PKA-RP2.5FAL Pka-Rp3Fal Pka-Rp4Fal: Technical & Service Manual
PKA-RP2.5FAL Pka-Rp3Fal Pka-Rp4Fal: Technical & Service Manual
PKA-RP2.5FAL Pka-Rp3Fal Pka-Rp4Fal: Technical & Service Manual
28 11:14 AM Page 1
CONTENTS
1. COMBINATION OF
INDOOR AND OUTDOOR UNITS ····················2
2. SAFETY PRECAUTION ····································3
3. PART NAMES AND FUNCTIONS·····················6
Model name 4. SPECIFICATIONS ·············································8
Indoor unit
indication 5. DATA································································13
6. OUTLINES AND DIMENSIONS ······················33
7. WIRING DIAGRAM ·········································35
8. REFRIGERANT SYSTEM DIAGRAM ·············36
9. TROUBLESHOOTING·····································37
10. DISASSEMBLY PROCEDURE ·······················47
11. PARTS LIST ····················································50
12. OPTIONAL PARTS··························Back Cover
Remote controller
OC301-A--1.qxp 04.4.28 11:14 AM Page 2
(R410A Inverter)
Outdoor unit [OC294 REVISED EDITION-A]
Heat pump type
Indoor unit
PUHZ-RP
2.5VHA 3VHA 4VHA
4VHA1
PKA-RP2.5FAL — —
PKA-RP3FAL — —
PKA-RP4FAL — —
PKA-RP2.5FAL — — — — — —
Heat pump without
electric heater
or PKA-RP3FAL — — — —
Cooling only
PKA-RP4FAL — — — — — —
VGAA1.UK YGAA1.UK VGAA1.UK YGAA1.UK VGAA1.UK YGAA1.UK VGAA1.UK YGAA1.UK VGAA1.UK YGAA1.UK VGAA1.UK YGAA1.UK
PKA-RP2.5FAL — — — — — — — —
Heat pump without
electric heater
or PKA-RP3FAL — — — — — — — —
Cooling only
PKA-RP4FAL — — — — — — — —
2
OC301-A--1.qxp 04.4.28 11:14 AM Page 3
2 SAFETY PRECAUTION
Do not use the existing refrigerant piping. Use liquid refrigerant to seal the system.
The old refrigerant and lubricant in the existing piping If gas refrigerant is used to seal the system, the composition
contains a large amount of chlorine which may cause the of the refrigerant in the cylinder will change and performance
lubricant deterioration of the new unit. may drop.
Use “low residual oil piping” Do not use a refrigerant other than R407C.
If there is a large amount of residual oil (hydraulic oil, etc.) If another refrigerant (R22, etc.) is used, the chlorine in the
inside the piping and joints, deterioration of the lubricant refrigerant may cause the lubricant deterioration.
will result.
Store the piping to be used during installation Use a vacuum pump with a reverse flow check valve.
indoors with keep both ends sealed until just The vacuum pump oil may flow back into the refrigerant
before brazing. cycle and cause the lubricant deterioration.
(Store elbows and other joints in a plastic bag.)
If dust, dirt, or water enters the refrigerant cycle, Ventilate the room if refrigerant leaks during
deterioration of the oil and compressor trouble may result. operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
Use ESTR , ETHER or HAB as the lubricant to
coat flares and flange connection parts.
If large amount of mineral oil enter, that can cause
deterioration of refrigerant oil etc.
Unit
Gravimeter
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
3
OC301-A--1.qxp 04.4.28 11:14 AM Page 4
4
OC301-A--1.qxp 04.4.28 11:14 AM Page 5
Use new refrigerant pipes. Do not use refrigerant other than R410A.
In case of using the existing pipes for R22, be careful with If other refrigerant (R22 etc.) is used, chlorine in refrige-
the followings. rant can cause deterioration of refrigerant oil etc.
· For RP4 be sure to perform replacement operation before
test run.
· Change flare nut to the one provided with this product.
Use a vacuum pump with a reverse flow check
Use a newly flared pipe. valve.
· Avoid using thin pipes. Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
If dirt, dust or moisture enter into refrigerant cycle, that can If dirt, dust or moisture enter into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of com- cause deterioration of refrigerant oil or malfunction of com-
pressor. pressor.
5
OC301-A--1.qxp 04.4.28 11:14 AM Page 6
Unit
Gravimeter
No. Specifications
1 Gauge manifold ·Only for R410A
·Use the existing fitting specifications. (UNF1/2)
·Use high-tension side pressure of 5.3MPa·G or over.
2 Charge hose ·Only for R410A
·Use pressure performance of 5.09MPa·G or over.
3 Electronic scale
4 Gas leak detector ·Use the detector for R134a, R407C or R410A.
5 Adaptor for reverse flow check ·Attach on vacuum pump.
6 Refrigerant charge base
7 Refrigerant cylinder ·Only for R410A Top of cylinder (Pink)
Cylinder with syphon
8 Refrigerant recovery equipment
Guide vane
Air flow can be changed to horizontally
by moving the Guide vane to the left or Swing louvers
right.
Disperses airflow up and
down as well as adjusts the
angle of air flow direction.
Air outlet Air outlet
6
OC301-A--1.qxp 04.4.28 11:14 AM Page 7
display
Lights up while transmission to the indoor
unit is mode using switches.
display
SET TEMP. display indicates desired temper-
ature set.
“ ”“ ” display
AMPM
Displays the order of timer operation.
NOT AVAILABLE
display “ ”“ ” display
ON/OFF TEMP Displays whether timer is on or off.
The vertical direction of air flow is indicated.
display
FAN SPEED display indicates which fan
button
speed has been selected. SET TEMPERATURE button sets any desired
room temperature.
FAN AUTO STOP
ON/OFF button
The unit is turned ON and OFF alternately MODE VANE AUTO START
each time the button is pressed. TIMER CONTROL buttons
CHECK LOUVER h AUTO STOP (OFF timer): when this switch
is set, the air conditioner will be au-
FAN SPEED SELECT button tomatically stopped at the preset time.
Used to change the fan speed. TEST RUN min AUTO START (ON timer): when this switch
is set, the air conditioner will be automatical-
ly started at the preset time.
MODE SELECT button SET RESET CLOCK
LOUVER button
CHECK-TEST RUN button
This switch the horizontal fan motion ON
Only press this button to perform an inspec- and OFF.
tion check or test operation.
(Not available for this model.)
Do not use it for normal operation.
CLOCK button
VANE CONTROL button
RESET button
Used to change the air flow direction.
SET button
7
OC301-A--1.qxp 04.4.28 11:14 AM Page 8
4 SPECIFICATIONS
4-1. Heat pump type (1)
Service Ref. PKA-RP2.5FAL
Item
Function Cooling Heating
Btu/h 20,500 23,900
Capacity
W 6,000(2,700~6,700) 7,000(2,800~8,200)
Total input kW 1.55 2.01
Service Ref. PKA-RP2.5FAL
Power supply(phase, cycle, voltage) Single phase, 50Hz, 220-230-240V
Input kW 0.09 0.09
Running current A 0.43 0.43
Starting current A 0.80 0.80
External finish Munsell 3.4Y 7.7/0.8
Heat exchanger Plate fin coil
INDOOR UNIT
4. Above data based on indicated voltage 5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.
Indoor Unit Single phase 230V 50Hz
Outdoor Unit Single phase 230V 50Hz
8
OC301-A--1.qxp 04.4.28 11:14 AM Page 9
4. Above data based on indicated voltage 5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.
Indoor Unit Single phase 230V 50Hz
Outdoor Unit Single phase 230V 50Hz
9
OC301-A--1.qxp 04.4.28 11:14 AM Page 10
4. Above data based on indicated voltage 5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.
Indoor Unit Single phase 230V 50Hz
Outdoor Unit 3 phase 400V 50Hz
10
OC301-A--1.qxp 04.4.28 11:14 AM Page 11
4. Above data based on indicated voltage 5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.
Indoor Unit Single phase 230V 50Hz
Outdoor Unit 3 phase 400V 50Hz
11
OC301-A--1.qxp 04.4.28 11:14 AM Page 12
3. Guaranteed voltage
198~264V, 50Hz
5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.
12
OC301-A--1.qxp 04.4.28 11:14 AM Page 13
3. Guaranteed voltage
198~264V, 50Hz
5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.
13
OC301-A--1.qxp 04.4.28 11:14 AM Page 14
5 DATA
14
OC301-A--1.qxp 04.4.28 11:14 AM Page 15
COOLING CAPACITY(2)
PKA-RP2.5FAL / PUHZ-RP2.5VHA
(230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 35 40 45
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 5,340 3,898 0.73 1.49 5,100 3,723 0.73 1.60 4,860 3,548 0.73 1.73
20 18 5,760 3,514 0.61 1.53 5,580 3,404 0.61 1.64 5,220 3,184 0.61 1.77
20 20 6,240 3,058 0.49 1.57 6,000 2,940 0.49 1.67 5,640 2,764 0.49 1.80
22 16 5,340 4,325 0.81 1.49 5,100 4,131 0.81 1.60 4,860 3,937 0.81 1.73
22 18 5,760 3,974 0.69 1.53 5,580 3,850 0.69 1.64 5,220 3,602 0.69 1.77
22 20 6,240 3,557 0.57 1.57 6,000 3,420 0.57 1.67 5,640 3,215 0.57 1.80
24 16 5,340 4,753 0.89 1.49 5,100 4,539 0.89 1.60 4,860 4,325 0.89 1.73
24 18 5,760 4,435 0.77 1.53 5,580 4,297 0.77 1.64 5,220 4,019 0.77 1.77
24 20 6,240 4,056 0.65 1.57 6,000 3,900 0.65 1.67 5,640 3,666 0.65 1.80
24 22 6,720 3,562 0.53 1.60 6,480 3,434 0.53 1.72 6,120 3,244 0.53 1.83
26 16 5,340 5,180 0.97 1.49 5,100 4,947 0.97 1.60 4,860 4,714 0.97 1.73
26 18 5,760 4,896 0.85 1.53 5,580 4,743 0.85 1.64 5,220 4,437 0.85 1.77
26 20 6,240 4,555 0.73 1.57 6,000 4,380 0.73 1.67 5,640 4,117 0.73 1.80
26 22 6,720 4,099 0.61 1.60 6,480 3,953 0.61 1.72 6,120 3,733 0.61 1.83
27 16 5,340 5,340 1.00 1.49 5,100 5,100 1.00 1.60 4,860 4,860 1.00 1.73
27 18 5,760 5,126 0.89 1.53 5,580 4,966 0.89 1.64 5,220 4,646 0.89 1.77
27 20 6,240 4,805 0.77 1.57 6,000 4,620 0.77 1.67 5,640 4,343 0.77 1.80
27 22 6,720 4,368 0.65 1.60 6,480 4,212 0.65 1.72 6,120 3,978 0.65 1.83
28 16 5,340 5,340 1.00 1.49 5,100 5,100 1.00 1.60 4,860 4,860 1.00 1.73
28 18 5,760 5,357 0.93 1.53 5,580 5,189 0.93 1.64 5,220 4,855 0.93 1.77
28 20 6,240 5,054 0.81 1.57 6,000 4,860 0.81 1.67 5,640 4,568 0.81 1.80
28 22 6,720 4,637 0.69 1.60 6,480 4,471 0.69 1.72 6,120 4,223 0.69 1.83
30 16 5,340 5,340 1.00 1.49 5,100 5,100 1.00 1.60 4,860 4,860 1.00 1.73
30 18 5,760 5,760 1.00 1.53 5,580 5,580 1.00 1.64 5,220 5,220 1.00 1.77
30 20 6,240 5,554 0.89 1.57 6,000 5,340 0.89 1.67 5,640 5,020 0.89 1.80
30 22 6,720 5,174 0.77 1.60 6,480 4,990 0.77 1.72 6,120 4,712 0.77 1.83
32 16 5,340 5,340 1.00 1.49 5,100 5,100 1.00 1.60 4,860 4,860 1.00 1.73
32 18 5,760 5,760 1.00 1.53 5,580 5,580 1.00 1.64 5,220 5,220 1.00 1.77
32 20 6,240 6,053 0.97 1.57 6,000 5,820 0.97 1.67 5,640 5,471 0.97 1.80
32 22 6,720 5,712 0.85 1.60 6,480 5,508 0.85 1.72 6,120 5,202 0.85 1.83
34 16 5,340 5,340 1.00 1.49 5,100 5,100 1.00 1.60 4,860 4,860 1.00 1.73
34 18 5,760 5,760 1.00 1.53 5,580 5,580 1.00 1.64 5,220 5,220 1.00 1.77
34 20 6,240 6,240 1.00 1.57 6,000 6,000 1.00 1.67 5,640 5,640 1.00 1.80
34 22 6,720 6,250 0.93 1.60 6,480 6,026 0.93 1.72 6,120 5,692 0.93 1.83
15
OC301-A--1.qxp 04.4.28 11:14 AM Page 16
COOLING CAPACITY(3)
PKA-RP3FAL / PUHZ-RP3VHA
(230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 20 25 30
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 7,029 4,709 0.67 1.58 6,816 4,567 0.67 1.67 6,603 4,424 0.67 1.77
20 18 7,526 4,139 0.55 1.61 7,313 4,022 0.55 1.70 7,065 3,885 0.55 1.82
20 20 8,094 3,480 0.43 1.66 7,917 3,404 0.43 1.74 7,704 3,313 0.43 1.86
22 16 7,029 5,272 0.75 1.58 6,816 5,112 0.75 1.67 6,603 4,952 0.75 1.77
22 18 7,526 4,741 0.63 1.61 7,313 4,607 0.63 1.70 7,065 4,451 0.63 1.82
22 20 8,094 4,128 0.51 1.66 7,917 4,037 0.51 1.74 7,704 3,929 0.51 1.86
24 16 7,029 5,834 0.83 1.58 6,816 5,657 0.83 1.67 6,603 5,480 0.83 1.77
24 18 7,526 5,343 0.71 1.61 7,313 5,192 0.71 1.70 7,065 5,016 0.71 1.82
24 20 8,094 4,775 0.59 1.66 7,917 4,671 0.59 1.74 7,704 4,545 0.59 1.86
24 22 8,627 4,054 0.47 1.70 8,449 3,971 0.47 1.80 8,236 3,871 0.47 1.92
26 16 7,029 6,396 0.91 1.58 6,816 6,203 0.91 1.67 6,603 6,009 0.91 1.77
26 18 7,526 5,946 0.79 1.61 7,313 5,777 0.79 1.70 7,065 5,581 0.79 1.82
26 20 8,094 5,423 0.67 1.66 7,917 5,304 0.67 1.74 7,704 5,161 0.67 1.86
26 22 8,627 4,745 0.55 1.70 8,449 4,647 0.55 1.80 8,236 4,530 0.55 1.92
27 16 7,029 6,678 0.95 1.58 6,816 6,475 0.95 1.67 6,603 6,273 0.95 1.77
27 18 7,526 6,247 0.83 1.61 7,313 6,070 0.83 1.70 7,,065 5,864 0.83 1.82
27 20 8,094 5,747 0.71 1.66 7,917 5,621 0.71 1.74 7,704 5,469 0.71 1.86
27 22 8,627 5,090 0.59 1.70 8,449 4,985 0.59 1.80 8,236 4,859 0.59 1.92
28 16 7,029 6,959 0.99 1.58 6,816 6,748 0.99 1.67 6,603 6,537 0.99 1.77
28 18 7,526 6,548 0.87 1.61 7,313 6,362 0.87 1.70 7,065 6,146 0.87 1.82
28 20 8,094 6,071 0.75 1.66 7,917 5,937 0.75 1.74 7,704 5,778 0.75 1.86
28 22 8,627 5,435 0.63 1.70 8,449 5,323 0.63 1.80 8,236 5,189 0.63 1.92
30 16 7,029 7,029 1.00 1.58 6,816 6,816 1.00 1.67 6,603 6,603 1.00 1.77
30 18 7,526 7,150 0.95 1.61 7,313 6,947 0.95 1.70 7,065 6,711 0.95 1.82
30 20 8,094 6,718 0.83 1.66 7,917 6,571 0.83 1.74 7,704 6,394 0.83 1.86
30 22 8,627 6,125 0.71 1.70 8,449 5,999 0.71 1.80 8,236 5,848 0.71 1.92
32 16 7,029 7,029 1.00 1.58 6,816 6,816 1.00 1.67 6,603 6,603 1.00 1.77
32 18 7,526 7,526 1.00 1.61 7,313 7,313 1.00 1.70 7,065 7,065 1.00 1.82
32 20 8,094 7,366 0.91 1.66 7,917 7,204 0.91 1.74 7,704 7,010 0.91 1.86
32 22 8,627 6,815 0.79 1.70 8,449 6,675 0.79 1.80 8,236 6,506 0.79 1.92
34 16 7,029 7,029 1.00 1.58 6,816 6,816 1.00 1.67 6,603 6,603 1.00 1.77
34 18 7,526 7,526 1.00 1.61 7,313 7,313 1.00 1.70 7,065 7,065 1.00 1.82
34 20 8,094 8,013 0.99 1.66 7,917 7,837 0.99 1.74 7,704 7,626 0.99 1.86
34 22 8,627 7,505 0.87 1.70 8,449 7,351 0.87 1.80 8,236 7,165 0.87 1.92
16
OC301-A--1.qxp 04.4.28 11:14 AM Page 17
COOLING CAPACITY(4)
PKA-RP3FAL / PUHZ-RP3VHA
(230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 35 40 45
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 6,319 4,234 0.67 1.90 6,035 4,043 0.67 2.04 5,751 3,853 0.67 2.21
20 18 6,816 3,749 0.55 1.95 6,603 3,632 0.55 2.10 6,177 3,397 0.55 2.26
20 20 7,384 3,175 0.43 2.00 7,100 3,053 0.43 2.14 6,674 2,870 0.43 2.30
22 16 6,319 4,739 0.75 1.90 6,035 4,526 0.75 2.04 5,751 4,313 0.75 2.21
22 18 6,816 4,294 0.63 1.95 6,603 4,160 0.63 2.10 6,177 3,892 0.63 2.26
22 20 7,384 3,766 0.51 2.00 7,100 3,621 0.51 2.14 6,674 3,404 0.51 2.30
24 16 6,319 5,245 0.83 1.90 6,035 5,009 0.83 2.04 5,751 4,773 0.83 2.21
24 18 6,816 4,839 0.71 1.95 6,603 4,688 0.71 2.10 6,177 4,386 0.71 2.26
24 20 7,384 4,357 0.59 2.00 7,100 4,189 0.59 2.14 6,674 3,938 0.59 2.30
24 22 7,952 3,737 0.47 2.04 7,668 3,604 0.47 2.20 7,242 3,404 0.47 2.34
26 16 6,319 5,750 0.91 1.90 6,035 5,492 0.91 2.04 5,751 5,233 0.91 2.21
26 18 6,816 5,385 0.79 1.95 6,603 5,216 0.79 2.10 6,177 4,880 0.79 2.26
26 20 7,384 4,947 0.67 2.00 7,100 4,757 0.67 2.14 6,674 4,472 0.67 2.30
26 22 7,952 4,374 0.55 2.04 7,668 4,217 0.55 2.20 7,242 3,983 0.55 2.34
27 16 6,319 6,003 0.95 1.90 6,035 5,733 0.95 2.04 5,751 5,463 0.95 2.21
27 18 6,816 5,657 0.83 1.95 6,603 5,480 0.83 2.10 6,177 5,127 0.83 2.26
27 20 7,384 5,243 0.71 2.00 7,100 5,041 0.71 2.14 6,674 4,739 0.71 2.30
27 22 7,952 4,692 0.59 2.04 7,668 4,524 0.59 2.20 7,242 4,273 0.59 2.34
28 16 6,319 6,256 0.99 1.90 6,035 5,975 0.99 2.04 5,751 5,693 0.99 2.21
28 18 6,816 5,930 0.87 1.95 6,603 5,745 0.87 2.10 6,177 5,374 0.87 2.26
28 20 7,384 5,538 0.75 2.00 7,100 5,325 0.75 2.14 6,674 5,006 0.75 2.30
28 22 7,952 5,010 0.63 2.04 7,668 4,831 0.63 2.20 7,242 4,562 0.63 2.34
30 16 6,319 6,319 1.00 1.90 6,035 6,035 1.00 2.04 5,751 5,751 1.00 2.21
30 18 6,816 6,475 0.95 1.95 6,603 6,273 0.95 2.10 6,177 5,868 0.95 2.26
30 20 7,384 6,129 0.83 2.00 7,100 5,893 0.83 2.14 6,674 5,539 0.83 2.30
30 22 7,952 5,646 0.71 2.04 7,668 5,444 0.71 2.20 7,242 5,142 0.71 2.34
32 16 6,319 6,319 1.00 1.90 6,035 6,035 1.00 2.04 5,751 5,751 1.00 2.21
32 18 6,816 6,816 1.00 1.95 6,603 6,603 1.00 2.10 6,177 6,177 1.00 2.26
32 20 7,384 6,719 0.91 2.00 7,100 6,461 0.91 2.14 6,674 6,073 0.91 2.30
32 22 7,952 6,282 0.79 2.04 7,668 6,058 0.79 2.20 7,242 5,721 0.79 2.34
34 16 6,319 6,319 1.00 1.90 6,035 6,035 1.00 2.04 5,751 5,751 1.00 2.21
34 18 6,816 6,816 1.00 1.95 6,603 6,603 1.00 2.10 6,177 6,177 1.00 2.26
34 20 7,384 7,310 0.99 2.00 7,100 7,029 0.99 2.14 6,674 6,607 0.99 2.30
34 22 7,952 6,918 0.87 2.04 7,668 6,671 0.87 2.20 7,242 6,301 0.87 2.34
17
OC301-A--1.qxp 04.4.28 11:14 AM Page 18
COOLING CAPACITY(5)
PKA-RP4FAL / PUHZ-RP4VHA
PUHZ-RP4VHA1 (230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 20 25 30
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 9,900 6,039 0.61 2.34 9,600 5,856 0.61 2.48 9,300 5,673 0.61 2.62
20 18 10,600 5,194 0.49 2.39 10,300 5,047 0.49 2.52 9,950 4,876 0.49 2.70
20 20 11,400 4,218 0.37 2.46 11,150 4,126 0.37 2.58 10,850 4,015 0.37 2.75
22 16 9,900 6,831 0.69 2.34 9,600 6,624 0.69 2.48 9,300 6,417 0.69 2.62
22 18 10,600 6,042 0.57 2.39 10,300 5,871 0.57 2.52 9,950 5,672 0.57 2.70
22 20 11,400 5,130 0.45 2.46 11,150 5,018 0.45 2.58 10,850 4,883 0.45 2.75
24 16 9,900 7,623 0.77 2.34 9,600 7,392 0.77 2.48 9,300 7,161 0.77 2.62
24 18 10,600 6,890 0.65 2.39 10,300 6,695 0.65 2.52 9,950 6,468 0.65 2.70
24 20 11,400 6,042 0.53 2.46 11,150 5,910 0.53 2.58 10,850 5,751 0.53 2.75
24 22 12,150 4,982 0.41 2.52 11,900 4,879 0.41 2.67 11,600 4,756 0.41 2.84
26 16 9,900 8,415 0.85 2.34 9,600 8,160 0.85 2.48 9,300 7,905 0.85 2.62
26 18 10,600 7,738 0.73 2.39 10,300 7,519 0.73 2.52 9,950 7,264 0.73 2.70
26 20 11,400 6,954 0.61 2.46 11,150 6,802 0.61 2.58 10,850 6,619 0.61 2.75
26 22 12,150 5,954 0.49 2.52 11,900 5,831 0.49 2.67 11,600 5,684 0.49 2.84
27 16 9,900 8,811 0.89 2.34 9,600 8,544 0.89 2.48 9,300 8,277 0.89 2.62
27 18 10,600 8,162 0.77 2.39 10,300 7,931 0.77 2.52 9,950 7,662 0.77 2.70
27 20 11,400 7,410 0.65 2.46 11,150 7,248 0.65 2.58 10,850 7,053 0.65 2.75
27 22 12,150 6,440 0.53 2.52 11,900 6,307 0.53 2.67 11,600 6,148 0.53 2.84
28 16 9,900 9,207 0.93 2.34 9,600 8,928 0.93 2.48 9,300 8,649 0.93 2.62
28 18 10,600 8,586 0.81 2.39 10,300 8,343 0.81 2.52 9,950 8,060 0.81 2.70
28 20 11,400 7,866 0.69 2.46 11,150 7,694 0.69 2.58 10,850 7,487 0.69 2.75
28 22 12,150 6,926 0.57 2.52 11,900 6,783 0.57 2.67 11,600 6,612 0.57 2.84
30 16 9,900 9,900 1.00 2.34 9,600 9,600 1.00 2.48 9,300 9,300 1.00 2.62
30 18 10,600 9,434 0.89 2.39 10,300 9,167 0.89 2.52 9,950 8,856 0.89 2.70
30 20 11,400 8,778 0.77 2.46 11,150 8,586 0.77 2.58 10,850 8,355 0.77 2.75
30 22 12,150 7,898 0.65 2.52 11,900 7,735 0.65 2.67 11,600 7,540 0.65 2.84
32 16 9,900 9,900 1.00 2.34 9,600 9,600 1.00 2.48 9,300 9,300 1.00 2.62
32 18 10,600 10,282 0.97 2.39 10,300 9,991 0.97 2.52 9,950 9,652 0.97 2.70
32 20 11,400 9,690 0.85 2.46 11,150 9,478 0.85 2.58 10,850 9,223 0.85 2.75
32 22 12,150 8,870 0.73 2.52 11,900 8,687 0.73 2.67 11,600 8,468 0.73 2.84
34 16 9,900 9,900 1.00 2.34 9,600 9,600 1.00 2.48 9,300 9,300 1.00 2.62
34 18 10,600 10,600 1.00 2.39 10,300 10,300 1.00 2.52 9,950 9,950 1.00 2.70
34 20 11,400 10,602 0.93 2.46 11,150 10,370 0.93 2.58 10,850 10,091 0.93 2.75
34 22 12,150 9,842 0.81 2.52 11,900 9,639 0.81 2.67 11,600 9,396 0.81 2.84
CA : Capacity (W) SHC(W) :Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
18
OC301-A--1.qxp 04.4.28 11:14 AM Page 19
COOLING CAPACITY(6)
PKA-RP4FAL / PUHZ-RP4VHA
PUHZ-RP4VHA1 (230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 35 40 45
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 8,900 5,429 0.61 2.81 8,500 5,185 0.61 3.02 8,100 4,941 0.61 3.27
20 18 9,600 4,704 0.49 2.89 9,300 4,557 0.49 3.11 8,700 4,263 0.49 3.34
20 20 10,400 3,848 0.37 2.96 10,000 3,700 0.37 3.16 9,400 3,478 0.37 3.40
22 16 8,900 6,141 0.69 2.81 8,500 5,865 0.69 3.02 8,100 5,589 0.69 3.27
22 18 9,600 5,472 0.57 2.89 9,300 5,301 0.57 3.11 8,700 4,959 0.57 3.34
22 20 10,400 4,680 0.45 2.96 10,000 4,500 0.45 3.16 9,400 4,230 0.45 3.40
24 16 8,900 6,853 0.77 2.81 8,500 6,545 0.77 3.02 8,100 6,237 0.77 3.27
24 18 9,600 6,240 0.65 2.89 9,300 6,045 0.65 3.11 8,700 5,655 0.65 3.34
24 20 10,400 5,512 0.53 2.96 10,000 5,300 0.53 3.16 9,400 4,982 0.53 3.40
24 22 11,200 4,592 0.41 3.02 10,800 4,428 0.41 3.25 10,200 4,182 0.41 3.46
26 16 8,900 7,565 0.85 2.81 8,500 7,225 0.85 3.02 8,100 6,885 0.85 3.27
26 18 9,600 7,008 0.73 2.89 9,300 6,789 0.73 3.11 8,700 6,351 0.73 3.34
26 20 10,400 6,344 0.61 2.96 10,000 6,100 0.61 3.16 9,400 5,734 0.61 3.40
26 22 11,200 5,488 0.49 3.02 10,800 5,292 0.49 3.25 10,200 4,998 0.49 3.46
27 16 8,900 7,921 0.89 2.81 8,500 7,565 0.89 3.02 8,100 7,209 0.89 3.27
27 18 9,600 7,392 0.77 2.89 9,300 7,161 0.77 3.11 8,700 6,699 0.77 3.34
27 20 10,400 6,760 0.65 2.96 10,000 6,500 0.65 3.16 9,400 6,110 0.65 3.40
27 22 11,200 5,936 0.53 3.02 10,800 5,724 0.53 3.25 10,200 5,406 0.53 3.46
28 16 8,900 8,277 0.93 2.81 8,500 7,905 0.93 3.02 8,100 7,533 0.93 3.27
28 18 9,600 7,776 0.81 2.89 9,300 7,533 0.81 3.11 8,700 7,047 0.81 3.34
28 20 10,400 7,176 0.69 2.96 10,000 6,900 0.69 3.16 9,400 6,486 0.69 3.40
28 22 11,200 6,384 0.57 3.02 10,800 6,156 0.57 3.25 10,200 5,814 0.57 3.46
30 16 8,900 8,900 1.00 2.81 8,500 8,500 1.00 3.02 8,100 8,100 1.00 3.27
30 18 9,600 8,544 0.89 2.89 9,300 8,277 0.89 3.11 8,700 7,743 0.89 3.34
30 20 10,400 8,008 0.77 2.96 10,000 7,700 0.77 3.16 9,400 7,238 0.77 3.40
30 22 11,200 7,280 0.65 3.02 10,800 7,020 0.65 3.25 10,200 6,630 0.65 3.46
32 16 8,900 8,900 1.00 2.81 8,500 8,500 1.00 3.02 8,100 8,100 1.00 3.27
32 18 9,600 9,312 0.97 2.89 9,300 9,021 0.97 3.11 8,700 8,439 0.97 3.34
32 20 10,400 8,840 0.85 2.96 10,000 8,500 0.85 3.16 9,400 7,990 0.85 3.40
32 22 11,200 8,176 0.73 3.02 10,800 7,884 0.73 3.25 10,200 7,446 0.73 3.46
34 16 8,900 8,900 1.00 2.81 8,500 8,500 1.00 3.02 8,100 8,100 1.00 3.27
34 18 9,600 9,600 1.00 2.89 9,300 9,300 1.00 3.11 8,700 8,700 1.00 3.34
34 20 10,400 9,672 0.93 2.96 10,000 9,300 0.93 3.16 9,400 8,742 0.93 3.40
34 22 11,200 9,072 0.81 3.02 10,800 8,748 0.81 3.25 10,200 8,262 0.81 3.46
CA : Capacity (W) SHC(W) :Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
19
OC301-A--1.qxp 04.4.28 11:14 AM Page 20
COOLING CAPACITY(7)
PKA-RP2.5FAL / PUH-P2.5VGAA
PUH-P2.5VGAA.UK PUH-P2.5YGAA.UK
PUH-P2.5VGAA1.UK PUH-P2.5YGAA1.UK
PU-P2.5VGAA
PU-P2.5VGAA.UK PU-P2.5YGAA.UK
PU-P2.5VGAA1.UK PU-P2.5YGAA1.UK
(230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 20 25 30
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 6,386 4,470 0.70 2.12 6,192 4,334 0.70 2.24 5,999 4,199 0.70 2.37
20 18 6,837 3,965 0.58 2.16 6,644 3,853 0.58 2.28 6,418 3,722 0.58 2.44
20 20 7,353 3,382 0.46 2.23 7,192 3,308 0.46 2.33 6,998 3,219 0.46 2.49
22 16 6,386 4,981 0.78 2.12 6,192 4,830 0.78 2.24 5,999 4,679 0.78 2.37
22 18 6,837 4,512 0.66 2.16 6,644 4,385 0.66 2.28 6,418 4,236 0.66 2.44
22 20 7,353 3,971 0.54 2.23 7,192 3,884 0.54 2.33 6,998 3,779 0.54 2.49
24 16 6,386 5,492 0.86 2.12 6,192 5,325 0.86 2.24 5,999 5,159 0.86 2.37
24 18 6,837 5,059 0.74 2.16 6,644 4,916 0.74 2.28 6,418 4,749 0.74 2.44
24 20 7,353 4,559 0.62 2.23 7,192 4,459 0.62 2.33 6,998 4,339 0.62 2.49
24 22 7,837 3,918 0.50 2.28 7,676 3,838 0.50 2.41 7,482 3,741 0.50 2.57
26 16 6,386 6,002 0.94 2.12 6,192 5,820 0.94 2.24 5,999 5,639 0.94 2.37
26 18 6,837 5,606 0.82 2.16 6,644 5,448 0.82 2.28 6,418 5,263 0.82 2.44
26 20 7,353 5,147 0.70 2.23 7,192 5,034 0.70 2.33 6,998 4,899 0.70 2.49
26 22 7,837 4,545 0.58 2.28 7,676 4,452 0.58 2.41 7,482 4,340 0.58 2.57
27 16 6,386 6,258 0.98 2.12 6,192 6,068 0.98 2.24 5,999 5,879 0.98 2.37
27 18 6,837 5,880 0.86 2.16 6,644 5,713 0.86 2.28 6,418 5,519 0.86 2.44
27 20 7,353 5,441 0.74 2.23 7,192 5,322 0.74 2.33 6,998 5,179 0.74 2.49
27 22 7,837 4,859 0.62 2.28 7,676 4,759 0.62 2.41 7,482 4,639 0.62 2.57
28 16 6,386 6,386 1.00 2.12 6,192 6,192 1.00 2.24 5,999 5,999 1.00 2.37
28 18 6,837 6,153 0.90 2.16 6,644 5,979 0.90 2.28 6,418 5,776 0.90 2.44
28 20 7,353 5,735 0.78 2.23 7,192 5,610 0.78 2.33 6,998 5,459 0.78 2.49
28 22 7,837 5,172 0.66 2.28 7,676 5,066 0.66 2.41 7,482 4,938 0.66 2.57
30 16 6,386 6,386 1.00 2.12 6,192 6,192 1.00 2.24 5,999 5,999 1.00 2.37
30 18 6,837 6,700 0.98 2.16 6,644 6,511 0.98 2.28 6,418 6,289 0.98 2.44
30 20 7,353 6,324 0.86 2.23 7,192 6,185 0.86 2.33 6,998 6,018 0.86 2.49
30 22 7,837 5,799 0.74 2.28 7,676 5,680 0.74 2.41 7,482 5,537 0.74 2.57
32 16 6,386 6,386 1.00 2.12 6,192 6,192 1.00 2.24 5,999 5,999 1.00 2.37
32 18 6,837 6,837 1.00 2.16 6,644 6,644 1.00 2.28 6,418 6,418 1.00 2.44
32 20 7,353 6,912 0.94 2.23 7,192 6,760 0.94 2.33 6,998 6,578 0.94 2.49
32 22 7,837 6,426 0.82 2.28 7,676 6,294 0.82 2.41 7,482 6,135 0.82 2.57
34 16 6,386 6,386 1.00 2.12 6,192 6,192 1.00 2.24 5,999 5,999 1.00 2.37
34 18 6,837 6,837 1.00 2.16 6,644 6,644 1.00 2.28 6,418 6,418 1.00 2.44
34 20 7,353 7,353 1.00 2.23 7,192 7,192 1.00 2.33 6,998 6,998 1.00 2.49
34 22 7,837 7,053 0.90 2.28 7,676 6,908 0.90 2.41 7,482 6,734 0.90 2.57
CA : Capacity (W) SHC(W) :Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
20
OC301-A--1.qxp 04.4.28 11:14 AM Page 21
COOLING CAPACITY(8)
PKA-RP2.5FAL / PUH-P2.5VGAA
PUH-P2.5VGAA.UK PUH-P2.5YGAA.UK
PUH-P2.5VGAA1.UK PUH-P2.5YGAA1.UK
PU-P2.5VGAA
PU-P2.5VGAA.UK PU-P2.5YGAA.UK
PU-P2.5VGAA1.UK PU-P2.5YGAA1.UK
(230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 35 40 45
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 5,741 4,018 0.70 2.54 5,483 3,838 0.70 2.73 5,225 3,657 0.70 2.95
20 18 6,192 3,591 0.58 2.61 5,999 3,479 0.58 2.81 5,612 3,255 0.58 3.02
20 20 6,708 3,086 0.46 2.68 6,450 2,967 0.46 2.86 6,063 2,789 0.46 3.07
22 16 5,741 4,478 0.78 2.54 5,483 4,276 0.78 2.73 5,225 4,075 0.78 2.95
22 18 6,192 4,087 0.66 2.61 5,999 3,959 0.66 2.81 5,612 3,704 0.66 3.02
22 20 6,708 3,622 0.54 2.68 6,450 3,483 0.54 2.86 6,063 3,274 0.54 3.07
24 16 5,741 4,937 0.86 2.54 5,483 4,715 0.86 2.73 5,225 4,493 0.86 2.95
24 18 6,192 4,582 0.74 2.61 5,999 4,439 0.74 2.81 5,612 4,153 0.74 3.02
24 20 6,708 4,159 0.62 2.68 6,450 3,999 0.62 2.86 6,063 3,759 0.62 3.07
24 22 7,224 3,612 0.50 2.73 6,966 3,483 0.50 2.94 6,579 3,290 0.50 3.13
26 16 5,741 5,396 0.94 2.54 5,483 5,154 0.94 2.73 5,225 4,911 0.94 2.95
26 18 6,192 5,077 0.82 2.61 5,999 4,919 0.82 2.81 5,612 4,601 0.82 3.02
26 20 6,708 4,696 0.70 2.68 6,450 4,515 0.70 2.86 6,063 4,244 0.70 3.07
26 22 7,224 4,190 0.58 2.73 6,966 4,040 0.58 2.94 6,579 3,816 0.58 3.13
27 16 5,741 5,626 0.98 2.54 5,483 5,373 0.98 2.73 5,225 5,120 0.98 2.95
27 18 6,192 5,325 0.86 2.61 5,999 5,159 0.86 2.81 5,612 4,826 0.86 3.02
27 20 6,708 4,964 0.74 2.68 6,450 4,773 0.74 2.86 6,063 4,487 0.74 3.07
27 22 7,224 4,479 0.62 2.73 6,966 4,319 0.62 2.94 6,579 4,079 0.62 3.13
28 16 5,741 5,741 1.00 2.54 5,483 5,483 1.00 2.73 5,225 5,225 1.00 2.95
28 18 6,192 5,573 0.90 2.61 5,999 5,399 0.90 2.81 5,612 5,050 0.90 3.02
28 20 6,708 5,232 0.78 2.68 6,450 5,031 0.78 2.86 6,063 4,729 0.78 3.07
28 22 7,224 4,768 0.66 2.73 6,966 4,598 0.66 2.94 6,579 4,342 0.66 3.13
30 16 5,741 5,741 1.00 2.54 5,483 5,483 1.00 2.73 5,225 5,225 1.00 2.95
30 18 6,192 6,068 0.98 2.61 5,999 5,879 0.98 2.81 5,612 5,499 0.98 3.02
30 20 6,708 5,769 0.86 2.68 6,450 5,547 0.86 2.86 6,063 5,214 0.86 3.07
30 22 7,224 5,346 0.74 2.73 6,966 5,155 0.74 2.94 6,579 4,868 0.74 3.13
32 16 5,741 5,741 1.00 2.54 5,483 5,483 1.00 2.73 5,225 5,225 1.00 2.95
32 18 6,192 6,192 1.00 2.61 5,999 5,999 1.00 2.81 5,612 5,612 1.00 3.02
32 20 6,708 6,306 0.94 2.68 6,450 6,063 0.94 2.86 6,063 5,699 0.94 3.07
32 22 7,224 5,924 0.82 2.73 6,966 5,712 0.82 2.94 6,579 5,395 0.82 3.13
34 16 5,741 5,741 1.00 2.54 5,483 5,483 1.00 2.73 5,225 5,225 1.00 2.95
34 18 6,192 6,192 1.00 2.61 5,999 5,999 1.00 2.81 5,612 5,612 1.00 3.02
34 20 6,708 6,708 1.00 2.68 6,450 6,450 1.00 2.86 6,063 6,063 1.00 3.07
34 22 7,224 6,502 0.90 2.73 6,966 6,269 0.90 2.94 6,579 5,921 0.90 3.13
CA : Capacity (W) SHC(W) :Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
21
OC301-A--1.qxp 04.4.28 11:14 AM Page 22
COOLING CAPACITY(9)
PKA-RP3FAL / PUH-P3VGAA PUH-P3YGAA
PUH-P3VGAA.UK PUH-P3YGAA.UK
PUH-P3VGAA1.UK PUH-P3YGAA1.UK
PU-P3VGAA PU-P3YGAA
PU-P3VGAA.UK PU-P3YGAA.UK
PU-P3VGAA1.UK PU-P3YGAA1.UK
(230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 20 25 30
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 7,772 4,974 0.64 2.74 7,536 4,823 0.64 2.90 7,301 4,672 0.64 3.07
20 18 8,321 4,327 0.52 2.80 8,086 4,204 0.52 2.95 7,811 4,062 0.52 3.16
20 20 8,949 3,580 0.40 2.88 8,753 3,501 0.40 3.02 8,517 3,407 0.40 3.22
22 16 7,772 5,595 0.72 2.74 7,536 5,426 0.72 2.90 7,301 5,256 0.72 3.07
22 18 8,321 4,993 0.60 2.80 8,086 4,851 0.60 2.95 7,811 4,686 0.60 3.16
22 20 8,949 4,296 0.48 2.88 8,753 4,201 0.48 3.02 8,517 4,088 0.48 3.22
24 16 7,772 6,217 0.80 2.74 7,536 6,029 0.80 2.90 7,301 5,840 0.80 3.07
24 18 8,321 5,658 0.68 2.80 8,086 5,498 0.68 2.95 7,811 5,311 0.68 3.16
24 20 8,949 5,011 0.56 2.88 8,753 4,902 0.56 3.02 8,517 4,770 0.56 3.22
24 22 9,538 4,197 0.44 2.95 9,342 4,110 0.44 3.12 9,106 4,007 0.44 3.33
26 16 7,772 6,839 0.88 2.74 7,536 6,632 0.88 2.90 7,301 6,424 0.88 3.07
26 18 8,321 6,324 0.76 2.80 8,086 6,145 0.76 2.95 7,811 5,936 0.76 3.16
26 20 8,949 5,727 0.64 2.88 8,753 5,602 0.64 3.02 8,517 5,451 0.64 3.22
26 22 9,538 4,960 0.52 2.95 9,342 4,858 0.52 3.12 9,106 4,735 0.52 3.33
27 16 7,772 7,150 0.92 2.74 7,536 6,933 0.92 2.90 7,301 6,716 0.92 3.07
27 18 8,321 6,657 0.80 2.80 8,086 6,468 0.80 2.95 7,811 6,249 0.80 3.16
27 20 8,949 6,085 0.68 2.88 8,753 5,952 0.68 3.02 8,517 5,792 0.68 3.22
27 22 9,538 5,341 0.56 2.95 9,342 5,231 0.56 3.12 9,106 5,099 0.56 3.33
28 16 7,772 7,461 0.96 2.74 7,536 7,235 0.96 2.90 7,301 7,008 0.96 3.07
28 18 8,321 6,990 0.84 2.80 8,086 6,792 0.84 2.95 7,811 6,561 0.84 3.16
28 20 8,949 6,443 0.72 2.88 8,753 6,302 0.72 3.02 8,517 6,132 0.72 3.22
28 22 9,538 5,723 0.60 2.95 9,342 5,605 0.60 3.12 9,106 5,464 0.60 3.33
30 16 7,772 7,772 1.00 2.74 7,536 7,536 1.00 2.90 7,301 7,301 1.00 3.07
30 18 8,321 7,655 0.92 2.80 8,086 7,439 0.92 2.95 7,811 7,186 0.92 3.16
30 20 8,949 7,159 0.80 2.88 8,753 7,002 0.80 3.02 8,517 6,814 0.80 3.22
30 22 9,538 6,486 0.68 2.95 9,342 6,352 0.68 3.12 9,106 6,192 0.68 3.33
32 16 7,772 7,772 1.00 2.74 7,536 7,536 1.00 2.90 7,301 7,301 1.00 3.07
32 18 8,321 8,321 1.00 2.80 8,086 8,086 1.00 2.95 7,811 7,811 1.00 3.16
32 20 8,949 7,875 0.88 2.88 8,753 7,702 0.88 3.02 8,517 7,495 0.88 3.22
32 22 9,538 7,249 0.76 2.95 9,342 7,100 0.76 3.12 9,106 6,921 0.76 3.33
34 16 7,772 7,772 1.00 2.74 7,536 7,536 1.00 2.90 7,301 7,301 1.00 3.07
34 18 8,321 8,321 1.00 2.80 8,086 8,086 1.00 2.95 7,811 7,811 1.00 3.16
34 20 8,949 8,591 0.96 2.88 8,753 8,403 0.96 3.02 8,517 8,177 0.96 3.22
34 22 9,538 8,012 0.84 2.95 9,342 7,847 0.84 3.12 9,106 7,649 0.84 3.33
CA : Capacity (W) SHC(W) :Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
22
OC301-A--1.qxp 04.4.28 11:14 AM Page 23
COOLING CAPACITY(10)
PKA-RP3FAL / PUH-P3VGAA PUH-P3YGAA
PUH-P3VGAA.UK PUH-P3YGAA.UK
PUH-P3VGAA1.UK PUH-P3YGAA1.UK
PU-P3VGAA PU-P3YGAA
PU-P3VGAA.UK PU-P3YGAA.UK
PU-P3VGAA1.UK PU-P3YGAA1.UK
(230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 35 40 45
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 6,987 4,471 0.64 3.29 6,673 4,270 0.64 3.53 6,359 4,069 0.64 3.82
20 18 7,536 3,919 0.52 3.38 7,301 3,796 0.52 3.64 6,830 3,551 0.52 3.91
20 20 8,164 3,266 0.40 3.46 7,850 3,140 0.40 3.70 7,379 2,952 0.40 3.98
22 16 6,987 5,030 0.72 3.29 6,673 4,804 0.72 3.53 6,359 4,578 0.72 3.82
22 18 7,536 4,522 0.60 3.38 7,301 4,380 0.60 3.64 6,830 4,098 0.60 3.91
22 20 8,164 3,919 0.48 3.46 7,850 3,768 0.48 3.70 7,379 3,542 0.48 3.98
24 16 6,987 5,589 0.80 3.29 6,673 5,338 0.80 3.53 6,359 5,087 0.80 3.82
24 18 7,536 5,124 0.68 3.38 7,301 4,964 0.68 3.64 6,830 4,644 0.68 3.91
24 20 8,164 4,572 0.56 3.46 7,850 4,396 0.56 3.70 7,379 4,132 0.56 3.98
24 22 8,792 3,868 0.44 3.53 8,478 3,730 0.44 3.81 8,007 3,523 0.44 4.05
26 16 6,987 6,148 0.88 3.29 6,673 5,872 0.88 3.53 6,359 5,595 0.88 3.82
26 18 7,536 5,727 0.76 3.38 7,301 5,548 0.76 3.64 6,830 5,190 0.76 3.91
26 20 8,164 5,225 0.64 3.46 7,850 5,024 0.64 3.70 7,379 4,723 0.64 3.98
26 22 8,792 4,572 0.52 3.53 8,478 4,409 0.52 3.81 8,007 4,164 0.52 4.05
27 16 6,987 6,428 0.92 3.29 6,673 6,139 0.92 3.53 6,359 5,850 0.92 3.82
27 18 7,536 6,029 0.80 3.38 7,301 5,840 0.80 3.64 6,830 5,464 0.80 3.91
27 20 8,164 5,552 0.68 3.46 7,850 5,338 0.68 3.70 7,379 5,018 0.68 3.98
27 22 8,792 4,924 0.56 3.53 8,478 4,748 0.56 3.81 8,007 4,484 0.56 4.05
28 16 6,987 6,707 0.96 3.29 6,673 6,406 0.96 3.53 6,359 6,104 0.96 3.82
28 18 7,536 6,330 0.84 3.38 7,301 6,132 0.84 3.64 6,830 5,737 0.84 3.91
28 20 8,164 5,878 0.72 3.46 7,850 5,652 0.72 3.70 7,379 5,313 0.72 3.98
28 22 8,792 5,275 0.60 3.53 8,478 5,087 0.60 3.81 8,007 4,804 0.60 4.05
30 16 6,987 6,987 1.00 3.29 6,673 6,673 1.00 3.53 6,359 6,359 1.00 3.82
30 18 7,536 6,933 0.92 3.38 7,301 6,716 0.92 3.64 6,830 6,283 0.92 3.91
30 20 8,164 6,531 0.80 3.46 7,850 6,280 0.80 3.70 7,379 5,903 0.80 3.98
30 22 8,792 5,979 0.68 3.53 8,478 5,765 0.68 3.81 8,007 5,445 0.68 4.05
32 16 6,987 6,987 1.00 3.29 6,673 6,673 1.00 3.53 6,359 6,359 1.00 3.82
32 18 7,536 7,536 1.00 3.38 7,301 7,301 1.00 3.64 6,830 6,830 1.00 3.91
32 20 8,164 7,184 0.88 3.46 7,850 6,908 0.88 3.70 7,379 6,494 0.88 3.98
32 22 8,792 6,682 0.76 3.53 8,478 6,443 0.76 3.81 8,007 6,085 0.76 4.05
34 16 6,987 6,987 1.00 3.29 6,673 6,673 1.00 3.53 6,359 6,359 1.00 3.82
34 18 7,536 7,536 1.00 3.38 7,301 7,301 1.00 3.64 6,830 6,830 1.00 3.91
34 20 8,164 7,837 0.96 3.46 7,850 7,536 0.96 3.70 7,379 7,084 0.96 3.98
34 22 8,792 7,385 0.84 3.53 8,478 7,122 0.84 3.81 8,007 6,726 0.84 4.05
CA : Capacity (W) SHC(W) :Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
23
OC301-A--1.qxp 04.4.28 11:14 AM Page 24
COOLING CAPACITY(11)
PKA-RP4FAL / PUH-P4YGAA
PUH-P4VGAA.UK PUH-P4YGAA.UK
PUH-P4VGAA1.UK PUH-P4YGAA1.UK
PU-P4YGAA
PU-P4VGAA.UK PU-P4YGAA.UK
PU-P4VGAA1.UK PU-P4YGAA1.UK (230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 20 25 30
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 9,306 6,142 0.66 2.87 9,024 5,956 0.66 3.03 8,742 5,770 0.66 3.21
20 18 9,964 5,381 0.54 2.93 9,682 5,228 0.54 3.09 9,353 5,051 0.54 3.30
20 20 10,716 4,501 0.42 3.02 10,481 4,402 0.42 3.16 10,199 4,284 0.42 3.37
22 16 9,306 6,886 0.74 2.87 9,024 6,678 0.74 3.03 8,742 6,469 0.74 3.21
22 18 9,964 6,178 0.62 2.93 9,682 6,003 0.62 3.09 9,353 5,799 0.62 3.30
22 20 10,716 5,358 0.50 3.02 10,481 5,241 0.50 3.16 10,199 5,100 0.50 3.37
24 16 9,306 7,631 0.82 2.87 9,024 7,400 0.82 3.03 8,742 7,168 0.82 3.21
24 18 9,964 6,975 0.70 2.93 9,682 6,777 0.70 3.09 9,353 6,547 0.70 3.30
24 20 10,716 6,215 0.58 3.02 10,481 6,079 0.58 3.16 10,199 5,915 0.58 3.37
24 22 11,421 5,254 0.46 3.09 11,186 5,146 0.46 3.27 10,904 5,016 0.46 3.48
26 16 9,306 8,375 0.90 2.87 9,024 8,122 0.90 3.03 8,742 7,868 0.90 3.21
26 18 9,964 7,772 0.78 2.93 9,682 7,552 0.78 3.09 9,353 7,295 0.78 3.30
26 20 10,716 7,073 0.66 3.02 10,481 6,917 0.66 3.16 10,199 6,731 0.66 3.37
26 22 11,421 6,167 0.54 3.09 11,186 6,040 0.54 3.27 10,904 5,888 0.54 3.48
27 16 9,306 8,748 0.94 2.87 9,024 8,483 0.94 3.03 8,742 8,217 0.94 3.21
27 18 9,964 8,170 0.82 2.93 9,682 7,939 0.82 3.09 9,353 7,669 0.82 3.30
27 20 10,716 7,501 0.70 3.02 10,481 7,337 0.70 3.16 10,199 7,139 0.70 3.37
27 22 11,421 6,624 0.58 3.09 11,186 6,488 0.58 3.27 10,904 6,324 0.58 3.48
28 16 9,306 9,120 0.98 2.87 9,024 8,844 0.98 3.03 8,742 8,567 0.98 3.21
28 18 9,964 8,569 0.86 2.93 9,682 8,327 0.86 3.09 9,353 8,044 0.86 3.30
28 20 10,716 7,930 0.74 3.02 10,481 7,756 0.74 3.16 10,199 7,547 0.74 3.37
28 22 11,421 7,081 0.62 3.09 11,186 6,935 0.62 3.27 10,904 6,760 0.62 3.48
30 16 9,306 9,306 1.00 2.87 9,024 9,024 1.00 3.03 8,742 8,742 1.00 3.21
30 18 9,964 9,366 0.94 2.93 9,682 9,101 0.94 3.09 9,353 8,792 0.94 3.30
30 20 10,716 8,787 0.82 3.02 10,481 8,594 0.82 3.16 10,199 8,363 0.82 3.37
30 22 11,421 7,995 0.70 3.09 11,186 7,830 0.70 3.27 10,904 7,633 0.70 3.48
32 16 9,306 9,306 1.00 2.87 9,024 9,024 1.00 3.03 8,742 8,742 1.00 3.21
32 18 9,964 9,964 1.00 2.93 9,682 9,682 1.00 3.09 9,353 9,353 1.00 3.30
32 20 10,716 9,644 0.90 3.02 10,481 9,433 0.90 3.16 10,199 9,179 0.90 3.37
32 22 11,421 8,908 0.78 3.09 11,186 8,725 0.78 3.27 10,904 8,505 0.78 3.48
34 16 9,306 9,306 1.00 2.87 9,024 9,024 1.00 3.03 8,742 8,742 1.00 3.21
34 18 9,964 9,964 1.00 2.93 9,682 9,682 1.00 3.09 9,353 9,353 1.00 3.30
34 20 10,716 10,502 0.98 3.02 10,481 10,271 0.98 3.16 10,199 9,995 0.98 3.37
34 22 11,421 9,822 0.86 3.09 11,186 9,620 0.86 3.27 10,904 9,377 0.86 3.48
24
OC301-A--1.qxp 04.4.28 11:14 AM Page 25
COOLING CAPACITY(12)
PKA-RP4FAL / PUH-P4YGAA
PUH-P4VGAA.UK PUH-P4YGAA.UK
PUH-P4VGAA1.UK PUH-P4YGAA1.UK
PU-P4YGAA
PU-P4VGAA.UK PU-P4YGAA.UK
PU-P4VGAA1.UK PU-P4YGAA1.UK
(230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 35 40 45
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 8,366 5,522 0.66 3.45 7,990 5,273 0.66 3.70 7,614 5,025 0.66 4.00
20 18 9,024 4,873 0.54 3.54 8,742 4,721 0.54 3.81 8,178 4,416 0.54 4.09
20 20 9,776 4,106 0.42 3.63 9,400 3,948 0.42 3.88 8,836 3,711 0.42 4.16
22 16 8,366 6,191 0.74 3.45 7,990 5,913 0.74 3.70 7,614 5,634 0.74 4.00
22 18 9,024 5,595 0.62 3.54 8,742 5,420 0.62 3.81 8,178 5,070 0.62 4.09
22 20 9,776 4,888 0.50 3.63 9,400 4,700 0.50 3.88 8,836 4,418 0.50 4.16
24 16 8,366 6,860 0.82 3.45 7,990 6,552 0.82 3.70 7,614 6,243 0.82 4.00
24 18 9,024 6,317 0.70 3.54 8,742 6,119 0.70 3.81 8,178 5,725 0.70 4.09
24 20 9,776 5,670 0.58 3.63 9,400 5,452 0.58 3.88 8,836 5,125 0.58 4.16
24 22 10,528 4,843 0.46 3.70 10,152 4,670 0.46 3.98 9,588 4,410 0.46 4.24
26 16 8,366 7,529 0.90 3.45 7,990 7,191 0.90 3.70 7,614 6,853 0.90 4.00
26 18 9,024 7,039 0.78 3.54 8,742 6,819 0.78 3.81 8,178 6,379 0.78 4.09
26 20 9,776 6,452 0.66 3.63 9,400 6,204 0.66 3.88 8,836 5,832 0.66 4.16
26 22 10,528 5,685 0.54 3.70 10,152 5,482 0.54 3.98 9,588 5,178 0.54 4.24
27 16 8,366 7,864 0.94 3.45 7,990 7,511 0.94 3.70 7,614 7,157 0.94 4.00
27 18 9,024 7,400 0.82 3.54 8,742 7,168 0.82 3.81 8,178 6,706 0.82 4.09
27 20 9,776 6,843 0.70 3.63 9,400 6,580 0.70 3.88 8,836 6,185 0.70 4.16
27 22 10,528 6,106 0.58 3.70 10,152 5,888 0.58 3.98 9,588 5,561 0.58 4.24
28 16 8,366 8,199 0.98 3.45 7,990 7,830 0.98 3.70 7,614 7,462 0.98 4.00
28 18 9,024 7,761 0.86 3.54 8,742 7,518 0.86 3.81 8,178 7,033 0.86 4.09
28 20 9,776 7,234 0.74 3.63 9,400 6,956 0.74 3.88 8,836 6,539 0.74 4.16
28 22 10,528 6,527 0.62 3.70 10,152 6,294 0.62 3.98 9,588 5,945 0.62 4.24
30 16 8,366 8,366 1.00 3.45 7,990 7,990 1.00 3.70 7,614 7,614 1.00 4.00
30 18 9,024 8,483 0.94 3.54 8,742 8,217 0.94 3.81 8,178 7,687 0.94 4.09
30 20 9,776 8,016 0.82 3.63 9,400 7,708 0.82 3.88 8,836 7,246 0.82 4.16
30 22 10,528 7,370 0.70 3.70 10,152 7,106 0.70 3.98 9,588 6,712 0.70 4.24
32 16 8,366 8,366 1.00 3.45 7,990 7,990 1.00 3.70 7,614 7,614 1.00 4.00
32 18 9,024 9,024 1.00 3.54 8,742 8,742 1.00 3.81 8,178 8,178 1.00 4.09
32 20 9,776 8,798 0.90 3.63 9,400 8,460 0.90 3.88 8,836 7,952 0.90 4.16
32 22 10,528 8,212 0.78 3.70 10,152 7,919 0.78 3.98 9,588 7,479 0.78 4.24
34 16 8,366 8,366 1.00 3.45 7,990 7,990 1.00 3.70 7,614 7,614 1.00 4.00
34 18 9,024 9,024 1.00 3.54 8,742 8,742 1.00 3.81 8,178 8,178 1.00 4.09
34 20 9,776 9,580 0.98 3.63 9,400 9,212 0.98 3.88 8,836 8,659 0.98 4.16
34 22 10,528 9,054 0.86 3.70 10,152 8,731 0.86 3.98 9,588 8,246 0.86 4.24
CA : Capacity (W) SHC(W) :Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
25
OC301-A--1.qxp 04.4.28 11:14 AM Page 26
26
OC301-A--1.qxp 04.4.28 11:14 AM Page 27
CAPACITY (RATIO)
cannot be conducted with the maximum 20
1.2 INDOOR 1.2 frequency in the area below the slanting line. 25 D.B.(°C)
W.B.(°C)
1.0 22 1.0
20
18
0.8
0.8
16
0.6
0.4
1.4
22 INDOOR In some cases, heating operation
1.2 cannot be conducted with the maximum 25
20 W.B.(°C) INDOOR
1.2 20
16 D.B.(°C)
15
1.0
1.0
0.8
0.8
0.6
0.6
0.4
0.4
-5 0 10 20 30 40 46
-12 -10 -5 0 5 10 15
OUTDOOR D.B.(°C) OUTDOOR W.B.(°C)
15 INDOOR
CAPACITY (RATIO)
20
1.2 INDOOR 1.2 25 D.B.(°C)
W.B.(°C)
1.0 22 1.0
20
18
0.8
0.8
16
0.6
0.4
1.4
22 INDOOR
1.2 20 W.B.(°C) 25 INDOOR
TOTAL INPUT (RATIO)
18
TOTAL INPUT (RATIO)
1.2 20
16 D.B.(°C)
15
1.0
1.0
0.8
0.8
0.6
0.6
0.4
0.4
-5 0 10 20 30 40 46
-12 -10 -5 0 5 10 15
OUTDOOR D.B.(°C) OUTDOOR W.B.(°C)
27
OC301-A--1.qxp 04.4.28 11:14 AM Page 28
PKA-RP4FAL 1.00 0.997 0.991 0.985 0.979 0.973 0.970 0.967 0.961 0.955
28
OC301-A--1.qxp 04.4.28 11:14 AM Page 29
Phase , Hz 1 , 50 1 , 50 1 , 50
Discahrge temperature ˚C 64 80 67 83 68 78
Condensing temperature ˚C 43 50 45 54 44 49
Suction temperature ˚C 11 2 10 2 8 3
Ref.pipe length m 5 5 5 5 5 5
D.B. ˚C 27 20 27 20 27 20
Indoor side
Intake air
temperature
W.B. ˚C 19 15 19 15 19 15
Discharge air
temperature D.B. ˚C 14.9 38.7 13.8 41.6 13.6 41.6
Outdoor
temperature
W.B. ˚C 24 6 24 6 24 6
The unit of pressure has been changed to Mpa on tha international system of unit (Sl system).
The converted score against tha traditional unit system can be gotten according to the formula below.
f)
1(MPa) = 10.2(kgf/f
29
OC301-A--1.qxp 04.4.28 11:14 AM Page 30
Input kW 2.65 2.63 2.65 2.63 3.43 3.61 3.43 3.61 3.59 3.77 3.59 3.77
Amperes 0.43 0.43 0.43 0.43 0.43 0.43 0.43 0.43 0.52 0.52 0.52 0.52
PUH-P2.5VGAA PUH-P3VGAA PUH-P3YGAA PUH-P4YGAA
Outdoor unit Service Ref. PUH-P2.5VGAA.UK PUH-P2.5YGAA.UK PUH-P3VGAA.UK PUH-P3YGAA.UK PUH-P4VGAA.UK PUH-P4YGAA.UK
PUH-P2.5VGAA1.UK PUH-P2.5YGAA1.UK PUH-P3VGAA1.UK PUH-P3YGAA1.UK PUH-P4VGAA1.UK PUH-P4YGAA1.UK
Phase , Hz 1 , 50 3 , 50 1 , 50 3 , 50 1 , 50 3 , 50
Amperes 12.23 12.14 3.78 3.75 15.96 16.82 5.02 5.30 16.63 17.49 5.18 5.47
Discharge pressure MPa 2.10 2.23 2.10 2.23 2.26 2.54 2.26 2.54 1.95 2.14 1.95 2.14
Refrigerant circuit
Suction pressure MPa 0.51 0.43 0.51 0.43 0.47 0.40 0.47 0.40 0.48 0.41 0.48 0.41
Discahrge temperature ˚C 76 80 76 80 81 91 81 91 75 70 75 70
Condensing temperature ˚C 49 49 49 49 51 54 51 54 47 47 47 47
Suction temperature ˚C 7 -1 7 -1 4 -1 4 -1 8 0 8 0
Ref.pipe length m 5 5 5 5 5 5 5 5 5 5 5 5
D.B.
Indoor side
Intake air ˚C 27 20 27 20 27 20 27 20 27 20 27 20
temperature
W.B. ˚C 19 15 19 15 19 15 19 15 19 15 19 15
Discharge air
temperature D.B. ˚C 14.4 39.9 14.4 39.9 13.0 39.9 13.0 39.9 14.5 41.0 14.5 41.0
Outdoor
temperature
W.B. ˚C 24 6 24 6 24 6 24 6 24 6 24 6
SHF 0.80 — 0.80 — 0.74 — 0.74 — 0.76 — 0.76 —
The unit of pressure has been changed to Mpa on tha international system of unit (Sl system).
The converted score against tha traditional unit system can be gotten according to the formula below.
f)
1(MPa) = 10.2(kgf/f
30
OC301-A--2.qxp 04.4.28 11:16 AM Page 31
D.B.
Indoor side
Intake air ˚C 27 27 27 27 27 27
temperature
W.B. ˚C 19 19 19 19 19 19
Discharge air
temperature D.B. ˚C 14.4 14.4 13.0 13.0 14.5 14.5
Outdoor
temperature
W.B. ˚C 24 24 24 24 24 24
SHF 0.80 0.80 0.74 0.74 0.76 0.76
The unit of pressure has been changed to Mpa on tha international system of unit (Sl system).
The converted score against tha traditional unit system can be gotten according to the formula below.
f)
1(MPa) = 10.2(kgf/f
31
OC301-A--2.qxp 04.4.28 11:16 AM Page 32
90 90
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
70 70
NC-70 NC-70
60 60
NC-60 NC-60
50 50
NC-50 NC-50
40 40
NC-40 NC-40
30 30
NC-30 NC-30
APPROXIMATE 20 APPROXIMATE
20
TERESHOLD OF TERESHOLD OF
HEARING FOR HEARING FOR
NC-20 CONTINUOUS
NC-20
CONTINUOUS
NOISE NOISE
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz
UNIT
WALL
1m
1m
MICROPHONE
32
OC301-A--2.qxp 04.4.28 11:16 AM Page 33
PKA-RP2.5FAL Unit : mm
PKA-RP3FAL
Display section
Top
62.5
Emergency switch(Heat)
Receiving
section Emergency switch(Cool)
Defrosting Initial heating lamp
235 45 235 45 235 45 235
13
Power lamp
Front Right side
197
A C
340
Bolt
42
58
Drain hose for 25 55 (Gas pipe) Drain hose O.D.20
Drain hose
left-hand side piping 120 107
1110 183 (Liquid pipe) 111
Lower side
Liquid pipe [9.52(3/8F)
Auto vane Gas pipe [15.88(5/8F)
1120 240
552 Air outlet 552 Air outlet
Unit center
990 245
455
10 91=(910) 285
900 19 Knock out hole for wiring
Wall fixture 18 18 Drainage range Drainage range 91
29
30 30
66-ø6 hole for
80
tapping screw
280
100
100
184
30
65
39
4 39
37
60
37 39 37
98 32
4
33
OC301-A--2.qxp 04.4.28 11:16 AM Page 34
PKA-RP4FAL Unit : mm
Top
Display section
62.5
Emergency switch(Heat)
235 45 235 45 235 45 235 45 235 Emergency switch(Cool)
13
Receiving
section Defrosting Initial heating lamp
Power lamp
Front Knock out hole for right piping
Right side
Left side 1680
235
1370 Air intake
197
C
340
Gas pipe
Bolt
42
25
Drain hose
58
55 (Gas pipe) Drain hose O.D.20
120 102
Drain hose for left-hand side piping 1110 Drain hose (Liquid pipe)
183 111
Lower side
1400 240 Gas pipe For PUHZ-RP type: [15.88(5/8F)
694 Air outlet 694 Air outlet For PU(H)-P type : [19.05(3/4F)
Auto vane
Unit center
Unit out line
1270 245
595
Wall fixture
13 91=(1183) 285
900 19 Knock out hole for wiring
84-ø6 hole for 18 18
tapping screw Drainage range Drainage range 91
on left-hand side on right-hand side A B C
29
10
30
30 30
80
100
280
100
184
30
65
39
4 39
37
37 39 37
60
98 32
4
Knockout hole for left rear piping Knockout hole for left rear piping
34
OC301-A--2.qxp 04.4.28 11:16 AM Page 35
7 WIRING DIAGRAM
PKA-RP2.5FAL PKA-RP3FAL PKA-RP4FAL
SYMBOL NAME SYMBOL NAME SYMBOL NAME
P.B INDOOR POWER BOARD C CAPACITOR(FAN MOTOR) W.B WIRELESS REMOTE CONTROLLER BOARD
F1 FUSE(4A) MF FAN MOTOR RU RECEIVING UNIT
ZNR VARISTOR MV VANE MOTOR BZ BUZZER
I.B INDOOR CONTROLLER BOARD TB4 TERMINAL BLOCK(INDOOR/OUTDOOR LED1 LED(RUN INDICATOR)
CN2L CONNECTOR(LOSSNAY) CONNECTING LINE) LED2 LED(HOT ADJUST)
CN32 CONNECTOR(REMOTE SWITCH) TB5 TERMINAL BLOCK(REMOTE CONTROLLER SW1 SWITCH(HEATING ON/OFF)
CN41 CONNECTOR(HA TERMINAL-A) TRANSMISSION LINE)(OPTION) SW2 SWITCH(COOLING ON/OFF)
SW1 JUMPER WIRE(MODEL SELECTION) TH1 ROOM TEMPERATURE THERMISTOR R.B REMOTE CONTROLLER BOARD(OPTION)
SW2 JUMPER WIRE(CAPACITY CODE) (0°C/15kΩ, 25°C/5.4kΩ DETECT) CN2 CONNECTOR(SCHEDULE TIMER)
SWE SWITCH(EMERGENCY OPERATION) TH2 PIPE TEMPERATURE THERMISTOR/LIQUID TB6 TERMINAL BLOCK(REMOTE CONTROLLER
X4 RELAY(FAN MOTOR) (0°C/15kΩ, 25°C/5.4kΩ DETECT) TRANSMISSION LINE)
FC FAN PHASE CONTROL TH5 CONDENSER / EVAPORATOR TEMPERATURE
LED1 POWER SUPPLY(I.B) THERMISTOR (0°C/15kΩ, 25°C/5.4kΩ DETECT)
LED2 POWER SUPPLY(R.B)
LED3 TRANSMISSION(INDOOR-OUTDOOR)
INDOOR UNIT CN2S(WHT)
P.B
F1
2
1 DC14V TB4
MF ZNR
3 1
YLW S1
1 2 3 ORN S2
2 2 TO OUTDOOR UNIT
C 1 3
BRN S3
CONT.BOARD OUTDOOR
WHT
WHT
ORN
YLW
BRN
RED
BLK
BLK
J11
J12
J13
J14
J15
35
OC301-A--2.qxp 04.4.28 11:16 AM Page 36
PKA-RP2.5FAL Unit : mm
PKA-RP3FAL
PKA-RP4FAL
Strainer
#50
Heat exchanger
Refrigerant GAS pipe connection
(Flare)
Condenser/evaporator
temperature thermistor
(TH5)
Refrigerant flow in cooling
Refrigerant flow in heating
36
OC301-A--2.qxp 04.4.28 11:16 AM Page 37
9 TROUBLESHOOTING
9-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit.
Actions to be taken for service and the inferior phenomenon reoccurrence at field are summarized in the table below. Check
the contents below before investigating details.
Unit conditions at service Error code Actions to be taken for service (summary)
37
OC301-A--2.qxp 04.4.28 11:16 AM Page 38
MODE VANE AUTO START 3. Point the remote controller at the • If an air conditioner error occurs, the
HOUR
button sensor on the indoor unit and indoor unit's sensor emits an intermit-
CHECK LOUVER h
press the HOUR button. tent buzzer sound, the operation light
CHECK TEST RUN min flashes, and the error code is
button output.
SET RESET CLOCK (It takes 3 seconds at most for error
code to appear.)
Inspected unit Check code Beep output Operation LED Inspected unit Check code Beep output Operation LED
(0.4sec+0.4sec)
beep beep O 1 time
unit
P4 beep O 4 times 1 sec.O 4 times E6–EE Other than above Other than above
No check code
P5 beep O 5 times 1 sec.O 5 times (normal) No output Lights off
No check code
P6 beep O 6 times 1 sec.O 6 times (mistake of match-
ing with refrigerant beep beep beep Lights off
P8 beep O 8 times 1 sec.O 8 times address)
P9 beep O 2 times 1 sec.O 2 times
E4, E5 Other than above Other than above
38
OC301-A--2.qxp 04.4.28 11:16 AM Page 39
Note: Refer to the manual of outdoor unit for the details of display
9-3. SELF-DIAGNOSIS ACTION TABLE such as F, U, and other E.
Error Code Meaning of error code and detection method Cause Countermeasure
Abnormality of room temperature 1 Defective thermistor 1–3 Check resistance value of thermistor.
thermistor (TH1) characteristics. 0: ······15.0k"
1 The unit is in three-minute resume 2 Contact failure of connector 10: ····9.6k"
prevention mode if short/open of (CN20) on the indoor controller 20: ····6.3k"
thermistor is detected. Abnormal if the board. (Insert failure) 30: ····4.3k"
unit does not reset normally after three 3 Breaking of wire or contact 40: ····3.0k"
minutes. (The unit returns to normal failure of thermistor wiring. If you put force on (draw or bend) the lead wire
operation, if it has normally reset.) 4 Defective indoor controller with measuring resistance value of thermistor
2 Constantly detected during cooling, board. breaking of wire or contact failure can be
drying, and heating operation. detected.
Short: 90: or more 2 Check contact failure of connector (CN20) on
P1 Open: -40: or less the indoor controller board. Refer to page 45.
Turn the power on again and check restart
after inserting connector again.
4 Check room temperature display on remote
controller.
Replace indoor controller board if there is
abnormal difference with actual room
temperature.
Abnormality of drain sensor (DS) 1 Defective thermistor 1–3 Check resistance value of thermistor.
1 Suspensive abnormality, if short/open of characteristics 0: ······6.0k"
thermistor is detected for 30 seconds 2 Contact failure of connector 10: ····3.9k"
continuously. (CN31) on the indoor controller 20: ····2.6k"
Turn off compressor and indoor fan. board. (Insert failure). 30: ····1.8k"
2 Short/open is detected for 30 seconds 3 Breaking of wire or contact 40: ····1.3k"
continuously during suspensive
failure of drain sensor wiring. 2 Check contact failure of connector (CN31) on
abnormality.
(The unit returns to normal operation, 4 Defective indoor controller board. the indoor controller board. Refer to page 45.
if it has normally reset.) Turn the power on again and check restart
P4
3 Detect the following condition. after inserting connector again.
• During cooling and drying operation. 4 Replace indoor controller board if drain
• In case that pipe <liquid> temperature pump operates with the line of drain sensor
- room temperature <-10deg connector CN31-1 and 2 is short-circuited,
(Except defrosting) and abnormality reappears.
• When pipe <liquid> temperature or
room temperature is short/open Turn the power off, and on again to operate
temperature. after check.
• During drain pomp operation.
Malfunction of drain pump (DP) 1 Malfunction of drain pump 1 Check if drain-up machine works.
1 Suspensive abnormality, if thermistor 2 Defective drain 2 Check drain function.
of drain sensor is let heat itself and Clogged drain pump 3 Check the setting of lead wire of drain sensor
temperature rises slightly. Turn off Clogged drain pipe and check clogs of the filter.
compressor and indoor fan. 3 Attached drop of water at the 4 Replace indoor controller board if drain
2 Drain pomp is abnormal if the condition drain sensor pump operates with the line of drain sensor
P5 connector CN31-1 and 2 is short-circuited
above is detected during suspensive • Drops of drain trickles from
abnormality. lead wire. and abnormality reappears.
Refer to page 45.
3 Constantly detected during drain pomp • Clogged filter is causing
operation. wave of drain.
Turn the power off, and on again to operate
4 Defective indoor controller board. after check.
39
OC301-A--2.qxp 04.4.28 11:16 AM Page 40
Error Code Meaning of error code and detection method Cause Countermeasure
Freezing/overheating protection is (Cooling or drying mode) (Cooling or drying mode)
working 1 Clogged filter (reduced airflow) 1 Check clogs of the filter.
1 Freezing protection (Cooling mode) 2 Short cycle of air path 2 Remove shields.
The unit is in six-minute resume prevention 3 Low-load (low temperature)
mode if pipe <liquid or condenser/evap- operation beyond the tolerance
orator> temperature stays under range
-15: for three minutes, three minutes
after the compressor started. Abnormal 4 Defective indoor fan motor 4 Measure the resistance of fan motor's winding.
if it stays under -15: for three minutes • Fan motor is defective. Measure the output voltage of fan's connector
again within 16 minutes after six-minute • Indoor controller board is (FAN) on the indoor controller board.
resume prevention mode. defective. WThe indoor controller board should be
2 Frost abnormality (Only for the combination normal when voltage of AC 220~240V is
with inverter-type outdoor unit) detected while fan motor is connected.
Suspensive abnormal if unit operates in Refer to page 45.
frost prevention mode (below) for 9 5 Overcharge of refrigerant 56 Check operating condition of refrigerant
minutes or more. After that, when frost 6 Defective refrigerant circuit circuit.
prevention mode is released and (clogs)
compressor restarts its operation, unit is
not detected as abnormal if compressor
keeps operating for 20 minutes continuously
and abnormal if compressor stops
operating within 20 minutes and unit (Heating mode) (Heating mode)
operates in frost prevention mode for 1 Clogged filter (reduced airflow) 1 Check clogs of the filter.
P6 more than 9 minutes again. (Not abnormal 2 Short cycle of air path 2 Remove shields.
if unit stops operating in frost prevention 3 Over-load (high temperature)
mode within 9 minutes) operation beyond the tolerance
<Frost prevention mode> range
If pipe <liquid or condenser-evaporator> 4 Defective indoor fan motor 4 Measure the resistance of fan motor's
temperature is 2: or below when 16 • Fan motor is defective. winding.
minutes has passed after compressor • Indoor controller board is Measure the output voltage of fan's connector
starts operating, unit will start operating defective. (FAN) on the indoor controller board.
in frost prevention mode which stops
WThe indoor controller board should be
compressor operation. After that, when
pipe <liquid or condenser/evaporator> normal when voltage of AC 220~240V is
temperature stays 10: or more for 3 detected while fan motor is connected.
minutes, frost prevention mode will be Refer to page 45.
released and compressor will restart its 5 Overcharge of refrigerant 5~7Check operating condition of refrigerant
operation. 6 Defective refrigerant circuit circuit.
3 Overheating protection (Heating mode) (clogs)
The units is in six-minute resume 7 Bypass circuit of outdoor unit
prevention mode if pipe <condenser / is defective.
evaporator> temperature is detected as
over 74: after the compressor started.
Abnormal if the temperature of over
74: is detected again within 10 minutes
after six-minute resume prevention
mode.
Abnormality of pipe temperature 1 Slight temperature difference 1~4 Check pipe <liquid or condenser /
<Cooling mode> between indoor room evaporator> temperature with room
Detected as abnormal when the pipe tem- temperature and pipe <liquid temperature display on remote
perature is not in the cooling range 3 min- or condenser / evaporator> controller and outdoor controller circuit
utes later of compressor start and 6 min- temperature thermistor board.
utes later of the liquid or condenser/evapo- • Shortage of refrigerant Pipe <liquid or condenser / evaporator>
rator pipe is out of cooling range. • Disconnected holder of pipe temperature display is indicated by
Note 1) It takes at least 9 min. to detect. <liquid or condenser / setting SW2 of outdoor controller circuit
Note 2) Abnormality P8 is not detected in evaporator> thermistor board as follows.
drying mode. • Defective refrigerant circuit
)
Conduct temperature check with outdoor
Cooling range : Indoor pipe temperature
(TH2 or TH5) – intake temperature
(TH1) [ -3 deg
2 Converse connection of
extension pipe (on plural units
connection)
( controller circuit board after connecting
‘A-Control Service Tool(PAC-SK52ST)’.
Temperature display of indoor condenser/
TH: Lower temperature between: liquid 3 Converse wiring of indoor/ Temperature display of indoor liquid pipe
Indoor 1 evaporator pipe Indoor 1
pipe temperature and condenser/ outdoor unit connecting wire 1 2 3 4 5 6 1 2 3 4 5 6
evaporator temperature (on plural units connection) ON ON
<Heating mode> room temperature and pipe Temperature display of indoor condenser/
Temperature display of indoor liquid pipe
When 10 seconds have passed after the <condenser / evaporator> Indoor 2 evaporator pipe Indoor 2
40
OC301-A--2.qxp 04.4.28 11:16 AM Page 41
Error Code Meaning of error code and detection method Cause Countermeasure
Abnormality of pipe temperature ther- 1 Defective thermistor 1–3 Check resistance value of thermistor.
mistor / Condenser-Evaporator (TH5) characteristics For characteristics, refer to (P1) above.
1 The unit is in three-minute resume pro- 2 Contact failure of connector 2 Check contact failure of connector (CN29)
tection mode if short/open of thermistor (CN29) on the indoor controller on the indoor controller board.
is detected. Abnormal if the unit does board. (Insert failure) Refer to page 45.
not get back to normal within three min- 3 Breaking of wire or contact Turn the power on and check restart after
utes. (The unit returns to normal opera- inserting connector again.
failure of thermistor wiring. 4 Operate in test run mode and check pipe
tion, if it has normally reset.) 4 Temperature of thermistor is <condenser / evaporator> temperature with
2 Constantly detected during cooling, dry- 90: or more or -40: or less outdoor controller circuit board. If pipe
ing, and heating operation (except caused by defective refrigerant <condenser / evaporator> temperature is
defrosting) circuit. exclusively low (in cooling mode) or high (in
Short: 90: or more 5 Defective indoor controller heating mode), refrigerant circuit may have
Open: -40: or less board. defective.
5 Operate in test run mode and check pipe
<condenser / evaporator> temperature with
P9 outdoor control circuit board. If there is
exclusive difference with actual pipe
<condenser / evaporator> temperature
replace indoor controller board.
There is no abnormality if none of above
comes within the unit.
Turn the power off and on again to operate.
In case of checking pipe temperature
(
with outdoor controller circuit board,
be sure to connect A-control service
tool (PAC-SK52ST).
Temperature display of indoor condenser/
)
Temperature display of indoor condenser/
evaporator pipe Indoor 1 evaporator pipe Indoor 2
1 2 3 4 5 6 1 2 3 4 5 6
ON ON
OFF OFF
Remote controller signal receiving error 1 Contact failure at transmission 1 Check disconnection or looseness of indoor
1 Abnormal if indoor controller board can wire of remote controller unit or transmission wire of remote controller.
not receive normally any data from 2 All remote controllers are set 2 Set one of the remote controllers “main”.
remote controller or from other indoor as “sub” remote controller. In If there is no problem with the action above.
controller board for three minutes. this case, E0 is displayed on 3 Diagnose remote controllers.
a) When “RC OK” is displayed,
2 Indoor control board cannot receive any remote controller, and E4 is Remote controllers have no problem.
signal from remote controller for two displayed at LED (LED1, LED2) Put the power off, and on again to check.
minutes. on the outdoor controller circuit If abnormality generates again, replace
E4 board. indoor controller board.
3 Defective transmitting receiving b) When “RC NG” is displayed,
circuit of remote controller Replace remote controller.
4 Defective transmitting receiving c) When “RC E3” is displayed,
d) When “ERC 00-06” is displayed,
circuit of indoor controller board.
[ c),d)➜Noise may be causing abnormality. ]
5 Noise has entered into the ✽ If the unit is not normal after replacing
transmission wire of remote indoor controller board in group control,
controller. indoor controller board of address “0”
may be abnormal.
Remote controller transmitting error 1 Defective transmitting receiving 12 Turn the power off, and on again to
1 Abnormal if indoor controller board cannot circuit of indoor controller board. check. If abnormality generates again,
E5 check the blank of transmission path for 2 Noise has entered into the replace indoor controller board.
three minutes. transmittion wire of remote
2 Abnormal if indoor controller board cannot
finish transmitting 30 times consecutively. controller.
Indoor/outdoor unit communication 1 Contact failure, short circuit or, ✽ Check LED display on the outdoor control
error (Signal receiving error) mis-wiring (converse wiring) of circuit board. (Connect A-control service tool,
1 Abnormal if indoor controller board indoor/outdoor unit connecting PAC-SK52ST.)
cannot receive any signal normally for wire Refer to EA-EC item if LED displays EA-EC.
six minutes after putting the power on. 1 Check disconnection or looseness of indoor/
2 Abnormal if indoor controller board 2 Defective transmitting receiving outdoor unit connecting wire of indoor unit or
cannot receive any signal normally for circuit of indoor controller board outdoor unit.
three minutes. 3 Defective transmitting receiving Check all the units in case of twin triple
E6 3 Consider the unit abnormal under the circuit of indoor controller board indoor unit system.
following condition: When two or more 4 Noise has entered into indoor/ 2-4 Turn the power off, and on again to
indoor units are connected to one outdoor unit connecting wire. check. If abnormality generates again,
outdoor unit, indoor controller board replace indoor controller board or outdoor
cannot receive a signal for three minutes controller circuit board.
from outdoor controller circuit board, a ✽ Other indoor controller board may have
signal which allows outdoor controller defective in case of twin triple indoor unit
circuit board to transmit signals. system.
Indoor/outdoor unit communication 1 Defective transmitting receiving 1-3 Turn the power off, and on again to
error (Transmitting error) circuit of indoor controller board check. If abnormality generates again,
Abnormal if “1” receiving is detected 30 2 Noise has entered into power replace indoor controller board.
E7
times continuously though indoor controller supply.
board has transmitted “0”. 3 Noise has entered into outdoor
control wire.
41
OC301-A--2.qxp 04.4.28 11:16 AM Page 42
42
OC301-A--2.qxp 04.4.28 11:16 AM Page 43
Emergency switch(Cool)
Emergency switch(Heat)
ON STAND
COOL HEAT
OFF BY
3. To stop operation
• Press either emergency operation switch (cooling/heating).
9-5-2. When wired remote controller or indoor unit micro computer troubles
1. If there is not any other wrong when trouble occures, emergency operation starts as the indoor controller board switch
(SWE) is set to ON.
During the emergency operation the indoor unit is as follows;
(1) Indoor fan high speed operation (2) Drain-up machine operation
2. When emergency operating for COOL or HEAT, setting of the switch (SWE) in the indoor controller board and outdoor unit
emergency operation are necessary.
43
OC301-A--2.qxp 04.4.28 11:16 AM Page 44
Vane motor (MV) Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:~30:)
4 Orange
Normal
5 Red M Connector Abnormal
RP2.5, RP3, RP4
2 Pink
Brown–Yellow
Yellow Brown Blue
Brown–Blue
186~214" Open or short
3 6 1 Red–Orange
Red–Pink
Thermistor R0=15kΩ ± 3% 30
Fixed number of B=3480K ± 2%
1 1
Rt=15exp { 3480( )} 20
273+t 273
0: 15kΩ
10: 9.6kΩ 10
20: 6.3kΩ
25: 5.4kΩ
30: 4.3kΩ 0
40: 3.0kΩ -20 -10 0 10 20 30 40 50
Temperature (:)
44
OC301-A--2.qxp 04.4.28 11:16 AM Page 45
CN22
CN90 CN2D Connect to the terminal block(TB5)
CN32 Connect to the wireless Connect to the indoor (Remote controller connecting wire)
CN6V Connector remote controller board power board (CN2S) (10~16V DC)
Vane motor output (Remote switch) (CNB) 12~16V DC
}
(MV)
}
– +
+ –
LED1 CN21
Power supply (I.B) Pipe temperature
thermistor/Liquid (TH2)
LED2 CN20
Power supply (R.B) Room temperature
thermistor (TH1)
LED3
Transmission
(Indoor/outdoor) CN2L
Connector (LOSSNAY)
CN41
Connector (HA terminal-A)
CN31
Drain sensor (DS)
CN29
Condenser/evaporator
CN03 } + temperature thermistor (TH5)
Connect to the indoor
power board (CN02) –
Between 1 to 3 220~240V AC
Between 3 to 5 0~24V DC
(Indoor/outdoor transmission) +
– } CN25
Humidifier output
(12~16V DC)
+
– } CN27
Drain-up machine
output (DP)
(12~16V DC)
SWE
Emergency operation
FAN
Fan motor output (MF)
Between 1 to 5 100~240V AC
45
OC301-A--2.qxp 04.4.28 11:16 AM Page 46
CN02
Connect to the indoor
controller board (CN03) +
}
Between 1 and 2 0~24V DC
–
(Indoor/Outdoor transmission)
Between 2 and 3 220~240V AC
+ – Fuse 4A/250V
}
CN01
Connect to the Terminal Block (TB4)
(Indoor/outdoor connecting line)
Between 1 and 2 220~240V AC
Between 2 and 3 0~24V DC
(Indoor/outdoor transmission)
46
OC301-A--2.qxp 04.4.28 11:16 AM Page 47
10 DISASSEMBLY PROCEDURE
PKA-RP3FAL
OPERATING PROCEDURE PHOTOS & ILLUSTRATION
1. Removing the lower side of the indoor unit from the
installation plate Figure 1
(1) Remove the 2 screws.
Hang the indoor unit hangers to the catches on the
installation plate.
Metal fixture
Screws
Terminal cover
Connector
47
OC301-A--2.qxp 04.4.28 11:16 AM Page 48
Indoor controller
board case Electrical parts box
Vane motor
Screws
Drain hose
48
OC301-A--2.qxp 04.4.28 11:16 AM Page 49
Motor fixture
Photo 9
Fan motor
Screw
Screw
Motor support
Motor
support
Photo 10
Line flow fans
Photo 11
Bearing support
Lineflow fan
49
OC301-A--2.qxp 04.4.28 11:16 AM Page 50
11 PARTS LIST
STRUCTURAL PARTS
PKA-RP2.5FAL
PKA-RP3FAL 12 11
1 13
10 9 8
5 7
4
6
50
OC301-A--2.qxp 04.4.28 11:16 AM Page 51
STRUCTURAL PARTS
PKA-RP4FAL
12 11
1 13
14 10 9 8
4
6
51
OC301-A--2.qxp 04.4.28 11:16 AM Page 52
ELECTRICAL PARTS
PKA-RP2.5FAL
PKA-RP3FAL 35
1
34
2 31
30 32
33
3
29
5 28
25
27
6
26 24
7 19
8
23 20 18
17
9 22 21
10 11 12 13 14 15 16
,
Q ty/set
Remarks Wiring Recom- Price
No. Part No. Part Name Specification PKA-
(Drawing No.) Diagram mended
,
Symbol Q ty
RP2.5FAL RP3FAL Unit Amount
1 R01 Z61 102 BEARING MOUNT 1 1
2 R01 13G 114 LEFT LINEFLOW FAN 1 1
R01 E61 480 HEAT EXCHANGER 1
3
R01 E62 480 HEAT EXCHANGER 1
4 T7W E13 529 DRAIN PAN 1 1
5 — GUIDE VANE 16 16 (BG25J821H01)
6 — ARM 3 3 (BG25H301H02)
7 R01 12G 621 CENTER COVER 1 1
8 R01 12G 063 JOINT SHAFT 1 1
9 R01 12G 002 AUTO VANE 2 2
10 R01 KV5 527 DRAIN HOSE 1 1
11 T7W E13 223 VANE MOTOR 1 1 MV
12 R01 50J 317 WIRELESS REMOTE CONTROLLER BOARD 1 1 W.B
13 — TERMINAL COVER 1 1 (BG02J608H07)
14 R01 588 255 CAPACITOR (FAN MOTOR) 2.0µF 440V 1 1 C
15 T7W E33 310 INDOOR CONTROLLER BOARD 1 1 I.B
16 T7W E00 239 FUSE 250V 4A 1 1 F1
17 — CONTROLLER COVER 1 1 (BG02A648G02)
52
OC301-A--2.qxp 04.4.28 11:16 AM Page 53
,
Q ty/set
Remarks Wiring Recom- Price
No. Part No. Part Name Specification PKA- Diagram mended
(Drawing No.) Symbol Q ty
,
RP2.5FAL RP3FAL Unit Amount
18 — CONTROLLER CASE 1 (BG25B573H06)
19 T7W E00 313 INDOOR POWER BOARD 1 P.B
20 T7W E13 716 TERMINAL BLOCK 3P(S1, S2, S3) 1 TB4
21 T7W E12 202 ROOM TEMPERATURE THERMISTOR 1 TH1
CONDENSER /
22 R01 E34 202 1 TH5
EVAPORATOR TEMPERATURE THERMISTOR
23 T7W E11 202 PIPE TEMPERATURE THERMISTOR 1 TH2
24 — MOTOR BAND 1 (BG02H065H01)
25 R01 12G 220 FAN MOTOR PN4S40-K 1 MF
26 R01 12G 105 RUBBER MOUNT 2
27 — MOTOR BAND 1 (BG02H178H01)
28 R01 13G 115 RIGHT LINEFLOW FAN 1
29 — CENTER SUPPORT 1 (BG00R259G07)
30 — BEARING BAND 1 (BG02L462H02)
31 R01 KV5 102 BEARING MOUNT 1
32 R01 12G 103 SLEEVE BEARING 1
33 — MOTOR LEG 1 (BG02A534H16)
34 T7W B02 675 FAN GUARD 2
35 R01 005 103 SLEEVE BEARING 1
53
OC301-A--2.qxp 04.4.28 11:16 AM Page 54
ELECTRICAL PARTS
PKA-RP4FAL
36
1
35
2 32
31 33
34
3
30
5 29
26
28
6
24 27 25
7 19
8
23 20 18
17
9 22 21
10 11 12 13 14 15 16
,
Q ty/set Remarks Wiring Recom- Price
No. Part No. Part Name Specification (Drawing No.) Diagram mended
,
PKA-RP4FAL Symbol Q ty Unit Amount
1 R01 Z61 102 BEARING MOUNT 1
2 R01 17G 114 LEFT LINEFLOW FAN 1
3 T7W E99 480 HEAT EXCHANGER 1
4 T7W E14 529 DRAIN PAN 1
5 — GUIDE VANE 22 (BG25J821H01)
6 — ARM 4 (BG25H301H02)
7 R01 12G 621 CENTER COVER 1
8 R01 12G 063 JOINT SHAFT 1
9 R01 16G 002 AUTO VANE 2
10 R01 KV5 527 DRAIN HOSE 1
11 T7W E13 223 VANE MOTOR 1 MV
12 R01 50J 317 WIRELESS REMOTE CONTROLLER BOARD 1 W.B
13 — TERMINAL COVER 1 (BG02J608H07)
14 R01 576 255 CAPACITOR (FAN MOTOR) 3.0µF 440V 1 C
15 T7W E33 310 INDOOR CONTROLLER BOARD 1 I.B
16 T7W E00 239 FUSE 250V 4A 1 F1
17 — CONTROLLER COVER 1 (BG02A648G02)
54
OC301-A--2.qxp 04.4.28 11:16 AM Page 55
,
Q ty/set Remarks Wiring Recom- Price
No. Part No. Part Name Specification Diagram mended
,
PKA-RP4FAL (Drawing No.) Symbol Q ty Unit Amount
18 — CONTROLLER CASE 1 (BG25B573H06)
19 T7W E00 313 INDOOR POWER BOARD 1 P.B
20 T7W E13 716 TERMINAL BLOCK 3P(S1, S2, S3) 1 TB4
21 T7W E12 202 ROOM TEMPERATURE THERMISTOR 1 TH1
CONDENSER /
22 R01 E34 202 1 TH5
EVAPORATOR TEMPERATURE THERMISTOR
23 T7W E11 202 PIPE TEMPERATURE THERMISTOR 1 TH2
24 T7W E00 457 FLARE NUT 5/8 1
25 — MOTOR BAND 1 (BG02H065H01)
26 T7W 571 762 FAN MOTOR PN4S70-K 1 MF
27 R01 16G 105 RUBBER MOUNT 2
28 — MOTOR BAND 1 (BG02H178H01)
29 R01 17G 115 RIGHT LINEFLOW FAN 1
30 — CENTER SUPPORT 1 (BG00R259G07)
31 — BEARING BAND 1 (BG02L462H02)
32 R01 KV5 102 BEARING MOUNT 1
33 R01 12G 103 SLEEVE BEARING 1
34 — MOTOR LEG 1 (BG02A534H17)
35 T7W B03 675 FAN GUARD 2
36 R01 005 103 SLEEVE BEARING 1
55
OC301-A--2.qxp 04.4.28 11:16 AM Page 56
12 OPTIONAL PARTS