ADDRESSING
For proper and accurate functioning of the system, PLC nodes need to be set as per the given table. As Galley panel has
master PLC, node address is available. While other panels have slave PLC, node address is set in all remaining panels. Each
panel has different node address set in PLC as follows:
Page 44 of 45
Node Id
Sr. no Panel
x10 x1
1 Pantry 0 2
3 XO’S Cabin 0 4
4 EO’S Cabin 0 5
5 LO’S Cabin 0 6
6 Wardroom 0 7
For convenience, a sticker is provided on right hand side of node address which depicts Node Id (x1) number. In the above
picture, the PLC of Pantry Cabin is shown illustrating its node address (i.e. “2”).
Page 45 of 45
GOA SHIPYARD LIMITED
QA&R DEPARTMENT
REPORT ON VERIFICATION OF PURCHASED PRODUCT (RECEIPT INSPECTION)
Date 05-09-2018 Page : 1
Company : 145
Form No.: 07/QSF/05, ISSUE:01, Rev. No:00
Req Category: Receipt Inspection Req Type: New Inspection
Project : 1233 Insp. Report No & Date: /197433 05-09-2018
Insp. Reqn. No & Date:197433 21-08-2018 Date of Insp. by QA: 01-09-2018 / 1000 INV No :
Prev. Insp. No: 0 Supplier: F00007 Fabricons
Date Of Receipt: 20-08-2018 Supplier Email : [email protected]
Purchase Order No & Date:185280/18-08-2018 PO Ref. G22/AMKS/1233-256/184716
PSU, CPU and PLC in Galley is master PLC so only one Talley
7. Component tallies of PSU, CPU and PLC are to be provided as per bill of material. is given. Tallies are provided as per wiring diagram. New
tallies will be available as per BOM.
Defect/Discrepancy Observed Not Provided
Defect/Discrepancy Observed Not Provided
120E termination resistance is provided with sleeve at PLC
8. Resistance 120E not found. (Galley call bell)
terminal. It is inside PLC side cover.
11.Hooter terminal screw is missing. (Galley call bell) Terminal will be provided