Catalogue Dehumidifier RFB F1 D RG08 1
Catalogue Dehumidifier RFB F1 D RG08 1
2015 D-RG08
INDUSTRIAL DEHUMIDIFIERS GENERAL CATALOG
Striving to make products that move you.
INDUSTRIAL DEHUMIDIFIERS
9 models of 4 different types
meet your various applications.
The ORION Dehumidifiers
eliminate harmful moisture.
RFB3750F1
RFB500F
Contents
Features of new models • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • P.1
RFB1500F Product lines, model selection & application examples • • • • • • • • P.2
Be sure to read the contents before selection and adoption • • • P.3
Dehumidifiers of stationary type • • • • • • • • • • • • • • • • • • • • • • • • • • • • • P.5
Dehumidifiers of portable type • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • P.7
Dehumidifiers idealized to use at construction & civil works sites
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • P.9
3.6KW 5.7KW
About About
% 17 15 %
energy saving energy saving
New model New model
RFB2200F1 RFB3750F1
3.0KW 4.8KW
※ Based on 25℃,80%,60Hz
Conventional model
New model
RFB2200F1
RFB-3750-E
16.0L/h
Dehumidify Capacity
RFB-2200-E
Dehumidify Capacity
14.7L/h
8.7L/h
Dehumidify Capacity
7.6L/h
RFB3750F1
40
30
20
10 Expanded range
0
30 40 50 60 70 80 90 95 100
Relative humidity(%)
※Refer to pages 5 & 6 for the detail specifications.
1
Dehumidifier explanation 1/1
Dehumidifier
Product lines, model selection & application examples
RF
B5 60Hz
RF
RF
B7
50
00
F 50Hz Ind
RF B1 F oo
RF B2 rh
20 50
B3
0F 0F um
75 1 idi
0F ty
1 70
%
65
60 %
55 %
50 %
%
Conditions: There is not any generating source of water vapor and at 30℃ of suction air temperature and 80% of relative humidity.
Example) One RFB2200F1 can be for a room capacity of 2,100m3 at the ventilation frequency of 0.5 time per hour and 60% of
indoor humidity.
※ If conditions are out of above mentioned range or room temperature control is needed, please consult your nearest local distributor.
※ Install an air ventilator if air flow from the dehumidifier is insufficient for the room air circulation.
2
Be sure to read 1/2
The cases where the operators are liable to death or severe injury if wrongly
WARNINGS handled.
Install the Product horizontally in a place free from vibrations and sturdy enough to bear
the product weight, and surely take necessary measures to prevent it from overturning.
Improper installation may cause water leakage, or injury from overturning or a fall.
Never install the Product in a place where any combustible gases may float in the air or
leak out.
Such gases, if leaked and pooled around the Product, may cause a fire accident.
Never use this equipment in the presence of corrosive gases, such as ammonia or sulfur,
or in the purpose of drying items generated corrosive elements such as woods, sea
products or incense stick.
The corrosion of the products or the heat exchanger may cause malfunctions.
Installation
Please arrange for installation, water supply or drainage works by your dealer or other
qualified persons.
Improper installation made by those without sufficient knowledge and experience may cause water
leakage, electric shock or fire accident.
Be certain that all electrical wiring is done in accordance with relevant electrical
construction and wiring regulations, and use only prescribed cables.
Installation with an insufficient power supply or improper installation can result in electric shock or fire.
Improperly securing cables to electrical contacts can lead to electric shock, overheating or fire.
Always install and use this equipment with an earth leakage breaker.
Using the equipment without an earth leakage breaker can lead to electric shock.
Ensure that the equipment is properly grounded. (Installation of a proper ground hookup
must be performed by a qualified electrician.)
Improper grounding of this equipment can lead to electric shock.
The cases where the operators are liable to bodily injury or material damage if
CAUTION wrongly handled.
Installation
Do not sit or stand on the Product. And do not put things on the Product in operation.
Make the power voltage to the Product to be within ±10% of the rated voltage and the
interphase imbalance to be within ±3% of the rated value.
Avoid any rise of piping to drain port, which obstructs smooth draining.
Reserve sufficient space around the Product so that it can perform its capability to the
utmost extent and also to allow easy access to it for maintenance.
(Upper opening)
200
500
50 15
or more or more
or more
50
600
500
500
When side is opened
or more
500
1,000
or more
600
Features
1. Wide temperature control range from 5℃ to 40℃. ※The model with cooling function(R type).
(Our corresponding conventional models: 16 - 40℃)
2. Operating temperature and humidity display by easy operation.
Possible to check it in inspection mode, such as a corresponding conventional models.
3. Cooling/dehumidifying switching operation by remote control.
※The model with cooling function(R type).
Easy work through the front side.
4. HFC refrigerant (R410A) adoption, ZERO destruction coefficient of ozone layer
■Specifications RFB3750F1・3750F1-R
Dehumidifying only With air conditioning function Dehumidifying only With air conditioning function
Item Model
RFB2200F1 RFB2200F1-R RFB3750F1 RFB3750F1-R
Dehumidifying capacity ※1 L/h 7.6/8.7 14.0/16.0 13.7/15.6
Cooling capacity ※2 kW ー 9.0/10.0 ー 15.3/16.2
Operable temperature range (Indoor type) ℃ 1 ∼ 40
Operable temperature range (Outdoor type) ※3 ℃ ー −5∼43 ー −5∼43
Controllable temperature range ℃ ー 5 ∼ 40 ー 5 ∼ 40
Power source V Three phase 200 ± 10% 50/60Hz
Power Electric current ※1 A 9.1/9.7 13.1/15.1
specifications Power consumption ※1 kW 2.3/3.0 3.7/4.8
Power capacity kVA 4.9 5.6 7.7 8.0
Compressor kW 2.2 3.75
Condenser, Evaporator Fin and tube type
Blower W 270 400
Equipment Air capacity m3/min 30 44/52
details Refrigerant controlling method Electronic expansion valve
Refrigerant R410A
Defrosting method Hot gas
Ventilating fan Double suction multi blade type
External dimensions (H × D × W) ※ 4 mm 1750(1517) × 400 × 650 1950(1745) × 500 × 800
Product mass ※5 kg 119 124 178 183
Over current relay
Compressor
Discharge pipe thermostat (For overheat prevention), Fuse
Protecting Blower Internal thermostat, Fuse
devices Refrigerating circuit High pressure cut
Operation circuit fuse
Electric circuit
Motor circuit fuse
Operation sound level ※6 dB 54 59/68
※1 The numerical value indicated above is based on 25℃ of suction air temperature and 80% of relative humidity. The performance capacity is 90% or more of the indicated.
※2 The numerical value indicated above is based on 25℃ of suction air temperature, 80% of relative humidity and 30℃ of ambient temperature of an outdoor unit.
The performance capacity is 90% or more of the indicated.
※3 In case of use of beyond operable temperature range, it cannot operate with cooler. (It may rise in room temperature due to force dehumidifying operation.)
※4 The figures in parentheses show dimensions before a plenum chamber is attached.
※5 Not including outdoor unit.
※6 The sound level is the value measured 1 meter away from the front and 1 meter high.
・The plenum chamber shall be assembled and installed at the site.
・The electric wiring, wiring of an outdoor unit and refrigeration piping must be arranged at the site.
25℃
40 Indoor suction air dry-bulb 20 18
25℃ Indoor suction air dry-bulb 25℃ Indoor suction air dry-bulb
temperature(℃)
temperature(℃) temperature(℃)
10
18
30℃ 16 30℃
35
Dehumidifying capacity (L/h)
30℃ 20℃
16 20℃
20℃ 20℃ 14
30 8 20℃
15℃
14
20℃ 15℃ 12
35℃ 35℃
25 35℃ 15℃
15℃ 12 15℃
6 10
15℃ 10℃
20 10 10℃
10℃ 40℃
40℃ 10℃ 40℃
8 10℃
8
15 4
10℃ 6
6
10 5℃
5℃ 5℃
4
2 5℃
4 5℃
5℃
5 1℃
2 2
1℃ 1℃ 1℃
1 1℃ 1℃
0 0 0
30 40 50 60 70 80 90 100 30 40 50 60 70 80 90 100 30 40 50 60 70 80 90 100 30 40 50 60 70 80 90 100
Indoor unit suction air dry-bulb humidity(%) Indoor suction air dry-bulb humidity(%) Indoor suction air dry-bulb humidity(%) Indoor suction air dry-bulb humidity(%)
5
Dehumidifiers of stationary type 2/2
250
Control panel Control panel
340(525)
340(525)
Air inlet Air inlet
(Filter) (Filter)
φ62 hole(With bush)
1750(1950)
1750(1950)
First drain port First drain port (Both sides)
578
578
Switchboard φ62 hole(With bush) Switchboard 80
(R3/4 Male) 68 (M5) (R3/4 Male) Refrigerant liquid piping output port
(Both sides) 68 (φ9.53(φ12.7)copper piping brazing on connection part)
Earth wire connection terminal Earth wire connection terminal
(M5) 175 Refrigerant gas piping output port
Indoor/outdoor crossover
125 power supply wiring connection port 125 (φ12.7(φ15.88)copper piping brazing on connection part)
484(499)
484(499)
(φ26 Knockout hole Both sides) 70
250 (176)
19 19
400(500)
400(500)
76
205(215)
A A A A
205
150
150
98
98
Power supply wiring connection hole 123
123(150)
123(150) (φ42 Knockout hole Both sides) (150) Drain piping connection hole
Power supply wiring connection hole 660(810) 400(500)
660(810) 400(500) Drain piping connection hole Indoor/outdoor crossover (R1 Male Both sides)
(φ42 Knockout hole Both sides) link wiring connection port
(R1 Male Both sides)
(φ26 Knockout hole Both sides)
※Plenum chamber must be assembled and installed at the site. ※Plenum chamber must be assembled and installed at the site.
※Drain pipes can be connected with either the right side or left side. ※Drain pipes can be connected with either the right side or left side.
※Power wire and transit wire can be connected with either the right side or left side. ※Power wire can be connected with either the right side or left side.
※Refrigerant pipe can be connected with either the right side or left side. ※Refrigerant pipe can be connected with either the right side or left side.
※Dimensions in parentheses are those of RFB-3750F1. ※Dimensions in parentheses are those of RFB3750F1-R.
15
15
355
385
355
385
62
Anchor volt fixed hole 43
15
65
30
(φ15.88 Copper pipe flare nut connection)
Power supply connection port
800
1240
272
40
828
40 45
78
80
78
119
25
373
363
40
29
(φ26.5 Knock hole)
50
50 35 70
78
80
78
25
119
10℃
18
12
Standard air flow Power frequency 50Hz 60Hz
16
RFB2200F1 RFB3750F1
10℃
Outdoor temperature
RFB2200F1-R RFB3750F1-R
Cooling capacity(kw)
10 14
Cooling capacity(kw)
30℃
40℃
8 40℃ 12
30℃
6 10 Cable set
4 8
2 6 The control panel can be taken away from
0 4
2
the dehumidifier to control it remotely.
10 y 80%
(Length of the cable: 15m, 30m)
Dehumidifying capacity(L/h)
Dehumidifying capacity(L/h)
midit
ve hu midit
y 80%
8 Relati 16
ve hu
60% 14 Relati
6 12 60%
10
4 8
6
2 40% 4 40%
2
0 0
2 4 6 8 10 12 14 16 18 20 22 24 26 28 2 4 6 8 10 12 14 16 18 20 22 24 26 28
Cable
5 Dry‐bulb temperature(℃) 5 Dry‐bulb temperature(℃)
Dry‐bulb temperature(℃)
10 10
Dry‐bulb temperature(℃)
Rela
tive Rela
15 hum
idit
15 tive
hum
Control panel
y90 80% idit
20 %
70%
20 y90
%
80% Dehumidifier
60% 70%
25 50% 25
60%
30
4
30 50
40 %
Remote control wiring assembly
35 30 0% 35 30 %
40
%
40
%
Connector for remote control terminal on
base material
6
Dehumidifiers of portable type 1/2
Features
1. Improvement of corrosion resistance by cation
electrodeposition coating (epoxy resin) adoption.
2. HFC Refrigerant (R407C) adoption, ZERO destruction
coefficient of ozone layer.
3. Single 100V power source adoption (RFE500F).
4. Slim and Compact. Easy movement (by casters) to places where
dehumidifying is needed. Patented (RFB500F has various options.)
5. A high temperature type(up to 45℃) included in the series.
RFB500F RFB1500F
■ Specifications
General purpose type High temperature type
Item Model
RFB500F RFB750F RFB1500F RFH1500F ※ 4
Dehumidifying capacity ※ 1 L/h 1.4/1.6 1.4/1.7 3.0/3.6 2.0/2.3
Operable temperature range ℃ 1 〜 40 20 〜 45
Power source V Single phase 100 ± 10% 50/60Hz Three phase 200 ± 10% 50/60Hz
Power Electric current ※ 1 A 6.1/6.1 2.7/3.0 5.2/5.8 5.1/5.6
specifications Power consumption ※ 1 kW 0.54/0.61 0.71/0.90 1.44/1.86 1.4/1.8
Power capacity kVA 1.0 1.5 3.3 3.0
Compressor kW 0.47 0.65 1.4 1.4
Condenser, Evaporator Forced air cooled fin and tube type Corrugated fin and tube type parallel flow
Blower W 10 25 100 100
Air capacity m3/min 8/9 13/14 26/30 26/30
Equipment
Refrigerant controlling method Capillary tube
details
Refrigerant R407C
Defrosting method Hot gas
Ventilating fan Propeller type
Humidity regulator Optional
External dimensions (H × D × W) mm 858 × 407 × 377 780 × 400 × 540 1007 × 465 × 655 1007 × 465 × 655
Product mass kg 36 46 77 77
Protecting Compressor Over current relay
devices Refrigerating circuit High pressure cut
Drain hose ※ 3 17L tank (with high water level stopper) φ 19 vinyl hose 2m
Accessories
Power cord With plug 5m Cabtyre cord 3m
Operation sound level ※ 5 dB 55/58 61/63 63/67 63/67
※1 The numerical value indicated above is based on 30℃ of suction air temperature and 60% (80% for RFB500F) of relative humidity. The performance capacity is 95% or more of the indicated.
※2 The sound level is the value measured 1 meter away from the front and 1 meter high. ※3 A hose of inside diameter ofφ19 can be attached to RFB500F. ※4 RFH1500F is manufactured to order.
40 40
30 30
20 20
10 10
0 0
30 40 50 60 70 80 90 100 30 40 50 60 70 80 90 100
Relative humidity (%) Relative humidity (%)
2.5
1.5
40℃ 20℃ 2.0 40℃ 20℃
30
1.0 1.5
20
10℃ 1.0 10℃
0.5
10 0.5
0 0
0 50 60 70 80 90 50 60 70 80 90
30 40 50 60 70 80 90 100
Relative humidity (%) Relative humidity (%)
Relative humidity (%)
7 ※50Hz: - - - - / 60Hz:———
※The performance curves are for reference only.
※50Hz: - - - - / 60Hz:———
※The performance curves are for reference only.
Dehumidifiers of portable type 2/2
Drain outlet
Air outlet
(Both sides)
Tank for drain is built-in (17L)
Caster (φ50) Power cord (5m)
RFB750F
46.5 447 RFB750F/1500F/RFH1500F
110 17
1. Humidistat
Setting range: up to 90% RH
Air outlet
Plug soket for humidity regulator
(Humidty:optional)
Operation switch
High-pressure switch (reset) 2. After heater [Built to order]
Suction port Use of an after heater enhances drying efficiency when temperature
(with filter)
is low.
Drain outlet 70
714
780
(Both sides)
Power cord
316
(3m)
■ Applicable model & specifications
66
Drain outlet 65
3. After cooler (Water cooled type) [Built to order]
923
1007
(Both sides)
● Ideal for applications that should not
Power cord raise room temperature
429
from rising
655 465
■ Applicable model & specifications
Model ZSA-750 ZSA-1500
Applicable model RFB750F RFB1500F RFH1500F
RFB1500F RFH1500F
Suction air temperature(℃) ZSA-750 ZSA-1500
6.0 30℃ 5
Water temp. (℃)
0℃ 10 10
Water quantity(L/min)
re3
Dehumidifying capacity (L/h)
5.0
4 ℃ e r atu
4.0 40℃ 20℃ 40 r temp 0℃
ai 2
3 tion
3.0 5
℃ Suc 5 5 24
2 4
2.0 24 20
10℃
1.0 1 20 15
0 0 0 15 0
50 60 70 80 90 40 50 60 70 80 90 25 30 20 25 30
Relative humidity (%) Relative humidity (%) Room temperature (℃) Room temperature (℃)
※50Hz: - - - - / 60Hz:——— ※The performance curves are based on 60Hz.
※The performance curves are for reference only. ※The capacity at 50Hz is about 85% of that of 60Hz. 8
L series Dehumidifiers idealized to use at construction & civil works sites
Features
1. Being equipped with large casters, it is easy to move the dehumidifiers.
2. It is possible to store dehumidifiers two-storied, thanks to the reinforced frame.
3. For such applications as・・・・・・
・Drying walls and interior of buildings at the construction sites.
・Dehumidifying in basement or preventing mildew or abnormal smell
from coming out.
・Dehumidifying in warehouses or humidity control in production plants.
■ Specifications
Item Model RFB500F L Storage Example RFB500F L
Dehumidifying capacity ※ 1、※ 2 L/h 1.4/1.6
Operable temperature range ℃ 1 〜 40
Power source V Single phase 100 ± 10% 50/60Hz
Power
Electric current A 6.1/6.1
specifications
Power consumption kW 0.54/0.61
Compressor kW 0.47
Condenser Forced air cooled fin and tube type
Blower W 10
Equipment Air capacity m3/min 8/9
details Refrigerant controlling method Capillary tube
Refrigerant R407C
Defrosting method Hot gas
Humidity regulator Optional ※1 The value of dehumidifying capacity is based on 30℃ of
External dimensions (Height × Depth × Width) 970 × 495 × 565
suction air temperature and 80% of relative humidity.
(Two-storied external dimensions)
mm
(1885 × 495 × 565)
※2 The dehumidifying capacity is 95% or more of the indicated.
※3 The sound level is the value measured 1 meter away from the
Product mass kg 46
front and 1 meter high.
Protecting Compressor Over current relay
●With large casters(Front: Frame, Behind: Tires(φ150))
devices Refrigerating circuit High-pressure pressure switch
●two-storied storage frame.
Drain hose 17L, with float type’s high water level stopper ※Overturn-prevention should be implemented in case of two-
Accessories
Power cord With plug 2 × 5m storied installation.
Operation sound level ※ 3 dB 55 / 58 ●Optional: Humidistat
40
30
1885
20
10
565
0
30 40 50 60 70 80 90 100
Relative humidity (%)
495
30℃
5.0
4.0 40℃ 20℃
φ21.7
3.0
970
2.0 10℃
1.0
※ 50Hz:
0
60Hz: ーーーー φ
50 60 70 80 90 ※ The performance curves 15 15
0
0 φ
Relative humidity (%) are for reference only.
9
Application Examples
Dehumidifying for various processing & applications
Application Examples
1 . DRYING
For planned production, not being influenced
by seasons or weather.
● Drying of concrete or wooden buildings
● Drying of tiles, pottery, dyed goods and others
● Drying of onion seed, noodles, pasta and so forth
● Drying of wet furniture with paint or varnish
● Drying of clothes and shoes at sports facilities
2. STORING
For storing such products, component parts or food
from which moisture must be kept away.
● Storing metal or resin materials
● Storing canned food, galenicals and clothes
● Storing fruits and bulbs
● Preventing carton box from the change of shape
by humidity.
3. PRODUCTION PROCESSING
For securing stable quality by controlling indoor humidity
● For various manufacturing processes like photo
albums, plywood coating, dried food packaging,
mixing cosmetic substances, and sealing of
seasonings and condiments
● For cultivating mushroom
● Dehumidifying in food producing plants
4. OTHERS
● Humidity control of three coordinate measuring rooms
● Humidity control of die machining plant
● Humidity control of computer/server room
● Stable operation of copy machine
10
Orion Products -- Service and Safety
● Safety Notes
・Before operating this equipment, please read the operating manual carefully, and only use as indicated.
・For installation of this equipment and required wiring, employ a qualified person or consult with your dealer.
・Be sure to select equipment which suits your needs. Do not use this equipment for purposes other than
those for which it is intended. Doing so can lead to accidents or equipment breakdown.
● Air-Cooled Models
If the condenser becomes clogged with dust or dirt, heat exchange will be greatly reduced and
electricity consumption will increase. This will lead not only to decreased performance, but can also lead
to the activation of built-in safety devices, and eventual damage to the equipment. For these reasons,
the condenser should be cleaned on a regular basis.
● Water-Cooled Models
In general, water used to cool condensers will be well-water, tap water, or water from a cooling tower.
However water of insufficient quality can lead to scaling in cooling pipes resulting in lower levels of heat
exchange, increased electricity consumption and lower performance. Therefore water quality should be
confirmed on a regular basis.
ISO 14001