PKA-RP2.5FAL Pka-Rp3Fal Pka-Rp4Fal: Technical & Service Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 56

OC301-A--1.qxp 04.4.

28 11:14 AM Page 1

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS


SPLIT-TYPE, AIR CONDITIONERS 2004
No.OC301
REVISED EDITION-A

TECHNICAL & SERVICE MANUAL


Series PKA Wall Mounted R407C/R410A
Indoor unit • PKA-RP2.5FAL is added in
[Model names] [Service Ref.] REVISED EDITION-A.

PKA-RP2.5FAL PKA-RP2.5FAL • This manual does not cover


outdoor units. When servicing
them, please refer to service
PKA-RP3FAL PKA-RP3FAL manual OC261 REVISED
EDITION-B, OC285, OC294
PKA-RP4FAL PKA-RP4FAL REVISED EDITION-A, OC298
and this manual in a set.
• Please void OC301.

CONTENTS

1. COMBINATION OF
INDOOR AND OUTDOOR UNITS ····················2
2. SAFETY PRECAUTION ····································3
3. PART NAMES AND FUNCTIONS·····················6
Model name 4. SPECIFICATIONS ·············································8
Indoor unit
indication 5. DATA································································13
6. OUTLINES AND DIMENSIONS ······················33
7. WIRING DIAGRAM ·········································35
8. REFRIGERANT SYSTEM DIAGRAM ·············36
9. TROUBLESHOOTING·····································37
10. DISASSEMBLY PROCEDURE ·······················47
11. PARTS LIST ····················································50
12. OPTIONAL PARTS··························Back Cover

Remote controller
OC301-A--1.qxp 04.4.28 11:14 AM Page 2

1 COMBINATION OF INDOOR AND OUTDOOR UNITS

(R410A Inverter)
Outdoor unit [OC294 REVISED EDITION-A]
Heat pump type
Indoor unit
PUHZ-RP
2.5VHA 3VHA 4VHA
4VHA1
PKA-RP2.5FAL — —
PKA-RP3FAL — —
PKA-RP4FAL — —

(R407C Fixed speed)


Outdoor unit [OC285] Outdoor unit [OC298]
Heat pump type Cooling only type
Indoor unit
PUH-P PU-P
2.5VGAA 3VGAA 3YGAA 4YGAA 2.5VGAA 3VGAA 3YGAA 4YGAA

PKA-RP2.5FAL — — — — — —
Heat pump without
electric heater
or PKA-RP3FAL — — — —
Cooling only
PKA-RP4FAL — — — — — —

(R407C Fixed speed)


Outdoor unit [OC261 REVISED EDITION-B]
Heat pump type Cooling only type
PUH-P PU-P
Indoor unit
2.5 3 4 2.5 3 4
VGAA.UK YGAA.UK VGAA.UK YGAA.UK VGAA.UK YGAA.UK VGAA.UK YGAA.UK VGAA.UK YGAA.UK VGAA.UK YGAA.UK

VGAA1.UK YGAA1.UK VGAA1.UK YGAA1.UK VGAA1.UK YGAA1.UK VGAA1.UK YGAA1.UK VGAA1.UK YGAA1.UK VGAA1.UK YGAA1.UK

PKA-RP2.5FAL — — — — — — — —
Heat pump without
electric heater
or PKA-RP3FAL — — — — — — — —
Cooling only
PKA-RP4FAL — — — — — — — —

2
OC301-A--1.qxp 04.4.28 11:14 AM Page 3

2 SAFETY PRECAUTION

CAUTIONS RELATED TO NEW REFRIGERANT


Cautions for units utilizing refrigerant R407C

Do not use the existing refrigerant piping. Use liquid refrigerant to seal the system.
The old refrigerant and lubricant in the existing piping If gas refrigerant is used to seal the system, the composition
contains a large amount of chlorine which may cause the of the refrigerant in the cylinder will change and performance
lubricant deterioration of the new unit. may drop.

Use “low residual oil piping” Do not use a refrigerant other than R407C.
If there is a large amount of residual oil (hydraulic oil, etc.) If another refrigerant (R22, etc.) is used, the chlorine in the
inside the piping and joints, deterioration of the lubricant refrigerant may cause the lubricant deterioration.
will result.

Store the piping to be used during installation Use a vacuum pump with a reverse flow check valve.
indoors with keep both ends sealed until just The vacuum pump oil may flow back into the refrigerant
before brazing. cycle and cause the lubricant deterioration.
(Store elbows and other joints in a plastic bag.)

If dust, dirt, or water enters the refrigerant cycle, Ventilate the room if refrigerant leaks during
deterioration of the oil and compressor trouble may result. operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
Use ESTR , ETHER or HAB as the lubricant to
coat flares and flange connection parts.
If large amount of mineral oil enter, that can cause
deterioration of refrigerant oil etc.

[1] Cautions for service


·After recovering the all refrigerant in the unit, proceed to working.
·Do not release refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.

[2] Refrigerant recharging


(1) Refrigerant recharging process
1Direct charging from the cylinder.
·R407C cylinder are available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it.
(By liquid refrigerant)

Unit

Gravimeter
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.

3
OC301-A--1.qxp 04.4.28 11:14 AM Page 4

[3] Service tools


Use the below service tools as exclusive tools for R407C refrigerant.

No. Tool name Specifications


1 Gauge manifold ·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
2 Charge hose ·Only for R407C.
·Use pressure performance of 5.10MPa·G or over.
3 Electronic scale
4 Gas leak detector ·Use the detector for R134a or R407C.
5 Adapter for reverse flow check. ·Attach on vacuum pump.
6 Refrigerant charge base.
7 Refrigerant cylinder. ·For R407C ·Top of cylinder (Brown)
·Cylinder with syphon
8 Refrigerant recovery equipment.

4
OC301-A--1.qxp 04.4.28 11:14 AM Page 5

CAUTIONS RELATED TO NEW REFRIGERANT


Cautions for units utilizing refrigerant R410A

Use new refrigerant pipes. Do not use refrigerant other than R410A.
In case of using the existing pipes for R22, be careful with If other refrigerant (R22 etc.) is used, chlorine in refrige-
the followings. rant can cause deterioration of refrigerant oil etc.
· For RP4 be sure to perform replacement operation before
test run.
· Change flare nut to the one provided with this product.
Use a vacuum pump with a reverse flow check
Use a newly flared pipe. valve.
· Avoid using thin pipes. Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.

Make sure that the inside and outside of refrige-


Use the following tools specifically designed for
rant piping is clean and it has no contamination
use with R410A refrigerant.
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc. The following tools are necessary to use R410A refrigerant.
In addition, use pipes with specified thickness. Tools for R410A
Gauge manifold Flare tool
Contamination inside refrigerant piping can cause deterio- Charge hose Size adjustment gauge
ration of refrigerant oil etc. Gas leak detector Vacuum pump adaptor
Torque wrench Electronic refrigerant
Store the piping to be used during installation charging scale
indoors and keep both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.) Keep the tools with care.

If dirt, dust or moisture enter into refrigerant cycle, that can If dirt, dust or moisture enter into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of com- cause deterioration of refrigerant oil or malfunction of com-
pressor. pressor.

Use ester oil, ether oil or alkylbenzene oil (small


Do not use a charging cylinder.
amount) as the refrigerant oil applied to flares
and flange connections. If a charging cylinder is used, the composition of refrigera-
If large amount of mineral oil enter, that can cause deterio- nt will change and the efficiency will be lowered.
ration of refrigerant oil etc.
Ventilate the room if refrigerant leaks during
Charge refrigerant from liquid phase of gas operation. If refrigerant comes into contact with
cylinder. a flame, poisonous gases will be released.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.

[1] Cautions for service


(1) Perform service after collecting the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.

[2] Additional refrigerant charge


When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)

5
OC301-A--1.qxp 04.4.28 11:14 AM Page 6

Unit

Gravimeter

[3] Service tools


Use the below service tools as exclusive tools for R410A refrigerant.

No. Specifications
1 Gauge manifold ·Only for R410A
·Use the existing fitting specifications. (UNF1/2)
·Use high-tension side pressure of 5.3MPa·G or over.
2 Charge hose ·Only for R410A
·Use pressure performance of 5.09MPa·G or over.
3 Electronic scale
4 Gas leak detector ·Use the detector for R134a, R407C or R410A.
5 Adaptor for reverse flow check ·Attach on vacuum pump.
6 Refrigerant charge base
7 Refrigerant cylinder ·Only for R410A Top of cylinder (Pink)
Cylinder with syphon
8 Refrigerant recovery equipment

3 PART NAMES AND FUNCTIONS


● Indoor Unit

Air intake Filter Air intake grille


room air is suctioned (Removes dust and dirt from the intake air.)
in here.

Indicator lamp section

Guide vane
Air flow can be changed to horizontally
by moving the Guide vane to the left or Swing louvers
right.
Disperses airflow up and
down as well as adjusts the
angle of air flow direction.
Air outlet Air outlet

6
OC301-A--1.qxp 04.4.28 11:14 AM Page 7

●Wireless remote controller


● When cover is open.

CHECK TEST RUN display


CHECK&TEST RUN display indicates that
the unit is being checked or test-run.

MODEL SELECT display


Blinks when model is selected.

display
Lights up while transmission to the indoor
unit is mode using switches.

display
SET TEMP. display indicates desired temper-
ature set.

display CLOCK display


OPERATION MODE display Displays the current time.
Operation mode display indicates which op-
eration mode is in effect. TIMER display
CHECK TEST RUN
MODEL SELECT ˚C Displays when in timer operation or when
AMPM
setting timer.

“ ”“ ” display
AMPM
Displays the order of timer operation.
NOT AVAILABLE

display “ ”“ ” display
ON/OFF TEMP Displays whether timer is on or off.
The vertical direction of air flow is indicated.
display
FAN SPEED display indicates which fan
button
speed has been selected. SET TEMPERATURE button sets any desired
room temperature.
FAN AUTO STOP
ON/OFF button
The unit is turned ON and OFF alternately MODE VANE AUTO START
each time the button is pressed. TIMER CONTROL buttons
CHECK LOUVER h AUTO STOP (OFF timer): when this switch
is set, the air conditioner will be au-
FAN SPEED SELECT button tomatically stopped at the preset time.
Used to change the fan speed. TEST RUN min AUTO START (ON timer): when this switch
is set, the air conditioner will be automatical-
ly started at the preset time.
MODE SELECT button SET RESET CLOCK

Used to switch the operation mode between


cooling, drying, blowing, heating and auto h and min buttons
mode. Buttons used to set the “hour and minute” of
the current time and timer settings.
w In case the outdoor unit is cool only type,
the heating mode is not available.

LOUVER button
CHECK-TEST RUN button
This switch the horizontal fan motion ON
Only press this button to perform an inspec- and OFF.
tion check or test operation.
(Not available for this model.)
Do not use it for normal operation.

CLOCK button
VANE CONTROL button
RESET button
Used to change the air flow direction.
SET button

7
OC301-A--1.qxp 04.4.28 11:14 AM Page 8

4 SPECIFICATIONS
4-1. Heat pump type (1)
Service Ref. PKA-RP2.5FAL
Item
Function Cooling Heating
Btu/h 20,500 23,900
Capacity
W 6,000(2,700~6,700) 7,000(2,800~8,200)
Total input kW 1.55 2.01
Service Ref. PKA-RP2.5FAL
Power supply(phase, cycle, voltage) Single phase, 50Hz, 220-230-240V
Input kW 0.09 0.09
Running current A 0.43 0.43
Starting current A 0.80 0.80
External finish Munsell 3.4Y 7.7/0.8
Heat exchanger Plate fin coil
INDOOR UNIT

Fan Fan(drive) x No. Line flow (direct) x 2


Fan motor output kW 0.040
Airflow(Low-High) K/min(CFM) 15-20(530-705)
External static pressure Pa(mmAq) 0(direct blow)
Operation control & Thermostat Wireless remote controller & built-in
Noise level(Low-High) dB 39-45
Unit drain pipe O.D. mm(in.) 26(1)
Dimensions W mm(in.) 1,400(55-1/8)
D mm(in.) 235(9-1/4)
H mm(in.) 340(13-3/8)
Weight kg(lbs) 24(53)
OUTDOOR Service Ref. PUHZ-RP2.5VHA
UNIT

Service Ref. PKA-RP3FAL


Item
Function Cooling Heating
Btu/h 24,200 27,300
Capacity
W 7,100(3,300~8,100) 8,000(3,500~10,200)
Total input kW 1.98 2.40
Service Ref. PKA-RP3FAL
Power supply(phase, cycle, voltage) Single phase, 50Hz, 220-230-240V
Input kW 0.09 0.09
Running current A 0.43 0.43
Starting current A 0.80 0.80
External finish Munsell 3.4Y 7.7/0.8
Heat exchanger Plate fin coil
INDOOR UNIT

Fan Fan(drive) x No. Line flow (direct) x 2


Fan motor output kW 0.040
Airflow(Low-High) K/min(CFM) 15-20(530-706)
External static pressure Pa(mmAq) 0(direct blow)
Operation control & Thermostat Wireless remote controller & built-in
Noise level(Low-High) dB 39-45
Unit drain pipe O.D. mm(in.) 26(1)
Dimensions W mm(in.) 1,400(55-1/8)
D mm(in.) 235(9-1/4)
H mm(in.) 340(13-3/8)
Weight kg(lbs) 24(53)
OUTDOOR Service Ref. PUHZ-RP3VHA
UNIT

Notes1. Rating Conditions (ISO T1)


Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)

2. Guaranteed operating range


Indoor Outdoor
Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
Cooling
Lower limit D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Upper limit D.B. 28˚C D.B. 21˚C, W.B. 15˚C
Heating
Lower limit D.B. 17˚C D.B. -11˚C, W.B. -12˚C
3. Guaranteed voltage
198~264V, 50Hz

4. Above data based on indicated voltage 5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.
Indoor Unit Single phase 230V 50Hz
Outdoor Unit Single phase 230V 50Hz

8
OC301-A--1.qxp 04.4.28 11:14 AM Page 9

Service Ref. PKA-RP4FAL


Item
Function Cooling Heating
Btu/h 34,100 38,200
Capacity PUHZ-RP4VAH W 10,000(5,000~11,400) 11,200(5,600~14,000)
PUHZ-RP4VAH1 W 10,000(4,900~11,400) 11,200(4,500~14,000)
Total input kW 2.93 3.25
Service Ref. PKA-RP4FAL
Power supply(phase, cycle, voltage) Single phase, 50Hz, 220-230-240V
Input kW 0.11 0.11
Running current A 0.52 0.52
Starting current A 0.90 0.90
External finish Munsell 3.4Y 7.7/0.8
Heat exchanger Plate fin coil
INDOOR UNIT

Fan Fan(drive) x No. Line flow (direct) x 2


Fan motor output kW 0.070
Airflow(Low-High) K/min(CFM) 22-28(780-990)
External static pressure Pa(mmAq) 0(direct blow)
Operation control & Thermostat Wireless remote controller & built-in
Noise level(Low-High) dB 41-46
Unit drain pipe O.D. mm(in.) 26(1)
Dimensions W mm(in.) 1,680(66-1/8)
D mm(in.) 235(9-1/4)
H mm(in.) 340(13-3/8)
Weight kg(lbs) 28(62)
OUTDOOR Service Ref. PUHZ-RP4VHA
UNIT PUHZ-RP4VHA1

Notes1. Rating Conditions (ISO T1)


Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)

2. Guaranteed operating range


Indoor Outdoor
Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
Cooling
Lower limit D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Upper limit D.B. 28˚C D.B. 21˚C, W.B. 15˚C
Heating
Lower limit D.B. 17˚C D.B. -11˚C, W.B. -12˚C
3. Guaranteed voltage
198~264V, 50Hz

4. Above data based on indicated voltage 5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.
Indoor Unit Single phase 230V 50Hz
Outdoor Unit Single phase 230V 50Hz

9
OC301-A--1.qxp 04.4.28 11:14 AM Page 10

4-2. Heat pump type (2)


Service Ref. PKA-RP2.5FAL
Item
Function Cooling Heating
Btu/h 22,000 25,100
Capacity
W 6,450 7,350
Total input kW 2.65 2.63
Service Ref. PKA-RP2.5FAL
Power supply(phase, cycle, voltage) Single phase, 50Hz, 220-230-240V
Input kW 0.09 0.09
Running current A 0.43 0.43
Starting current A 0.80 0.80
External finish Munsell 3.4Y 7.7/0.8
Heat exchanger Plate fin coil
INDOOR UNIT

Fan Fan(drive) x No. Line flow (direct) x 2


Fan motor output kW 0.040
Airflow(Low-High) K/min(CFM) 15-20(530-706)
External static pressure Pa(mmAq) 0(direct blow)
Operation control & Thermostat Wireless remote controller & built-in
Noise level(Low-High) dB 39-45
Unit drain pipe O.D. mm(in.) 26(1)
Dimensions W mm(in.) 1,400(55-1/8)
D mm(in.) 235(9-1/4)
H mm(in.) 340(13-3/8)
Weight kg(lbs) 24(53)
PUH-P2.5VGAA
OUTDOOR PUH-P2.5VGAA.UK / PUH-P2.5YGAA.UK
UNIT Service Ref.
PUH-P2.5VGAA1.UK/ PUH-P2.5YGAA1.UK

Service Ref. PKA-RP3FAL


Item
Function Cooling Heating
Btu/h 26,800 32,100
Capacity
W 7,850 9,400
Total input kW 3.43 3.61
Service Ref. PKA-RP3FAL
Power supply(phase, cycle, voltage) Single phase, 50Hz, 220-230-240V
Input kW 0.09 0.09
Running current A 0.43 0.43
Starting current A 0.80 0.80
External finish Munsell 3.4Y 7.7/0.8
Heat exchanger Plate fin coil
INDOOR UNIT

Fan Fan(drive) x No. Line flow (direct) x 2


Fan motor output kW 0.040
Airflow(Low-High) K/min(CFM) 15-20(530-705)
External static pressure Pa(mmAq) 0(direct blow)
Operation control & Thermostat Wireless remote controller & built-in
Noise level(Low-High) dB 39-45
Unit drain pipe O.D. mm(in.) 26(1)
Dimensions W mm(in.) 1,400(55-1/8)
D mm(in.) 235(9-1/4)
H mm(in.) 340(13-3/8)
Weight kg(lbs) 24(53)
PUH-P3VGAA / PUH-P3YGAA
OUTDOOR Service Ref.
UNIT PUH-P3VGAA.UK / PUH-P3YGAA.UK
PUH-P3VGAA1.UK / PUH-P3YGAA1.UK

Notes1. Rating Conditions (ISO T1)


Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)

2. Guaranteed operating range


Indoor Outdoor
Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
Cooling
Lower limit D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Upper limit D.B. 28˚C D.B. 24˚C, W.B. 18˚C
Heating
Lower limit D.B. 17˚C D.B. -11˚C, W.B. -12˚C
3. Guaranteed voltage
198~264V, 50Hz

4. Above data based on indicated voltage 5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.
Indoor Unit Single phase 230V 50Hz
Outdoor Unit 3 phase 400V 50Hz

10
OC301-A--1.qxp 04.4.28 11:14 AM Page 11

Service Ref. PKA-RP4FAL


Item
Function Cooling Heating
Btu/h 32,100 36,800
Capacity
W 9,400 10,800
Total input kW 3.59 3.77
Service Ref. PKA-RP4FAL
Power supply(phase, cycle, voltage) Single phase, 50Hz, 220-230-240V
Input kW 0.11 0.11
Running current A 0.52 0.52
Starting current A 0.90 0.90
External finish Munsell 3.4Y 7.7/0.8
Heat exchanger Plate fin coil
INDOOR UNIT

Fan Fan(drive) x No. Line flow (direct) x 2


Fan motor output kW 0.070
Airflow(Low-High) K/min(CFM) 22-28(775-990)
External static pressure Pa(mmAq) 0(direct blow)
Operation control & Thermostat Wireless remote controller & built-in
Noise level(Low-High) dB 41-46
Unit drain pipe O.D. mm(in.) 26(1)
Dimensions W mm(in.) 1,680(66-1/8)
D mm(in.) 235(9-1/4)
H mm(in.) 340(13-3/8)
Weight kg(lbs) 28(62)
PUH-P4YGAA
OUTDOOR
UNIT Service Ref. PUH-P4VGAA.UK / PUH-P4YGAA.UK
PUH-P4VGAA1.UK / PUH-P4YGAA1.UK

Notes1. Rating Conditions (ISO T1)


Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)

2. Guaranteed operating range


Indoor Outdoor
Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
Cooling
Lower limit D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Upper limit D.B. 28˚C D.B. 24˚C, W.B. 18˚C
Heating
Lower limit D.B. 17˚C D.B. -11˚C, W.B. -12˚C
3. Guaranteed voltage
198~264V, 50Hz

4. Above data based on indicated voltage 5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.
Indoor Unit Single phase 230V 50Hz
Outdoor Unit 3 phase 400V 50Hz

11
OC301-A--1.qxp 04.4.28 11:14 AM Page 12

4-3. Cooling only type


Service Ref. PKA-RP2.5FAL
Item
Function Cooling
Btu/h 22,000
Capacity 6,450
W
Total input kW 2.65
Service Ref. PKA-RP2.5FAL
Power supply(phase, cycle, voltage) Single phase, 50Hz, 220-230-240V
Input kW 0.09
Running current A 0.43
Starting current A 0.80
External finish Munsell 3.4Y 7.7/0.8
Heat exchanger Plate fin coil
INDOOR UNIT

Fan Fan(drive) x No. Line flow (direct) x 2


Fan motor output kW 0.040
Airflow(Low-High) K/min(CFM) 15-20(530-706)
External static pressure Pa(mmAq) 0(direct blow)
Operation control & Thermostat Wireless remote controller & built-in
Noise level(Low-High) dB 39-45
Unit drain pipe O.D. mm(in.) 26(1)
Dimensions W mm(in.) 1,400(55-1/8)
D mm(in.) 235(9-1/4)
H mm(in.) 340(13-3/8)
Weight kg(lbs) 24(53)
PU-P2.5VGAA
OUTDOOR PU-P2.5VGAA.UK /PU-P2.5YGAA.UK
UNIT Service Ref.
PU-P2.5VGAA1.UK/ PU-P2.5YGAA1.UK

Service Ref. PKA-RP3FAL


Item
Function Cooling
Btu/h 26,800
Capacity 7,850
W
Total input kW 3.43
Service Ref. PKA-RP3FAL
Power supply(phase, cycle, voltage) Single phase, 50Hz, 220-230-240V
Input kW 0.09
Running current A 0.43
Starting current A 0.80
External finish Munsell 3.4Y 7.7/0.8
Heat exchanger Plate fin coil
INDOOR UNIT

Fan Fan(drive) x No. Line flow (direct) x 2


Fan motor output kW 0.040
Airflow(Low-High) K/min(CFM) 15-20(530-705)
External static pressure Pa(mmAq) 0(direct blow)
Operation control & Thermostat Wireless remote controller & built-in
Noise level(Low-High) dB 39-45
Unit drain pipe O.D. mm(in.) 26(1)
Dimensions W mm(in.) 1,400(55-1/8)
D mm(in.) 235(9-1/4)
H mm(in.) 340(13-3/8)
Weight kg(lbs) 24(53)
PU-P3VGAA / PU-P3YGAA
OUTDOOR PU-P3VGAA.UK / PU-P3YGAA.UK
UNIT Service Ref.
PU-P3VGAA1.UK / PU-P3YGAA1.UK

Notes1. Rating Conditions (ISO T1)


Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Indoor Outdoor
Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
Cooling
Lower limit D.B. 19˚C, W.B. 15˚C D.B. -5˚C

3. Guaranteed voltage
198~264V, 50Hz

4. Above data based on indicated voltage


Indoor Unit Single phase 230V 50Hz
Outdoor Unit 3 phase 400V 50Hz

5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.

12
OC301-A--1.qxp 04.4.28 11:14 AM Page 13

Service Ref. PKA-RP4FAL


Item
Function Cooling
Btu/h 32,100
Capacity
W 9,400
Total input kW 3.59
Service Ref. PKA-RP4FAL
Power supply(phase, cycle, voltage) Single phase, 50Hz, 220-230-240V
Input kW 0.11
Running current A 0.52
Starting current A 0.90
External finish Munsell 3.4Y 7.7/0.8
Heat exchanger Plate fin coil
INDOOR UNIT

Fan Fan(drive) x No. Line flow (direct) x 2


Fan motor output kW 0.070
Airflow(Low-High) K/min(CFM) 22-28(775-990)
External static pressure Pa(mmAq) 0(direct blow)
Operation control & Thermostat Wireless remote controller & built-in
Noise level(Low-High) dB 41-46
Unit drain pipe O.D. mm(in.) 26(1)
Dimensions W mm(in.) 1,680(66-1/8)
D mm(in.) 235(9-1/4)
H mm(in.) 340(13-3/8)
Weight kg(lbs) 28(62)
PU-P4YGAA
OUTDOOR
UNIT Service Ref. PU-P4VGAA.UK / PU-P4YGAA.UK
PU-P4VGAA1.UK / PU-P4YGAA1.UK

Notes1. Rating Conditions (ISO T1)


Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Indoor Outdoor
Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
Cooling
Lower limit D.B. 19˚C, W.B. 15˚C D.B. -5˚C

3. Guaranteed voltage
198~264V, 50Hz

4. Above data based on indicated voltage


Indoor Unit Single phase 230V 50Hz
Outdoor Unit 3 phase 400V 50Hz

5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.

13
OC301-A--1.qxp 04.4.28 11:14 AM Page 14

5 DATA

5-1. PERFORMANCE DATA


COOLING CAPACITY(1)
PKA-RP2.5FAL / PUHZ-RP2.5VHA
(230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 20 25 30
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 5,940 4,336 0.73 1.24 5,760 4,205 0.73 1.31 5,580 4,073 0.73 1.39
20 18 6,360 3,880 0.61 1.26 6,180 3,770 0.61 1.33 5,970 3,642 0.61 1.43
20 20 6,840 3,352 0.49 1.30 6,690 3,278 0.49 1.36 6,510 3,190 0.49 1.46
22 16 5,940 4,811 0.81 1.24 5,760 4,666 0.81 1.31 5,580 4,520 0.81 1.39
22 18 6,360 4,388 0.69 1.26 6,180 4,264 0.69 1.33 5,970 4,119 0.69 1.43
22 20 6,840 3,899 0.57 1.30 6,690 3,813 0.57 1.36 6,510 3,711 0.57 1.46
24 16 5,940 5,287 0.89 1.33 7,140 5,126 0.89 1.31 5,580 4,966 0.89 1.50
24 18 6,360 4,897 0.77 1.24 5,760 4,759 0.77 1.33 5,970 4,597 0.77 1.39
24 20 6,840 4,446 0.65 1.26 6,180 4,349 0.65 1.36 6,510 4,232 0.65 1.43
24 22 7,290 3,864 0.53 1.30 6,690 3,784 0.53 1.41 6,960 3,689 0.53 1.46
26 16 5,940 5,762 0.97 1.24 5,760 5,587 0.97 1.31 5,580 5,413 0.97 1.39
26 18 6,360 5,406 0.85 1.26 6,180 5,253 0.85 1.33 5,970 5,075 0.85 1.43
26 20 6,840 4,993 0.73 1.30 6,690 4,884 0.73 1.36 6,510 4,752 0.73 1.46
26 22 7,290 4,447 0.61 1.33 7,140 4,355 0.61 1.41 6,960 4,246 0.61 1.50
27 16 5,940 5,940 1.00 1.24 5,760 5,760 1.00 1.31 5,580 5,580 1.00 1.39
27 18 6,360 5,660 0.89 1.26 6,180 5,500 0.89 1.33 5,970 5,313 0.89 1.43
27 20 6,840 5,267 0.77 1.30 6,690 5,151 0.77 1.36 6,510 5,013 0.77 1.46
27 22 7,290 4,739 0.65 1.33 7,140 4,641 0.65 1.41 6,960 4,524 0.65 1.50
28 16 5,940 5,940 1.00 1.24 5,760 5,760 1.00 1.31 5,580 5,580 1.00 1.39
28 18 6,360 5,915 0.93 1.26 6,180 5,747 0.93 1.33 5,970 5,552 0.93 1.43
28 20 6,840 5,540 0.81 1.30 6,690 5,419 0.81 1.36 6,510 5,273 0.81 1.46
28 22 7,290 5,030 0.69 1.33 7,140 4,927 0.69 1.41 6,960 4,802 0.69 1.50
30 16 5,940 5,940 1.00 1.24 5,760 5,760 1.00 1.31 5,580 5,580 1.00 1.39
30 18 6,360 6,360 1.00 1.26 6,180 6,180 1.00 1.33 5,970 5,970 1.00 1.43
30 20 6,840 6,088 0.89 1.30 6,690 5,954 0.89 1.36 6,510 5,794 0.89 1.46
30 22 7,290 5,613 0.77 1.33 7,140 5,498 0.77 1.41 6,960 5,359 0.77 1.50
32 16 5,940 5,940 1.00 1.24 5,760 5,760 1.00 1.31 5,580 5,580 1.00 1.39
32 18 6,360 6,360 1.00 1.26 6,180 6,180 1.00 1.33 5,970 5,970 1.00 1.43
32 20 6,840 6,635 0.97 1.30 6,690 6,489 0.97 1.36 6,510 6,315 0.97 1.46
32 22 7,290 6,197 0.85 1.33 7,140 6,069 0.85 1.41 6,960 5,916 0.85 1.50
34 16 5,940 5,940 1.00 1.24 5,760 5,760 1.00 1.31 5,580 5,580 1.00 1.39
34 18 6,360 6,360 1.00 1.26 6,180 6,180 1.00 1.33 5,970 5,970 1.00 1.43
34 20 6,840 6,840 1.00 1.30 6,690 6,690 1.00 1.36 6,510 6,510 1.00 1.46
34 22 7,290 6,780 0.93 1.33 7,140 6,640 0.93 1.41 6,960 6,473 0.93 1.50

CA : Capacity (W) SHC(W) :Sensible heat capacity


P.C. : Power consumption (kW) SHF : Sensible heat factor

14
OC301-A--1.qxp 04.4.28 11:14 AM Page 15

COOLING CAPACITY(2)
PKA-RP2.5FAL / PUHZ-RP2.5VHA

(230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 35 40 45
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 5,340 3,898 0.73 1.49 5,100 3,723 0.73 1.60 4,860 3,548 0.73 1.73
20 18 5,760 3,514 0.61 1.53 5,580 3,404 0.61 1.64 5,220 3,184 0.61 1.77
20 20 6,240 3,058 0.49 1.57 6,000 2,940 0.49 1.67 5,640 2,764 0.49 1.80
22 16 5,340 4,325 0.81 1.49 5,100 4,131 0.81 1.60 4,860 3,937 0.81 1.73
22 18 5,760 3,974 0.69 1.53 5,580 3,850 0.69 1.64 5,220 3,602 0.69 1.77
22 20 6,240 3,557 0.57 1.57 6,000 3,420 0.57 1.67 5,640 3,215 0.57 1.80
24 16 5,340 4,753 0.89 1.49 5,100 4,539 0.89 1.60 4,860 4,325 0.89 1.73
24 18 5,760 4,435 0.77 1.53 5,580 4,297 0.77 1.64 5,220 4,019 0.77 1.77
24 20 6,240 4,056 0.65 1.57 6,000 3,900 0.65 1.67 5,640 3,666 0.65 1.80
24 22 6,720 3,562 0.53 1.60 6,480 3,434 0.53 1.72 6,120 3,244 0.53 1.83
26 16 5,340 5,180 0.97 1.49 5,100 4,947 0.97 1.60 4,860 4,714 0.97 1.73
26 18 5,760 4,896 0.85 1.53 5,580 4,743 0.85 1.64 5,220 4,437 0.85 1.77
26 20 6,240 4,555 0.73 1.57 6,000 4,380 0.73 1.67 5,640 4,117 0.73 1.80
26 22 6,720 4,099 0.61 1.60 6,480 3,953 0.61 1.72 6,120 3,733 0.61 1.83
27 16 5,340 5,340 1.00 1.49 5,100 5,100 1.00 1.60 4,860 4,860 1.00 1.73
27 18 5,760 5,126 0.89 1.53 5,580 4,966 0.89 1.64 5,220 4,646 0.89 1.77
27 20 6,240 4,805 0.77 1.57 6,000 4,620 0.77 1.67 5,640 4,343 0.77 1.80
27 22 6,720 4,368 0.65 1.60 6,480 4,212 0.65 1.72 6,120 3,978 0.65 1.83
28 16 5,340 5,340 1.00 1.49 5,100 5,100 1.00 1.60 4,860 4,860 1.00 1.73
28 18 5,760 5,357 0.93 1.53 5,580 5,189 0.93 1.64 5,220 4,855 0.93 1.77
28 20 6,240 5,054 0.81 1.57 6,000 4,860 0.81 1.67 5,640 4,568 0.81 1.80
28 22 6,720 4,637 0.69 1.60 6,480 4,471 0.69 1.72 6,120 4,223 0.69 1.83
30 16 5,340 5,340 1.00 1.49 5,100 5,100 1.00 1.60 4,860 4,860 1.00 1.73
30 18 5,760 5,760 1.00 1.53 5,580 5,580 1.00 1.64 5,220 5,220 1.00 1.77
30 20 6,240 5,554 0.89 1.57 6,000 5,340 0.89 1.67 5,640 5,020 0.89 1.80
30 22 6,720 5,174 0.77 1.60 6,480 4,990 0.77 1.72 6,120 4,712 0.77 1.83
32 16 5,340 5,340 1.00 1.49 5,100 5,100 1.00 1.60 4,860 4,860 1.00 1.73
32 18 5,760 5,760 1.00 1.53 5,580 5,580 1.00 1.64 5,220 5,220 1.00 1.77
32 20 6,240 6,053 0.97 1.57 6,000 5,820 0.97 1.67 5,640 5,471 0.97 1.80
32 22 6,720 5,712 0.85 1.60 6,480 5,508 0.85 1.72 6,120 5,202 0.85 1.83
34 16 5,340 5,340 1.00 1.49 5,100 5,100 1.00 1.60 4,860 4,860 1.00 1.73
34 18 5,760 5,760 1.00 1.53 5,580 5,580 1.00 1.64 5,220 5,220 1.00 1.77
34 20 6,240 6,240 1.00 1.57 6,000 6,000 1.00 1.67 5,640 5,640 1.00 1.80
34 22 6,720 6,250 0.93 1.60 6,480 6,026 0.93 1.72 6,120 5,692 0.93 1.83

CA : Capacity (W) SHC(W) :Sensible heat capacity


P.C. : Power consumption (kW) SHF : Sensible heat factor

15
OC301-A--1.qxp 04.4.28 11:14 AM Page 16

COOLING CAPACITY(3)
PKA-RP3FAL / PUHZ-RP3VHA
(230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 20 25 30
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 7,029 4,709 0.67 1.58 6,816 4,567 0.67 1.67 6,603 4,424 0.67 1.77
20 18 7,526 4,139 0.55 1.61 7,313 4,022 0.55 1.70 7,065 3,885 0.55 1.82
20 20 8,094 3,480 0.43 1.66 7,917 3,404 0.43 1.74 7,704 3,313 0.43 1.86
22 16 7,029 5,272 0.75 1.58 6,816 5,112 0.75 1.67 6,603 4,952 0.75 1.77
22 18 7,526 4,741 0.63 1.61 7,313 4,607 0.63 1.70 7,065 4,451 0.63 1.82
22 20 8,094 4,128 0.51 1.66 7,917 4,037 0.51 1.74 7,704 3,929 0.51 1.86
24 16 7,029 5,834 0.83 1.58 6,816 5,657 0.83 1.67 6,603 5,480 0.83 1.77
24 18 7,526 5,343 0.71 1.61 7,313 5,192 0.71 1.70 7,065 5,016 0.71 1.82
24 20 8,094 4,775 0.59 1.66 7,917 4,671 0.59 1.74 7,704 4,545 0.59 1.86
24 22 8,627 4,054 0.47 1.70 8,449 3,971 0.47 1.80 8,236 3,871 0.47 1.92
26 16 7,029 6,396 0.91 1.58 6,816 6,203 0.91 1.67 6,603 6,009 0.91 1.77
26 18 7,526 5,946 0.79 1.61 7,313 5,777 0.79 1.70 7,065 5,581 0.79 1.82
26 20 8,094 5,423 0.67 1.66 7,917 5,304 0.67 1.74 7,704 5,161 0.67 1.86
26 22 8,627 4,745 0.55 1.70 8,449 4,647 0.55 1.80 8,236 4,530 0.55 1.92
27 16 7,029 6,678 0.95 1.58 6,816 6,475 0.95 1.67 6,603 6,273 0.95 1.77
27 18 7,526 6,247 0.83 1.61 7,313 6,070 0.83 1.70 7,,065 5,864 0.83 1.82
27 20 8,094 5,747 0.71 1.66 7,917 5,621 0.71 1.74 7,704 5,469 0.71 1.86
27 22 8,627 5,090 0.59 1.70 8,449 4,985 0.59 1.80 8,236 4,859 0.59 1.92
28 16 7,029 6,959 0.99 1.58 6,816 6,748 0.99 1.67 6,603 6,537 0.99 1.77
28 18 7,526 6,548 0.87 1.61 7,313 6,362 0.87 1.70 7,065 6,146 0.87 1.82
28 20 8,094 6,071 0.75 1.66 7,917 5,937 0.75 1.74 7,704 5,778 0.75 1.86
28 22 8,627 5,435 0.63 1.70 8,449 5,323 0.63 1.80 8,236 5,189 0.63 1.92
30 16 7,029 7,029 1.00 1.58 6,816 6,816 1.00 1.67 6,603 6,603 1.00 1.77
30 18 7,526 7,150 0.95 1.61 7,313 6,947 0.95 1.70 7,065 6,711 0.95 1.82
30 20 8,094 6,718 0.83 1.66 7,917 6,571 0.83 1.74 7,704 6,394 0.83 1.86
30 22 8,627 6,125 0.71 1.70 8,449 5,999 0.71 1.80 8,236 5,848 0.71 1.92
32 16 7,029 7,029 1.00 1.58 6,816 6,816 1.00 1.67 6,603 6,603 1.00 1.77
32 18 7,526 7,526 1.00 1.61 7,313 7,313 1.00 1.70 7,065 7,065 1.00 1.82
32 20 8,094 7,366 0.91 1.66 7,917 7,204 0.91 1.74 7,704 7,010 0.91 1.86
32 22 8,627 6,815 0.79 1.70 8,449 6,675 0.79 1.80 8,236 6,506 0.79 1.92
34 16 7,029 7,029 1.00 1.58 6,816 6,816 1.00 1.67 6,603 6,603 1.00 1.77
34 18 7,526 7,526 1.00 1.61 7,313 7,313 1.00 1.70 7,065 7,065 1.00 1.82
34 20 8,094 8,013 0.99 1.66 7,917 7,837 0.99 1.74 7,704 7,626 0.99 1.86
34 22 8,627 7,505 0.87 1.70 8,449 7,351 0.87 1.80 8,236 7,165 0.87 1.92

CA : Capacity (W) SHC(W) :Sensible heat capacity


P.C. : Power consumption (kW) SHF : Sensible heat factor

16
OC301-A--1.qxp 04.4.28 11:14 AM Page 17

COOLING CAPACITY(4)
PKA-RP3FAL / PUHZ-RP3VHA
(230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 35 40 45
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 6,319 4,234 0.67 1.90 6,035 4,043 0.67 2.04 5,751 3,853 0.67 2.21
20 18 6,816 3,749 0.55 1.95 6,603 3,632 0.55 2.10 6,177 3,397 0.55 2.26
20 20 7,384 3,175 0.43 2.00 7,100 3,053 0.43 2.14 6,674 2,870 0.43 2.30
22 16 6,319 4,739 0.75 1.90 6,035 4,526 0.75 2.04 5,751 4,313 0.75 2.21
22 18 6,816 4,294 0.63 1.95 6,603 4,160 0.63 2.10 6,177 3,892 0.63 2.26
22 20 7,384 3,766 0.51 2.00 7,100 3,621 0.51 2.14 6,674 3,404 0.51 2.30
24 16 6,319 5,245 0.83 1.90 6,035 5,009 0.83 2.04 5,751 4,773 0.83 2.21
24 18 6,816 4,839 0.71 1.95 6,603 4,688 0.71 2.10 6,177 4,386 0.71 2.26
24 20 7,384 4,357 0.59 2.00 7,100 4,189 0.59 2.14 6,674 3,938 0.59 2.30
24 22 7,952 3,737 0.47 2.04 7,668 3,604 0.47 2.20 7,242 3,404 0.47 2.34
26 16 6,319 5,750 0.91 1.90 6,035 5,492 0.91 2.04 5,751 5,233 0.91 2.21
26 18 6,816 5,385 0.79 1.95 6,603 5,216 0.79 2.10 6,177 4,880 0.79 2.26
26 20 7,384 4,947 0.67 2.00 7,100 4,757 0.67 2.14 6,674 4,472 0.67 2.30
26 22 7,952 4,374 0.55 2.04 7,668 4,217 0.55 2.20 7,242 3,983 0.55 2.34
27 16 6,319 6,003 0.95 1.90 6,035 5,733 0.95 2.04 5,751 5,463 0.95 2.21
27 18 6,816 5,657 0.83 1.95 6,603 5,480 0.83 2.10 6,177 5,127 0.83 2.26
27 20 7,384 5,243 0.71 2.00 7,100 5,041 0.71 2.14 6,674 4,739 0.71 2.30
27 22 7,952 4,692 0.59 2.04 7,668 4,524 0.59 2.20 7,242 4,273 0.59 2.34
28 16 6,319 6,256 0.99 1.90 6,035 5,975 0.99 2.04 5,751 5,693 0.99 2.21
28 18 6,816 5,930 0.87 1.95 6,603 5,745 0.87 2.10 6,177 5,374 0.87 2.26
28 20 7,384 5,538 0.75 2.00 7,100 5,325 0.75 2.14 6,674 5,006 0.75 2.30
28 22 7,952 5,010 0.63 2.04 7,668 4,831 0.63 2.20 7,242 4,562 0.63 2.34
30 16 6,319 6,319 1.00 1.90 6,035 6,035 1.00 2.04 5,751 5,751 1.00 2.21
30 18 6,816 6,475 0.95 1.95 6,603 6,273 0.95 2.10 6,177 5,868 0.95 2.26
30 20 7,384 6,129 0.83 2.00 7,100 5,893 0.83 2.14 6,674 5,539 0.83 2.30
30 22 7,952 5,646 0.71 2.04 7,668 5,444 0.71 2.20 7,242 5,142 0.71 2.34
32 16 6,319 6,319 1.00 1.90 6,035 6,035 1.00 2.04 5,751 5,751 1.00 2.21
32 18 6,816 6,816 1.00 1.95 6,603 6,603 1.00 2.10 6,177 6,177 1.00 2.26
32 20 7,384 6,719 0.91 2.00 7,100 6,461 0.91 2.14 6,674 6,073 0.91 2.30
32 22 7,952 6,282 0.79 2.04 7,668 6,058 0.79 2.20 7,242 5,721 0.79 2.34
34 16 6,319 6,319 1.00 1.90 6,035 6,035 1.00 2.04 5,751 5,751 1.00 2.21
34 18 6,816 6,816 1.00 1.95 6,603 6,603 1.00 2.10 6,177 6,177 1.00 2.26
34 20 7,384 7,310 0.99 2.00 7,100 7,029 0.99 2.14 6,674 6,607 0.99 2.30
34 22 7,952 6,918 0.87 2.04 7,668 6,671 0.87 2.20 7,242 6,301 0.87 2.34

CA : Capacity (W) SHC(W) :Sensible heat capacity


P.C. : Power consumption (kW) SHF : Sensible heat factor

17
OC301-A--1.qxp 04.4.28 11:14 AM Page 18

COOLING CAPACITY(5)
PKA-RP4FAL / PUHZ-RP4VHA
PUHZ-RP4VHA1 (230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 20 25 30
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 9,900 6,039 0.61 2.34 9,600 5,856 0.61 2.48 9,300 5,673 0.61 2.62
20 18 10,600 5,194 0.49 2.39 10,300 5,047 0.49 2.52 9,950 4,876 0.49 2.70
20 20 11,400 4,218 0.37 2.46 11,150 4,126 0.37 2.58 10,850 4,015 0.37 2.75
22 16 9,900 6,831 0.69 2.34 9,600 6,624 0.69 2.48 9,300 6,417 0.69 2.62
22 18 10,600 6,042 0.57 2.39 10,300 5,871 0.57 2.52 9,950 5,672 0.57 2.70
22 20 11,400 5,130 0.45 2.46 11,150 5,018 0.45 2.58 10,850 4,883 0.45 2.75
24 16 9,900 7,623 0.77 2.34 9,600 7,392 0.77 2.48 9,300 7,161 0.77 2.62
24 18 10,600 6,890 0.65 2.39 10,300 6,695 0.65 2.52 9,950 6,468 0.65 2.70
24 20 11,400 6,042 0.53 2.46 11,150 5,910 0.53 2.58 10,850 5,751 0.53 2.75
24 22 12,150 4,982 0.41 2.52 11,900 4,879 0.41 2.67 11,600 4,756 0.41 2.84
26 16 9,900 8,415 0.85 2.34 9,600 8,160 0.85 2.48 9,300 7,905 0.85 2.62
26 18 10,600 7,738 0.73 2.39 10,300 7,519 0.73 2.52 9,950 7,264 0.73 2.70
26 20 11,400 6,954 0.61 2.46 11,150 6,802 0.61 2.58 10,850 6,619 0.61 2.75
26 22 12,150 5,954 0.49 2.52 11,900 5,831 0.49 2.67 11,600 5,684 0.49 2.84
27 16 9,900 8,811 0.89 2.34 9,600 8,544 0.89 2.48 9,300 8,277 0.89 2.62
27 18 10,600 8,162 0.77 2.39 10,300 7,931 0.77 2.52 9,950 7,662 0.77 2.70
27 20 11,400 7,410 0.65 2.46 11,150 7,248 0.65 2.58 10,850 7,053 0.65 2.75
27 22 12,150 6,440 0.53 2.52 11,900 6,307 0.53 2.67 11,600 6,148 0.53 2.84
28 16 9,900 9,207 0.93 2.34 9,600 8,928 0.93 2.48 9,300 8,649 0.93 2.62
28 18 10,600 8,586 0.81 2.39 10,300 8,343 0.81 2.52 9,950 8,060 0.81 2.70
28 20 11,400 7,866 0.69 2.46 11,150 7,694 0.69 2.58 10,850 7,487 0.69 2.75
28 22 12,150 6,926 0.57 2.52 11,900 6,783 0.57 2.67 11,600 6,612 0.57 2.84
30 16 9,900 9,900 1.00 2.34 9,600 9,600 1.00 2.48 9,300 9,300 1.00 2.62
30 18 10,600 9,434 0.89 2.39 10,300 9,167 0.89 2.52 9,950 8,856 0.89 2.70
30 20 11,400 8,778 0.77 2.46 11,150 8,586 0.77 2.58 10,850 8,355 0.77 2.75
30 22 12,150 7,898 0.65 2.52 11,900 7,735 0.65 2.67 11,600 7,540 0.65 2.84
32 16 9,900 9,900 1.00 2.34 9,600 9,600 1.00 2.48 9,300 9,300 1.00 2.62
32 18 10,600 10,282 0.97 2.39 10,300 9,991 0.97 2.52 9,950 9,652 0.97 2.70
32 20 11,400 9,690 0.85 2.46 11,150 9,478 0.85 2.58 10,850 9,223 0.85 2.75
32 22 12,150 8,870 0.73 2.52 11,900 8,687 0.73 2.67 11,600 8,468 0.73 2.84
34 16 9,900 9,900 1.00 2.34 9,600 9,600 1.00 2.48 9,300 9,300 1.00 2.62
34 18 10,600 10,600 1.00 2.39 10,300 10,300 1.00 2.52 9,950 9,950 1.00 2.70
34 20 11,400 10,602 0.93 2.46 11,150 10,370 0.93 2.58 10,850 10,091 0.93 2.75
34 22 12,150 9,842 0.81 2.52 11,900 9,639 0.81 2.67 11,600 9,396 0.81 2.84
CA : Capacity (W) SHC(W) :Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor

18
OC301-A--1.qxp 04.4.28 11:14 AM Page 19

COOLING CAPACITY(6)
PKA-RP4FAL / PUHZ-RP4VHA
PUHZ-RP4VHA1 (230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 35 40 45
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 8,900 5,429 0.61 2.81 8,500 5,185 0.61 3.02 8,100 4,941 0.61 3.27
20 18 9,600 4,704 0.49 2.89 9,300 4,557 0.49 3.11 8,700 4,263 0.49 3.34
20 20 10,400 3,848 0.37 2.96 10,000 3,700 0.37 3.16 9,400 3,478 0.37 3.40
22 16 8,900 6,141 0.69 2.81 8,500 5,865 0.69 3.02 8,100 5,589 0.69 3.27
22 18 9,600 5,472 0.57 2.89 9,300 5,301 0.57 3.11 8,700 4,959 0.57 3.34
22 20 10,400 4,680 0.45 2.96 10,000 4,500 0.45 3.16 9,400 4,230 0.45 3.40
24 16 8,900 6,853 0.77 2.81 8,500 6,545 0.77 3.02 8,100 6,237 0.77 3.27
24 18 9,600 6,240 0.65 2.89 9,300 6,045 0.65 3.11 8,700 5,655 0.65 3.34
24 20 10,400 5,512 0.53 2.96 10,000 5,300 0.53 3.16 9,400 4,982 0.53 3.40
24 22 11,200 4,592 0.41 3.02 10,800 4,428 0.41 3.25 10,200 4,182 0.41 3.46
26 16 8,900 7,565 0.85 2.81 8,500 7,225 0.85 3.02 8,100 6,885 0.85 3.27
26 18 9,600 7,008 0.73 2.89 9,300 6,789 0.73 3.11 8,700 6,351 0.73 3.34
26 20 10,400 6,344 0.61 2.96 10,000 6,100 0.61 3.16 9,400 5,734 0.61 3.40
26 22 11,200 5,488 0.49 3.02 10,800 5,292 0.49 3.25 10,200 4,998 0.49 3.46
27 16 8,900 7,921 0.89 2.81 8,500 7,565 0.89 3.02 8,100 7,209 0.89 3.27
27 18 9,600 7,392 0.77 2.89 9,300 7,161 0.77 3.11 8,700 6,699 0.77 3.34
27 20 10,400 6,760 0.65 2.96 10,000 6,500 0.65 3.16 9,400 6,110 0.65 3.40
27 22 11,200 5,936 0.53 3.02 10,800 5,724 0.53 3.25 10,200 5,406 0.53 3.46
28 16 8,900 8,277 0.93 2.81 8,500 7,905 0.93 3.02 8,100 7,533 0.93 3.27
28 18 9,600 7,776 0.81 2.89 9,300 7,533 0.81 3.11 8,700 7,047 0.81 3.34
28 20 10,400 7,176 0.69 2.96 10,000 6,900 0.69 3.16 9,400 6,486 0.69 3.40
28 22 11,200 6,384 0.57 3.02 10,800 6,156 0.57 3.25 10,200 5,814 0.57 3.46
30 16 8,900 8,900 1.00 2.81 8,500 8,500 1.00 3.02 8,100 8,100 1.00 3.27
30 18 9,600 8,544 0.89 2.89 9,300 8,277 0.89 3.11 8,700 7,743 0.89 3.34
30 20 10,400 8,008 0.77 2.96 10,000 7,700 0.77 3.16 9,400 7,238 0.77 3.40
30 22 11,200 7,280 0.65 3.02 10,800 7,020 0.65 3.25 10,200 6,630 0.65 3.46
32 16 8,900 8,900 1.00 2.81 8,500 8,500 1.00 3.02 8,100 8,100 1.00 3.27
32 18 9,600 9,312 0.97 2.89 9,300 9,021 0.97 3.11 8,700 8,439 0.97 3.34
32 20 10,400 8,840 0.85 2.96 10,000 8,500 0.85 3.16 9,400 7,990 0.85 3.40
32 22 11,200 8,176 0.73 3.02 10,800 7,884 0.73 3.25 10,200 7,446 0.73 3.46
34 16 8,900 8,900 1.00 2.81 8,500 8,500 1.00 3.02 8,100 8,100 1.00 3.27
34 18 9,600 9,600 1.00 2.89 9,300 9,300 1.00 3.11 8,700 8,700 1.00 3.34
34 20 10,400 9,672 0.93 2.96 10,000 9,300 0.93 3.16 9,400 8,742 0.93 3.40
34 22 11,200 9,072 0.81 3.02 10,800 8,748 0.81 3.25 10,200 8,262 0.81 3.46
CA : Capacity (W) SHC(W) :Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor

19
OC301-A--1.qxp 04.4.28 11:14 AM Page 20

COOLING CAPACITY(7)
PKA-RP2.5FAL / PUH-P2.5VGAA
PUH-P2.5VGAA.UK PUH-P2.5YGAA.UK
PUH-P2.5VGAA1.UK PUH-P2.5YGAA1.UK
PU-P2.5VGAA
PU-P2.5VGAA.UK PU-P2.5YGAA.UK
PU-P2.5VGAA1.UK PU-P2.5YGAA1.UK
(230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 20 25 30
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 6,386 4,470 0.70 2.12 6,192 4,334 0.70 2.24 5,999 4,199 0.70 2.37
20 18 6,837 3,965 0.58 2.16 6,644 3,853 0.58 2.28 6,418 3,722 0.58 2.44
20 20 7,353 3,382 0.46 2.23 7,192 3,308 0.46 2.33 6,998 3,219 0.46 2.49
22 16 6,386 4,981 0.78 2.12 6,192 4,830 0.78 2.24 5,999 4,679 0.78 2.37
22 18 6,837 4,512 0.66 2.16 6,644 4,385 0.66 2.28 6,418 4,236 0.66 2.44
22 20 7,353 3,971 0.54 2.23 7,192 3,884 0.54 2.33 6,998 3,779 0.54 2.49
24 16 6,386 5,492 0.86 2.12 6,192 5,325 0.86 2.24 5,999 5,159 0.86 2.37
24 18 6,837 5,059 0.74 2.16 6,644 4,916 0.74 2.28 6,418 4,749 0.74 2.44
24 20 7,353 4,559 0.62 2.23 7,192 4,459 0.62 2.33 6,998 4,339 0.62 2.49
24 22 7,837 3,918 0.50 2.28 7,676 3,838 0.50 2.41 7,482 3,741 0.50 2.57
26 16 6,386 6,002 0.94 2.12 6,192 5,820 0.94 2.24 5,999 5,639 0.94 2.37
26 18 6,837 5,606 0.82 2.16 6,644 5,448 0.82 2.28 6,418 5,263 0.82 2.44
26 20 7,353 5,147 0.70 2.23 7,192 5,034 0.70 2.33 6,998 4,899 0.70 2.49
26 22 7,837 4,545 0.58 2.28 7,676 4,452 0.58 2.41 7,482 4,340 0.58 2.57
27 16 6,386 6,258 0.98 2.12 6,192 6,068 0.98 2.24 5,999 5,879 0.98 2.37
27 18 6,837 5,880 0.86 2.16 6,644 5,713 0.86 2.28 6,418 5,519 0.86 2.44
27 20 7,353 5,441 0.74 2.23 7,192 5,322 0.74 2.33 6,998 5,179 0.74 2.49
27 22 7,837 4,859 0.62 2.28 7,676 4,759 0.62 2.41 7,482 4,639 0.62 2.57
28 16 6,386 6,386 1.00 2.12 6,192 6,192 1.00 2.24 5,999 5,999 1.00 2.37
28 18 6,837 6,153 0.90 2.16 6,644 5,979 0.90 2.28 6,418 5,776 0.90 2.44
28 20 7,353 5,735 0.78 2.23 7,192 5,610 0.78 2.33 6,998 5,459 0.78 2.49
28 22 7,837 5,172 0.66 2.28 7,676 5,066 0.66 2.41 7,482 4,938 0.66 2.57
30 16 6,386 6,386 1.00 2.12 6,192 6,192 1.00 2.24 5,999 5,999 1.00 2.37
30 18 6,837 6,700 0.98 2.16 6,644 6,511 0.98 2.28 6,418 6,289 0.98 2.44
30 20 7,353 6,324 0.86 2.23 7,192 6,185 0.86 2.33 6,998 6,018 0.86 2.49
30 22 7,837 5,799 0.74 2.28 7,676 5,680 0.74 2.41 7,482 5,537 0.74 2.57
32 16 6,386 6,386 1.00 2.12 6,192 6,192 1.00 2.24 5,999 5,999 1.00 2.37
32 18 6,837 6,837 1.00 2.16 6,644 6,644 1.00 2.28 6,418 6,418 1.00 2.44
32 20 7,353 6,912 0.94 2.23 7,192 6,760 0.94 2.33 6,998 6,578 0.94 2.49
32 22 7,837 6,426 0.82 2.28 7,676 6,294 0.82 2.41 7,482 6,135 0.82 2.57
34 16 6,386 6,386 1.00 2.12 6,192 6,192 1.00 2.24 5,999 5,999 1.00 2.37
34 18 6,837 6,837 1.00 2.16 6,644 6,644 1.00 2.28 6,418 6,418 1.00 2.44
34 20 7,353 7,353 1.00 2.23 7,192 7,192 1.00 2.33 6,998 6,998 1.00 2.49
34 22 7,837 7,053 0.90 2.28 7,676 6,908 0.90 2.41 7,482 6,734 0.90 2.57
CA : Capacity (W) SHC(W) :Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor

20
OC301-A--1.qxp 04.4.28 11:14 AM Page 21

COOLING CAPACITY(8)
PKA-RP2.5FAL / PUH-P2.5VGAA
PUH-P2.5VGAA.UK PUH-P2.5YGAA.UK
PUH-P2.5VGAA1.UK PUH-P2.5YGAA1.UK
PU-P2.5VGAA
PU-P2.5VGAA.UK PU-P2.5YGAA.UK
PU-P2.5VGAA1.UK PU-P2.5YGAA1.UK
(230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 35 40 45
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 5,741 4,018 0.70 2.54 5,483 3,838 0.70 2.73 5,225 3,657 0.70 2.95
20 18 6,192 3,591 0.58 2.61 5,999 3,479 0.58 2.81 5,612 3,255 0.58 3.02
20 20 6,708 3,086 0.46 2.68 6,450 2,967 0.46 2.86 6,063 2,789 0.46 3.07
22 16 5,741 4,478 0.78 2.54 5,483 4,276 0.78 2.73 5,225 4,075 0.78 2.95
22 18 6,192 4,087 0.66 2.61 5,999 3,959 0.66 2.81 5,612 3,704 0.66 3.02
22 20 6,708 3,622 0.54 2.68 6,450 3,483 0.54 2.86 6,063 3,274 0.54 3.07
24 16 5,741 4,937 0.86 2.54 5,483 4,715 0.86 2.73 5,225 4,493 0.86 2.95
24 18 6,192 4,582 0.74 2.61 5,999 4,439 0.74 2.81 5,612 4,153 0.74 3.02
24 20 6,708 4,159 0.62 2.68 6,450 3,999 0.62 2.86 6,063 3,759 0.62 3.07
24 22 7,224 3,612 0.50 2.73 6,966 3,483 0.50 2.94 6,579 3,290 0.50 3.13
26 16 5,741 5,396 0.94 2.54 5,483 5,154 0.94 2.73 5,225 4,911 0.94 2.95
26 18 6,192 5,077 0.82 2.61 5,999 4,919 0.82 2.81 5,612 4,601 0.82 3.02
26 20 6,708 4,696 0.70 2.68 6,450 4,515 0.70 2.86 6,063 4,244 0.70 3.07
26 22 7,224 4,190 0.58 2.73 6,966 4,040 0.58 2.94 6,579 3,816 0.58 3.13
27 16 5,741 5,626 0.98 2.54 5,483 5,373 0.98 2.73 5,225 5,120 0.98 2.95
27 18 6,192 5,325 0.86 2.61 5,999 5,159 0.86 2.81 5,612 4,826 0.86 3.02
27 20 6,708 4,964 0.74 2.68 6,450 4,773 0.74 2.86 6,063 4,487 0.74 3.07
27 22 7,224 4,479 0.62 2.73 6,966 4,319 0.62 2.94 6,579 4,079 0.62 3.13
28 16 5,741 5,741 1.00 2.54 5,483 5,483 1.00 2.73 5,225 5,225 1.00 2.95
28 18 6,192 5,573 0.90 2.61 5,999 5,399 0.90 2.81 5,612 5,050 0.90 3.02
28 20 6,708 5,232 0.78 2.68 6,450 5,031 0.78 2.86 6,063 4,729 0.78 3.07
28 22 7,224 4,768 0.66 2.73 6,966 4,598 0.66 2.94 6,579 4,342 0.66 3.13
30 16 5,741 5,741 1.00 2.54 5,483 5,483 1.00 2.73 5,225 5,225 1.00 2.95
30 18 6,192 6,068 0.98 2.61 5,999 5,879 0.98 2.81 5,612 5,499 0.98 3.02
30 20 6,708 5,769 0.86 2.68 6,450 5,547 0.86 2.86 6,063 5,214 0.86 3.07
30 22 7,224 5,346 0.74 2.73 6,966 5,155 0.74 2.94 6,579 4,868 0.74 3.13
32 16 5,741 5,741 1.00 2.54 5,483 5,483 1.00 2.73 5,225 5,225 1.00 2.95
32 18 6,192 6,192 1.00 2.61 5,999 5,999 1.00 2.81 5,612 5,612 1.00 3.02
32 20 6,708 6,306 0.94 2.68 6,450 6,063 0.94 2.86 6,063 5,699 0.94 3.07
32 22 7,224 5,924 0.82 2.73 6,966 5,712 0.82 2.94 6,579 5,395 0.82 3.13
34 16 5,741 5,741 1.00 2.54 5,483 5,483 1.00 2.73 5,225 5,225 1.00 2.95
34 18 6,192 6,192 1.00 2.61 5,999 5,999 1.00 2.81 5,612 5,612 1.00 3.02
34 20 6,708 6,708 1.00 2.68 6,450 6,450 1.00 2.86 6,063 6,063 1.00 3.07
34 22 7,224 6,502 0.90 2.73 6,966 6,269 0.90 2.94 6,579 5,921 0.90 3.13
CA : Capacity (W) SHC(W) :Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor

21
OC301-A--1.qxp 04.4.28 11:14 AM Page 22

COOLING CAPACITY(9)
PKA-RP3FAL / PUH-P3VGAA PUH-P3YGAA
PUH-P3VGAA.UK PUH-P3YGAA.UK
PUH-P3VGAA1.UK PUH-P3YGAA1.UK
PU-P3VGAA PU-P3YGAA
PU-P3VGAA.UK PU-P3YGAA.UK
PU-P3VGAA1.UK PU-P3YGAA1.UK
(230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 20 25 30
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 7,772 4,974 0.64 2.74 7,536 4,823 0.64 2.90 7,301 4,672 0.64 3.07
20 18 8,321 4,327 0.52 2.80 8,086 4,204 0.52 2.95 7,811 4,062 0.52 3.16
20 20 8,949 3,580 0.40 2.88 8,753 3,501 0.40 3.02 8,517 3,407 0.40 3.22
22 16 7,772 5,595 0.72 2.74 7,536 5,426 0.72 2.90 7,301 5,256 0.72 3.07
22 18 8,321 4,993 0.60 2.80 8,086 4,851 0.60 2.95 7,811 4,686 0.60 3.16
22 20 8,949 4,296 0.48 2.88 8,753 4,201 0.48 3.02 8,517 4,088 0.48 3.22
24 16 7,772 6,217 0.80 2.74 7,536 6,029 0.80 2.90 7,301 5,840 0.80 3.07
24 18 8,321 5,658 0.68 2.80 8,086 5,498 0.68 2.95 7,811 5,311 0.68 3.16
24 20 8,949 5,011 0.56 2.88 8,753 4,902 0.56 3.02 8,517 4,770 0.56 3.22
24 22 9,538 4,197 0.44 2.95 9,342 4,110 0.44 3.12 9,106 4,007 0.44 3.33
26 16 7,772 6,839 0.88 2.74 7,536 6,632 0.88 2.90 7,301 6,424 0.88 3.07
26 18 8,321 6,324 0.76 2.80 8,086 6,145 0.76 2.95 7,811 5,936 0.76 3.16
26 20 8,949 5,727 0.64 2.88 8,753 5,602 0.64 3.02 8,517 5,451 0.64 3.22
26 22 9,538 4,960 0.52 2.95 9,342 4,858 0.52 3.12 9,106 4,735 0.52 3.33
27 16 7,772 7,150 0.92 2.74 7,536 6,933 0.92 2.90 7,301 6,716 0.92 3.07
27 18 8,321 6,657 0.80 2.80 8,086 6,468 0.80 2.95 7,811 6,249 0.80 3.16
27 20 8,949 6,085 0.68 2.88 8,753 5,952 0.68 3.02 8,517 5,792 0.68 3.22
27 22 9,538 5,341 0.56 2.95 9,342 5,231 0.56 3.12 9,106 5,099 0.56 3.33
28 16 7,772 7,461 0.96 2.74 7,536 7,235 0.96 2.90 7,301 7,008 0.96 3.07
28 18 8,321 6,990 0.84 2.80 8,086 6,792 0.84 2.95 7,811 6,561 0.84 3.16
28 20 8,949 6,443 0.72 2.88 8,753 6,302 0.72 3.02 8,517 6,132 0.72 3.22
28 22 9,538 5,723 0.60 2.95 9,342 5,605 0.60 3.12 9,106 5,464 0.60 3.33
30 16 7,772 7,772 1.00 2.74 7,536 7,536 1.00 2.90 7,301 7,301 1.00 3.07
30 18 8,321 7,655 0.92 2.80 8,086 7,439 0.92 2.95 7,811 7,186 0.92 3.16
30 20 8,949 7,159 0.80 2.88 8,753 7,002 0.80 3.02 8,517 6,814 0.80 3.22
30 22 9,538 6,486 0.68 2.95 9,342 6,352 0.68 3.12 9,106 6,192 0.68 3.33
32 16 7,772 7,772 1.00 2.74 7,536 7,536 1.00 2.90 7,301 7,301 1.00 3.07
32 18 8,321 8,321 1.00 2.80 8,086 8,086 1.00 2.95 7,811 7,811 1.00 3.16
32 20 8,949 7,875 0.88 2.88 8,753 7,702 0.88 3.02 8,517 7,495 0.88 3.22
32 22 9,538 7,249 0.76 2.95 9,342 7,100 0.76 3.12 9,106 6,921 0.76 3.33
34 16 7,772 7,772 1.00 2.74 7,536 7,536 1.00 2.90 7,301 7,301 1.00 3.07
34 18 8,321 8,321 1.00 2.80 8,086 8,086 1.00 2.95 7,811 7,811 1.00 3.16
34 20 8,949 8,591 0.96 2.88 8,753 8,403 0.96 3.02 8,517 8,177 0.96 3.22
34 22 9,538 8,012 0.84 2.95 9,342 7,847 0.84 3.12 9,106 7,649 0.84 3.33
CA : Capacity (W) SHC(W) :Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor

22
OC301-A--1.qxp 04.4.28 11:14 AM Page 23

COOLING CAPACITY(10)
PKA-RP3FAL / PUH-P3VGAA PUH-P3YGAA
PUH-P3VGAA.UK PUH-P3YGAA.UK
PUH-P3VGAA1.UK PUH-P3YGAA1.UK
PU-P3VGAA PU-P3YGAA
PU-P3VGAA.UK PU-P3YGAA.UK
PU-P3VGAA1.UK PU-P3YGAA1.UK
(230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 35 40 45
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 6,987 4,471 0.64 3.29 6,673 4,270 0.64 3.53 6,359 4,069 0.64 3.82
20 18 7,536 3,919 0.52 3.38 7,301 3,796 0.52 3.64 6,830 3,551 0.52 3.91
20 20 8,164 3,266 0.40 3.46 7,850 3,140 0.40 3.70 7,379 2,952 0.40 3.98
22 16 6,987 5,030 0.72 3.29 6,673 4,804 0.72 3.53 6,359 4,578 0.72 3.82
22 18 7,536 4,522 0.60 3.38 7,301 4,380 0.60 3.64 6,830 4,098 0.60 3.91
22 20 8,164 3,919 0.48 3.46 7,850 3,768 0.48 3.70 7,379 3,542 0.48 3.98
24 16 6,987 5,589 0.80 3.29 6,673 5,338 0.80 3.53 6,359 5,087 0.80 3.82
24 18 7,536 5,124 0.68 3.38 7,301 4,964 0.68 3.64 6,830 4,644 0.68 3.91
24 20 8,164 4,572 0.56 3.46 7,850 4,396 0.56 3.70 7,379 4,132 0.56 3.98
24 22 8,792 3,868 0.44 3.53 8,478 3,730 0.44 3.81 8,007 3,523 0.44 4.05
26 16 6,987 6,148 0.88 3.29 6,673 5,872 0.88 3.53 6,359 5,595 0.88 3.82
26 18 7,536 5,727 0.76 3.38 7,301 5,548 0.76 3.64 6,830 5,190 0.76 3.91
26 20 8,164 5,225 0.64 3.46 7,850 5,024 0.64 3.70 7,379 4,723 0.64 3.98
26 22 8,792 4,572 0.52 3.53 8,478 4,409 0.52 3.81 8,007 4,164 0.52 4.05
27 16 6,987 6,428 0.92 3.29 6,673 6,139 0.92 3.53 6,359 5,850 0.92 3.82
27 18 7,536 6,029 0.80 3.38 7,301 5,840 0.80 3.64 6,830 5,464 0.80 3.91
27 20 8,164 5,552 0.68 3.46 7,850 5,338 0.68 3.70 7,379 5,018 0.68 3.98
27 22 8,792 4,924 0.56 3.53 8,478 4,748 0.56 3.81 8,007 4,484 0.56 4.05
28 16 6,987 6,707 0.96 3.29 6,673 6,406 0.96 3.53 6,359 6,104 0.96 3.82
28 18 7,536 6,330 0.84 3.38 7,301 6,132 0.84 3.64 6,830 5,737 0.84 3.91
28 20 8,164 5,878 0.72 3.46 7,850 5,652 0.72 3.70 7,379 5,313 0.72 3.98
28 22 8,792 5,275 0.60 3.53 8,478 5,087 0.60 3.81 8,007 4,804 0.60 4.05
30 16 6,987 6,987 1.00 3.29 6,673 6,673 1.00 3.53 6,359 6,359 1.00 3.82
30 18 7,536 6,933 0.92 3.38 7,301 6,716 0.92 3.64 6,830 6,283 0.92 3.91
30 20 8,164 6,531 0.80 3.46 7,850 6,280 0.80 3.70 7,379 5,903 0.80 3.98
30 22 8,792 5,979 0.68 3.53 8,478 5,765 0.68 3.81 8,007 5,445 0.68 4.05
32 16 6,987 6,987 1.00 3.29 6,673 6,673 1.00 3.53 6,359 6,359 1.00 3.82
32 18 7,536 7,536 1.00 3.38 7,301 7,301 1.00 3.64 6,830 6,830 1.00 3.91
32 20 8,164 7,184 0.88 3.46 7,850 6,908 0.88 3.70 7,379 6,494 0.88 3.98
32 22 8,792 6,682 0.76 3.53 8,478 6,443 0.76 3.81 8,007 6,085 0.76 4.05
34 16 6,987 6,987 1.00 3.29 6,673 6,673 1.00 3.53 6,359 6,359 1.00 3.82
34 18 7,536 7,536 1.00 3.38 7,301 7,301 1.00 3.64 6,830 6,830 1.00 3.91
34 20 8,164 7,837 0.96 3.46 7,850 7,536 0.96 3.70 7,379 7,084 0.96 3.98
34 22 8,792 7,385 0.84 3.53 8,478 7,122 0.84 3.81 8,007 6,726 0.84 4.05
CA : Capacity (W) SHC(W) :Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor

23
OC301-A--1.qxp 04.4.28 11:14 AM Page 24

COOLING CAPACITY(11)
PKA-RP4FAL / PUH-P4YGAA
PUH-P4VGAA.UK PUH-P4YGAA.UK
PUH-P4VGAA1.UK PUH-P4YGAA1.UK
PU-P4YGAA
PU-P4VGAA.UK PU-P4YGAA.UK
PU-P4VGAA1.UK PU-P4YGAA1.UK (230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 20 25 30
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 9,306 6,142 0.66 2.87 9,024 5,956 0.66 3.03 8,742 5,770 0.66 3.21
20 18 9,964 5,381 0.54 2.93 9,682 5,228 0.54 3.09 9,353 5,051 0.54 3.30
20 20 10,716 4,501 0.42 3.02 10,481 4,402 0.42 3.16 10,199 4,284 0.42 3.37
22 16 9,306 6,886 0.74 2.87 9,024 6,678 0.74 3.03 8,742 6,469 0.74 3.21
22 18 9,964 6,178 0.62 2.93 9,682 6,003 0.62 3.09 9,353 5,799 0.62 3.30
22 20 10,716 5,358 0.50 3.02 10,481 5,241 0.50 3.16 10,199 5,100 0.50 3.37
24 16 9,306 7,631 0.82 2.87 9,024 7,400 0.82 3.03 8,742 7,168 0.82 3.21
24 18 9,964 6,975 0.70 2.93 9,682 6,777 0.70 3.09 9,353 6,547 0.70 3.30
24 20 10,716 6,215 0.58 3.02 10,481 6,079 0.58 3.16 10,199 5,915 0.58 3.37
24 22 11,421 5,254 0.46 3.09 11,186 5,146 0.46 3.27 10,904 5,016 0.46 3.48
26 16 9,306 8,375 0.90 2.87 9,024 8,122 0.90 3.03 8,742 7,868 0.90 3.21
26 18 9,964 7,772 0.78 2.93 9,682 7,552 0.78 3.09 9,353 7,295 0.78 3.30
26 20 10,716 7,073 0.66 3.02 10,481 6,917 0.66 3.16 10,199 6,731 0.66 3.37
26 22 11,421 6,167 0.54 3.09 11,186 6,040 0.54 3.27 10,904 5,888 0.54 3.48
27 16 9,306 8,748 0.94 2.87 9,024 8,483 0.94 3.03 8,742 8,217 0.94 3.21
27 18 9,964 8,170 0.82 2.93 9,682 7,939 0.82 3.09 9,353 7,669 0.82 3.30
27 20 10,716 7,501 0.70 3.02 10,481 7,337 0.70 3.16 10,199 7,139 0.70 3.37
27 22 11,421 6,624 0.58 3.09 11,186 6,488 0.58 3.27 10,904 6,324 0.58 3.48
28 16 9,306 9,120 0.98 2.87 9,024 8,844 0.98 3.03 8,742 8,567 0.98 3.21
28 18 9,964 8,569 0.86 2.93 9,682 8,327 0.86 3.09 9,353 8,044 0.86 3.30
28 20 10,716 7,930 0.74 3.02 10,481 7,756 0.74 3.16 10,199 7,547 0.74 3.37
28 22 11,421 7,081 0.62 3.09 11,186 6,935 0.62 3.27 10,904 6,760 0.62 3.48
30 16 9,306 9,306 1.00 2.87 9,024 9,024 1.00 3.03 8,742 8,742 1.00 3.21
30 18 9,964 9,366 0.94 2.93 9,682 9,101 0.94 3.09 9,353 8,792 0.94 3.30
30 20 10,716 8,787 0.82 3.02 10,481 8,594 0.82 3.16 10,199 8,363 0.82 3.37
30 22 11,421 7,995 0.70 3.09 11,186 7,830 0.70 3.27 10,904 7,633 0.70 3.48
32 16 9,306 9,306 1.00 2.87 9,024 9,024 1.00 3.03 8,742 8,742 1.00 3.21
32 18 9,964 9,964 1.00 2.93 9,682 9,682 1.00 3.09 9,353 9,353 1.00 3.30
32 20 10,716 9,644 0.90 3.02 10,481 9,433 0.90 3.16 10,199 9,179 0.90 3.37
32 22 11,421 8,908 0.78 3.09 11,186 8,725 0.78 3.27 10,904 8,505 0.78 3.48
34 16 9,306 9,306 1.00 2.87 9,024 9,024 1.00 3.03 8,742 8,742 1.00 3.21
34 18 9,964 9,964 1.00 2.93 9,682 9,682 1.00 3.09 9,353 9,353 1.00 3.30
34 20 10,716 10,502 0.98 3.02 10,481 10,271 0.98 3.16 10,199 9,995 0.98 3.37
34 22 11,421 9,822 0.86 3.09 11,186 9,620 0.86 3.27 10,904 9,377 0.86 3.48

CA : Capacity (W) SHC(W) :Sensible heat capacity


P.C. : Power consumption (kW) SHF : Sensible heat factor

24
OC301-A--1.qxp 04.4.28 11:14 AM Page 25

COOLING CAPACITY(12)
PKA-RP4FAL / PUH-P4YGAA
PUH-P4VGAA.UK PUH-P4YGAA.UK
PUH-P4VGAA1.UK PUH-P4YGAA1.UK
PU-P4YGAA
PU-P4VGAA.UK PU-P4YGAA.UK
PU-P4VGAA1.UK PU-P4YGAA1.UK
(230V)
Outdoor intake air D.B.(°C)
Indoor Indoor
Intake air Intake air 35 40 45
D.B.(°C) W.B.(°C) CA SHC(W) SHF P.C. CA SHC(W) SHF P.C. CA SHC(W) SHF P.C.
20 16 8,366 5,522 0.66 3.45 7,990 5,273 0.66 3.70 7,614 5,025 0.66 4.00
20 18 9,024 4,873 0.54 3.54 8,742 4,721 0.54 3.81 8,178 4,416 0.54 4.09
20 20 9,776 4,106 0.42 3.63 9,400 3,948 0.42 3.88 8,836 3,711 0.42 4.16
22 16 8,366 6,191 0.74 3.45 7,990 5,913 0.74 3.70 7,614 5,634 0.74 4.00
22 18 9,024 5,595 0.62 3.54 8,742 5,420 0.62 3.81 8,178 5,070 0.62 4.09
22 20 9,776 4,888 0.50 3.63 9,400 4,700 0.50 3.88 8,836 4,418 0.50 4.16
24 16 8,366 6,860 0.82 3.45 7,990 6,552 0.82 3.70 7,614 6,243 0.82 4.00
24 18 9,024 6,317 0.70 3.54 8,742 6,119 0.70 3.81 8,178 5,725 0.70 4.09
24 20 9,776 5,670 0.58 3.63 9,400 5,452 0.58 3.88 8,836 5,125 0.58 4.16
24 22 10,528 4,843 0.46 3.70 10,152 4,670 0.46 3.98 9,588 4,410 0.46 4.24
26 16 8,366 7,529 0.90 3.45 7,990 7,191 0.90 3.70 7,614 6,853 0.90 4.00
26 18 9,024 7,039 0.78 3.54 8,742 6,819 0.78 3.81 8,178 6,379 0.78 4.09
26 20 9,776 6,452 0.66 3.63 9,400 6,204 0.66 3.88 8,836 5,832 0.66 4.16
26 22 10,528 5,685 0.54 3.70 10,152 5,482 0.54 3.98 9,588 5,178 0.54 4.24
27 16 8,366 7,864 0.94 3.45 7,990 7,511 0.94 3.70 7,614 7,157 0.94 4.00
27 18 9,024 7,400 0.82 3.54 8,742 7,168 0.82 3.81 8,178 6,706 0.82 4.09
27 20 9,776 6,843 0.70 3.63 9,400 6,580 0.70 3.88 8,836 6,185 0.70 4.16
27 22 10,528 6,106 0.58 3.70 10,152 5,888 0.58 3.98 9,588 5,561 0.58 4.24
28 16 8,366 8,199 0.98 3.45 7,990 7,830 0.98 3.70 7,614 7,462 0.98 4.00
28 18 9,024 7,761 0.86 3.54 8,742 7,518 0.86 3.81 8,178 7,033 0.86 4.09
28 20 9,776 7,234 0.74 3.63 9,400 6,956 0.74 3.88 8,836 6,539 0.74 4.16
28 22 10,528 6,527 0.62 3.70 10,152 6,294 0.62 3.98 9,588 5,945 0.62 4.24
30 16 8,366 8,366 1.00 3.45 7,990 7,990 1.00 3.70 7,614 7,614 1.00 4.00
30 18 9,024 8,483 0.94 3.54 8,742 8,217 0.94 3.81 8,178 7,687 0.94 4.09
30 20 9,776 8,016 0.82 3.63 9,400 7,708 0.82 3.88 8,836 7,246 0.82 4.16
30 22 10,528 7,370 0.70 3.70 10,152 7,106 0.70 3.98 9,588 6,712 0.70 4.24
32 16 8,366 8,366 1.00 3.45 7,990 7,990 1.00 3.70 7,614 7,614 1.00 4.00
32 18 9,024 9,024 1.00 3.54 8,742 8,742 1.00 3.81 8,178 8,178 1.00 4.09
32 20 9,776 8,798 0.90 3.63 9,400 8,460 0.90 3.88 8,836 7,952 0.90 4.16
32 22 10,528 8,212 0.78 3.70 10,152 7,919 0.78 3.98 9,588 7,479 0.78 4.24
34 16 8,366 8,366 1.00 3.45 7,990 7,990 1.00 3.70 7,614 7,614 1.00 4.00
34 18 9,024 9,024 1.00 3.54 8,742 8,742 1.00 3.81 8,178 8,178 1.00 4.09
34 20 9,776 9,580 0.98 3.63 9,400 9,212 0.98 3.88 8,836 8,659 0.98 4.16
34 22 10,528 9,054 0.86 3.70 10,152 8,731 0.86 3.98 9,588 8,246 0.86 4.24
CA : Capacity (W) SHC(W) :Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor

25
OC301-A--1.qxp 04.4.28 11:14 AM Page 26

HEATING CAPACITY (1)


PKA-RP•FAL / PUHZ-RP•VHA
PUHZ-RP•VHA1 (230V)
Indoor Outdoor intake air W.B. (:)
Service Ref. intake are -10 -5 0 5 10 15
D.B. (˚C) CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C.
15 4,445 1.19 4,830 1.31 5,390 1.51 7,070 1.81 7,980 2.01 8,890 2.17
PKA-RP2.5FAL 20 4,270 1.29 4,620 1.41 5,110 1.63 6,825 1.95 7,700 2.17 8,575 2.33
25 4,130 1.37 4,480 1.53 4,900 1.77 6,440 2.07 7,420 2.32 8,260 2.50
15 5,080 1.42 5,520 1.56 6,160 1.80 8,080 2.16 9,120 2.40 10,160 2.59
PKA-RP3FAL 20 4,880 1.54 5,280 1.68 5,840 1.94 7,800 2.33 8,800 2.59 9,800 2.78
25 4,720 1.63 5,120 1.82 5,600 2.11 7,360 2.47 8,480 2.77 9,440 2.99
15 7,112 1.92 7,728 2.11 8,624 2.44 11,312 2.93 12,768 3.25 14,224 3.51
PKA-RP4FAL 20 6,832 2.08 7,392 2.28 8,176 2.63 10,920 3.15 12,320 3.51 13,720 3.77
25 6,608 2.21 7,168 2.47 7,840 2.86 10,304 3.35 11,872 3.75 13,216 4.05

NOTE: CA: Capacity (W) P.C.: Power consumption (kW)

HEATING CAPACITY (2)


PKA-RP•FAL / PUH-P•VGAA PUH-P•YGAA PUH-P•VGAA.UK PUH-P•YGAA.UK
PUH-P•VGAA1.UK PUH-P•YGAA1.UK (230V)
Indoor Outdoor intake air W.B. (:)
Service Ref. intake are -10 -5 0 5 10 15
D.B. (˚C) CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C.
15 4,667 1.55 5,072 1.71 5,660 1.97 7,424 2.37 8,379 2.63 9,335 2.84
PKA-RP2.5FAL 20 4,484 1.68 4,851 1.84 5,366 2.13 7,166 2.55 8,085 2.84 9,004 3.05
25 4,337 1.79 4,704 2.00 5,145 2.31 6,762 2.71 7,791 3.04 8,673 3.27
15 5,969 2.13 6,486 2.35 7,238 2.71 9,494 3.25 10,716 3.61 11,938 3.90
PKA-RP3FAL 20 5,734 2.31 6,204 2.53 6,862 2.92 9,165 3.50 10,340 3.90 11,515 4.19
25 5,546 2.45 6,016 2.74 6,580 3.18 8,648 3.72 9,964 4.17 11,092 4.49
15 6,858 2.22 7,452 2.45 8,316 2.83 10,908 3.39 12,312 3.77 13,716 4.07
PKA-RP4FAL 20 6,588 2.41 7,128 2.64 7,884 3.05 10,530 3.66 11,880 4.07 13,230 4.37
25 6,372 2.56 6,912 2.87 7,560 3.32 9,936 3.88 11,448 4.35 12,744 4.69

NOTE: CA: Capacity (W) P.C.: Power consumption (kW)

26
OC301-A--1.qxp 04.4.28 11:14 AM Page 27

5-2. PERFORMANCE CURVE


PKA-RP•FAL / PUHZ-RP•VHA
PUHZ-RP•VHA1
Cooling performance curve(50Hz) Heating performance curve(50Hz)
Correcting the capacity line influenced by frosting
Not correcting the capacity line influenced by frosting
1.4 1.4
CAPACITY (RATIO)

In some cases, heating operation 15 INDOOR

CAPACITY (RATIO)
cannot be conducted with the maximum 20
1.2 INDOOR 1.2 frequency in the area below the slanting line. 25 D.B.(°C)
W.B.(°C)
1.0 22 1.0
20
18
0.8
0.8
16

0.6

0.4

1.4
22 INDOOR In some cases, heating operation
1.2 cannot be conducted with the maximum 25
20 W.B.(°C) INDOOR

TOTAL INPUT (RATIO)


18 frequency in the area above the slanting line.
TOTAL INPUT (RATIO)

1.2 20
16 D.B.(°C)
15
1.0
1.0

0.8
0.8

0.6
0.6

0.4
0.4
-5 0 10 20 30 40 46
-12 -10 -5 0 5 10 15
OUTDOOR D.B.(°C) OUTDOOR W.B.(°C)

PKA-RP•FAL / PUH-P•VGAA PUH-P•YGAA PUH-P•VGAA.UK PUH-P•YGAA.UK


PU-P•VGAA PU-P•YGAA PU-P•VGAA.UK PU-P•YGAA.UK
PUH-P•VGAA1.UK PUH-P•YGAA1.UK
PU-P•VGAA1.UK PU-P•YGAA1.UK
Cooling performance curve(50Hz) Heating performance curve(50Hz)
Correcting the capacity line influenced by frosting
Not correcting the capactiy line influenced by frosting
1.4 1.4
CAPACITY (RATIO)

15 INDOOR
CAPACITY (RATIO)

20
1.2 INDOOR 1.2 25 D.B.(°C)
W.B.(°C)
1.0 22 1.0
20
18
0.8
0.8
16

0.6

0.4

1.4
22 INDOOR
1.2 20 W.B.(°C) 25 INDOOR
TOTAL INPUT (RATIO)

18
TOTAL INPUT (RATIO)

1.2 20
16 D.B.(°C)
15
1.0
1.0

0.8
0.8

0.6
0.6

0.4
0.4
-5 0 10 20 30 40 46
-12 -10 -5 0 5 10 15
OUTDOOR D.B.(°C) OUTDOOR W.B.(°C)

27
OC301-A--1.qxp 04.4.28 11:14 AM Page 28

5-3. Correction factors


PKA-RP•FAL / PUHZ-RP•VHA
PUHZ-RP•VHA1
Cooling capacity correction factors
Refrigerant piping length (one way)
Service Ref.
5m 10m 20m 30m 40m 50m 55m 60m 70m 80m
PKA-RP2.5FAL 1.00 0.992 0.976 0.962 0.949 0.936 0.930 — — —

PKA-RP3FAL 1.00 0.988 0.966 0.946 0.929 0.913 0.905 — — —


PKA-RP4FAL 1.00 0.985 0.957 0.931 0.908 0.886 0.876 0.865 0.846 0.829

Heating capacity correction factors


Refrigerant piping length (one way)
Service Ref. 5m 10m 30m 40m 50m 55m 60m 70m 80m
20m
PKA-RP2.5FAL 1.00 0.997 0.991 0.985 0.979 0.973 0.970 — — —

PKA-RP3FAL 1.00 0.997 0.991 0.985 0.979 0.973 0.970 — — —

PKA-RP4FAL 1.00 0.997 0.991 0.985 0.979 0.973 0.970 0.967 0.961 0.955

PKA-RP•FAL / PUH-P•VGAA PUH-P•YGAA PUH-P•VGAA.UK PUH-P•YGAA.UK


PU-P•VGAA PU-P•YGAA PU-P•VGAA.UK PU-P•YGAA.UK
PUH-P•VGAA1.UK PUH-P•YGAA1.UK
Cooling capacity correction factors PU-P•VGAA1.UK PU-P•YGAA1.UK
Refrigerant piping length(one way)
Service Ref.
5m 10m 20m 30m 40m 50m
PKA-RP2.5FAL 1.00 0.989 0.970 0.950 0.930 0.910

PKA-RP3FAL 1.00 0.981 0.952 0.925 0.900 0.874

PKA-RP4FAL 1.00 0.989 0.970 0.950 0.930 0.910

Heating capacity correction factors


Refrigerant piping length(one way)
Service Ref.
5m 10m 20m 30m 40m 50m
PKA-RP2.5FAL 1.00 0.998 0.993 0.988 0.983 0.978

PKA-RP3FAL 1.00 0.998 0.993 0.988 0.983 0.978

PKA-RP4FAL 1.00 0.998 0.993 0.988 0.983 0.978

28
OC301-A--1.qxp 04.4.28 11:14 AM Page 29

5-4. STANDARD OPERATION DATA


Heat pump type (1)
Service Ref. PKA-RP2.5FAL PKA-RP3FAL PKA-RP4FAL

Mode Cooling Heating Cooling Heating Cooling Heating


Capacity W 6,000 7,000 7,100 8,000 10,000 11,200
Total

Input kW 1.55 2.01 1.98 2.40 2.93 3.25

Indoor unit Service Ref. PKA-RP2.5FAL PKA-RP3FAL PKA-RP4FAL

Phase , Hz 1 , 50 1 , 50 1 , 50

Volts 230 230 230


Electrical circuit

Amperes 0.43 0.43 0.43 0.43 0.52 0.52

Outdoor unit Service Ref. PUHZ-RP2.5VHA PUHZ-RP3VHA PUHZ-RP4VHA


PUHZ-RP4VHA1
Phase , Hz 1 , 50 1 , 50 1 , 50

Volts 230 230 230

Amperes 6.52 8.58 8.44 10.33 12.61 14.05

Discharge pressure MPa 2.61 3.08 2.71 3.24 2.57 2.90


Refrigerant circuit

Suction pressure MPa 1.01 0.75 0.96 0.73 0.88 0.74

Discahrge temperature ˚C 64 80 67 83 68 78

Condensing temperature ˚C 43 50 45 54 44 49

Suction temperature ˚C 11 2 10 2 8 3

Ref.pipe length m 5 5 5 5 5 5

D.B. ˚C 27 20 27 20 27 20
Indoor side

Intake air
temperature
W.B. ˚C 19 15 19 15 19 15
Discharge air
temperature D.B. ˚C 14.9 38.7 13.8 41.6 13.6 41.6
Outdoor

Intake air D.B. ˚C 35 7 35 7 35 7


side

temperature
W.B. ˚C 24 6 24 6 24 6

SHF 0.83 — 0.77 — 0.71 —

BF 0.13 — 0.13 — 0.10 —

The unit of pressure has been changed to Mpa on tha international system of unit (Sl system).
The converted score against tha traditional unit system can be gotten according to the formula below.
f)
1(MPa) = 10.2(kgf/f

29
OC301-A--1.qxp 04.4.28 11:14 AM Page 30

Heat pump type (2)


Service Ref. PKA-RP2.5FAL PKA-RP3FAL PKA-RP4FAL
Mode Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating
Capacity W 6,450 7,350 6,450 7,350 7,850 9,400 7,850 9,400 9,400 10,800 9,400 10,800
Total

Input kW 2.65 2.63 2.65 2.63 3.43 3.61 3.43 3.61 3.59 3.77 3.59 3.77

Indoor unit Service Ref. PKA-RP2.5FAL PKA-RP3FAL PKA-RP4FAL


Phase , Hz 1 , 50 1 , 50 1 , 50
Volts 230 230 230
Electrical circuit

Amperes 0.43 0.43 0.43 0.43 0.43 0.43 0.43 0.43 0.52 0.52 0.52 0.52
PUH-P2.5VGAA PUH-P3VGAA PUH-P3YGAA PUH-P4YGAA
Outdoor unit Service Ref. PUH-P2.5VGAA.UK PUH-P2.5YGAA.UK PUH-P3VGAA.UK PUH-P3YGAA.UK PUH-P4VGAA.UK PUH-P4YGAA.UK
PUH-P2.5VGAA1.UK PUH-P2.5YGAA1.UK PUH-P3VGAA1.UK PUH-P3YGAA1.UK PUH-P4VGAA1.UK PUH-P4YGAA1.UK
Phase , Hz 1 , 50 3 , 50 1 , 50 3 , 50 1 , 50 3 , 50

Volts 230 400 230 400 230 400

Amperes 12.23 12.14 3.78 3.75 15.96 16.82 5.02 5.30 16.63 17.49 5.18 5.47
Discharge pressure MPa 2.10 2.23 2.10 2.23 2.26 2.54 2.26 2.54 1.95 2.14 1.95 2.14
Refrigerant circuit

Suction pressure MPa 0.51 0.43 0.51 0.43 0.47 0.40 0.47 0.40 0.48 0.41 0.48 0.41
Discahrge temperature ˚C 76 80 76 80 81 91 81 91 75 70 75 70
Condensing temperature ˚C 49 49 49 49 51 54 51 54 47 47 47 47
Suction temperature ˚C 7 -1 7 -1 4 -1 4 -1 8 0 8 0
Ref.pipe length m 5 5 5 5 5 5 5 5 5 5 5 5

D.B.
Indoor side

Intake air ˚C 27 20 27 20 27 20 27 20 27 20 27 20
temperature
W.B. ˚C 19 15 19 15 19 15 19 15 19 15 19 15
Discharge air
temperature D.B. ˚C 14.4 39.9 14.4 39.9 13.0 39.9 13.0 39.9 14.5 41.0 14.5 41.0
Outdoor

Intake air D.B. ˚C 35 7 35 7 35 7 35 7 35 7 35 7


side

temperature
W.B. ˚C 24 6 24 6 24 6 24 6 24 6 24 6
SHF 0.80 — 0.80 — 0.74 — 0.74 — 0.76 — 0.76 —

BF 0.13 — 0.13 — 0.11 — 0.11 — 0.16 — 0.16 —

The unit of pressure has been changed to Mpa on tha international system of unit (Sl system).
The converted score against tha traditional unit system can be gotten according to the formula below.
f)
1(MPa) = 10.2(kgf/f

30
OC301-A--2.qxp 04.4.28 11:16 AM Page 31

Cooling only type


Service Ref. PKA-RP2.5FAL PKA-RP3FAL PKA-RP4FAL

Mode Cooling Cooling Cooling Cooling Cooling Cooling


Capacity W 6,450 6,450 7,850 7,850 9,400 9,400
Total

Input kW 2.65 2.65 3.43 3.43 3.59 3.59

Indoor unit Service Ref. PKA-RP2.5FAL PKA-RP3FAL PKA-RP4FAL


Phase , Hz 1 , 50 1 , 50 1 , 50
Volts 230 230 230
Electrical circuit

Amperes 0.43 0.43 0.43 0.43 0.52 0.52


PU-P2.5VGAA PU-P3VGAA PU-P3YGAA PU-P4YGAA
Outdoor unit Service Ref. PU-P2.5VGAA.UK PU-P2.5YGAA.UK PU-P3VGAA.UK PU-P3YGAA.UK PU-P4VGAA.UK PU-P4YGAA.UK
PU-P2.5VGAA1.UK PU-P2.5YGAA1.UK PU-P3VGAA1.UK PU-P3YGAA1.UK PU-P4VGAA1.UK PU-P4YGAA1.UK
Phase , Hz 1 , 50 3 , 50 1 , 50 3 , 50 1 , 50 3 , 50

Volts 230 400 230 400 230 400

Amperes 12.23 3.78 15.96 5.02 16.63 5.18


Discharge pressure MPa 2.10 2.10 2.26 2.26 1.95 1.95
Refrigerant circuit

Suction pressure MPa 0.51 0.51 0.47 0.47 0.48 0.48


Discahrge temperature ˚C 76 76 81 81 75 75
Condensing temperature ˚C 49 49 51 51 47 47
Suction temperature ˚C 7 7 4 4 8 8
Ref.pipe length m 5 5 5 5 5 5

D.B.
Indoor side

Intake air ˚C 27 27 27 27 27 27
temperature
W.B. ˚C 19 19 19 19 19 19
Discharge air
temperature D.B. ˚C 14.4 14.4 13.0 13.0 14.5 14.5
Outdoor

Intake air D.B. ˚C 35 35 35 35 35 35


side

temperature
W.B. ˚C 24 24 24 24 24 24
SHF 0.80 0.80 0.74 0.74 0.76 0.76

BF 0.13 0.13 0.11 0.11 0.16 0.16

The unit of pressure has been changed to Mpa on tha international system of unit (Sl system).
The converted score against tha traditional unit system can be gotten according to the formula below.
f)
1(MPa) = 10.2(kgf/f

5-5. OUTLET AIR SPEED COVERAGE RANGE

PKA-RP2.5FAL PKA-RP3FAL PKA-RP4FAL

Air flow m3/min 20 20 28


Air speed m/sec 4.9 4.9 5.4
Coverage range m (ft) 12.4(40.7) 12.4(40.7) 15.3(50.2)
The air coverage range is the value up to the position where the air speed is 0.25m/sec. when air is blown out horizontally from
the unit at the Hi notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the furni-
ture inside the room.

31
OC301-A--2.qxp 04.4.28 11:16 AM Page 32

5-6. NOISE CRITERION CURVES


PKA-RP2.5FAL NOTCH SPL(dB) LINE PKA-RP4FAL NOTCH SPL(dB) LINE
Hi 45 Hi 46
PKA-RP3FAL Lo 39 Lo 41

90 90
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR


80 80

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

APPROXIMATE 20 APPROXIMATE
20
TERESHOLD OF TERESHOLD OF
HEARING FOR HEARING FOR
NC-20 CONTINUOUS
NC-20
CONTINUOUS
NOISE NOISE
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz

UNIT
WALL

1m

1m

MICROPHONE

32
OC301-A--2.qxp 04.4.28 11:16 AM Page 33

6 OUTLINES AND DIMENSIONS

PKA-RP2.5FAL Unit : mm
PKA-RP3FAL
Display section
Top

62.5
Emergency switch(Heat)
Receiving
section Emergency switch(Cool)
Defrosting Initial heating lamp
235 45 235 45 235 45 235

13
Power lamp
Front Right side

Left side 1400 235


Knock out hole for right piping
1090 Air intake
Refrigerant pipe. Drain pipe

197
A C
340

Terminal block for indoor/outdoor connecting line


Knock out hole for Liquid pipe 15
left piping
Gas pipe

Bolt

42
58
Drain hose for 25 55 (Gas pipe) Drain hose O.D.20
Drain hose
left-hand side piping 120 107
1110 183 (Liquid pipe) 111

Lower side
Liquid pipe [9.52(3/8F)
Auto vane Gas pipe [15.88(5/8F)
1120 240
552 Air outlet 552 Air outlet

Under panel Change vane (manual)


B
Removable at left-hand
side piping Knock out hole for under-piping
Refrigerant pipe. Drain pipe

Unit center
990 245
455
10 91=(910) 285
900 19 Knock out hole for wiring
Wall fixture 18 18 Drainage range Drainage range 91
29

on left-hand side on right-hand side


A B C
10
30

30 30
66-ø6 hole for
80

tapping screw
280

100
100
184
30

65

39
4 39

37
60

37 39 37
98 32
4

32-ø12 hole for bolt 74


30

225 240 180 280 314 74


610 90 Rear piping access hole
12-ø6 hole for
tapping screw Knockout hole for left rear piping

33
OC301-A--2.qxp 04.4.28 11:16 AM Page 34

PKA-RP4FAL Unit : mm

Top
Display section

62.5
Emergency switch(Heat)
235 45 235 45 235 45 235 45 235 Emergency switch(Cool)

13
Receiving
section Defrosting Initial heating lamp
Power lamp
Front Knock out hole for right piping
Right side
Left side 1680
235
1370 Air intake

197
C
340

Knock out hole for left piping


Terminal block for indoor/outdoor connecting line
Liquid pipe 15

Gas pipe

Bolt

42
25
Drain hose
58
55 (Gas pipe) Drain hose O.D.20
120 102
Drain hose for left-hand side piping 1110 Drain hose (Liquid pipe)
183 111
Lower side
1400 240 Gas pipe For PUHZ-RP type: [15.88(5/8F)
694 Air outlet 694 Air outlet For PU(H)-P type : [19.05(3/4F)

Liquid pipe [9.52(3/8F)

Change vane (manual)


Under panel B
(Removable at left-hand side piping)

Auto vane

Knock out hole for under-piping


Refrigerant pipe. Drain pipe

Unit center
Unit out line
1270 245
595
Wall fixture
13 91=(1183) 285
900 19 Knock out hole for wiring
84-ø6 hole for 18 18
tapping screw Drainage range Drainage range 91
on left-hand side on right-hand side A B C
29
10
30

30 30
80

100
280

100
184
30

65

39
4 39

37

37 39 37
60

98 32
4

41-ø12 hole for bolt 74 74


30

295 225 240 180 280 314


750 90 Rear piping access hole

Knockout hole for left rear piping Knockout hole for left rear piping

12-ø6 hole for tapping screw

34
OC301-A--2.qxp 04.4.28 11:16 AM Page 35

7 WIRING DIAGRAM
PKA-RP2.5FAL PKA-RP3FAL PKA-RP4FAL
SYMBOL NAME SYMBOL NAME SYMBOL NAME
P.B INDOOR POWER BOARD C CAPACITOR(FAN MOTOR) W.B WIRELESS REMOTE CONTROLLER BOARD
F1 FUSE(4A) MF FAN MOTOR RU RECEIVING UNIT
ZNR VARISTOR MV VANE MOTOR BZ BUZZER
I.B INDOOR CONTROLLER BOARD TB4 TERMINAL BLOCK(INDOOR/OUTDOOR LED1 LED(RUN INDICATOR)
CN2L CONNECTOR(LOSSNAY) CONNECTING LINE) LED2 LED(HOT ADJUST)
CN32 CONNECTOR(REMOTE SWITCH) TB5 TERMINAL BLOCK(REMOTE CONTROLLER SW1 SWITCH(HEATING ON/OFF)
CN41 CONNECTOR(HA TERMINAL-A) TRANSMISSION LINE)(OPTION) SW2 SWITCH(COOLING ON/OFF)
SW1 JUMPER WIRE(MODEL SELECTION) TH1 ROOM TEMPERATURE THERMISTOR R.B REMOTE CONTROLLER BOARD(OPTION)
SW2 JUMPER WIRE(CAPACITY CODE) (0°C/15kΩ, 25°C/5.4kΩ DETECT) CN2 CONNECTOR(SCHEDULE TIMER)
SWE SWITCH(EMERGENCY OPERATION) TH2 PIPE TEMPERATURE THERMISTOR/LIQUID TB6 TERMINAL BLOCK(REMOTE CONTROLLER
X4 RELAY(FAN MOTOR) (0°C/15kΩ, 25°C/5.4kΩ DETECT) TRANSMISSION LINE)
FC FAN PHASE CONTROL TH5 CONDENSER / EVAPORATOR TEMPERATURE
LED1 POWER SUPPLY(I.B) THERMISTOR (0°C/15kΩ, 25°C/5.4kΩ DETECT)
LED2 POWER SUPPLY(R.B)
LED3 TRANSMISSION(INDOOR-OUTDOOR)
INDOOR UNIT CN2S(WHT)
P.B
F1
2
1 DC14V TB4
MF ZNR
3 1
YLW S1
1 2 3 ORN S2
2 2 TO OUTDOOR UNIT
C 1 3
BRN S3
CONT.BOARD OUTDOOR
WHT

WHT
ORN
YLW

BRN
RED

BLK

BLK

CN02 (WHT) CN01 (BLU)


I.B
POWER MV
1 3 5 VANE
FAN CN03 1 3 5 1 2
CN6V 6
(WHT) (RED) POWER (WHT)
CN2D (WHT)
X4 CN41 CN2L
FC 9
WIRELESS W.B R.B
X4 CN25 CN32 CN90 RECEI
(WHT) CNB TB6
LED3 LED2 LED1 -VER BZ
2 1
CN2
SWE SW2 SW1 HEATER INTAKE LIQUID PIPE REMOCON RU LED1 LED2 SW2 SW1
ON CN24 CN20 CN21 CN29 CN22
(YLW) (RED) (WHT) (BLK) (BLU)
J21
J22
J23
J24

J11
J12
J13
J14
J15

TRANSMISSION WIRES DC12V


OFF
1 2 1 2 1 2 1 2 1 2
Please set the voltage
2 using the remote controller.
SW1 SW2
Manufacture MODELS Manufacture Service board 1 For the setting method,
please refer to the indoor
1234 TB5
ON TH1 TH2 TH5 unit Installation Manual.
2.5FAL
J11J12J13J14J15 J21J22J23J24 OFF
Service board 1234
3FAL ON
12345 OFF
ON J21J22J23J24
OFF
1234
4FAL ON
J21J22J23J24 OFF
NOTES:
1.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2.Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers(S1, S2, S3).
3.Symbols used in wiring diagram above are, :Connector, :Terminal (block).
[Self-diagnosis]
An explanation of the wireless remote controller self checking operations, check codes, buzzer sounds and LED signals are given
below. For check codes and symptom see the table below please.
1.Press the CHECK button twice continuously. 3.While pointing the remote controller toward the unit's
• CHECK begins to light and refrigerant address display receiver, press the h button.
"00" begins to blink. • The check code will be indicated by the number of times
• Start this operation from the status of remote controller that the buzzer sounds from the receiver section and the
display turned off. number of blinks of the operation lamp.
2.Press the TEMP ▼ , ▲ buttons. 4.While pointing the remote controller toward the unit's
• Set the refrigerant address of the indoor unit that is to receiver, press the ON/OFF button.
be self-diagnosed. • Self-check mode is canceled.
• Set the refrigerant address of outdoor unit by outdoor unit
dip switch "SW1".
(Refer to installation manual of outdoor unit for the detail.)
Check code Operation lamp Buzzer sound Symptom
P1 1SEC.FLASH ✕ 1 Single beep ✕ 1 Abnormality of room temperature thermistor(TH1).
P2 1SEC.FLASH ✕ 2 Single beep ✕ 2 Abnormality of pipe temperature thermistor/Liquid(TH2).
P4 1SEC.FLASH ✕ 4 Single beep ✕ 4 Abnormality of drain sensor(DS).
P5 1SEC.FLASH ✕ 5 Single beep ✕ 5 Malfunction of drain-up machine.
P6 1SEC.FLASH ✕ 6 Single beep ✕ 6 Freezing /overheating protection is working.
P8 1SEC.FLASH ✕ 8 Single beep ✕ 8 Abnormality of pipe temperature.
P9 1SEC.FLASH ✕ 2 Single beep ✕ 2 Abnormality of pipe temperature thermistor/ Condenser/Evaporator(TH5).
U0~UL (0.4+0.4)SEC.FLASH ✕ 1 Double beep ✕ 1 Abnormality in outdoor unit. Refer to outdoor unit wiring diagram.
F1~F9
E6~EF DIFFERENT FROM ABOVE Sounds other than Abnormality of signal transmission between indoor unit and outdoor unit
above ("EE" indicates abnormality of combination).
---- OFF No sound No trouble generated in the past.
FFFF OFF Triple beep No corresponding unit.

35
OC301-A--2.qxp 04.4.28 11:16 AM Page 36

8 REFRIGERANT SYSTEM DIAGRAM

PKA-RP2.5FAL Unit : mm
PKA-RP3FAL
PKA-RP4FAL

Strainer
#50
Heat exchanger
Refrigerant GAS pipe connection
(Flare)
Condenser/evaporator
temperature thermistor
(TH5)
Refrigerant flow in cooling
Refrigerant flow in heating

Refrigerant LIQUID pipe connection


(Flare)
Pipe temperature
Room temperature thermistor/liquid
thermistor (TH1) (TH2)
Strainer
Distributor #50
with strainer
#50

36
OC301-A--2.qxp 04.4.28 11:16 AM Page 37

9 TROUBLESHOOTING

9-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit.
Actions to be taken for service and the inferior phenomenon reoccurrence at field are summarized in the table below. Check
the contents below before investigating details.

Unit conditions at service Error code Actions to be taken for service (summary)

Judge what is wrong and take a corrective action


Displayed according to “Self-diagnosis action table” (Page 39).
The inferior phenomenon is
reoccurring.
Identify the cause of the inferior phenomenon and take
Not displayed a corrective action according to “Trouble shooting by
inferior phenomena” (Page 42).

1Consider the temporary defects such as the work of


protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
inferior phenomenon occurred, and wiring related.
Logged
2Reset error code logs and restart the unit after finishing
service.
3There is no abnormality in electrical components,
controller boards, and remote controller.
The inferior phenomenon is
not reoccurring.
1Recheck the abnormal symptom.
2Identify the cause of the inferior phenomenon and take
a corrective action according to “Trouble shooting by
inferior phenomena” (Page 42).
Not logged 3Continue to operate unit for the time being if the cause
is not ascertained.
4There is no abnormality in electrical components,
controller boards, remote controller etc.

37
OC301-A--2.qxp 04.4.28 11:16 AM Page 38

9-2. Malfunction-diagnosis method by remote controller


<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<Malfunction-diagnosis method at maintenance service>
[Procedure]
1. Press the CHECK button twice. • "CHECK" lights, and refrigerant
Refrigerant
address address "00" flashes.
display • Check that the remote controller's
CHECK
CHECK display has stopped before continuing.
display
2. Press the temperature • Select the refrigerant address of the
Temperature buttons.
button indoor unit for the self-diagnosis.
ON/OFF TEMP Note: Set refrigerant address using the
outdoor unit’s DIP switch (SW1).
ON/OFF
button (For more information, see the
outdoor unit installation manual.)
FAN AUTO STOP

MODE VANE AUTO START 3. Point the remote controller at the • If an air conditioner error occurs, the
HOUR
button sensor on the indoor unit and indoor unit's sensor emits an intermit-
CHECK LOUVER h
press the HOUR button. tent buzzer sound, the operation light
CHECK TEST RUN min flashes, and the error code is
button output.
SET RESET CLOCK (It takes 3 seconds at most for error
code to appear.)

4. Point the remote controller at the • The check mode is cancelled.


sensor on the indoor unit and
press the ON/OFF button.

✽ Malfunction diagnosis can be performed only for refrigerant system control-


ling wireless units.

Inspected unit Check code Beep output Operation LED Inspected unit Check code Beep output Operation LED

P1 beep O 1 time 1 sec. O 1 time F1–F9


Outdoor

(0.4sec+0.4sec)
beep beep O 1 time
unit

P2 beep O 2 times 1 sec.O 2 times U0–UP O 1 time


Indoor unit

P4 beep O 4 times 1 sec.O 4 times E6–EE Other than above Other than above
No check code
P5 beep O 5 times 1 sec.O 5 times (normal) No output Lights off
No check code
P6 beep O 6 times 1 sec.O 6 times (mistake of match-
ing with refrigerant beep beep beep Lights off
P8 beep O 8 times 1 sec.O 8 times address)
P9 beep O 2 times 1 sec.O 2 times
E4, E5 Other than above Other than above

38
OC301-A--2.qxp 04.4.28 11:16 AM Page 39

Note: Refer to the manual of outdoor unit for the details of display
9-3. SELF-DIAGNOSIS ACTION TABLE such as F, U, and other E.

Error Code Meaning of error code and detection method Cause Countermeasure
Abnormality of room temperature 1 Defective thermistor 1–3 Check resistance value of thermistor.
thermistor (TH1) characteristics. 0: ······15.0k"
1 The unit is in three-minute resume 2 Contact failure of connector 10: ····9.6k"
prevention mode if short/open of (CN20) on the indoor controller 20: ····6.3k"
thermistor is detected. Abnormal if the board. (Insert failure) 30: ····4.3k"
unit does not reset normally after three 3 Breaking of wire or contact 40: ····3.0k"
minutes. (The unit returns to normal failure of thermistor wiring. If you put force on (draw or bend) the lead wire
operation, if it has normally reset.) 4 Defective indoor controller with measuring resistance value of thermistor
2 Constantly detected during cooling, board. breaking of wire or contact failure can be
drying, and heating operation. detected.
Short: 90: or more 2 Check contact failure of connector (CN20) on
P1 Open: -40: or less the indoor controller board. Refer to page 45.
Turn the power on again and check restart
after inserting connector again.
4 Check room temperature display on remote
controller.
Replace indoor controller board if there is
abnormal difference with actual room
temperature.

Turn the power off, and on again to operate


after check.
Abnormality of pipe temperature 1 Defective thermistor 1–3 Check resistance value of thermistor.
thermistor/Liquid (TH2) characteristics. For characteristics, refer to (P1) above.
1 The unit is in three-minute resume 2 Contact failure of connector 2 Check contact failure of connector (CN21) on
prevention mode if short/open of (CN21) on the indoor controller the indoor controller board. Refer to page 45.
thermistor is detected. Abnormal if the board. (Insert failure) Turn the power on and check restart after
unit does not reset normally after three 3 Breaking of wire or contact inserting connector again.
minutes. (The unit returns to normal failure of thermistor wiring. 4 Check pipe <liquid> temperature with remote
operation, if it has normally reset.) 4 Defective refrigerant circuit is controller in test run mode. If pipe <liquid>
2 Constantly detected during cooling, causing thermistor temperature temperature is exclusively low (in cooling
P2 drying, and heating (except defrosting) of 90: or more or -40: or mode) or high (in heating mode), refrigerant
operation. less. circuit may have defective.
Short: 90: or more 5 Defective indoor controller board. 5 Check pipe <liquid> temperature with remote
Open: -40: or less controller in test run mode. If there is exclusive
difference with actual pipe <liquid> temperature,
replace indoor controller board.

Turn the power off, and on again to operate


after check.

Abnormality of drain sensor (DS) 1 Defective thermistor 1–3 Check resistance value of thermistor.
1 Suspensive abnormality, if short/open of characteristics 0: ······6.0k"
thermistor is detected for 30 seconds 2 Contact failure of connector 10: ····3.9k"
continuously. (CN31) on the indoor controller 20: ····2.6k"
Turn off compressor and indoor fan. board. (Insert failure). 30: ····1.8k"
2 Short/open is detected for 30 seconds 3 Breaking of wire or contact 40: ····1.3k"
continuously during suspensive
failure of drain sensor wiring. 2 Check contact failure of connector (CN31) on
abnormality.
(The unit returns to normal operation, 4 Defective indoor controller board. the indoor controller board. Refer to page 45.
if it has normally reset.) Turn the power on again and check restart
P4
3 Detect the following condition. after inserting connector again.
• During cooling and drying operation. 4 Replace indoor controller board if drain
• In case that pipe <liquid> temperature pump operates with the line of drain sensor
- room temperature <-10deg connector CN31-1 and 2 is short-circuited,
(Except defrosting) and abnormality reappears.
• When pipe <liquid> temperature or
room temperature is short/open Turn the power off, and on again to operate
temperature. after check.
• During drain pomp operation.
Malfunction of drain pump (DP) 1 Malfunction of drain pump 1 Check if drain-up machine works.
1 Suspensive abnormality, if thermistor 2 Defective drain 2 Check drain function.
of drain sensor is let heat itself and Clogged drain pump 3 Check the setting of lead wire of drain sensor
temperature rises slightly. Turn off Clogged drain pipe and check clogs of the filter.
compressor and indoor fan. 3 Attached drop of water at the 4 Replace indoor controller board if drain
2 Drain pomp is abnormal if the condition drain sensor pump operates with the line of drain sensor
P5 connector CN31-1 and 2 is short-circuited
above is detected during suspensive • Drops of drain trickles from
abnormality. lead wire. and abnormality reappears.
Refer to page 45.
3 Constantly detected during drain pomp • Clogged filter is causing
operation. wave of drain.
Turn the power off, and on again to operate
4 Defective indoor controller board. after check.

39
OC301-A--2.qxp 04.4.28 11:16 AM Page 40

Error Code Meaning of error code and detection method Cause Countermeasure
Freezing/overheating protection is (Cooling or drying mode) (Cooling or drying mode)
working 1 Clogged filter (reduced airflow) 1 Check clogs of the filter.
1 Freezing protection (Cooling mode) 2 Short cycle of air path 2 Remove shields.
The unit is in six-minute resume prevention 3 Low-load (low temperature)
mode if pipe <liquid or condenser/evap- operation beyond the tolerance
orator> temperature stays under range
-15: for three minutes, three minutes
after the compressor started. Abnormal 4 Defective indoor fan motor 4 Measure the resistance of fan motor's winding.
if it stays under -15: for three minutes • Fan motor is defective. Measure the output voltage of fan's connector
again within 16 minutes after six-minute • Indoor controller board is (FAN) on the indoor controller board.
resume prevention mode. defective. WThe indoor controller board should be
2 Frost abnormality (Only for the combination normal when voltage of AC 220~240V is
with inverter-type outdoor unit) detected while fan motor is connected.
Suspensive abnormal if unit operates in Refer to page 45.
frost prevention mode (below) for 9 5 Overcharge of refrigerant 56 Check operating condition of refrigerant
minutes or more. After that, when frost 6 Defective refrigerant circuit circuit.
prevention mode is released and (clogs)
compressor restarts its operation, unit is
not detected as abnormal if compressor
keeps operating for 20 minutes continuously
and abnormal if compressor stops
operating within 20 minutes and unit (Heating mode) (Heating mode)
operates in frost prevention mode for 1 Clogged filter (reduced airflow) 1 Check clogs of the filter.
P6 more than 9 minutes again. (Not abnormal 2 Short cycle of air path 2 Remove shields.
if unit stops operating in frost prevention 3 Over-load (high temperature)
mode within 9 minutes) operation beyond the tolerance
<Frost prevention mode> range
If pipe <liquid or condenser-evaporator> 4 Defective indoor fan motor 4 Measure the resistance of fan motor's
temperature is 2: or below when 16 • Fan motor is defective. winding.
minutes has passed after compressor • Indoor controller board is Measure the output voltage of fan's connector
starts operating, unit will start operating defective. (FAN) on the indoor controller board.
in frost prevention mode which stops
WThe indoor controller board should be
compressor operation. After that, when
pipe <liquid or condenser/evaporator> normal when voltage of AC 220~240V is
temperature stays 10: or more for 3 detected while fan motor is connected.
minutes, frost prevention mode will be Refer to page 45.
released and compressor will restart its 5 Overcharge of refrigerant 5~7Check operating condition of refrigerant
operation. 6 Defective refrigerant circuit circuit.
3 Overheating protection (Heating mode) (clogs)
The units is in six-minute resume 7 Bypass circuit of outdoor unit
prevention mode if pipe <condenser / is defective.
evaporator> temperature is detected as
over 74: after the compressor started.
Abnormal if the temperature of over
74: is detected again within 10 minutes
after six-minute resume prevention
mode.

Abnormality of pipe temperature 1 Slight temperature difference 1~4 Check pipe <liquid or condenser /
<Cooling mode> between indoor room evaporator> temperature with room
Detected as abnormal when the pipe tem- temperature and pipe <liquid temperature display on remote
perature is not in the cooling range 3 min- or condenser / evaporator> controller and outdoor controller circuit
utes later of compressor start and 6 min- temperature thermistor board.
utes later of the liquid or condenser/evapo- • Shortage of refrigerant Pipe <liquid or condenser / evaporator>
rator pipe is out of cooling range. • Disconnected holder of pipe temperature display is indicated by
Note 1) It takes at least 9 min. to detect. <liquid or condenser / setting SW2 of outdoor controller circuit
Note 2) Abnormality P8 is not detected in evaporator> thermistor board as follows.
drying mode. • Defective refrigerant circuit

)
Conduct temperature check with outdoor
Cooling range : Indoor pipe temperature
(TH2 or TH5) – intake temperature
(TH1) [ -3 deg
2 Converse connection of
extension pipe (on plural units
connection)
( controller circuit board after connecting
‘A-Control Service Tool(PAC-SK52ST)’.
Temperature display of indoor condenser/
TH: Lower temperature between: liquid 3 Converse wiring of indoor/ Temperature display of indoor liquid pipe
Indoor 1 evaporator pipe Indoor 1
pipe temperature and condenser/ outdoor unit connecting wire 1 2 3 4 5 6 1 2 3 4 5 6
evaporator temperature (on plural units connection) ON ON

P8 4 Defective detection of indoor OFF OFF

<Heating mode> room temperature and pipe Temperature display of indoor condenser/
Temperature display of indoor liquid pipe
When 10 seconds have passed after the <condenser / evaporator> Indoor 2 evaporator pipe Indoor 2

compressor starts operation and the hot temperature thermistor 1 2 3 4 5 6 1 2 3 4 5 6


ON ON
adjustment mode has finished, the unit is 5 Stop valve is not opened
OFF OFF
detected as abnormal when completely.
condenser/evaporator pipe temperature is A-Control Service Tool SW2 setting
not in heating range within 20 minutes.
23Check converse connection of extension
Note 3) It takes at least 27 minutes to pipe or converse wiring of indoor/outdoor
detect abnormality. unit connecting wire.
Note 4) It excludes the period of defrosting
(Detection restarts when defrosting
mode is over)
Heating range : 3 deg [ (Condenser/
Evaporator temperature(TH5) –
intake temperature(TH1))

40
OC301-A--2.qxp 04.4.28 11:16 AM Page 41

Error Code Meaning of error code and detection method Cause Countermeasure
Abnormality of pipe temperature ther- 1 Defective thermistor 1–3 Check resistance value of thermistor.
mistor / Condenser-Evaporator (TH5) characteristics For characteristics, refer to (P1) above.
1 The unit is in three-minute resume pro- 2 Contact failure of connector 2 Check contact failure of connector (CN29)
tection mode if short/open of thermistor (CN29) on the indoor controller on the indoor controller board.
is detected. Abnormal if the unit does board. (Insert failure) Refer to page 45.
not get back to normal within three min- 3 Breaking of wire or contact Turn the power on and check restart after
utes. (The unit returns to normal opera- inserting connector again.
failure of thermistor wiring. 4 Operate in test run mode and check pipe
tion, if it has normally reset.) 4 Temperature of thermistor is <condenser / evaporator> temperature with
2 Constantly detected during cooling, dry- 90: or more or -40: or less outdoor controller circuit board. If pipe
ing, and heating operation (except caused by defective refrigerant <condenser / evaporator> temperature is
defrosting) circuit. exclusively low (in cooling mode) or high (in
Short: 90: or more 5 Defective indoor controller heating mode), refrigerant circuit may have
Open: -40: or less board. defective.
5 Operate in test run mode and check pipe
<condenser / evaporator> temperature with
P9 outdoor control circuit board. If there is
exclusive difference with actual pipe
<condenser / evaporator> temperature
replace indoor controller board.
There is no abnormality if none of above
comes within the unit.
Turn the power off and on again to operate.
In case of checking pipe temperature

(
with outdoor controller circuit board,
be sure to connect A-control service
tool (PAC-SK52ST).
Temperature display of indoor condenser/
)
Temperature display of indoor condenser/
evaporator pipe Indoor 1 evaporator pipe Indoor 2
1 2 3 4 5 6 1 2 3 4 5 6
ON ON

OFF OFF

A-Control Service Tool SW2 setting

Remote controller signal receiving error 1 Contact failure at transmission 1 Check disconnection or looseness of indoor
1 Abnormal if indoor controller board can wire of remote controller unit or transmission wire of remote controller.
not receive normally any data from 2 All remote controllers are set 2 Set one of the remote controllers “main”.
remote controller or from other indoor as “sub” remote controller. In If there is no problem with the action above.
controller board for three minutes. this case, E0 is displayed on 3 Diagnose remote controllers.
a) When “RC OK” is displayed,
2 Indoor control board cannot receive any remote controller, and E4 is Remote controllers have no problem.
signal from remote controller for two displayed at LED (LED1, LED2) Put the power off, and on again to check.
minutes. on the outdoor controller circuit If abnormality generates again, replace
E4 board. indoor controller board.
3 Defective transmitting receiving b) When “RC NG” is displayed,
circuit of remote controller Replace remote controller.
4 Defective transmitting receiving c) When “RC E3” is displayed,
d) When “ERC 00-06” is displayed,
circuit of indoor controller board.
[ c),d)➜Noise may be causing abnormality. ]
5 Noise has entered into the ✽ If the unit is not normal after replacing
transmission wire of remote indoor controller board in group control,
controller. indoor controller board of address “0”
may be abnormal.
Remote controller transmitting error 1 Defective transmitting receiving 12 Turn the power off, and on again to
1 Abnormal if indoor controller board cannot circuit of indoor controller board. check. If abnormality generates again,
E5 check the blank of transmission path for 2 Noise has entered into the replace indoor controller board.
three minutes. transmittion wire of remote
2 Abnormal if indoor controller board cannot
finish transmitting 30 times consecutively. controller.
Indoor/outdoor unit communication 1 Contact failure, short circuit or, ✽ Check LED display on the outdoor control
error (Signal receiving error) mis-wiring (converse wiring) of circuit board. (Connect A-control service tool,
1 Abnormal if indoor controller board indoor/outdoor unit connecting PAC-SK52ST.)
cannot receive any signal normally for wire Refer to EA-EC item if LED displays EA-EC.
six minutes after putting the power on. 1 Check disconnection or looseness of indoor/
2 Abnormal if indoor controller board 2 Defective transmitting receiving outdoor unit connecting wire of indoor unit or
cannot receive any signal normally for circuit of indoor controller board outdoor unit.
three minutes. 3 Defective transmitting receiving Check all the units in case of twin triple
E6 3 Consider the unit abnormal under the circuit of indoor controller board indoor unit system.
following condition: When two or more 4 Noise has entered into indoor/ 2-4 Turn the power off, and on again to
indoor units are connected to one outdoor unit connecting wire. check. If abnormality generates again,
outdoor unit, indoor controller board replace indoor controller board or outdoor
cannot receive a signal for three minutes controller circuit board.
from outdoor controller circuit board, a ✽ Other indoor controller board may have
signal which allows outdoor controller defective in case of twin triple indoor unit
circuit board to transmit signals. system.
Indoor/outdoor unit communication 1 Defective transmitting receiving 1-3 Turn the power off, and on again to
error (Transmitting error) circuit of indoor controller board check. If abnormality generates again,
Abnormal if “1” receiving is detected 30 2 Noise has entered into power replace indoor controller board.
E7
times continuously though indoor controller supply.
board has transmitted “0”. 3 Noise has entered into outdoor
control wire.

41
OC301-A--2.qxp 04.4.28 11:16 AM Page 42

9-4. TROUBLESHOOTING BY INFERIOR PHENOMENA


Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Phenomena Cause Countermeasure
(1)LED2 on indoor controller board • When LED1 on indoor controller board is also off.
is off. 1 Power supply of 220~240V is not supplied to outdoor 1 Check the voltage of outdoor power
unit. supply terminal block (L, N)
• When AC 220~240V is not detected.
Check the power wiring to outdoor unit
and the breaker.
• When AC 220~240V is detected.
—Check 2 (below).
2 Defective outdoor controller circuit board. 2 Check the voltage between outdoor
terminal block S1 and S2.
• When AC 220~240V is not detected.
Check the fuse on outdoor controller
circuit board (10A).
Check the wiring connection.
• When AC 220~240V is detected.
—Check 3 (below).
3 Power supply of 220~240V is not supplied to indoor 3 Check the voltage between indoor terminal
unit. block S1 and S2.
• When AC 220~240V is not detected.
Check indoor/outdoor unit connecting
wire for mis-wiring.
• When AC 220~240V is detected.
—Check 4 (below).
4 Defective indoor power board. 4 Check voltage output from CN2S on indoor
power board (DC14V). Refer to page 46.
• When no voltage is output.
Check the fuse on indoor power board.
Check the wiring connection.
• When output voltage is between 12V
and 16V.
—Check 5 (below).
5 Defective indoor controller board. 5 Check the wiring connection between
indoor controller board and indoor power
board. If no problems are found, indoor
controller board is defective.

• When LED1 on indoor controller board is lit.


1 Mis-setting of refrigerant address for outdoor unit 1 Reconfirm the setting of refrigerant
(There is no unit corresponding to refrigerant address for outdoor unit
address “0”.) Set the refrigerant address to “0”.
(For grouping control system under
which 2 or more outdoor units are
connected, set one of the units to “0”.)
Set refrigerant address using SW1 (3-6)
on outdoor controller circuit board.
(2)LED2 on indoor controller board • When LED1 on indoor controller board is also blinking. Check indoor/outdoor unit connecting wire
is blinking. Connection failure of indoor/outdoor unit connecting for connection failure. Check the connection
wire of remote controller wires in case of twin
• When LED1 is lit. triple indoor unit system. When 2 or more
Mis-wiring of remote controller wires indoor units are wired in one refrigerant
Under twin triple indoor unit system, 2 or more indoor system, connect remote controller wires to
units are wired together. one of those units.
1 Refrigerant address for outdoor unit is wrong or not 1 Check the setting of refrigerant address
set. in case of grouping control system.
Under grouping control system, there are some units If there are some units whose refrigerant
whose refrigerant address is 0. addresses are 0 in one group, set one of
the units to 0 using SW1 (3-6) on outdoor
controller circuit board.
2 Short-cut of remote controller wires 23 Remove remote controller wires and
3 Defective remote controller check LED2 on indoor controller board.
• When LED2 is blinking, check the
short-cut of remote controller wires.
• When LED2 is lit, connect remote
controller wires again and:
if LED2 is blinking, remote controller
is defective; if LED2 is lit, connection
failure of remote controller terminal
block etc. has returned to normal.
(3)Upward/downward vane 1 The vane is not downward during defrosting and 1 Normal operation (The vane is set to hor-
performance failure heat preparation and when the thermostat is OFF in izontal regardless of remote control.)
HEAT mode. (Working of COOL protection function) 2 Check 2 (left).
2 Vane motor does not rotate. • Check the vane motor. (Refer to “How
• Defective vane motor to check the parts”.)
• Breaking of wire or connection failure of connector • Check for breaking of wire or connec-
tion failure of connector.
3 Upward/downward vane does not work. 3 Normal operation (Each connector on
• The vane is set to fixed position. vane motor side is disconnected.)

42
OC301-A--2.qxp 04.4.28 11:16 AM Page 43

9-5. EMERGENCY OPERATION


9-5-1. When wireless remote controller troubles or its battery is exhausted
1. Emergency operation is available in such a case using emergency operation switch equipped next to the receiver of indoor
unit.
2. To start operation
• Cooling Operation·······Press (Cooling) switch.

• Heating Operation·······Press (Heating) switch.


wWhen the unit starts operating, the power lamp is lit.

Emergency switch(Cool)
Emergency switch(Heat)

ON STAND
COOL HEAT
OFF BY

Receiving Defrosting • Initial heating lamp


section
Power lamp

wEmergency operation will be performed as follows.


Mode Cooling Heating
Set temperature 24: 24:
Fan speed High High
Airflow direction Horizontal (30deg) Downward (70deg)

3. To stop operation
• Press either emergency operation switch (cooling/heating).

9-5-2. When wired remote controller or indoor unit micro computer troubles
1. If there is not any other wrong when trouble occures, emergency operation starts as the indoor controller board switch
(SWE) is set to ON.
During the emergency operation the indoor unit is as follows;
(1) Indoor fan high speed operation (2) Drain-up machine operation

2. When emergency operating for COOL or HEAT, setting of the switch (SWE) in the indoor controller board and outdoor unit
emergency operation are necessary.

3. Check items and notices as the emergency operation


(1) Emergency operation cannot be used as follows;
• When the outdoor unit is something wrong.
• When the indoor fan is something wrong.
• When drain over flow protected operation is detected during self-diagnosis. (Error code : P5)
(2) Emergency operation will be serial operation by the power supply ON/OFF.
ON/OFF or temperature, etc. adjustment is not operated by the remote controller.
(3) Do not operate for a long time as cold air is blown when the outdoor unit starts defrosting operation during heat emer-
gency operation.
(4) Cool emergency operation must be within 10 hours at most. It may cause heat exchanger frosting in the indoor unit.
(5) After completing the emergency operation, return the switch setting, etc. in former state.
(6) Since vane does not work at emergency operation, position the vane manually and slowly.

43
OC301-A--2.qxp 04.4.28 11:16 AM Page 44

9-6. How to check the parts


PKA-RP2.5FAL
PKA-RP3FAL
PKA-RP4FAL
Parts name Check points
Room temperature Disconnect the connector then measure the resistance using a tester.
thermistor (TH1) (Surrounding temperature 10:~30:)
Pipe temperature
thermistor/liquid(TH2)
Normal Abnormal
Condenser/evaporator
temperature thermistor 4.3k"~9.6k" Open or short
(TH5)
Fan motor (MF) Measure the resistance between the terminals using a tester.
Relay connector (Winding temperature 20:)
1 Red Normal
1 Motor terminal
2 White
2 or RP2.5 Abnormal
Relay connector RP4
3 Black
3
RP3
Red–Black 99.5" 62.6"
Open or short
Protector White–Black
OPEN : 130i 5: 103.9" 74.0"
CLOSE : 80i 20:

Vane motor (MV) Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:~30:)
4 Orange
Normal
5 Red M Connector Abnormal
RP2.5, RP3, RP4
2 Pink
Brown–Yellow
Yellow Brown Blue
Brown–Blue
186~214" Open or short
3 6 1 Red–Orange
Red–Pink

<Thermistor Characteristic graph> < Thermistor for lower temperature >


50
Thermistor for •Room temperature thermistor(TH1)
lower temperature •Pipe temperature thermistor/liquid(TH2)
•Condenser/evaporator temperature 40
thermistor(TH5)
Resistance (K")

Thermistor R0=15kΩ ± 3% 30
Fixed number of B=3480K ± 2%
1 1
Rt=15exp { 3480( )} 20
273+t 273
0: 15kΩ
10: 9.6kΩ 10
20: 6.3kΩ
25: 5.4kΩ
30: 4.3kΩ 0
40: 3.0kΩ -20 -10 0 10 20 30 40 50
Temperature (:)

44
OC301-A--2.qxp 04.4.28 11:16 AM Page 45

9-7. TEST POINT DIAGRAM


9-7-1. Indoor controller board
PKA-RP2.5FAL
PKA-RP3FAL
PKA-RP4FAL

CN22
CN90 CN2D Connect to the terminal block(TB5)
CN32 Connect to the wireless Connect to the indoor (Remote controller connecting wire)
CN6V Connector remote controller board power board (CN2S) (10~16V DC)
Vane motor output (Remote switch) (CNB) 12~16V DC

}
(MV)

}
– +
+ –
LED1 CN21
Power supply (I.B) Pipe temperature
thermistor/Liquid (TH2)
LED2 CN20
Power supply (R.B) Room temperature
thermistor (TH1)
LED3
Transmission
(Indoor/outdoor) CN2L
Connector (LOSSNAY)

CN41
Connector (HA terminal-A)

CN31
Drain sensor (DS)
CN29
Condenser/evaporator
CN03 } + temperature thermistor (TH5)
Connect to the indoor
power board (CN02) –
Between 1 to 3 220~240V AC
Between 3 to 5 0~24V DC
(Indoor/outdoor transmission) +
– } CN25
Humidifier output
(12~16V DC)

+
– } CN27
Drain-up machine
output (DP)
(12~16V DC)

Jumper wire J41, J42


Pair number setting with
wireless remote controller

Jumper wire J11~J15


Model setting

Jumper wire J21~J24


Capacity setting

SWE
Emergency operation
FAN
Fan motor output (MF)
Between 1 to 5 100~240V AC

45
OC301-A--2.qxp 04.4.28 11:16 AM Page 46

9-7-2. Indoor power board


CN2S
PKA-RP2.5FAL Connect to the indoor controller

PKA-RP3FAL
PKA-RP4FAL + } board (CN2D)
(12~16V DC)

CN02
Connect to the indoor
controller board (CN03) +
}
Between 1 and 2 0~24V DC

(Indoor/Outdoor transmission)
Between 2 and 3 220~240V AC

+ – Fuse 4A/250V
}

CN01
Connect to the Terminal Block (TB4)
(Indoor/outdoor connecting line)
Between 1 and 2 220~240V AC
Between 2 and 3 0~24V DC
(Indoor/outdoor transmission)

9-8. FUNCTIONS OF JUMPER WIRE


Each function is controlled by the jumper wire on control p.c. board. For service parts, J11- J15 and J21-J24, DIP switches
(SW1 and SW2) are equipped with jumper wire.
(Marks in the table below) Jumper wire ( : Short : Open)
DIP switch ( : ON : OFF)
Jumper wire Functions Open/short of jumper wire Remarks

Models : PKA-RP2.5, RP3, RP4


J11~J15 Model J11 J12 J13 J14 J15
(SW1) settings Heater-less

Models J21 J22 J23 J24


J21~J24 Capacity RP2.5
(SW2) settings RP3
RP4

<Settings at time of factory shipment>


Wireless remote controller: 0
Wireless remote Control PCB setting Control PCB: (for both J41 and J42)
Pair number controller setting J41 J42
setting with Four pair number settings are supported.
J41 0
wireless The pair number settings of the wireless remote
J42 1
remote controller and indoor control PCB (J41/J42) are
2
controller given in the table on the left.
3~9
(' ' in the table indicates the jumper line is disco-
nnected.)

46
OC301-A--2.qxp 04.4.28 11:16 AM Page 47

10 DISASSEMBLY PROCEDURE

PKA-RP3FAL
OPERATING PROCEDURE PHOTOS & ILLUSTRATION
1. Removing the lower side of the indoor unit from the
installation plate Figure 1
(1) Remove the 2 screws.
Hang the indoor unit hangers to the catches on the
installation plate.

Hanger of indoor unit

Catch of installation plate

Metal fixture

Screws

2. Removing the right side panel Figure 2


(1) Remove the 2 screws of the right side panel:one on the Connector
bottom and the other on the upper right-hand side. Indoor controller
(2) Disconnect the connector from the adapter case. board
(3) Sliding the right side panel to the right, pull it out toward
you. Right side panel

Terminal cover
Connector

Electrical parts box cover

3. Removing the indoor controller board Electrical parts


Photo 1 Indoor controller
(1) Remove the right side panel. box cover
board
(2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Disconnect the connectors on the indoor controller board.
(4) To unhook the catches on the right-hand side of the indoor
controller board, pull the left-hand side toward you and lift
up the cover to the right. Then the indoor controller board Catches
can be removed.

4. Removing the electrical parts box Photo 2 Room temperature thermistor


(1) Remove the right side panel. Condenser / evaporator
(2) Remove the screw of the electrical parts box cover, temperature thermistor
and remove the cover.
(3) Remove the room temperature thermistor and the
condenser / evaporator temperature thermistor.
(4) Disconnect the vane motor connector on the indoor
controller board. Screws
(5) Remove the 2 screws of the electrical parts box.
(6) Disconnect the connector of the heater lead wire
connector.
(7) Disconnect the connector of the fan motor lead wire.
(8) Remove the electrical parts box. Electrical parts
box

47
OC301-A--2.qxp 04.4.28 11:16 AM Page 48

OPERATING PROCEDURE PHOTOS & ILLUSTRATION


(9) Remove the screws of the indoor controller board case,
and pull out the indoor controller board case. Photo 3 Relay
Then the indoor power board, the capacitor and the relay
can be serviced.
Indoor
Capacitor power board

Indoor controller
board case Electrical parts box

5. Removing the vane motor


(1) Remove the right side panel. Photo 4 Screws
(2) Remove the screw of the electrical parts box cover,
and remove the cover.
(3) Remove the 2 screws of the vane motor, and remove
the motor from the shaft.
(4) Disconnect the vane motor connector on the indoor
controller board.

Vane motor

Indoor controller board

6 Removing the intake grilles


(1) Remove the right side panel. Figure 3
(2) To remove the left side panel, remove the screw on the Catch on the left side panel
bottom and the screw on the upper left-hand side. (See
Figure 3.) Catch on
1. Press up this side of the left side panel to unhook the the unit
catch on the panel from the catch on the unit.
2. Slide the left side panel to the left to remove the panel.
Note: Fix the unit to the metal fixture securely
(3) Remove the air filters.
(4) Hold and press the centre cover to remove. Photo 5
(5) Remove the screws of the grilles.
Left side panel Slide to the
(6) Pull the lower side of the grille toward you and slide the Grilles
right
upper to the right to remove the grilles.

Screws for grills

7. Removing the drain pan


(1) Remove the left and right side panels. Photo 6 Drain hose
Drain pan
(2) Remove the grilles. band
(3) Remove the electrical parts box cover.
(4) Loosen the drain hose band to remove.
(5) Remove the 3 screws of the drain pan, and slide the drain
pan toward you to remove.

Screws
Drain hose

48
OC301-A--2.qxp 04.4.28 11:16 AM Page 49

OPERATING PROCEDURE PHOTOS


8. Removing the line flow fan and the fan motor
(1) Remove the left and right side panels. Photo 7
(2) Remove the grilles.
(3) Remove the electrical parts box. Screw
(4) Remove the drain pan. Line flow fan
(5) Loosen the screw that fixes the line flow fan to the fan Fan motor
motor. (See Photo 7. )
(6) Remove the 4 screws of the motor fixture, and remove the
fan motor and the motor fixture at a time (See Photo 8.)
(7) Remove the screws of the left and right motor supports,
and remove the motor supports and the fan motor. (See
Photo 9.)
(8) Remove the 2 screws on the left and right sides of the heat
exchanger, and pull the bearing support toward you. (See
Photo 11.)
(9) Remove the screw of the centre support, and remove the Photo 8
support. (See Photo 10. )
(10) Pull the left-hand side of the heat exchanger toward you, Screws
and remove the line flow fan. Fan motor

Motor fixture

Photo 9
Fan motor
Screw
Screw

Motor support

Motor
support

Photo 10
Line flow fans

Centre support Screw

Photo 11

Bearing support

Lineflow fan

49
OC301-A--2.qxp 04.4.28 11:16 AM Page 50

11 PARTS LIST

STRUCTURAL PARTS
PKA-RP2.5FAL
PKA-RP3FAL 12 11

1 13

10 9 8

5 7

4
6

Part numbers that is circled is not shown in the figure.


,
Q ty/set
Remarks Wiring Recom- Price
No. Part No. Part Name Specifications PKA- Diagram mended
,
(Drawing No.) Symbol Q ty
RP2.5FAL RP3FAL Unit Amount
1 R01 12G 662 LEFT SIDE PANEL 1 1
2 R01 E01 812 UNDER PLATE 1 1
3 R01 E00 811 NOSE 1 1
4 R01 A17 500 AIR FILTER 4 4
5 R01 12G 691 INTAKE GRILLE 2 2
6 R01 24K 658 RECEIVER 1 1 RU
7 T7W E05 661 RIGHT SIDE PANEL 1 1
8 R01 E00 075 WIRELESS REMOTE CONTROLLER HOLDER 1 1
9 R01 E01 049 WIRELESS REMOTE CONTROLLER DOOR 1 1
10 T7W E06 714 WIRELESS REMOTE CONTROLLER 1 1
11 R01 12G 808 BACK PLATE 1 1
R01 E01 641 TOP PLATE 1
12
R01 E00 641 TOP PLATE 1
13 — BOX ASSEMBLY 1 1 (RG00A734GE9)
14 R01 12G 523 DRAIN SOKET 1 1

50
OC301-A--2.qxp 04.4.28 11:16 AM Page 51

STRUCTURAL PARTS
PKA-RP4FAL
12 11

1 13

14 10 9 8

4
6

Part numbers that is circled is not shown in the figure.


, Wiring Recom-
Q ty/set Remarks Price
No. Part No. Part Name Specification (Drawing No.)
Diagram mended
,
PKA-RP4FAL Symbol Q ty Unit Amount
1 R01 12G 662 LEFT SIDE PANEL 1
2 R01 E00 812 UNDER PLATE 1
3 R01 E01 811 NOSE 1
4 R01 A17 500 AIR FILTER 5
5 R01 12G 691 INTAKE GRILLE 2
6 R01 24K 658 RECEIVER 1 RU
7 T7W E05 661 RIGHT SIDE PANEL 1
8 R01 E00 075 WIRELESS REMOTE CONTROLLER HOLDER 1
9 R01 E01 049 WIRELESS REMOTE CONTROLLER DOOR 1
10 T7W E06 714 WIRELESS REMOTE CONTROLLER 1
11 R01 16G 808 BACK PLATE 1
12 T7W E00 641 TOP PLATE 1
13 — BOX ASSEMBLY 1 (RG00A734GF0)
14 R01 16G 692 INTAKE GRILLE 1
15 R01 12G 523 DRAIN SOKET 1

51
OC301-A--2.qxp 04.4.28 11:16 AM Page 52

ELECTRICAL PARTS
PKA-RP2.5FAL
PKA-RP3FAL 35
1
34

2 31
30 32
33
3

29
5 28
25
27

6
26 24

7 19
8
23 20 18

17
9 22 21

10 11 12 13 14 15 16

,
Q ty/set
Remarks Wiring Recom- Price
No. Part No. Part Name Specification PKA-
(Drawing No.) Diagram mended
,
Symbol Q ty
RP2.5FAL RP3FAL Unit Amount
1 R01 Z61 102 BEARING MOUNT 1 1
2 R01 13G 114 LEFT LINEFLOW FAN 1 1
R01 E61 480 HEAT EXCHANGER 1
3
R01 E62 480 HEAT EXCHANGER 1
4 T7W E13 529 DRAIN PAN 1 1
5 — GUIDE VANE 16 16 (BG25J821H01)
6 — ARM 3 3 (BG25H301H02)
7 R01 12G 621 CENTER COVER 1 1
8 R01 12G 063 JOINT SHAFT 1 1
9 R01 12G 002 AUTO VANE 2 2
10 R01 KV5 527 DRAIN HOSE 1 1
11 T7W E13 223 VANE MOTOR 1 1 MV
12 R01 50J 317 WIRELESS REMOTE CONTROLLER BOARD 1 1 W.B
13 — TERMINAL COVER 1 1 (BG02J608H07)
14 R01 588 255 CAPACITOR (FAN MOTOR) 2.0µF 440V 1 1 C
15 T7W E33 310 INDOOR CONTROLLER BOARD 1 1 I.B
16 T7W E00 239 FUSE 250V 4A 1 1 F1
17 — CONTROLLER COVER 1 1 (BG02A648G02)

Continued to the next page.

52
OC301-A--2.qxp 04.4.28 11:16 AM Page 53

From the previous page.

,
Q ty/set
Remarks Wiring Recom- Price
No. Part No. Part Name Specification PKA- Diagram mended
(Drawing No.) Symbol Q ty
,
RP2.5FAL RP3FAL Unit Amount
18 — CONTROLLER CASE 1 (BG25B573H06)
19 T7W E00 313 INDOOR POWER BOARD 1 P.B
20 T7W E13 716 TERMINAL BLOCK 3P(S1, S2, S3) 1 TB4
21 T7W E12 202 ROOM TEMPERATURE THERMISTOR 1 TH1
CONDENSER /
22 R01 E34 202 1 TH5
EVAPORATOR TEMPERATURE THERMISTOR
23 T7W E11 202 PIPE TEMPERATURE THERMISTOR 1 TH2
24 — MOTOR BAND 1 (BG02H065H01)
25 R01 12G 220 FAN MOTOR PN4S40-K 1 MF
26 R01 12G 105 RUBBER MOUNT 2
27 — MOTOR BAND 1 (BG02H178H01)
28 R01 13G 115 RIGHT LINEFLOW FAN 1
29 — CENTER SUPPORT 1 (BG00R259G07)
30 — BEARING BAND 1 (BG02L462H02)
31 R01 KV5 102 BEARING MOUNT 1
32 R01 12G 103 SLEEVE BEARING 1
33 — MOTOR LEG 1 (BG02A534H16)
34 T7W B02 675 FAN GUARD 2
35 R01 005 103 SLEEVE BEARING 1

53
OC301-A--2.qxp 04.4.28 11:16 AM Page 54

ELECTRICAL PARTS
PKA-RP4FAL
36
1
35

2 32
31 33
34
3

30
5 29
26
28

6
24 27 25

7 19
8
23 20 18

17
9 22 21

10 11 12 13 14 15 16

,
Q ty/set Remarks Wiring Recom- Price
No. Part No. Part Name Specification (Drawing No.) Diagram mended
,
PKA-RP4FAL Symbol Q ty Unit Amount
1 R01 Z61 102 BEARING MOUNT 1
2 R01 17G 114 LEFT LINEFLOW FAN 1
3 T7W E99 480 HEAT EXCHANGER 1
4 T7W E14 529 DRAIN PAN 1
5 — GUIDE VANE 22 (BG25J821H01)
6 — ARM 4 (BG25H301H02)
7 R01 12G 621 CENTER COVER 1
8 R01 12G 063 JOINT SHAFT 1
9 R01 16G 002 AUTO VANE 2
10 R01 KV5 527 DRAIN HOSE 1
11 T7W E13 223 VANE MOTOR 1 MV
12 R01 50J 317 WIRELESS REMOTE CONTROLLER BOARD 1 W.B
13 — TERMINAL COVER 1 (BG02J608H07)
14 R01 576 255 CAPACITOR (FAN MOTOR) 3.0µF 440V 1 C
15 T7W E33 310 INDOOR CONTROLLER BOARD 1 I.B
16 T7W E00 239 FUSE 250V 4A 1 F1
17 — CONTROLLER COVER 1 (BG02A648G02)

Continued to the next page.

54
OC301-A--2.qxp 04.4.28 11:16 AM Page 55

From the previous page.

,
Q ty/set Remarks Wiring Recom- Price
No. Part No. Part Name Specification Diagram mended
,
PKA-RP4FAL (Drawing No.) Symbol Q ty Unit Amount
18 — CONTROLLER CASE 1 (BG25B573H06)
19 T7W E00 313 INDOOR POWER BOARD 1 P.B
20 T7W E13 716 TERMINAL BLOCK 3P(S1, S2, S3) 1 TB4
21 T7W E12 202 ROOM TEMPERATURE THERMISTOR 1 TH1
CONDENSER /
22 R01 E34 202 1 TH5
EVAPORATOR TEMPERATURE THERMISTOR
23 T7W E11 202 PIPE TEMPERATURE THERMISTOR 1 TH2
24 T7W E00 457 FLARE NUT 5/8 1
25 — MOTOR BAND 1 (BG02H065H01)
26 T7W 571 762 FAN MOTOR PN4S70-K 1 MF
27 R01 16G 105 RUBBER MOUNT 2
28 — MOTOR BAND 1 (BG02H178H01)
29 R01 17G 115 RIGHT LINEFLOW FAN 1
30 — CENTER SUPPORT 1 (BG00R259G07)
31 — BEARING BAND 1 (BG02L462H02)
32 R01 KV5 102 BEARING MOUNT 1
33 R01 12G 103 SLEEVE BEARING 1
34 — MOTOR LEG 1 (BG02A534H17)
35 T7W B03 675 FAN GUARD 2
36 R01 005 103 SLEEVE BEARING 1

55
OC301-A--2.qxp 04.4.28 11:16 AM Page 56

12 OPTIONAL PARTS

12-1. WIRED REMOTE CONTROLLER


Part No. PAR-20MAAT-E

12-2. PROGRAM TIMER


Part No. PAC-SC32PTA

12-3. REMOTE SENSOR


Part No. PAC-SC41TS-E

12-4. REMOTE OPERATION ADAPTER


Part No. PAC-SF40RM-E

12-5. REMOTE ON/OFF ADAPTER


Part No. PAC-SE55RA-E

12-6. DRAIN LIFT UP MECHANISM


Part No. PAC-SE88DM-E

HEAD OFFICE : MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU TOKYO 100-8310, JAPAN

cCopyright 2004 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD New publication, effective May 2004
Distributed in May 2004. No.OC301 REVISED EDITION-A PDF 9 Specifications subject to change without notice
Distributed in Jan. 2004. No.OC301 PDF 9
Made in Japan