BCM Power Analyser

UMG 804
www.janitza.com

Modbus address list


(for firmware version 1.048 or lower)
08/2021
Dok. Nr. 2.063.010.0.b

Janitza electronics GmbH


Vor dem Polstück 6
D-35633 Lahnau
Support Tel. 0049 6441 9642-22
e-mail: [email protected]
www.janitza.com
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter Information
Serial Number 1 2 UINT32 Device Object Serial_Number R NV
Bootloader Version 3 UINT16 R NV
Firmware Version 4 UINT16 Device Object Firmware_Revision R NV
Device ID 5 UINT16 R/W NV 15172, 22000 22000 = Janitza Pointmap
Power Up Counter 6 UINT16 R NV
Uptime 7 8 UINT32 R NV Seconds
Smart Port ID #1 10 UINT16 R NV
Smart Port ID #2 11 UINT16 R NV
See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
Smart Port ID #4 13 UINT16 R NV
Smart Port #1 Serial Number 14 15 UINT32 R NV
Smart Port #2 Serial Number 16 17 UINT32 R NV
Smart Port #3 Serial Number 18 19 UINT32 R NV
Smart Port #4 Serial Number 20 21 UINT32 R NV
Smart Port #1 Firmware Version 22 UINT16 R NV
Smart Port #2 Firmware Version 23 UINT16 R NV
Smart Port #3 Firmware Version 24 UINT16 R NV
Smart Port #4 Firmware Version 25 UINT16 R NV
MAC Address (Bit 33-48) 26 R NV
MAC Address (Bit 17-32) 27 R NV
MAC Address (Bit 1-16) 28 R NV
Brand Name (16 Registers) 29 44 R NV
Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Lock Transformer Ratios 77 BITS R NV 0 = unlocked, 1 = locked (only for firmware version 1.048)
Meter Configuration
Demand # of Sub-Intervals 100 UINT16 Analog Value 1 R/W NV 1-6
Demand Sub-Interval Length 101 UINT16 Analog Value 2 R/W NV Seconds 0, 10 - 32767 0 = Sync to Comms
Demand Time Stamp (Year) 102 R Year Years since 1900 (118 = 2018)
Demand Time Stamp (Month) 103 R Month 0 - 11 Month (0 = January)
Demand Time Stamp (Day) 104 R Day 1 - 31 Day of the Month
Demand Time Stamp (Weekday) 105 R Weekday 0-6 Weekday (1 = Monday)
Demand Time Stamp (Hour) 106 R Hour 0 - 23 Hour (13 = 1PM)
Demand Time Stamp (Minute) 107 R Minute 0 - 59 Minute
Demand Time Stamp (Second) 108 R Seconds 0 - 59 Second
Writing to RTC will disable NTP by clearing out URL and/or IP Address
Real Time Clock (Year) 109 UINT16 R/W Year Years since 1900 (118 = 2018)
Real Time Clock (Month) 110 UINT16 R/W Month 0 - 11 Month (0 = January)
Device Object Local_Date
Real Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Digital Output #1 116 Binary Output 1 R/W 0, 1
Digital Output #2 117 Binary Output 2 R/W 0, 1
Digital Input #1 State 118 Binary Input 1 R 0, 1
Digital Input #2 State 119 Binary Input 2 R 0, 1
Modbus Slave Address 124 UINT16 R/W NV 1 - 254
Modbus TCP Port 125 UINT16 R NV 502
IP Address 126 127 R/W NV
Meter must be rebooted for new network settings to affect.
Gateway 128 129 R/W NV
Device can be rebooted remotely using Global Reset/Command (Register 192)
Mask 130 131 R/W NV

UMG 804
2
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter Information
NTP 132 133 R/W NV Write to NTP register over Modbus will clear the NTP string in webserver
SerialDNS
Number 1
134 2
135 UINT32 Device Object Serial_Number R
R/W NV
Bootloader
Baudrate Version 3
140 141 UINT16
UINT32 R
R/W NV Baud 0-4 0 = 9600, 1 = 19200, 2 = 38400, 3 = 57600, 4 = 76800 (Value can be written to MSW or LSW)
Firmware
Dip Switch Version
Enabled 4
144 UINT16 Device Object Firmware_Revision R
R/W NV 0, 1 Bit0 - Enables Dipswitch for setting Modbus slave address
DipsDevice
SwitchID Value 5
145 UINT16 R/W
R NV 15172, 22000 When Dip Switch is enabled,22000this
= Janitza Pointmap
value is used for Modbus Slave Address
Power
Panel 1 (Smart Up1&2)
Port Counter
Configuration 6
147 UINT16 Analog Value 3 R
R/W NV 0-4 0 = Top Feed, 1 = Bottom Feed, 2 = Single Row Sequential,
Uptime
Panel 2 (Smart Port 3&4) Configuration 7
148 8 UINT32 Analog Value 4 R
R/W NV Seconds 0-4 3 = Single Row Odd/Even, 4 = Sequential
Smart Port IDEnabled
CT Compensation #1 10
149 UINT16 Analog Value 5 R
R/W NV 0-3 Bit0 - Enable CT Compensation for 1/3V CTs
Smart Port ID #2 11 UINT16 R NV Bit1 - Legacy CT Compensation (Only used for Schneider Addapter Board)
See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
Smart Port ID #4 13 UINT16 R NV
Circuit
Smart PortConfiguration
#1 Serial Number 14 15 UINT32 R NV
Smart Port Global
#2 Serial Number 16 17 UINT32 R NV
Smart Port #3 Serial
Global CT SizeNumber 18
190 19 UINT32
UINT16 Analog Value 6 R
R/W NV 0 - 32000 (Always Reads 0) Writing this register will set all branches to same CT size
Smart Port #4
Global Serial Size
Breaker Number 20
191 21 UINT32
UINT16 Analog Value 7 R
R/W NV 0 - 32000 (Always Reads 0) Writing this register will set all branches to same breaker size
Smart Port Reset/Command
Global #1 Firmware Version 22
192 UINT16 Analog Value 8 R
R/W NV 12345 = Reboot Device, 20097 = Reset Max Demand, 24658 = Clear True Meter Assignment
Smart Port #2 Firmware Version 23 UINT16 R NV 24659 = Reset True Meter to Default, 26012 = New Demand SubInterval
See Notes
Smart Port #3 Firmware Version 24 UINT16 R NV 26013 = Reset Demand, 29877 = Reset Max kW and Current,
Smart Port #4 Firmware Version 25 UINT16 R NV 31010 = Clear All Latching Alarms, 32123 = Start Waveform Capture (All Circuits)
MAC Address (Bit 33-48) 26 R NV
MAC AddressCT Size(Bit 17-32) 27
200 295 UINT16 Analog Value 10 - 105 R
R/W NV Amps 0 - 32000
MAC CTAddress (Bit 1-16)
Size - Circuit 1 1 28
200 UINT16 Analog Value 10 R
R/W NV Amps 0 - 32000
BrandCTName
Size -(16 Registers)
Circuit 2 2 29
201 44 UINT16 Analog Value 11 R
R/W NV Amps 0 - 32000
Brand Name, Model Name and Device Name
Model CTName (16 Register)
Size - Circuit 3 3 45
202 60 UINT16 Device
AnalogObject
Value Model_Name
12 R
R/W NV Amps 0 - 32000
supports up to 32 characters (16 registers)
DeviceCTName
Size - (16 Registers)
Circuit 4 4 61
203 76 UINT16 Device
AnalogObject
Value Object_Name
13 R/W NV Amps 0 - 32000
CT Size - Circuit 5 5 204 UINT16 Analog Value 14 R/W NV Amps 0 - 32000
Meter Configuration
CT Size - Circuit 6 6 205 UINT16 Analog Value 15 R/W NV Amps 0 - 32000
Demand # of- Sub-Intervals
CT Size Circuit 7 7 100
206 UINT16 Analog Value 1
16 R/W NV Amps 0 -132000
-6
Demand Sub-Interval
CT Size - Circuit 8Length 8 101
207 UINT16 Analog Value 2
17 R/W NV Seconds
Amps 0,010 - 32767
- 32000 0 = Sync to Comms
DemandCT Size
Time- Circuit
Stamp 9(Year) 9 208
102 UINT16 Analog Value 18 R/W
R NV Amps
Year 0 - 32000 Years since 1900 (118 = 2018)
Demand CT Size
Time- Stamp
Circuit (Month)
10 10 209
103 UINT16 Analog Value 19 R/W
R NV Amps
Month 0 -032000
- 11 Month (0 = January)
CT Size
Demand - Circuit
Time Stamp11(Day) 11 210
104 UINT16 Analog Value 20 R/W
R NV Amps
Day 0 -132000
- 31 Day of the Month
Demand CTTime
Size Stamp
- Circuit(Weekday)
12 12 211
105 UINT16 Analog Value 21 R/W
R NV Amps
Weekday 0 - 32000
0-6 Weekday (1 = Monday)
DemandCT Size
Time- Circuit
Stamp13 (Hour) 13 212
106 UINT16 Analog Value 22 R/W
R NV Amps
Hour 0 -032000
- 23 Hour (13 = 1PM)
Demand CT Time
Size - Stamp
Circuit (Minute)
14 14 213
107 UINT16 Analog Value 23 R/W
R NV Amps
Minute 0 -032000
- 59 Minute
CT Size - Circuit 15 15 214 UINT16 Analog Value 24 R/W NV Amps 0 - 32000
Demand Time Stamp (Second) 108 R Seconds 0 - 59 Second
CT Size - Circuit 16 16 215 UINT16 Analog Value 25 R/W NV Amps 0 - 32000
Writing to RTC will disable NTP by clearing out URL and/or IP Address
CT Size - Circuit 17 17 216 UINT16 Analog Value 26 R/W NV Amps 0 - 32000
Real Time Clock (Year) 109 UINT16 R/W Year Years since 1900 (118 = 2018)
CT Size - Circuit 18 18 217 UINT16 Analog Value 27 R/W NV Amps 0 - 32000
Real Time Clock (Month) 110 UINT16 R/W Month 0 - 11 Month (0 = January)
CT Size - Circuit 19 19 218 UINT16 AnalogObject
Device Value Local_Date
28 R/W NV Amps 0 - 32000
Real Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
CT Size - Circuit 20 20 219 UINT16 Analog Value 29 R/W NV Amps 0 - 32000
Real CT
Time
SizeClock (Weekday)
- Circuit 21 21 112
220 UINT16
UINT16 Analog Value 30
R/W
R/W NV Weekday
Amps 0 -032000
-6 Weekday (1 = Monday)
Real
CT Time
Size -Clock
Circuit(Hour)
22 22 113
221 UINT16
UINT16 Analog Value 31
R/W
R/W NV Hour
Amps 0 -032000
- 23 Hour (13 = 1PM)
Real Time Clock (Min)
CT Size - Circuit 23 23 114
222 UINT16
UINT16
Device Object
Analog Value
Local_Time
32 R/W
R/W NV Minute
Amps 0 -032000
- 59 Minute
RealCTTime Clock (Second)
Size - Circuit 24 24 115
223 UINT16
UINT16 Analog Value 33 R/W
R/W NV Seconds
Amps 0 -032000
- 59 Second
Digital
CT Size -Output
Circuit#1 25 25 116
224 UINT16 Binary
AnalogOutput
Value 1
34 R/W
R/W NV Amps 0 - 0, 1
32000
Digital
CT Size -Output
Circuit#2 26 26 117
225 UINT16 Binary
AnalogOutput
Value 2
35 R/W NV Amps 0 - 0, 1
32000
Digital
CT SizeInput #1 State
- Circuit 27 27 118
226 UINT16 Binary Input
Analog Value 1
36 R
R/W NV Amps 0 - 0, 1
32000
Digital
CT SizeInput #2 State
- Circuit 28 28 119
227 UINT16 Binary Input
Analog Value 2
37 R
R/W NV Amps 0 - 0, 1
32000
CT SizeSlave
Modbus - Circuit 29
Address 29 228
124 UINT16 Analog Value 38 R/W NV Amps 01- -32000
254
CT Size - Circuit
Modbus TCP Port 30 30 229
125 UINT16 Analog Value 39 R/W
R NV Amps 0 - 502
32000
CT Size - Circuit 31
IP Address 31 230
126 127 UINT16 Analog Value 40 R/W
R/W NV
NV Amps 0 - 32000
CT Size - Circuit 32 32 231 UINT16 Analog Value 41 R/W NV Amps 0 - 32000 Meter must be rebooted for new network settings to affect.
Gateway 128 129 R/W NV
CT SizeMask
- Circuit 33 33 232 UINT16 Analog Value 42 R/W NV Amps 0 - 32000 Device can be rebooted remotely using Global Reset/Command (Register 192)
130 131 R/W NV
CT Size - Circuit 34 34 233 UINT16 Analog Value 43 R/W NV Amps 0 - 32000
CT Size - Circuit 35 35 234 UINT16 Analog Value 44 R/W NV Amps 0 - 32000
CT Size - Circuit 36 36 235 UINT16 Analog Value 45 R/W NV Amps 0 - 32000
CT Size - Circuit 37 37 236 UINT16 Analog Value 46 R/W NV Amps 0 - 32000

UMG 804
3
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
CT SizeInformation
Meter - Circuit 38 38 237 UINT16 Analog Value 47 R/W NV Amps 0 - 32000
CTSerial
Size -Number
Circuit 39 39 238
1 2 UINT16
UINT32 AnalogObject
Device Value 48
Serial_Number R/W
R NV
NV Amps 0 - 32000
CT Size - Circuit
Bootloader 40
Version 40 239
3 UINT16
UINT16 Analog Value 49 R/W
R NV
NV Amps 0 - 32000
CT Size - Circuit
Firmware Version41 41 240
4 UINT16
UINT16 AnalogObject
Device Value 50
Firmware_Revision R/W
R NV
NV Amps 0 - 32000
CT Size - Circuit
Device ID 42 42 241
5 UINT16
UINT16
Analog Value 51 R/W
R/W NV
NV Amps 0 - 32000
15172, 22000 22000 = Janitza Pointmap
CT Size - Circuit 43 43 242 UINT16 Analog Value 52 R/W NV Amps 0 - 32000
Power Up Counter 6 UINT16 R NV
CT Size - Circuit 44 44 243 UINT16 Analog Value 53 R/W NV Amps 0 - 32000
Uptime 7 8 UINT32 R NV Seconds
CT Size - Circuit 45 45 244 UINT16 Analog Value 54 R/W NV Amps 0 - 32000
Smart Port ID #1 10 UINT16 R NV
CT Size - Circuit 46 46 245 UINT16 Analog Value 55 R/W NV Amps 0 - 32000
Smart Port ID #2 11 UINT16 R NV
CT Size - Circuit 47 47 246 UINT16 Analog Value 56 R/W NV Amps 0 - 32000
See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart
CT Size Port ID #3
- Circuit 48 48 12
247 UINT16
UINT16 Analog Value 57 R
R/W NV
NV Amps 0 - 32000
Smart
CT Size Port ID #4
- Circuit 49 49 13
248 UINT16
UINT16 Analog Value 58 R
R/W NV
NV Amps 0 - 32000
SmartCTPort
Size#1- Circuit
Serial Number
50 50 14
249 15 UINT32
UINT16 Analog Value 59 R
R/W NV
NV Amps 0 - 32000
SmartCTPort
Size#2- Circuit
Serial Number
51 51 16
250 17 UINT32
UINT16 Analog Value 60 R
R/W NV
NV Amps 0 - 32000
SmartCTPort
Size#3- Circuit
Serial Number
52 52 18
251 19 UINT32
UINT16 Analog Value 61 R
R/W NV Amps 0 - 32000
SmartCTPort
Size#4- Circuit
Serial Number
53 53 20
252 21 UINT32
UINT16 Analog Value 62 R
R/W NV Amps 0 - 32000
CT Size
Smart Port #1 -Firmware
Circuit 54Version 54 253
22 UINT16 Analog Value 63 R/W
R NV Amps 0 - 32000
CT Size
Smart Port #2 -Firmware
Circuit 55Version 55 254
23 UINT16 Analog Value 64 R/W
R NV Amps 0 - 32000
CT Size
Smart Port #3 -Firmware
Circuit 56Version 56 255
24 UINT16 Analog Value 65 R/W
R NV Amps 0 - 32000
CT Size
Smart Port #4 -Firmware
Circuit 57Version 57 256
25 UINT16
UINT16 Analog Value 66 R/W
R NV
NV Amps 0 - 32000
MACCTAddress
Size - Circuit 58
(Bit 33-48) 58 257
26 UINT16 Analog Value 67 R/W
R NV
NV Amps 0 - 32000
MACCTAddress
Size - Circuit 59
(Bit 17-32) 59 258
27 UINT16 Analog Value 68 R/W
R NV
NV Amps 0 - 32000
CT Address
MAC Size - Circuit 60
(Bit 1-16) 60 259
28 UINT16 Analog Value 69 R/W
R NV
NV Amps 0 - 32000
CT Size - Circuit 61 61 260 UINT16 Analog Value 70 R/W NV Amps 0 - 32000
Brand Name (16 Registers) 29 44 R NV
CT Size - Circuit 62 62 261 UINT16 Analog Value 71 R/W NV Amps 0 - 32000 Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
CT Size - Circuit 63 63 262 UINT16 Analog Value 72 R/W NV Amps 0 - 32000 supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
CT Size - Circuit 64 64 263 UINT16 Analog Value 73 R/W NV Amps 0 - 32000
CT Size - Circuit 65 65 264 UINT16 Analog Value 74 R/W NV Amps 0 - 32000
Meter
CT SizeConfiguration
- Circuit 66 66 265 UINT16 Analog Value 75 R/W NV Amps 0 - 32000
Demand # of
CT Size Sub-Intervals
- Circuit 67 67 100
266 UINT16
UINT16 Analog Value
Analog Value 1
76 R/W
R/W NV
NV Amps 0 -132000
-6
Demand Sub-Interval
CT Size - Circuit 68 Length 68 101
267 UINT16
UINT16 Analog Value
Analog Value 2
77 R/W
R/W NV
NV Seconds
Amps 0,010 - 32767
- 32000 0 = Sync to Comms
Demand Time Stamp
CT Size - Circuit 69 (Year) 69 102
268 UINT16 Analog Value 78 R
R/W NV Year
Amps 0 - 32000 Years since 1900 (118 = 2018)
Demand Time- Stamp
CT Size Circuit (Month)
70 70 103
269 UINT16 Analog Value 79 R
R/W NV Month
Amps 0 -032000
- 11 Month (0 = January)
Demand Time
CT Size Stamp71(Day)
- Circuit 71 104
270 UINT16 Analog Value 80 R
R/W NV Day
Amps 0 -132000
- 31 Day of the Month
Demand CTTime
Size Stamp
- Circuit(Weekday)
72 72 271
105 UINT16 Analog Value 81 R/W
R NV Amps
Weekday 0 -032000
-6 Weekday (1 = Monday)
CT Size
Demand Time - Circuit
Stamp73 (Hour) 73 272
106 UINT16 Analog Value 82 R/W
R NV Amps
Hour 0 -032000
- 23 Hour (13 = 1PM)
DemandCT Size
Time- Stamp
Circuit (Minute)
74 74 273
107 UINT16 Analog Value 83 R/W
R NV Amps
Minute 0 -032000
- 59 Minute
DemandCT Size
Time- Stamp
Circuit (Second)
75 75 274
108 UINT16 Analog Value 84 R/W
R NV Amps
Seconds 0 -032000
- 59 Second
CT Size - Circuit 76 76 275 UINT16 Analog Value 85 R/W NV Amps 0 - 32000 Writing to RTC will disable NTP by clearing out URL and/or IP Address
CT Time
Real Size - Clock
Circuit(Year)
77 77 276
109 UINT16
UINT16 Analog Value 86 R/W
R/W NV Amps
Year 0 - 32000 Years since 1900 (118 = 2018)
CTTime
Real Size Clock
- Circuit 78
(Month) 78 277
110 UINT16
UINT16 Analog Value 87 R/W
R/W NV Amps
Month 0 -032000
- 11 Month (0 = January)
CT Size Device
AnalogObject Local_Date
Time- Clock
Circuit(Day)
79 79 278 UINT16 R/W NV Amps 0 -132000
Value 88
Real 111 UINT16 R/W Day - 31 Day of the Month
CT Size - Circuit 80 80 279 UINT16 Analog Value 89 R/W NV Amps 0 - 32000
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
CT Size - Circuit 81 81 280 UINT16 Analog Value 90 R/W NV Amps 0 - 32000
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
CT Size - Circuit 82 82 281 UINT16 Analog Value 91 R/W NV Amps 0 - 32000
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
CT Size - Circuit 83 83 282 UINT16 Analog Value 92 R/W NV Amps 0 - 32000
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
CT Size - Circuit 84 84 283 UINT16 Analog Value 93 R/W NV Amps 0 - 32000
Digital Output #1 116 Binary Output 1 R/W 0, 1
CT Size - Circuit 85 85 284 UINT16 Analog Value 94 R/W NV Amps 0 - 32000
Digital
CT Size -Output
Circuit#286 86 117
285 UINT16
Binary Output
Analog Value
2
95 R/W
R/W NV Amps 0 - 0, 1
32000
Digital
CT SizeInput #1 State
- Circuit 87 87 118
286 UINT16 Binary Input
Analog Value
1
96 R
R/W NV Amps 0 - 0, 1
32000
Digital
CT SizeInput #2 State
- Circuit 88 88 119
287 UINT16 Binary Input
Analog Value 2
97 R
R/W NV Amps 0 - 0, 1
32000
Modbus
CT SizeSlave Address
- Circuit 89 89 124
288 UINT16
UINT16 Analog Value 98 R/W
R/W NV
NV Amps 01- -32000
254
Modbus TCP Port
CT Size - Circuit 90 90 125
289 UINT16
UINT16 Analog Value 99 R
R/W NV
NV Amps 0 - 502
32000
IP Address
CT Size - Circuit 91 91 126
290 127 UINT16 Analog Value 100 R/W
R/W NV
NV Amps 0 - 32000 Meter must be rebooted for new network settings to affect.
Gateway
CT Size - Circuit 92 92 128
291 129 UINT16 Analog Value 101 R/W
R/W NV
NV Amps 0 - 32000 Device can be rebooted remotely using Global Reset/Command (Register 192)
CT SizeMask
- Circuit 93 93 130
292 131 UINT16 Analog Value 102 R/W
R/W NV
NV Amps 0 - 32000
CT Size - Circuit 94 94 293 UINT16 Analog Value 103 R/W NV Amps 0 - 32000
CT Size - Circuit 95 95 294 UINT16 Analog Value 104 R/W NV Amps 0 - 32000
CT Size - Circuit 96 96 295 UINT16 Analog Value 105 R/W NV Amps 0 - 32000

UMG 804
4
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter Information
Breaker
Serial Size
Number 296
1 391
2 UINT16
UINT32 AnalogObject
Device Value 106 - 201
Serial_Number R/W
R NV
NV Amps 0 - 32000
Breaker Size -Version
Bootloader Circuit 1 1 296
3 UINT16
UINT16 Analog Value 106 R/W
R NV
NV Amps 0 - 32000
Breaker
FirmwareSize Version
- Circuit 2 2 297
4 UINT16
UINT16 AnalogObject
Device Value 107
Firmware_Revision R/W
R NV
NV Amps 0 - 32000
Breaker Size -ID
Device Circuit 3 3 298
5 UINT16
UINT16 Analog Value 108 R/W
R/W NV
NV Amps 0 - 32000
15172, 22000 22000 = Janitza Pointmap
Breaker
PowerSize - Circuit 4
Up Counter 4 299
6 UINT16
UINT16 Analog Value 109 R/W
R NV
NV Amps 0 - 32000
BreakerUptime
Size - Circuit 5 5 300
7 8 UINT16
UINT32 Analog Value 110 R/W
R NV
NV Amps
Seconds 0 - 32000
Breaker
SmartSize
Port- Circuit
ID #1 6 6 301
10 UINT16
UINT16 Analog Value 111 R/W
R NV
NV Amps 0 - 32000
Breaker
SmartSize
Port- Circuit
ID #2 7 7 302
11 UINT16
UINT16 Analog Value 112 R/W
R NV
NV Amps 0 - 32000
See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Breaker
SmartSize
Port- Circuit
ID #3 8 8 303
12 UINT16
UINT16 Analog Value 113 R/W
R NV
NV Amps 0 - 32000
Breaker
SmartSize
Port- Circuit
ID #4 9 9 304
13 UINT16
UINT16 Analog Value 114 R/W
R NV
NV Amps 0 - 32000
Breaker
Smart Port Size - Circuit
#1 Serial 10
Number 10 305
14 15 UINT16
UINT32
Analog Value 115 R/W
R NV
NV Amps 0 - 32000
Breaker Size - Circuit 11 11 306 UINT16 Analog Value 116 R/W NV Amps 0 - 32000
Smart Port #2 Serial Number 16 17 UINT32 R NV
Breaker Size - Circuit 12 12 307 UINT16 Analog Value 117 R/W NV Amps 0 - 32000
Smart Port #3 Serial Number 18 19 UINT32 R NV
Breaker Size - Circuit 13 13 308 UINT16 Analog Value 118 R/W NV Amps 0 - 32000
Smart Port #4 Serial Number 20 21 UINT32 R NV
Breaker Size - Circuit 14 14 309 UINT16 Analog Value 119 R/W NV Amps 0 - 32000
Smart Port #1 Firmware Version 22 UINT16 R NV
Breaker Size - Circuit 15 15 310 UINT16 Analog Value 120 R/W NV Amps 0 - 32000
Smart Port #2Size
Breaker Firmware
- CircuitVersion
16 16 23
311 UINT16
UINT16 Analog Value 121
R
R/W NV
NV Amps 0 - 32000
Smart Port #3Size
Breaker Firmware
- CircuitVersion
17 17 24
312 UINT16
UINT16 Analog Value 122 R
R/W NV
NV Amps 0 - 32000
Smart Port #4Size
Breaker Firmware
- CircuitVersion
18 18 25
313 UINT16
UINT16 Analog Value 123 R
R/W NV
NV Amps 0 - 32000
MAC Address
Breaker Size -(Bit 33-48)
Circuit 19 19 26
314 UINT16 Analog Value 124 R
R/W NV
NV Amps 0 - 32000
MAC Address
Breaker Size -(Bit 17-32)
Circuit 20 20 27
315 UINT16 Analog Value 125 R
R/W NV Amps 0 - 32000
MAC Address
Breaker Size - (Bit 1-16)
Circuit 21 21 28
316 UINT16 Analog Value 126 R
R/W NV Amps 0 - 32000
Brand Name
Breaker Size(16 Registers)
- Circuit 22 22 29
317 44 UINT16 Analog Value 127 R
R/W NV Amps 0 - 32000
Brand Name, Model Name and Device Name
Breaker
Model NameSize(16
- Circuit 23
Register) 23 318
45 60 UINT16 AnalogObject
Device Value 128
Model_Name R/W
R NV Amps 0 - 32000
supports up to 32 characters (16 registers)
Breaker
Device NameSize(16
- Circuit 24
Registers) 24 319
61 76 UINT16 AnalogObject
Device Value 129
Object_Name R/W NV Amps 0 - 32000
Breaker Size - Circuit 25 25 320 UINT16 Analog Value 130 R/W NV Amps 0 - 32000
Breaker Size - Circuit 26
Meter Configuration 26 321 UINT16 Analog Value 131 R/W NV Amps 0 - 32000
Breaker#Size
Demand - Circuit 27
of Sub-Intervals 27 322
100 UINT16
UINT16 Analog Value
Analog Value 132
1 R/W
R/W NV
NV Amps 0 -132000
-6
Breaker
Demand Size - Circuit
Sub-Interval 28
Length 28 323
101 UINT16
UINT16 Analog Value
Analog Value 133
2 R/W
R/W NV
NV Amps
Seconds 0,010
- 32000
- 32767 0 = Sync to Comms
Breaker Size - Circuit 29 29 324 UINT16 Analog Value 134 R/W NV Amps 0 - 32000
Demand Time Stamp (Year) 102 R Year Years since 1900 (118 = 2018)
Breaker Size - Circuit 30 30 325 UINT16 Analog Value 135 R/W NV Amps 0 - 32000
Demand Time Stamp (Month) 103 R Month 0 - 11 Month (0 = January)
Breaker Size - Circuit 31 31 326 UINT16 Analog Value 136 R/W NV Amps 0 - 32000
Demand Time Stamp (Day) 104 R Day 1 - 31 Day of the Month
Breaker Size - Circuit 32 32 327 UINT16 Analog Value 137 R/W NV Amps 0 - 32000
Demand Time Stamp (Weekday) 105 R Weekday 0-6 Weekday (1 = Monday)
Breaker Size - Circuit 33 33 328 UINT16 Analog Value 138 R/W NV Amps 0 - 32000
Demand
BreakerTime
SizeStamp
- Circuit(Hour)
34 34 106
329 UINT16 Analog Value 139
R
R/W NV Hour
Amps 00 - 23
- 32000 Hour (13 = 1PM)
Demand
BreakerTime
SizeStamp (Minute)
- Circuit 35 35 107
330 UINT16 Analog Value 140 R
R/W NV Minute
Amps 00 - 59
- 32000 Minute
Demand Time Stamp (Second)
Breaker Size - Circuit 36 36 108
331 UINT16 Analog Value 141 R
R/W NV Seconds
Amps 00 - 59
- 32000 Second
Breaker Size - Circuit 37 37 332 UINT16 Analog Value 142 R/W NV Amps 0 - 32000 Writing to RTC will disable NTP by clearing out URL and/or IP Address
Real Time
Breaker Clock
Size (Year)
- Circuit 38 38 109
333 UINT16
UINT16 Analog Value 143 R/W
R/W NV Year
Amps 0 - 32000 Years since 1900 (118 = 2018)
Real TimeSize
Breaker Clock (Month)
- Circuit 39 39 110
334 UINT16 Analog Value 144 R/W NV Month
Amps 00 - 11
- 32000 Month (0 = January)
Device Object Local_Date
Real Time
Breaker SizeClock (Day)
- Circuit 40 40 111
335 UINT16 Analog Value 145 R/W NV Day
Amps 01 - 31
- 32000 Day of the Month
Real Time Size
Breaker Clock- Circuit
(Weekday)41 41 112
336 UINT16 Analog Value 146 R/W NV Weekday
Amps 0 -032000
-6 Weekday (1 = Monday)
Real Time
Breaker Clock
Size (Hour)
- Circuit 42 42 113
337 UINT16 Analog Value 147 R/W NV Hour
Amps 00 - 23
- 32000 Hour (13 = 1PM)
Breaker
Real TimeSizeClock
- Circuit 43
(Min) 43 338
114 UINT16 AnalogObject
Device Value Local_Time
148 R/W NV Amps
Minute 00- 32000
- 59 Minute
Breaker
Real TimeSize - Circuit
Clock 44
(Second) 44 339
115 UINT16 Analog Value 149 R/W NV Amps
Seconds 00- 32000
- 59 Second
Breaker
DigitalSize - Circuit
Output #1 45 45 340
116 UINT16 AnalogOutput
Binary Value 150
1 R/W
R/W NV Amps 0 - 0,
32000
1
Breaker
DigitalSize - Circuit
Output #2 46 46 341
117 UINT16 AnalogOutput
Binary Value 151
2 R/W
R/W NV Amps 0 - 0,
32000
1
Breaker Size - #1
Digital Input Circuit
State47 47 342
118 UINT16 Analog Value
Binary Input 152
1 R/W
R NV Amps 0 - 0,
32000
1
Breaker Size - #2
Digital Input Circuit
State48 48 343
119 UINT16 Analog Value
Binary Input
153
2 R/W
R NV Amps 0 - 0,
32000
1
Breaker Size - Circuit 49 49 344 UINT16 Analog Value 154 R/W NV Amps 0 - 32000
Modbus Slave Address 124 UINT16 R/W NV 1 - 254
Breaker Size - Circuit 50 50 345 UINT16 Analog Value 155 R/W NV Amps 0 - 32000
Modbus TCP Port 125 UINT16 R NV 502
Breaker Size - Circuit 51 51 346 UINT16 Analog Value 156 R/W NV Amps 0 - 32000
IP Address 126 127 R/W NV
Breaker Size - Circuit 52 52 347 UINT16 Analog Value 157 R/W NV Amps 0 - 32000 Meter must be rebooted for new network settings to affect.
Gateway 128 129 R/W NV
Breaker Size - Circuit 53 53 348 UINT16 Analog Value 158 R/W NV Amps 0 - 32000 Device can be rebooted remotely using Global Reset/Command (Register 192)
Mask
Breaker Size - Circuit 54 54 130
349 131 UINT16 Analog Value 159
R/W
R/W NV
NV Amps 0 - 32000
Breaker Size - Circuit 55 55 350 UINT16 Analog Value 160 R/W NV Amps 0 - 32000
Breaker Size - Circuit 56 56 351 UINT16 Analog Value 161 R/W NV Amps 0 - 32000
Breaker Size - Circuit 57 57 352 UINT16 Analog Value 162 R/W NV Amps 0 - 32000

UMG 804
5
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Breaker
MeterSize - Circuit 58
Information 58 353 UINT16 Analog Value 163 R/W NV Amps 0 - 32000
Breaker Size
Serial - Circuit 59
Number 59 354
1 2 UINT16
UINT32 AnalogObject
Device Value 164
Serial_Number R/W
R NV
NV Amps 0 - 32000
Breaker Size - Version
Bootloader Circuit 60 60 355
3 UINT16
UINT16 Analog Value 165 R/W
R NV
NV Amps 0 - 32000
Breaker Size -Version
Firmware Circuit 61 61 356
4 UINT16
UINT16 AnalogObject
Device Value 166
Firmware_Revision R/W
R NV
NV Amps 0 - 32000
BreakerDevice
Size - Circuit
ID 62 62 357
5 UINT16
UINT16
Analog Value 167 R/W
R/W NV
NV Amps 0 - 32000
15172, 22000 22000 = Janitza Pointmap
Breaker Size - Circuit 63 63 358 UINT16 Analog Value 168 R/W NV Amps 0 - 32000
Power Up Counter 6 UINT16 R NV
Breaker Size - Circuit 64 64 359 UINT16 Analog Value 169 R/W NV Amps 0 - 32000
Uptime 7 8 UINT32 R NV Seconds
Breaker Size - Circuit 65 65 360 UINT16 Analog Value 170 R/W NV Amps 0 - 32000
Smart Port ID #1 10 UINT16 R NV
Breaker Size - Circuit 66 66 361 UINT16 Analog Value 171 R/W NV Amps 0 - 32000
Smart Port ID #2 11 UINT16 R NV
Breaker Size - Circuit 67 67 362 UINT16 Analog Value 172 R/W NV Amps 0 - 32000
See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart
Breaker Port
Size ID #3 68
- Circuit 68 12
363 UINT16
UINT16 Analog Value 173
R
R/W NV
NV Amps 0 - 32000
Smart
Breaker Port
Size ID #4 69
- Circuit 69 13
364 UINT16
UINT16 Analog Value 174 R
R/W NV
NV Amps 0 - 32000
Smart PortSize
Breaker #1 Serial Number
- Circuit 70 70 14
365 15 UINT32
UINT16 Analog Value 175 R
R/W NV
NV Amps 0 - 32000
Smart PortSize
Breaker #2 Serial Number
- Circuit 71 71 16
366 17 UINT32
UINT16 Analog Value 176 R
R/W NV
NV Amps 0 - 32000
Smart PortSize
Breaker #3 Serial Number
- Circuit 72 72 18
367 19 UINT32
UINT16 Analog Value 177 R
R/W NV Amps 0 - 32000
Smart PortSize
Breaker #4 Serial Number
- Circuit 73 73 20
368 21 UINT32
UINT16 Analog Value 178 R
R/W NV Amps 0 - 32000
Smart Port #1
Breaker Firmware
Size - CircuitVersion
74 74 22
369 UINT16 Analog Value 179 R
R/W NV Amps 0 - 32000
Breaker
Smart Port #2Size - CircuitVersion
Firmware 75 75 370
23 UINT16 Analog Value 180 R/W
R NV Amps 0 - 32000
Breaker
Smart Port #3Size - CircuitVersion
Firmware 76 76 371
24 UINT16 Analog Value 181 R/W
R NV Amps 0 - 32000
Breaker
Smart Port #4Size - CircuitVersion
Firmware 77 77 372
25 UINT16
UINT16 Analog Value 182 R/W
R NV
NV Amps 0 - 32000
Breaker
MAC Size -(Bit
Address Circuit 78
33-48) 78 373
26 UINT16 Analog Value 183 R/W
R NV
NV Amps 0 - 32000
Breaker
MAC Size -(Bit
Address Circuit 79
17-32) 79 374
27 UINT16 Analog Value 184 R/W
R NV
NV Amps 0 - 32000
Breaker Size - Circuit
MAC Address 80
(Bit 1-16) 80 375
28 UINT16 Analog Value 185 R/W
R NV
NV Amps 0 - 32000
Breaker Size - Circuit 81 81 376 UINT16 Analog Value 186 R/W NV Amps 0 - 32000
Brand Name (16 Registers) 29 44 R NV
Breaker Size - Circuit 82 82 377 UINT16 Analog Value 187 R/W NV Amps 0 - 32000 Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Breaker Size - Circuit 83 83 378 UINT16 Analog Value 188 R/W NV Amps 0 - 32000 supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Breaker Size - Circuit 84 84 379 UINT16 Analog Value 189 R/W NV Amps 0 - 32000
Breaker Size - Circuit 85 85 380 UINT16 Analog Value 190 R/W NV Amps 0 - 32000
Meter Configuration
Breaker Size - Circuit 86 86 381 UINT16 Analog Value 191 R/W NV Amps 0 - 32000
Demand
Breaker#Sizeof Sub-Intervals
- Circuit 87 87 100
382 UINT16
UINT16 Analog Value
Analog Value
1
192 R/W
R/W NV
NV Amps 0 -132000
-6
Demand Sub-Interval
Breaker Size - Circuit Length
88 88 101
383 UINT16
UINT16 Analog Value
Analog Value 2
193 R/W
R/W NV
NV Seconds
Amps 0,010 - 32767
- 32000 0 = Sync to Comms
Demand
Breaker Size - Circuit(Year)
Time Stamp 89 89 102
384 UINT16 Analog Value 194 R
R/W NV Year
Amps 0 - 32000 Years since 1900 (118 = 2018)
Demand
BreakerTime
SizeStamp (Month)
- Circuit 90 90 103
385 UINT16 Analog Value 195 R
R/W NV Month
Amps 0 -032000
- 11 Month (0 = January)
Demand
BreakerTime
Size -Stamp
Circuit(Day)
91 91 104
386 UINT16 Analog Value 196 R
R/W NV Day
Amps 0 -132000
- 31 Day of the Month
Demand Time
Breaker Stamp
Size (Weekday)
- Circuit 92 92 105
387 UINT16 Analog Value 197 R
R/W NV Weekday
Amps 0 -032000
-6 Weekday (1 = Monday)
Demand
BreakerTime
Size Stamp
- Circuit(Hour)
93 93 106
388 UINT16 Analog Value 198 R
R/W NV Hour
Amps 0 -032000
- 23 Hour (13 = 1PM)
Demand Time Stamp (Minute)
Breaker Size - Circuit 94 94 107
389 UINT16 Analog Value 199 R
R/W NV Minute
Amps 0 -032000
- 59 Minute
Demand Time Stamp (Second)
Breaker Size - Circuit 95 95 108
390 UINT16 Analog Value 200 R
R/W NV Seconds
Amps 0 -032000
- 59 Second
Breaker Size - Circuit 96 96 391 UINT16 Analog Value 201 R/W NV Amps 0 - 32000 Writing to RTC will disable NTP by clearing out URL and/or IP Address
Real Time Clock (Year) 109 UINT16 R/W Year Years since 1900 (118 = 2018)
Real Time
VoltageClock (Month)
Phase 110
392 487 UINT16
UINT16 AnalogObject
Value 202 - 297 R/W
R/W NV Month 0 -1,112
0, VoltageMonth
Phase:(00 == L1,
January)
1 = L2, 2 = L3
Device Local_Date
Real Time
Voltage Clock
Phase (Day)1
- Circuit 1 111
392 UINT16
UINT16 Analog Value 202 R/W
R/W NV Day 1 -1,312
0, Day of0the
Voltage Phase: Month
= L1, 1 = L2, 2 = L3
Real TimePhase
Voltage Clock -(Weekday)
Circuit 2 2 112
393 UINT16
UINT16 Analog Value 203 R/W
R/W NV Weekday 0,0 1,
- 62 Voltage Weekday
Phase: 0(1= =L1,
Monday)
1 = L2, 2 = L3
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
Voltage Phase - Circuit 3 3 394 UINT16 Analog Value 204 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Voltage Phase - Circuit 4 4 395 UINT16 Analog Value 205 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Voltage Phase - Circuit 5 5 396 UINT16 Analog Value 206 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Digital Output #1 116 Binary Output 1 R/W 0, 1
Voltage Phase - Circuit 6 6 397 UINT16 Analog Value 207 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Digital Output #2 117 Binary Output 2 R/W 0, 1
Voltage Phase - Circuit 7 7 398 UINT16 Analog Value 208 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Digital Phase
Voltage Input #1 State 8
- Circuit 8 118
399 UINT16
Binary Input
Analog Value
1
209
R
R/W NV 0,0,1,12 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Digital Phase
Voltage Input #2 State 9
- Circuit 9 119
400 UINT16 Binary Input
Analog Value
2
210 R
R/W NV 0,0,1,12 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Modbus
Voltage Slave- Address
Phase Circuit 10 10 124
401 UINT16
UINT16 Analog Value 211 R/W
R/W NV
NV 10,- 1,
2542 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Modbus
Voltage Phase TCP Port 11
- Circuit 11 125
402 UINT16
UINT16 Analog Value 212 R
R/W NV
NV 0,502
1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
VoltageIP Address
Phase - Circuit 12 12 126
403 127 UINT16 Analog Value 213 R/W NV 0, 1, 2 Meter must Voltage Phase:
be rebooted for0new
= L1,network
1 = L2, 2settings
= L3 to affect.
Gateway
Voltage Phase - Circuit 13 13 128
404 129 UINT16 Analog Value 214 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Device can be rebooted remotely using Global Reset/Command (Register 192)
Mask- Circuit 14
Voltage Phase 14 130
405 131 UINT16 Analog Value 215 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Phase - Circuit 15 15 406 UINT16 Analog Value 216 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Phase - Circuit 16 16 407 UINT16 Analog Value 217 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Phase - Circuit 17 17 408 UINT16 Analog Value 218 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3

UMG 804
6
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
MeterPhase
Voltage Information
- Circuit 18 18 409 UINT16 Analog Value 219 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Phase
Serial - Circuit 19
Number 19 410
1 2 UINT16
UINT32 AnalogObject
Device Value 220
Serial_Number R/W
R NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Phase -Version
Bootloader Circuit 20 20 411
3 UINT16
UINT16 Analog Value 221 R/W
R NV
NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage PhaseVersion
Firmware - Circuit 21 21 412
4 UINT16
UINT16 AnalogObject
Device Value 222
Firmware_Revision R/W
R NV
NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Device
Phase -ID Circuit 22 22 413
5 UINT16
UINT16 Analog Value 223 R/W
R/W NV
NV 0, 1,22000
15172, 2 Voltage Phase:
22000 0 = L1,Pointmap
= Janitza 1 = L2, 2 = L3
Voltage
PowerPhase - Circuit 23
Up Counter 23 414
6 UINT16
UINT16
Analog Value 224 R/W
R NV
NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Phase - Circuit 24 24 415 UINT16 Analog Value 225 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Uptime 7 8 UINT32 R NV Seconds
Voltage Phase - Circuit 25 25 416 UINT16 Analog Value 226 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart Port ID #1 10 UINT16 R NV
Voltage Phase - Circuit 26 26 417 UINT16 Analog Value 227 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart Port ID #2 11 UINT16 R NV
Voltage Phase - Circuit 27 27 418 UINT16 Analog Value 228 R/W NV See 0, Notes
1, 2 Voltage
0=Nothing Connected, 1=DIN RAIL CTPhase: 0 = Card,
Interface L1, 1 4=DIN
= L2, 2RAIL
= L3CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
Voltage Phase - Circuit 28 28 419 UINT16 Analog Value 229 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart
Voltage Port- ID
Phase #4 29
Circuit 29 13
420 UINT16
UINT16 Analog Value 230 R
R/W NV
NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart PortPhase
Voltage #1 Serial Number
- Circuit 30 30 14
421 15 UINT32
UINT16 Analog Value 231 R
R/W NV
NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart PortPhase
Voltage #2 Serial Number
- Circuit 31 31 16
422 17 UINT32
UINT16 Analog Value 232 R
R/W NV
NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart PortPhase
Voltage #3 Serial Number
- Circuit 32 32 18
423 19 UINT32
UINT16 Analog Value 233 R
R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart PortPhase
Voltage #4 Serial Number
- Circuit 33 33 20
424 21 UINT32
UINT16 Analog Value 234 R
R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart Port #1
Voltage Firmware
Phase - CircuitVersion
34 34 22
425 UINT16 Analog Value 235 R
R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage
Smart Phase
Port #2 - CircuitVersion
Firmware 35 35 426
23 UINT16 Analog Value 236 R/W
R NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage
Smart Phase
Port #3 - CircuitVersion
Firmware 36 36 427
24 UINT16 Analog Value 237 R/W
R NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage
Smart Phase
Port #4 - CircuitVersion
Firmware 37 37 428
25 UINT16 Analog Value 238 R/W
R NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Phase (Bit
MAC Address - Circuit 38
33-48) 38 429
26 UINT16 Analog Value 239 R/W
R NV
NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Phase (Bit
MAC Address - Circuit 39
17-32) 39 430
27 UINT16 Analog Value 240 R/W
R NV
NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Phase -(Bit
MAC Address Circuit
1-16)40 40 431
28 UINT16 Analog Value 241 R/W
R NV
NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage
Brand Phase
Name (16- Circuit 41
Registers) 41 432
29 44 UINT16 Analog Value 242 R/W
R NV
NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Phase - Circuit 42 42 433 UINT16 Analog Value 243 R/W NV 0, 1, 2 Brand Voltage
Name, Model
Phase: 0Name
= L1, 1and
= L2,Device
2 = L3Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Voltage Phase - Circuit 43 43 434 UINT16 Analog Value 244 R/W NV 0, 1, 2 supports up to
Voltage 32 characters
Phase: (162registers)
0 = L1, 1 = L2, = L3
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Voltage Phase - Circuit 44 44 435 UINT16 Analog Value 245 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Phase - Circuit 45 45 436 UINT16 Analog Value 246 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Meter Configuration
Voltage Phase - Circuit 46 46 437 UINT16 Analog Value 247 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Demand # of Sub-Intervals
Voltage Phase - Circuit 47 47 100
438 UINT16
UINT16
Analog Value
Analog Value
1
248 R/W
R/W NV
NV 0,1 1,
- 62 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Demand
VoltageSub-Interval
Phase - Circuit Length
48 48 101
439 UINT16
UINT16 Analog Value
Analog Value 2
249 R/W
R/W NV
NV Seconds 0, 100, -1,32767
2 0 = Sync0 to
Voltage Phase: Comms
= L1, 1 = L2, 2 = L3
Demand Time Stamp
Voltage Phase - Circuit (Year)
49 49 102
440 UINT16 Analog Value 250 R
R/W NV Year 0, 1, 2 YearsPhase:
Voltage since 1900 (118
0 = L1, 1 ==L2,
2018)
2 = L3
Demand
VoltageTime
PhaseStamp (Month)
- Circuit 50 50 103
441 UINT16 Analog Value 251 R
R/W NV Month 0 -1,112
0, VoltageMonth
Phase:(00 == L1,
January)
1 = L2, 2 = L3
Demand Time Stamp
Voltage Phase - Circuit(Day)
51 51 104
442 UINT16 Analog Value 252 R
R/W NV Day 1 -1,312
0, Day of0the
Voltage Phase: Month
= L1, 1 = L2, 2 = L3
Demand
VoltageTime Stamp
Phase (Weekday)
- Circuit 52 52 105
443 UINT16 Analog Value 253 R
R/W NV Weekday 0,0 1,
- 62 Voltage Weekday
Phase: 0(1= =L1,
Monday)
1 = L2, 2 = L3
Voltage Time
Demand PhaseStamp
- Circuit 53
(Hour) 53 444
106 UINT16 Analog Value 254 R/W
R NV Hour 0,
0 -1,232 Voltage Phase: 0 = =L1,
Hour (13 1 = L2, 2 = L3
1PM)
VoltageTime
Demand Phase - Circuit
Stamp 54
(Minute) 54 445
107 UINT16 Analog Value 255 R/W
R NV Minute 0,
0 -1,592 Voltage Phase:Minute
0 = L1, 1 = L2, 2 = L3
VoltageTime
Demand Phase - Circuit
Stamp 55
(Second) 55 446
108 UINT16 Analog Value 256 R/W
R NV Seconds 0,
0 -1,592 Voltage Phase:Second
0 = L1, 1 = L2, 2 = L3
Voltage Phase - Circuit 56 56 447 UINT16 Analog Value 257 R/W NV 0, 1, 2 Voltage
Writing to RTC will disablePhase:
NTP by0 =clearing
L1, 1 = out
L2, 2URL
= L3and/or IP Address
Voltage Phase
Real Time - Circuit
Clock (Year)57 57 448
109 UINT16
UINT16 Analog Value 258 R/W
R/W NV Year 0, 1, 2 Voltage
Years Phase: 0 = L1,
since 1900 1 == L2,
(118 2 = L3
2018)
Voltage
Real TimePhase
Clock- Circuit
(Month) 58 58 449
110 UINT16
UINT16 Analog Value 259 R/W
R/W NV Month 0,
0 -1,112 VoltageMonth
Phase:(00 == L1, 1 = L2, 2 = L3
January)
Voltage Phase - Circuit Device
AnalogObject Local_Date
Real Time Clock (Day)59 59 450
111 UINT16
UINT16 Value 260 R/W
R/W NV Day 0,
1 -1,312 Voltage Phase:
Day of0the
= L1, 1 = L2, 2 = L3
Month
Voltage
Real TimePhase
Clock-(Weekday)
Circuit 60 60 451
112 UINT16
UINT16
Analog Value 261 R/W
R/W NV Weekday 0,0 1,
- 62 Voltage Phase: 0(1= =L1,
Weekday 1 = L2, 2 = L3
Monday)
Voltage Phase
Real Time - Circuit
Clock (Hour)61 61 452
113 UINT16
UINT16
Analog Value 262 R/W
R/W NV Hour 0,
0 -1,232 Voltage Phase: 0 = =L1,
Hour (13 1 = L2, 2 = L3
1PM)
Voltage Phase - Circuit 62 62 453 UINT16 Analog Value 263 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Voltage Phase - Circuit 63 63 454 UINT16 Analog Value 264 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Voltage Phase - Circuit 64 64 455 UINT16 Analog Value 265 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Digital Output #1 116 Binary Output 1 R/W 0, 1
Voltage Phase - Circuit 65 65 456 UINT16 Analog Value 266 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Digital Output #2 117 Binary Output 2 R/W 0, 1
Voltage Phase - Circuit 66 66 457 UINT16 Analog Value 267 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
DigitalPhase
Voltage Input -#1 State67
Circuit 67 118
458 UINT16
Binary Input
Analog Value
1
268 R
R/W NV 0,0,1,12 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
DigitalPhase
Voltage Input -#2 State68
Circuit 68 119
459 UINT16 Binary Input
Analog Value
2
269 R
R/W NV 0,0,1,12 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Modbus
Voltage Slave- Address
Phase Circuit 69 69 124
460 UINT16
UINT16 Analog Value 270 R/W
R/W NV
NV 10,- 1,
2542 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Modbus
Voltage Phase TCP Port 70
- Circuit 70 125
461 UINT16
UINT16 Analog Value 271 R
R/W NV
NV 0,502
1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
VoltageIP Address
Phase - Circuit 71 71 126
462 127 UINT16 Analog Value 272 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Meter must be rebooted for new network settings to affect.
Gateway
Voltage Phase - Circuit 72 72 128
463 129 UINT16 Analog Value 273 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Device can be rebooted remotely using Global Reset/Command (Register 192)
Voltage Phase
Mask- Circuit 73 73 464
130 131 UINT16 Analog Value 274 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Phase - Circuit 74 74 465 UINT16 Analog Value 275 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Phase - Circuit 75 75 466 UINT16 Analog Value 276 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Phase - Circuit 76 76 467 UINT16 Analog Value 277 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3

UMG 804
7
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
MeterPhase
Voltage Information
- Circuit 77 77 468 UINT16 Analog Value 278 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Phase
Serial - Circuit 78
Number 78 469
1 2 UINT16
UINT32 AnalogObject
Device Value 279
Serial_Number R/W
R NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Phase -Version
Bootloader Circuit 79 79 470
3 UINT16
UINT16 Analog Value 280 R/W
R NV
NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage PhaseVersion
Firmware - Circuit 80 80 471
4 UINT16
UINT16 AnalogObject
Device Value 281
Firmware_Revision R/W
R NV
NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Device
Phase -ID Circuit 81 81 472
5 UINT16
UINT16 Analog Value 282 R/W
R/W NV
NV 0, 1,22000
15172, 2 Voltage Phase:
22000 0 = L1,Pointmap
= Janitza 1 = L2, 2 = L3
Voltage
PowerPhase - Circuit 82
Up Counter 82 473
6 UINT16
UINT16
Analog Value 283 R/W
R NV
NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Voltage Phase - Circuit 83 83 474 UINT16 Analog Value 284 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Uptime 7 8 UINT32 R NV Seconds
Voltage Phase - Circuit 84 84 475 UINT16 Analog Value 285 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart Port ID #1 10 UINT16 R NV
Voltage Phase - Circuit 85 85 476 UINT16 Analog Value 286 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart Port ID #2 11 UINT16 R NV
Voltage Phase - Circuit 86 86 477 UINT16 Analog Value 287 R/W NV 0, Notes
See 1, 2 Voltage
0=Nothing Connected, 1=DIN RAIL CTPhase: 0 = Card,
Interface L1, 1 4=DIN
= L2, 2RAIL
= L3CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
Voltage Phase - Circuit 87 87 478 UINT16 Analog Value 288 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart Port ID #4 13 UINT16 R NV
Voltage Phase - Circuit 88 88 479 UINT16 Analog Value 289 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart Port #1 Serial Number 14 15 UINT32 R NV
Voltage Phase - Circuit 89 89 480 UINT16 Analog Value 290 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart Port #2 Serial Number 16 17 UINT32 R NV
Voltage Phase - Circuit 90 90 481 UINT16 Analog Value 291 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart Port #3 Serial Number 18 19 UINT32 R NV
Voltage Phase - Circuit 91 91 482 UINT16 Analog Value 292 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart Port #4 Serial Number 20 21 UINT32 R NV
Voltage Phase - Circuit 92 92 483 UINT16 Analog Value 293 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart Port #1 Firmware Version 22 UINT16 R NV
Voltage Phase - Circuit 93 93 484 UINT16 Analog Value 294 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart Port #2 Firmware Version 23 UINT16 R NV
Voltage Phase - Circuit 94 94 485 UINT16 Analog Value 295 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart Port #3 Firmware Version 24 UINT16 R NV
Voltage Phase - Circuit 95 95 486 UINT16 Analog Value 296 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
Smart Port #4 Firmware Version 25 UINT16 R NV
Voltage Phase - Circuit 96 96 487 UINT16 Analog Value 297 R/W NV 0, 1, 2 Voltage Phase: 0 = L1, 1 = L2, 2 = L3
MAC Address (Bit 33-48) 26 R NV
MAC Address (Bit 17-32) 27 R NV
True Meter Assignment 488 583 UINT16 Analog Value 298 - 393 R/W NV 0 - 96 True Meter Assignment (Starting at register 15000), 0 = Disabled
MAC Address (Bit 1-16) 28 R NV
True Meter Assignment - Circuit 1 1 488 UINT16 Analog Value 298 R/W NV 0 - 96
Brand Name (16 Registers) 29 44 R NV
True Meter Assignment - Circuit 2 2 489 UINT16 Analog Value 299 R/W NV 0 - 96 Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
True Meter Assignment - Circuit 3 3 490 UINT16 Analog Value 300 R/W NV 0 - 96 supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
True Meter Assignment - Circuit 4 4 491 UINT16 Analog Value 301 R/W NV 0 - 96
True Meter Assignment - Circuit 5 5 492 UINT16 Analog Value 302 R/W NV 0 - 96
Meter Configuration
True Meter Assignment - Circuit 6 6 493 UINT16 Analog Value 303 R/W NV 0 - 96
Demand # of Sub-Intervals 100 UINT16 Analog Value 1 R/W NV 1-6
True Meter Assignment - Circuit 7 7 494 UINT16 Analog Value 304 R/W NV 0 - 96
Demand
True Meter Sub-Interval
Assignment -LengthCircuit 8 8 101
495 UINT16
UINT16
Analog Value
Analog Value
2
305 R/W
R/W NV
NV Seconds 0, 100 -- 96
32767 0 = Sync to Comms
Demand
True Time Stamp-(Year)
Meter Assignment Circuit 9 9 102
496 UINT16 Analog Value 306 R
R/W NV Year 0 - 96 Years since 1900 (118 = 2018)
Demand
True Meter Time Stamp -(Month)
Assignment Circuit 10 10 103
497 UINT16 Analog Value 307 R
R/W NV Month 00 -- 96
11 Month (0 = January)
TrueDemand Time Stamp- Circuit
Meter Assignment (Day) 11 11 104
498 UINT16 Analog Value 308 R
R/W NV Day 01 -- 96
31 Day of the Month
Demand
True MeterTime Stamp (Weekday)
Assignment - Circuit 12 12 105
499 UINT16 Analog Value 309 R
R/W NV Weekday 00--96 6 Weekday (1 = Monday)
TrueDemand Time Stamp- (Hour)
Meter Assignment Circuit 13 13 106
500 UINT16 Analog Value 310 R
R/W NV Hour 0 - 9623 Hour (13 = 1PM)
True Meter Time
Demand Assignment - Circuit 14
Stamp (Minute) 14 501
107 UINT16 Analog Value 311 R/W
R NV Minute 0 - 9659 Minute
True Meter Time
Demand Assignment - Circuit 15
Stamp (Second) 15 502
108 UINT16 Analog Value 312 R/W
R NV Seconds 0 - 9659 Second
True Meter Assignment - Circuit 16 16 503 UINT16 Analog Value 313 R/W NV 0 - 96 Writing to RTC will disable NTP by clearing out URL and/or IP Address
True Meter Assignment
Real Time - Circuit 17
Clock (Year) 17 504
109 UINT16 Analog Value 314 R/W NV Year 0 - 96 Years since 1900 (118 = 2018)
True Meter Assignment
Real Time - Circuit 18
Clock (Month) 18 505
110 UINT16
UINT16 Analog Value 315 R/W
R/W NV Month 00 -- 96
11 Month (0 = January)
Device
AnalogObject
Local_Date
True Meter Assignment
Real Time - Circuit 19
Clock (Day) 19 506
111 UINT16
UINT16 Value 316 R/W
R/W NV Day 01 -- 96
31 Day of the Month
TrueReal
Meter Assignment
Time - Circuit 20
Clock (Weekday) 20 507
112 UINT16
UINT16 Analog Value 317 R/W
R/W NV Weekday 0 -
0-6 96 Weekday (1 = Monday)
True Meter Assignment
Real Time - Circuit 21
Clock (Hour) 21 508
113 UINT16
UINT16 Analog Value 318 R/W
R/W NV Hour 0 - 96
0 - 23 Hour (13 = 1PM)
True Meter Assignment
Real Time - Circuit 22
Clock (Min) 22 509
114 UINT16
UINT16
Analog Value
Device Object
319
Local_Time R/W
R/W NV Minute 00 -- 96
59 Minute
True Meter Assignment - Circuit 23 23 510 UINT16 Analog Value 320 R/W NV 0 - 96
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
True Meter Assignment - Circuit 24 24 511 UINT16 Analog Value 321 R/W NV 0 - 96
Digital Output #1 116 Binary Output 1 R/W 0, 1
True Meter Assignment - Circuit 25 25 512 UINT16 Analog Value 322 R/W NV 0 - 96
Digital Output #2 117 Binary Output 2 R/W 0, 1
True Meter Assignment - Circuit 26 26 513 UINT16 Analog Value 323 R/W NV 0 - 96
Digital Input #1 State 118 Binary Input 1 R 0, 1
True Meter Assignment - Circuit 27 27 514 UINT16 Analog Value 324 R/W NV 0 - 96
Digital
True Meter Input #2 State
Assignment - Circuit 28 28 119
515 UINT16
Binary Input
Analog Value
2
325 R
R/W NV 00,- 96
1
Modbus
True Meter Slave Address
Assignment - Circuit 29 29 124
516 UINT16
UINT16 Analog Value 326 R/W
R/W NV
NV 10--25496
Modbus TCP Port
True Meter Assignment - Circuit 30 30 125
517 UINT16
UINT16 Analog Value 327 R
R/W NV
NV 0502
- 96
IP Address - Circuit 31
True Meter Assignment 31 126
518 127 UINT16 Analog Value 328 R/W
R/W NV
NV 0 - 96 Meter must be rebooted for new network settings to affect.
Gateway - Circuit 32
True Meter Assignment 32 128
519 129 UINT16 Analog Value 329 R/W NV 0 - 96 Device can be rebooted remotely using Global Reset/Command (Register 192)
Mask
True Meter Assignment - Circuit 33 33 130
520 131 UINT16 Analog Value 330 R/W NV 0 - 96
True Meter Assignment - Circuit 34 34 521 UINT16 Analog Value 331 R/W NV 0 - 96
True Meter Assignment - Circuit 35 35 522 UINT16 Analog Value 332 R/W NV 0 - 96
True Meter Assignment - Circuit 36 36 523 UINT16 Analog Value 333 R/W NV 0 - 96

UMG 804
8
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter
True Meter Information
Assignment - Circuit 37 37 524 UINT16 Analog Value 334 R/W NV 0 - 96
True MeterSerial
Assignment
Number- Circuit 38 38 525
1 2 UINT16
UINT32 AnalogObject
Device Value 335
Serial_Number R/W
R NV 0 - 96
True Meter Assignment
Bootloader - Circuit 39
Version 39 526
3 UINT16 Analog Value 336 R/W
R NV 0 - 96
True Meter Assignment
Firmware - Circuit 40
Version 40 527
4 UINT16
UINT16 AnalogObject
Device Value 337
Firmware_Revision R/W
R NV
NV 0 - 96
True Meter Assignment
Device ID - Circuit 41 41 528
5 UINT16
UINT16 Analog Value 338 R/W
R/W NV
NV 15172,0 - 96
22000 22000 = Janitza Pointmap
True Meter Assignment
Power Up Counter - Circuit 42 42 529
6 UINT16
UINT16 Analog Value 339 R/W
R NV
NV 0 - 96
True Meter Assignment
Uptime - Circuit 43 43 530
7 8 UINT16
UINT32
Analog Value 340 R/W
R NV
NV Seconds 0 - 96
True Meter Assignment - Circuit 44 44 531 UINT16 Analog Value 341 R/W NV 0 - 96
Smart Port ID #1 10 UINT16 R NV
True Meter Assignment - Circuit 45 45 532 UINT16 Analog Value 342 R/W NV 0 - 96
Smart Port ID #2 11 UINT16 R NV
True Meter Assignment - Circuit 46 46 533 UINT16 Analog Value 343 R/W NV See 0 -Notes
96 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
True Meter Assignment - Circuit 47 47 534 UINT16 Analog Value 344 R/W NV 0 - 96
Smart Port ID #4 13 UINT16 R NV
True Meter Assignment - Circuit 48 48 535 UINT16 Analog Value 345 R/W NV 0 - 96
Smart
True MeterPort #1 Serial Number
Assignment - Circuit 49 49 14
536 15 UINT32
UINT16 Analog Value 346
R
R/W NV
NV 0 - 96
Smart
True MeterPort #2 Serial Number
Assignment - Circuit 50 50 16
537 17 UINT32
UINT16 Analog Value 347 R
R/W NV
NV 0 - 96
Smart
True MeterPort #3 Serial Number
Assignment - Circuit 51 51 18
538 19 UINT32
UINT16 Analog Value 348 R
R/W NV
NV 0 - 96
Smart
True MeterPort #4 Serial Number
Assignment - Circuit 52 52 20
539 21 UINT32
UINT16 Analog Value 349 R
R/W NV
NV 0 - 96
Smart
True PortAssignment
Meter #1 Firmware Version53
- Circuit 53 22
540 UINT16 Analog Value 350 R
R/W NV 0 - 96
Smart
True PortAssignment
Meter #2 Firmware Version54
- Circuit 54 23
541 UINT16 Analog Value 351 R
R/W NV 0 - 96
Smart
True PortAssignment
Meter #3 Firmware Version55
- Circuit 55 24
542 UINT16 Analog Value 352 R
R/W NV 0 - 96
True Meter
Smart PortAssignment
#4 Firmware - Circuit
Version56 56 543
25 UINT16 Analog Value 353 R/W
R NV 0 - 96
True Meter Assignment
MAC Address - Circuit 57
(Bit 33-48) 57 544
26 UINT16 Analog Value 354 R/W
R NV 0 - 96
True Meter Assignment
MAC Address - Circuit 58
(Bit 17-32) 58 545
27 UINT16 Analog Value 355 R/W
R NV
NV 0 - 96
True Meter Assignment
MAC Address - Circuit 59
(Bit 1-16) 59 546
28 UINT16 Analog Value 356 R/W
R NV
NV 0 - 96
TrueBrand
MeterName
Assignment - Circuit 60
(16 Registers) 60 547
29 44 UINT16 Analog Value 357 R/W
R NV
NV 0 - 96
TrueModel
MeterName
Assignment - Circuit 61 61 548 UINT16 Analog Value 358 R/W NV 0 - 96 Brand Name, Model Name and Device Name
(16 Register) 45 60 Device Object Model_Name R NV
True Meter Assignment - Circuit 62 62 549 UINT16 Analog Value 359 R/W NV 0 - 96 supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
True Meter Assignment - Circuit 63 63 550 UINT16 Analog Value 360 R/W NV 0 - 96
True Meter Assignment - Circuit 64 64 551 UINT16 Analog Value 361 R/W NV 0 - 96
Meter Configuration
True Meter Assignment - Circuit 65 65 552 UINT16 Analog Value 362 R/W NV 0 - 96
Demand # of Sub-Intervals 100 UINT16 Analog Value 1 R/W NV 1-6
True Meter Assignment - Circuit 66 66 553 UINT16 Analog Value 363 R/W NV 0 - 96
Demand
True Sub-Interval-Length
Meter Assignment Circuit 67 67 101
554 UINT16
UINT16
Analog Value
Analog Value
2
364
R/W
R/W NV
NV Seconds 0, 100 -- 32767
96 0 = Sync to Comms
TrueDemand Time Stamp- (Year)
Meter Assignment Circuit 68 68 102
555 UINT16 Analog Value 365 R
R/W NV Year 0 - 96 Years since 1900 (118 = 2018)
Demand
True Meter Time Stamp (Month)
Assignment - Circuit 69 69 103
556 UINT16 Analog Value 366 R
R/W NV Month 00 -- 11
96 Month (0 = January)
TrueDemand Time Stamp- Circuit
Meter Assignment (Day) 70 70 104
557 UINT16 Analog Value 367 R
R/W NV Day 10 -- 31
96 Day of the Month
Demand
True MeterTime Stamp (Weekday)
Assignment - Circuit 71 71 105
558 UINT16 Analog Value 368 R
R/W NV Weekday 00--966 Weekday (1 = Monday)
TrueDemand Time Stamp- (Hour)
Meter Assignment Circuit 72 72 106
559 UINT16 Analog Value 369 R
R/W NV Hour 0 - 2396 Hour (13 = 1PM)
Demand
True MeterTime Stamp (Minute)
Assignment - Circuit 73 73 107
560 UINT16 Analog Value 370 R
R/W NV Minute 0 - 5996 Minute
True MeterTime
Demand Assignment - Circuit 74
Stamp (Second) 74 561
108 UINT16 Analog Value 371 R/W
R NV Seconds 0 - 5996 Second
True Meter Assignment - Circuit 75 75 562 UINT16 Analog Value 372 R/W NV 0 - 96 Writing to RTC will disable NTP by clearing out URL and/or IP Address
True Meter Assignment
Real Time - Circuit 76
Clock (Year) 76 563
109 UINT16 Analog Value 373 R/W NV Year 0 - 96 Years since 1900 (118 = 2018)
True Meter Assignment
Real Time - Circuit 77
Clock (Month) 77 564
110 UINT16
UINT16 Analog Value 374 R/W
R/W NV Month 00 -- 11
96 Month (0 = January)
Device Object Local_Date
True Meter Assignment
Real Time - Circuit 78
Clock (Day) 78 565
111 UINT16
UINT16 Analog Value 375 R/W
R/W NV Day 10 -- 31
96 Day of the Month
TrueReal
Meter Assignment
Time - Circuit 79
Clock (Weekday) 79 566
112 UINT16
UINT16 Analog Value 376 R/W
R/W NV Weekday 00--966 Weekday (1 = Monday)
True Meter Assignment
Real Time - Circuit 80
Clock (Hour) 80 567
113 UINT16
UINT16 Analog Value 377 R/W
R/W NV Hour 00 -- 23
96 Hour (13 = 1PM)
True Meter Assignment
Real Time - Circuit 81
Clock (Min) 81 568
114 UINT16
UINT16
Analog Value
Device Object
378
Local_Time R/W
R/W NV Minute 00 -- 59
96 Minute
True Meter Assignment - Circuit 82 82 569 UINT16 Analog Value 379 R/W NV 0 - 96
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
True Meter Assignment - Circuit 83 83 570 UINT16 Analog Value 380 R/W NV 0 - 96
Digital Output #1 116 Binary Output 1 R/W 0, 1
True Meter Assignment - Circuit 84 84 571 UINT16 Analog Value 381 R/W NV 0 - 96
Digital Output #2 117 Binary Output 2 R/W 0, 1
True Meter Assignment - Circuit 85 85 572 UINT16 Analog Value 382 R/W NV 0 - 96
Digital Input #1 State 118 Binary Input 1 R 0, 1
True Meter Assignment - Circuit 86 86 573 UINT16 Analog Value 383 R/W NV 0 - 96
Digital
True Meter Input #2 State
Assignment - Circuit 87 87 119
574 UINT16
Binary Input
Analog Value
2
384
R
R/W NV 00,- 96
1
Modbus
True Meter Slave Address
Assignment - Circuit 88 88 124
575 UINT16
UINT16 Analog Value 385 R/W
R/W NV
NV 10--25496
Modbus TCP Port
True Meter Assignment - Circuit 89 89 125
576 UINT16
UINT16 Analog Value 386 R
R/W NV
NV 0502
- 96
IP Address - Circuit 90
True Meter Assignment 90 126
577 127 UINT16 Analog Value 387 R/W
R/W NV
NV 0 - 96 Meter must be rebooted for new network settings to affect.
Gateway - Circuit 91
True Meter Assignment 91 128
578 129 UINT16 Analog Value R/W
R/W NV
NV 0 - 96
388 Device can be rebooted remotely using Global Reset/Command (Register 192)
Mask
True Meter Assignment - Circuit 92 92 130
579 131 UINT16 Analog Value 389 R/W
R/W NV
NV 0 - 96
True Meter Assignment - Circuit 93 93 580 UINT16 Analog Value 390 R/W NV 0 - 96
True Meter Assignment - Circuit 94 94 581 UINT16 Analog Value 391 R/W NV 0 - 96
True Meter Assignment - Circuit 95 95 582 UINT16 Analog Value 392 R/W NV 0 - 96

UMG 804
9
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
True Meter
MeterAssignment - Circuit 96
Information 96 583 UINT16 Analog Value 393 R/W NV 0 - 96
Serial Number 1 2 UINT32 Device Object Serial_Number R NV
Reset/Command
Bootloader Version 584
3 679 UINT16 Analog Value 394 - 489 R NV 29877 = Reset Max kW and Current, 32123 = Waveform Capture (Only Selected Circuit)
Reset/Command - Circuit 1
Firmware Version 1 584
4 UINT16 AnalogObject
Device Value 394
Firmware_Revision R/W
R NV
Reset/Command
Device ID- Circuit 2 2 585
5 UINT16 Analog Value 395 R/W NV 15172, 22000 22000 = Janitza Pointmap
Reset/Command - Circuit 3
Power Up Counter 3 586
6 UINT16 Analog Value 396 R/W
R NV
Reset/Command
Uptime - Circuit 4 4 587
7 8 UINT32 Analog Value 397 R/W
R NV Seconds
Reset/Command
Smart Port ID - Circuit
#1 5 5 588
10 UINT16 Analog Value 398 R/W
R NV
Reset/Command
Smart Port ID - Circuit
#2 6 6 589
11 UINT16 Analog Value 399 R/W
R NV
See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Reset/Command
Smart Port ID - Circuit
#3 7 7 590
12 UINT16 Analog Value 400 R/W
R NV
Reset/Command
Smart Port ID - Circuit
#4 8 8 591
13 UINT16 Analog Value 401 R/W
R NV
NV
Reset/Command
Smart - Circuit
Port #1 Serial Number 9 9 592
14 15 UINT32 Analog Value 402 R/W
R NV
NV
Reset/Command
Smart - Circuit
Port #2 Serial Number10 10 593
16 17 UINT32 Analog Value 403 R/W
R NV
NV
Reset/Command
Smart - Circuit
Port #3 Serial Number11 11 594
18 19 UINT32
Analog Value 404 R/W
R NV
NV
Reset/Command - Circuit 12 12 595 Analog Value 405 R/W NV
Smart Port #4 Serial Number 20 21 UINT32 R NV
Reset/Command - Circuit 13 13 596 Analog Value 406 R/W NV
Smart Port #1 Firmware Version 22 UINT16 R NV
Reset/Command - Circuit 14 14 597 Analog Value 407 R/W NV
Smart Port #2 Firmware Version 23 UINT16 R NV
Reset/Command - Circuit 15 15 598 Analog Value 408 R/W NV
Smart Port #3 Firmware Version 24 UINT16 R NV
Reset/Command - Circuit 16 16 599 Analog Value 409 R/W NV
Smart Port #4 Firmware
Reset/Command Version
- Circuit 17 17 25
600 UINT16 Analog Value 410 R
R/W NV
NV
MAC Address (Bit
Reset/Command 33-48)18
- Circuit 18 26
601 Analog Value 411 R
R/W NV
NV
MAC Address (Bit
Reset/Command 17-32)19
- Circuit 19 27
602 Analog Value 412 R
R/W NV
NV
MAC Address (Bit
Reset/Command 1-16)20
- Circuit 20 28
603 Analog Value 413 R
R/W NV
Brand Name (16 -Registers)
Reset/Command Circuit 21 21 29
604 44 Analog Value 414 R
R/W NV
Brand Name, Model Name and Device Name
Model Name (16- Register)
Reset/Command Circuit 22 22 45
605 60 Device
AnalogObject
Value Model_Name
415 R
R/W NV
supports up to 32 characters (16 registers)
Reset/Command
Device Name (16-Registers)
Circuit 23 23 606
61 76 Device
AnalogObject
Value Object_Name
416 R/W NV
Reset/Command - Circuit 24 24 607 Analog Value 417 R/W NV
Reset/Command - Circuit 25
Meter Configuration 25 608 Analog Value 418 R/W NV
Reset/Command - Circuit 26
Demand # of Sub-Intervals 26 609
100 UINT16 Analog Value
Analog Value 419
1 R/W
R/W NV
NV 1-6
Reset/Command
Demand - Circuit
Sub-Interval 27
Length 27 610
101 UINT16 Analog Value
Analog Value 420
2 R/W
R/W NV
NV Seconds 0, 10 - 32767 0 = Sync to Comms
Reset/Command
Demand Time Stamp - Circuit 28
(Year) 28 611
102 Analog Value 421 R/W
R NV Year Years since 1900 (118 = 2018)
Reset/Command
Demand Time Stamp- Circuit 29
(Month) 29 612
103
Analog Value 422 R/W
R NV Month 0 - 11 Month (0 = January)
Reset/Command - Circuit 30 30 613 Analog Value 423 R/W NV
Demand Time Stamp (Day) 104 R Day 1 - 31 Day of the Month
Reset/Command - Circuit 31 31 614 Analog Value 424 R/W NV
Demand Time Stamp (Weekday) 105 R Weekday 0-6 Weekday (1 = Monday)
Reset/Command - Circuit 32 32 615 Analog Value 425 R/W NV
Demand Time Stamp (Hour) 106 R Hour 0 - 23 Hour (13 = 1PM)
Reset/Command - Circuit 33 33 616 Analog Value 426 R/W NV
Demand Time Stamp (Minute) 107 R Minute 0 - 59 Minute
Reset/Command - Circuit 34 34 617 Analog Value 427 R/W NV
Demand Time Stamp
Reset/Command (Second)
- Circuit 35 35 108
618 Analog Value 428 R
R/W NV Seconds 0 - 59 Second
Reset/Command - Circuit 36 36 619 Analog Value 429 R/W NV Writing to RTC will disable NTP by clearing out URL and/or IP Address
Real Time Clock
Reset/Command (Year) 37
- Circuit 37 109
620 UINT16 Analog Value 430 R/W
R/W NV Year Years since 1900 (118 = 2018)
Real Time Clock-(Month)
Reset/Command Circuit 38 38 110
621 UINT16 AnalogObject
Value 431 R/W
R/W NV Month 0 - 11 Month (0 = January)
Device Local_Date
Real Time Clock
Reset/Command (Day) 39
- Circuit 39 111
622 UINT16 Analog Value 432 R/W
R/W NV Day 1 - 31 Day of the Month
Real Time Clock (Weekday)
Reset/Command - Circuit 40 40 112
623 UINT16 Analog Value 433 R/W NV Weekday 0-6 Weekday (1 = Monday)
Real Time Clock- Circuit
Reset/Command (Hour) 41 41 113
624 UINT16 Analog Value 434 R/W NV Hour 0 - 23 Hour (13 = 1PM)
Real Time Clock
Reset/Command (Min) 42
- Circuit 42 114
625 UINT16 Device
AnalogObject
Value Local_Time
435 R/W NV Minute 0 - 59 Minute
Reset/Command
Real Time Clock-(Second)
Circuit 43 43 626
115 UINT16 Analog Value 436 R/W NV Seconds 0 - 59 Second
Reset/Command - Circuit
Digital Output #1 44 44 627
116 AnalogOutput
Binary Value 437
1 R/W NV 0, 1
Reset/Command - Circuit
Digital Output #2 45 45 628
117 AnalogOutput
Binary Value 438
2 R/W NV 0, 1
Reset/Command - Circuit
Digital Input #1 State 46 46 629
118 Analog Value
Binary Input 439
1 R/W
R NV 0, 1
Reset/Command - Circuit
Digital Input #2 State 47 47 630
119 Analog Value
Binary Input 440
2 R/W
R NV 0, 1
Reset/Command
Modbus Slave -Address
Circuit 48 48 631
124 UINT16 Analog Value 441 R/W
R/W NV
NV 1 - 254
Reset/Command
Modbus TCP- Port
Circuit 49 49 632
125 UINT16
Analog Value 442 R/W
R NV
NV 502
Reset/Command - Circuit 50 50 633 Analog Value 443 R/W NV
IP Address 126 127 R/W NV
Reset/Command - Circuit 51 51 634 Analog Value 444 R/W NV Meter must be rebooted for new network settings to affect.
Gateway 128 129 R/W NV
Reset/Command - Circuit 52 52 635 Analog Value 445 R/W NV Device can be rebooted remotely using Global Reset/Command (Register 192)
Mask 130 131 R/W NV
Reset/Command - Circuit 53 53 636 Analog Value 446 R/W NV
Reset/Command - Circuit 54 54 637 Analog Value 447 R/W NV
Reset/Command - Circuit 55 55 638 Analog Value 448 R/W NV
Reset/Command - Circuit 56 56 639 Analog Value 449 R/W NV

UMG 804
10
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Reset/Command - Circuit 57
Meter Information 57 640 Analog Value 450 R/W NV
Reset/Command - Circuit 58
Serial Number 58 641
1 2 UINT32 AnalogObject
Device Value 451
Serial_Number R/W
R NV
NV
Reset/Command - Circuit 59
Bootloader Version 59 642
3 UINT16 Analog Value 452 R/W
R NV
NV
Reset/Command - Circuit 60
Firmware Version 60 643
4 UINT16
AnalogObject
Device Value 453
Firmware_Revision R/W
R NV
NV
Reset/Command - Circuit 61 61 644 Analog Value 454 R/W NV
Device ID 5 UINT16 R/W NV 15172, 22000 22000 = Janitza Pointmap
Reset/Command - Circuit 62 62 645 Analog Value 455 R/W NV
Power Up Counter 6 UINT16 R NV
Reset/Command - Circuit 63 63 646 Analog Value 456 R/W NV
Uptime 7 8 UINT32 R NV Seconds
Reset/Command - Circuit 64 64 647 Analog Value 457 R/W NV
Smart Port ID #1 10 UINT16 R NV
Reset/Command - Circuit 65 65 648 Analog Value 458 R/W NV
Smart Port ID
Reset/Command #2 66
- Circuit 66 11
649 UINT16 Analog Value R
R/W NV
NV
459 See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID
Reset/Command #3 67
- Circuit 67 12
650 UINT16 Analog Value 460 R
R/W NV
NV
Smart Port ID
Reset/Command #4 68
- Circuit 68 13
651 UINT16 Analog Value 461 R
R/W NV
NV
Smart Port #1 Serial
Reset/Command Number
- Circuit 69 69 14
652 15 UINT32 Analog Value 462 R
R/W NV
NV
Smart Port #2 Serial
Reset/Command Number
- Circuit 70 70 16
653 17 UINT32 Analog Value 463 R
R/W NV
Smart Port #3 Serial
Reset/Command Number
- Circuit 71 71 18
654 19 UINT32 Analog Value 464 R
R/W NV
Smart Port #4 Serial
Reset/Command Number
- Circuit 72 72 20
655 21 UINT32 Analog Value 465 R
R/W NV
Reset/Command
Smart - Circuit
Port #1 Firmware 73
Version 73 656
22 UINT16 Analog Value 466 R/W
R NV
Reset/Command
Smart - Circuit
Port #2 Firmware 74
Version 74 657
23 UINT16 Analog Value 467 R/W
R NV
Reset/Command
Smart - Circuit
Port #3 Firmware 75
Version 75 658
24 UINT16 Analog Value 468 R/W
R NV
NV
Reset/Command
Smart - Circuit
Port #4 Firmware 76
Version 76 659
25 UINT16 Analog Value 469 R/W
R NV
NV
Reset/Command
MAC Address (Bit - Circuit
33-48)77 77 660
26 Analog Value 470 R/W
R NV
NV
Reset/Command
MAC Address (Bit - Circuit
17-32)78 78 661
27
Analog Value 471 R/W
R NV
NV
Reset/Command - Circuit 79 79 662 Analog Value 472 R/W NV
MAC Address (Bit 1-16) 28 R NV
Reset/Command - Circuit 80 80 663 Analog Value 473 R/W NV
Brand Name (16 Registers) 29 44 R NV
Reset/Command - Circuit 81 81 664 Analog Value 474 R/W NV Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Reset/Command - Circuit 82 82 665 Analog Value 475 R/W NV supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Reset/Command - Circuit 83 83 666 Analog Value 476 R/W NV
Reset/Command - Circuit 84 84 667 Analog Value 477 R/W NV
Meter Configuration
Reset/Command - Circuit 85 85 668 Analog Value 478 R/W NV
Demand # of Sub-Intervals
Reset/Command - Circuit 86 86 100
669 UINT16 Analog Value
Analog Value 1
479 R/W
R/W NV
NV 1-6
Demand Sub-Interval
Reset/Command - Circuit Length
87 87 101
670 UINT16 Analog Value
Analog Value 2
480 R/W
R/W NV
NV Seconds 0, 10 - 32767 0 = Sync to Comms
Demand Time Stamp
Reset/Command - Circuit (Year)
88 88 102
671 Analog Value 481 R
R/W NV Year Years since 1900 (118 = 2018)
Demand Time Stamp
Reset/Command (Month)
- Circuit 89 89 103
672 Analog Value 482 R
R/W NV Month 0 - 11 Month (0 = January)
Demand Time Stamp
Reset/Command (Day)
- Circuit 90 90 104
673 Analog Value 483 R
R/W NV Day 1 - 31 Day of the Month
Demand Time Stamp
Reset/Command (Weekday)
- Circuit 91 91 105
674 Analog Value 484 R
R/W NV Weekday 0-6 Weekday (1 = Monday)
Demand Time Stamp
Reset/Command (Hour)
- Circuit 92 92 106
675 Analog Value 485 R
R/W NV Hour 0 - 23 Hour (13 = 1PM)
Demand Time Stamp
Reset/Command (Minute)
- Circuit 93 93 107
676 Analog Value 486 R
R/W NV Minute 0 - 59 Minute
Demand Time Stamp
Reset/Command (Second)
- Circuit 94 94 108
677 Analog Value 487 R
R/W NV Seconds 0 - 59 Second
Reset/Command - Circuit 95 95 678 Analog Value 488 R/W NV Writing to RTC will disable NTP by clearing out URL and/or IP Address
Real Time Clock
Reset/Command (Year) 96
- Circuit 96 109
679 UINT16 Analog Value 489 R/W
R/W NV Year Years since 1900 (118 = 2018)
Real Time Clock (Month) 110 UINT16 R/W Month 0 - 11 Month (0 = January)
Device Object Local_Date
Real Time Clock
Alarm/Event (Day)
Configuration 111 UINT16 R/W Day 1 - 31 Day of the Month
Real Time
Voltage Clock
Alarm (Weekday)
Configuration 112
1000 1003 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
Real TimeAlarm
Overvoltage ClockTime
(Hour) Delay 113
1000 UINT16
UINT16 R/W
R/W NV Hour
Seconds 0 -032767
- 23 Hour (13 = 1PM)
Real TimeAlarm
Undervoltage ClockTime
(Min)Delay 114
1001 UINT16
UINT16 Device Object Local_Time R/W
R/W NV Minute
Seconds 0 -032767
- 59 Minute
Real Time Clock (Second)
Overvoltage Latching Alarm Threshold 115
1002 UINT16
UINT16 R/W
R/W NV Seconds
Volts 0 -032767
- 59 VoltsSecond
Line to Line
UndervotageDigital Output
Latching #1 Threshold
Alarm 116
1003 UINT16 Binary Output 1 R/W
R/W NV Volts 0 - 0, 1
32767 Volts Line to Line
Digital Output #2 117 Binary Output 2 R/W 0, 1
Digital
Branch Input
Alarm #1 State
Configuration 118
1007 1015 Binary Input 1 R 0, 1
Digital Input
High Latching Alarm#2 Time
StateDelay 119
1008 UINT16 Binary Input 2 R
R/W NV Seconds 0 - 0, 1
32767
Low Modbus
LatchingSlave
AlarmAddress
Time Delay 124
1009 UINT16
UINT16 R/W
R/W NV
NV Seconds 01- -32767
254
ModbusAlarm
High Latching TCP PortThresold 125
1014 -1 UINT16
UINT16 R
R/W NV
NV Percent 0 -5021000 Percent of Breaker Size (700 = 70%)
IP Address
Low Latching Alarm Threshold 126
1015 127 -1 UINT16 R/W
R/W NV
NV Percent 0 - 1000 Meter must Percent of Breaker
be rebooted Size
for new (100 =settings
network 10%) to affect.
Gateway 128 129 R/W NV
Device can be rebooted remotely using Global Reset/Command (Register 192)
Waveform CaptureMask Configuration 130
1100 131
1102 R/W NV
Voltage Capture High RMS Threshold 1100 UINT16 R/W NV Volts 0 - 32767 Volts LL (All line voltages will be captured on event)
Current Capture High RMS Threshold 1102 -1 UINT16 R/W NV Percent 0 - 1000 Percent of Breaker Size (800 = 80%)

UMG 804
11
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter Information
Alarms
Serial and Status
Number 1 2 UINT32 Device Object Serial_Number R NV
Global Alarm
Bootloader Version 3
1200 1207 UINT16 R NV
GlobalFirmware
Latching Version
Alarm Status 4
1200 UINT16 Device Object Firmware_Revision R
R/W NV Summary of all Alarm Status Registers (96 Circuits and 3 Voltage)
Device ID 5 UINT16 R/W NV 15172, 22000 22000
Bit1 = Janitza
= High Pointmap
Latching Alarm,
Power Up Counter 6 UINT16 R NV Bit2 = Low Latching Alarm,
Uptime 7 8 UINT32 R NV Seconds Bit8 = Overvoltage Latching Alarm,
Smart Port ID #1 10 UINT16 R NV See Notes Bit9 = Undervoltage Latching Alarm,
Smart Port ID #2 11 UINT16 R NV Bit11 = Waveform Capture Triggered,
See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV Bit12 = Zero Current Detected,
Smart Port ID #4 13 UINT16 R NV Bit13 = Presence of Voltage
Smart Port #1 Serial Number 14 15 UINT32 R NV (All Other Bits are Currently Unused)
SmartRecent
Global Most Port #2 Serial Number
Latching Alarm Channel 16
1202 17 UINT32 R NV
Smart of
Total Number Port #3 Serial
Latching NumberIn Alarm
Channels 18
1204 19 UINT32 R NV
Smart Port #4 Serial Number 20 21 UINT32 R NV
Voltage
Smart Port Status Version
#1 Firmware 22 UINT16 R NV
SmartVoltage
Port #2Alarm
Firmware Version
Status 23
1208 1210 UINT16 R
R/W NV Bit0 = Overvoltage Latching Alarm,
Smart Port #3 Firmware Version 24 UINT16 R NV Bit1 = Undervoltage Latching Alarm,
See Notes
Smart Port #4 Firmware Version 25 UINT16 R NV Bit11 = Waveform Capture Triggered,
MAC Address (Bit 33-48) 26 R NV (All Other Bits are Currently Unused)
MAC Address
Voltage Alarm(Bit 17-32)
Status L1 27
1208 R
R/W NV
MAC Address
Voltage Alarm(Bit 1-16)
Status L2 28
1209 R
R/W NV
Brand Name
Voltage (16Status
Alarm Registers)
L3 29
1210 44 R
R/W NV
Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
supports up to 32 characters (16 registers)
DeviceBranch
Name (16Status
Registers) 61 76 Device Object Object_Name R/W NV
Branch Alarm Status 1211 1306 R/W NV Bit1 = High Latching Alarm,
Bit2 = Low Latching Alarm,
Meter Configuration
Bit11 = Waveform Capture Triggered,
Demand # of Sub-Intervals 100 UINT16 Analog Value 1 R/W NV See1 Notes
-6
Bit12 = Zero Current Detected,
Demand Sub-Interval Length 101 UINT16 Analog Value 2 R/W NV Seconds 0, 10 - 32767 0 == Presence
Bit13 Sync to Comms
of Voltage
Demand Time Stamp (Year) 102 R Year (All Othersince
Years 1900
Bits are (118 = Unused)
Currently 2018)
Demand
AlarmTime Stamp
Status (Month)
- Circuit 1 1 103
1211 R
R/W NV Month 0 - 11 Month (0 = January)
Demand Time Stamp
Alarm Status - Circuit(Day)
2 2 104
1212 R
R/W Day 1 - 31 Day of the Month
Demand
AlarmTime Stamp
Status (Weekday)
- Circuit 3 3 105
1213 R
R/W Weekday 0-6 Weekday (1 = Monday)
Demand
Alarm Time
StatusStamp (Hour)
- Circuit 4 4 106
1214 R
R/W Hour 0 - 23 Hour (13 = 1PM)
Demand
AlarmTime Stamp
Status (Minute)
- Circuit 5 5 107
1215 R
R/W Minute 0 - 59 Minute
Demand
AlarmTime Stamp
Status (Second)
- Circuit 6 6 108
1216 R
R/W Seconds 0 - 59 Second
Alarm Status - Circuit 7 7 1217 R/W Writing to RTC will disable NTP by clearing out URL and/or IP Address
Real Time
Alarm Clock
Status (Year)8
- Circuit 8 109
1218 UINT16 R/W Year Years since 1900 (118 = 2018)
Alarm
Real TimeStatus
Clock- Circuit
(Month) 9 9 1219
110 UINT16 R/W Month 0 - 11 Month (0 = January)
Device Object Local_Date
Alarm Status
Real Time - Circuit
Clock (Day)10 10 1220
111 UINT16 R/W Day 1 - 31 Day of the Month
Alarm
Real TimeStatus
Clock- Circuit
(Weekday) 11 11 1221
112 UINT16 R/W
R/W Weekday 0-6 Weekday (1 = Monday)
Alarm Status
Real Time - Circuit
Clock (Hour) 12 12 1222
113 UINT16 R/W
R/W Hour 0 - 23 Hour (13 = 1PM)
Alarm Status
Real Time - Circuit
Clock (Min)13 13 1223
114 UINT16 Device Object Local_Time R/W
R/W Minute 0 - 59 Minute
Alarm
Real Status
Time - Circuit
Clock (Second) 14 14 1224
115 UINT16 R/W
R/W Seconds 0 - 59 Second
Alarm Status
Digital - Circuit
Output #1 15 15 1225
116 Binary Output 1 R/W
R/W 0, 1
Alarm Status - Circuit 16 16 1226 R/W
Digital Output #2 117 Binary Output 2 R/W 0, 1
Alarm Status - Circuit 17 17 1227 R/W
Digital Input #1 State 118 Binary Input 1 R 0, 1
Alarm Status - Circuit 18 18 1228 R/W
Digital Input #2 State 119 Binary Input 2 R 0, 1
Alarm Status - Circuit 19 19 1229 R/W
Modbus Slave Address 124 UINT16 R/W NV 1 - 254
Alarm Status - Circuit 20 20 1230 R/W
Modbus
Alarm StatusTCP Port 21
- Circuit 21 125
1231 UINT16 R
R/W NV 502
IP Address
Alarm Status - Circuit 22 22 126
1232 127 R/W
R/W NV
Meter must be rebooted for new network settings to affect.
Gateway
Alarm Status - Circuit 23 23 128
1233 129 R/W
R/W NV
Device can be rebooted remotely using Global Reset/Command (Register 192)
Mask
Alarm Status - Circuit 24 24 130
1234 131 R/W
R/W NV
Alarm Status - Circuit 25 25 1235 R/W
Alarm Status - Circuit 26 26 1236 R/W
Alarm Status - Circuit 27 27 1237 R/W

UMG 804
12
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Alarm
Meter Status - Circuit 28
Information 28 1238 R/W
AlarmSerial
Status - Circuit 29
Number 29 1239
1 2 UINT32 Device Object Serial_Number R/W
R NV
Alarm Status -Version
Bootloader Circuit 30 30 1240
3 UINT16 R/W
R NV
Alarm Status Version
Firmware - Circuit 31 31 1241
4 UINT16 Device Object Firmware_Revision R/W
R NV
Alarm Status
Device- ID
Circuit 32 32 1242
5 UINT16 R/W
R/W NV 15172, 22000 22000 = Janitza Pointmap
Alarm Status - Circuit 33 33 1243 R/W
Power Up Counter 6 UINT16 R NV
Alarm Status - Circuit 34 34 1244 R/W
Uptime 7 8 UINT32 R NV Seconds
Alarm Status - Circuit 35 35 1245 R/W
Smart Port ID #1 10 UINT16 R NV
Alarm Status - Circuit 36 36 1246 R/W
Smart Port ID #2 11 UINT16 R NV
Alarm Status - Circuit 37 37 1247 R/W See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart
Alarm Port- Circuit
Status ID #3 38 38 12
1248 UINT16 R
R/W NV
Smart
Alarm Port- Circuit
Status ID #4 39 39 13
1249 UINT16 R
R/W NV
Smart
AlarmPort #1 Serial
Status Number
- Circuit 40 40 14
1250 15 UINT32 R
R/W NV
Smart
AlarmPort #2 Serial
Status Number
- Circuit 41 41 16
1251 17 UINT32 R
R/W NV
Smart
AlarmPort #3 Serial
Status Number
- Circuit 42 42 18
1252 19 UINT32 R
R/W NV
Smart
AlarmPort #4 Serial
Status Number
- Circuit 43 43 20
1253 21 UINT32 R
R/W NV
Alarm
Smart PortStatus - CircuitVersion
#1 Firmware 44 44 1254
22 UINT16 R/W
R NV
Alarm
Smart PortStatus - CircuitVersion
#2 Firmware 45 45 1255
23 UINT16 R/W
R NV
Alarm
Smart PortStatus - CircuitVersion
#3 Firmware 46 46 1256
24 UINT16 R/W
R NV
Alarm
Smart PortStatus - CircuitVersion
#4 Firmware 47 47 1257
25 UINT16 R/W
R NV
AlarmAddress
MAC Status -(Bit
Circuit 48
33-48) 48 1258
26 R/W
R NV
AlarmAddress
MAC Status -(Bit
Circuit 49
17-32) 49 1259
27 R/W
R NV
Alarm Status - (Bit
MAC Address Circuit
1-16)50 50 1260
28 R/W
R NV
Alarm Status - Circuit 51 51 1261 R/W
Brand Name (16 Registers) 29 44 R NV
Alarm Status - Circuit 52 52 1262 R/W Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Alarm Status - Circuit 53 53 1263 R/W supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Alarm Status - Circuit 54 54 1264 R/W
Alarm Status - Circuit 55 55 1265 R/W
MeterStatus
Alarm Configuration
- Circuit 56 56 1266 R/W
Demand # of Sub-Intervals
Alarm Status - Circuit 57 57 100
1267 UINT16 Analog Value 1 R/W
R/W NV 1-6
Demand Sub-Interval
Alarm Status - Circuit Length
58 58 101
1268 UINT16 Analog Value 2 R/W
R/W NV Seconds 0, 10 - 32767 0 = Sync to Comms
Demand Time Stamp
Alarm Status - Circuit (Year)
59 59 102
1269 R
R/W Year Years since 1900 (118 = 2018)
Demand
Alarm Time
StatusStamp (Month)
- Circuit 60 60 103
1270 R
R/W Month 0 - 11 Month (0 = January)
Demand Time Stamp
Alarm Status - Circuit(Day)
61 61 104
1271 R
R/W Day 1 - 31 Day of the Month
AlarmTime
Demand Status - Circuit
Stamp 62
(Weekday) 62 1272
105 R/W
R Weekday 0-6 Weekday (1 = Monday)
Alarm Status
Demand - Circuit
Time Stamp 63
(Hour) 63 1273
106 R/W
R Hour 0 - 23 Hour (13 = 1PM)
AlarmTime
Demand Status - Circuit
Stamp 64
(Minute) 64 1274
107 R/W
R Minute 0 - 59 Minute
AlarmTime
Demand Status - Circuit
Stamp 65
(Second) 65 1275
108 R/W
R Seconds 0 - 59 Second
Alarm Status - Circuit 66 66 1276 R/W Writing to RTC will disable NTP by clearing out URL and/or IP Address
Alarm Status
Real Time - Circuit
Clock (Year)67 67 1277
109 UINT16 R/W
R/W Year Years since 1900 (118 = 2018)
Alarm
Real Status
Time - Circuit
Clock (Month) 68 68 1278
110 UINT16 R/W
R/W Month 0 - 11 Month (0 = January)
Alarm StatusClock
- Circuit Device Object Local_Date
Real Time (Day)69 69 1279
111 UINT16 R/W
R/W Day 1 - 31 Day of the Month
Alarm Status - Circuit 70 70 1280 R/W
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
Alarm Status - Circuit 71 71 1281 R/W
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
Alarm Status - Circuit 72 72 1282 R/W
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Alarm Status - Circuit 73 73 1283 R/W
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Alarm Status - Circuit 74 74 1284 R/W
Digital Output #1 116 Binary Output 1 R/W 0, 1
Alarm Status - Circuit 75 75 1285 R/W
Digital
Alarm Output
Status #2 76
- Circuit 76 117
1286
Binary Output 2 R/W
R/W 0, 1
Digital
Alarm Input- #1
Status State77
Circuit 77 118
1287 Binary Input 1 R
R/W 0, 1
Digital
Alarm Input- #2
Status State78
Circuit 78 119
1288 Binary Input 2 R
R/W 0, 1
Modbus
Alarm Slave
Status Address
- Circuit 79 79 124
1289 UINT16 R/W
R/W NV 1 - 254
Modbus
Alarm StatusTCP Port 80
- Circuit 80 125
1290 UINT16 R
R/W NV 502
IP Address
Alarm Status - Circuit 81 81 126
1291 127 R/W NV
Meter must be rebooted for new network settings to affect.
Alarm Status
Gateway- Circuit 82 82 1292
128 129 R/W NV
Device can be rebooted remotely using Global Reset/Command (Register 192)
Alarm Status
Mask - Circuit 83 83 1293
130 131 R/W NV
Alarm Status - Circuit 84 84 1294 R/W
Alarm Status - Circuit 85 85 1295 R/W
Alarm Status - Circuit 86 86 1296 R/W

UMG 804
13
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Alarm
Meter Status - Circuit 87
Information 87 1297 R/W
AlarmSerial
Status - Circuit 88
Number 88 1298
1 2 UINT32 Device Object Serial_Number R/W
R NV
Alarm Status -Version
Bootloader Circuit 89 89 1299
3 UINT16 R/W
R NV
Alarm Status Version
Firmware - Circuit 90 90 1300
4 UINT16 Device Object Firmware_Revision R/W
R NV
Alarm Status
Device- ID
Circuit 91 91 1301
5 UINT16 R/W
R/W NV 15172, 22000 22000 = Janitza Pointmap
Alarm Status
Power - Circuit 92
Up Counter 92 1302
6 UINT16 R/W
R NV
Alarm Status - Circuit 93
Uptime 93 1303
7 8 UINT32 R/W
R NV Seconds
Alarm Status
Smart Port- Circuit
ID #1 94 94 1304
10 UINT16 R/W
R NV
Alarm Status
Smart Port- Circuit
ID #2 95 95 1305
11 UINT16 R/W
R NV
Alarm Status See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port- Circuit
ID #3 96 96 1306
12 UINT16 R/W
R NV
Smart Port ID #4 13 UINT16 R NV
Smart Port #1 Serial Number 14 15 UINT32 R NV
Smart Port #2 Serial Number 16 17 UINT32 R NV
SmartZero
PortCurrent State
#3 Serial Number 1403
18 1498
19 UINT16
UINT32 Analog Input 1841 - 1936
R NV Zero Current State registers will be updated when current drops to 0A
Branch Zero
Smart Current
Port State
#4 Serial - Circuit 1
Number 1 1403
20 21 UINT32 Analog Input 1841 R
R NV
Branch
SmartZero
PortCurrent State Version
#1 Firmware - Circuit 2 2 1404
22 UINT16 Analog Input 1842 R
R NV
Branch
SmartZero
PortCurrent State Version
#2 Firmware - Circuit 3 3 1405
23 UINT16 Analog Input 1843 R
R NV
Branch
SmartZero
PortCurrent State Version
#3 Firmware - Circuit 4 4 1406
24 UINT16 Analog Input 1844 R
R NV
Branch
SmartZero
PortCurrent State Version
#4 Firmware - Circuit 5 5 1407
25 UINT16
Analog Input 1845 R
R NV
Branch Zero Current State - Circuit 6 6 1408 Analog Input 1846 R
MAC Address (Bit 33-48) 26 R NV
Branch Zero Current State - Circuit 7 7 1409 Analog Input 1847 R
MAC Address (Bit 17-32) 27 R NV
Branch Zero Current State - Circuit 8 8 1410 Analog Input 1848 R
MAC Address (Bit 1-16) 28 R NV
Branch Zero Current State - Circuit 9 9 1411 Analog Input 1849 R
Brand Name (16 Registers) 29 44 R NV
Branch Zero Current State - Circuit 10 10 1412 Analog Input 1850 R Brand Name, Model Name and Device Name
Model
Branch Zero Name
Current(16 Register)
State - Circuit 11 11 45
1413 60 Device Object Model_Name R
R NV
Analog Input 1851 supports up to 32 characters (16 registers)
Device
Branch ZeroName
Current(16State
Registers)
- Circuit 12 12 61
1414 76 Device Object
Analog Input
Object_Name
1852 R/W
R NV
Branch Zero Current State - Circuit 13 13 1415 Analog Input 1853 R
Branch Meter Configuration
Zero Current State - Circuit 14 14 1416 Analog Input 1854 R
Demand
Branch # of Sub-Intervals
Zero Current State - Circuit 15 15 100
1417 UINT16 Analog
Analog Value
Input 1
1855 R/W
R NV 1-6
Demand
Branch Sub-Interval
Zero Current StateLength
- Circuit 16 16 101
1418 UINT16 Analog Value
Input 2
1856 R/W
R NV Seconds 0, 10 - 32767 0 = Sync to Comms
Demand
Branch Time Stamp
Zero Current State (Year)
- Circuit 17 17 102
1419 Analog Input 1857 R Year Years since 1900 (118 = 2018)
Branch Zero Current
Demand Time StampState(Month)
- Circuit 18 18 1420
103 Analog Input 1858 R Month 0 - 11 Month (0 = January)
Branch Zero Current
Demand State -(Day)
Time Stamp Circuit 19 19 1421
104 Analog Input 1859 R Day 1 - 31 Day of the Month
Branch ZeroTime
Demand Current
StampState - Circuit 20
(Weekday) 20 1422
105 Analog Input 1860 R
R Weekday 0-6 Weekday (1 = Monday)
Branch Zero Current
Demand State (Hour)
Time Stamp - Circuit 21 21 1423
106 Analog Input 1861 R
R Hour 0 - 23 Hour (13 = 1PM)
Branch Zero Time
Demand Current State(Minute)
Stamp - Circuit 22 22 1424
107 Analog Input 1862 R
R Minute 0 - 59 Minute
Branch Zero Time
Demand Current State(Second)
Stamp - Circuit 23 23 1425
108
Analog Input 1863 R
R Seconds 0 - 59 Second
Branch Zero Current State - Circuit 24 24 1426 Analog Input 1864 R
Writing to RTC will disable NTP by clearing out URL and/or IP Address
Branch Zero Current State - Circuit 25 25 1427 Analog Input 1865 R
Real Time Clock (Year) 109 UINT16 R/W Year Years since 1900 (118 = 2018)
Branch Zero Current State - Circuit 26 26 1428 Analog Input 1866 R
Real Time Clock (Month) 110 UINT16 R/W Month 0 - 11 Month (0 = January)
Branch Zero Current State - Circuit 27 27 1429 Device
AnalogObject
Input Local_Date
1867 R
Real Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
Branch Zero Current State - Circuit 28 28 1430 Analog Input 1868 R
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
Branch Zero Current State - Circuit 29 29 1431 Analog Input 1869 R
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
Branch Zero Current State - Circuit 30 30 1432 Analog Input 1870 R
Real Time
Branch Zero CurrentClock (Min)
State - Circuit 31 31 114
1433 UINT16 Device Object
Analog Input
Local_Time
1871
R/W
R Minute 0 - 59 Minute
BranchReal
ZeroTime ClockState
Current (Second)
- Circuit 32 32 115
1434 UINT16 Analog Input 1872 R/W
R Seconds 0 - 59 Second
Digital
Branch Zero Output
Current State#1- Circuit 33 33 116
1435 Binary
AnalogOutput
Input 1
1873 R/W
R 0, 1
Digital
Branch Zero Output
Current State#2- Circuit 34 34 117
1436 Binary
AnalogOutput
Input 2
1874 R/W
R 0, 1
Digital
Branch Zero Input State
Current #1 State
- Circuit 35 35 118
1437 Binary Input
Analog Input 1
1875 R 0, 1
Digital
Branch Zero Input State
Current #2 State
- Circuit 36 36 119
1438 Binary Input
Analog Input 2
1876 R 0, 1
Branch Modbus SlaveState
Zero Current Address
- Circuit 37 37 124
1439 UINT16 Analog Input 1877 R/W
R NV 1 - 254
Branch Zero Current
Modbus TCPState
Port- Circuit 38 38 1440
125 UINT16 Analog Input 1878 R NV 502
Branch Zero Current State - Circuit 39
IP Address 39 1441
126 127 Analog Input 1879 R
R/W NV
Meter must be rebooted for new network settings to affect.
Branch Zero Current
Gateway State - Circuit 40 40 1442
128 129 Analog Input 1880 R
R/W NV
Branch Zero Current Device can be rebooted remotely using Global Reset/Command (Register 192)
MaskState - Circuit 41 41 1443
130 131 Analog Input 1881 R
R/W NV
Branch Zero Current State - Circuit 42 42 1444 Analog Input 1882 R
Branch Zero Current State - Circuit 43 43 1445 Analog Input 1883 R
Branch Zero Current State - Circuit 44 44 1446 Analog Input 1884 R

UMG 804
14
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Branch Zero
MeterCurrent State - Circuit 45
Information 45 1447 Analog Input 1885 R
Branch ZeroSerial
Current State - Circuit 46
Number 46 1448
1 2 UINT32 AnalogObject
Device Input 1886
Serial_Number R
R NV
Branch Zero Current Version
Bootloader State - Circuit 47 47 1449
3 UINT16 Analog Input 1887 R
R NV
Branch Zero CurrentVersion
Firmware State - Circuit 48 48 1450
4 UINT16 AnalogObject
Device Input 1888
Firmware_Revision R
R NV
Branch Zero Current
Device State
ID - Circuit 49 49 1451
5 UINT16
Analog Input 1889 R
R/W NV 15172, 22000 22000 = Janitza Pointmap
Branch Zero Current State - Circuit 50 50 1452 Analog Input 1890 R
Power Up Counter 6 UINT16 R NV
Branch Zero Current State - Circuit 51 51 1453 Analog Input 1891 R
Uptime 7 8 UINT32 R NV Seconds
Branch Zero Current State - Circuit 52 52 1454 Analog Input 1892 R
Smart Port ID #1 10 UINT16 R NV
Branch Zero Current State - Circuit 53 53 1455 Analog Input 1893 R
Smart Port ID #2 11 UINT16 R NV
Branch Zero Current State - Circuit 54 54 1456 Analog Input 1894 R See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Branch ZeroSmart PortState
Current ID #3- Circuit 55 55 12
1457 UINT16 Analog Input 1895
R
R NV
Branch ZeroSmart PortState
Current ID #4- Circuit 56 56 13
1458 UINT16 Analog Input 1896 R
R NV
Smart
Branch ZeroPort #1 Serial
Current StateNumber
- Circuit 57 57 14
1459 15 UINT32 Analog Input 1897 R
R NV
Smart
Branch ZeroPort #2 Serial
Current StateNumber
- Circuit 58 58 16
1460 17 UINT32 Analog Input 1898 R
R NV
Smart
Branch ZeroPort #3 Serial
Current StateNumber
- Circuit 59 59 18
1461 19 UINT32 Analog Input 1899 R NV
Smart
Branch ZeroPort #4 Serial
Current StateNumber
- Circuit 60 60 20
1462 21 UINT32 Analog Input 1900 R NV
SmartZero
Branch PortCurrent
#1 Firmware
State -Version
Circuit 61 61 22
1463 UINT16 Analog Input 1901 R NV
Branch
SmartZero
PortCurrent State -Version
#2 Firmware Circuit 62 62 1464
23 UINT16 Analog Input 1902 R NV
Branch
SmartZero
PortCurrent State -Version
#3 Firmware Circuit 63 63 1465
24 UINT16 Analog Input 1903 R NV
Branch
SmartZero
PortCurrent State -Version
#4 Firmware Circuit 64 64 1466
25 UINT16 Analog Input 1904 R
R NV
BranchMAC
ZeroAddress
Current(Bit
State - Circuit 65
33-48) 65 1467
26 Analog Input 1905 R
R NV
BranchMAC
ZeroAddress
Current(Bit
State - Circuit 66
17-32) 66 1468
27 Analog Input 1906 R
R NV
BranchMAC
Zero Address
Current State - Circuit 67
(Bit 1-16) 67 1469
28
Analog Input 1907 R
R NV
Branch Zero Current State - Circuit 68 68 1470 Analog Input 1908 R
Brand Name (16 Registers) 29 44 R NV
Branch Zero Current State - Circuit 69 69 1471 Analog Input 1909 R Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Branch Zero Current State - Circuit 70 70 1472 Analog Input 1910 R supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Branch Zero Current State - Circuit 71 71 1473 Analog Input 1911 R
Branch Zero Current State - Circuit 72 72 1474 Analog Input 1912 R
Branch Meter Configuration
Zero Current State - Circuit 73 73 1475 Analog Input 1913 R
BranchDemand # of Sub-Intervals
Zero Current State - Circuit 74 74 100
1476 UINT16 Analog Value
Analog Input
1
1914 R/W
R NV 1-6
Branch Zero Current StateLength
Demand Sub-Interval - Circuit 75 75 101
1477 UINT16 Analog
Analog Value
Input 2
1915 R/W
R NV Seconds 0, 10 - 32767 0 = Sync to Comms
Branch Zero Current State (Year)
Demand Time Stamp - Circuit 76 76 102
1478 Analog Input 1916 R
R Year Years since 1900 (118 = 2018)
Demand
Branch Time Stamp
Zero Current State(Month)
- Circuit 77 77 103
1479 Analog Input 1917 R Month 0 - 11 Month (0 = January)
BranchDemand Time Stamp
Zero Current State -(Day)
Circuit 78 78 104
1480 Analog Input 1918 R Day 1 - 31 Day of the Month
Demand
Branch ZeroTime Stamp
Current (Weekday)
State - Circuit 79 79 105
1481 Analog Input 1919 R Weekday 0-6 Weekday (1 = Monday)
Branch Zero Current
Demand State (Hour)
Time Stamp - Circuit 80 80 1482
106 Analog Input 1920 R Hour 0 - 23 Hour (13 = 1PM)
Branch Zero Time
Demand Current State(Minute)
Stamp - Circuit 81 81 1483
107 Analog Input 1921 R Minute 0 - 59 Minute
Branch Zero Time
Demand Current State(Second)
Stamp - Circuit 82 82 1484
108 Analog Input 1922 R
R Seconds 0 - 59 Second
Branch Zero Current State - Circuit 83 83 1485 Analog Input 1923 R Writing to RTC will disable NTP by clearing out URL and/or IP Address
Branch Real
Zero Time
Current State
Clock - Circuit 84
(Year) 84 1486
109 UINT16 Analog Input 1924 R
R/W Year Years since 1900 (118 = 2018)
BranchReal
ZeroTime
Current State
Clock - Circuit 85
(Month) 85 1487
110 UINT16 Analog Input 1925 R
R/W Month 0 - 11 Month (0 = January)
Branch Zero Device
AnalogObject Local_Date
Real Current State - Circuit 86 86 1488 R
Input 1926
Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
Branch Zero Current State - Circuit 87 87 1489 Analog Input 1927 R
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
Branch Zero Current State - Circuit 88 88 1490 Analog Input 1928 R
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
Branch Zero Current State - Circuit 89 89 1491 Analog Input 1929 R
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Branch Zero Current State - Circuit 90 90 1492 Analog Input 1930 R
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Branch Zero Current State - Circuit 91 91 1493 Analog Input 1931 R
Digital Output #1 116 Binary Output 1 R/W 0, 1
Branch Zero Current State - Circuit 92 92 1494 Analog Input 1932 R
Branch ZeroDigital Output
Current State #2- Circuit 93 93 117
1495
Binary Output
Analog Input
2
1933
R/W
R 0, 1
Digital
Branch Zero Input State
Current #1 State
- Circuit 94 94 118
1496 Binary Input
Analog Input
1
1934 R
R 0, 1
Digital
Branch Zero Input State
Current #2 State
- Circuit 95 95 119
1497 Binary Input
Analog Input 2
1935 R
R 0, 1
Modbus Slave Address
Branch Zero Current State - Circuit 96 96 124
1498 UINT16 Analog Input 1936 R/W
R NV 1 - 254
Modbus TCP Port 125 UINT16 R NV 502
IP Address 126 127 R/W NV
Meter must be rebooted for new network settings to affect.
Gateway
Smart Port/Panel Configuration 128 129 R/W NV
Device can be rebooted remotely using Global Reset/Command (Register 192)
Smart Port 1/2 (PanelMask
1) Circuit Configuration 130
1800 131 R/W
R/W NV
NV 0-4 0 = Top Feed, 1 = Bottom Feed, 2 = Single Row Sequential,
Smart Port 3/4 (Panel 2) Circuit Configuration 1801 R/W NV 0-4 3 = Single Row Odd/Even, 4 = Sequential
Panel 1 Location (64 Registers) 1802 1865 R/W NV Location string for Panel 1 and Panel 2,
Panel 2 Location (64 Registers) 1866 1929 R/W NV Each string supports up to 128 characters (64 registers)

UMG 804
15
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter Information
Smart Port 1 Status 1930 R
Serial
Smart Number
Port 2 Status 1
1931 2 UINT32 Device Object Serial_Number R NV
0-3 0 = Nothing Detected, 1 = Status OK, 2 = Offline, 3 = Invalid Device Detected
Bootloader
Smart Port 3Version
Status 3
1932 UINT16 R NV
Firmware
Smart Port Version
4 Status 4
1933 UINT16 Device Object Firmware_Revision R NV
Device ID 5 UINT16 R/W NV 15172, 22000 22000 = Janitza Pointmap
Voltage
Power UpReadings
Counter 6 UINT16 R NV
Uptime
Voltage Scale 7 8 UINT32 R NV Seconds
Smart Port ID #1
Frequency 10 UINT16 4900 4901 Analog Input 1 R NV Hz Derived from L1
Smart Port
Voltage ID #2
LN Average 11 UINT16 4902 4903 Analog Input 2 R NV Volts
See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port
Voltage ID #3
LL Average 12 UINT16 4904 4905 Analog Input 3 R NV Volts
Smart Port ID #4 13 UINT16 R NV
Smart Port #1 Serial
Voltage LN Number 14 15 UINT32 4906 4911 Analog Input 4-6 R NV Volts
Smart Port #2 Serial
Voltage L1 Number 16 17 UINT32 4906 4907 Analog Input 4 R NV Volts
Smart Port #3 Serial
Voltage L2 Number 18 19 UINT32 4908 4909 Analog Input 5 R NV Volts
Smart Port #4 Serial
Voltage L3 Number 20 21 UINT32 4910 4911 Analog Input 6 R NV Volts
Smart Port #1 Firmware Version 22 UINT16 R NV
Smart PortVoltage
#2 Firmware
LL Version 23 UINT16 4912 4917 Analog Input 7-9 R NV Volts
Smart Port #3 Firmware
Voltage L1 - L2 Version 24 UINT16 4912 4913 Analog Input 7 R NV Volts
Smart Port #4 Firmware
Voltage L2 - L3 Version 25 UINT16 4914 4915 Analog Input 8 R NV Volts
MACVoltage
AddressL3 (Bit 33-48)
- L1 26 4916 4917 Analog Input 9 R NV Volts
MAC Address (Bit 17-32) 27 R NV
MAC Address
Percent THD(Bit 1-16) 28 4918 4925 Analog Input 10 - 13 R NV Percent
Brand
Percent Name
THD (16 Registers)
Average (L1, L2 & L3) 29 44 4918 4919 Analog Input 10 R NV Percent
Brand Name, Model Name and Device Name
Model Name THD
Percent (16 Register)
- L1 45 60 4920 4921 Device
AnalogObject
Input Model_Name
11 R NV Percent
supports up to 32 characters (16 registers)
DevicePercent
Name THD
(16 Registers)
- L2 61 76 4922 4923 Device
AnalogObject
Input Object_Name
12 R/W
R NV Percent
Percent THD - L3 4924 4925 Analog Input 13 R Percent
Meter Configuration
Demand # of Sub-Intervals
Voltage Angle 100 UINT16 4926 4931 Analog Value
Input 14 1- 16 R/W
R NV Degrees 1-6
Demand Sub-Interval
L1 Angle Length 101 UINT16 4926 4927 Analog Value
Input 2
14 R/W
R NV Seconds
Degrees 0, 10 - 32767 Reference used to derive 0 =angle
Sync for
to Comms
other phases - Always Reads 0
Demand Time Stamp (Year)
L2 Angle 102 4928 4929 Analog Input 15 R Year
Degrees Years since 1900 (118 = 2018)
Demand Time Stamp (Month)
L3 Angle 103 4930 4931 Analog Input 16 R Month
Degrees 0 - 11 Month (0 = January)
Demand Time Stamp (Day) 104 R Day 1 - 31 Day of the Month
Demand Time Stamp (Weekday) 105 R Weekday 0-6 Weekday (1 = Monday)
Single Phase
Demand Time Reading by Type
Stamp (Hour) 106 R Hour 0 - 23 Hour (13 = 1PM)
Demand Time Stamp (Minute) 107 R Minute 0 - 59 Minute
Demand TimekWh Stamp (Second) 108 10000 10191 Analog Input 17 - 112 R NV Seconds
kWh 0 - 59 Second
kWh - Circuit 1 1 10000 10001 Analog Input 17 R NV kWh Writing to RTC will disable NTP by clearing out URL and/or IP Address
RealkWh
Time- Circuit
Clock (Year)
2 2 109 UINT16 10002 10003 Analog Input 18 R/W
R NV Year
kWh Years since 1900 (118 = 2018)
Real Time
kWh -Clock (Month)
Circuit 3 3 110 UINT16 10004 10005 Analog Input 19 R/W
R NV Month
kWh 0 - 11 Month (0 = January)
Device Object Local_Date
RealkWh
Time- Circuit
Clock (Day)
4 4 111 UINT16 10006 10007 Analog Input 20 R/W
R NV Day
kWh 1 - 31 Day of the Month
Real Time
kWhClock (Weekday)
- Circuit 5 5 112 UINT16 10008 10009 Analog Input 21 R/W
R NV Weekday
kWh 0-6 Weekday (1 = Monday)
RealkWh
Time- Clock
Circuit(Hour)
6 6 113 UINT16 10010 10011 Analog Input 22 R/W
R NV Hour
kWh 0 - 23 Hour (13 = 1PM)
RealkWh
Time- Circuit
Clock (Min)
7 7 114 UINT16 10012 10013 Device
AnalogObject
Input Local_Time
23 R/W
R NV Minute
kWh 0 - 59 Minute
Real Time
kWh -Clock (Second)
Circuit 8 8 115 UINT16 10014 10015 Analog Input 24 R/W
R NV Seconds
kWh 0 - 59 Second
Digital
kWh -Output
Circuit #1
9 9 116 10016 10017 Binary
AnalogOutput
Input 1
25 R/W
R NV kWh 0, 1
Digital
kWh - Output #2
Circuit 10 10 117 10018 10019 Binary
AnalogOutput
Input 2
26 R/W
R NV kWh 0, 1
Digital
kWhInput #1 State
- Circuit 11 11 118 10020 10021 Binary Input
Analog Input 1
27 R
R NV kWh 0, 1
Digital
kWhInput #2 State
- Circuit 12 12 119 10022 10023 Binary Input
Analog Input 2
28 R
R NV kWh 0, 1
Modbus
kWh -Slave Address
Circuit 13 13 124 UINT16 10024 10025 Analog Input 29 R/W
R NV
NV kWh 1 - 254
Modbus TCP Port
kWh - Circuit 14 14 125 UINT16 10026 10027 Analog Input 30 R NV kWh 502
kWhIP -Address
Circuit 15 15 126 127 10028 10029 Analog Input 31 R/W
R NV kWh
Meter must be rebooted for new network settings to affect.
kWhGateway
- Circuit 16 16 128 129 10030 10031 Analog Input 32 R
R/W NV kWh
Device can be rebooted remotely using Global Reset/Command (Register 192)
kWh -Mask
Circuit 17 17 130 131 10032 10033 Analog Input 33 R
R/W NV kWh
kWh - Circuit 18 18 10034 10035 Analog Input 34 R NV kWh
kWh - Circuit 19 19 10036 10037 Analog Input 35 R NV kWh
kWh - Circuit 20 20 10038 10039 Analog Input 36 R NV kWh

UMG 804
16
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter
kWh -Information
Circuit 21 21 10040 10041 Analog Input 37 R NV kWh
kWh
Serial- Circuit
Number 22 22 1 2 UINT32 10042 10043 AnalogObject
Device Input 38
Serial_Number R NV kWh
kWh - Circuit
Bootloader 23
Version 23 3 UINT16 10044 10045 Analog Input 39 R
R NV
NV kWh
kWh - Circuit
Firmware 24
Version 24 4 UINT16 10046 10047 AnalogObject
Device Input 40
Firmware_Revision R
R NV
NV kWh
kWh - Circuit
Device ID 25 25 5 UINT16 10048 10049 Analog Input 41 R
R/W NV
NV kWh 15172, 22000 22000 = Janitza Pointmap
kWh -Up
Power Circuit
Counter26 26 6 UINT16 10050 10051 Analog Input 42 R
R NV
NV kWh
kWh - Circuit 27 27 10052 10053 Analog Input 43 R NV kWh
Uptime 7 8 UINT32 R NV Seconds
kWh - Circuit 28 28 10054 10055 Analog Input 44 R NV kWh
Smart Port ID #1 10 UINT16 R NV
kWh - Circuit 29 29 10056 10057 Analog Input 45 R NV kWh
Smart Port ID #2 11 UINT16 R NV
kWh - Circuit 30 30 10058 10059 Analog Input 46 R NV kWh See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
kWh - Circuit 31 31 10060 10061 Analog Input 47 R NV kWh
Smart
kWh - Port
CircuitID 32
#4 32 13 UINT16 10062 10063 Analog Input 48 R
R NV
NV kWh
Smart kWh
Port #1 Serial33
- Circuit Number 33 14 15 UINT32 10064 10065 Analog Input 49 R
R NV
NV kWh
Smart kWh
Port #2 Serial34
- Circuit Number 34 16 17 UINT32 10066 10067 Analog Input 50 R
R NV
NV kWh
Smart kWh
Port #3 Serial35
- Circuit Number 35 18 19 UINT32 10068 10069 Analog Input 51 R NV kWh
Smart kWh
Port #4 Serial36
- Circuit Number 36 20 21 UINT32 10070 10071 Analog Input 52 R NV kWh
Smart Port
kWh #1- Firmware
Circuit 37 Version 37 22 UINT16 10072 10073 Analog Input 53 R NV kWh
kWh
Smart Port #2- Firmware
Circuit 38 Version 38 23 UINT16 10074 10075 Analog Input 54 R NV kWh
kWh
Smart Port #3- Firmware
Circuit 39 Version 39 24 UINT16 10076 10077 Analog Input 55 R NV kWh
kWh
Smart Port #4- Firmware
Circuit 40 Version 40 25 UINT16 10078 10079 Analog Input 56 R NV kWh
MACkWh - Circuit
Address (Bit 41
33-48) 41 26 10080 10081 Analog Input 57 R
R NV
NV kWh
MACkWh - Circuit
Address (Bit 42
17-32) 42 27 10082 10083 Analog Input 58 R
R NV
NV kWh
MACkWh - Circuit
Address (Bit431-16) 43 28 10084 10085 Analog Input 59 R
R NV
NV kWh
BrandkWh - Circuit 44 44 10086 10087 R NV kWh
Analog Input 60
Name (16 Registers) 29 44 R NV
kWh - Circuit 45 45 10088 10089 Analog Input 61 R NV kWh Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
kWh - Circuit 46 46 10090 10091 Analog Input 62 R NV kWh supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
kWh - Circuit 47 47 10092 10093 Analog Input 63 R NV kWh
kWh - Circuit 48 48 10094 10095 Analog Input 64 R NV kWh
Meter Configuration
kWh - Circuit 49 49 10096 10097 Analog Input 65 R NV kWh
DemandkWh# -ofCircuit
Sub-Intervals
50 50 100 UINT16 10098 10099
Analog Value
Analog Input
1
66 R/W
R NV
NV kWh 1-6
Demand kWhSub-Interval
- Circuit 51Length 51 101 UINT16 10100 10101 Analog
Analog Value
Input
2
67 R/W
R NV
NV Seconds
kWh 0, 10 - 32767 0 = Sync to Comms
Demand kWh - Circuit 52(Year)
Time Stamp 52 102 10102 10103 Analog Input 68 R
R NV Year
kWh Years since 1900 (118 = 2018)
Demand Time
kWh Stamp53
- Circuit (Month) 53 103 10104 10105 Analog Input 69 R
R NV Month
kWh 0 - 11 Month (0 = January)
DemandkWhTime Stamp
- Circuit 54(Day) 54 104 10106 10107 Analog Input 70 R NV Day
kWh 1 - 31 Day of the Month
DemandkWh Time- Stamp
Circuit (Weekday)
55 55 105 10108 10109 Analog Input 71 R NV Weekday
kWh 0-6 Weekday (1 = Monday)
Demand kWh - Circuit
Time Stamp 56(Hour) 56 106 10110 10111 Analog Input 72 R NV kWh
Hour 0 - 23 Hour (13 = 1PM)
Demand kWh
Time- Circuit
Stamp57 (Minute) 57 107 10112 10113 Analog Input 73 R NV kWh
Minute 0 - 59 Minute
Demand kWh
Time- Circuit
Stamp58 (Second) 58 108 10114 10115 Analog Input 74 R NV kWh
Seconds 0 - 59 Second
kWh - Circuit 59 59 10116 10117 Analog Input 75 R NV kWh Writing to RTC will disable NTP by clearing out URL and/or IP Address
RealkWh
Time- Circuit 60
Clock (Year) 60 109 UINT16 10118 10119 Analog Input 76 R
R/W NV kWh
Year Years since 1900 (118 = 2018)
RealkWh
Time- Clock
Circuit(Month)
61 61 110 UINT16 10120 10121 Analog Input 77 R
R/W NV kWh
Month 0 - 11 Month (0 = January)
kWh - Circuit 62 62 10122 10123 Device
AnalogObject
Input Local_Date
78 R NV kWh
Real Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
kWh Clock
Real Time - Circuit 63
(Weekday) 63 112 UINT16 10124 10125 Analog Input 79 R
R/W NV kWh
Weekday 0-6 Weekday (1 = Monday)
RealkWh - Circuit 64 64 10126 10127 R NV kWh
Analog Input 80
Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
kWh - Circuit 65 65 10128 10129 Analog Input 81 R NV kWh
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
kWh - Circuit 66 66 10130 10131 Analog Input 82 R NV kWh
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
kWh - Circuit 67 67 10132 10133 Analog Input 83 R NV kWh
Digital Output #1 116 Binary Output 1 R/W 0, 1
kWh - Circuit 68 68 10134 10135 Analog Input 84 R NV kWh
Digital Output #2 117 Binary Output 2 R/W 0, 1
kWh - Circuit 69 69 10136 10137 Analog Input 85 R NV kWh
Digital
kWhInput #1 State
- Circuit 70 70 118 10138 10139
Binary Input
Analog Input
1
86 R
R NV kWh 0, 1
Digital
kWhInput #2 State
- Circuit 71 71 119 10140 10141 Binary Input
Analog Input
2
87 R
R NV kWh 0, 1
Modbus Slave
kWh - Circuit 72Address 72 124 UINT16 10142 10143 Analog Input 88 R/W
R NV
NV kWh 1 - 254
Modbus TCP
kWh - Circuit 73 Port 73 125 UINT16 10144 10145 Analog Input 89 R
R NV
NV kWh 502
kWhIP -Address
Circuit 74 74 126 127 10146 10147 Analog Input 90 R/W
R NV kWh
Meter must be rebooted for new network settings to affect.
kWhGateway
- Circuit 75 75 128 129 10148 10149 Analog Input 91 R/W
R NV kWh
Device can be rebooted remotely using Global Reset/Command (Register 192)
kWh -MaskCircuit 76 76 130 131 10150 10151 Analog Input 92 R
R/W NV kWh
kWh - Circuit 77 77 10152 10153 Analog Input 93 R NV kWh
kWh - Circuit 78 78 10154 10155 Analog Input 94 R NV kWh
kWh - Circuit 79 79 10156 10157 Analog Input 95 R NV kWh

UMG 804
17
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
kWh -Information
Meter Circuit 80 80 10158 10159 Analog Input 96 R NV kWh
kWh - Circuit
Serial Number 81 81 1 2 UINT32 10160 10161 AnalogObject
Device Input 97
Serial_Number R
R NV
NV kWh
kWh - Circuit
Bootloader 82
Version 82 3 UINT16 10162 10163 Analog Input 98 R
R NV
NV kWh
kWh - Circuit
Firmware 83
Version 83 4 UINT16 10164 10165 AnalogObject
Device Input 99
Firmware_Revision R
R NV
NV kWh
kWh - Circuit
Device ID 84 84 5 UINT16 10166 10167 Analog Input 100 R
R/W NV
NV kWh 15172, 22000 22000 = Janitza Pointmap
kWh - Circuit 85 85 10168 10169 Analog Input 101 R NV kWh
Power Up Counter 6 UINT16 R NV
kWh - Circuit 86 86 10170 10171 Analog Input 102 R NV kWh
Uptime 7 8 UINT32 R NV Seconds
kWh - Circuit 87 87 10172 10173 Analog Input 103 R NV kWh
Smart Port ID #1 10 UINT16 R NV
kWh - Circuit 88 88 10174 10175 Analog Input 104 R NV kWh
Smart Port ID #2 11 UINT16 R NV
kWh - Circuit 89 89 10176 10177 Analog Input 105 R NV kWh See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart
kWh - Port ID 90
Circuit #3 90 12 UINT16 10178 10179 Analog Input 106
R
R NV
NV kWh
Smart
kWh - Port ID 91
Circuit #4 91 13 UINT16 10180 10181 Analog Input 107 R
R NV
NV kWh
Smart kWh
Port #1 Serial92
- Circuit Number 92 14 15 UINT32 10182 10183 Analog Input 108 R
R NV
NV kWh
Smart kWh
Port #2 Serial93
- Circuit Number 93 16 17 UINT32 10184 10185 Analog Input 109 R
R NV
NV kWh
Smart kWh
Port #3 Serial94
- Circuit Number 94 18 19 UINT32 10186 10187 Analog Input 110 R
R NV
NV kWh
Smart kWh
Port #4 Serial95
- Circuit Number 95 20 21 UINT32 10188 10189 Analog Input 111 R
R NV
NV kWh
Smart Port
kWh#1- Firmware
Circuit 96 Version 96 22 UINT16 10190 10191 Analog Input 112 R
R NV
NV kWh
Smart Port #2 Firmware Version 23 UINT16 R NV
Smart Port #3kVARh
Firmware Version 24 UINT16 10192 10383 Analog Input 113 - 208 R
R NV
NV kVARh
Smart Port #4 Firmware
kVARh - Circuit 1 Version 1 25 UINT16 10192 10193 Analog Input 113 R
R NV
NV kVARh
MACkVARh
Address (Bit 33-48)
- Circuit 2 2 26 10194 10195 Analog Input 114 R
R NV
NV kVARh
MACkVARh
Address (Bit 17-32)
- Circuit 3 3 27 10196 10197 Analog Input 115 R
R NV
NV kVARh
MAC Address
kVARh (Bit 1-16)
- Circuit 4 4 28 10198 10199 Analog Input 116 R
R NV
NV kVARh
BrandkVARh
Name- (16 Registers)
Circuit 5 5 29 44 10200 10201 Analog Input 117 R
R NV
NV kVARh Brand Name, Model Name and Device Name
Model Name (16
kVARh - Circuit 6Register) 6 45 60 10202 10203 Device
AnalogObject
Input Model_Name
118 R
R NV
NV kVARh supports up to 32 characters (16 registers)
Device Name- (16
kVARh Registers)
Circuit 7 7 61 76 10204 10205 Device
AnalogObject
Input Object_Name
119 R/W
R NV
NV kVARh
kVARh - Circuit 8 8 10206 10207 Analog Input 120 R NV kVARh
Meter
kVARhConfiguration
- Circuit 9 9 10208 10209 Analog Input 121 R NV kVARh
Demand
kVARh # of Sub-Intervals
- Circuit 10 10 100 UINT16 10210 10211 Analog
Analog Value
Input 1
122 R/W
R NV
NV kVARh 1-6
Demand
kVARhSub-Interval
- Circuit 11Length 11 101 UINT16 10212 10213 Analog
Analog Value
Input 2
123 R/W
R NV
NV Seconds
kVARh 0, 10 - 32767 0 = Sync to Comms
Demand
kVARh Time Stamp12(Year)
- Circuit 12 102 10214 10215 Analog Input 124 R NV Year
kVARh Years since 1900 (118 = 2018)
Demand Time- Circuit
kVARh Stamp 13 (Month) 13 103 10216 10217 Analog Input 125 R NV Month
kVARh 0 - 11 Month (0 = January)
Demand
kVARh Time Stamp14(Day)
- Circuit 14 104 10218 10219 Analog Input 126 R NV Day
kVARh 1 - 31 Day of the Month
Demand kVARh
Time -Stamp
Circuit(Weekday)
15 15 105 10220 10221 Analog Input 127 R NV kVARh
Weekday 0-6 Weekday (1 = Monday)
kVARh
Demand Time- Circuit
Stamp16 (Hour) 16 106 10222 10223 Analog Input 128 R NV kVARh
Hour 0 - 23 Hour (13 = 1PM)
DemandkVARh
Time- Stamp
Circuit (Minute)
17 17 107 10224 10225 Analog Input 129 R
R NV kVARh
Minute 0 - 59 Minute
DemandkVARh
Time- Stamp
Circuit (Second)
18 18 108 10226 10227 Analog Input 130 R
R NV kVARh
Seconds 0 - 59 Second
kVARh - Circuit 19 19 10228 10229 Analog Input 131 R NV kVARh Writing to RTC will disable NTP by clearing out URL and/or IP Address
kVARh
Real Time- Clock
Circuit(Year)
20 20 109 UINT16 10230 10231 Analog Input 132 R
R/W NV kVARh
Year Years since 1900 (118 = 2018)
RealkVARh - Circuit 21 21 10232 10233 R NV kVARh
Analog Input 133
Time Clock (Month) 110 UINT16 R/W Month 0 - 11 Month (0 = January)
kVARh - Circuit 22 22 10234 10235 Device
AnalogObject
Input Local_Date
134 R NV kVARh
Real Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
kVARh - Circuit 23 23 10236 10237 Analog Input 135 R NV kVARh
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
kVARh - Circuit 24 24 10238 10239 Analog Input 136 R NV kVARh
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
kVARh - Circuit 25 25 10240 10241 Analog Input 137 R NV kVARh
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
kVARh - Circuit 26 26 10242 10243 Analog Input 138 R NV kVARh
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
kVARh - Circuit 27 27 10244 10245 Analog Input 139 R NV kVARh
Digital -Output
kVARh Circuit #1
28 28 116 10246 10247
Binary Output
Analog Input
1
140
R/W
R NV kVARh 0, 1
Digital -Output
kVARh Circuit #2
29 29 117 10248 10249 Binary Output
Analog Input
2
141 R/W
R NV kVARh 0, 1
Digital
kVARhInput #1 State
- Circuit 30 30 118 10250 10251 Binary Input
Analog Input 1
142 R
R NV kVARh 0, 1
Digital
kVARhInput #2 State
- Circuit 31 31 119 10252 10253 Binary Input
Analog Input 2
143 R
R NV kVARh 0, 1
Modbus
kVARhSlave Address
- Circuit 32 32 124 UINT16 10254 10255 Analog Input 144 R/W
R NV kVARh 1 - 254
Modbus
kVARh TCP Port
- Circuit 33 33 125 UINT16 10256 10257 Analog Input 145 R NV kVARh 502
kVARhIP Address
- Circuit 34 34 126 127 10258 10259 Analog Input 146 R/W
R NV kVARh
Meter must be rebooted for new network settings to affect.
kVARh - Circuit 35
Gateway 35 128 129 10260 10261 Analog Input 147 R
R/W NV kVARh
Device can be rebooted remotely using Global Reset/Command (Register 192)
kVARhMask- Circuit 36 36 130 131 10262 10263 Analog Input 148 R
R/W NV kVARh
kVARh - Circuit 37 37 10264 10265 Analog Input 149 R NV kVARh
kVARh - Circuit 38 38 10266 10267 Analog Input 150 R NV kVARh
kVARh - Circuit 39 39 10268 10269 Analog Input 151 R NV kVARh

UMG 804
18
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter
kVARhInformation
- Circuit 40 40 10270 10271 Analog Input 152 R NV kVARh
kVARh
Serial-Number
Circuit 41 41 1 2 UINT32 10272 10273 AnalogObject
Device Input 153
Serial_Number R NV kVARh
kVARh - Circuit
Bootloader 42
Version 42 3 UINT16 10274 10275 Analog Input 154 R
R NV
NV kVARh
kVARh
Firmware- Circuit
Version43 43 4 UINT16 10276 10277 AnalogObject
Device Input 155
Firmware_Revision R
R NV
NV kVARh
kVARh - Circuit
Device ID 44 44 5 UINT16 10278 10279 Analog Input 156 R
R/W NV
NV kVARh 15172, 22000 22000 = Janitza Pointmap
kVARh Up
Power - Circuit
Counter45 45 6 UINT16 10280 10281 Analog Input 157 R
R NV
NV kVARh
kVARh - Circuit 46 46 10282 10283 Analog Input 158 R NV kVARh
Uptime 7 8 UINT32 R NV Seconds
kVARh - Circuit 47 47 10284 10285 Analog Input 159 R NV kVARh
Smart Port ID #1 10 UINT16 R NV
kVARh - Circuit 48 48 10286 10287 Analog Input 160 R NV kVARh
Smart Port ID #2 11 UINT16 R NV
kVARh - Circuit 49 49 10288 10289 Analog Input 161 R NV kVARh See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
kVARh - Circuit 50 50 10290 10291 Analog Input 162 R NV kVARh
Smart -Port
kVARh ID #4
Circuit 51 51 13 UINT16 10292 10293 Analog Input 163 R
R NV
NV kVARh
SmartkVARh
Port #1 Serial Number
- Circuit 52 52 14 15 UINT32 10294 10295 Analog Input 164 R
R NV
NV kVARh
SmartkVARh
Port #2 Serial Number
- Circuit 53 53 16 17 UINT32 10296 10297 Analog Input 165 R
R NV
NV kVARh
SmartkVARh
Port #3 Serial Number
- Circuit 54 54 18 19 UINT32 10298 10299 Analog Input 166 R NV kVARh
SmartkVARh
Port #4 Serial Number
- Circuit 55 55 20 21 UINT32 10300 10301 Analog Input 167 R NV kVARh
Smart Port
kVARh#1 -Firmware
Circuit 56Version 56 22 UINT16 10302 10303 Analog Input 168 R NV kVARh
kVARh
Smart Port #2 -Firmware
Circuit 57Version 57 23 UINT16 10304 10305 Analog Input 169 R NV kVARh
kVARh
Smart Port #3 -Firmware
Circuit 58Version 58 24 UINT16 10306 10307 Analog Input 170 R NV kVARh
kVARh
Smart Port #4 -Firmware
Circuit 59Version 59 25 UINT16 10308 10309 Analog Input 171 R NV kVARh
MAC kVARh - Circuit
Address 60
(Bit 33-48) 60 26 10310 10311 Analog Input 172 R
R NV
NV kVARh
MAC kVARh - Circuit
Address 61
(Bit 17-32) 61 27 10312 10313 Analog Input 173 R
R NV
NV kVARh
MACkVARh - Circuit
Address 62
(Bit 1-16) 62 28 10314 10315 Analog Input 174 R
R NV
NV kVARh
BrandkVARh
Name- Circuit 63
(16 Registers) 63 29 44 10316 10317 Analog Input 175 R
R NV
NV kVARh
kVARh - Circuit 64 64 10318 10319 Analog Input 176 R NV kVARh Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
kVARh - Circuit 65 65 10320 10321 Analog Input 177 R NV kVARh supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
kVARh - Circuit 66 66 10322 10323 Analog Input 178 R NV kVARh
kVARh - Circuit 67 67 10324 10325 Analog Input 179 R NV kVARh
Meter Configuration
kVARh - Circuit 68 68 10326 10327 Analog Input 180 R NV kVARh
Demand
kVARh# of Sub-Intervals
- Circuit 69 69 100 UINT16 10328 10329
Analog Value
Analog Input
1
181 R/W
R NV
NV kVARh 1-6
Demand Sub-Interval
kVARh - Circuit 70 Length 70 101 UINT16 10330 10331 Analog
Analog Value
Input
2
182 R/W
R NV
NV Seconds
kVARh 0, 10 - 32767 0 = Sync to Comms
DemandkVARh - Circuit 71(Year)
Time Stamp 71 102 10332 10333 Analog Input 183 R
R NV Year
kVARh Years since 1900 (118 = 2018)
Demand Time- Circuit
kVARh Stamp 72 (Month) 72 103 10334 10335 Analog Input 184 R
R NV Month
kVARh 0 - 11 Month (0 = January)
Demand
kVARhTime Stamp73(Day)
- Circuit 73 104 10336 10337 Analog Input 185 R NV Day
kVARh 1 - 31 Day of the Month
Demand Time -Stamp
kVARh Circuit(Weekday)
74 74 105 10338 10339 Analog Input 186 R NV Weekday
kVARh 0-6 Weekday (1 = Monday)
DemandkVARh
Time- Circuit
Stamp75 (Hour) 75 106 10340 10341 Analog Input 187 R NV kVARh
Hour 0 - 23 Hour (13 = 1PM)
Demand kVARh
Time- Stamp
Circuit (Minute)
76 76 107 10342 10343 Analog Input 188 R NV kVARh
Minute 0 - 59 Minute
Demand kVARh
Time- Stamp
Circuit (Second)
77 77 108 10344 10345 Analog Input 189 R NV kVARh
Seconds 0 - 59 Second
kVARh - Circuit 78 78 10346 10347 Analog Input 190 R NV kVARh Writing to RTC will disable NTP by clearing out URL and/or IP Address
kVARh
Real Time- Clock
Circuit(Year)
79 79 109 UINT16 10348 10349 Analog Input 191 R
R/W NV kVARh
Year Years since 1900 (118 = 2018)
RealkVARh - Circuit
Time Clock 80
(Month) 80 110 UINT16 10350 10351 Analog Input 192 R
R/W NV kVARh
Month 0 - 11 Month (0 = January)
kVARh Device
AnalogObject Local_Date
Real Time- Circuit 81
Clock (Day) 81 111 UINT16 10352 10353 Input 193 R
R/W NV kVARh
Day 1 - 31 Day of the Month
Real kVARh - Circuit 82 82 10354 10355 R NV kVARh
Analog Input 194
Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
kVARh
Real Time- Clock
Circuit(Hour)
83 83 113 UINT16 10356 10357 Analog Input 195 R
R/W NV kVARh
Hour 0 - 23 Hour (13 = 1PM)
kVARh - Circuit 84 84 10358 10359 Analog Input 196 R NV kVARh
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
kVARh - Circuit 85 85 10360 10361 Analog Input 197 R NV kVARh
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
kVARh - Circuit 86 86 10362 10363 Analog Input 198 R NV kVARh
Digital Output #1 116 Binary Output 1 R/W 0, 1
kVARh - Circuit 87 87 10364 10365 Analog Input 199 R NV kVARh
Digital Output #2 117 Binary Output 2 R/W 0, 1
kVARh - Circuit 88 88 10366 10367 Analog Input 200 R NV kVARh
Digital
kVARhInput #1 State
- Circuit 89 89 118 10368 10369
Binary Input
Analog Input
1
201 R
R NV kVARh 0, 1
Digital
kVARhInput #2 State
- Circuit 90 90 119 10370 10371 Binary Input
Analog Input
2
202 R
R NV kVARh 0, 1
Modbus Slave Address
kVARh - Circuit 91 91 124 UINT16 10372 10373 Analog Input 203 R/W
R NV
NV kVARh 1 - 254
Modbus TCP
kVARh - Circuit 92Port 92 125 UINT16 10374 10375 Analog Input 204 R
R NV
NV kVARh 502
IP Address
kVARh - Circuit 93 93 126 127 10376 10377 Analog Input 205 R/W
R NV
NV kVARh Meter must be rebooted for new network settings to affect.
kVARhGateway
- Circuit 94 94 128 129 10378 10379 Analog Input 206 R/W
R NV
NV kVARh Device can be rebooted remotely using Global Reset/Command (Register 192)
kVARhMask
- Circuit 95 95 130 131 10380 10381 Analog Input 207 R/W
R NV
NV kVARh
kVARh - Circuit 96 96 10382 10383 Analog Input 208 R NV kVARh

kVAh 10384 10575 Analog Input 209 - 304 R NV kVAh

UMG 804
19
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter
kVAhInformation
- Circuit 1 1 10384 10385 Analog Input 209 R NV kVAh
kVAh
Serial- Number
Circuit 2 2 1 2 UINT32 10386 10387 AnalogObject
Device Input 210
Serial_Number R NV kVAh
kVAh - Circuit
Bootloader Version3 3 3 UINT16 10388 10389 Analog Input 211 R NV kVAh
kVAh - Circuit
Firmware Version 4 4 4 UINT16 10390 10391 AnalogObject
Device Input 212
Firmware_Revision R NV kVAh
kVAh - Circuit
Device ID 5 5 5 UINT16 10392 10393 Analog Input 213 R
R/W NV kVAh 15172, 22000 22000 = Janitza Pointmap
kVAh Up
Power - Circuit
Counter 6 6 6 UINT16 10394 10395 Analog Input 214 R NV kVAh
kVAh - Circuit 7
Uptime 7 7 8 UINT32 10396 10397 Analog Input 215 R NV kVAh
Seconds
kVAh -Port
Smart Circuit 8
ID #1 8 10 UINT16 10398 10399 Analog Input 216 R NV kVAh
kVAh -Port
Smart Circuit 9
ID #2 9 11 UINT16 10400 10401 Analog Input 217 R NV kVAh
See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
kVAh
Smart-Port
Circuit 10
ID #3 10 12 UINT16 10402 10403 Analog Input 218 R NV kVAh
kVAh
Smart-Port
Circuit 11
ID #4 11 13 UINT16 10404 10405 Analog Input 219 R NV kVAh
SmartkVAh - Circuit
Port #1 Serial 12Number 12 14 15 UINT32 10406 10407 Analog Input 220 R
R NV
NV kVAh
SmartkVAh - Circuit
Port #2 Serial 13Number 13 16 17 UINT32 10408 10409 Analog Input 221 R
R NV
NV kVAh
kVAh - Circuit
Smart Port #3 Serial Number14 14 18 19 UINT32 10410 10411 Analog Input 222 R
R NV
NV kVAh
kVAh - Circuit
Smart Port #4 Serial Number15 15 20 21 UINT32 10412 10413 Analog Input 223 R
R NV
NV kVAh
kVAh - Circuit 16 16 10414 10415 Analog Input 224 R NV kVAh
Smart Port #1 Firmware Version 22 UINT16 R NV
kVAh - Circuit 17 17 10416 10417 Analog Input 225 R NV kVAh
Smart Port #2 Firmware Version 23 UINT16 R NV
kVAh - Circuit 18 18 10418 10419 Analog Input 226 R NV kVAh
Smart Port #3 Firmware Version 24 UINT16 R NV
kVAh - Circuit 19 19 10420 10421 Analog Input 227 R NV kVAh
Smart Port #4 Firmware Version 25 UINT16 R NV
kVAh - Circuit 20 20 10422 10423 Analog Input 228 R NV kVAh
MACkVAh
Address (Bit 33-48)
- Circuit 21 21 26 10424 10425 Analog Input 229 R
R NV
NV kVAh
MACkVAh
Address (Bit 17-32)
- Circuit 22 22 27 10426 10427 Analog Input 230 R
R NV
NV kVAh
MAC Address (Bit
kVAh - Circuit 23 1-16) 23 28 10428 10429 Analog Input 231 R
R NV
NV kVAh
BrandkVAh
Name (16 Registers)
- Circuit 24 24 29 44 10430 10431 Analog Input 232 R NV kVAh Brand Name, Model Name and Device Name
Model Name
kVAh (16 Register)
- Circuit 25 25 45 60 10432 10433 Device
AnalogObject
Input Model_Name
233 R NV kVAh
supports up to 32 characters (16 registers)
DevicekVAh
Name (16 Registers)
- Circuit 26 26 61 76 10434 10435 Device
AnalogObject
Input Object_Name
234 R/W
R NV kVAh
kVAh - Circuit 27 27 10436 10437 Analog Input 235 R NV kVAh
Meter
kVAhConfiguration
- Circuit 28 28 10438 10439 Analog Input 236 R NV kVAh
kVAh# -ofCircuit
Demand 29
Sub-Intervals 29 100 UINT16 10440 10441 Input
Analog Value 237
1 R
R/W NV kVAh 1-6
DemandkVAh - Circuit 30Length
Sub-Interval 30 101 UINT16 10442 10443 Analog Value
Analog Input 238
2 R
R/W NV
NV kVAh
Seconds 0, 10 - 32767 0 = Sync to Comms
DemandkVAh - Circuit
Time Stamp 31(Year) 31 102 10444 10445 Analog Input 239 R
R NV kVAh
Year Years since 1900 (118 = 2018)
Demand kVAh
Time- Circuit
Stamp32 (Month) 32 103 10446 10447 Analog Input 240 R
R NV kVAh
Month 0 - 11 Month (0 = January)
kVAh
Demand - Circuit
Time Stamp 33(Day) 33 104 10448 10449 Analog Input 241 R
R NV kVAh
Day 1 - 31 Day of the Month
kVAh - Circuit 34 34 10450 10451 Analog Input 242 R NV kVAh
Demand Time Stamp (Weekday) 105 R Weekday 0-6 Weekday (1 = Monday)
kVAh - Circuit 35 35 10452 10453 Analog Input 243 R NV kVAh
Demand Time Stamp (Hour) 106 R Hour 0 - 23 Hour (13 = 1PM)
kVAh - Circuit 36 36 10454 10455 Analog Input 244 R NV kVAh
Demand Time Stamp (Minute) 107 R Minute 0 - 59 Minute
kVAh - Circuit 37 37 10456 10457 Analog Input 245 R NV kVAh
Demand Time Stamp (Second) 108 R Seconds 0 - 59 Second
kVAh - Circuit 38 38 10458 10459 Analog Input 246 R NV kVAh
kVAh - Circuit 39 39 10460 10461 Analog Input 247 R NV kVAh Writing to RTC will disable NTP by clearing out URL and/or IP Address
Real Time- Circuit
kVAh Clock (Year)
40 40 109 UINT16 10462 10463 Analog Input 248 R/W
R NV Year
kVAh Years since 1900 (118 = 2018)
RealkVAh
Time-Clock
Circuit (Month)
41 41 110 UINT16 10464 10465 AnalogObject
Input 249 R/W
R NV Month
kVAh 0 - 11 Month (0 = January)
Device Local_Date
Real Time
kVAh Clock (Day)
- Circuit 42 42 111 UINT16 10466 10467 Analog Input 250 R/W
R NV Day
kVAh 1 - 31 Day of the Month
Real Time
kVAhClock
- Circuit(Weekday)
43 43 112 UINT16 10468 10469 Analog Input 251 R/W
R NV Weekday
kVAh 0-6 Weekday (1 = Monday)
Real Time- Circuit
kVAh Clock (Hour)
44 44 113 UINT16 10470 10471 Analog Input 252 R/W
R NV Hour
kVAh 0 - 23 Hour (13 = 1PM)
Real Time
kVAh Clock (Min)
- Circuit 45 45 114 UINT16 10472 10473 Device
AnalogObject
Input Local_Time
253 R/W
R NV Minute
kVAh 0 - 59 Minute
RealkVAh
Time -Clock
Circuit (Second)
46 46 115 UINT16 10474 10475 Analog Input 254 R/W
R NV Seconds
kVAh 0 - 59 Second
kVAh - Output
Digital Circuit 47 #1 47 116 10476 10477 Binary
AnalogOutput
Input 1
255 R
R/W NV kVAh 0, 1
kVAh - Output
Digital Circuit 48 #2 48 117 10478 10479 AnalogOutput
Binary Input 256
2 R
R/W NV kVAh 0, 1
kVAhInput
Digital - Circuit 49
#1 State 49 118 10480 10481 Analog Input
Binary Input 257
1 R NV kVAh 0, 1
kVAhInput
Digital - Circuit 50
#2 State 50 119 10482 10483 Analog Input
Binary Input 258
2 R
R NV kVAh 0, 1
kVAh Slave
Modbus - Circuit 51
Address 51 124 UINT16 10484 10485 Analog Input 259 R
R/W NV
NV kVAh 1 - 254
kVAh - Circuit
Modbus TCP Port 52 52 125 UINT16 10486 10487 Analog Input 260 R
R NV
NV kVAh 502
kVAh - Circuit 53
IP Address 53 126 127 10488 10489 Analog Input 261 R
R/W NV
NV kVAh
kVAh - Circuit 54 54 10490 10491 Analog Input 262 R NV kVAh Meter must be rebooted for new network settings to affect.
Gateway 128 129 R/W NV
kVAh - Circuit 55 55 10492 10493 Analog Input 263 R NV kVAh Device can be rebooted remotely using Global Reset/Command (Register 192)
Mask 130 131 R/W NV
kVAh - Circuit 56 56 10494 10495 Analog Input 264 R NV kVAh
kVAh - Circuit 57 57 10496 10497 Analog Input 265 R NV kVAh
kVAh - Circuit 58 58 10498 10499 Analog Input 266 R NV kVAh
kVAh - Circuit 59 59 10500 10501 Analog Input 267 R NV kVAh

UMG 804
20
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
kVAh Information
Meter - Circuit 60 60 10502 10503 Analog Input 268 R NV kVAh
kVAh
Serial- Circuit
Number 61 61 1 2 UINT32 10504 10505 AnalogObject
Device Input 269
Serial_Number R
R NV
NV kVAh
kVAh - Circuit
Bootloader 62
Version 62 3 UINT16 10506 10507 Analog Input 270 R
R NV
NV kVAh
kVAh - Circuit
Firmware 63
Version 63 4 UINT16 10508 10509 AnalogObject
Device Input 271
Firmware_Revision R
R NV
NV kVAh
kVAh - Circuit
Device ID 64 64 5 UINT16 10510 10511 Analog Input 272 R
R/W NV
NV kVAh 15172, 22000 22000 = Janitza Pointmap
kVAh - Circuit 65 65 10512 10513 Analog Input 273 R NV kVAh
Power Up Counter 6 UINT16 R NV
kVAh - Circuit 66 66 10514 10515 Analog Input 274 R NV kVAh
Uptime 7 8 UINT32 R NV Seconds
kVAh - Circuit 67 67 10516 10517 Analog Input 275 R NV kVAh
Smart Port ID #1 10 UINT16 R NV
kVAh - Circuit 68 68 10518 10519 Analog Input 276 R NV kVAh
Smart Port ID #2 11 UINT16 R NV
kVAh - Circuit 69 69 10520 10521 Analog Input 277 R NV kVAh See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart- Port
kVAh ID 70
Circuit #3 70 12 UINT16 10522 10523 Analog Input 278 R
R NV
NV kVAh
Smart- Port
kVAh ID 71
Circuit #4 71 13 UINT16 10524 10525 Analog Input 279 R
R NV
NV kVAh
SmartkVAh
Port #1 Serial 72
- Circuit Number 72 14 15 UINT32 10526 10527 Analog Input 280 R
R NV
NV kVAh
SmartkVAh
Port #2 Serial 73
- Circuit Number 73 16 17 UINT32 10528 10529 Analog Input 281 R NV kVAh
SmartkVAh
Port #3 Serial 74
- Circuit Number 74 18 19 UINT32 10530 10531 Analog Input 282 R NV kVAh
SmartkVAh
Port #4 Serial 75
- Circuit Number 75 20 21 UINT32 10532 10533 Analog Input 283 R NV kVAh
kVAh
Smart Port #1- Firmware
Circuit 76 Version 76 22 UINT16 10534 10535 Analog Input 284 R NV kVAh
kVAh
Smart Port #2- Firmware
Circuit 77 Version 77 23 UINT16 10536 10537 Analog Input 285 R NV kVAh
kVAh
Smart Port #3- Firmware
Circuit 78 Version 78 24 UINT16 10538 10539 Analog Input 286 R NV kVAh
kVAh
Smart Port #4- Firmware
Circuit 79 Version 79 25 UINT16 10540 10541 Analog Input 287 R
R NV
NV kVAh
MACkVAh - Circuit
Address 80
(Bit 33-48) 80 26 10542 10543 Analog Input 288 R
R NV
NV kVAh
MACkVAh - Circuit
Address 81
(Bit 17-32) 81 27 10544 10545 Analog Input 289 R
R NV
NV kVAh
MACkVAh - Circuit
Address (Bit82
1-16) 82 28 10546 10547 Analog Input 290 R
R NV
NV kVAh
kVAh - Circuit 83 83 10548 10549 Analog Input 291 R NV kVAh
Brand Name (16 Registers) 29 44 R NV
kVAh - Circuit 84 84 10550 10551 Analog Input 292 R NV kVAh Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
kVAh - Circuit 85 85 10552 10553 Analog Input 293 R NV kVAh supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
kVAh - Circuit 86 86 10554 10555 Analog Input 294 R NV kVAh
kVAh - Circuit 87 87 10556 10557 Analog Input 295 R NV kVAh
Meter
kVAhConfiguration
- Circuit 88 88 10558 10559 Analog Input 296 R NV kVAh
Demand
kVAh# -ofCircuit
Sub-Intervals
89 89 100 UINT16 10560 10561 Analog
Analog Value
Input
1
297 R/W
R NV
NV kVAh 1-6
DemandkVAh - Circuit 90Length
Sub-Interval 90 101 UINT16 10562 10563 Analog
Analog Value
Input 2
298 R/W
R NV
NV Seconds
kVAh 0, 10 - 32767 0 = Sync to Comms
DemandkVAh - Circuit 91(Year)
Time Stamp 91 102 10564 10565 Analog Input 299 R
R NV Year
kVAh Years since 1900 (118 = 2018)
Demand Time
kVAh Stamp92
- Circuit (Month) 92 103 10566 10567 Analog Input 300 R
R NV Month
kVAh 0 - 11 Month (0 = January)
Demand
kVAhTime Stamp
- Circuit 93(Day) 93 104 10568 10569 Analog Input 301 R
R NV Day
kVAh 1 - 31 Day of the Month
DemandkVAh
Time- Stamp
Circuit (Weekday)
94 94 105 10570 10571 Analog Input 302 R
R NV Weekday
kVAh 0-6 Weekday (1 = Monday)
Demand Time
kVAh Stamp95(Hour)
- Circuit 95 106 10572 10573 Analog Input 303 R
R NV Hour
kVAh 0 - 23 Hour (13 = 1PM)
Demand Time
kVAh Stamp96
- Circuit (Minute) 96 107 10574 10575 Analog Input 304 R
R NV Minute
kVAh 0 - 59 Minute
Demand Time Stamp (Second) 108 R Seconds 0 - 59 Second
kW 10576 10767 Analog Input 305 - 400 R kW Writing to RTC will disable NTP by clearing out URL and/or IP Address
RealkWTime Clock (Year)
- Circuit 1 1 109 UINT16 10576 10577 Analog Input 305 R/W
R Year
kW Years since 1900 (118 = 2018)
Real Time
kW - Clock
Circuit(Month)
2 2 110 UINT16 10578 10579 AnalogObject
Input 306 R/W
R Month
kW 0 - 11 Month (0 = January)
Device Local_Date
RealkWTime Clock (Day)
- Circuit 3 3 111 UINT16 10580 10581 Analog Input 307 R/W
R Day
kW 1 - 31 Day of the Month
Real Time
kW Clock (Weekday)
- Circuit 4 4 112 UINT16 10582 10583 Analog Input 308 R/W
R Weekday
kW 0-6 Weekday (1 = Monday)
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
kW - Circuit 5 5 10584 10585 Analog Input 309 R kW
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
kW - Circuit 6 6 10586 10587 Analog Input 310 R kW
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
kW - Circuit 7 7 10588 10589 Analog Input 311 R kW
Digital Output8#1
kW - Circuit 8 116 10590 10591
Binary Output
Analog Input
1
312 R/W
R kW 0, 1
Digital Output9#2
kW - Circuit 9 117 10592 10593 Binary
AnalogOutput
Input
2
313 R/W
R kW 0, 1
Digital
kW Input #110
- Circuit State 10 118 10594 10595 Binary Input
Analog Input 1
314 R
R kW 0, 1
Digital
kW Input #211
- Circuit State 11 119 10596 10597 Binary Input
Analog Input 2
315 R
R kW 0, 1
Modbus
kW - Slave
CircuitAddress
12 12 124 UINT16 10598 10599 Analog Input 316 R/W
R NV kW 1 - 254
Modbus TCP Port
kW - Circuit 13 13 125 UINT16 10600 10601 Analog Input 317 R NV kW 502
kWIP-Address
Circuit 14 14 126 127 10602 10603 Analog Input 318 R
R/W NV kW
Meter must be rebooted for new network settings to affect.
kWGateway
- Circuit 15 15 128 129 10604 10605 Analog Input 319 R
R/W NV kW
Device can be rebooted remotely using Global Reset/Command (Register 192)
kW -Mask
Circuit 16 16 130 131 10606 10607 Analog Input 320 R
R/W NV kW
kW - Circuit 17 17 10608 10609 Analog Input 321 R kW
kW - Circuit 18 18 10610 10611 Analog Input 322 R kW
kW - Circuit 19 19 10612 10613 Analog Input 323 R kW

UMG 804
21
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
kW -Information
Meter Circuit 20 20 10614 10615 Analog Input 324 R kW
kW - Circuit
Serial Number 21 21 1 2 UINT32 10616 10617 AnalogObject
Device Input 325
Serial_Number R
R NV kW
kW - Circuit
Bootloader 22
Version 22 3 UINT16 10618 10619 Analog Input 326 R
R NV kW
kW - Circuit
Firmware 23
Version 23 4 UINT16 10620 10621 AnalogObject
Device Input 327
Firmware_Revision R
R NV kW
kWDevice
- Circuit
ID 24 24 5 UINT16 10622 10623 Analog Input 328 R
R/W NV kW 15172, 22000 22000 = Janitza Pointmap
kW - Circuit 25 25 10624 10625 Analog Input 329 R kW
Power Up Counter 6 UINT16 R NV
kW - Circuit 26 26 10626 10627 Analog Input 330 R kW
Uptime 7 8 UINT32 R NV Seconds
kW - Circuit 27 27 10628 10629 Analog Input 331 R kW
Smart Port ID #1 10 UINT16 R NV
kW - Circuit 28 28 10630 10631 Analog Input 332 R kW
Smart Port ID #2 11 UINT16 R NV
kW - Circuit 29 29 10632 10633 Analog Input 333 R kW See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID30
kW - Circuit #3 30 12 UINT16 10634 10635 Analog Input 334
R
R NV kW
Smart Port ID31
kW - Circuit #4 31 13 UINT16 10636 10637 Analog Input 335 R
R NV kW
Smart Port
kW -#1 Serial32Number
Circuit 32 14 15 UINT32 10638 10639 Analog Input 336 R
R NV kW
Smart Port
kW -#2 Serial33Number
Circuit 33 16 17 UINT32 10640 10641 Analog Input 337 R
R NV kW
Smart Port
kW -#3 Serial34Number
Circuit 34 18 19 UINT32 10642 10643 Analog Input 338 R NV kW
Smart Port
kW -#4 Serial35Number
Circuit 35 20 21 UINT32 10644 10645 Analog Input 339 R NV kW
Smart PortkW#1- Circuit
Firmware 36 Version 36 22 UINT16 10646 10647 Analog Input 340 R NV kW
Smart PortkW#2- Circuit
Firmware 37 Version 37 23 UINT16 10648 10649 Analog Input 341 R NV kW
Smart PortkW#3- Circuit
Firmware 38 Version 38 24 UINT16 10650 10651 Analog Input 342 R NV kW
Smart PortkW#4- Circuit
Firmware 39 Version 39 25 UINT16 10652 10653 Analog Input 343 R
R NV kW
MAC kW - Circuit
Address (Bit40
33-48) 40 26 10654 10655 Analog Input 344 R
R NV kW
MAC kW - Circuit
Address (Bit41
17-32) 41 27 10656 10657 Analog Input 345 R
R NV kW
kW - Circuit 42
MAC Address (Bit 1-16) 42 28 10658 10659 Analog Input 346 R
R NV kW
kW - Circuit 43 43 10660 10661 Analog Input 347 R kW
Brand Name (16 Registers) 29 44 R NV
kW - Circuit 44 44 10662 10663 Analog Input 348 R kW Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
kW - Circuit 45 45 10664 10665 Analog Input 349 R kW supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
kW - Circuit 46 46 10666 10667 Analog Input 350 R kW
kW - Circuit 47 47 10668 10669 Analog Input 351 R kW
MeterkW Configuration
- Circuit 48 48 10670 10671 Analog Input 352 R kW
Demand kW#- of Sub-Intervals
Circuit 49 49 100 UINT16 10672 10673 Analog Value
Analog Input
1
353 R/W
R NV kW 1-6
Demand kW - Circuit 50Length
Sub-Interval 50 101 UINT16 10674 10675 Analog
Analog Value
Input 2
354 R/W
R NV Seconds
kW 0, 10 - 32767 0 = Sync to Comms
Demand kW - Circuit 51 (Year)
Time Stamp 51 102 10676 10677 Analog Input 355 R
R Year
kW Years since 1900 (118 = 2018)
DemandkW Time Stamp52(Month)
- Circuit 52 103 10678 10679 Analog Input 356 R Month
kW 0 - 11 Month (0 = January)
Demand kWTime Stamp
- Circuit 53 (Day) 53 104 10680 10681 Analog Input 357 R Day
kW 1 - 31 Day of the Month
Demand kW Time- Circuit
Stamp 54 (Weekday) 54 105 10682 10683 Analog Input 358 R Weekday
kW 0-6 Weekday (1 = Monday)
Demand kWTime
- Circuit
Stamp 55 (Hour) 55 106 10684 10685 Analog Input 359 R kW
Hour 0 - 23 Hour (13 = 1PM)
DemandkW - Circuit
Time Stamp56(Minute) 56 107 10686 10687 Analog Input 360 R kW
Minute 0 - 59 Minute
DemandkW - Circuit
Time Stamp57(Second) 57 108 10688 10689 Analog Input 361 R
R kW
Seconds 0 - 59 Second
kW - Circuit 58 58 10690 10691 Analog Input 362 R kW Writing to RTC will disable NTP by clearing out URL and/or IP Address
RealkW - Circuit
Time Clock 59(Year) 59 109 UINT16 10692 10693 Analog Input 363 R
R/W kW
Year Years since 1900 (118 = 2018)
kW - Circuit
Real Time 60
Clock (Month) 60 110 UINT16 10694 10695 Analog Input 364 R
R/W kW
Month 0 - 11 Month (0 = January)
kW - Circuit 61 61 10696 10697 Device
AnalogObject
Input Local_Date
365 R kW
Real Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
kW - Circuit 62 62 10698 10699 Analog Input 366 R kW
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
kW - Circuit 63 63 10700 10701 Analog Input 367 R kW
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
kW - Circuit 64 64 10702 10703 Analog Input 368 R kW
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
kW - Circuit 65 65 10704 10705 Analog Input 369 R kW
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
kW - Circuit 66 66 10706 10707 Analog Input 370 R kW
Digital Output #1 116 Binary Output 1 R/W 0, 1
kW - Circuit 67 67 10708 10709 Analog Input 371 R kW
Digital Output68
kW - Circuit #2 68 117 10710 10711
Binary Output
Analog Input
2
372
R/W
R kW 0, 1
Digital
kW Input #169
- Circuit State 69 118 10712 10713 Binary Input
Analog Input
1
373 R
R kW 0, 1
Digital
kW Input #270
- Circuit State 70 119 10714 10715 Binary Input
Analog Input 2
374 R
R kW 0, 1
Modbus
kW - Slave
CircuitAddress
71 71 124 UINT16 10716 10717 Analog Input 375 R/W
R NV kW 1 - 254
Modbus TCP Port
kW - Circuit 72 72 125 UINT16 10718 10719 Analog Input 376 R NV kW 502
kWIP-Address
Circuit 73 73 126 127 10720 10721 Analog Input 377 R/W
R NV kW
Meter must be rebooted for new network settings to affect.
kWGateway
- Circuit 74 74 128 129 10722 10723 Analog Input 378 R/W
R NV kW
Device can be rebooted remotely using Global Reset/Command (Register 192)
kW -Mask
Circuit 75 75 130 131 10724 10725 Analog Input 379 R
R/W NV kW
kW - Circuit 76 76 10726 10727 Analog Input 380 R kW
kW - Circuit 77 77 10728 10729 Analog Input 381 R kW
kW - Circuit 78 78 10730 10731 Analog Input 382 R kW

UMG 804
22
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
kW -Information
Meter Circuit 79 79 10732 10733 Analog Input 383 R kW
kW - Circuit
Serial Number 80 80 1 2 UINT32 10734 10735 AnalogObject
Device Input 384
Serial_Number R
R NV kW
kW - Circuit
Bootloader 81
Version 81 3 UINT16 10736 10737 Analog Input 385 R
R NV kW
kW - Circuit
Firmware 82
Version 82 4 UINT16 10738 10739 AnalogObject
Device Input 386
Firmware_Revision R
R NV kW
kW - Circuit 83 83 10740 10741 Analog Input 387 R kW
Device ID 5 UINT16 R/W NV 15172, 22000 22000 = Janitza Pointmap
kW - Circuit 84 84 10742 10743 Analog Input 388 R kW
Power Up Counter 6 UINT16 R NV
kW - Circuit 85 85 10744 10745 Analog Input 389 R kW
Uptime 7 8 UINT32 R NV Seconds
kW - Circuit 86 86 10746 10747 Analog Input 390 R kW
Smart Port ID #1 10 UINT16 R NV
kW - Circuit 87 87 10748 10749 Analog Input 391 R kW
Smart Port ID #2 11 UINT16 R NV
kW - Circuit 88 88 10750 10751 Analog Input 392 R kW See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
kW - Circuit 89 89 10752 10753 Analog Input 393 R kW
Smart Port ID #4 13 UINT16 R NV
kW - Circuit 90 90 10754 10755 Analog Input 394 R kW
Smart Port #1 Serial Number 14 15 UINT32 R NV
kW - Circuit 91 91 10756 10757 Analog Input 395 R kW
Smart Port #2 Serial Number 16 17 UINT32 R NV
kW - Circuit 92 92 10758 10759 Analog Input 396 R kW
Smart Port #3 Serial Number 18 19 UINT32 R NV
kW - Circuit 93 93 10760 10761 Analog Input 397 R kW
Smart Port #4 Serial Number 20 21 UINT32 R NV
kW - Circuit 94 94 10762 10763 Analog Input 398 R kW
Smart Port #1 Firmware Version 22 UINT16 R NV
kW - Circuit 95 95 10764 10765 Analog Input 399 R kW
Smart Port #2 Firmware Version 23 UINT16 R NV
kW - Circuit 96 96 10766 10767 Analog Input 400 R kW
Smart Port #3 Firmware Version 24 UINT16 R NV
Smart Port #4 Firmware Version 25 UINT16 R NV
kVAR 10768 10959 Analog Input 401 - 496 R kVAR
MAC Address (Bit 33-48) 26 R NV
kVAR - Circuit 1 1 10768 10769 Analog Input 401 R kVAR
MAC Address (Bit 17-32) 27 R NV
kVAR - Circuit 2 2 10770 10771 Analog Input 402 R kVAR
MAC Address (Bit 1-16) 28 R NV
kVAR - Circuit 3 3 10772 10773 Analog Input 403 R kVAR
Brand Name (16 Registers) 29 44 R NV
kVAR - Circuit 4 4 10774 10775 Analog Input 404 R kVAR Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
kVAR - Circuit 5 5 10776 10777 Analog Input 405 R kVAR supports up to 32 characters (16 registers)
DevicekVAR
Name (16 Registers)
- Circuit 6 6 61 76 10778 10779
Device Object
Analog Input
Object_Name
406
R/W
R NV kVAR
kVAR - Circuit 7 7 10780 10781 Analog Input 407 R kVAR
Meter
kVARConfiguration
- Circuit 8 8 10782 10783 Analog Input 408 R kVAR
DemandkVAR# of Sub-Intervals
- Circuit 9 9 100 UINT16 10784 10785 Analog
Analog Value
Input 1
409 R/W
R NV kVAR 1-6
DemandkVARSub-Interval
- Circuit 10Length 10 101 UINT16 10786 10787 Analog
Analog Value
Input 2
410 R/W
R NV Seconds
kVAR 0, 10 - 32767 0 = Sync to Comms
DemandkVAR Time Stamp
- Circuit 11(Year) 11 102 10788 10789 Analog Input 411 R Year
kVAR Years since 1900 (118 = 2018)
Demand Time
kVAR Stamp12
- Circuit (Month) 12 103 10790 10791 Analog Input 412 R Month
kVAR 0 - 11 Month (0 = January)
kVAR
Demand - Circuit
Time Stamp13(Day) 13 104 10792 10793 Analog Input 413 R kVAR
Day 1 - 31 Day of the Month
DemandkVARTime-Stamp
Circuit(Weekday)
14 14 105 10794 10795 Analog Input 414 R kVAR
Weekday 0-6 Weekday (1 = Monday)
DemandkVAR - Circuit
Time Stamp15(Hour) 15 106 10796 10797 Analog Input 415 R
R kVAR
Hour 0 - 23 Hour (13 = 1PM)
Demand kVAR
Time- Circuit
Stamp16 (Minute) 16 107 10798 10799 Analog Input 416 R
R kVAR
Minute 0 - 59 Minute
Demand kVAR
Time- Circuit
Stamp17 (Second) 17 108 10800 10801 Analog Input 417 R
R kVAR
Seconds 0 - 59 Second
kVAR - Circuit 18 18 10802 10803 Analog Input 418 R kVAR Writing to RTC will disable NTP by clearing out URL and/or IP Address
kVAR
Real Time- Circuit 19
Clock (Year) 19 109 UINT16 10804 10805 Analog Input 419 R
R/W kVAR
Year Years since 1900 (118 = 2018)
kVAR - Circuit 20 20 10806 10807 Analog Input 420 R kVAR
Real Time Clock (Month) 110 UINT16 R/W Month 0 - 11 Month (0 = January)
kVAR - Circuit 21 21 10808 10809 Device
AnalogObject
Input Local_Date
421 R kVAR
Real Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
kVAR - Circuit 22 22 10810 10811 Analog Input 422 R kVAR
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
kVAR - Circuit 23 23 10812 10813 Analog Input 423 R kVAR
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
kVAR - Circuit 24 24 10814 10815 Analog Input 424 R kVAR
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
kVAR - Circuit 25 25 10816 10817 Analog Input 425 R kVAR
RealkVAR
Time -Clock (Second)
Circuit 26 26 115 UINT16 10818 10819 Analog Input 426
R/W
R Seconds
kVAR 0 - 59 Second
Digital
kVAR - Output #1
Circuit 27 27 116 10820 10821 Binary Output
Analog Input
1
427 R/W
R kVAR 0, 1
Digital
kVAR - Output #2
Circuit 28 28 117 10822 10823 Binary
AnalogOutput
Input 2
428 R/W
R kVAR 0, 1
Digital
kVARInput #1 State
- Circuit 29 29 118 10824 10825 Binary Input
Analog Input 1
429 R
R kVAR 0, 1
Digital
kVARInput #2 State
- Circuit 30 30 119 10826 10827 Binary Input
Analog Input 2
430 R kVAR 0, 1
Modbus
kVAR Slave Address
- Circuit 31 31 124 UINT16 10828 10829 Analog Input 431 R/W
R NV kVAR 1 - 254
Modbus TCP Port
kVAR - Circuit 32 32 125 UINT16 10830 10831 Analog Input 432 R NV kVAR 502
kVAR - Circuit 33
IP Address 33 126 127 10832 10833 Analog Input 433 R
R/W NV kVAR
Meter must be rebooted for new network settings to affect.
kVAR - Circuit 34
Gateway 34 128 129 10834 10835 Analog Input 434 R
R/W NV kVAR
Device can be rebooted remotely using Global Reset/Command (Register 192)
kVAR Mask
- Circuit 35 35 130 131 10836 10837 Analog Input 435 R
R/W NV kVAR
kVAR - Circuit 36 36 10838 10839 Analog Input 436 R kVAR
kVAR - Circuit 37 37 10840 10841 Analog Input 437 R kVAR
kVAR - Circuit 38 38 10842 10843 Analog Input 438 R kVAR

UMG 804
23
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter
kVAR Information
- Circuit 39 39 10844 10845 Analog Input 439 R kVAR
kVAR
Serial- Circuit
Number 40 40 1 2 UINT32 10846 10847 AnalogObject
Device Input 440
Serial_Number R NV kVAR
kVAR - Circuit
Bootloader 41
Version 41 3 UINT16 10848 10849 Analog Input 441 R
R NV kVAR
kVAR - Circuit
Firmware Version42 42 4 UINT16 10850 10851 AnalogObject
Device Input 442
Firmware_Revision R
R NV kVAR
kVAR - Circuit
Device ID 43 43 5 UINT16 10852 10853 Analog Input 443 R
R/W NV kVAR 15172, 22000 22000 = Janitza Pointmap
kVAR -Up
Power Circuit
Counter44 44 6 UINT16 10854 10855 Analog Input 444 R
R NV kVAR
kVAR - Circuit 45 45 10856 10857 Analog Input 445 R kVAR
Uptime 7 8 UINT32 R NV Seconds
kVAR - Circuit 46 46 10858 10859 Analog Input 446 R kVAR
Smart Port ID #1 10 UINT16 R NV
kVAR - Circuit 47 47 10860 10861 Analog Input 447 R kVAR
Smart Port ID #2 11 UINT16 R NV
kVAR - Circuit 48 48 10862 10863 Analog Input 448 R kVAR See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
kVAR - Circuit 49 49 10864 10865 Analog Input 449 R kVAR
Smart-Port
kVAR CircuitID #4
50 50 13 UINT16 10866 10867 Analog Input 450
R
R NV kVAR
SmartkVAR
Port #1 Serial 51
- Circuit Number 51 14 15 UINT32 10868 10869 Analog Input 451 R
R NV kVAR
SmartkVAR
Port #2 Serial 52
- Circuit Number 52 16 17 UINT32 10870 10871 Analog Input 452 R
R NV kVAR
SmartkVAR
Port #3 Serial 53
- Circuit Number 53 18 19 UINT32 10872 10873 Analog Input 453 R
R NV kVAR
SmartkVAR
Port #4 Serial 54
- Circuit Number 54 20 21 UINT32 10874 10875 Analog Input 454 R NV kVAR
Smart Port
kVAR #1- Firmware
Circuit 55 Version 55 22 UINT16 10876 10877 Analog Input 455 R NV kVAR
Smart Port
kVAR #2- Firmware
Circuit 56 Version 56 23 UINT16 10878 10879 Analog Input 456 R NV kVAR
kVAR
Smart Port #3- Firmware
Circuit 57 Version 57 24 UINT16 10880 10881 Analog Input 457 R NV kVAR
kVAR
Smart Port #4- Firmware
Circuit 58 Version 58 25 UINT16 10882 10883 Analog Input 458 R NV kVAR
MACkVAR - Circuit
Address 59
(Bit 33-48) 59 26 10884 10885 Analog Input 459 R
R NV kVAR
MACkVAR - Circuit
Address 60
(Bit 17-32) 60 27 10886 10887 Analog Input 460 R
R NV kVAR
MACkVAR - Circuit
Address (Bit61
1-16) 61 28 10888 10889 Analog Input 461 R
R NV kVAR
BrandkVAR - Circuit 62 62 10890 10891 R kVAR
Analog Input 462
Name (16 Registers) 29 44 R NV
kVAR - Circuit 63 63 10892 10893 Analog Input 463 R kVAR Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
kVAR - Circuit 64 64 10894 10895 Analog Input 464 R kVAR supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
kVAR - Circuit 65 65 10896 10897 Analog Input 465 R kVAR
kVAR - Circuit 66 66 10898 10899 Analog Input 466 R kVAR
Meter Configuration
kVAR - Circuit 67 67 10900 10901 Analog Input 467 R kVAR
Demand
kVAR# -ofCircuit
Sub-Intervals
68 68 100 UINT16 10902 10903
Analog Value
Analog Input
1
468
R/W
R NV kVAR 1-6
DemandkVARSub-Interval
- Circuit 69Length 69 101 UINT16 10904 10905 Analog Value
Analog Input
2
469 R/W
R NV Seconds
kVAR 0, 10 - 32767 0 = Sync to Comms
DemandkVAR - Circuit 70(Year)
Time Stamp 70 102 10906 10907 Analog Input 470 R
R Year
kVAR Years since 1900 (118 = 2018)
Demand Time
kVAR Stamp71
- Circuit (Month) 71 103 10908 10909 Analog Input 471 R
R Month
kVAR 0 - 11 Month (0 = January)
Demand
kVAR Time Stamp
- Circuit 72(Day) 72 104 10910 10911 Analog Input 472 R Day
kVAR 1 - 31 Day of the Month
DemandkVARTime-Stamp
Circuit(Weekday)
73 73 105 10912 10913 Analog Input 473 R Weekday
kVAR 0-6 Weekday (1 = Monday)
DemandkVARTime Stamp74(Hour)
- Circuit 74 106 10914 10915 Analog Input 474 R Hour
kVAR 0 - 23 Hour (13 = 1PM)
Demand kVAR
Time- Circuit
Stamp75 (Minute) 75 107 10916 10917 Analog Input 475 R kVAR
Minute 0 - 59 Minute
Demand kVAR
Time- Circuit
Stamp76 (Second) 76 108 10918 10919 Analog Input 476 R kVAR
Seconds 0 - 59 Second
kVAR - Circuit 77 77 10920 10921 Analog Input 477 R kVAR Writing to RTC will disable NTP by clearing out URL and/or IP Address
kVAR
Real Time- Circuit 78
Clock (Year) 78 109 UINT16 10922 10923 Analog Input 478 R
R/W kVAR
Year Years since 1900 (118 = 2018)
RealkVAR
Time-Clock
Circuit 79
(Month) 79 110 UINT16 10924 10925 Analog Input 479 R
R/W kVAR
Month 0 - 11 Month (0 = January)
kVAR - Circuit 80 80 10926 10927 Device
AnalogObject
Input Local_Date
480 R kVAR
Real Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
kVARClock
Real Time - Circuit 81
(Weekday) 81 112 UINT16 10928 10929 Analog Input 481 R
R/W kVAR
Weekday 0-6 Weekday (1 = Monday)
kVAR
Real Time- Circuit 82
Clock (Hour) 82 113 UINT16 10930 10931 Analog Input 482 R
R/W kVAR
Hour 0 - 23 Hour (13 = 1PM)
kVAR - Circuit 83 83 10932 10933 Analog Input 483 R kVAR
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
kVAR - Circuit 84 84 10934 10935 Analog Input 484 R kVAR
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
kVAR - Circuit 85 85 10936 10937 Analog Input 485 R kVAR
Digital Output #1 116 Binary Output 1 R/W 0, 1
kVAR - Circuit 86 86 10938 10939 Analog Input 486 R kVAR
Digital Output #2 117 Binary Output 2 R/W 0, 1
kVAR - Circuit 87 87 10940 10941 Analog Input 487 R kVAR
Digital Input #1 State 118 Binary Input 1 R 0, 1
kVAR - Circuit 88 88 10942 10943 Analog Input 488 R kVAR
Digital Input #2 State 119 Binary Input 2 R 0, 1
kVAR - Circuit 89 89 10944 10945 Analog Input 489 R kVAR
Modbus Slave Address 124 UINT16 R/W NV 1 - 254
kVAR - Circuit 90 90 10946 10947 Analog Input 490 R kVAR
Modbus TCP Port 125 UINT16 R NV 502
kVAR - Circuit 91 91 10948 10949 Analog Input 491 R kVAR
IP Address 126 127 R/W NV
kVAR - Circuit 92 92 10950 10951 Analog Input 492 R kVAR Meter must be rebooted for new network settings to affect.
Gateway 128 129 R/W NV
kVAR - Circuit 93 93 10952 10953 Analog Input 493 R kVAR Device can be rebooted remotely using Global Reset/Command (Register 192)
Mask 130 131 R/W NV
kVAR - Circuit 94 94 10954 10955 Analog Input 494 R kVAR
kVAR - Circuit 95 95 10956 10957 Analog Input 495 R kVAR
kVAR - Circuit 96 96 10958 10959 Analog Input 496 R kVAR

UMG 804
24
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter Information
SerialkVA
Number 1 2 UINT32 10960 11151 AnalogObject
Device Input 497 - 592
Serial_Number R NV kVA
kVA - Circuit
Bootloader 1
Version 1 3 UINT16 10960 10961 Analog Input 497 R NV kVA
kVA - Circuit
Firmware Version2 2 4 UINT16 10962 10963 AnalogObject
Device Input 498
Firmware_Revision R NV kVA
kVA - Circuit
Device ID 3 3 5 UINT16 10964 10965 Analog Input 499 R
R/W NV kVA 15172, 22000 22000 = Janitza Pointmap
kVA -Up
Power Circuit
Counter4 4 6 UINT16 10966 10967 Analog Input 500 R NV kVA
kVAUptime
- Circuit 5 5 7 8 UINT32 10968 10969 Analog Input 501 R
R NV kVA
Seconds
kVA - Port
Smart CircuitID 6#1 6 10 UINT16 10970 10971 Analog Input 502 R
R NV kVA
kVA - Port
Smart CircuitID 7#2 7 11 UINT16 10972 10973 Analog Input 503 R
R NV kVA
kVA - Port
Circuit See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
ID 8#3 8 10974 10975 R kVA
Analog Input 504
Smart 12 UINT16 R NV
kVA - Circuit 9 9 10976 10977 Analog Input 505 R kVA
Smart Port ID #4 13 UINT16 R NV
kVA - Circuit 10 10 10978 10979 Analog Input 506 R kVA
Smart Port #1 Serial Number 14 15 UINT32 R NV
kVA - Circuit 11 11 10980 10981 Analog Input 507 R kVA
Smart Port #2 Serial Number 16 17 UINT32 R NV
kVA - Circuit 12 12 10982 10983 Analog Input 508 R kVA
Smart Port #3 Serial Number 18 19 UINT32 R NV
kVA - Circuit 13 13 10984 10985 Analog Input 509 R kVA
Smart Port
kVA -#4 Serial14
Circuit Number 14 20 21 UINT32 10986 10987 Analog Input 510
R
R NV kVA
Smart Port
kVA#1- Circuit
Firmware 15 Version 15 22 UINT16 10988 10989 Analog Input 511 R
R NV kVA
Smart Port
kVA#2- Circuit
Firmware 16 Version 16 23 UINT16 10990 10991 Analog Input 512 R
R NV kVA
Smart Port
kVA#3- Circuit
Firmware 17 Version 17 24 UINT16 10992 10993 Analog Input 513 R
R NV kVA
Smart Port
kVA#4- Circuit
Firmware 18 Version 18 25 UINT16 10994 10995 Analog Input 514 R NV kVA
MACkVAAddress (Bit19
- Circuit 33-48) 19 26 10996 10997 Analog Input 515 R NV kVA
MACkVAAddress (Bit20
- Circuit 17-32) 20 27 10998 10999 Analog Input 516 R NV kVA
MACkVA - Circuit
Address (Bit211-16) 21 28 11000 11001 Analog Input 517 R NV kVA
BrandkVA
Name - Circuit 22
(16 Registers) 22 29 44 11002 11003 Analog Input 518 R NV kVA
Brand Name, Model Name and Device Name
ModelkVAName- Circuit 23
(16 Register) 23 45 60 11004 11005 AnalogObject
Device Input 519
Model_Name R
R NV kVA
supports up to 32 characters (16 registers)
DevicekVAName- Circuit 24
(16 Registers) 24 61 76 11006 11007 AnalogObject
Device Input 520
Object_Name R
R/W NV kVA
kVA - Circuit 25 25 11008 11009 Analog Input 521 R kVA
kVAConfiguration
Meter - Circuit 26 26 11010 11011 Analog Input 522 R kVA
kVA - Circuit 27 27 11012 11013 Analog Input 523 R kVA
Demand # of Sub-Intervals 100 UINT16 Analog Value 1 R/W NV 1-6
kVA - Circuit 28 28 11014 11015 Analog Input 524 R kVA
Demand Sub-Interval Length 101 UINT16 Analog Value 2 R/W NV Seconds 0, 10 - 32767 0 = Sync to Comms
kVA - Circuit 29 29 11016 11017 Analog Input 525 R kVA
Demand Time Stamp (Year) 102 R Year Years since 1900 (118 = 2018)
kVA - Circuit 30 30 11018 11019 Analog Input 526 R kVA
Demand Time Stamp (Month) 103 R Month 0 - 11 Month (0 = January)
kVA - Circuit 31 31 11020 11021 Analog Input 527 R kVA
DemandkVATime Stamp
- Circuit 32 (Day) 32 104 11022 11023 Analog Input 528
R
R Day
kVA 1 - 31 Day of the Month
DemandkVA Time- Circuit
Stamp 33 (Weekday) 33 105 11024 11025 Analog Input 529 R
R Weekday
kVA 0-6 Weekday (1 = Monday)
Demand kVATime Stamp
- Circuit 34(Hour) 34 106 11026 11027 Analog Input 530 R
R Hour
kVA 0 - 23 Hour (13 = 1PM)
DemandkVA Time Stamp35
- Circuit (Minute) 35 107 11028 11029 Analog Input 531 R
R Minute
kVA 0 - 59 Minute
DemandkVA Time Stamp36
- Circuit (Second) 36 108 11030 11031 Analog Input 532 R Seconds
kVA 0 - 59 Second
kVA - Circuit 37 37 11032 11033 Analog Input 533 R kVA Writing to RTC will disable NTP by clearing out URL and/or IP Address
RealkVA
Time Clock (Year)
- Circuit 38 38 109 UINT16 11034 11035 Analog Input 534 R/W
R Year
kVA Years since 1900 (118 = 2018)
Real kVA
Time- Clock
Circuit(Month)
39 39 110 UINT16 11036 11037 Analog Input 535 R/W
R Month
kVA 0 - 11 Month (0 = January)
Device Object Local_Date
RealkVA
Time- Circuit
Clock 40(Day) 40 111 UINT16 11038 11039 Analog Input 536 R
R/W kVA
Day 1 - 31 Day of the Month
kVA Clock
Real Time - Circuit 41
(Weekday) 41 112 UINT16 11040 11041 Analog Input 537 R
R/W kVA
Weekday 0-6 Weekday (1 = Monday)
RealkVA
Time- Circuit 42
Clock (Hour) 42 113 UINT16 11042 11043 Analog Input 538 R
R/W kVA
Hour 0 - 23 Hour (13 = 1PM)
RealkVA
Time- Circuit
Clock 43(Min) 43 114 UINT16 11044 11045 AnalogObject
Device Input 539
Local_Time R
R/W kVA
Minute 0 - 59 Minute
Real kVA
Time- Clock
Circuit(Second)
44 44 115 UINT16 11046 11047 Analog Input 540 R
R/W kVA
Seconds 0 - 59 Second
kVA - Circuit
Digital Output45 #1 45 116 11048 11049 AnalogOutput
Binary Input 541
1 R
R/W kVA 0, 1
kVA - Circuit
Digital Output46 #2 46 117 11050 11051 AnalogOutput
Binary Input 542
2 R
R/W kVA 0, 1
kVA - Circuit 47 47 11052 11053 Analog Input 543 R kVA
Digital Input #1 State 118 Binary Input 1 R 0, 1
kVA - Circuit 48 48 11054 11055 Analog Input 544 R kVA
Digital Input #2 State 119 Binary Input 2 R 0, 1
kVA - Circuit 49 49 11056 11057 Analog Input 545 R kVA
Modbus Slave Address 124 UINT16 R/W NV 1 - 254
kVA - Circuit 50 50 11058 11059 Analog Input 546 R kVA
Modbus TCP Port 125 UINT16 R NV 502
kVA - Circuit 51 51 11060 11061 Analog Input 547 R kVA
kVAIP -Address
Circuit 52 52 126 127 11062 11063 Analog Input R/W
R NV kVA
548 Meter must be rebooted for new network settings to affect.
kVAGateway
- Circuit 53 53 128 129 11064 11065 Analog Input 549 R/W
R NV kVA Device can be rebooted remotely using Global Reset/Command (Register 192)
kVA -Mask
Circuit 54 54 130 131 11066 11067 Analog Input 550 R/W
R NV kVA
kVA - Circuit 55 55 11068 11069 Analog Input 551 R kVA
kVA - Circuit 56 56 11070 11071 Analog Input 552 R kVA
kVA - Circuit 57 57 11072 11073 Analog Input 553 R kVA

UMG 804
25
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter
kVA -Information
Circuit 58 58 11074 11075 Analog Input 554 R kVA
kVA - Circuit
Serial Number 59 59 1 2 UINT32 11076 11077 AnalogObject
Device Input 555
Serial_Number R NV kVA
kVA - Circuit
Bootloader 60
Version 60 3 UINT16 11078 11079 Analog Input 556 R
R NV kVA
kVA - Circuit
Firmware 61
Version 61 4 UINT16 11080 11081 AnalogObject
Device Input 557
Firmware_Revision R
R NV kVA
kVADevice
- Circuit
ID 62 62 5 UINT16 11082 11083 Analog Input 558 R
R/W NV kVA 15172, 22000 22000 = Janitza Pointmap
kVA -Up
Power Circuit 63
Counter 63 6 UINT16 11084 11085 Analog Input 559 R
R NV kVA
kVA - Circuit 64 64 11086 11087 Analog Input 560 R kVA
Uptime 7 8 UINT32 R NV Seconds
kVA - Circuit 65 65 11088 11089 Analog Input 561 R kVA
Smart Port ID #1 10 UINT16 R NV
kVA - Circuit 66 66 11090 11091 Analog Input 562 R kVA
Smart Port ID #2 11 UINT16 R NV
kVA - Circuit 67 67 11092 11093 Analog Input 563 R kVA See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
kVA - Circuit 68 68 11094 11095 Analog Input 564 R kVA
Smart Port ID69
kVA - Circuit #4 69 13 UINT16 11096 11097 Analog Input 565 R
R NV kVA
Smart Port
kVA -#1Circuit
Serial70Number 70 14 15 UINT32 11098 11099 Analog Input 566 R
R NV kVA
Smart Port
kVA -#2Circuit
Serial71Number 71 16 17 UINT32 11100 11101 Analog Input 567 R
R NV kVA
Smart Port
kVA -#3Circuit
Serial72Number 72 18 19 UINT32 11102 11103 Analog Input 568 R NV kVA
Smart Port
kVA -#4Circuit
Serial73Number 73 20 21 UINT32 11104 11105 Analog Input 569 R NV kVA
Smart Port
kVA#1- Circuit
Firmware 74 Version 74 22 UINT16 11106 11107 Analog Input 570 R NV kVA
kVA#2- Circuit
Smart Port Firmware 75 Version 75 23 UINT16 11108 11109 Analog Input 571 R NV kVA
kVA#3- Circuit
Smart Port Firmware 76 Version 76 24 UINT16 11110 11111 Analog Input 572 R NV kVA
kVA#4- Circuit
Smart Port Firmware 77 Version 77 25 UINT16 11112 11113 Analog Input 573 R NV kVA
MACkVA - Circuit
Address (Bit78
33-48) 78 26 11114 11115 Analog Input 574 R
R NV kVA
MACkVA - Circuit
Address (Bit79
17-32) 79 27 11116 11117 Analog Input 575 R
R NV kVA
MACkVA - Circuit
Address (Bit80
1-16) 80 28 11118 11119 Analog Input 576 R
R NV kVA
BrandkVA - Circuit 81 81 11120 11121 R kVA
Analog Input 577
Name (16 Registers) 29 44 R NV
kVA - Circuit 82 82 11122 11123 Analog Input 578 R kVA Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
kVA - Circuit 83 83 11124 11125 Analog Input 579 R kVA supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
kVA - Circuit 84 84 11126 11127 Analog Input 580 R kVA
kVA - Circuit 85 85 11128 11129 Analog Input 581 R kVA
Meter Configuration
kVA - Circuit 86 86 11130 11131 Analog Input 582 R kVA
Demand # of Sub-Intervals 100 UINT16 Analog Value 1 R/W NV 1-6
kVA - Circuit 87 87 11132 11133 Analog Input 583 R kVA
Demand Sub-Interval Length 101 UINT16 Analog Value 2 R/W NV Seconds 0, 10 - 32767 0 = Sync to Comms
kVA - Circuit 88 88 11134 11135 Analog Input 584 R kVA
Demand Time Stamp (Year) 102 R Year Years since 1900 (118 = 2018)
kVA - Circuit 89 89 11136 11137 Analog Input 585 R kVA
Demand Time Stamp (Month) 103 R Month 0 - 11 Month (0 = January)
kVA - Circuit 90 90 11138 11139 Analog Input 586 R kVA
Demand Time Stamp (Day) 104 R Day 1 - 31 Day of the Month
kVA - Circuit 91 91 11140 11141 Analog Input 587 R kVA
Demand Time Stamp (Weekday) 105 R Weekday 0-6 Weekday (1 = Monday)
kVA - Circuit 92 92 11142 11143 Analog Input 588 R kVA
Demand Time Stamp (Hour) 106 R Hour 0 - 23 Hour (13 = 1PM)
kVA - Circuit 93 93 11144 11145 Analog Input 589 R kVA
Demand Time Stamp (Minute) 107 R Minute 0 - 59 Minute
kVA - Circuit 94 94 11146 11147 Analog Input 590 R kVA
Demand Time Stamp (Second) 108 R Seconds 0 - 59 Second
kVA - Circuit 95 95 11148 11149 Analog Input 591 R kVA
Writing to RTC will disable NTP by clearing out URL and/or IP Address
kVA - Circuit 96 96 11150 11151 Analog Input 592 R kVA
Real Time Clock (Year) 109 UINT16 R/W Year Years since 1900 (118 = 2018)
Real Time Clock (Month) 110 UINT16 R/W Month 0 - 11 Month (0 = January)
Current 11152 11343 Device
AnalogObject
Input Local_Date
593 - 688 R Amps
Real Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
Current - Circuit 1 1 11152 11153 Analog Input 593 R Amps
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
Current - Circuit 2 2 11154 11155 Analog Input 594 R Amps
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
Current - Circuit 3 3 11156 11157 Analog Input 595 R Amps
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Current - Circuit 4 4 11158 11159 Analog Input 596 R Amps
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Current - Circuit 5 5 11160 11161 Analog Input 597 R Amps
Digital Output #1 116 Binary Output 1 R/W 0, 1
Current - Circuit 6 6 11162 11163 Analog Input 598 R Amps
Digital Output
Current - Circuit#27 7 117 11164 11165
Binary Output
Analog Input
2
599 R/W
R Amps 0, 1
Digital Input
Current #1 State
- Circuit 8 8 118 11166 11167 Binary Input
Analog Input
1
600 R
R Amps 0, 1
Digital Input
Current #2 State
- Circuit 9 9 119 11168 11169 Binary Input
Analog Input 2
601 R
R Amps 0, 1
Modbus
CurrentSlave Address
- Circuit 10 10 124 UINT16 11170 11171 Analog Input 602 R/W
R NV Amps 1 - 254
Modbus TCP Port
Current - Circuit 11 11 125 UINT16 11172 11173 Analog Input 603 R NV Amps 502
IP Address
Current - Circuit 12 12 126 127 11174 11175 Analog Input 604 R/W
R NV Amps
Meter must be rebooted for new network settings to affect.
Current - Circuit 13
Gateway 13 128 129 11176 11177 Analog Input 605 R
R/W NV Amps
Device can be rebooted remotely using Global Reset/Command (Register 192)
CurrentMask
- Circuit 14 14 130 131 11178 11179 Analog Input 606 R
R/W NV Amps
Current - Circuit 15 15 11180 11181 Analog Input 607 R Amps
Current - Circuit 16 16 11182 11183 Analog Input 608 R Amps
Current - Circuit 17 17 11184 11185 Analog Input 609 R Amps

UMG 804
26
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
CurrentInformation
Meter - Circuit 18 18 11186 11187 Analog Input 610 R Amps
Current
Serial -Number
Circuit 19 19 1 2 UINT32 11188 11189 AnalogObject
Device Input 611
Serial_Number R
R NV Amps
Current - Circuit
Bootloader 20
Version 20 3 UINT16 11190 11191 Analog Input 612 R
R NV Amps
Current
Firmware - Circuit
Version21 21 4 UINT16 11192 11193 AnalogObject
Device Input 613
Firmware_Revision R
R NV Amps
Current - Circuit
Device ID 22 22 5 UINT16 11194 11195 Analog Input 614 R
R/W NV Amps 15172, 22000 22000 = Janitza Pointmap
Current - Circuit 23 23 11196 11197 Analog Input 615 R Amps
Power Up Counter 6 UINT16 R NV
Current - Circuit 24 24 11198 11199 Analog Input 616 R Amps
Uptime 7 8 UINT32 R NV Seconds
Current - Circuit 25 25 11200 11201 Analog Input 617 R Amps
Smart Port ID #1 10 UINT16 R NV
Current - Circuit 26 26 11202 11203 Analog Input 618 R Amps
Smart Port ID #2 11 UINT16 R NV
Current - Circuit 27 27 11204 11205 Analog Input 619 R Amps See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port
Current ID #3
- Circuit 28 28 12 UINT16 11206 11207 Analog Input 620
R
R NV Amps
Smart Port
Current ID #4
- Circuit 29 29 13 UINT16 11208 11209 Analog Input 621 R
R NV Amps
SmartCurrent
Port #1- Circuit
Serial Number
30 30 14 15 UINT32 11210 11211 Analog Input 622 R
R NV Amps
SmartCurrent
Port #2- Circuit
Serial Number
31 31 16 17 UINT32 11212 11213 Analog Input 623 R
R NV Amps
SmartCurrent
Port #3- Circuit
Serial Number
32 32 18 19 UINT32 11214 11215 Analog Input 624 R NV Amps
SmartCurrent
Port #4- Circuit
Serial Number
33 33 20 21 UINT32 11216 11217 Analog Input 625 R NV Amps
Smart Port #1 Firmware
Current - Circuit 34Version 34 22 UINT16 11218 11219 Analog Input 626 R NV Amps
Current
Smart Port - Circuit 35Version
#2 Firmware 35 23 UINT16 11220 11221 Analog Input 627 R NV Amps
Current
Smart Port - Circuit 36Version
#3 Firmware 36 24 UINT16 11222 11223 Analog Input 628 R NV Amps
Current
Smart Port - Circuit 37Version
#4 Firmware 37 25 UINT16 11224 11225 Analog Input 629 R
R NV Amps
MACCurrent
Address- Circuit 38
(Bit 33-48) 38 26 11226 11227 Analog Input 630 R
R NV Amps
MACCurrent
Address- Circuit 39
(Bit 17-32) 39 27 11228 11229 Analog Input 631 R
R NV Amps
Current
MAC - Circuit
Address 40
(Bit 1-16) 40 28 11230 11231 Analog Input 632 R
R NV Amps
Current - Circuit 41 41 11232 11233 Analog Input 633 R Amps
Brand Name (16 Registers) 29 44 R NV
Current - Circuit 42 42 11234 11235 Analog Input 634 R Amps Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Current - Circuit 43 43 11236 11237 Analog Input 635 R Amps supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Current - Circuit 44 44 11238 11239 Analog Input 636 R Amps
Current - Circuit 45 45 11240 11241 Analog Input 637 R Amps
Meter
CurrentConfiguration
- Circuit 46 46 11242 11243 Analog Input 638 R Amps
Demand # of- Circuit
Current Sub-Intervals
47 47 100 UINT16 11244 11245 Analog Value
Analog Input
1
639 R/W
R NV Amps 1-6
Demand Sub-Interval
Current - Circuit 48 Length 48 101 UINT16 11246 11247 Analog
Analog Value
Input 2
640 R/W
R NV Seconds
Amps 0, 10 - 32767 0 = Sync to Comms
Demand Time Stamp
Current - Circuit 49 (Year) 49 102 11248 11249 Analog Input 641 R
R Year
Amps Years since 1900 (118 = 2018)
Demand Time- Stamp
Current Circuit (Month)
50 50 103 11250 11251 Analog Input 642 R Month
Amps 0 - 11 Month (0 = January)
Demand Time
Current Stamp51
- Circuit (Day) 51 104 11252 11253 Analog Input 643 R Day
Amps 1 - 31 Day of the Month
Demand Time Stamp
Current - Circuit(Weekday)
52 52 105 11254 11255 Analog Input 644 R Weekday
Amps 0-6 Weekday (1 = Monday)
Current
Demand Time - Circuit
Stamp53 (Hour) 53 106 11256 11257 Analog Input 645 R Amps
Hour 0 - 23 Hour (13 = 1PM)
DemandCurrent
Time-Stamp
Circuit(Minute)
54 54 107 11258 11259 Analog Input 646 R Amps
Minute 0 - 59 Minute
DemandCurrent
Time-Stamp
Circuit(Second)
55 55 108 11260 11261 Analog Input 647 R
R Amps
Seconds 0 - 59 Second
Current - Circuit 56 56 11262 11263 Analog Input 648 R Amps Writing to RTC will disable NTP by clearing out URL and/or IP Address
Current
Real Time-Clock
Circuit 57
(Year) 57 109 UINT16 11264 11265 Analog Input 649 R
R/W Amps
Year Years since 1900 (118 = 2018)
Current
Real - Circuit
Time Clock 58
(Month) 58 110 UINT16 11266 11267 Analog Input 650 R
R/W Amps
Month 0 - 11 Month (0 = January)
Current Device
AnalogObject Local_Date
Time- Clock
Circuit(Day)
59 59 11268 11269 R Amps
Input 651
Real 111 UINT16 R/W Day 1 - 31 Day of the Month
Current - Circuit 60 60 11270 11271 Analog Input 652 R Amps
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
Current - Circuit 61 61 11272 11273 Analog Input 653 R Amps
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
Current - Circuit 62 62 11274 11275 Analog Input 654 R Amps
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Current - Circuit 63 63 11276 11277 Analog Input 655 R Amps
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Current - Circuit 64 64 11278 11279 Analog Input 656 R Amps
Digital Output #1 116 Binary Output 1 R/W 0, 1
Current - Circuit 65 65 11280 11281 Analog Input 657 R Amps
Digital Output
Current - Circuit#266 66 117 11282 11283
Binary Output
Analog Input
2
658
R/W
R Amps 0, 1
Digital
CurrentInput #1 State
- Circuit 67 67 118 11284 11285 Binary Input
Analog Input
1
659 R
R Amps 0, 1
Digital
CurrentInput #2 State
- Circuit 68 68 119 11286 11287 Binary Input
Analog Input 2
660 R
R Amps 0, 1
Modbus Slave Address
Current - Circuit 69 69 124 UINT16 11288 11289 Analog Input 661 R/W
R NV Amps 1 - 254
Modbus TCP Port
Current - Circuit 70 70 125 UINT16 11290 11291 Analog Input 662 R NV Amps 502
IP Address
Current - Circuit 71 71 126 127 11292 11293 Analog Input 663 R/W
R NV Amps
Meter must be rebooted for new network settings to affect.
Gateway
Current - Circuit 72 72 128 129 11294 11295 Analog Input 664 R/W
R NV Amps
Device can be rebooted remotely using Global Reset/Command (Register 192)
CurrentMask
- Circuit 73 73 130 131 11296 11297 Analog Input 665 R
R/W NV Amps
Current - Circuit 74 74 11298 11299 Analog Input 666 R Amps
Current - Circuit 75 75 11300 11301 Analog Input 667 R Amps
Current - Circuit 76 76 11302 11303 Analog Input 668 R Amps

UMG 804
27
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter
CurrentInformation
- Circuit 77 77 11304 11305 Analog Input 669 R Amps
Serial -Number
Current Circuit 78 78 1 2 UINT32 11306 11307 Device
AnalogObject
Input Serial_Number
670 R NV Amps
Current - Circuit
Bootloader Version79 79 3 UINT16 11308 11309 Analog Input 671 R NV Amps
Current
Firmware - Circuit
Version 80 80 4 UINT16 11310 11311 AnalogObject
Device Input 672
Firmware_Revision R NV Amps
Current - Circuit
Device ID 81 81 5 UINT16 11312 11313 Analog Input 673 R
R/W NV Amps 15172, 22000 22000 = Janitza Pointmap
Current
Power Up - Circuit
Counter 82 82 6 UINT16 11314 11315 Analog Input 674 R
R NV Amps
Current - Circuit 83
Uptime 83 7 8 UINT32 11316 11317 Analog Input 675 R
R NV Amps
Seconds
Current - Circuit
Smart Port ID #1 84 84 10 UINT16 11318 11319 Analog Input 676 R
R NV Amps
Current - Circuit 85 85 11320 11321 Analog Input 677 R Amps
Smart Port ID #2 11 UINT16 R NV
Current - Circuit 86 86 11322 11323 Analog Input 678 R Amps See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
Current - Circuit 87 87 11324 11325 Analog Input 679 R Amps
Smart Port ID #4 13 UINT16 R NV
Current - Circuit 88 88 11326 11327 Analog Input 680 R Amps
Smart Port #1 Serial Number 14 15 UINT32 R NV
Current - Circuit 89 89 11328 11329 Analog Input 681 R Amps
SmartCurrent
Port #2- Circuit
Serial Number
90 90 16 17 UINT32 11330 11331 Analog Input 682
R
R NV Amps
SmartCurrent
Port #3- Circuit
Serial Number
91 91 18 19 UINT32 11332 11333 Analog Input 683 R
R NV Amps
SmartCurrent
Port #4- Circuit
Serial Number
92 92 20 21 UINT32 11334 11335 Analog Input 684 R
R NV Amps
Smart Port #1 Firmware
Current - Circuit 93Version 93 22 UINT16 11336 11337 Analog Input 685 R
R NV Amps
Smart Port
Current - Circuit 94Version
#2 Firmware 94 23 UINT16 11338 11339 Analog Input 686 R NV Amps
Smart Port #3 Firmware
Current - Circuit 95Version 95 24 UINT16 11340 11341 Analog Input 687 R NV Amps
Smart Port #4 Firmware
Current - Circuit 96Version 96 25 UINT16 11342 11343 Analog Input 688 R NV Amps
MAC Address (Bit 33-48) 26 R NV
MAC Address (Bit 17-32)
Power Factor 27 11344 11535 Analog Input 689 - 784 R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
MAC Address
Power Factor -(Bit 1-16)1
Circuit 1 28 11344 11345 Analog Input 689 R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power
Brand Factor
Name (16- Circuit
Registers)2 2 29 44 11346 11347 Analog Input 690 R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Brand Name, Model Name and Device Name
PowerName
Model Factor(16- Circuit
Register)3 3 45 60 11348 11349 Device
AnalogObject
Input Model_Name
691 R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
supports up to 32 characters (16 registers)
Device
PowerName
Factor(16- Circuit
Registers)4 4 61 76 11350 11351 Device
AnalogObject
Input Object_Name
692 R/W
R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power Factor - Circuit 5 5 11352 11353 Analog Input 693 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
MeterFactor
Power Configuration
- Circuit 6 6 11354 11355 Analog Input 694 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Demand # of Sub-Intervals
Power Factor - Circuit 7 7 100 UINT16 11356 11357 Analog Value
Input 1
695 R/W
R NV 1 -- 61.0
-1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Demand
PowerSub-Interval
Factor - Circuit Length
8 8 101 UINT16 11358 11359 Analog Value
Input 2
696 R/W
R NV Seconds 0, -1.0
10 - -32767
1.0 0 = Sync toNegative
Positive for Leading (Capacitive), Comms for Lagging (Inductive)
Demand Time Stamp
Power Factor (Year)
- Circuit 9 9 102 11360 11361 Analog Input 697 R Year -1.0 - 1.0 Positive for LeadingYears since 1900Negative
(Capacitive), (118 = 2018)
for Lagging (Inductive)
Demand
Power Time
FactorStamp (Month)
- Circuit 10 10 103 11362 11363 Analog Input 698 R Month 0 - -11
-1.0 1.0 Month (0 =Negative
Positive for Leading (Capacitive), January)for Lagging (Inductive)
Demand Time Stamp
Power Factor - Circuit (Day)
11 11 104 11364 11365 Analog Input 699 R Day 1 - -31
-1.0 1.0 Day of theNegative
Positive for Leading (Capacitive), Month for Lagging (Inductive)
Demand
PowerTime Stamp
Factor (Weekday)
- Circuit 12 12 105 11366 11367 Analog Input 700 R Weekday 0 -- 61.0
-1.0 Weekday (1 Negative
Positive for Leading (Capacitive), = Monday) for Lagging (Inductive)
Demand Time Stamp
Power Factor - Circuit(Hour)
13 13 106 11368 11369 Analog Input 701 R Hour 0 - -23
-1.0 1.0 Hour (13Negative
Positive for Leading (Capacitive), = 1PM) for Lagging (Inductive)
Demand
PowerTime
FactorStamp (Minute)
- Circuit 14 14 107 11370 11371 Analog Input 702 R Minute 0 - -59
-1.0 1.0 Minute
Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Demand
PowerTime
FactorStamp (Second)
- Circuit 15 15 108 11372 11373 Analog Input 703 R Seconds 0 - -59
-1.0 1.0 Second
Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power Factor - Circuit 16 16 11374 11375 Analog Input 704 R -1.0 - 1.0 Positive
Writing tofor
RTCLeading (Capacitive),
will disable Negativeout
NTP by clearing forURL
Lagging (Inductive)
and/or IP Address
Power Factor
Real Time - Circuit
Clock (Year)17 17 109 UINT16 11376 11377 Analog Input 705 R
R/W Year -1.0 - 1.0 Positive for Leading (Capacitive),
Years since 1900Negative for Lagging (Inductive)
(118 = 2018)
Power Factor
Real Time - Circuit
Clock (Month) 18 18 110 UINT16 11378 11379 Analog Input 706 R
R/W Month -1.0
0 - -111.0 Positive for Leading (Capacitive),
Month (0 =Negative
January)for Lagging (Inductive)
Device Object Local_Date
Power Factor
Real Time - Circuit
Clock (Day)19 19 111 UINT16 11380 11381 Analog Input 707 R
R/W Day -1.0
1 - -311.0 Positive for Leading (Capacitive),
Day of theNegative
Month for Lagging (Inductive)
Power
Real TimeFactor
Clock- (Weekday)
Circuit 20 20 112 UINT16 11382 11383 Analog Input 708 R
R/W Weekday -1.0
0 -- 61.0 Positive for Leading (Capacitive),
Weekday (1 Negative
= Monday) for Lagging (Inductive)
Power Factor
Real Time - Circuit
Clock (Hour) 21 21 113 UINT16 11384 11385 Analog Input 709 R
R/W Hour -1.0
0 - -231.0 Positive for Leading (Capacitive),
Hour (13Negative
= 1PM) for Lagging (Inductive)
Power Factor
Real Time - Circuit
Clock (Min)22 22 114 UINT16 11386 11387 AnalogObject
Device Input 710
Local_Time R
R/W Minute -1.0
0 - -591.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Minute
Power
Real Factor
Time Clock- Circuit
(Second) 23 23 115 UINT16 11388 11389 Analog Input 711 R
R/W Seconds -1.0
0 - -591.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Second
Power Factor - Circuit 24 24 11390 11391 Analog Input 712 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Digital Output #1 116 Binary Output 1 R/W 0, 1
Power Factor - Circuit 25 25 11392 11393 Analog Input 713 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Digital Output #2 117 Binary Output 2 R/W 0, 1
Power Factor - Circuit 26 26 11394 11395 Analog Input 714 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Digital Input #1 State 118 Binary Input 1 R 0, 1
Power Factor - Circuit 27 27 11396 11397 Analog Input 715 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Digital Input #2 State 119 Binary Input 2 R 0, 1
Power Factor - Circuit 28 28 11398 11399 Analog Input 716 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Modbus
Power Slave- Circuit
Factor Address 29 29 124 UINT16 11400 11401 Analog Input 717
R/W
R NV 1 - 254
-1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Modbus
Power FactorTCP Port 30
- Circuit 30 125 UINT16 11402 11403 Analog Input 718 R
R NV 502
-1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
IP Address
Power Factor - Circuit 31 31 126 127 11404 11405 R/W
R NV -1.0 - 1.0 Positive
Analog Input 719
Meterfor Leading
must (Capacitive),
be rebooted Negative
for new networkforsettings
Laggingto(Inductive)
affect.
Gateway
Power Factor - Circuit 32 32 128 129 11406 11407 R/W
R NV -1.0 - 1.0
Analog Input 720
DevicePositive for Leading
can be rebooted (Capacitive),
remotely Negative
using Global for Lagging (Inductive)
Reset/Command (Register 192)
Mask- Circuit 33
Power Factor 33 130 131 11408 11409 Analog Input 721 R/W
R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power Factor - Circuit 34 34 11410 11411 Analog Input 722 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power Factor - Circuit 35 35 11412 11413 Analog Input 723 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power Factor - Circuit 36 36 11414 11415 Analog Input 724 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)

UMG 804
28
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Power
MeterFactor - Circuit 37
Information 37 11416 11417 Analog Input 725 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
PowerSerial
Factor - Circuit 38
Number 38 1 2 UINT32 11418 11419 AnalogObject
Device Input 726
Serial_Number R
R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power Factor -Version
Bootloader Circuit 39 39 3 UINT16 11420 11421 Analog Input 727 R
R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power Factor Version
Firmware - Circuit 40 40 4 UINT16 11422 11423 AnalogObject
Device Input 728
Firmware_Revision R
R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power Factor
Device- ID
Circuit 41 41 5 UINT16 11424 11425 Analog Input 729 R
R/W NV -1.0 -22000
15172, 1.0 Positive for Leading 22000
(Capacitive), Negative
= Janitza for Lagging (Inductive)
Pointmap
Power Factor - Circuit 42 42 11426 11427 Analog Input 730 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power Up Counter 6 UINT16 R NV
Power Factor - Circuit 43 43 11428 11429 Analog Input 731 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Uptime 7 8 UINT32 R NV Seconds
Power Factor - Circuit 44 44 11430 11431 Analog Input 732 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Smart Port ID #1 10 UINT16 R NV
Power Factor - Circuit 45 45 11432 11433 Analog Input 733 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Smart Port ID #2 11 UINT16 R NV
Power Factor - Circuit 46 46 11434 11435 Analog Input 734 R -1.0Notes
See - 1.0 0=Nothing Positive for1=DIN
Connected, Leading (Capacitive),
RAIL CT Interface Negative forRAIL
Card, 4=DIN Lagging (Inductive)
CT Interface Floating Board
Smart
Power Port- Circuit
Factor ID #3 47 47 12 UINT16 11436 11437 Analog Input 735
R
R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Smart
Power Port- Circuit
Factor ID #4 48 48 13 UINT16 11438 11439 Analog Input 736 R
R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Smart
PowerPort #1 Serial
Factor Number
- Circuit 49 49 14 15 UINT32 11440 11441 Analog Input 737 R
R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Smart
PowerPort #2 Serial
Factor Number
- Circuit 50 50 16 17 UINT32 11442 11443 Analog Input 738 R
R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Smart
PowerPort #3 Serial
Factor Number
- Circuit 51 51 18 19 UINT32 11444 11445 Analog Input 739 R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Smart
PowerPort #4 Serial
Factor Number
- Circuit 52 52 20 21 UINT32 11446 11447 Analog Input 740 R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Smart PortFactor
Power #1 Firmware
- CircuitVersion
53 53 22 UINT16 11448 11449 Analog Input 741 R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power
Smart PortFactor - CircuitVersion
#2 Firmware 54 54 23 UINT16 11450 11451 Analog Input 742 R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power
Smart PortFactor - CircuitVersion
#3 Firmware 55 55 24 UINT16 11452 11453 Analog Input 743 R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power
Smart PortFactor - CircuitVersion
#4 Firmware 56 56 25 UINT16 11454 11455 Analog Input 744 R
R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power Factor -(Bit
MAC Address Circuit 57
33-48) 57 26 11456 11457 Analog Input 745 R
R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power Factor -(Bit
MAC Address Circuit 58
17-32) 58 27 11458 11459 Analog Input 746 R
R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power Factor -(Bit
MAC Address Circuit
1-16)59 59 28 11460 11461 Analog Input 747 R
R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power Factor - Circuit 60 60 11462 11463 Analog Input 748 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Brand Name (16 Registers) 29 44 R NV
Power Factor - Circuit 61 61 11464 11465 Analog Input 749 R -1.0 - 1.0 Positive Brand Name,
for Leading Model Name
(Capacitive), and Device
Negative Name
for Lagging (Inductive)
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Power Factor - Circuit 62 62 11466 11467 Analog Input 750 R -1.0 - 1.0 supports
Positive for Leadingup to 32 characters
(Capacitive), Negative(16
forregisters)
Lagging (Inductive)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Power Factor - Circuit 63 63 11468 11469 Analog Input 751 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power Factor - Circuit 64 64 11470 11471 Analog Input 752 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
MeterFactor
Power Configuration
- Circuit 65 65 11472 11473 Analog Input 753 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Demand # of Sub-Intervals
Power Factor - Circuit 66 66 100 UINT16 11474 11475 Analog Value
Analog Input
1
754 R/W
R NV 1 -- 61.0
-1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Demand Sub-Interval
Power Factor - Circuit Length
67 67 101 UINT16 11476 11477 Analog
Analog Value
Input 2
755 R/W
R NV Seconds 0, -1.0
10 - -32767
1.0 0 = Sync toNegative
Positive for Leading (Capacitive), Comms for Lagging (Inductive)
Demand Time Stamp
Power Factor - Circuit (Year)
68 68 102 11478 11479 Analog Input 756 R
R Year -1.0 - 1.0 Positive for LeadingYears since 1900Negative
(Capacitive), (118 = 2018)
for Lagging (Inductive)
Demand
Power Time
FactorStamp (Month)
- Circuit 69 69 103 11480 11481 Analog Input 757 R Month 0 - -11
-1.0 1.0 Month (0 =Negative
Positive for Leading (Capacitive), January)for Lagging (Inductive)
Demand Time Stamp
Power Factor - Circuit(Day)
70 70 104 11482 11483 Analog Input 758 R Day 1 - -31
-1.0 1.0 Day of theNegative
Positive for Leading (Capacitive), Month for Lagging (Inductive)
Demand
PowerTime Stamp
Factor (Weekday)
- Circuit 71 71 105 11484 11485 Analog Input 759 R Weekday 0 -- 61.0
-1.0 Weekday (1 Negative
Positive for Leading (Capacitive), = Monday) for Lagging (Inductive)
Power Factor
Demand - Circuit
Time Stamp 72
(Hour) 72 106 11486 11487 Analog Input 760 R Hour -1.0
0 - -23
1.0 Positive for Leading (Capacitive),
Hour (13Negative
= 1PM) for Lagging (Inductive)
PowerTime
Demand Factor - Circuit
Stamp 73
(Minute) 73 107 11488 11489 Analog Input 761 R Minute -1.0
0 - -59
1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Minute
PowerTime
Demand Factor - Circuit
Stamp 74
(Second) 74 108 11490 11491 Analog Input 762 R
R Seconds -1.0
0 - -59
1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Second
Power Factor - Circuit 75 75 11492 11493 Analog Input 763 R -1.0 - 1.0 Positive
Writing tofor
RTCLeading (Capacitive),
will disable Negativeout
NTP by clearing forURL
Lagging
and/or(Inductive)
IP Address
Power Factor
Real Time - Circuit
Clock (Year)76 76 109 UINT16 11494 11495 Analog Input 764 R
R/W Year -1.0 - 1.0 Positive for Leading (Capacitive),
Years since 1900Negative for Lagging (Inductive)
(118 = 2018)
Power Factor
Real Time - Circuit
Clock (Month) 77 77 110 UINT16 11496 11497 Analog Input 765 R
R/W Month -1.0
0 - -11
1.0 Positive for Leading (Capacitive), Negative
Month (0 = January) for Lagging (Inductive)
Power Factor - Circuit Device
AnalogObject Local_Date
(Day)78 78 11498 11499 R -1.0
1 - -31
1.0 Positive for Leading (Capacitive),
Day of theNegative
Month for Lagging (Inductive)
Input 766
Real Time Clock 111 UINT16 R/W Day
Power Factor - Circuit 79 79 11500 11501 Analog Input 767 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
Power Factor - Circuit 80 80 11502 11503 Analog Input 768 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
Power Factor - Circuit 81 81 11504 11505 Analog Input 769 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Power Factor - Circuit 82 82 11506 11507 Analog Input 770 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Power Factor - Circuit 83 83 11508 11509 Analog Input 771 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Digital Output #1 116 Binary Output 1 R/W 0, 1
Power Factor - Circuit 84 84 11510 11511 Analog Input 772 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Digital
Power Output
Factor #2 85
- Circuit 85 117 11512 11513
Binary Output
Analog Input
2
773
R/W
R 0,-11.0
-1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Digital
Power Input-#1
Factor State86
Circuit 86 118 11514 11515 Binary Input
Analog Input
1
774 R
R 0,-11.0
-1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Digital
Power Input-#2
Factor State87
Circuit 87 119 11516 11517 Binary Input
Analog Input 2
775 R
R 0,-11.0
-1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Modbus
Power Slave- Circuit
Factor Address 88 88 124 UINT16 11518 11519 Analog Input 776 R/W
R NV 1 - 254
-1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Modbus
Power FactorTCP Port 89
- Circuit 89 125 UINT16 11520 11521 Analog Input 777 R NV 502
-1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
IP Address
Power Factor - Circuit 90 90 126 127 11522 11523 Analog Input 778 R/W
R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Meter must be rebooted for new network settings to affect.
Gateway
Power Factor - Circuit 91 91 128 129 11524 11525 Analog Input 779 R/W
R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Device can be rebooted remotely using Global Reset/Command (Register 192)
Power Factor
Mask- Circuit 92 92 130 131 11526 11527 Analog Input 780 R
R/W NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power Factor - Circuit 93 93 11528 11529 Analog Input 781 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power Factor - Circuit 94 94 11530 11531 Analog Input 782 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Power Factor - Circuit 95 95 11532 11533 Analog Input 783 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)

UMG 804
29
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter
Power Information
Factor - Circuit 96 96 11534 11535 Analog Input 784 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Serial Number 1 2 UINT32 Device Object Serial_Number R NV
Bootloader Version
Current Angle 3 UINT16 11536 11727 Analog Input 785 - 880 R NV Degrees -180° - 180° Referenced to Assigned Voltage Phase
Firmware
Current Angle- Version
Circuit 1 1 4 UINT16 11536 11537 Device
AnalogObject
Input Firmware_Revision
785 R NV Degrees
CurrentDevice
Angle-IDCircuit 2 2 5 UINT16 11538 11539 Analog Input 786 R/W
R NV Degrees 15172, 22000 22000 = Janitza Pointmap
PowerAngle-
Current Up Counter
Circuit 3 3 6 UINT16 11540 11541 Analog Input 787 R NV Degrees
Current Uptime
Angle- Circuit 4 4 7 8 UINT32 11542 11543 Analog Input 788 R NV Seconds
Degrees
Smart
Current Port ID
Angle- #1 5
Circuit 5 10 UINT16 11544 11545 Analog Input 789 R NV Degrees
Smart
Current Port ID
Angle- #2 6
Circuit 6 11 UINT16 11546 11547 Analog Input 790 R NV Degrees
See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart
Current Port ID
Angle- #3 7
Circuit 7 12 UINT16 11548 11549 Analog Input 791 R NV Degrees
Smart
Current Port ID
Angle- #4 8
Circuit 8 13 UINT16 11550 11551 Analog Input 792 R NV Degrees
Smart PortAngle-
Current #1 Serial Number
Circuit 9 9 14 15 UINT32 11552 11553 Analog Input 793 R NV Degrees
Smart PortAngle-
Current #2 Serial Number
Circuit 10 10 16 17 UINT32 11554 11555 Analog Input 794 R NV Degrees
Smart PortAngle-
Current #3 Serial Number
Circuit 11 11 18 19 UINT32 11556 11557 Analog Input 795 R NV Degrees
Smart PortAngle-
Current #4 Serial Number
Circuit 12 12 20 21 UINT32 11558 11559 Analog Input 796 R NV Degrees
Smart Port #1
Current Firmware
Angle- CircuitVersion
13 13 22 UINT16 11560 11561 Analog Input 797 R NV Degrees
Smart Port #2
Current Firmware
Angle- CircuitVersion
14 14 23 UINT16 11562 11563 Analog Input 798 R NV Degrees
Current
Smart Angle-
Port #3 CircuitVersion
Firmware 15 15 24 UINT16 11564 11565 Analog Input 799 R NV Degrees
Current
Smart Angle-
Port #4 CircuitVersion
Firmware 16 16 25 UINT16 11566 11567 Analog Input 800 R NV Degrees
Current Angle-(Bit
MAC Address Circuit 17
33-48) 17 26 11568 11569 Analog Input 801 R
R NV Degrees
Current Angle-(Bit
MAC Address Circuit 18
17-32) 18 27 11570 11571 Analog Input 802 R
R NV Degrees
Current Angle-(Bit
MAC Address Circuit
1-16)19 19 28 11572 11573 Analog Input 803 R
R NV Degrees
Current
Brand Angle-
Name (16Circuit 20
Registers) 20 29 44 11574 11575 Analog Input 804 R
R NV Degrees
Current Angle- Circuit 21 21 11576 11577 Analog Input 805 R Degrees Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Current Angle- Circuit 22 22 11578 11579 Analog Input 806 R Degrees supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Current Angle- Circuit 23 23 11580 11581 Analog Input 807 R Degrees
Current Angle- Circuit 24 24 11582 11583 Analog Input 808 R Degrees
Meter Configuration
Current Angle- Circuit 25 25 11584 11585 Analog Input 809 R Degrees
Demand
Current #Angle-
of Sub-Intervals
Circuit 26 26 100 UINT16 11586 11587
Analog Value
Analog Input
1
810
R/W
R NV Degrees 1-6
Demand
CurrentSub-Interval
Angle- Circuit Length
27 27 101 UINT16 11588 11589 Analog Value
Analog Input
2
811 R/W
R NV Seconds
Degrees 0, 10 - 32767 0 = Sync to Comms
Demand Time Stamp
Current Angle- Circuit (Year)
28 28 102 11590 11591 Analog Input 812 R
R Year
Degrees Years since 1900 (118 = 2018)
Demand
CurrentTime Stamp
Angle- (Month)
Circuit 29 29 103 11592 11593 Analog Input 813 R
R Month
Degrees 0 - 11 Month (0 = January)
Demand
Current Time
Angle- Stamp
Circuit(Day)
30 30 104 11594 11595 Analog Input 814 R Day
Degrees 1 - 31 Day of the Month
Demand Time
Current Stamp
Angle- (Weekday)
Circuit 31 31 105 11596 11597 Analog Input 815 R Weekday
Degrees 0-6 Weekday (1 = Monday)
Demand
CurrentTime
Angle- Stamp (Hour)
Circuit 32 32 106 11598 11599 Analog Input 816 R Hour
Degrees 0 - 23 Hour (13 = 1PM)
Current
Demand Angle-
Time StampCircuit 33
(Minute) 33 107 11600 11601 Analog Input 817 R Degrees
Minute 0 - 59 Minute
Current
Demand Angle-
Time StampCircuit 34
(Second) 34 108 11602 11603 Analog Input 818 R Degrees
Seconds 0 - 59 Second
Current Angle- Circuit 35 35 11604 11605 Analog Input 819 R Degrees Writing to RTC will disable NTP by clearing out URL and/or IP Address
Current Angle-
Real Time ClockCircuit
(Year)36 36 109 UINT16 11606 11607 Analog Input 820 R
R/W Degrees
Year Years since 1900 (118 = 2018)
Current
Real TimeAngle-
ClockCircuit
(Month) 37 37 110 UINT16 11608 11609 Analog Input 821 R
R/W Degrees
Month 0 - 11 Month (0 = January)
Current Angle- Circuit Device
AnalogObject Local_Date
Real Time Clock (Day)38 38 111 UINT16 11610 11611 Input 822 R
R/W Degrees
Day 1 - 31 Day of the Month
Current
Real TimeAngle- Circuit 39
Clock (Weekday) 39 112 UINT16 11612 11613 Analog Input 823 R
R/W Degrees
Weekday 0-6 Weekday (1 = Monday)
Current Angle-
Real Time ClockCircuit
(Hour) 40 40 113 UINT16 11614 11615 Analog Input 824 R
R/W Degrees
Hour 0 - 23 Hour (13 = 1PM)
Current Angle- Circuit 41 41 11616 11617 Analog Input 825 R Degrees
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Current Angle- Circuit 42 42 11618 11619 Analog Input 826 R Degrees
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Current Angle- Circuit 43 43 11620 11621 Analog Input 827 R Degrees
Digital Output #1 116 Binary Output 1 R/W 0, 1
Current Angle- Circuit 44 44 11622 11623 Analog Input 828 R Degrees
Digital Output #2 117 Binary Output 2 R/W 0, 1
Current Angle- Circuit 45 45 11624 11625 Analog Input 829 R Degrees
DigitalAngle-
Current Input #1 State46
Circuit 46 118 11626 11627
Binary Input
Analog Input
1
830
R
R Degrees 0, 1
DigitalAngle-
Current Input #2 State47
Circuit 47 119 11628 11629 Binary Input
Analog Input
2
831 R
R Degrees 0, 1
ModbusAngle-
Current Slave Circuit
Address 48 48 124 UINT16 11630 11631 Analog Input 832 R/W
R NV Degrees 1 - 254
Modbus
Current Angle-TCPCircuit
Port 49 49 125 UINT16 11632 11633 Analog Input 833 R
R NV Degrees 502
CurrentIPAngle-
Address Circuit 50 50 126 127 11634 11635 Analog Input 834 R/W
R NV Degrees Meter must be rebooted for new network settings to affect.
Current Gateway
Angle- Circuit 51 51 128 129 11636 11637 Analog Input 835 R/W
R NV Degrees
Device can be rebooted remotely using Global Reset/Command (Register 192)
Mask Circuit 52
Current Angle- 52 130 131 11638 11639 Analog Input 836 R/W
R NV Degrees
Current Angle- Circuit 53 53 11640 11641 Analog Input 837 R Degrees
Current Angle- Circuit 54 54 11642 11643 Analog Input 838 R Degrees
Current Angle- Circuit 55 55 11644 11645 Analog Input 839 R Degrees

UMG 804
30
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
MeterAngle-
Current Information
Circuit 56 56 11646 11647 Analog Input 840 R Degrees
Current Angle-
Serial NumberCircuit 57 57 1 2 UINT32 11648 11649 AnalogObject
Device Input 841
Serial_Number R NV Degrees
Current Angle-Version
Bootloader Circuit 58 58 3 UINT16 11650 11651 Analog Input 842 R
R NV Degrees
Current Angle-Version
Firmware Circuit 59 59 4 UINT16 11652 11653 AnalogObject
Device Input 843
Firmware_Revision R
R NV Degrees
CurrentDevice
Angle- ID Circuit 60 60 5 UINT16 11654 11655 Analog Input 844 R
R/W NV Degrees 15172, 22000 22000 = Janitza Pointmap
Current
Power Angle- Circuit 61
Up Counter 61 6 UINT16 11656 11657 Analog Input 845 R
R NV Degrees
Current Angle- Circuit 62 62 11658 11659 Analog Input 846 R Degrees
Uptime 7 8 UINT32 R NV Seconds
Current Angle- Circuit 63 63 11660 11661 Analog Input 847 R Degrees
Smart Port ID #1 10 UINT16 R NV
Current Angle- Circuit 64 64 11662 11663 Analog Input 848 R Degrees
Smart Port ID #2 11 UINT16 R NV
Current Angle- Circuit 65 65 11664 11665 Analog Input 849 R Degrees See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
Current Angle- Circuit 66 66 11666 11667 Analog Input 850 R Degrees
Smart
Current Port Circuit
Angle- ID #4 67 67 13 UINT16 11668 11669 Analog Input 851 R
R NV Degrees
Smart PortAngle-
Current #1 Serial Number
Circuit 68 68 14 15 UINT32 11670 11671 Analog Input 852 R
R NV Degrees
Smart PortAngle-
Current #2 Serial Number
Circuit 69 69 16 17 UINT32 11672 11673 Analog Input 853 R
R NV Degrees
Smart PortAngle-
Current #3 Serial Number
Circuit 70 70 18 19 UINT32 11674 11675 Analog Input 854 R NV Degrees
Smart PortAngle-
Current #4 Serial Number
Circuit 71 71 20 21 UINT32 11676 11677 Analog Input 855 R NV Degrees
Smart Port #1
Current Firmware
Angle- CircuitVersion
72 72 22 UINT16 11678 11679 Analog Input 856 R NV Degrees
Current
Smart Angle-
Port #2 CircuitVersion
Firmware 73 73 23 UINT16 11680 11681 Analog Input 857 R NV Degrees
Current
Smart Angle-
Port #3 CircuitVersion
Firmware 74 74 24 UINT16 11682 11683 Analog Input 858 R NV Degrees
Current
Smart Angle-
Port #4 CircuitVersion
Firmware 75 75 25 UINT16 11684 11685 Analog Input 859 R NV Degrees
Current Angle-(Bit
MAC Address Circuit 76
33-48) 76 26 11686 11687 Analog Input 860 R
R NV Degrees
Current Angle-(Bit
MAC Address Circuit 77
17-32) 77 27 11688 11689 Analog Input 861 R
R NV Degrees
Current Angle-(Bit
MAC Address Circuit
1-16)78 78 28 11690 11691 Analog Input 862 R
R NV Degrees
Current
Brand Angle-
Name (16Circuit 79
Registers) 79 29 44 11692 11693 Analog Input 863 R
R NV Degrees
Current Angle- Circuit 80 80 11694 11695 Analog Input 864 R Degrees Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Current Angle- Circuit 81 81 11696 11697 Analog Input 865 R Degrees supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Current Angle- Circuit 82 82 11698 11699 Analog Input 866 R Degrees
Current Angle- Circuit 83 83 11700 11701 Analog Input 867 R Degrees
Meter Configuration
Current Angle- Circuit 84 84 11702 11703 Analog Input 868 R Degrees
Demand
Current #Angle-
of Sub-Intervals
Circuit 85 85 100 UINT16 11704 11705
Analog Value
Analog Input
1
869 R/W
R NV Degrees 1-6
Demand
CurrentSub-Interval
Angle- Circuit Length
86 86 101 UINT16 11706 11707 Analog
Analog Value
Input
2
870 R/W
R NV Seconds
Degrees 0, 10 - 32767 0 = Sync to Comms
Demand Time Stamp
Current Angle- Circuit (Year)
87 87 102 11708 11709 Analog Input 871 R
R Year
Degrees Years since 1900 (118 = 2018)
Demand
CurrentTime Stamp
Angle- (Month)
Circuit 88 88 103 11710 11711 Analog Input 872 R
R Month
Degrees 0 - 11 Month (0 = January)
Demand
Current Time
Angle- Stamp
Circuit(Day)
89 89 104 11712 11713 Analog Input 873 R Day
Degrees 1 - 31 Day of the Month
Demand Time
Current Stamp
Angle- (Weekday)
Circuit 90 90 105 11714 11715 Analog Input 874 R Weekday
Degrees 0-6 Weekday (1 = Monday)
CurrentTime
Demand Angle- Circuit
Stamp 91
(Hour) 91 106 11716 11717 Analog Input 875 R Degrees
Hour 0 - 23 Hour (13 = 1PM)
Current
Demand Angle-
Time Stamp Circuit 92
(Minute) 92 107 11718 11719 Analog Input 876 R Degrees
Minute 0 - 59 Minute
Current
Demand Angle-
Time Stamp Circuit 93
(Second) 93 108 11720 11721 Analog Input 877 R Degrees
Seconds 0 - 59 Second
Current Angle- Circuit 94 94 11722 11723 Analog Input 878 R Degrees Writing to RTC will disable NTP by clearing out URL and/or IP Address
Current Angle-
Real Time Clock Circuit
(Year)95 95 109 UINT16 11724 11725 Analog Input 879 R
R/W Degrees
Year Years since 1900 (118 = 2018)
Current
Real TimeAngle-
ClockCircuit
(Month) 96 96 110 UINT16 11726 11727 Analog Input 880 R
R/W Degrees
Month 0 - 11 Month (0 = January)
Device Object Local_Date
Real Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
Percent
Real Time ClockTHD(Weekday) 112 UINT16 11728 11919 Analog Input 681 - 976 R
R/W Percent
Weekday 0-6 Weekday (1 = Monday)
Percent
Real TimeTHD - Circuit
Clock (Hour) 1 1 113 UINT16 11728 11729 Analog Input 881 R
R/W Percent
Hour 0 - 23 Hour (13 = 1PM)
Percent
Real Time THD - Circuit
Clock (Min)2 2 114 UINT16 11730 11731 AnalogObject
Device Input Local_Time
882 R
R/W Percent
Minute 0 - 59 Minute
Percent
Real TimeTHDClock - Circuit
(Second)3 3 115 UINT16 11732 11733 Analog Input 883 R
R/W Percent
Seconds 0 - 59 Second
Percent
DigitalTHD - Circuit
Output #1 4 4 116 11734 11735 AnalogOutput
Binary Input 884
1 R
R/W Percent 0, 1
Percent
DigitalTHD - Circuit
Output #2 5 5 117 11736 11737 AnalogOutput
Binary Input 885
2 R
R/W Percent 0, 1
Percent THD -#1
Digital Input Circuit
State6 6 118 11738 11739 Analog Input
Binary Input 886
1 R Percent 0, 1
Percent THD -#2
Digital Input Circuit
State7 7 119 11740 11741 Analog Input
Binary Input 887
2 R Percent 0, 1
Percent THD
Modbus Slave- Circuit
Address8 8 124 UINT16 11742 11743 Analog Input 888 R
R/W NV Percent 1 - 254
Percent
Modbus THDTCP - Circuit
Port 9 9 125 UINT16 11744 11745 Analog Input 889 R NV Percent 502
PercentIPTHD - Circuit 10
Address 10 126 127 11746 11747 Analog Input 890 R
R/W NV Percent
Meter must be rebooted for new network settings to affect.
PercentGateway
THD - Circuit 11 11 128 129 11748 11749 Analog Input 891 R
R/W NV Percent
Device can be rebooted remotely using Global Reset/Command (Register 192)
Percent THDMask - Circuit 12 12 130 131 11750 11751 Analog Input 892 R
R/W NV Percent
Percent THD - Circuit 13 13 11752 11753 Analog Input 893 R Percent
Percent THD - Circuit 14 14 11754 11755 Analog Input 894 R Percent
Percent THD - Circuit 15 15 11756 11757 Analog Input 895 R Percent

UMG 804
31
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
MeterTHD
Percent Information
- Circuit 16 16 11758 11759 Analog Input 896 R Percent
Percent THD
Serial - Circuit 17
Number 17 1 2 UINT32 11760 11761 Device
AnalogObject
Input Serial_Number
897 R NV Percent
Percent THD - Version
Bootloader Circuit 18 18 3 UINT16 11762 11763 Analog Input 898 R NV Percent
Percent THD -Version
Firmware Circuit 19 19 4 UINT16 11764 11765 AnalogObject
Device Input 899
Firmware_Revision R NV Percent
PercentDevice
THD - Circuit
ID 20 20 5 UINT16 11766 11767 Analog Input 900 R
R/W NV Percent 15172, 22000 22000 = Janitza Pointmap
Percent
PowerTHD - Circuit 21
Up Counter 21 6 UINT16 11768 11769 Analog Input 901 R
R NV Percent
Percent Uptime
THD - Circuit 22 22 7 8 UINT32 11770 11771 Analog Input 902 R
R NV Percent
Seconds
Percent
SmartTHD - Circuit
Port ID #1 23 23 10 UINT16 11772 11773 Analog Input 903 R
R NV Percent
Percent THD - Circuit 24 24 11774 11775 Analog Input 904 R Percent
Smart Port ID #2 11 UINT16 R NV
Percent THD - Circuit 25 25 11776 11777 Analog Input 905 R Percent See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
Percent THD - Circuit 26 26 11778 11779 Analog Input 906 R Percent
Smart Port ID #4 13 UINT16 R NV
Percent THD - Circuit 27 27 11780 11781 Analog Input 907 R Percent
Smart Port #1 Serial Number 14 15 UINT32 R NV
Percent THD - Circuit 28 28 11782 11783 Analog Input 908 R Percent
Smart PortTHD
Percent #2 Serial Number
- Circuit 29 29 16 17 UINT32 11784 11785 Analog Input 909 R
R NV Percent
Smart PortTHD
Percent #3 Serial Number
- Circuit 30 30 18 19 UINT32 11786 11787 Analog Input 910 R
R NV Percent
Smart PortTHD
Percent #4 Serial Number
- Circuit 31 31 20 21 UINT32 11788 11789 Analog Input 911 R
R NV Percent
Smart Port #1
Percent THDFirmware
- CircuitVersion
32 32 22 UINT16 11790 11791 Analog Input 912 R NV Percent
Smart Port #2
Percent THDFirmware
- CircuitVersion
33 33 23 UINT16 11792 11793 Analog Input 913 R NV Percent
Smart Port #3
Percent THDFirmware
- CircuitVersion
34 34 24 UINT16 11794 11795 Analog Input 914 R NV Percent
Percent
Smart Port #4THD - CircuitVersion
Firmware 35 35 25 UINT16 11796 11797 Analog Input 915 R NV Percent
Percent
MAC THD -(Bit
Address Circuit 36
33-48) 36 26 11798 11799 Analog Input 916 R NV Percent
Percent
MAC THD -(Bit
Address Circuit 37
17-32) 37 27 11800 11801 Analog Input 917 R NV Percent
Percent THD - (Bit
MAC Address Circuit 38
1-16) 38 28 11802 11803 Analog Input 918 R
R NV Percent
Percent
Brand THD(16
Name - Circuit 39
Registers) 39 29 44 11804 11805 Analog Input 919 R
R NV Percent
Percent THD(16- Circuit 40 40 11806 11807 AnalogObject
Input 920 R Percent Brand Name, Model Name and Device Name
Model Name Register) 45 60 Device Model_Name R NV
Percent THD(16- Circuit 41 41 11808 11809 Analog Input 921 R Percent supports up to 32 characters (16 registers)
Device Name Registers) 61 76 Device Object Object_Name R/W NV
Percent THD - Circuit 42 42 11810 11811 Analog Input 922 R Percent
Percent THD - Circuit 43 43 11812 11813 Analog Input 923 R Percent
Meter Configuration
Percent THD - Circuit 44 44 11814 11815 Analog Input 924 R Percent
Demand # of Sub-Intervals 100 UINT16 Analog Value 1 R/W NV 1-6
Percent THD - Circuit 45 45 11816 11817 Analog Input 925 R Percent
Demand Sub-Interval Length 101 UINT16 Analog Value 2 R/W NV Seconds 0, 10 - 32767 0 = Sync to Comms
Percent THD - Circuit 46 46 11818 11819 Analog Input 926 R Percent
Demand
PercentTime
THD Stamp
- Circuit(Year)
47 47 102 11820 11821 Analog Input 927 R
R Year
Percent Years since 1900 (118 = 2018)
Demand
Percent Time
THDStamp
- Circuit(Month)
48 48 103 11822 11823 Analog Input 928 R
R Month
Percent 0 - 11 Month (0 = January)
Demand
PercentTime
THD Stamp
- Circuit(Day)
49 49 104 11824 11825 Analog Input 929 R
R Day
Percent 1 - 31 Day of the Month
Demand Time
Percent THDStamp (Weekday)
- Circuit 50 50 105 11826 11827 Analog Input 930 R Weekday
Percent 0-6 Weekday (1 = Monday)
Demand
PercentTime
THDStamp
- Circuit (Hour)
51 51 106 11828 11829 Analog Input 931 R Hour
Percent 0 - 23 Hour (13 = 1PM)
Demand
Percent Time
THDStamp
- Circuit(Minute)
52 52 107 11830 11831 Analog Input 932 R Minute
Percent 0 - 59 Minute
Percent
Demand THDStamp
Time - Circuit 53
(Second) 53 108 11832 11833 Analog Input 933 R Percent
Seconds 0 - 59 Second
Percent THD - Circuit 54 54 11834 11835 Analog Input 934 R Percent Writing to RTC will disable NTP by clearing out URL and/or IP Address
Percent
Real TimeTHD - Circuit
Clock (Year)55 55 109 UINT16 11836 11837 Analog Input 935 R
R/W Percent
Year Years since 1900 (118 = 2018)
Percent
Real TimeTHD - Circuit
Clock (Month) 56 56 110 UINT16 11838 11839 Analog Input 936 R
R/W Percent
Month 0 - 11 Month (0 = January)
Device Object Local_Date
Percent
Real TimeTHDClock
- Circuit
(Day)57 57 111 UINT16 11840 11841 Analog Input 937 R
R/W Percent
Day 1 - 31 Day of the Month
Percent
Real Time THD
Clock- Circuit
(Weekday) 58 58 112 UINT16 11842 11843 Analog Input 938 R
R/W Percent
Weekday 0-6 Weekday (1 = Monday)
Percent
Real TimeTHD - Circuit
Clock (Hour)59 59 113 UINT16 11844 11845 Analog Input 939 R
R/W Percent
Hour 0 - 23 Hour (13 = 1PM)
Percent
Real TimeTHDClock
- Circuit
(Min)60 60 114 UINT16 11846 11847 AnalogObject
Device Input 940
Local_Time R
R/W Percent
Minute 0 - 59 Minute
Percent
Real TimeTHD - Circuit
Clock (Second)61 61 115 UINT16 11848 11849 Analog Input 941 R
R/W Percent
Seconds 0 - 59 Second
Percent THD - Circuit 62 62 11850 11851 Analog Input 942 R Percent
Digital Output #1 116 Binary Output 1 R/W 0, 1
Percent THD - Circuit 63 63 11852 11853 Analog Input 943 R Percent
Digital Output #2 117 Binary Output 2 R/W 0, 1
Percent THD - Circuit 64 64 11854 11855 Analog Input 944 R Percent
Digital Input #1 State 118 Binary Input 1 R 0, 1
Percent THD - Circuit 65 65 11856 11857 Analog Input 945 R Percent
Digital Input #2 State 119 Binary Input 2 R 0, 1
Percent THD - Circuit 66 66 11858 11859 Analog Input 946 R Percent
ModbusTHD
Percent Slave Address
- Circuit 67 67 124 UINT16 11860 11861 Analog Input 947 R/W
R NV Percent 1 - 254
Modbus
Percent THDTCP Port 68
- Circuit 68 125 UINT16 11862 11863 Analog Input 948 R
R NV Percent 502
PercentIPTHD
Address
- Circuit 69 69 126 127 11864 11865 Analog Input 949 R/W
R NV Percent Meter must be rebooted for new network settings to affect.
PercentGateway
THD - Circuit 70 70 128 129 11866 11867 Analog Input 950 R/W
R NV Percent Device can be rebooted remotely using Global Reset/Command (Register 192)
Percent THDMask - Circuit 71 71 130 131 11868 11869 Analog Input 951 R/W
R NV Percent
Percent THD - Circuit 72 72 11870 11871 Analog Input 952 R Percent
Percent THD - Circuit 73 73 11872 11873 Analog Input 953 R Percent
Percent THD - Circuit 74 74 11874 11875 Analog Input 954 R Percent

UMG 804
32
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
MeterTHD
Percent Information
- Circuit 75 75 11876 11877 Analog Input 955 R Percent
Percent THD
Serial - Circuit 76
Number 76 1 2 UINT32 11878 11879 AnalogObject
Device Input 956
Serial_Number R NV Percent
Percent THD - Version
Bootloader Circuit 77 77 3 UINT16 11880 11881 Analog Input 957 R
R NV Percent
Percent THD -Version
Firmware Circuit 78 78 4 UINT16 11882 11883 AnalogObject
Device Input 958
Firmware_Revision R
R NV Percent
PercentDevice
THD - Circuit
ID 79 79 5 UINT16 11884 11885 Analog Input 959 R
R/W NV Percent 15172, 22000 22000 = Janitza Pointmap
Percent
PowerTHD Up -Counter
Circuit 80 80 6 UINT16 11886 11887 Analog Input 960 R
R NV Percent
Percent THD - Circuit 81 81 11888 11889 Analog Input 961 R Percent
Uptime 7 8 UINT32 R NV Seconds
Percent THD - Circuit 82 82 11890 11891 Analog Input 962 R Percent
Smart Port ID #1 10 UINT16 R NV
Percent THD - Circuit 83 83 11892 11893 Analog Input 963 R Percent
Smart Port ID #2 11 UINT16 R NV
Percent THD - Circuit 84 84 11894 11895 Analog Input 964 R Percent See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
Percent THD - Circuit 85 85 11896 11897 Analog Input 965 R Percent
Smart
Percent THDPort ID #4 86
- Circuit 86 13 UINT16 11898 11899 Analog Input 966 R
R NV Percent
Smart PortTHD
Percent #1 Serial Number
- Circuit 87 87 14 15 UINT32 11900 11901 Analog Input 967 R
R NV Percent
Smart PortTHD
Percent #2 Serial Number
- Circuit 88 88 16 17 UINT32 11902 11903 Analog Input 968 R
R NV Percent
Smart PortTHD
Percent #3 Serial Number
- Circuit 89 89 18 19 UINT32 11904 11905 Analog Input 969 R NV Percent
Smart PortTHD
Percent #4 Serial Number
- Circuit 90 90 20 21 UINT32 11906 11907 Analog Input 970 R NV Percent
Smart Port #1
Percent THDFirmware
- CircuitVersion
91 91 22 UINT16 11908 11909 Analog Input 971 R NV Percent
Smart Port #2
Percent THDFirmware
- CircuitVersion
92 92 23 UINT16 11910 11911 Analog Input 972 R NV Percent
Smart Port #3
Percent THDFirmware
- CircuitVersion
93 93 24 UINT16 11912 11913 Analog Input 973 R NV Percent
Smart Port #4
Percent THDFirmware
- CircuitVersion
94 94 25 UINT16 11914 11915 Analog Input 974 R NV Percent
MAC
PercentAddress
THD -(Bit 33-48)
Circuit 95 95 26 11916 11917 Analog Input 975 R NV Percent
MAC
PercentAddress
THD -(Bit 17-32)
Circuit 96 96 27 11918 11919 Analog Input 976 R NV Percent
MAC Address (Bit 1-16) 28 R NV
Brand Name (16 Registers)
Max Current 29 44 11920 12111 Analog Input 977 - 1072 R NV Amps
Brand Name, Model Name and Device Name
Model
Max Name
Current-(16Circuit
Register)
1 1 45 60 11920 11921 Device
AnalogObject
Input Model_Name
977 R NV Amps
supports up to 32 characters (16 registers)
Device
Max Name
Current-(16Circuit
Registers)
2 2 61 76 11922 11923 Device
AnalogObject
Input Object_Name
978 R/W
R NV Amps
Max Current- Circuit 3 3 11924 11925 Analog Input 979 R NV Amps
Meter Configuration
Max Current- Circuit 4 4 11926 11927 Analog Input 980 R NV Amps
Demand # of Sub-Intervals
Max Current- Circuit 5 5 100 UINT16 11928 11929 Analog Value
Input 1
981 R/W
R NV Amps 1-6
Max Current-
Demand Circuit
Sub-Interval 6
Length 6 101 UINT16 11930 11931 Analog Value
Input 2
982 R
R/W NV Amps
Seconds 0, 10 - 32767 0 = Sync to Comms
Max Current-
Demand Time StampCircuit 7
(Year) 7 102 11932 11933 Analog Input 983 R NV Amps
Year Years since 1900 (118 = 2018)
Max Current-
Demand Time Stamp Circuit 8
(Month) 8 103 11934 11935 Analog Input 984 R NV Amps
Month 0 - 11 Month (0 = January)
Max Current-
Demand Time StampCircuit(Day)
9 9 104 11936 11937 Analog Input 985 R
R NV Amps
Day 1 - 31 Day of the Month
Max Time
Demand Current-
StampCircuit 10
(Weekday) 10 105 11938 11939 Analog Input 986 R
R NV Amps
Weekday 0-6 Weekday (1 = Monday)
Max Current-
Demand Time StampCircuit(Hour)
11 11 106 11940 11941 Analog Input 987 R
R NV Amps
Hour 0 - 23 Hour (13 = 1PM)
Max Current-
Demand Time Stamp Circuit 12
(Minute) 12 107 11942 11943 Analog Input 988 R
R NV Amps
Minute 0 - 59 Minute
Max Current- Circuit 13 13 11944 11945 Analog Input 989 R NV Amps
Demand Time Stamp (Second) 108 R Seconds 0 - 59 Second
Max Current- Circuit 14 14 11946 11947 Analog Input 990 R NV Amps
Writing to RTC will disable NTP by clearing out URL and/or IP Address
Max Current- Circuit 15 15 11948 11949 Analog Input 991 R NV Amps
Real Time Clock (Year) 109 UINT16 R/W Year Years since 1900 (118 = 2018)
Max Current- Circuit 16 16 11950 11951 Analog Input 992 R NV Amps
Real Time Clock (Month) 110 UINT16 R/W Month 0 - 11 Month (0 = January)
Max Current- Circuit 17 17 11952 11953 AnalogObject
Device Input 993
Local_Date R NV Amps
Real Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
Max Current- Circuit 18 18 11954 11955 Analog Input 994 R NV Amps
Real
MaxTime Clock Circuit
Current- (Weekday) 19 19 112 UINT16 11956 11957 Analog Input 995 R/W
R NV Weekday
Amps 0-6 Weekday (1 = Monday)
Real Current-
Max Time Clock (Hour)
Circuit 20 20 113 UINT16 11958 11959 Analog Input 996 R/W
R NV Hour
Amps 0 - 23 Hour (13 = 1PM)
Real Time Clock
Max Current- Circuit 21(Min) 21 114 UINT16 11960 11961 Device
AnalogObject
Input
Local_Time
997 R/W
R NV Minute
Amps 0 - 59 Minute
Real Time Clock (Second)
Max Current- Circuit 22 22 115 UINT16 11962 11963 Analog Input 998 R/W
R NV Seconds
Amps 0 - 59 Second
MaxDigital Output
Current- #1 23
Circuit 23 116 11964 11965 Binary
AnalogOutput
Input 1
999 R/W
R NV Amps 0, 1
MaxDigital Output
Current- #2 24
Circuit 24 117 11966 11967 Binary
AnalogOutput
Input 2
1000 R/W
R NV Amps 0, 1
Digital
Max Input Circuit
Current- #1 State 25 25 118 11968 11969 Binary Input
Analog Input 1
1001 R NV Amps 0, 1
Max Current-
Digital Input Circuit
#2 State 26 26 119 11970 11971 Binary Input
Analog Input 2
1002 R NV Amps 0, 1
Max
ModbusCurrent-
SlaveCircuit
Address 27 27 124 UINT16 11972 11973 Analog Input 1003 R
R/W NV Amps 1 - 254
Max Current-
Modbus TCPCircuit
Port 28 28 125 UINT16 11974 11975 Analog Input 1004 R NV Amps 502
Max Current-
IP AddressCircuit 29 29 126 127 11976 11977 Analog Input 1005 R
R/W NV
NV Amps
Max Current- Circuit 30 30 11978 11979 Analog Input 1006 R NV Amps Meter must be rebooted for new network settings to affect.
Gateway 128 129 R/W NV
Max Current- Device can be rebooted remotely using Global Reset/Command (Register 192)
MaskCircuit 31 31 130 131 11980 11981 Analog Input 1007 R
R/W NV
NV Amps
Max Current- Circuit 32 32 11982 11983 Analog Input 1008 R NV Amps
Max Current- Circuit 33 33 11984 11985 Analog Input 1009 R NV Amps
Max Current- Circuit 34 34 11986 11987 Analog Input 1010 R NV Amps

UMG 804
33
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Max
MeterCurrent- Circuit 35
Information 35 11988 11989 Analog Input 1011 R NV Amps
Max Serial
Current- Circuit 36
Number 36 1 2 UINT32 11990 11991 AnalogObject
Device Input 1012
Serial_Number R
R NV
NV Amps
Max Current- Version
Bootloader Circuit 37 37 3 UINT16 11992 11993 Analog Input 1013 R
R NV
NV Amps
Max Current-Version
Firmware Circuit 38 38 4 UINT16 11994 11995 AnalogObject
Device Input 1014
Firmware_Revision R
R NV
NV Amps
Max Current-
Device Circuit
ID 39 39 5 UINT16 11996 11997 Analog Input 1015 R
R/W NV
NV Amps 15172, 22000 22000 = Janitza Pointmap
Max Current- Circuit 40 40 11998 11999 Analog Input 1016 R NV Amps
Power Up Counter 6 UINT16 R NV
Max Current- Circuit 41 41 12000 12001 Analog Input 1017 R NV Amps
Uptime 7 8 UINT32 R NV Seconds
Max Current- Circuit 42 42 12002 12003 Analog Input 1018 R NV Amps
Smart Port ID #1 10 UINT16 R NV
Max Current- Circuit 43 43 12004 12005 Analog Input 1019 R NV Amps
Smart Port ID #2 11 UINT16 R NV
Max Current- Circuit 44 44 12006 12007 Analog Input 1020 R NV Amps See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
MaxSmart PortCircuit
Current- ID #3 45 45 12 UINT16 12008 12009 Analog Input 1021
R
R NV
NV Amps
MaxSmart PortCircuit
Current- ID #4 46 46 13 UINT16 12010 12011 Analog Input 1022 R
R NV
NV Amps
Smart
MaxPort #1 Serial
Current- Number
Circuit 47 47 14 15 UINT32 12012 12013 Analog Input 1023 R
R NV
NV Amps
Smart
MaxPort #2 Serial
Current- Number
Circuit 48 48 16 17 UINT32 12014 12015 Analog Input 1024 R
R NV
NV Amps
Smart
MaxPort #3 Serial
Current- Number
Circuit 49 49 18 19 UINT32 12016 12017 Analog Input 1025 R NV Amps
Smart
MaxPort #4 Serial
Current- Number
Circuit 50 50 20 21 UINT32 12018 12019 Analog Input 1026 R NV Amps
Smart Port
Max #1 Firmware
Current- CircuitVersion
51 51 22 UINT16 12020 12021 Analog Input 1027 R NV Amps
SmartMax
PortCurrent- CircuitVersion
#2 Firmware 52 52 23 UINT16 12022 12023 Analog Input 1028 R NV Amps
SmartMax
PortCurrent- CircuitVersion
#3 Firmware 53 53 24 UINT16 12024 12025 Analog Input 1029 R NV Amps
SmartMax
PortCurrent- CircuitVersion
#4 Firmware 54 54 25 UINT16 12026 12027 Analog Input 1030 R
R NV
NV Amps
Max Address
MAC Current- (Bit
Circuit 55
33-48) 55 26 12028 12029 Analog Input 1031 R
R NV
NV Amps
Max Address
MAC Current- (Bit
Circuit 56
17-32) 56 27 12030 12031 Analog Input 1032 R
R NV
NV Amps
Max
MACCurrent-
Address Circuit 57
(Bit 1-16) 57 28 12032 12033 Analog Input 1033 R
R NV
NV Amps
Max Current- Circuit 58 58 12034 12035 Analog Input 1034 R NV Amps
Brand Name (16 Registers) 29 44 R NV
Max Current- Circuit 59 59 12036 12037 Analog Input 1035 R NV Amps Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Max Current- Circuit 60 60 12038 12039 Analog Input 1036 R NV Amps supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Max Current- Circuit 61 61 12040 12041 Analog Input 1037 R NV Amps
Max Current- Circuit 62 62 12042 12043 Analog Input 1038 R NV Amps
Meter
Max Configuration
Current- Circuit 63 63 12044 12045 Analog Input 1039 R NV Amps
Demand # of Sub-Intervals
Max Current- Circuit 64 64 100 UINT16 12046 12047 Analog Value
Analog Input
1
1040 R/W
R NV
NV Amps 1-6
Demand
Max Current- CircuitLength
Sub-Interval 65 65 101 UINT16 12048 12049 Analog
Analog Value
Input 2
1041 R/W
R NV
NV Seconds
Amps 0, 10 - 32767 0 = Sync to Comms
Demand
Max Current- Circuit(Year)
Time Stamp 66 66 102 12050 12051 Analog Input 1042 R
R NV Year
Amps Years since 1900 (118 = 2018)
Demand Time Stamp
Max Current- Circuit(Month)
67 67 103 12052 12053 Analog Input 1043 R NV Month
Amps 0 - 11 Month (0 = January)
Demand Time Stamp
Max Current- Circuit(Day)
68 68 104 12054 12055 Analog Input 1044 R NV Day
Amps 1 - 31 Day of the Month
Demand
Max Time Stamp
Current- (Weekday)
Circuit 69 69 105 12056 12057 Analog Input 1045 R NV Weekday
Amps 0-6 Weekday (1 = Monday)
Max Current-
Demand Circuit(Hour)
Time Stamp 70 70 106 12058 12059 Analog Input 1046 R NV Amps
Hour 0 - 23 Hour (13 = 1PM)
Max Current-
Demand Time StampCircuit 71
(Minute) 71 107 12060 12061 Analog Input 1047 R NV Amps
Minute 0 - 59 Minute
Max Current-
Demand Time StampCircuit 72
(Second) 72 108 12062 12063 Analog Input 1048 R
R NV Amps
Seconds 0 - 59 Second
Max Current- Circuit 73 73 12064 12065 Analog Input 1049 R NV Amps Writing to RTC will disable NTP by clearing out URL and/or IP Address
Max
Real Current-
Time ClockCircuit 74
(Year) 74 109 UINT16 12066 12067 Analog Input 1050 R
R/W NV Amps
Year Years since 1900 (118 = 2018)
MaxTime
Real Current- Circuit
Clock (Month)75 75 110 UINT16 12068 12069 Analog Input 1051 R
R/W NV Amps
Month 0 - 11 Month (0 = January)
Max Device
AnalogObject Local_Date
RealCurrent- Circuit 76 76 12070 12071 R NV Amps
Input 1052
Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
Max Current- Circuit 77 77 12072 12073 Analog Input 1053 R NV Amps
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
Max Current- Circuit 78 78 12074 12075 Analog Input 1054 R NV Amps
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
Max Current- Circuit 79 79 12076 12077 Analog Input 1055 R NV Amps
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Max Current- Circuit 80 80 12078 12079 Analog Input 1056 R NV Amps
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Max Current- Circuit 81 81 12080 12081 Analog Input 1057 R NV Amps
Digital Output #1 116 Binary Output 1 R/W 0, 1
Max Current- Circuit 82 82 12082 12083 Analog Input 1058 R NV Amps
MaxDigital Output
Current- #2 83
Circuit 83 117 12084 12085
Binary Output
Analog Input
2
1059
R/W
R NV Amps 0, 1
Digital
Max Input Circuit
Current- #1 State 84 84 118 12086 12087 Binary Input
Analog Input
1
1060 R
R NV Amps 0, 1
Digital
Max Input Circuit
Current- #2 State 85 85 119 12088 12089 Binary Input
Analog Input 2
1061 R
R NV Amps 0, 1
Modbus Slave Address
Max Current- Circuit 86 86 124 UINT16 12090 12091 Analog Input 1062 R/W
R NV
NV Amps 1 - 254
Modbus TCP Port
Max Current- Circuit 87 87 125 UINT16 12092 12093 Analog Input 1063 R
R NV
NV Amps 502
IP Address
Max Current- Circuit 88 88 126 127 12094 12095 Analog Input 1064 R/W
R NV
NV Amps Meter must be rebooted for new network settings to affect.
Gateway
Max Current- Circuit 89 89 128 129 12096 12097 Analog Input 1065 R/W
R NV
NV Amps Device can be rebooted remotely using Global Reset/Command (Register 192)
MaskCircuit 90
Max Current- 90 130 131 12098 12099 Analog Input 1066 R/W
R NV
NV Amps
Max Current- Circuit 91 91 12100 12101 Analog Input 1067 R NV Amps
Max Current- Circuit 92 92 12102 12103 Analog Input 1068 R NV Amps
Max Current- Circuit 93 93 12104 12105 Analog Input 1069 R NV Amps

UMG 804
34
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter
Max Information
Current- Circuit 94 94 12106 12107 Analog Input 1070 R NV Amps
MaxSerial
Current- Circuit 95
Number 95 1 2 UINT32 12108 12109 AnalogObject
Device Input 1071
Serial_Number R NV Amps
Max Current- Version
Bootloader Circuit 96 96 3 UINT16 12110 12111 Analog Input 1072 R NV Amps
Firmware Version 4 UINT16 Device Object Firmware_Revision R NV
Max kW
Device ID 5 UINT16 12112 12303 Analog Input 1073 - 1068 R
R/W NV kW 15172, 22000 22000 = Janitza Pointmap
Max kW-
Power Up Circuit
Counter 1 1 6 UINT16 12112 12113 Analog Input 1073 R NV kW
Max kW-
UptimeCircuit 2 2 7 8 UINT32 12114 12115 Analog Input 1074 R NV kW
Seconds
Max
Smart kW- Circuit
Port ID #13 3 10 UINT16 12116 12117 Analog Input 1075 R NV kW
Max
Smart kW- Circuit
Port ID #24 4 11 UINT16 12118 12119 Analog Input 1076 R NV kW
See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Max
Smart kW- Circuit
Port ID #35 5 12 UINT16 12120 12121 Analog Input 1077 R NV kW
Max
Smart kW- Circuit
Port ID #46 6 13 UINT16 12122 12123 Analog Input 1078 R
R NV
NV kW
SmartMaxPortkW- CircuitNumber
#1 Serial 7 7 14 15 UINT32 12124 12125 Analog Input 1079 R
R NV
NV kW
SmartMaxPortkW- CircuitNumber
#2 Serial 8 8 16 17 UINT32 12126 12127 Analog Input 1080 R
R NV
NV kW
SmartMaxPortkW- CircuitNumber
9 9 12128 12129 R NV kW
Analog Input 1081
#3 Serial 18 19 UINT32 R NV
Max kW- Circuit 10 10 12130 12131 Analog Input 1082 R NV kW
Smart Port #4 Serial Number 20 21 UINT32 R NV
Max kW- Circuit 11 11 12132 12133 Analog Input 1083 R NV kW
Smart Port #1 Firmware Version 22 UINT16 R NV
Max kW- Circuit 12 12 12134 12135 Analog Input 1084 R NV kW
Smart Port #2 Firmware Version 23 UINT16 R NV
Max kW- Circuit 13 13 12136 12137 Analog Input 1085 R NV kW
Smart Port #3 Firmware Version 24 UINT16 R NV
Max kW- Circuit 14 14 12138 12139 Analog Input 1086 R NV kW
Smart Max
Port #4
kW-Firmware
Circuit 15Version 15 25 UINT16 12140 12141 Analog Input 1087 R
R NV
NV kW
MACMaxAddress (Bit 33-48)
kW- Circuit 16 16 26 12142 12143 Analog Input 1088 R
R NV
NV kW
MACMaxAddress (Bit 17-32)
kW- Circuit 17 17 27 12144 12145 Analog Input 1089 R
R NV
NV kW
MAC
MaxAddress (Bit 1-16)
kW- Circuit 18 18 28 12146 12147 Analog Input 1090 R NV kW
Brand
MaxName
kW- (16 Registers)
Circuit 19 19 29 44 12148 12149 Analog Input 1091 R NV kW
Brand Name, Model Name and Device Name
Model
MaxName (16 Register)
kW- Circuit 20 20 45 60 12150 12151 Device
AnalogObject
Input Model_Name
1092 R NV kW
supports up to 32 characters (16 registers)
Max
Device kW- (16
Name Circuit 21
Registers) 21 61 76 12152 12153 Device
AnalogObject
Input Object_Name
1093 R
R/W NV kW
Max kW- Circuit 22 22 12154 12155 Analog Input 1094 R NV kW
Max kW-
Meter Circuit 23
Configuration 23 12156 12157 Analog Input 1095 R NV kW
Max kW-
Demand # of Circuit 24
Sub-Intervals 24 100 UINT16 12158 12159 Analog Value
Analog Input 1096
1 R
R/W NV
NV kW 1-6
MaxSub-Interval
Demand kW- Circuit 25 Length 25 101 UINT16 12160 12161 Analog Value
Analog Input 1097
2 R
R/W NV
NV kW
Seconds 0, 10 - 32767 0 = Sync to Comms
Max Time
Demand kW- Circuit
Stamp26 (Year) 26 102 12162 12163 Analog Input 1098 R
R NV kW
Year Years since 1900 (118 = 2018)
DemandMaxTime
kW-Stamp
Circuit(Month)
27 27 103 12164 12165 Analog Input 1099 R
R NV kW
Month 0 - 11 Month (0 = January)
Max kW- Circuit 28 28 12166 12167 Analog Input 1100 R NV kW
Demand Time Stamp (Day) 104 R Day 1 - 31 Day of the Month
Max kW- Circuit 29 29 12168 12169 Analog Input 1101 R NV kW
Demand Time Stamp (Weekday) 105 R Weekday 0-6 Weekday (1 = Monday)
Max kW- Circuit 30 30 12170 12171 Analog Input 1102 R NV kW
Demand Time Stamp (Hour) 106 R Hour 0 - 23 Hour (13 = 1PM)
Max kW- Circuit 31 31 12172 12173 Analog Input 1103 R NV kW
Demand Time Stamp (Minute) 107 R Minute 0 - 59 Minute
Max kW- Circuit 32 32 12174 12175 Analog Input 1104 R NV kW
DemandMaxTime
kW-Stamp
Circuit(Second)
33 33 108 12176 12177 Analog Input 1105 R
R NV Seconds
kW 0 - 59 Second
Max kW- Circuit 34 34 12178 12179 Analog Input 1106 R NV kW Writing to RTC will disable NTP by clearing out URL and/or IP Address
Real
MaxTime
kW-Clock
Circuit (Year)
35 35 109 UINT16 12180 12181 Analog Input 1107 R/W
R NV Year
kW Years since 1900 (118 = 2018)
Real
MaxTime
kW- Clock (Month)
Circuit 36 36 110 UINT16 12182 12183 AnalogObject
Input 1108 R/W
R NV Month
kW 0 - 11 Month (0 = January)
Device Local_Date
Real
MaxTime
kW-Clock
Circuit(Day)
37 37 111 UINT16 12184 12185 Analog Input 1109 R/W
R NV Day
kW 1 - 31 Day of the Month
RealMax
TimekW-Clock (Weekday)
Circuit 38 38 112 UINT16 12186 12187 Analog Input 1110 R/W
R NV Weekday
kW 0-6 Weekday (1 = Monday)
Real
Max Time
kW-Clock
Circuit(Hour)
39 39 113 UINT16 12188 12189 Analog Input 1111 R/W
R NV Hour
kW 0 - 23 Hour (13 = 1PM)
Real
MaxTime
kW-Clock
Circuit(Min)
40 40 114 UINT16 12190 12191 Device
AnalogObject
Input Local_Time
1112 R/W
R NV Minute
kW 0 - 59 Minute
Max
Real TimekW- Circuit
Clock 41
(Second) 41 115 UINT16 12192 12193 Analog Input 1113 R
R/W NV kW
Seconds 0 - 59 Second
Max kW-Output
Digital Circuit#1 42 42 116 12194 12195 AnalogOutput
Binary Input 1114
1 R
R/W NV kW 0, 1
Max kW-Output
Digital Circuit#2 43 43 117 12196 12197 AnalogOutput
Binary Input 1115
2 R
R/W NV kW 0, 1
Max kW-
Digital InputCircuit 44
#1 State 44 118 12198 12199 Analog Input
Binary Input 1116
1 R
R NV kW 0, 1
Max kW-
Digital InputCircuit 45
#2 State 45 119 12200 12201 Analog Input
Binary Input 1117
2 R
R NV kW 0, 1
Max kW-
Modbus Circuit
Slave 46
Address 46 124 UINT16 12202 12203 Analog Input 1118 R
R/W NV
NV kW 1 - 254
Max kW- TCP
Modbus Circuit 47
Port 47 125 UINT16 12204 12205 Analog Input 1119 R
R NV
NV kW 502
Max kW- Circuit 48 48 12206 12207 Analog Input 1120 R NV kW
IP Address 126 127 R/W NV
Max kW- Circuit 49 49 12208 12209 Analog Input 1121 R NV kW Meter must be rebooted for new network settings to affect.
Gateway 128 129 R/W NV
Max kW- Circuit 50 50 12210 12211 Analog Input 1122 R NV kW Device can be rebooted remotely using Global Reset/Command (Register 192)
Mask 130 131 R/W NV
Max kW- Circuit 51 51 12212 12213 Analog Input 1123 R NV kW
Max kW- Circuit 52 52 12214 12215 Analog Input 1124 R NV kW
Max kW- Circuit 53 53 12216 12217 Analog Input 1125 R NV kW
Max kW- Circuit 54 54 12218 12219 Analog Input 1126 R NV kW

UMG 804
35
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter Information
Max kW- Circuit 55 55 12220 12221 Analog Input 1127 R NV kW
Max kW-Number
Serial Circuit 56 56 1 2 UINT32 12222 12223 AnalogObject
Device Input 1128
Serial_Number R NV kW
Max kW- Circuit
Bootloader Version57 57 3 UINT16 12224 12225 Analog Input 1129 R
R NV
NV kW
Max kW- Circuit
Firmware Version 58 58 4 UINT16 12226 12227 AnalogObject
Device Input 1130
Firmware_Revision R
R NV
NV kW
Max Device
kW- Circuit
ID 59 59 5 UINT16 12228 12229 Analog Input 1131 R
R/W NV
NV kW 15172, 22000 22000 = Janitza Pointmap
Max
Power kW-UpCircuit
Counter 60 60 6 UINT16 12230 12231 Analog Input 1132 R
R NV
NV kW
Max kW- Circuit 61 61 12232 12233 Analog Input 1133 R NV kW
Uptime 7 8 UINT32 R NV Seconds
Max kW- Circuit 62 62 12234 12235 Analog Input 1134 R NV kW
Smart Port ID #1 10 UINT16 R NV
Max kW- Circuit 63 63 12236 12237 Analog Input 1135 R NV kW
Smart Port ID #2 11 UINT16 R NV
Max kW- Circuit 64 64 12238 12239 Analog Input 1136 R NV kW See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
Max kW- Circuit 65 65 12240 12241 Analog Input 1137 R NV kW
Smart
Max kW-Port ID #466
Circuit 66 13 UINT16 12242 12243 Analog Input 1138 R
R NV
NV kW
SmartMaxPortkW-
#1 Serial
CircuitNumber
67 67 14 15 UINT32 12244 12245 Analog Input 1139 R
R NV
NV kW
SmartMaxPortkW-
#2 Serial
CircuitNumber
68 68 16 17 UINT32 12246 12247 Analog Input 1140 R
R NV
NV kW
SmartMaxPortkW-
#3 Serial
CircuitNumber
69 69 18 19 UINT32 12248 12249 Analog Input 1141 R NV kW
SmartMaxPortkW-
#4 Serial
CircuitNumber
70 70 20 21 UINT32 12250 12251 Analog Input 1142 R NV kW
Smart Max
Port #1
kW-Firmware
Circuit 71Version 71 22 UINT16 12252 12253 Analog Input 1143 R NV kW
Smart Max kW-Firmware
Port #2 Circuit 72Version 72 23 UINT16 12254 12255 Analog Input 1144 R NV kW
Smart Max kW-Firmware
Port #3 Circuit 73Version 73 24 UINT16 12256 12257 Analog Input 1145 R NV kW
Smart Max kW-Firmware
Port #4 Circuit 74Version 74 25 UINT16 12258 12259 Analog Input 1146 R NV kW
MACMax kW- Circuit
Address 75
(Bit 33-48) 75 26 12260 12261 Analog Input 1147 R
R NV
NV kW
MACMax kW- Circuit
Address 76
(Bit 17-32) 76 27 12262 12263 Analog Input 1148 R
R NV
NV kW
MaxAddress
MAC kW- Circuit 77
(Bit 1-16) 77 28 12264 12265 Analog Input 1149 R
R NV
NV kW
Max
Brand kW- (16
Name Circuit 78
Registers) 78 29 44 12266 12267 Analog Input 1150 R
R NV
NV kW
Max kW- Circuit 79 79 12268 12269 Analog Input 1151 R NV kW Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Max kW- Circuit 80 80 12270 12271 Analog Input 1152 R NV kW supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Max kW- Circuit 81 81 12272 12273 Analog Input 1153 R NV kW
Max kW- Circuit 82 82 12274 12275 Analog Input 1154 R NV kW
Meter Configuration
Max kW- Circuit 83 83 12276 12277 Analog Input 1155 R NV kW
Demand # of Sub-Intervals 100 UINT16 Analog Value 1 R/W NV 1-6
Max kW- Circuit 84 84 12278 12279 Analog Input 1156 R NV kW
Demand Sub-Interval Length 101 UINT16 Analog Value 2 R/W NV Seconds 0, 10 - 32767 0 = Sync to Comms
Max kW- Circuit 85 85 12280 12281 Analog Input 1157 R NV kW
Demand Time Stamp (Year) 102 R Year Years since 1900 (118 = 2018)
Max kW- Circuit 86 86 12282 12283 Analog Input 1158 R NV kW
Demand Time Stamp (Month) 103 R Month 0 - 11 Month (0 = January)
Max kW- Circuit 87 87 12284 12285 Analog Input 1159 R NV kW
Demand Time Stamp (Day) 104 R Day 1 - 31 Day of the Month
Max kW- Circuit 88 88 12286 12287 Analog Input 1160 R NV kW
Demand Time Stamp (Weekday) 105 R Weekday 0-6 Weekday (1 = Monday)
Max kW- Circuit 89 89 12288 12289 Analog Input 1161 R NV kW
Demand Time Stamp (Hour) 106 R Hour 0 - 23 Hour (13 = 1PM)
Max kW- Circuit 90 90 12290 12291 Analog Input 1162 R NV kW
Demand Time Stamp (Minute) 107 R Minute 0 - 59 Minute
Max kW- Circuit 91 91 12292 12293 Analog Input 1163 R NV kW
Demand Time Stamp (Second) 108 R Seconds 0 - 59 Second
Max kW- Circuit 92 92 12294 12295 Analog Input 1164 R NV kW
Writing to RTC will disable NTP by clearing out URL and/or IP Address
Max kW- Circuit 93 93 12296 12297 Analog Input 1165 R NV kW
Real Time Clock (Year) 109 UINT16 R/W Year Years since 1900 (118 = 2018)
Max kW- Circuit 94 94 12298 12299 Analog Input 1166 R NV kW
Real Time Clock (Month) 110 UINT16 R/W Month 0 - 11 Month (0 = January)
Max kW- Circuit 95 95 12300 12301 AnalogObject
Device Input 1167
Local_Date R NV kW
Real Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
Max kW- Circuit 96 96 12302 12303 Analog Input 1168 R NV kW
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
Current Demand 12304 12495 Analog Input 1169 - 1264 R Amps
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Current Demand- Circuit 1 1 12304 12305 Analog Input 1169 R Amps
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Current Demand- Circuit 2 2 12306 12307 Analog Input 1170 R Amps
Digital Output #1 116 Binary Output 1 R/W 0, 1
Current Demand- Circuit 3 3 12308 12309 Analog Input 1171 R Amps
Digital
Current OutputCircuit
Demand- #2 4 4 117 12310 12311
Binary Output
Analog Input
2
1172 R/W
R Amps 0, 1
DigitalDemand-
Current Input #1Circuit
State 5 5 118 12312 12313 Binary Input
Analog Input
1
1173 R
R Amps 0, 1
DigitalDemand-
Current Input #2Circuit
State 6 6 119 12314 12315 Binary Input
Analog Input 2
1174 R
R Amps 0, 1
Modbus
Current Slave Address
Demand- Circuit 7 7 124 UINT16 12316 12317 Analog Input 1175 R/W
R NV Amps 1 - 254
Modbus
Current TCP Port
Demand- Circuit 8 8 125 UINT16 12318 12319 Analog Input 1176 R NV Amps 502
Current IP AddressCircuit 9
Demand- 9 126 127 12320 12321 Analog Input 1177 R/W
R NV Amps
Meter must be rebooted for new network settings to affect.
Current Demand-
GatewayCircuit 10 10 128 129 12322 12323 Analog Input 1178 R
R/W NV Amps
Device can be rebooted remotely using Global Reset/Command (Register 192)
Current Demand-
Mask Circuit 11 11 130 131 12324 12325 Analog Input 1179 R
R/W NV Amps
Current Demand- Circuit 12 12 12326 12327 Analog Input 1180 R Amps
Current Demand- Circuit 13 13 12328 12329 Analog Input 1181 R Amps
Current Demand- Circuit 14 14 12330 12331 Analog Input 1182 R Amps

UMG 804
36
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter
Current Information
Demand- Circuit 15 15 12332 12333 Analog Input 1183 R Amps
CurrentSerial
Demand-NumberCircuit 16 16 1 2 UINT32 12334 12335 AnalogObject
Device Input 1184
Serial_Number R NV Amps
Current Demand-
Bootloader Circuit 17
Version 17 3 UINT16 12336 12337 Analog Input 1185 R NV Amps
Current Demand-
Firmware Circuit 18
Version 18 4 UINT16 12338 12339 AnalogObject
Device Input 1186
Firmware_Revision R
R NV Amps
Current Demand-
Device IDCircuit 19 19 5 UINT16 12340 12341 Analog Input 1187 R
R/W NV Amps 15172, 22000 22000 = Janitza Pointmap
Current Demand-
Power Circuit 20
Up Counter 20 6 UINT16 12342 12343 Analog Input 1188 R
R NV Amps
Current Demand-
Uptime Circuit 21 21 7 8 UINT32 12344 12345 Analog Input 1189 R
R NV Amps
Seconds
Current Demand- Circuit 22 22 12346 12347 Analog Input 1190 R Amps
Smart Port ID #1 10 UINT16 R NV
Current Demand- Circuit 23 23 12348 12349 Analog Input 1191 R Amps
Smart Port ID #2 11 UINT16 R NV
Current Demand- Circuit 24 24 12350 12351 Analog Input 1192 R Amps See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
Current Demand- Circuit 25 25 12352 12353 Analog Input 1193 R Amps
Smart Port ID #4 13 UINT16 R NV
Current Demand- Circuit 26 26 12354 12355 Analog Input 1194 R Amps
Smart
CurrentPort #1 Serial
Demand- Number
Circuit 27 27 14 15 UINT32 12356 12357 Analog Input 1195 R
R NV Amps
Smart
CurrentPort #2 Serial
Demand- Number
Circuit 28 28 16 17 UINT32 12358 12359 Analog Input 1196 R
R NV Amps
Smart
CurrentPort #3 Serial
Demand- Number
Circuit 29 29 18 19 UINT32 12360 12361 Analog Input 1197 R
R NV Amps
Smart
CurrentPort #4 Serial
Demand- Number
Circuit 30 30 20 21 UINT32 12362 12363 Analog Input 1198 R NV Amps
Smart PortDemand-
Current #1 FirmwareCircuit Version
31 31 22 UINT16 12364 12365 Analog Input 1199 R NV Amps
Smart PortDemand-
Current #2 FirmwareCircuit Version
32 32 23 UINT16 12366 12367 Analog Input 1200 R NV Amps
Current
Smart PortDemand-
#3 FirmwareCircuit 33
Version 33 24 UINT16 12368 12369 Analog Input 1201 R NV Amps
Current
Smart PortDemand-
#4 FirmwareCircuit 34
Version 34 25 UINT16 12370 12371 Analog Input 1202 R NV Amps
Current Demand-
MAC Address (BitCircuit
33-48)35 35 26 12372 12373 Analog Input 1203 R NV Amps
Current Demand-
MAC Address (BitCircuit
17-32)36 36 27 12374 12375 Analog Input 1204 R
R NV Amps
Current Demand-
MAC Address Circuit
(Bit 1-16)37 37 28 12376 12377 Analog Input 1205 R
R NV Amps
Current Demand-
Brand Name Circuit 38
(16 Registers) 38 29 44 12378 12379 Analog Input 1206 R
R NV Amps
Current Demand- Circuit 39 39 12380 12381 Analog Input 1207 R Amps Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Current Demand- Circuit 40 40 12382 12383 Analog Input 1208 R Amps supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Current Demand- Circuit 41 41 12384 12385 Analog Input 1209 R Amps
Current Demand- Circuit 42 42 12386 12387 Analog Input 1210 R Amps
Meter Configuration
Current Demand- Circuit 43 43 12388 12389 Analog Input 1211 R Amps
Demand # of Sub-Intervals 100 UINT16 Analog Value 1 R/W NV 1-6
Current Demand- Circuit 44 44 12390 12391 Analog Input 1212 R Amps
Demand Sub-Interval
Current Demand- Length
Circuit 45 45 101 UINT16 12392 12393
Analog Value
Analog Input
2
1213 R/W
R NV Seconds
Amps 0, 10 - 32767 0 = Sync to Comms
Demand Time Stamp
Current Demand- Circuit(Year)
46 46 102 12394 12395 Analog Input 1214 R
R Year
Amps Years since 1900 (118 = 2018)
Demand
Current Time
Demand-Stamp (Month)
Circuit 47 47 103 12396 12397 Analog Input 1215 R
R Month
Amps 0 - 11 Month (0 = January)
DemandDemand-
Current Time Stamp Circuit(Day)
48 48 104 12398 12399 Analog Input 1216 R Day
Amps 1 - 31 Day of the Month
Demand
CurrentTime StampCircuit
Demand- (Weekday)
49 49 105 12400 12401 Analog Input 1217 R Weekday
Amps 0-6 Weekday (1 = Monday)
Demand Time Stamp
Current Demand- (Hour)
Circuit 50 50 106 12402 12403 Analog Input 1218 R Hour
Amps 0 - 23 Hour (13 = 1PM)
CurrentTime
Demand Demand-Stamp Circuit 51
(Minute) 51 107 12404 12405 Analog Input 1219 R Amps
Minute 0 - 59 Minute
CurrentTime
Demand Demand-Stamp Circuit 52
(Second) 52 108 12406 12407 Analog Input 1220 R Amps
Seconds 0 - 59 Second
Current Demand- Circuit 53 53 12408 12409 Analog Input 1221 R Amps Writing to RTC will disable NTP by clearing out URL and/or IP Address
Current Demand-
Real Time ClockCircuit
(Year) 54 54 109 UINT16 12410 12411 Analog Input 1222 R
R/W Amps
Year Years since 1900 (118 = 2018)
Current Demand-
Real Time Circuit 55
Clock (Month) 55 110 UINT16 12412 12413 Analog Input 1223 R
R/W Amps
Month 0 - 11 Month (0 = January)
Device
AnalogObject
Local_Date
Current Demand-
Real Time ClockCircuit
(Day) 56 56 111 UINT16 12414 12415 Input 1224 R
R/W Amps
Day 1 - 31 Day of the Month
Current Demand-
Real Time Circuit 57
Clock (Weekday) 57 112 UINT16 12416 12417 Analog Input 1225 R
R/W Amps
Weekday 0-6 Weekday (1 = Monday)
Current Demand-
Real Time ClockCircuit
(Hour)58 58 113 UINT16 12418 12419 Analog Input 1226 R
R/W Amps
Hour 0 - 23 Hour (13 = 1PM)
Current Demand-
Real Time ClockCircuit
(Min) 59 59 114 UINT16 12420 12421 Analog Input
Device Object
1227
Local_Time R
R/W Amps
Minute 0 - 59 Minute
Current Demand- Circuit 60 60 12422 12423 Analog Input 1228 R Amps
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Current Demand- Circuit 61 61 12424 12425 Analog Input 1229 R Amps
Digital Output #1 116 Binary Output 1 R/W 0, 1
Current Demand- Circuit 62 62 12426 12427 Analog Input 1230 R Amps
Digital Output #2 117 Binary Output 2 R/W 0, 1
Current Demand- Circuit 63 63 12428 12429 Analog Input 1231 R Amps
Digital Input #1 State 118 Binary Input 1 R 0, 1
Current Demand- Circuit 64 64 12430 12431 Analog Input 1232 R Amps
Digital
Current Input #2Circuit
Demand- State 65 65 119 12432 12433
Binary Input
Analog Input
2
1233 R
R Amps 0, 1
Modbus
Current Slave Address
Demand- Circuit 66 66 124 UINT16 12434 12435 Analog Input 1234 R/W
R NV Amps 1 - 254
Modbus
Current Demand- TCP Circuit
Port 67 67 125 UINT16 12436 12437 Analog Input 1235 R
R NV Amps 502
IP AddressCircuit 68
Current Demand- 68 126 127 12438 12439 Analog Input 1236 R/W
R NV Amps Meter must be rebooted for new network settings to affect.
GatewayCircuit 69
Current Demand- 69 128 129 12440 12441 Analog Input 1237 R/W
R NV Amps Device can be rebooted remotely using Global Reset/Command (Register 192)
Mask Circuit 70
Current Demand- 70 130 131 12442 12443 Analog Input 1238 R/W
R NV Amps
Current Demand- Circuit 71 71 12444 12445 Analog Input 1239 R Amps
Current Demand- Circuit 72 72 12446 12447 Analog Input 1240 R Amps
Current Demand- Circuit 73 73 12448 12449 Analog Input 1241 R Amps

UMG 804
37
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter
Current Information
Demand- Circuit 74 74 12450 12451 Analog Input 1242 R Amps
CurrentSerial
Demand- Circuit 75
Number 75 1 2 UINT32 12452 12453 AnalogObject
Device Input 1243
Serial_Number R NV Amps
Current Demand-
Bootloader Circuit 76
Version 76 3 UINT16 12454 12455 Analog Input 1244 R NV Amps
Current Demand-
Firmware Circuit 77
Version 77 4 UINT16 12456 12457 AnalogObject
Device Input 1245
Firmware_Revision R
R NV Amps
Current Demand-
Device IDCircuit 78 78 5 UINT16 12458 12459 Analog Input 1246 R
R/W NV Amps 15172, 22000 22000 = Janitza Pointmap
Current Demand-
Power Circuit 79
Up Counter 79 6 UINT16 12460 12461 Analog Input 1247 R
R NV Amps
Current Demand-
Uptime Circuit 80 80 7 8 UINT32 12462 12463 Analog Input 1248 R
R NV Amps
Seconds
Current Demand- Circuit 81 81 12464 12465 Analog Input 1249 R Amps
Smart Port ID #1 10 UINT16 R NV
Current Demand- Circuit 82 82 12466 12467 Analog Input 1250 R Amps
Smart Port ID #2 11 UINT16 R NV
Current Demand- Circuit 83 83 12468 12469 Analog Input 1251 R Amps See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
Current Demand- Circuit 84 84 12470 12471 Analog Input 1252 R Amps
Smart Port ID #4 13 UINT16 R NV
Current Demand- Circuit 85 85 12472 12473 Analog Input 1253 R Amps
Smart Port
Current #1 Serial
Demand- Number
Circuit 86 86 14 15 UINT32 12474 12475 Analog Input 1254 R
R NV Amps
Smart Port
Current #2 Serial
Demand- Number
Circuit 87 87 16 17 UINT32 12476 12477 Analog Input 1255 R
R NV Amps
Smart Port
Current #3 Serial
Demand- Number
Circuit 88 88 18 19 UINT32 12478 12479 Analog Input 1256 R
R NV Amps
Smart Port
Current #4 Serial
Demand- Number
Circuit 89 89 20 21 UINT32 12480 12481 Analog Input 1257 R NV Amps
Smart PortDemand-
Current #1 Firmware Version
Circuit 90 90 22 UINT16 12482 12483 Analog Input 1258 R NV Amps
Smart PortDemand-
Current #2 Firmware Version
Circuit 91 91 23 UINT16 12484 12485 Analog Input 1259 R NV Amps
Current
Smart PortDemand- Circuit
#3 Firmware 92
Version 92 24 UINT16 12486 12487 Analog Input 1260 R NV Amps
Current
Smart PortDemand- Circuit
#4 Firmware 93
Version 93 25 UINT16 12488 12489 Analog Input 1261 R NV Amps
Current Demand-
MAC Address (BitCircuit
33-48)94 94 26 12490 12491 Analog Input 1262 R NV Amps
Current Demand-
MAC Address (BitCircuit
17-32)95 95 27 12492 12493 Analog Input 1263 R
R NV Amps
Current Demand-
MAC Address Circuit
(Bit 1-16)96 96 28 12494 12495 Analog Input 1264 R
R NV Amps
Brand Name (16 Registers) 29 44 R NV
kW Demand 12496 12687 AnalogObject
Input 1265 - 1360 R kW Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Model_Name R NV
kW Demand- supports up to 32 characters (16 registers)
Device Name (16Circuit 1
Registers) 1 61 76 12496 12497 AnalogObject
Device Input 1265
Object_Name R
R/W NV kW
kW Demand- Circuit 2 2 12498 12499 Analog Input 1266 R kW
kW Demand-
Meter Circuit 3
Configuration 3 12500 12501 Analog Input 1267 R kW
kW Demand-
Demand Circuit 4
# of Sub-Intervals 4 100 UINT16 12502 12503 Analog Value
Analog Input 1268
1 R
R/W NV kW 1-6
kW Demand-
Demand Circuit
Sub-Interval 5
Length 5 101 UINT16 12504 12505 Analog Value
Analog Input 1269
2 R
R/W NV kW
Seconds 0, 10 - 32767 0 = Sync to Comms
kW Demand-
Demand Circuit
Time Stamp 6
(Year) 6 102 12506 12507 Analog Input 1270 R
R kW
Year Years since 1900 (118 = 2018)
kW Demand-
Demand Time StampCircuit 7
(Month) 7 103 12508 12509 Analog Input 1271 R
R kW
Month 0 - 11 Month (0 = January)
kW Demand-
Demand Circuit(Day)
Time Stamp 8 8 104 12510 12511 Analog Input 1272 R
R kW
Day 1 - 31 Day of the Month
DemandkW Time
Demand- Circuit
Stamp 9
(Weekday) 9 105 12512 12513 Analog Input 1273 R
R kW
Weekday 0-6 Weekday (1 = Monday)
kW Demand-
Demand Circuit(Hour)
Time Stamp 10 10 106 12514 12515 Analog Input 1274 R
R kW
Hour 0 - 23 Hour (13 = 1PM)
kW Demand-
Demand Time StampCircuit 11
(Minute) 11 107 12516 12517 Analog Input 1275 R
R kW
Minute 0 - 59 Minute
kW Demand-
Demand Time StampCircuit 12
(Second) 12 108 12518 12519 Analog Input 1276 R
R kW
Seconds 0 - 59 Second
kW Demand- Circuit 13 13 12520 12521 Analog Input 1277 R kW Writing to RTC will disable NTP by clearing out URL and/or IP Address
kW
RealDemand-
Time ClockCircuit 14
(Year) 14 109 UINT16 12522 12523 Analog Input 1278 R
R/W kW
Year Years since 1900 (118 = 2018)
kW Demand-
Real Time Clock Circuit
(Month)15 15 110 UINT16 12524 12525 Analog Input 1279 R
R/W kW
Month 0 - 11 Month (0 = January)
Device
AnalogObject
Local_Date
kW
RealDemand-
Time ClockCircuit
(Day)16 16 111 UINT16 12526 12527 Input 1280 R
R/W kW
Day 1 - 31 Day of the Month
kWTime
Real Demand-
ClockCircuit
(Weekday)17 17 112 UINT16 12528 12529 Analog Input 1281 R
R/W kW
Weekday 0-6 Weekday (1 = Monday)
kW
RealDemand-
Time ClockCircuit
(Hour)18 18 113 UINT16 12530 12531 Analog Input 1282 R
R/W kW
Hour 0 - 23 Hour (13 = 1PM)
kW
RealDemand-
Time ClockCircuit
(Min)19 19 114 UINT16 12532 12533 Analog Input
Device Object
1283
Local_Time R
R/W kW
Minute 0 - 59 Minute
kW Demand- Circuit 20 20 12534 12535 Analog Input 1284 R kW
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
kW Demand- Circuit 21 21 12536 12537 Analog Input 1285 R kW
Digital Output #1 116 Binary Output 1 R/W 0, 1
kW Demand- Circuit 22 22 12538 12539 Analog Input 1286 R kW
Digital Output #2 117 Binary Output 2 R/W 0, 1
kW Demand- Circuit 23 23 12540 12541 Analog Input 1287 R kW
Digital Input #1 State 118 Binary Input 1 R 0, 1
kW Demand- Circuit 24 24 12542 12543 Analog Input 1288 R kW
Digital
kW Input Circuit
Demand- #2 State 25 25 119 12544 12545
Binary Input
Analog Input
2
1289 R
R kW 0, 1
Modbus
kW Demand-SlaveCircuit
Address 26 26 124 UINT16 12546 12547 Analog Input 1290 R/W
R NV kW 1 - 254
Modbus TCP Port
kW Demand- Circuit 27 27 125 UINT16 12548 12549 Analog Input 1291 R
R NV kW 502
IP Address
kW Demand- Circuit 28 28 126 127 12550 12551 Analog Input 1292 R/W
R NV kW Meter must be rebooted for new network settings to affect.
Gateway
kW Demand- Circuit 29 29 128 129 12552 12553 Analog Input 1293 R/W
R NV kW Device can be rebooted remotely using Global Reset/Command (Register 192)
kW Demand-MaskCircuit 30 30 130 131 12554 12555 Analog Input 1294 R/W
R NV kW
kW Demand- Circuit 31 31 12556 12557 Analog Input 1295 R kW
kW Demand- Circuit 32 32 12558 12559 Analog Input 1296 R kW
kW Demand- Circuit 33 33 12560 12561 Analog Input 1297 R kW

UMG 804
38
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter
kW Demand-Information
Circuit 34 34 12562 12563 Analog Input 1298 R kW
kW Demand- Circuit 35
Serial Number 35 1 2 UINT32 12564 12565 AnalogObject
Device Input 1299
Serial_Number R NV kW
kW Demand- Version
Bootloader Circuit 36 36 3 UINT16 12566 12567 Analog Input 1300 R NV kW
kWFirmware
Demand-Version
Circuit 37 37 4 UINT16 12568 12569 AnalogObject
Device Input 1301
Firmware_Revision R
R NV kW
kW Demand-
Device Circuit
ID 38 38 5 UINT16 12570 12571 Analog Input 1302 R
R/W NV kW 15172, 22000 22000 = Janitza Pointmap
kWPower
Demand- Circuit 39
Up Counter 39 6 UINT16 12572 12573 Analog Input 1303 R
R NV kW
kW Demand-Uptime Circuit 40 40 7 8 UINT32 12574 12575 Analog Input 1304 R
R NV kW
Seconds
kW Demand- Circuit 41 41 12576 12577 Analog Input 1305 R kW
Smart Port ID #1 10 UINT16 R NV
kW Demand- Circuit 42 42 12578 12579 Analog Input 1306 R kW
Smart Port ID #2 11 UINT16 R NV
kW Demand- Circuit 43 43 12580 12581 Analog Input 1307 R kW See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
kW Demand- Circuit 44 44 12582 12583 Analog Input 1308 R kW
Smart Port ID #4 13 UINT16 R NV
kW Demand- Circuit 45 45 12584 12585 Analog Input 1309 R kW
Smart
kW Port
Demand-#1 Serial Number
Circuit 46 46 14 15 UINT32 12586 12587 Analog Input 1310
R
R NV kW
Smart
kW Port
Demand-#2 Serial Number
Circuit 47 47 16 17 UINT32 12588 12589 Analog Input 1311 R
R NV kW
Smart
kW Port
Demand-#3 Serial Number
Circuit 48 48 18 19 UINT32 12590 12591 Analog Input 1312 R
R NV kW
Smart
kW Port
Demand-#4 Serial Number
Circuit 49 49 20 21 UINT32 12592 12593 Analog Input 1313 R
R NV kW
SmartkWPort #1 Firmware
Demand- CircuitVersion
50 50 22 UINT16 12594 12595 Analog Input 1314 R NV kW
SmartkWPort #2 Firmware
Demand- CircuitVersion
51 51 23 UINT16 12596 12597 Analog Input 1315 R NV kW
SmartkWPort #3 Firmware
Demand- CircuitVersion
52 52 24 UINT16 12598 12599 Analog Input 1316 R NV kW
SmartkWPort
Demand- CircuitVersion
#4 Firmware 53 53 25 UINT16 12600 12601 Analog Input 1317 R NV kW
kW Demand-
MAC Circuit
Address (Bit 54
33-48) 54 26 12602 12603 Analog Input 1318 R NV kW
kW Demand-
MAC Circuit
Address (Bit 55
17-32) 55 27 12604 12605 Analog Input 1319 R
R NV kW
kW
MACDemand-
Address Circuit
(Bit 1-16)56 56 28 12606 12607 Analog Input 1320 R
R NV kW
kW Demand-
Brand Name (16Circuit 57
Registers) 57 29 44 12608 12609 Analog Input 1321 R
R NV kW
kW Demand- Circuit 58 58 12610 12611 Analog Input 1322 R kW Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
kW Demand- Circuit 59 59 12612 12613 Analog Input 1323 R kW supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
kW Demand- Circuit 60 60 12614 12615 Analog Input 1324 R kW
kW Demand- Circuit 61 61 12616 12617 Analog Input 1325 R kW
Meter Configuration
kW Demand- Circuit 62 62 12618 12619 Analog Input 1326 R kW
Demand # of Sub-Intervals 100 UINT16 Analog Value 1 R/W NV 1-6
kW Demand- Circuit 63 63 12620 12621 Analog Input 1327 R kW
Demand Sub-Interval
kW Demand- CircuitLength
64 64 101 UINT16 12622 12623
Analog Value
Analog Input
2
1328
R/W
R NV Seconds
kW 0, 10 - 32767 0 = Sync to Comms
Demand Time Stamp
kW Demand- Circuit(Year)
65 65 102 12624 12625 Analog Input 1329 R
R Year
kW Years since 1900 (118 = 2018)
Demand Time Stamp
kW Demand- Circuit(Month)
66 66 103 12626 12627 Analog Input 1330 R
R Month
kW 0 - 11 Month (0 = January)
Demand Time Stamp
kW Demand- Circuit(Day)
67 67 104 12628 12629 Analog Input 1331 R
R Day
kW 1 - 31 Day of the Month
Demand Time Stamp
kW Demand- (Weekday)
Circuit 68 68 105 12630 12631 Analog Input 1332 R Weekday
kW 0-6 Weekday (1 = Monday)
Demand Time Stamp
kW Demand- Circuit(Hour)
69 69 106 12632 12633 Analog Input 1333 R Hour
kW 0 - 23 Hour (13 = 1PM)
Demand Time Stamp
kW Demand- Circuit(Minute)
70 70 107 12634 12635 Analog Input 1334 R Minute
kW 0 - 59 Minute
kW Demand-
Demand Time StampCircuit 71
(Second) 71 108 12636 12637 Analog Input 1335 R kW
Seconds 0 - 59 Second
kW Demand- Circuit 72 72 12638 12639 Analog Input 1336 R kW Writing to RTC will disable NTP by clearing out URL and/or IP Address
kW
RealDemand-
Time Clock Circuit 73
(Year) 73 109 UINT16 12640 12641 Analog Input 1337 R
R/W kW
Year Years since 1900 (118 = 2018)
kW Demand-
Real Time Clock Circuit
(Month)74 74 110 UINT16 12642 12643 Analog Input 1338 R
R/W kW
Month 0 - 11 Month (0 = January)
Device Object Local_Date
kW Demand-
Real Time ClockCircuit
(Day)75 75 111 UINT16 12644 12645 Analog Input 1339 R
R/W kW
Day 1 - 31 Day of the Month
kWTime
Real Demand-ClockCircuit
(Weekday)76 76 112 UINT16 12646 12647 Analog Input 1340 R
R/W kW
Weekday 0-6 Weekday (1 = Monday)
kW
RealDemand-
Time Clock Circuit
(Hour)77 77 113 UINT16 12648 12649 Analog Input 1341 R
R/W kW
Hour 0 - 23 Hour (13 = 1PM)
kW
RealDemand-
Time ClockCircuit
(Min)78 78 114 UINT16 12650 12651 Analog Input
Device Object
1342
Local_Time R
R/W kW
Minute 0 - 59 Minute
kW Demand- Circuit 79 79 12652 12653 Analog Input 1343 R kW
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
kW Demand- Circuit 80 80 12654 12655 Analog Input 1344 R kW
Digital Output #1 116 Binary Output 1 R/W 0, 1
kW Demand- Circuit 81 81 12656 12657 Analog Input 1345 R kW
Digital Output #2 117 Binary Output 2 R/W 0, 1
kW Demand- Circuit 82 82 12658 12659 Analog Input 1346 R kW
Digital Input #1 State 118 Binary Input 1 R 0, 1
kW Demand- Circuit 83 83 12660 12661 Analog Input 1347 R kW
Digital
kW Input Circuit
Demand- #2 State 84 84 119 12662 12663
Binary Input
Analog Input
2
1348
R
R kW 0, 1
Modbus
kW Demand- SlaveCircuit
Address 85 85 124 UINT16 12664 12665 Analog Input 1349 R/W
R NV kW 1 - 254
Modbus TCP
kW Demand- Circuit 86Port 86 125 UINT16 12666 12667 Analog Input 1350 R
R NV kW 502
IP Address
kW Demand- Circuit 87 87 126 127 12668 12669 Analog Input 1351 R/W
R NV kW Meter must be rebooted for new network settings to affect.
Gateway
kW Demand- Circuit 88 88 128 129 12670 12671 Analog Input 1352 R/W
R NV kW Device can be rebooted remotely using Global Reset/Command (Register 192)
kW Demand- MaskCircuit 89 89 130 131 12672 12673 Analog Input 1353 R/W
R NV kW
kW Demand- Circuit 90 90 12674 12675 Analog Input 1354 R kW
kW Demand- Circuit 91 91 12676 12677 Analog Input 1355 R kW
kW Demand- Circuit 92 92 12678 12679 Analog Input 1356 R kW

UMG 804
39
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter
kW Information
Demand- Circuit 93 93 12680 12681 Analog Input 1357 R kW
kW Demand- Circuit 94
Serial Number 94 1 2 UINT32 12682 12683 AnalogObject
Device Input 1358
Serial_Number R NV kW
kW Demand- Version
Bootloader Circuit 95 95 3 UINT16 12684 12685 Analog Input 1359 R
R NV kW
kWFirmware
Demand-Version
Circuit 96 96 4 UINT16 12686 12687 AnalogObject
Device Input 1360
Firmware_Revision R
R NV kW
Device ID 5 UINT16 R/W NV 15172, 22000 22000 = Janitza Pointmap
Max Current
Power Demand
Up Counter 6 UINT16 12688 12879 Analog Input 1361 - 1456 R
R NV
NV Amps
Max CurrentUptime
Demand - Circuit 1 1 7 8 UINT32 12688 12689 Analog Input 1361 R
R NV
NV Amps
Seconds
Max Current
SmartDemand
Port ID #1- Circuit 2 2 10 UINT16 12690 12691 Analog Input 1362 R
R NV
NV Amps
Max Current
SmartDemand
Port ID #2- Circuit 3 3 11 UINT16 12692 12693 Analog Input 1363 R
R NV
NV Amps
See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Max Current
SmartDemand
Port ID #3- Circuit 4 4 12 UINT16 12694 12695 Analog Input 1364 R
R NV
NV Amps
Max Current
SmartDemand
Port ID #4- Circuit 5 5 13 UINT16 12696 12697 Analog Input 1365 R
R NV
NV Amps
Max Current
Smart Demand
Port #1 - Circuit 6
Serial Number 6 14 15 UINT32 12698 12699 Analog Input 1366 R
R NV
NV Amps
Max Current
Smart Demand
Port #2 - Circuit 7
Serial Number 7 16 17 UINT32 12700 12701 Analog Input 1367 R
R NV
NV Amps
Max Current
Smart Demand
Port #3 - Circuit 8
Serial Number 8 18 19 UINT32 12702 12703 Analog Input 1368 R
R NV
NV Amps
Max Current
Smart Demand
Port #4 - Circuit 9
Serial Number 9 20 21 UINT32 12704 12705 Analog Input 1369 R
R NV
NV Amps
Max
SmartCurrent
Port #1Demand
Firmware - Circuit 10
Version 10 22 UINT16 12706 12707 Analog Input 1370 R
R NV
NV Amps
Max
SmartCurrent
Port #2Demand
Firmware - Circuit 11
Version 11 23 UINT16 12708 12709 Analog Input 1371 R
R NV
NV Amps
Max
SmartCurrent
Port #3Demand
Firmware - Circuit 12
Version 12 24 UINT16 12710 12711 Analog Input 1372 R
R NV
NV Amps
Max
SmartCurrent
Port #4Demand
Firmware - Circuit 13
Version 13 25 UINT16 12712 12713 Analog Input 1373 R
R NV
NV Amps
MaxMAC
Current Demand
Address - Circuit 14
(Bit 33-48) 14 26 12714 12715 Analog Input 1374 R
R NV
NV Amps
MaxMAC
Current Demand
Address - Circuit 15
(Bit 17-32) 15 27 12716 12717 Analog Input 1375 R
R NV
NV Amps
Max MAC
Current Demand
Address (Bit-1-16)
Circuit 16 16 28 12718 12719 Analog Input 1376 R
R NV
NV Amps
Max Current Demand - Circuit 17 17 12720 12721 Analog Input 1377 R NV Amps
Brand Name (16 Registers) 29 44 R NV
Max Current Demand - Circuit 18 18 12722 12723 Analog Input 1378 R NV Amps Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Max Current Demand - Circuit 19 19 12724 12725 Analog Input 1379 R NV Amps supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Max Current Demand - Circuit 20 20 12726 12727 Analog Input 1380 R NV Amps
Max Current Demand - Circuit 21 21 12728 12729 Analog Input 1381 R NV Amps
Meter Configuration
Max Current Demand - Circuit 22 22 12730 12731 Analog Input 1382 R NV Amps
MaxDemand
Current#Demand
of Sub-Intervals
- Circuit 23 23 100 UINT16 12732 12733 Analog
Analog Value
Input
1
1383 R/W
R NV
NV Amps 1-6
Demand Sub-Interval
Max Current Demand - CircuitLength24 24 101 UINT16 12734 12735 Analog
Analog Value
Input 2
1384 R/W
R NV
NV Seconds
Amps 0, 10 - 32767 0 = Sync to Comms
Demand Time Stamp
Max Current Demand - Circuit (Year) 25 25 102 12736 12737 Analog Input 1385 R
R NV Year
Amps Years since 1900 (118 = 2018)
Demand
Max Time
Current Stamp- (Month)
Demand Circuit 26 26 103 12738 12739 Analog Input 1386 R NV Month
Amps 0 - 11 Month (0 = January)
MaxDemand
CurrentTime
DemandStamp (Day) 27
- Circuit 27 104 12740 12741 Analog Input 1387 R NV Day
Amps 1 - 31 Day of the Month
Max Current
Demand TimeDemand - Circuit 28
Stamp (Weekday) 28 105 12742 12743 Analog Input 1388 R NV Amps
Weekday 0-6 Weekday (1 = Monday)
Max CurrentTime
Demand DemandStamp- Circuit
(Hour) 29 29 106 12744 12745 Analog Input 1389 R NV Amps
Hour 0 - 23 Hour (13 = 1PM)
Max Current
Demand Demand
Time Stamp-(Minute)
Circuit 30 30 107 12746 12747 Analog Input 1390 R NV Amps
Minute 0 - 59 Minute
Max Current
Demand Demand
Time Stamp-(Second)
Circuit 31 31 108 12748 12749 Analog Input 1391 R
R NV Amps
Seconds 0 - 59 Second
Max Current Demand - Circuit 32 32 12750 12751 Analog Input 1392 R NV Amps Writing to RTC will disable NTP by clearing out URL and/or IP Address
Max Current
Real TimeDemand - Circuit 33
Clock (Year) 33 109 UINT16 12752 12753 Analog Input 1393 R
R/W NV Amps
Year Years since 1900 (118 = 2018)
MaxReal
Current
TimeDemand - Circuit 34
Clock (Month) 34 110 UINT16 12754 12755 Analog Input 1394 R
R/W NV Amps
Month 0 - 11 Month (0 = January)
Max Current Demand - Circuit 35 35 12756 12757 Device
AnalogObject
Input Local_Date
1395 R NV Amps
Real Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
Max Current Demand - Circuit 36 36 12758 12759 Analog Input 1396 R NV Amps
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
Max Current Demand - Circuit 37 37 12760 12761 Analog Input 1397 R NV Amps
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
Max Current Demand - Circuit 38 38 12762 12763 Analog Input 1398 R NV Amps
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Max Current Demand - Circuit 39 39 12764 12765 Analog Input 1399 R NV Amps
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Max Current Demand - Circuit 40 40 12766 12767 Analog Input 1400 R NV Amps
Digital Output #1 116 Binary Output 1 R/W 0, 1
Max Current Demand - Circuit 41 41 12768 12769 Analog Input 1401 R NV Amps
DigitalDemand
Max Current Output -#2 Circuit 42 42 117 12770 12771
Binary Output
Analog Input
2
1402 R/W
R NV Amps 0, 1
Digital Input
Max Current Demand #1 State
- Circuit 43 43 118 12772 12773 Binary Input
Analog Input
1
1403 R
R NV Amps 0, 1
Digital Input
Max Current Demand #2 State
- Circuit 44 44 119 12774 12775 Binary Input
Analog Input 2
1404 R
R NV Amps 0, 1
ModbusDemand
Max Current Slave Address
- Circuit 45 45 124 UINT16 12776 12777 Analog Input 1405 R/W
R NV
NV Amps 1 - 254
Modbus TCP Port
Max Current Demand - Circuit 46 46 125 UINT16 12778 12779 Analog Input 1406 R NV Amps 502
Max Current IPDemand
Address - Circuit 47 47 126 127 12780 12781 Analog Input 1407 R/W
R NV Amps
Meter must be rebooted for new network settings to affect.
Max CurrentGateway
Demand - Circuit 48 48 128 129 12782 12783 Analog Input 1408 R
R/W NV Amps
Device can be rebooted remotely using Global Reset/Command (Register 192)
Max Current Demand
Mask - Circuit 49 49 130 131 12784 12785 Analog Input 1409 R
R/W NV Amps
Max Current Demand - Circuit 50 50 12786 12787 Analog Input 1410 R NV Amps
Max Current Demand - Circuit 51 51 12788 12789 Analog Input 1411 R NV Amps
Max Current Demand - Circuit 52 52 12790 12791 Analog Input 1412 R NV Amps

UMG 804
40
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
MeterDemand
Max Current Information- Circuit 53 53 12792 12793 Analog Input 1413 R NV Amps
Max Current Demand
Serial Number - Circuit 54 54 1 2 UINT32 12794 12795 AnalogObject
Device Input 1414
Serial_Number R NV Amps
Max Current Demand
Bootloader - Circuit 55
Version 55 3 UINT16 12796 12797 Analog Input 1415 R
R NV
NV Amps
Max Current Demand
Firmware - Circuit 56
Version 56 4 UINT16 12798 12799 AnalogObject
Device Input 1416
Firmware_Revision R
R NV
NV Amps
Max CurrentDevice
Demand ID - Circuit 57 57 5 UINT16 12800 12801 Analog Input 1417 R
R/W NV
NV Amps 15172, 22000 22000 = Janitza Pointmap
Max Current
PowerDemand
Up Counter- Circuit 58 58 6 UINT16 12802 12803 Analog Input 1418 R
R NV
NV Amps
Max Current Demand - Circuit 59 59 12804 12805 Analog Input 1419 R NV Amps
Uptime 7 8 UINT32 R NV Seconds
Max Current Demand - Circuit 60 60 12806 12807 Analog Input 1420 R NV Amps
Smart Port ID #1 10 UINT16 R NV
Max Current Demand - Circuit 61 61 12808 12809 Analog Input 1421 R NV Amps
Smart Port ID #2 11 UINT16 R NV
Max Current Demand - Circuit 62 62 12810 12811 Analog Input 1422 R NV Amps See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
Max Current Demand - Circuit 63 63 12812 12813 Analog Input 1423 R NV Amps
SmartDemand
Max Current Port ID -#4Circuit 64 64 13 UINT16 12814 12815 Analog Input 1424
R
R NV
NV Amps
Smart
Max Port Demand
Current #1 Serial -Number
Circuit 65 65 14 15 UINT32 12816 12817 Analog Input 1425 R
R NV
NV Amps
Smart
Max Port Demand
Current #2 Serial -Number
Circuit 66 66 16 17 UINT32 12818 12819 Analog Input 1426 R
R NV
NV Amps
Smart
Max Port Demand
Current #3 Serial -Number
Circuit 67 67 18 19 UINT32 12820 12821 Analog Input 1427 R
R NV
NV Amps
Smart
Max Port Demand
Current #4 Serial -Number
Circuit 68 68 20 21 UINT32 12822 12823 Analog Input 1428 R NV Amps
Smart
Max Port #1Demand
Current Firmware Version
- Circuit 69 69 22 UINT16 12824 12825 Analog Input 1429 R NV Amps
Smart
Max Port #2Demand
Current Firmware Version
- Circuit 70 70 23 UINT16 12826 12827 Analog Input 1430 R NV Amps
Max
SmartCurrent
Port #3Demand
Firmware - Circuit 71
Version 71 24 UINT16 12828 12829 Analog Input 1431 R NV Amps
Max
SmartCurrent
Port #4Demand
Firmware - Circuit 72
Version 72 25 UINT16 12830 12831 Analog Input 1432 R NV Amps
MaxMAC
Current Demand
Address (Bit -33-48)
Circuit 73 73 26 12832 12833 Analog Input 1433 R
R NV
NV Amps
MaxMAC
Current Demand
Address (Bit -17-32)
Circuit 74 74 27 12834 12835 Analog Input 1434 R
R NV
NV Amps
Max MAC
Current Demand
Address (Bit-1-16)
Circuit 75 75 28 12836 12837 Analog Input 1435 R
R NV
NV Amps
Max Current
Brand NameDemand - Circuit 76
(16 Registers) 76 29 44 12838 12839 Analog Input 1436 R
R NV
NV Amps
Max Current Demand - Circuit 77 77 12840 12841 Analog Input 1437 R NV Amps Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Max Current Demand - Circuit 78 78 12842 12843 Analog Input 1438 R NV Amps supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Max Current Demand - Circuit 79 79 12844 12845 Analog Input 1439 R NV Amps
Max Current Demand - Circuit 80 80 12846 12847 Analog Input 1440 R NV Amps
Meter Configuration
Max Current Demand - Circuit 81 81 12848 12849 Analog Input 1441 R NV Amps
MaxDemand
Current#Demand
of Sub-Intervals
- Circuit 82 82 100 UINT16 12850 12851
Analog Value
Analog Input
1
1442
R/W
R NV
NV Amps 1-6
Demand
Max CurrentSub-Interval Length83
Demand - Circuit 83 101 UINT16 12852 12853 Analog Value
Analog Input
2
1443 R/W
R NV
NV Seconds
Amps 0, 10 - 32767 0 = Sync to Comms
Demand Time Stamp
Max Current Demand - Circuit (Year) 84 84 102 12854 12855 Analog Input 1444 R
R NV Year
Amps Years since 1900 (118 = 2018)
Demand
Max Time
Current Stamp- (Month)
Demand Circuit 85 85 103 12856 12857 Analog Input 1445 R
R NV Month
Amps 0 - 11 Month (0 = January)
MaxDemand
CurrentTime
DemandStamp (Day) 86
- Circuit 86 104 12858 12859 Analog Input 1446 R NV Day
Amps 1 - 31 Day of the Month
Demand
Max TimeDemand
Current Stamp (Weekday)
- Circuit 87 87 105 12860 12861 Analog Input 1447 R NV Weekday
Amps 0-6 Weekday (1 = Monday)
Demand
Max CurrentTime
DemandStamp- Circuit
(Hour)88 88 106 12862 12863 Analog Input 1448 R NV Hour
Amps 0 - 23 Hour (13 = 1PM)
Max Current
Demand Demand
Time Stamp-(Minute)
Circuit 89 89 107 12864 12865 Analog Input 1449 R NV Amps
Minute 0 - 59 Minute
Max Current
Demand Demand
Time Stamp-(Second)
Circuit 90 90 108 12866 12867 Analog Input 1450 R NV Amps
Seconds 0 - 59 Second
Max Current Demand - Circuit 91 91 12868 12869 Analog Input 1451 R NV Amps Writing to RTC will disable NTP by clearing out URL and/or IP Address
Max Current
Real TimeDemand - Circuit 92
Clock (Year) 92 109 UINT16 12870 12871 Analog Input 1452 R
R/W NV Amps
Year Years since 1900 (118 = 2018)
MaxReal
Current
TimeDemand - Circuit 93
Clock (Month) 93 110 UINT16 12872 12873 Analog Input 1453 R
R/W NV Amps
Month 0 - 11 Month (0 = January)
Device
AnalogObject
Local_Date
Max Current
Real TimeDemand - Circuit 94
Clock (Day) 94 111 UINT16 12874 12875 Input 1454 R
R/W NV Amps
Day 1 - 31 Day of the Month
Max Current
Real Time Demand - Circuit 95
Clock (Weekday) 95 112 UINT16 12876 12877 Analog Input 1455 R
R/W NV Amps
Weekday 0-6 Weekday (1 = Monday)
Max Current
Real TimeDemand - Circuit 96
Clock (Hour) 96 113 UINT16 12878 12879 Analog Input 1456 R
R/W NV Amps
Hour 0 - 23 Hour (13 = 1PM)
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
RealMax
TimekW Demand
Clock (Second) 115 UINT16 12880 13071 Analog Input 1457 - 1552 R
R/W NV kW
Seconds 0 - 59 Second
Max kW Demand
Digital Output- Circuit
#1 1 1 116 12880 12881 AnalogOutput
Binary Input 1457
1 R
R/W NV kW 0, 1
Max kW Demand
Digital Output- Circuit
#2 2 2 117 12882 12883 AnalogOutput
Binary Input 1458
2 R
R/W NV kW 0, 1
Max kW Demand
Digital Input #1- State
Circuit 3 3 118 12884 12885 Analog Input
Binary Input 1459
1 R
R NV kW 0, 1
Max kW Demand
Digital Input #2- State
Circuit 4 4 119 12886 12887 Analog Input
Binary Input 1460
2 R
R NV kW 0, 1
Max kW Demand
Modbus - Circuit 5
Slave Address 5 124 UINT16 12888 12889 Analog Input 1461 R
R/W NV
NV kW 1 - 254
Max kW Demand
Modbus TCP -Port
Circuit 6 6 125 UINT16 12890 12891 Analog Input 1462 R
R NV
NV kW 502
Max kW IPDemand
Address- Circuit 7 7 126 127 12892 12893 Analog Input 1463 R
R/W NV
NV kW
Meter must be rebooted for new network settings to affect.
Max kW Demand
Gateway- Circuit 8 8 128 129 12894 12895 Analog Input 1464 R
R/W NV
NV kW
Device can be rebooted remotely using Global Reset/Command (Register 192)
Max kW Demand
Mask - Circuit 9 9 130 131 12896 12897 Analog Input 1465 R
R/W NV
NV kW
Max kW Demand - Circuit 10 10 12898 12899 Analog Input 1466 R NV kW
Max kW Demand - Circuit 11 11 12900 12901 Analog Input 1467 R NV kW
Max kW Demand - Circuit 12 12 12902 12903 Analog Input 1468 R NV kW

UMG 804
41
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
MaxMeter Information
kW Demand - Circuit 13 13 12904 12905 Analog Input 1469 R NV kW
Max kWSerial
Demand - Circuit 14
Number 14 1 2 UINT32 12906 12907 AnalogObject
Device Input 1470
Serial_Number R NV kW
Max Bootloader
kW DemandVersion
- Circuit 15 15 3 UINT16 12908 12909 Analog Input 1471 R
R NV
NV kW
Max kW Demand
Firmware - Circuit 16
Version 16 4 UINT16 12910 12911 AnalogObject
Device Input 1472
Firmware_Revision R
R NV
NV kW
Max kW Demand
Device ID- Circuit 17 17 5 UINT16 12912 12913 Analog Input 1473 R
R/W NV
NV kW 15172, 22000 22000 = Janitza Pointmap
Max kW Demand
Power - Circuit 18
Up Counter 18 6 UINT16 12914 12915 Analog Input 1474 R
R NV
NV kW
Max kW Demand - Circuit 19 19 12916 12917 Analog Input 1475 R NV kW
Uptime 7 8 UINT32 R NV Seconds
Max kW Demand - Circuit 20 20 12918 12919 Analog Input 1476 R NV kW
Smart Port ID #1 10 UINT16 R NV
Max kW Demand - Circuit 21 21 12920 12921 Analog Input 1477 R NV kW
Smart Port ID #2 11 UINT16 R NV
Max kW Demand - Circuit 22 22 12922 12923 Analog Input 1478 R NV kW See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
Max kW Demand - Circuit 23 23 12924 12925 Analog Input 1479 R NV kW
Max kWSmart Port ID
Demand #4 24
- Circuit 24 13 UINT16 12926 12927 Analog Input 1480 R
R NV
NV kW
Smart
Max kW Port #1 Serial
Demand Number
- Circuit 25 25 14 15 UINT32 12928 12929 Analog Input 1481 R
R NV
NV kW
Smart
Max kW Port #2 Serial
Demand Number
- Circuit 26 26 16 17 UINT32 12930 12931 Analog Input 1482 R
R NV
NV kW
Smart
Max kW Port #3 Serial
Demand Number
- Circuit 27 27 18 19 UINT32 12932 12933 Analog Input 1483 R NV kW
Smart
Max kW Port #4 Serial
Demand Number
- Circuit 28 28 20 21 UINT32 12934 12935 Analog Input 1484 R NV kW
Smart
Max Port #1 Firmware
kW Demand Version
- Circuit 29 29 22 UINT16 12936 12937 Analog Input 1485 R NV kW
Max Port
Smart kW Demand - Circuit
#2 Firmware 30
Version 30 23 UINT16 12938 12939 Analog Input 1486 R NV kW
Max Port
Smart kW Demand - Circuit
#3 Firmware 31
Version 31 24 UINT16 12940 12941 Analog Input 1487 R NV kW
Max Port
Smart kW Demand - Circuit
#4 Firmware 32
Version 32 25 UINT16 12942 12943 Analog Input 1488 R NV kW
Max
MACkWAddress
Demand - Circuit
(Bit 33-48)33 33 26 12944 12945 Analog Input 1489 R
R NV
NV kW
Max
MACkWAddress
Demand - Circuit
(Bit 17-32)34 34 27 12946 12947 Analog Input 1490 R
R NV
NV kW
Max kWAddress
MAC Demand(Bit - Circuit
1-16) 35 35 28 12948 12949 Analog Input 1491 R
R NV
NV kW
Max kWName
Brand Demand - Circuit 36
(16 Registers) 36 29 44 12950 12951 Analog Input 1492 R
R NV
NV kW
Max kW Demand - Circuit 37 37 12952 12953 Analog Input 1493 R NV kW Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Max kW Demand - Circuit 38 38 12954 12955 Analog Input 1494 R NV kW supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Max kW Demand - Circuit 39 39 12956 12957 Analog Input 1495 R NV kW
Max kW Demand - Circuit 40 40 12958 12959 Analog Input 1496 R NV kW
Meter Configuration
Max kW Demand - Circuit 41 41 12960 12961 Analog Input 1497 R NV kW
Demand
Max # of Sub-Intervals
kW Demand - Circuit 42 42 100 UINT16 12962 12963
Analog Value
Analog Input
1
1498 R/W
R NV
NV kW 1-6
Demand
Max Sub-Interval
kW Demand Length
- Circuit 43 43 101 UINT16 12964 12965 Analog
Analog Value
Input
2
1499 R/W
R NV
NV Seconds
kW 0, 10 - 32767 0 = Sync to Comms
Demand Time Stamp
Max kW Demand - Circuit (Year)
44 44 102 12966 12967 Analog Input 1500 R
R NV Year
kW Years since 1900 (118 = 2018)
Demand
Max kW Time
DemandStamp (Month)
- Circuit 45 45 103 12968 12969 Analog Input 1501 R
R NV Month
kW 0 - 11 Month (0 = January)
Demand
Max Time Stamp
kW Demand (Day)
- Circuit 46 46 104 12970 12971 Analog Input 1502 R NV Day
kW 1 - 31 Day of the Month
Demand
Max kWTime Stamp- Circuit
Demand (Weekday)
47 47 105 12972 12973 Analog Input 1503 R NV Weekday
kW 0-6 Weekday (1 = Monday)
Max kW Demand
Demand Time Stamp- Circuit 48
(Hour) 48 106 12974 12975 Analog Input 1504 R NV kW
Hour 0 - 23 Hour (13 = 1PM)
Max kWTime
Demand DemandStamp- Circuit 49
(Minute) 49 107 12976 12977 Analog Input 1505 R NV kW
Minute 0 - 59 Minute
Max kWTime
Demand DemandStamp- Circuit 50
(Second) 50 108 12978 12979 Analog Input 1506 R NV kW
Seconds 0 - 59 Second
Max kW Demand - Circuit 51 51 12980 12981 Analog Input 1507 R NV kW Writing to RTC will disable NTP by clearing out URL and/or IP Address
Max kWTime
Real DemandClock- Circuit
(Year) 52 52 109 UINT16 12982 12983 Analog Input 1508 R
R/W NV kW
Year Years since 1900 (118 = 2018)
Max kW
Real Demand
Time Clock -(Month)
Circuit 53 53 110 UINT16 12984 12985 Analog Input 1509 R
R/W NV kW
Month 0 - 11 Month (0 = January)
MaxReal
kW Time
Demand Device
AnalogObject Local_Date
Clock- Circuit
(Day) 54 54 111 UINT16 12986 12987 Input 1510 R
R/W NV kW
Day 1 - 31 Day of the Month
Max
RealkW Demand
Time - Circuit 55
Clock (Weekday) 55 112 UINT16 12988 12989 Analog Input 1511 R
R/W NV kW
Weekday 0-6 Weekday (1 = Monday)
Max kWTime
Real DemandClock- (Hour)
Circuit 56 56 113 UINT16 12990 12991 Analog Input 1512 R
R/W NV kW
Hour 0 - 23 Hour (13 = 1PM)
Max kW Demand - Circuit 57 57 12992 12993 Analog Input 1513 R NV kW
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Max kW Demand - Circuit 58 58 12994 12995 Analog Input 1514 R NV kW
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Max kW Demand - Circuit 59 59 12996 12997 Analog Input 1515 R NV kW
Digital Output #1 116 Binary Output 1 R/W 0, 1
Max kW Demand - Circuit 60 60 12998 12999 Analog Input 1516 R NV kW
Digital Output #2 117 Binary Output 2 R/W 0, 1
Max kW Demand - Circuit 61 61 13000 13001 Analog Input 1517 R NV kW
MaxDigital Input #1- Circuit
State 62 118 R 0, 1
Binary Input 1
kW Demand 62 13002 13003 Analog Input 1518 R NV kW
MaxDigital Input #2- Circuit
kW Demand State 63 63 119 13004 13005 Binary Input
Analog Input
2
1519 R
R NV kW 0, 1
MaxModbus Slave Address
kW Demand - Circuit 64 64 124 UINT16 13006 13007 Analog Input 1520 R/W
R NV
NV kW 1 - 254
Max kWModbus
Demand TCP-Port
Circuit 65 65 125 UINT16 13008 13009 Analog Input 1521 R
R NV
NV kW 502
IP Address
Max kW Demand - Circuit 66 66 126 127 13010 13011 Analog Input 1522 R/W
R NV kW
Meter must be rebooted for new network settings to affect.
Gateway- Circuit 67
Max kW Demand 67 128 129 13012 13013 Analog Input 1523 R/W
R NV kW
Device can be rebooted remotely using Global Reset/Command (Register 192)
Max kW DemandMask - Circuit 68 68 130 131 13014 13015 Analog Input 1524 R
R/W NV kW
Max kW Demand - Circuit 69 69 13016 13017 Analog Input 1525 R NV kW
Max kW Demand - Circuit 70 70 13018 13019 Analog Input 1526 R NV kW
Max kW Demand - Circuit 71 71 13020 13021 Analog Input 1527 R NV kW

UMG 804
42
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
MaxMeter Information
kW Demand - Circuit 72 72 13022 13023 Analog Input 1528 R NV kW
Max kWSerial
Demand - Circuit 73
Number 73 1 2 UINT32 13024 13025 AnalogObject
Device Input 1529
Serial_Number R NV kW
Max Bootloader
kW DemandVersion
- Circuit 74 74 3 UINT16 13026 13027 Analog Input 1530 R
R NV
NV kW
Max kW Demand
Firmware - Circuit 75
Version 75 4 UINT16 13028 13029 AnalogObject
Device Input 1531
Firmware_Revision R
R NV
NV kW
Max kW Demand
Device ID- Circuit 76 76 5 UINT16 13030 13031 Analog Input 1532 R
R/W NV
NV kW 15172, 22000 22000 = Janitza Pointmap
Max kW Demand
Power - Circuit 77
Up Counter 77 6 UINT16 13032 13033 Analog Input 1533 R
R NV
NV kW
Max kW Demand - Circuit 78 78 13034 13035 Analog Input 1534 R NV kW
Uptime 7 8 UINT32 R NV Seconds
Max kW Demand - Circuit 79 79 13036 13037 Analog Input 1535 R NV kW
Smart Port ID #1 10 UINT16 R NV
Max kW Demand - Circuit 80 80 13038 13039 Analog Input 1536 R NV kW
Smart Port ID #2 11 UINT16 R NV
Max kW Demand - Circuit 81 81 13040 13041 Analog Input 1537 R NV kW See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
Max kW Demand - Circuit 82 82 13042 13043 Analog Input 1538 R NV kW
Max kWSmart Port ID
Demand #4 83
- Circuit 83 13 UINT16 13044 13045 Analog Input 1539 R
R NV
NV kW
Smart
Max kWPort #1 Serial
Demand Number
- Circuit 84 84 14 15 UINT32 13046 13047 Analog Input 1540 R
R NV
NV kW
Smart
Max kWPort #2 Serial
Demand Number
- Circuit 85 85 16 17 UINT32 13048 13049 Analog Input 1541 R
R NV
NV kW
Smart
Max kWPort #3 Serial
Demand Number
- Circuit 86 86 18 19 UINT32 13050 13051 Analog Input 1542 R NV kW
Smart
Max kWPort #4 Serial
Demand Number
- Circuit 87 87 20 21 UINT32 13052 13053 Analog Input 1543 R NV kW
Smart
Max Port #1 Firmware
kW Demand Version
- Circuit 88 88 22 UINT16 13054 13055 Analog Input 1544 R NV kW
Max Port
Smart kW Demand - Circuit
#2 Firmware 89
Version 89 23 UINT16 13056 13057 Analog Input 1545 R NV kW
Max Port
Smart kW Demand - Circuit
#3 Firmware 90
Version 90 24 UINT16 13058 13059 Analog Input 1546 R NV kW
Max Port
Smart kW Demand - Circuit
#4 Firmware 91
Version 91 25 UINT16 13060 13061 Analog Input 1547 R NV kW
Max
MACkWAddress
Demand - Circuit
(Bit 33-48)92 92 26 13062 13063 Analog Input 1548 R NV kW
Max
MACkWAddress
Demand - Circuit
(Bit 17-32)93 93 27 13064 13065 Analog Input 1549 R NV kW
Max kWAddress
MAC Demand(Bit- Circuit
1-16) 94 94 28 13066 13067 Analog Input 1550 R NV kW
Max kWName
Brand Demand - Circuit 95
(16 Registers) 95 29 44 13068 13069 Analog Input 1551 R NV kW
Brand Name, Model Name and Device Name
Max kWName
Model Demand(16-Register)
Circuit 96 96 45 60 13070 13071 AnalogObject
Device Input 1552
Model_Name R NV kW
supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
KWH Snapshot 13072 13263 Analog Input 1553 - 1648 R kWh
KWH
MeterSnapshot - Circuit 1
Configuration 1 13072 13073 Analog Input 1553 R kWh
KWH Snapshot
Demand - Circuit 2
# of Sub-Intervals 2 100 UINT16 13074 13075 Analog Value
Analog Input 1554
1 R
R/W NV kWh 1-6
KWH Snapshot
Demand - Circuit
Sub-Interval 3
Length 3 101 UINT16 13076 13077 Analog Value
Analog Input 1555
2 R
R/W NV kWh
Seconds 0, 10 - 32767 0 = Sync to Comms
KWH Snapshot
Demand - Circuit
Time Stamp 4
(Year) 4 102 13078 13079 Analog Input 1556 R kWh
Year Years since 1900 (118 = 2018)
KWH Snapshot
Demand Time Stamp- Circuit 5
(Month) 5 103 13080 13081 Analog Input 1557 R kWh
Month 0 - 11 Month (0 = January)
KWH Snapshot
Demand - Circuit
Time Stamp 6
(Day) 6 104 13082 13083 Analog Input 1558 R kWh
Day 1 - 31 Day of the Month
KWH Time
Demand Snapshot
Stamp- Circuit 7
(Weekday) 7 105 13084 13085 Analog Input 1559 R kWh
Weekday 0-6 Weekday (1 = Monday)
KWH Snapshot
Demand - Circuit
Time Stamp 8
(Hour) 8 106 13086 13087 Analog Input 1560 R kWh
Hour 0 - 23 Hour (13 = 1PM)
KWH Snapshot
Demand Time Stamp- Circuit 9
(Minute) 9 107 13088 13089 Analog Input 1561 R kWh
Minute 0 - 59 Minute
KWH Snapshot
Demand - Circuit
Time Stamp 10
(Second) 10 108 13090 13091 Analog Input 1562 R
R kWh
Seconds 0 - 59 Second
KWH Snapshot - Circuit 11 11 13092 13093 Analog Input 1563 R kWh Writing to RTC will disable NTP by clearing out URL and/or IP Address
KWH
RealSnapshot - Circuit
Time Clock (Year)12 12 109 UINT16 13094 13095 Analog Input 1564 R
R/W kWh
Year Years since 1900 (118 = 2018)
KWH
Real Snapshot
Time Clock- Circuit
(Month) 13 13 110 UINT16 13096 13097 Analog Input 1565 R
R/W kWh
Month 0 - 11 Month (0 = January)
KWH Device
AnalogObject Local_Date
RealSnapshot - Circuit
(Day)14 14 13098 13099 R kWh
Input 1566
Time Clock 111 UINT16 R/W Day 1 - 31 Day of the Month
KWH Snapshot - Circuit 15 15 13100 13101 Analog Input 1567 R kWh
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
KWH Snapshot - Circuit 16 16 13102 13103 Analog Input 1568 R kWh
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
KWH Snapshot - Circuit 17 17 13104 13105 Analog Input 1569 R kWh
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
KWH Snapshot - Circuit 18 18 13106 13107 Analog Input 1570 R kWh
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
KWH Snapshot - Circuit 19 19 13108 13109 Analog Input 1571 R kWh
Digital Output #1 116 Binary Output 1 R/W 0, 1
KWH Snapshot - Circuit 20 20 13110 13111 Analog Input 1572 R kWh
KWHDigital Output #2 21 117 R/W 0, 1
Binary Output 2
Snapshot - Circuit 21 13112 13113 Analog Input 1573 R kWh
KWHDigital Input -#1Circuit
Snapshot State22 22 118 13114 13115 Binary Input
Analog Input
1
1574 R
R kWh 0, 1
KWHDigital Input -#2Circuit
Snapshot State23 23 119 13116 13117 Binary Input
Analog Input 2
1575 R
R kWh 0, 1
Modbus
KWH Slave- Address
Snapshot Circuit 24 24 124 UINT16 13118 13119 Analog Input 1576 R/W
R NV kWh 1 - 254
KWHModbus
Snapshot TCP Port 25
- Circuit 25 125 UINT16 13120 13121 Analog Input 1577 R NV kWh 502
IP Address
KWH Snapshot - Circuit 26 26 126 127 13122 13123 Analog Input 1578 R/W
R NV kWh
Meter must be rebooted for new network settings to affect.
KWH Snapshot
Gateway- Circuit 27 27 128 129 13124 13125 Analog Input 1579 R
R/W NV kWh
Device can be rebooted remotely using Global Reset/Command (Register 192)
KWH SnapshotMask- Circuit 28 28 130 131 13126 13127 Analog Input 1580 R
R/W NV kWh
KWH Snapshot - Circuit 29 29 13128 13129 Analog Input 1581 R kWh
KWH Snapshot - Circuit 30 30 13130 13131 Analog Input 1582 R kWh
KWH Snapshot - Circuit 31 31 13132 13133 Analog Input 1583 R kWh

UMG 804
43
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
KWHMeter Information
Snapshot - Circuit 32 32 13134 13135 Analog Input 1584 R kWh
KWH Snapshot
Serial Number- Circuit 33 33 1 2 UINT32 13136 13137 AnalogObject
Device Input 1585
Serial_Number R NV kWh
KWH Snapshot Version
Bootloader - Circuit 34 34 3 UINT16 13138 13139 Analog Input 1586 R
R NV kWh
KWHFirmware
SnapshotVersion
- Circuit 35 35 4 UINT16 13140 13141 AnalogObject
Device Input 1587
Firmware_Revision R
R NV kWh
KWH Snapshot
Device -IDCircuit 36 36 5 UINT16 13142 13143 Analog Input 1588 R
R/W NV kWh 15172, 22000 22000 = Janitza Pointmap
KWHPower
Snapshot - Circuit 37
Up Counter 37 6 UINT16 13144 13145 Analog Input 1589 R
R NV kWh
KWH Snapshot - Circuit 38 38 13146 13147 Analog Input 1590 R kWh
Uptime 7 8 UINT32 R NV Seconds
KWH Snapshot - Circuit 39 39 13148 13149 Analog Input 1591 R kWh
Smart Port ID #1 10 UINT16 R NV
KWH Snapshot - Circuit 40 40 13150 13151 Analog Input 1592 R kWh
Smart Port ID #2 11 UINT16 R NV
KWH Snapshot - Circuit 41 41 13152 13153 Analog Input 1593 R kWh See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
KWH Snapshot - Circuit 42 42 13154 13155 Analog Input 1594 R kWh
KWHSmart
SnapshotPort-ID #4 43
Circuit 43 13 UINT16 13156 13157 Analog Input 1595 R
R NV kWh
Smart
KWH Port #1 Serial
Snapshot Number
- Circuit 44 44 14 15 UINT32 13158 13159 Analog Input 1596 R
R NV kWh
Smart
KWH Port #2 Serial
Snapshot Number
- Circuit 45 45 16 17 UINT32 13160 13161 Analog Input 1597 R
R NV kWh
Smart
KWH Port #3 Serial
Snapshot Number
- Circuit 46 46 18 19 UINT32 13162 13163 Analog Input 1598 R NV kWh
Smart
KWH Port #4 Serial
Snapshot Number
- Circuit 47 47 20 21 UINT32 13164 13165 Analog Input 1599 R NV kWh
Smart
KWH Port #1 Firmware
Snapshot - CircuitVersion
48 48 22 UINT16 13166 13167 Analog Input 1600 R NV kWh
KWH
Smart Snapshot
Port - Circuit
#2 Firmware 49
Version 49 23 UINT16 13168 13169 Analog Input 1601 R NV kWh
KWH
Smart Snapshot
Port - Circuit
#3 Firmware 50
Version 50 24 UINT16 13170 13171 Analog Input 1602 R NV kWh
KWH
Smart Snapshot
Port - Circuit
#4 Firmware 51
Version 51 25 UINT16 13172 13173 Analog Input 1603 R NV kWh
KWH
MACSnapshot
Address (Bit- Circuit
33-48)52 52 26 13174 13175 Analog Input 1604 R
R NV kWh
KWH
MACSnapshot
Address (Bit- Circuit
17-32)53 53 27 13176 13177 Analog Input 1605 R
R NV kWh
KWH
MACSnapshot - Circuit
Address (Bit 1-16)54 54 28 13178 13179 Analog Input 1606 R
R NV kWh
KWH Snapshot
Brand Name (16- Registers)
Circuit 55 55 29 44 13180 13181 Analog Input 1607 R
R NV kWh
KWH Snapshot - Circuit 56 56 13182 13183 Analog Input 1608 R kWh Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
KWH Snapshot - Circuit 57 57 13184 13185 Analog Input 1609 R kWh supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
KWH Snapshot - Circuit 58 58 13186 13187 Analog Input 1610 R kWh
KWH Snapshot - Circuit 59 59 13188 13189 Analog Input 1611 R kWh
Meter Configuration
KWH Snapshot - Circuit 60 60 13190 13191 Analog Input 1612 R kWh
Demand # of Sub-Intervals
KWH Snapshot - Circuit 61 61 100 UINT16 13192 13193
Analog Value
Analog Input
1
1613 R/W
R NV kWh 1-6
Demand Sub-Interval
KWH Snapshot Length
- Circuit 62 62 101 UINT16 13194 13195 Analog
Analog Value
Input
2
1614 R/W
R NV Seconds
kWh 0, 10 - 32767 0 = Sync to Comms
Demand Time Stamp
KWH Snapshot - Circuit (Year)
63 63 102 13196 13197 Analog Input 1615 R
R Year
kWh Years since 1900 (118 = 2018)
Demand Time Stamp
KWH Snapshot (Month)
- Circuit 64 64 103 13198 13199 Analog Input 1616 R
R Month
kWh 0 - 11 Month (0 = January)
Demand Time Stamp
KWH Snapshot (Day)
- Circuit 65 65 104 13200 13201 Analog Input 1617 R Day
kWh 1 - 31 Day of the Month
Demand Time Stamp
KWH Snapshot (Weekday)
- Circuit 66 66 105 13202 13203 Analog Input 1618 R Weekday
kWh 0-6 Weekday (1 = Monday)
KWH Snapshot
Demand Time Stamp- Circuit 67
(Hour) 67 106 13204 13205 Analog Input 1619 R kWh
Hour 0 - 23 Hour (13 = 1PM)
KWH Snapshot
Demand Time Stamp - Circuit 68
(Minute) 68 107 13206 13207 Analog Input 1620 R kWh
Minute 0 - 59 Minute
KWH Snapshot
Demand Time Stamp - Circuit 69
(Second) 69 108 13208 13209 Analog Input 1621 R kWh
Seconds 0 - 59 Second
KWH Snapshot - Circuit 70 70 13210 13211 Analog Input 1622 R kWh Writing to RTC will disable NTP by clearing out URL and/or IP Address
KWH
RealSnapshot
Time Clock - Circuit
(Year)71 71 109 UINT16 13212 13213 Analog Input 1623 R
R/W kWh
Year Years since 1900 (118 = 2018)
KWH
Real Snapshot
Time Clock- Circuit
(Month) 72 72 110 UINT16 13214 13215 Analog Input 1624 R
R/W kWh
Month 0 - 11 Month (0 = January)
KWH Device
AnalogObject Local_Date
RealSnapshot
Time Clock - Circuit
(Day)73 73 111 UINT16 13216 13217 Input 1625 R
R/W kWh
Day 1 - 31 Day of the Month
KWHTime
Real Snapshot
Clock -(Weekday)
Circuit 74 74 112 UINT16 13218 13219 Analog Input 1626 R
R/W kWh
Weekday 0-6 Weekday (1 = Monday)
KWH
RealSnapshot
Time Clock - Circuit
(Hour)75 75 113 UINT16 13220 13221 Analog Input 1627 R
R/W kWh
Hour 0 - 23 Hour (13 = 1PM)
KWH Snapshot - Circuit 76 76 13222 13223 Analog Input 1628 R kWh
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
KWH Snapshot - Circuit 77 77 13224 13225 Analog Input 1629 R kWh
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
KWH Snapshot - Circuit 78 78 13226 13227 Analog Input 1630 R kWh
Digital Output #1 116 Binary Output 1 R/W 0, 1
KWH Snapshot - Circuit 79 79 13228 13229 Analog Input 1631 R kWh
Digital Output #2 117 Binary Output 2 R/W 0, 1
KWH Snapshot - Circuit 80 80 13230 13231 Analog Input 1632 R kWh
KWHDigital Input #1
Snapshot State81
- Circuit 81 118 13232 13233
Binary Input
Analog Input
1
1633 R
R kWh 0, 1
KWHDigital Input -#2Circuit
Snapshot State82 82 119 13234 13235 Binary Input
Analog Input
2
1634 R
R kWh 0, 1
Modbus
KWH Slave- Address
Snapshot Circuit 83 83 124 UINT16 13236 13237 Analog Input 1635 R/W
R NV kWh 1 - 254
KWHModbus
Snapshot TCP Port 84
- Circuit 84 125 UINT16 13238 13239 Analog Input 1636 R
R NV kWh 502
IP Address
KWH Snapshot - Circuit 85 85 126 127 13240 13241 Analog Input 1637 R/W
R NV kWh
Meter must be rebooted for new network settings to affect.
Gateway
KWH Snapshot - Circuit 86 86 128 129 13242 13243 Analog Input 1638 R/W
R NV kWh
Device can be rebooted remotely using Global Reset/Command (Register 192)
KWH SnapshotMask- Circuit 87 87 130 131 13244 13245 Analog Input 1639 R
R/W NV kWh
KWH Snapshot - Circuit 88 88 13246 13247 Analog Input 1640 R kWh
KWH Snapshot - Circuit 89 89 13248 13249 Analog Input 1641 R kWh
KWH Snapshot - Circuit 90 90 13250 13251 Analog Input 1642 R kWh

UMG 804
44
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
KWHMeter Information
Snapshot - Circuit 91 91 13252 13253 Analog Input 1643 R kWh
KWH Snapshot - Circuit 92
Serial Number 92 1 2 UINT32 13254 13255 AnalogObject
Device Input 1644
Serial_Number R NV kWh
KWH Snapshot Version
Bootloader - Circuit 93 93 3 UINT16 13256 13257 Analog Input 1645 R NV kWh
KWHFirmware
SnapshotVersion
- Circuit 94 94 4 UINT16 13258 13259 AnalogObject
Device Input 1646
Firmware_Revision R NV kWh
KWH Snapshot
Device -IDCircuit 95 95 5 UINT16 13260 13261 Analog Input 1647 R
R/W NV kWh 15172, 22000 22000 = Janitza Pointmap
KWHPower
Snapshot - Circuit 96
Up Counter 96 6 UINT16 13262 13263 Analog Input 1648 R NV kWh
Uptime 7 8 UINT32 R NV Seconds
CrestPort
Smart Factor
ID #1 10 UINT16 13264 13455 Analog Input 1649 - 1744 R NV
Crest Factor
Smart Port- Circuit
ID #2 1 1 11 UINT16 13264 13265 Analog Input 1649 R NV
See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Crest Factor
Smart Port- Circuit
ID #3 2 2 12 UINT16 13266 13267 Analog Input 1650 R NV
Crest Factor
Smart Port- Circuit
ID #4 3 3 13 UINT16 13268 13269 Analog Input 1651 R NV
Crest
Smart Factor
Port - Circuit
#1 Serial 4
Number 4 14 15 UINT32 13270 13271 Analog Input 1652 R NV
Crest
Smart Factor
Port - Circuit
#2 Serial 5
Number 5 16 17 UINT32 13272 13273 Analog Input 1653 R NV
Crest
Smart Factor
Port - Circuit
#3 Serial 6
Number 6 18 19 UINT32 13274 13275 Analog Input 1654 R NV
Crest
Smart Factor
Port - Circuit
#4 Serial 7
Number 7 20 21 UINT32 13276 13277 Analog Input 1655 R NV
SmartCrest
PortFactor - CircuitVersion
#1 Firmware 8 8 22 UINT16 13278 13279 Analog Input 1656 R NV
SmartCrest
PortFactor - CircuitVersion
#2 Firmware 9 9 23 UINT16 13280 13281 Analog Input 1657 R NV
SmartCrest
PortFactor - CircuitVersion
#3 Firmware 10 10 24 UINT16 13282 13283 Analog Input 1658 R NV
SmartCrest
PortFactor - CircuitVersion
#4 Firmware 11 11 25 UINT16 13284 13285 Analog Input 1659 R
R NV
CrestAddress
MAC Factor -(Bit
Circuit 12
33-48) 12 26 13286 13287 Analog Input 1660 R
R NV
CrestAddress
MAC Factor -(Bit
Circuit 13
17-32) 13 27 13288 13289 Analog Input 1661 R
R NV
Crest Factor - (Bit
MAC Address Circuit 14
1-16) 14 28 13290 13291 Analog Input 1662 R
R NV
Crest Factor - Circuit 15 15 13292 13293 Analog Input 1663 R
Brand Name (16 Registers) 29 44 R NV
Crest Factor - Circuit 16 16 13294 13295 Analog Input 1664 R Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Crest Factor - Circuit 17 17 13296 13297 Analog Input 1665 R supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Crest Factor - Circuit 18 18 13298 13299 Analog Input 1666 R
Crest Factor - Circuit 19 19 13300 13301 Analog Input 1667 R
Meter
Crest Configuration
Factor - Circuit 20 20 13302 13303 Analog Input 1668 R
Demand # of Sub-Intervals
Crest Factor - Circuit 21 21 100 UINT16 13304 13305 Analog
Analog Value
Input
1
1669 R/W
R NV 1-6
Demand Sub-Interval
Crest Factor - Circuit Length
22 22 101 UINT16 13306 13307 Analog
Analog Value
Input 2
1670 R/W
R NV Seconds 0, 10 - 32767 0 = Sync to Comms
Demand
Crest Factor - Circuit(Year)
Time Stamp 23 23 102 13308 13309 Analog Input 1671 R
R Year Years since 1900 (118 = 2018)
Demand Time Stamp
Crest Factor (Month)
- Circuit 24 24 103 13310 13311 Analog Input 1672 R Month 0 - 11 Month (0 = January)
Demand Time -Stamp
Crest Factor Circuit(Day)
25 25 104 13312 13313 Analog Input 1673 R Day 1 - 31 Day of the Month
CrestTime
Demand Factor - Circuit
Stamp 26
(Weekday) 26 105 13314 13315 Analog Input 1674 R Weekday 0-6 Weekday (1 = Monday)
Crest Factor
Demand - Circuit(Hour)
Time Stamp 27 27 106 13316 13317 Analog Input 1675 R Hour 0 - 23 Hour (13 = 1PM)
Crest Time
Demand FactorStamp
- Circuit 28
(Minute) 28 107 13318 13319 Analog Input 1676 R Minute 0 - 59 Minute
Crest Time
Demand FactorStamp
- Circuit 29
(Second) 29 108 13320 13321 Analog Input 1677 R
R Seconds 0 - 59 Second
Crest Factor - Circuit 30 30 13322 13323 Analog Input 1678 R Writing to RTC will disable NTP by clearing out URL and/or IP Address
Crest FactorClock
Real Time - Circuit 31
(Year) 31 109 UINT16 13324 13325 Analog Input 1679 R
R/W Year Years since 1900 (118 = 2018)
CrestTime
Real Factor - Circuit
Clock (Month)32 32 110 UINT16 13326 13327 Analog Input 1680 R
R/W Month 0 - 11 Month (0 = January)
Crest Device
AnalogObject Local_Date
Real Factor - Circuit 33 33 13328 13329 R
Input 1681
Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
Crest Factor - Circuit 34 34 13330 13331 Analog Input 1682 R
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
Crest Factor - Circuit 35 35 13332 13333 Analog Input 1683 R
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
Crest Factor - Circuit 36 36 13334 13335 Analog Input 1684 R
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Crest Factor - Circuit 37 37 13336 13337 Analog Input 1685 R
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Crest Factor - Circuit 38 38 13338 13339 Analog Input 1686 R
Digital Output #1 116 Binary Output 1 R/W 0, 1
Crest Factor - Circuit 39 39 13340 13341 Analog Input 1687 R
Digital
Crest Output
Factor #2 40
- Circuit 40 117 13342 13343
Binary Output
Analog Input
2
1688 R/W
R 0, 1
Digital
Crest Input- Circuit
Factor #1 State 41 41 118 13344 13345 Binary Input
Analog Input
1
1689 R
R 0, 1
Digital
Crest Input- Circuit
Factor #2 State 42 42 119 13346 13347 Binary Input
Analog Input 2
1690 R
R 0, 1
Modbus
Crest Slave
Factor Address
- Circuit 43 43 124 UINT16 13348 13349 Analog Input 1691 R/W
R NV 1 - 254
Modbus TCP Port
Crest Factor - Circuit 44 44 125 UINT16 13350 13351 Analog Input 1692 R NV 502
IP Address
Crest Factor - Circuit 45 45 126 127 13352 13353 Analog Input 1693 R/W
R NV
Meter must be rebooted for new network settings to affect.
Crest Factor - Circuit 46
Gateway 46 128 129 13354 13355 Analog Input 1694 R
R/W NV
Device can be rebooted remotely using Global Reset/Command (Register 192)
Crest Factor
Mask- Circuit 47 47 130 131 13356 13357 Analog Input 1695 R
R/W NV
Crest Factor - Circuit 48 48 13358 13359 Analog Input 1696 R
Crest Factor - Circuit 49 49 13360 13361 Analog Input 1697 R
Crest Factor - Circuit 50 50 13362 13363 Analog Input 1698 R

UMG 804
45
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter
Crest Information
Factor - Circuit 51 51 13364 13365 Analog Input 1699 R
CrestSerial
Factor - Circuit 52
Number 52 1 2 UINT32 13366 13367 AnalogObject
Device Input 1700
Serial_Number R NV
Crest Factor - Version
Bootloader Circuit 53 53 3 UINT16 13368 13369 Analog Input 1701 R
R NV
Crest Factor -Version
Firmware Circuit 54 54 4 UINT16 13370 13371 AnalogObject
Device Input 1702
Firmware_Revision R
R NV
Crest Factor
Device- Circuit
ID 55 55 5 UINT16 13372 13373 Analog Input 1703 R
R/W NV 15172, 22000 22000 = Janitza Pointmap
Crest Factor
Power Up -Counter
Circuit 56 56 6 UINT16 13374 13375 Analog Input 1704 R
R NV
Crest Factor - Circuit 57 57 13376 13377 Analog Input 1705 R
Uptime 7 8 UINT32 R NV Seconds
Crest Factor - Circuit 58 58 13378 13379 Analog Input 1706 R
Smart Port ID #1 10 UINT16 R NV
Crest Factor - Circuit 59 59 13380 13381 Analog Input 1707 R
Smart Port ID #2 11 UINT16 R NV
Crest Factor - Circuit 60 60 13382 13383 Analog Input 1708 R See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
Crest Factor - Circuit 61 61 13384 13385 Analog Input 1709 R
Smart
Crest FactorPort ID #4 62
- Circuit 62 13 UINT16 13386 13387 Analog Input 1710 R
R NV
Smart
CrestPort #1 Serial
Factor Number
- Circuit 63 63 14 15 UINT32 13388 13389 Analog Input 1711 R
R NV
Smart
CrestPort #2 Serial
Factor Number
- Circuit 64 64 16 17 UINT32 13390 13391 Analog Input 1712 R
R NV
Smart
CrestPort #3 Serial
Factor Number
- Circuit 65 65 18 19 UINT32 13392 13393 Analog Input 1713 R NV
Smart
CrestPort #4 Serial
Factor Number
- Circuit 66 66 20 21 UINT32 13394 13395 Analog Input 1714 R NV
Smart PortFactor
Crest #1 Firmware
- CircuitVersion
67 67 22 UINT16 13396 13397 Analog Input 1715 R NV
SmartCrest
PortFactor - CircuitVersion
#2 Firmware 68 68 23 UINT16 13398 13399 Analog Input 1716 R NV
SmartCrest
PortFactor - CircuitVersion
#3 Firmware 69 69 24 UINT16 13400 13401 Analog Input 1717 R NV
SmartCrest
PortFactor - CircuitVersion
#4 Firmware 70 70 25 UINT16 13402 13403 Analog Input 1718 R NV
CrestAddress
MAC Factor -(Bit
Circuit 71
33-48) 71 26 13404 13405 Analog Input 1719 R
R NV
CrestAddress
MAC Factor -(Bit
Circuit 72
17-32) 72 27 13406 13407 Analog Input 1720 R
R NV
Crest Factor - Circuit
MAC Address (Bit 1-16)73 73 28 13408 13409 Analog Input 1721 R
R NV
CrestName
Brand Factor(16- Circuit 74
Registers) 74 29 44 13410 13411 Analog Input 1722 R
R NV
Crest Factor - Circuit 75 75 13412 13413 Analog Input 1723 R Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Crest Factor - Circuit 76 76 13414 13415 Analog Input 1724 R supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Crest Factor - Circuit 77 77 13416 13417 Analog Input 1725 R
Crest Factor - Circuit 78 78 13418 13419 Analog Input 1726 R
Meter Configuration
Crest Factor - Circuit 79 79 13420 13421 Analog Input 1727 R
Demand # of Sub-Intervals
Crest Factor - Circuit 80 80 100 UINT16 13422 13423
Analog Value
Analog Input
1
1728 R/W
R NV 1-6
Demand Sub-Interval
Crest Factor - Circuit Length
81 81 101 UINT16 13424 13425 Analog
Analog Value
Input
2
1729 R/W
R NV Seconds 0, 10 - 32767 0 = Sync to Comms
Demand
Crest Factor - Circuit(Year)
Time Stamp 82 82 102 13426 13427 Analog Input 1730 R
R Year Years since 1900 (118 = 2018)
Demand Time Stamp
Crest Factor - Circuit(Month)
83 83 103 13428 13429 Analog Input 1731 R
R Month 0 - 11 Month (0 = January)
Demand Time -Stamp
Crest Factor Circuit(Day)
84 84 104 13430 13431 Analog Input 1732 R Day 1 - 31 Day of the Month
Demand
CrestTime
FactorStamp (Weekday)
- Circuit 85 85 105 13432 13433 Analog Input 1733 R Weekday 0-6 Weekday (1 = Monday)
Crest Factor
Demand - Circuit(Hour)
Time Stamp 86 86 106 13434 13435 Analog Input 1734 R Hour 0 - 23 Hour (13 = 1PM)
Crest Time
Demand FactorStamp
- Circuit 87
(Minute) 87 107 13436 13437 Analog Input 1735 R Minute 0 - 59 Minute
Crest Time
Demand FactorStamp
- Circuit 88
(Second) 88 108 13438 13439 Analog Input 1736 R Seconds 0 - 59 Second
Crest Factor - Circuit 89 89 13440 13441 Analog Input 1737 R Writing to RTC will disable NTP by clearing out URL and/or IP Address
Crest FactorClock
Real Time - Circuit
(Year)90 90 109 UINT16 13442 13443 Analog Input 1738 R
R/W Year Years since 1900 (118 = 2018)
CrestTime
Real Factor - Circuit
Clock (Month)91 91 110 UINT16 13444 13445 Analog Input 1739 R
R/W Month 0 - 11 Month (0 = January)
Device Object Local_Date
Crest
Real Factor - Circuit
Time Clock (Day)92 92 111 UINT16 13446 13447 Analog Input 1740 R
R/W Day 1 - 31 Day of the Month
Crest
Real TimeFactor
Clock- Circuit
(Weekday)93 93 112 UINT16 13448 13449 Analog Input 1741 R
R/W Weekday 0-6 Weekday (1 = Monday)
Crest Factor
Real Time - Circuit
Clock (Hour)94 94 113 UINT16 13450 13451 Analog Input 1742 R
R/W Hour 0 - 23 Hour (13 = 1PM)
Crest
Real Factor - Circuit
Time Clock (Min)95 95 114 UINT16 13452 13453 AnalogObject
Device Input 1743
Local_Time R
R/W Minute 0 - 59 Minute
CrestTime
Real Factor - Circuit
Clock 96
(Second) 96 115 UINT16 13454 13455 Analog Input 1744 R
R/W Seconds 0 - 59 Second
Digital Output #1 116 Binary Output 1 R/W 0, 1
Breaker Utilization
Digital Output #2 117 13456 13647 AnalogOutput
Binary Input 1745 2- 1840 R
R/W Percent 0, 1 Circuit Utilization = (Current / Breaker Size) * 100
Breaker Utilization
Digital Input #1-StateCircuit 1 1 118 13456 13457 Analog Input
Binary Input 1745
1 R Percent 0, 1
Breaker Utilization
Digital Input #2-StateCircuit 2 2 119 13458 13459 Analog Input
Binary Input 1746
2 R Percent 0, 1
Breaker
Modbus Utilization - Circuit 3
Slave Address 3 124 UINT16 13460 13461 Analog Input 1747 R
R/W NV Percent 1 - 254
Breaker Utilization
Modbus - Circuit 4
TCP Port 4 125 UINT16 13462 13463 Analog Input 1748 R NV Percent 502
Breaker Utilization
IP Address- Circuit 5 5 126 127 13464 13465 Analog Input 1749 R
R/W NV Percent
Meter must be rebooted for new network settings to affect.
Breaker Utilization
Gateway - Circuit 6 6 128 129 13466 13467 Analog Input 1750 R
R/W NV Percent
Device can be rebooted remotely using Global Reset/Command (Register 192)
Breaker Utilization
Mask - Circuit 7 7 130 131 13468 13469 Analog Input 1751 R
R/W NV Percent
Breaker Utilization - Circuit 8 8 13470 13471 Analog Input 1752 R Percent
Breaker Utilization - Circuit 9 9 13472 13473 Analog Input 1753 R Percent
Breaker Utilization - Circuit 10 10 13474 13475 Analog Input 1754 R Percent

UMG 804
46
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter
Breaker Information
Utilization - Circuit 11 11 13476 13477 Analog Input 1755 R Percent
BreakerSerial
Utilization
Number- Circuit 12 12 1 2 UINT32 13478 13479 AnalogObject
Device Input 1756
Serial_Number R NV Percent
Breaker Utilization
Bootloader - Circuit 13
Version 13 3 UINT16 13480 13481 Analog Input 1757 R
R NV Percent
Breaker Utilization
Firmware - Circuit 14
Version 14 4 UINT16 13482 13483 AnalogObject
Device Input 1758
Firmware_Revision R
R NV Percent
Breaker Utilization
Device ID- Circuit 15 15 5 UINT16 13484 13485 Analog Input 1759 R
R/W NV Percent 15172, 22000 22000 = Janitza Pointmap
Breaker Utilization
Power - Circuit 16
Up Counter 16 6 UINT16 13486 13487 Analog Input 1760 R
R NV Percent
Breaker Utilization - Circuit 17 17 13488 13489 Analog Input 1761 R Percent
Uptime 7 8 UINT32 R NV Seconds
Breaker Utilization - Circuit 18 18 13490 13491 Analog Input 1762 R Percent
Smart Port ID #1 10 UINT16 R NV
Breaker Utilization - Circuit 19 19 13492 13493 Analog Input 1763 R Percent
Smart Port ID #2 11 UINT16 R NV
Breaker Utilization - Circuit 20 20 13494 13495 Analog Input 1764 R Percent See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
Breaker Utilization - Circuit 21 21 13496 13497 Analog Input 1765 R Percent
BreakerSmart Port ID- Circuit
Utilization #4 22 22 13 UINT16 13498 13499 Analog Input 1766 R
R NV Percent
Smart Port
Breaker #1 Serial
Utilization Number
- Circuit 23 23 14 15 UINT32 13500 13501 Analog Input 1767 R
R NV Percent
Smart Port
Breaker #2 Serial
Utilization Number
- Circuit 24 24 16 17 UINT32 13502 13503 Analog Input 1768 R
R NV Percent
Smart Port
Breaker #3 Serial
Utilization Number
- Circuit 25 25 18 19 UINT32 13504 13505 Analog Input 1769 R NV Percent
Smart Port
Breaker #4 Serial
Utilization Number
- Circuit 26 26 20 21 UINT32 13506 13507 Analog Input 1770 R NV Percent
Smart Port
Breaker #1 Firmware
Utilization Version
- Circuit 27 27 22 UINT16 13508 13509 Analog Input 1771 R NV Percent
Breaker
Smart PortUtilization
#2 Firmware- Circuit 28
Version 28 23 UINT16 13510 13511 Analog Input 1772 R NV Percent
Breaker
Smart PortUtilization
#3 Firmware- Circuit 29
Version 29 24 UINT16 13512 13513 Analog Input 1773 R NV Percent
Breaker
Smart PortUtilization
#4 Firmware- Circuit 30
Version 30 25 UINT16 13514 13515 Analog Input 1774 R NV Percent
Breaker Utilization
MAC Address (Bit- Circuit
33-48) 31 31 26 13516 13517 Analog Input 1775 R
R NV Percent
Breaker Utilization
MAC Address (Bit- Circuit
17-32) 32 32 27 13518 13519 Analog Input 1776 R
R NV Percent
Breaker
MAC Utilization
Address (Bit - Circuit
1-16) 33 33 28 13520 13521 Analog Input 1777 R
R NV Percent
Breaker Utilization
Brand Name - Circuit 34
(16 Registers) 34 29 44 13522 13523 Analog Input 1778 R
R NV Percent
Breaker Utilization - Circuit 35 35 13524 13525 Analog Input 1779 R Percent Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
Breaker Utilization - Circuit 36 36 13526 13527 Analog Input 1780 R Percent supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
Breaker Utilization - Circuit 37 37 13528 13529 Analog Input 1781 R Percent
Breaker Utilization - Circuit 38 38 13530 13531 Analog Input 1782 R Percent
Meter Configuration
Breaker Utilization - Circuit 39 39 13532 13533 Analog Input 1783 R Percent
Demand
Breaker # of Sub-Intervals
Utilization - Circuit 40 40 100 UINT16 13534 13535
Analog Value
Analog Input
1
1784 R/W
R NV Percent 1-6
DemandUtilization
Breaker Sub-Interval Length
- Circuit 41 41 101 UINT16 13536 13537 Analog
Analog Value
Input
2
1785 R/W
R NV Seconds
Percent 0, 10 - 32767 0 = Sync to Comms
Demand Time Stamp
Breaker Utilization - Circuit(Year)42 42 102 13538 13539 Analog Input 1786 R
R Year
Percent Years since 1900 (118 = 2018)
DemandUtilization
Breaker Time Stamp (Month)
- Circuit 43 43 103 13540 13541 Analog Input 1787 R
R Month
Percent 0 - 11 Month (0 = January)
Demand
Breaker Time Stamp
Utilization (Day)44
- Circuit 44 104 13542 13543 Analog Input 1788 R Day
Percent 1 - 31 Day of the Month
Demand
BreakerTime Stamp- (Weekday)
Utilization Circuit 45 45 105 13544 13545 Analog Input 1789 R Weekday
Percent 0-6 Weekday (1 = Monday)
Breaker
DemandUtilization
Time Stamp - Circuit
(Hour)46 46 106 13546 13547 Analog Input 1790 R Percent
Hour 0 - 23 Hour (13 = 1PM)
Breaker Utilization
Demand Time Stamp - Circuit 47
(Minute) 47 107 13548 13549 Analog Input 1791 R Percent
Minute 0 - 59 Minute
Breaker Utilization
Demand Time Stamp - Circuit 48
(Second) 48 108 13550 13551 Analog Input 1792 R Percent
Seconds 0 - 59 Second
Breaker Utilization - Circuit 49 49 13552 13553 Analog Input 1793 R Percent Writing to RTC will disable NTP by clearing out URL and/or IP Address
Breaker
Real Utilization
Time Clock- (Year)
Circuit 50 50 109 UINT16 13554 13555 Analog Input 1794 R
R/W Percent
Year Years since 1900 (118 = 2018)
Breaker Utilization
Real Time - Circuit 51
Clock (Month) 51 110 UINT16 13556 13557 Analog Input 1795 R
R/W Percent
Month 0 - 11 Month (0 = January)
Breaker Device
AnalogObject Local_Date
RealUtilization
Time Clock- (Day)
Circuit 52 52 111 UINT16 13558 13559 Input 1796 R
R/W Percent
Day 1 - 31 Day of the Month
Breaker Utilization
Real Time - Circuit 53
Clock (Weekday) 53 112 UINT16 13560 13561 Analog Input 1797 R
R/W Percent
Weekday 0-6 Weekday (1 = Monday)
Breaker
Real Utilization
Time Clock-(Hour)
Circuit 54 54 113 UINT16 13562 13563 Analog Input 1798 R
R/W Percent
Hour 0 - 23 Hour (13 = 1PM)
Breaker Utilization - Circuit 55 55 13564 13565 Analog Input 1799 R Percent
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Breaker Utilization - Circuit 56 56 13566 13567 Analog Input 1800 R Percent
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Breaker Utilization - Circuit 57 57 13568 13569 Analog Input 1801 R Percent
Digital Output #1 116 Binary Output 1 R/W 0, 1
Breaker Utilization - Circuit 58 58 13570 13571 Analog Input 1802 R Percent
Digital Output #2 117 Binary Output 2 R/W 0, 1
Breaker Utilization - Circuit 59 59 13572 13573 Analog Input 1803 R Percent
Digital
Breaker Input #1- State
Utilization Circuit 60 60 118 13574 13575
Binary Input
Analog Input
1
1804 R
R Percent 0, 1
Digital
Breaker Input #2- State
Utilization Circuit 61 61 119 13576 13577 Binary Input
Analog Input
2
1805 R
R Percent 0, 1
Modbus Slave Address
Breaker Utilization - Circuit 62 62 124 UINT16 13578 13579 Analog Input 1806 R/W
R NV Percent 1 - 254
Modbus TCP Port
Breaker Utilization - Circuit 63 63 125 UINT16 13580 13581 Analog Input 1807 R
R NV Percent 502
IP Address- Circuit 64
Breaker Utilization 64 126 127 13582 13583 Analog Input 1808 R/W
R NV Percent
Meter must be rebooted for new network settings to affect.
Gateway- Circuit 65
Breaker Utilization 65 128 129 13584 13585 Analog Input 1809 R/W
R NV Percent
Device can be rebooted remotely using Global Reset/Command (Register 192)
Breaker Utilization
Mask - Circuit 66 66 130 131 13586 13587 Analog Input 1810 R
R/W NV Percent
Breaker Utilization - Circuit 67 67 13588 13589 Analog Input 1811 R Percent
Breaker Utilization - Circuit 68 68 13590 13591 Analog Input 1812 R Percent
Breaker Utilization - Circuit 69 69 13592 13593 Analog Input 1813 R Percent

UMG 804
47
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Breaker
MeterUtilization - Circuit 70
Information 70 13594 13595 Analog Input 1814 R Percent
BreakerSerial
Utilization
Number- Circuit 71 71 1 2 UINT32 13596 13597 AnalogObject
Device Input 1815
Serial_Number R
R NV Percent
Breaker Utilization
Bootloader - Circuit 72
Version 72 3 UINT16 13598 13599 Analog Input 1816 R
R NV Percent
Breaker Utilization
Firmware - Circuit 73
Version 73 4 UINT16 13600 13601 AnalogObject
Device Input 1817
Firmware_Revision R
R NV Percent
Breaker Utilization
Device ID- Circuit 74 74 5 UINT16 13602 13603 Analog Input 1818 R
R/W NV Percent 15172, 22000 22000 = Janitza Pointmap
Breaker Utilization - Circuit 75 75 13604 13605 Analog Input 1819 R Percent
Power Up Counter 6 UINT16 R NV
Breaker Utilization - Circuit 76 76 13606 13607 Analog Input 1820 R Percent
Uptime 7 8 UINT32 R NV Seconds
Breaker Utilization - Circuit 77 77 13608 13609 Analog Input 1821 R Percent
Smart Port ID #1 10 UINT16 R NV
Breaker Utilization - Circuit 78 78 13610 13611 Analog Input 1822 R Percent
Smart Port ID #2 11 UINT16 R NV
Breaker Utilization - Circuit 79 79 13612 13613 Analog Input 1823 R Percent See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
BreakerSmart Port ID- Circuit
Utilization #3 80 80 12 UINT16 13614 13615 Analog Input 1824 R
R NV Percent
BreakerSmart Port ID- Circuit
Utilization #4 81 81 13 UINT16 13616 13617 Analog Input 1825 R
R NV Percent
Smart Port
Breaker #1 Serial
Utilization Number
- Circuit 82 82 14 15 UINT32 13618 13619 Analog Input 1826 R
R NV Percent
Smart Port
Breaker #2 Serial
Utilization Number
- Circuit 83 83 16 17 UINT32 13620 13621 Analog Input 1827 R NV Percent
Smart Port
Breaker #3 Serial
Utilization Number
- Circuit 84 84 18 19 UINT32 13622 13623 Analog Input 1828 R NV Percent
Smart Port
Breaker #4 Serial
Utilization Number
- Circuit 85 85 20 21 UINT32 13624 13625 Analog Input 1829 R NV Percent
Breaker
Smart PortUtilization
#1 Firmware- Circuit 86
Version 86 22 UINT16 13626 13627 Analog Input 1830 R NV Percent
Breaker
Smart PortUtilization
#2 Firmware- Circuit 87
Version 87 23 UINT16 13628 13629 Analog Input 1831 R NV Percent
Breaker
Smart PortUtilization
#3 Firmware- Circuit 88
Version 88 24 UINT16 13630 13631 Analog Input 1832 R NV Percent
Breaker
Smart PortUtilization
#4 Firmware- Circuit 89
Version 89 25 UINT16 13632 13633 Analog Input 1833 R NV Percent
Breaker Utilization
MAC Address (Bit- Circuit
33-48) 90 90 26 13634 13635 Analog Input 1834 R NV Percent
Breaker Utilization
MAC Address (Bit- Circuit
17-32) 91 91 27 13636 13637 Analog Input 1835 R NV Percent
Breaker
MAC Utilization
Address (Bit - Circuit
1-16) 92 92 28 13638 13639 Analog Input 1836 R NV Percent
Breaker Utilization
Brand Name - Circuit 93
(16 Registers) 93 29 44 13640 13641 Analog Input 1837 R NV Percent
Brand Name, Model Name and Device Name
Breaker
Model Utilization - Circuit 94
Name (16 Register) 94 45 60 13642 13643 AnalogObject
Device Input 1838
Model_Name R NV Percent
supports up to 32 characters (16 registers)
Breaker
Device Utilization - Circuit 95
Name (16 Registers) 95 61 76 13644 13645 AnalogObject
Device Input 1839
Object_Name R
R/W NV Percent
Breaker Utilization - Circuit 96 96 13646 13647 Analog Input 1840 R Percent
Meter Configuration
Demand # of Sub-Intervals 100 UINT16 Analog Value 1 R/W NV 1-6
DemandTrue Meter Length
Sub-Interval 101 UINT16 Analog Value 2 R/W NV Seconds 0, 10 - 32767 0 = Sync to Comms
MeterTime
Demand Configuration
Stamp (Year) 102 R Year Years since 1900 (118 = 2018)
Demand True
Time Meter
Stamp#1(Month) 1 103 15060 15485 R Month 0 - 11 Add 500 for
Month (0 =next Circuit
January)
Demand Time Stamp (Day) 104 R Day 1 - 31 Day of the Month
Demand # ofTime
Circuits Assigned
Stamp (Weekday) 105 R Weekday 0-6 Weekday (1 = Monday)
DemandAssigned Circuits(Hour)
Time Stamp 106 R NV Hour 0 - 23 Read Only Registers (Use Meter Configuration
Hour (13 = 1PM) registers to configure)
Assigned Circuit
Demand Timeto Stamp
True Meter Circuit 1
(Minute) 107 R NV Minute 0 - 59 Minute
Assigned Circuit
Demand Timeto Stamp
True Meter Circuit 2
(Second) 108 R NV Seconds 0 - 59 Second
Assigned Circuit to True Meter Circuit 3 R NV Writing to RTC will disable NTP by clearing out URL and/or IP Address
Real Time Clock (Year) 109 UINT16 R/W Year Years since 1900 (118 = 2018)
Real TimeCTClock
Size (Month) 110 UINT16 R
R/W NV Amps
Month 0 - 11 Meter(0
Read Only Registers (UseMonth Configuration
= January) registers to configure)
Device Object Local_Date
CTReal
Size Time
- Assigned
Clock Circuit
(Day) 1 111 UINT16 R
R/W NV Amps
Day 1 - 31 Day of the Month
CT Size
Real - Assigned
Time Circuit 2
Clock (Weekday) 112 UINT16 R
R/W NV Amps
Weekday 0-6 Weekday (1 = Monday)
CTReal
SizeTime Clock (Hour)
- Assigned Circuit 3 113 UINT16 R/W
R NV Hour
Amps 0 - 23 Hour (13 = 1PM)
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Real Time ClockSize
Breaker (Second) 115 UINT16 R/W
R NV Seconds
Amps 0 - 59 Read Only Registers (Use MeterSecond
Configuration registers to configure)
BreakerDigital Output #1Circuit 1
Size - Assigned 116 Binary Output 1 R/W
R NV Amps 0, 1
BreakerDigital Output #2Circuit 2
Size - Assigned 117 Binary Output 2 R/W
R NV Amps 0, 1
Digital
Breaker Size Input #1 State
- Assigned Circuit 3 118 Binary Input 1 R NV Amps 0, 1
Digital Input #2 State 119 Binary Input 2 R 0, 1
Modbus Slave
Voltage Address
Phase 124 UINT16 R/W
R NV 1 - 254 Read Only Registers (Use Meter Configuration registers to configure)
Voltage Modbus TCP Port Circuit 1
Phase - Assigned 125 UINT16 R NV 502
Voltage Phase IP Address
- Assigned Circuit 2 126 127 R/W
R NV
Meter must be rebooted for new network settings to affect.
Voltage Phase Gateway
- Assigned Circuit 3 128 129 R/W
R NV
Device can be rebooted remotely using Global Reset/Command (Register 192)
Mask 130 131 R/W NV

Meter Name - 40 Characters (20 Register)

UMG 804
48
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Meter Information
Voltage
Serial Number 1 2 UINT32 Device Object Serial_Number R NV
Frequency
Bootloader Version 3 UINT16 15060 15061 R
R NV Hz
Firmware Version 4 UINT16 Device Object Firmware_Revision R NV
Voltage LN
Device ID 5 UINT16 15062 15069 R
R/W NV Volts 15172, 22000 22000 = Janitza Pointmap
Voltage LNPower
- Average of Assigned Circuit
Up Counter 6 UINT16 15062 15063 R
R NV Volts
Voltage LN -Uptime
Assigned Circuit 1 7 8 UINT32 15064 15065 R
R NV Volts
Seconds
VoltageSmart
LN - Assigned Circuit 2
Port ID #1 10 UINT16 15066 15067 R
R NV Volts
VoltageSmart
LN - Assigned Circuit 3
Port ID #2 11 UINT16 15068 15069 R
R NV Volts
See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port ID #3 12 UINT16 R NV
Voltage
Smart LNID
Port THD#4 13 UINT16 15070 15077 R
R NV Volts
Voltage Smart
LN THDPort
- Average of Number
#1 Serial Assigned Circuit 14 15 UINT32 15070 15071 R
R NV Volts
Voltage
SmartLNPort
THD#2- Assigned Circuit 1
Serial Number 16 17 UINT32 15072 15073 R
R NV Volts
Voltage
SmartLNPort
THD#3- Assigned Circuit 2
Serial Number 18 19 UINT32 15074 15075 R
R NV Volts
Voltage
SmartLNPort
THD#4- Assigned Circuit 3
Serial Number 20 21 UINT32 15076 15077 R
R NV Volts
Smart Port #1 Firmware Version 22 UINT16 R NV
Smart Port #2 Firmware Version 23 UINT16 R NV
True
SmartMeter
Port #3#1 Total/Average
Firmware Version 24 UINT16 R NV
Smart PortEnergy Scale Version
#4 Firmware 25 UINT16 R NV
Power Scale
MAC Address (Bit 33-48) 26 R NV
Current Scale
MAC Address (Bit 17-32) 27 R NV
MACVoltage
AddressScale
(Bit 1-16) 28 R NV
Alarm (16
Brand Name StatusRegisters) 29 44 R NV
kWh 15300 15301 R NV kWh
Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
kVARh 15302 15303 R NV kVARh supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV
kVAh 15304 15305 R NV kVAh
kW
Meter Configuration 15306 15307 R kW
Demand # kVAR
of Sub-Intervals 100 UINT16 15308 15309 Analog Value 1 R
R/W NV kVAR 1-6
kVA
Demand Sub-Interval Length 101 UINT16 15310 15311 Analog Value 2 R
R/W NV kVA
Seconds 0, 10 - 32767 0 = Sync to Comms
Demand Time Current
Stamp (Year) 102 15312 15313 R
R Amps
Year Years since 1900 (118 = 2018)
PowerTime
Demand Factor
StampAverage
(Month) 103 15314 15315 R
R Month 00 -- 1.0
11 AverageMonth
Power(0Factor is not signed
= January)
DemandNeutral
TimeCurrent
Stamp (Day) 104 15316 15317 R Amps
Day 1 - 31 Day of the Month
Current THD Average
Demand Time Stamp (Weekday) 105 15318 15319 R
R Percent
Weekday 0-6 Weekday (1 = Monday)
DemandMax Time Current
Stamp (Hour) 106 15320 15321 R
R Amps
Hour 0 - 23 Hour (13 = 1PM)
Demand Time MaxStamp
kW (Minute) 107 15322 15323 R
R kW
Minute 0 - 59 Minute
Current Demand 15324 15325 R Amps
Demand Time Stamp (Second) 108 R Seconds 0 - 59 Second
kW Demand 15326 15327 R kW
Writing to RTC will disable NTP by clearing out URL and/or IP Address
Max Current Demand 15328 15329 R Amps
Real Time Clock (Year) 109 UINT16 R/W Year Years since 1900 (118 = 2018)
Max kW Demand 15330 15331 R kW
Real Time Clock (Month) 110 UINT16 R/W Month 0 - 11 Month (0 = January)
KWH Snapshot 15332 15333 Device Object Local_Date R kWh
Real Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
Crest Factor 15334 15335 R
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
True Meter #1 Circuit 1
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Energy Scale
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Power Scale
Digital Output #1 116 Binary Output 1 R/W 0, 1
Current Scale
Digital Output #2 117 Binary Output 2 R/W 0, 1
Voltage Scale
Digital Input #1 State 118 Binary Input 1 R 0, 1
Alarm Status
Digital Input #2 State 119 Binary Input 2 R 0, 1
kWh 15350 15351 R NV kWh
Modbus Slave Address 124 UINT16 R/W NV 1 - 254
kVARh 15352 15353 R NV kVARh
Modbus TCP Port 125 UINT16 R NV 502
kVAh 15354 15355 R NV kVAh
IP Address 126 127 R/W NV
kW 15356 15357 R kW Meter must be rebooted for new network settings to affect.
Gateway 128 129 R/W NV
kVAR 15358 15359 R kVAR Device can be rebooted remotely using Global Reset/Command (Register 192)
Mask 130 131 R/W NV
kVA 15360 15361 R kVA
Current 15362 15363 R Amps
Power Factor 15364 15365 R -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)

UMG 804
49
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
Current
Meter Angle
Information 15366 15367 R Degrees
Percent
Serial THD
Number 1 2 UINT32 15368 15369 Device Object Serial_Number R
R NV Percent
Max Current
Bootloader Version 3 UINT16 15370 15371 R
R NV Amps
Max kW
Firmware Version 4 UINT16 15372 15373 Device Object Firmware_Revision R
R NV kW
Current Demand
Device ID 5 UINT16 15374 15375 R
R/W NV Amps 15172, 22000 22000 = Janitza Pointmap
kW Demand 15376 15377 R kW
Power Up Counter 6 UINT16 R NV
Max Current Demand 15378 15379 R Amps
Uptime 7 8 UINT32 R NV Seconds
Max kW Demand 15380 15381 R kW
Smart Port ID #1 10 UINT16 R NV
KWH Snapshot 15382 15383 R kWh
Smart Port ID #2 11 UINT16 R NV
Crest Factor 15384 15385 R See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface Card, 4=DIN RAIL CT Interface Floating Board
Smart Port
Breaker ID #3
Utilization 12 UINT16 15386 15387 R
R NV Percent (Current / Breaker Size) * 100
Smart Port ID #4 13 UINT16 R NV
Smart
TruePort #1 Serial
Meter Number
#1 Circuit 2 14 15 UINT32 R NV
Smart Port #2 Serial
Energy ScaleNumber 16 17 UINT32 R NV
Smart Port #3 Serial
Power Scale Number 18 19 UINT32 R NV
Smart Port #4 Serial
Current ScaleNumber 20 21 UINT32 R NV
Smart Port #1 Firmware
Voltage Scale Version 22 UINT16 R NV
Smart PortAlarm
#2 Firmware
Status Version 23 UINT16 R NV
Smart Port #3kWh
Firmware Version 24 UINT16 15400 15401 R
R NV
NV kWh
Smart Port #4kVARh
Firmware Version 25 UINT16 15402 15403 R
R NV
NV kVARh
MAC AddresskVAh(Bit 33-48) 26 15404 15405 R
R NV
NV kVAh
MAC Address kW(Bit 17-32) 27 15406 15407 R
R NV kW
MAC Address
kVAR(Bit 1-16) 28 15408 15409 R
R NV kVAR
Brand NamekVA (16 Registers) 29 44 15410 15411 R
R NV kVA Brand Name, Model Name and Device Name
Model Name (16 Register)
Current 45 60 15412 15413
Device Object Model_Name R
R NV Amps supports up to 32 characters (16 registers)
Device Power
Name (16 Registers)
Factor 61 76 15414 15415
Device Object Object_Name R/W
R NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Current Angle 15416 15417 R Degrees
Meter Configuration
Percent THD 15418 15419 R Percent
Demand # ofCurrent
Max Sub-Intervals 100 UINT16 15420 15421 Analog Value 1 R/W
R NV Amps 1-6
Demand Sub-Interval
Max kW Length 101 UINT16 15422 15423 Analog Value 2 R/W
R NV Seconds
kW 0, 10 - 32767 0 = Sync to Comms
Demand TimeDemand
Current Stamp (Year) 102 15424 15425 R Year
Amps Years since 1900 (118 = 2018)
Demand kW
Time Stamp (Month)
Demand 103 15426 15427 R Month
kW 0 - 11 Month (0 = January)
Demand Time Stamp
Max Current Demand(Day) 104 15428 15429 R Day
Amps 1 - 31 Day of the Month
DemandMax
TimekW Demand
Stamp (Weekday) 105 15430 15431 R kW
Weekday 0-6 Weekday (1 = Monday)
DemandKWH Snapshot
Time Stamp (Hour) 106 15432 15433 R kWh
Hour 0 - 23 Hour (13 = 1PM)
Crest Stamp
Demand Time Factor (Minute) 107 15434 15435 R
R Minute 0 - 59 Minute
Breaker
Demand Time Utilization
Stamp (Second) 108 15436 15437 R
R Percent
Seconds 0 - 59 (Current / Breaker
Second Size) * 100
Writing to RTC will disable NTP by clearing out URL and/or IP Address
True
Real Meter #1 Circuit
Time Clock (Year)3 109 UINT16 R/W Year Years since 1900 (118 = 2018)
Energy
Real Time Scale
Clock (Month) 110 UINT16 R/W Month 0 - 11 Month (0 = January)
Device Object Local_Date
Real Power Scale(Day)
Time Clock 111 UINT16 R/W Day 1 - 31 Day of the Month
Current
Real Time ClockScale
(Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
Real Voltage
Time ClockScale
(Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
Real Alarm Status(Min)
Time Clock 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Real Time kWh
Clock (Second) 115 UINT16 15450 15451 R
R/W NV kWh
Seconds 0 - 59 Second
DigitalkVARh
Output #1 116 15452 15453 Binary Output 1 R
R/W NV kVARh 0, 1
DigitalkVAh
Output #2 117 15454 15455 Binary Output 2 R
R/W NV kVAh 0, 1
kW #1 State
Digital Input 118 15456 15457 Binary Input 1 R kW 0, 1
kVAR#2 State
Digital Input 119 15458 15459 Binary Input 2 R kVAR 0, 1
Modbus SlavekVA Address 124 UINT16 15460 15461 R
R/W NV kVA 1 - 254
ModbusCurrent
TCP Port 125 UINT16 15462 15463 R NV Amps 502
Power Factor
IP Address 126 127 15464 15465 R
R/W NV -1.0 - 1.0 Positive for Leading (Capacitive), Negative for Lagging (Inductive)
Meter must be rebooted for new network settings to affect.
Current
GatewayAngle 128 129 15466 15467 R
R/W NV Degrees
Device can be rebooted remotely using Global Reset/Command (Register 192)
Percent
MaskTHD 130 131 15468 15469 R
R/W NV Percent
Max Current 15470 15471 R Amps
Max kW 15472 15473 R kW
Current Demand 15474 15475 R Amps

UMG 804
50
Modbus address list
Modbus Registers
Bacnet Objects
Integer Float
Description # Start (MSW) End (LSW) Scale Type MSW LSW Object Type Instance # R/W NV Units Range Notes
kW Information
Meter Demand 15476 15477 R kW
MaxSerial
Current Demand
Number 1 2 UINT32 15478 15479 Device Object Serial_Number R
R NV Amps
Max kW Demand
Bootloader Version 3 UINT16 15480 15481 R
R NV kW
KWH Snapshot
Firmware Version 4 UINT16 15482 15483 Device Object Firmware_Revision R
R NV kWh
Crest Factor
Device ID 5 UINT16 15484 15485 R
R/W NV 15172, 22000 22000 = Janitza Pointmap
Breaker Utilization 15486 15487 R Percent (Current / Breaker Size) * 100
Power Up Counter 6 UINT16 R NV
Uptime 7 8 UINT32 R NV Seconds
Smart Port ID #1 10 UINT16 R NV
True Meter #2
Smart Port ID #2
2
11 UINT16
15500 15999
R NV
Meter #2 = (Meter #1 + 500)
True Meter #3 3 16000 16499 See Notes 0=Nothing Connected, 1=DIN RAIL CT Interface
Meter Card,#24=DIN
#3 = (Meter RAIL CT Interface Floating Board
+ 500)
Smart Port ID #3 12 UINT16 R NV
Smart Port ID #4 13 UINT16 R NV
Smart Port #1 Serial Number 14 15 UINT32 R NV
Smart Port #2 Serial Number 16 17 UINT32 R NV
Smart Port #3 Serial Number 18 19 UINT32 R NV
Smart Port #4 Serial Number 20 21 UINT32 R NV
Smart Port #1 Firmware Version 22 UINT16 R NV
Smart Port #2 Firmware Version 23 UINT16 R NV
Smart Port #3 Firmware Version 24 UINT16 R NV
Smart Port #4 Firmware Version 25 UINT16 R NV
MAC Address (Bit 33-48) 26 R NV
MAC Address (Bit 17-32) 27 R NV
MAC Address (Bit 1-16) 28 R NV
Brand Name (16 Registers) 29 44 R NV
Brand Name, Model Name and Device Name
Model Name (16 Register) 45 60 Device Object Model_Name R NV
supports up to 32 characters (16 registers)
Device Name (16 Registers) 61 76 Device Object Object_Name R/W NV

Meter Configuration
Demand # of Sub-Intervals 100 UINT16 Analog Value 1 R/W NV 1-6
Demand Sub-Interval Length 101 UINT16 Analog Value 2 R/W NV Seconds 0, 10 - 32767 0 = Sync to Comms
Demand Time Stamp (Year) 102 R Year Years since 1900 (118 = 2018)
Demand Time Stamp (Month) 103 R Month 0 - 11 Month (0 = January)
Demand Time Stamp (Day) 104 R Day 1 - 31 Day of the Month
Demand Time Stamp (Weekday) 105 R Weekday 0-6 Weekday (1 = Monday)
Demand Time Stamp (Hour) 106 R Hour 0 - 23 Hour (13 = 1PM)
Demand Time Stamp (Minute) 107 R Minute 0 - 59 Minute
Demand Time Stamp (Second) 108 R Seconds 0 - 59 Second
Writing to RTC will disable NTP by clearing out URL and/or IP Address
Real Time Clock (Year) 109 UINT16 R/W Year Years since 1900 (118 = 2018)
Real Time Clock (Month) 110 UINT16 R/W Month 0 - 11 Month (0 = January)
Device Object Local_Date
Real Time Clock (Day) 111 UINT16 R/W Day 1 - 31 Day of the Month
Real Time Clock (Weekday) 112 UINT16 R/W Weekday 0-6 Weekday (1 = Monday)
Real Time Clock (Hour) 113 UINT16 R/W Hour 0 - 23 Hour (13 = 1PM)
Real Time Clock (Min) 114 UINT16 Device Object Local_Time R/W Minute 0 - 59 Minute
Real Time Clock (Second) 115 UINT16 R/W Seconds 0 - 59 Second
Digital Output #1 116 Binary Output 1 R/W 0, 1
Digital Output #2 117 Binary Output 2 R/W 0, 1
Digital Input #1 State 118 Binary Input 1 R 0, 1
Digital Input #2 State 119 Binary Input 2 R 0, 1
Modbus Slave Address 124 UINT16 R/W NV 1 - 254
Modbus TCP Port 125 UINT16 R NV 502
IP Address 126 127 R/W NV
Meter must be rebooted for new network settings to affect.
Gateway 128 129 R/W NV
Device can be rebooted remotely using Global Reset/Command (Register 192)
Mask 130 131 R/W NV

UMG 804