Download as pdf or txt
Download as pdf or txt
You are on page 1of 83

Liebert S600 Single and Parallel System 10kVA- 20kVA

User Manual

Version: V1.1
Revision date: September 27, 2018
BOM: 50490209008

Vertiv Co provides customers with technical support. Users may contact the nearest Vertiv local sales office or
service center.

@2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of
Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their
respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv
Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or
for any errors or omissions. Specifications are subject to change without notice.

Vertiv Energy Pvt. Ltd., India


Address: Plot No. C-20, Road No. 19, Wagle Industrial Estate, Thane – 400 604, Maharashtra, India
Homepage: www.vertivco.com
Special Declaration

Personnel Safety

1. This product must be installed and commissioned by professional engineers of the manufacturer or its
authorized agent. Failure to observe this could result in product malfunction or personnel safety risk.
2. Take the time to read this product manual and the safety precaution thoroughly before installing and
commissioning this product. Failure to observe this could result in product malfunction or personnel
safety risk.
3. This product is not intended for life support equipment application.
4. Never dispose of the internal or external battery of this product in a fire, as it may explode and
jeopardize personnel safety when exposed to flame.

Product Safety

1. If this product will be stored or remain de-energized for a long period, it must be placed in a dry and
clean environment within specified temperature range.
2. This product should be used in an appropriate operating environment. For details, refer to the section on
the environmental requirement in this manual.
3. This product is not designed for application in an environment:
 Where the temperature and relative humidity are outside the specifications
 Subject to vibrations or shocks
 Where conductive dusts, corrosive gases, salts, or flammable gases are present
 Near heat sources or strong electromagnetic interferences

Disclaimer

Vertiv disclaims any and all responsibility or liability for the defects or malfunction caused by:
 Application range or operating environment outside the specifications
 Unauthorized modification, improper installation or operation
 Force majeure
 Other actions not in compliance with the instructions in this manual

Application Note:
S600 UPS is suitable for IT load applications such as computers, servers, routers, CCTV, banking automation
equipments, scientific equipments, projector, POS, etc. The UPS is suitable for industrial customer for above
load and UPS should be installed in AC environment. The UPS is not suitable for industrial load such as
motors, drives, lift, PLC, DCS, SCADA, etc.
Safety Precaution
Always observe the following safety symbols!
Safety symbol Explanation
Used for instructions intended to alert the user to
the risk of death or severe injury should the unit
be used improperly
Used for instructions intended to alert the user to
the risk of injury or equipment damage should the
unit be used improperly
Used for instructions intended to notify the user to
carefully read and observe this unit though it may
not cause damage

This manual contains information concerning the installation and operation of the Liebert eXM UPS
single UPS module and parallel system 80kVA ~ 200kVA.
Read this manual thoroughly before installing, using and servicing the UPS.

Important

The UPS with standard configuration is a category C3 product for commercial and industrial application
in the second environment. Installation restrictions or additional measures may be needed to prevent
disturbances.

Important

The UPS adding C2 EMC option based on the standard configuration is a category C2 product. In a
residential environment, this product may cause radio interference, in which case the user may be
required to take additional measures.

Conformity and standards

This product complies with CE 2006/95/EC (low voltage safety) and 2004/108/EC (EMC), EMC
standards of Australia and New Zealand (C-Tick), and the following UPS product standards:
* IEC62040-1 General safety requirements for UPS
* IEC62040-2-EMC
* IEC62040-3 Performance requirements and test methods
For details, refer to Chapter 11 Specifications.
Continued compliance requires installation in accordance with these instructions and the use of
manufacturer approved accessories only.

Warning
The selection of the upstream distribution protection equipment of the UPS shall be selected in
accordance with the details in 3.1.4 Selection Of UPS I/O Switch and shall comply with the local

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 4


electrical regulations.

Warning: high earth leakage current

Earth connection is critical before connecting the input supply (including both mains supply and
battery).
This equipment is installed with an EMC filter.
Earth leakage current is less than 3000mA.
Transient and steady state earth leakage currents, which may occur when the equipment is started,
should be taken into account in the selection of instantaneous RCCBs or RCD devices.
RCCB which is sensitive to unidirectional DC pulse (class A) and insensitive to transient state current
pulse must be selected.
Note also that the earth leakage currents of the load will be carried by the RCCBs or RCDs.
The equipment must be earthed in accordance with the local electrical code of practice.

Warning: backfeeding protection

This UPS is fitted with a dry contact closure signal for use with an external automatic disconnect device
(supplied by others) to protect against backfeeding voltage into the incoming terminal through the
rectifier or bypass static switch circuit. A label must be added at all external incoming primary supply
disconnect device to warn service personnel that the circuit is connected to a UPS. The text of the label
has the following meaning: Risk of voltage backfeed! Isolate the UPS, then check for hazardous voltage
between all terminals including the protective earth before working on this circuit.

User serviceable components (For service personnel)

All equipment maintenance and servicing procedures involving internal access requires the use of a tool
and should be carried out only by trained personnel. There are no user-serviceable parts behind covers
requiring a tool/key for removal.

Battery voltage exceeds 400Vdc (For service personnel)

All physical battery maintenance and servicing procedures requires the use of a tool/key and should be
carried out only by trained personnel.
Take special care when working with the batteries associated with this UPS. When connected together,
the battery terminal voltage will exceed 400Vdc and is potentially lethal.
Battery manufacturers supply details of the necessary precautions to be observed in working on, or in
the vicinity of, a large bank of battery cells. These precautions should be followed implicitly at all times.
Particular attention should be paid to the recommendations concerning local environmental conditions
and the provision of protective clothing, first aid and fire-fighting facilities.

General safety (For users)


Like other types of large power equipment, the UPS and battery circuit breaker box/battery cabinet

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 5


have high voltage inside. Because the components with high voltage can be accessed only when the
front door is opened, the risk of contacting high voltage has been minimized. This equipment meets the
IP20 standard, and other safety shields are provided inside the equipment.
There will not be any risk when operating this equipment according to the general instructions and the
steps recommended in this manual.

Multiple power inputs (For users)

This UPS system receives power from more than one source. Disconnection of all AC source and the
DC source is required before servicing.
This UPS has several circuits that are energized with high AC as well as DC voltages. Check for voltage
with both AC and DC voltmeters before working within the UPS.

Warning
When the internal fuse of the UPS is damaged, it must be replaced with fuse of the same electric
parameters by qualified personnel.

Important
Beside the communication board is a static sensitive area, an ESD-proof action is critical before
contacting with this area.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 6


Revision Information
V1.0 (August 21, 2018)
Initial release.

V1.1 (September 27, 2018)


Revision 1

V1.2 (October 11, 2018)


Revision 2

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 7


Contents

Chapter 1 Product Information ..............................................................................................................................................................11

1.1 Features ..................................................................................................................................................................................11


1.2 Model Configuration ..............................................................................................................................................................11
1.3 Appearance and Components .................................................................................................................................................12
1.3.1 Appearance.................................................................................................................................................................12
1.3.2 Components ...............................................................................................................................................................12
1.4 Operating Principle.................................................................................................................................................................14
1.5 UPS State and Operation Modes ............................................................................................................................................15
1.5.1 Normal Mode .............................................................................................................................................................15
1.5.2 Bypass Mode ..............................................................................................................................................................15
1.5.3 Battery Mode..............................................................................................................................................................15
1.5.4 ECO Mode (For Single UPS with External Battery Only) .........................................................................................15
1.5.5 Fault State ..................................................................................................................................................................16
1.5.6 Maintenance Bypass Mode ........................................................................................................................................16
1.6 Specifications .........................................................................................................................................................................17

Chapter 2 Installation and Commissioning ............................................................................................................................................19

2.1 Unpacking and Inspection ......................................................................................................................................................19


2.2 Equipment’s Accessories........................................................................................................................................................20
2.2.1 UPS ............................................................................................................................................................................20
2.3 Installation Preparation...........................................................................................................................................................20
2.3.1 Location .....................................................................................................................................................................20
2.3.2 Environmental Requirement.......................................................................................................................................20
2.4 Selecting Power Cables ..........................................................................................................................................................22
2.5 Connecting Battery Cables .....................................................................................................................................................23
2.6 Single UPS Commissioning ...................................................................................................................................................23
2.6.1 Start-up Interface ........................................................................................................................................................23
2.6.2 Normal Mode Start-Up...............................................................................................................................................23
2.6.3 Battery Mode Start-Up ...............................................................................................................................................24

Chapter 3 Parallel UPS Installation and Commissioning.......................................................................................................................26

3.1 Features ..................................................................................................................................................................................26


3.2 Requirements ..........................................................................................................................................................................26
3.3 Connecting Power Cables.......................................................................................................................................................27
3.3.1 Connecting Power Cables ..........................................................................................................................................27

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 8


3.3.2 Connecting Parallel Cables ........................................................................................................................................27
3.3.3 Connecting Battery Cables .........................................................................................................................................28
3.4 Commissioning of Parallel Cables .........................................................................................................................................31
3.4.1 Check Before Start-Up ...............................................................................................................................................31
3.4.2 Parallel System Parameters Setting ............................................................................................................................31
3.4.3 Power-On Commissioning for Parallel System ..........................................................................................................32
3.5 Installation and Commissioning for a Dual Bus System (for 20kVA system only) ................................................................34
3.5.1 Introduction ................................................................................................................................................................34
3.5.2 Connecting LBS Cable ...............................................................................................................................................34
3.5.3 Setting Parameters Of LBS ........................................................................................................................................35

Chapter 4 Operation and Display Panel .................................................................................................................................................37

4.1 Introduction ............................................................................................................................................................................37


4.1.1 LED Indicator ............................................................................................................................................................38
4.1.2 Audible Alarm (Buzzer) .............................................................................................................................................38
4.1.3 LCD and Functional Keys ..........................................................................................................................................38
4.2 Initial Start-Up Guidance .......................................................................................................................................................39
4.3 LCD Menu Structure ..............................................................................................................................................................43
4.4 LCD Screen Types .................................................................................................................................................................43
4.4.1 Start Screen ................................................................................................................................................................43
4.4.2 Flow Screen................................................................................................................................................................44
4.4.3 Main Menu Screen .....................................................................................................................................................44
4.4.4 Submenu Screen .........................................................................................................................................................45
4.4.5 Default Screen ............................................................................................................................................................49
4.5 Prompt Window .....................................................................................................................................................................50
4.6 UPS Alarm Message List .......................................................................................................................................................51

Chapter 5 UPS Operation Instructions...................................................................................................................................................57

5.1 UPS Start-Up ..........................................................................................................................................................................57


5.2 Transfer Procedures Between Operating Modes ....................................................................................................................57
5.3 Transfer from Normal Mode to Battery Mode .......................................................................................................................57
5.4 Transfer from Inverter Mode to Bypass Mode .......................................................................................................................57
5.4.1 Transfer from Bypass Mode to Inverter Mode ...........................................................................................................59
5.4.2 Transfer from Inverter Mode to Maintenance Bypass ................................................................................................60
5.4.3 Transfer from Maintenance Bypass to Inverter Mode ................................................................................................61
5.5 REPO .....................................................................................................................................................................................61
5.6 Auto Restart ...........................................................................................................................................................................62
5.7 Language Selection ................................................................................................................................................................62
5.8 Changing Current Date and Time ...........................................................................................................................................64
5.9 Setting Password ....................................................................................................................................................................65

Chapter 6 Communication .....................................................................................................................................................................69

6.1 Installing Intelligent Card .......................................................................................................................................................69

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 9


6.1.1 Intelligent Card Port ...................................................................................................................................................69
6.1.2 Intelligent Card Option...............................................................................................................................................70
6.2 Connection Cables for Dry Contact Port ................................................................................................................................71
6.3 Connecting USB .....................................................................................................................................................................73
6.4 Connecting Serial Port Communication Cables .....................................................................................................................73
6.5 Connecting Control Port .........................................................................................................................................................73
6.6 Connecting Built-In Ethrenet Port ..........................................................................................................................................73

Chapter 7 Maintenance ..........................................................................................................................................................................75

7.1 Fan Maintenance ....................................................................................................................................................................75


7.2 Battery Maintenance...............................................................................................................................................................75
7.3 Cleaning UPS .........................................................................................................................................................................76
7.4 Checking UPS Status..............................................................................................................................................................76
7.5 Checking UPS Function .........................................................................................................................................................77

Chapter 8 Options ..................................................................................................................................................................................78

8.1 Option List .............................................................................................................................................................................78


8.2 Communication Cables ..........................................................................................................................................................78

Appendix 1 LCD Parameter Settings.....................................................................................................................................................80

Appendix 2 Glossary .............................................................................................................................................................................82

Appendix 3 Hazardous Substances or Elements Announcement ...........................................................................................................83

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 10


Chapter 1 Product Information

S600 10~ 20kVA UPS is an intelligent online UPS system with sine wave output developed by Vertiv Co. The UPS
offers reliable and high-quality AC power to the precision instrument.

This chapter introduces the features, model configurations, appearance and components, operating principle, UPS state
and operation mode, and specifications of the UPS.

1.1 Features

The UPS features include:


• Output power factor is 1, which enhances the UPS load capacity.
• On-line double conversion efficiency up to 91% and ECO efficiency up to 94%, which provide more efficient
products for the customer.
• Product volume decreased by 30% compared with the previous generation; little space occupied, simple handling
and assembly.
• Capable of parallel connection to achieve up to 3 + 1 parallel redundant power
• High-frequency double conversion topology structure, with high input power factor, wide input voltage range,
and output immune to grid interference, thus adaptable to areas with unstable mains supply
• Full digital control platform and hardware design platform, which can adapt worse unstable mains supply and
load impact
• Support 12, 16, 20-block batteries (10kVA); 24, 32, 40-block batteries (20kVA). The long back-up model has a
built-in large power charger with 13A charging capacity to provide fast charging
• Provide programmable terminals with cascade protection, to protect the key devices for the customer when the
load is heavy
• Innovative design of the layout and the whole process greatly promote the reliability of the product; pass high
temperature humidity durability experiment test of 1000 hours
• Operation and display panel with colorful LCD to help you learn about the UPS operation state and operating
parameters. The LCD display will change according to the layout of the model
• Integrate Ethernet port, support HTTP protocol, and use the web browser to achieve the remote monitoring, no
extra monitoring software required
• Full configuration can achieve the functions such as Interlock, external temperature & humidity sensor, and
battery module automatic identification
• Capable of ECO power supply mode and smart sleep mode, which help you save energy to the maximum extent

1.2 Model Configuration

Table 1-1 Model Configurations

Model Input Output Remark


10kVA Three-Phase Single phase Common input configuration, split bypass
configuration
20kVA Three-Phase Single Phase Common input configuration (default), split bypass
configuration

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 11


1.3 Appearance and Components

1.3.1 Appearance
The UPS appearance is shown in Figure 1-1.

Figure 1-1 UPS Appearance in isometric view and front view respectivel)

1.3.2 Components
Front Panel
As shown in Figure 1-2, the UPS front panel provides ventilation holes, operation and display panel, LED
indicators and functional keys.

Display Panel

Figure 1-2 UPS front Panel

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 12


Rear Panel
As shown in Figure 1-3, the UPS rear panel provides input, output, bypass, maintenance bypas and battery MCBs.
The figure also shows UPS power module, output transformer and a contactor. Transformer primary and
secondary are connected to the contactor through cables.

Bypass MCB Q2
Output MCB Q5

Input MCB Q1
Maintenance Bypass
MCB Q3

Power Module

Battery Fuse
Holder

Contactor KM1

Figure 1-3 UPS Rear side

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 13


1.4 Operating Principle

The operating principle of the UPS is shown in the figure 1-4.

Figure 1-4 UPS Operating Principle

1. The UPS is composed of mains input (main and bypass), rectifier/PFC, charger, inverter, bypass, battery, DSP
controller, single phase transformer, contactor and final output.

2. When the mains is normal, the rectifier will start, and the charger will charge the battery string. Before turning
on the UPS, the output voltage is bypass voltage, and the mains supplies power to the load through the bypass.
After turning on the UPS, the electronic transfer switch connects the inverter output to the load, and the mains
supplies DC power to the inverter through the rectifier/PFC circuit. The inverter then converts DC power into pure
sine wave AC power and supplies the AC power to the transformer connected to contactor. Final output is supplied
to load from transformer secondary through electronic transfer switch. Refer figure 1-3 for the position of contactor
and transformer.

3. When the mains is abnormal, the rectifier/PFC circuit boosts the battery voltage and supplies it to the inverter.
The inverter then converts it into pure sine wave AC power and supplies the AC power to the load through the
electronic transfer switch.

4. After the mains returns to normal state, the UPS will automatically transfer from Battery mode to Normal mode,
the mains supply DC power to the inverter through the rectifier/PFC circuit, and then the electronic transfer switch
supplies AC power to the load.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 14


1.5 UPS State and Operation Modes

The UPS state and operation mode include: Normal mode, Bypass mode, Battery Mode, ECO mode, Fault State mode
and Maintenance Bypass mode. The operation schematic diagrams of Normal mode, Bypass mode, Battery Mode and
Maintenance bypass mode are shown in Figure

1.5.1 Normal Mode

When the mains input is normal, the load is supplied with voltage-stabilizing and frequency-stabilizing power by the
mains after processing of the rectifier and the inverter, and meanwhile, the charger is charging the battery. The
operation mode is Normal mode.
In Normal mode, the run indicator (green) is on, the alarm indicator is off, and the buzzer is silent.

1.5.2 Bypass Mode

If the overload overtime, inverter or rectifier failure appears during the UPS operation in Normal mode, the UPS will
transfer to Bypass mode, that is, the load is powered by the bypass source, which comes directly from the mains input.
If the rectifier is normal, the internal charger will charge the battery.
In Bypass mode, the run indicator (green) is on, alarm indicator (yellow) is on, and the buzzer beeps every second. The
'Current' page in LCD will display 'On Bypass'.

1.5.3 Battery Mode

Upon mains failure or voltage out of range, the rectifier and internal charger will stop running, and the battery will
supply power to the load through the inverter. In Battery mode, the run indicator (green) is on, alarm indicator (yellow)
is on, and the buzzer beeps every second. The 'Current' page in LCD will display 'On Battery'.

1. The battery has been fully charged before delivery. However, transportation and storage will inevitably cause some
capacity loss. Therefore, it is required to charge the battery for eight hours before putting the UPS into operation for
the first time, to ensure the adequate backup time for battery.
2. The battery cold start can also be used to start the UPS from the Battery (charged) mode upon mains failure.
Therefore, the battery power can be used independently for improving the system availability to some extent.

1.5.4 ECO Mode (For Single UPS with External Battery Only)

In ECO Mode, the load is powered by bypass when the bypass voltage is normal, and the load is powered by inverter
when the bypass voltage is abnormal. ECO mode is an energy-saving operation mode. For power equipment
insensitive to power grid quality, you can use the ECO mode for power supply through bypass to reduce the power
loss.

1. In ECO mode, if the bypass failure or abnormal bypass voltage appears when the output is not overloaded, the UPS
will transfer to Normal mode. However, if the bypass failure or abnormal bypass voltage appears when the output is
overloaded, the UPS will not transfer to Normal mode, but shut down the bypass.
2. In ECO mode, the efficiency of the UPS is up to 94%.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 15


1.5.5 Fault State

In the normal mode, the UPS will transfer the load to Bypass mode in case of inverter failure or UPS
over-temperature. In Battery mode (with no bypass mains), the UPS will shut down and stop the output if the
inverter failure or UPS overtemperature appears. In UPS Fault State, the alarm indicator (red) will be solid on, the
buzzer will keep beeping, and the corresponding fault information will be displayed on LCD.

1.5.6 Maintenance Bypass Mode

If maintenance and repair for UPS are needed, you can switch the load to the Maintenance Bypass through
maintenance bypass MCB, and the power to the load is not interrupted. The maintenance bypass MCB is located at
the back of the UPS cabinet, and the capacity meets the requirements of total load capacities.

When the UPS has malfunctions, and can not working normally, please get in touch with the nearest Vertiv branch
office or local service center. It is prohibited to repaire the UPS by yourself, otherwise the personnel injury and
damage to the equipment will occur.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 16


1.6 Specifications

Table 1-2 Specifications

Specifications
Item
10kVA (3-in 1-out) 20kVA (3-in 1-out)
Rated voltage 400vac 3-phase,4 wire 400Vac 3-Phase,4 wire

Volatge Range 176 -288VAC at 100% load; 100VAC - 288VAC at 50% load
Input
Rated Frequency 50Hz/60Hz
Frequency Range 40Hz ~ 70Hz
Power factor ≥ 0.95 at full load
Input Phase Reversal Yes NO
Rated power 10KVA/10kW 20KVA/20kW
Voltage 220Vac/230Vac/240Vac (Single phase output)
Frequency synchronization
range
Rated frequency±3Hz. Configurable range: ±0.5Hz ~ ±5Hz

Rated Power Factor Unity


Crest Factor 3:1
Voltage harmonic
< 2% (linear load)
distortion
Output
Voltage Regulation ± 2%
Dynamic response
recovery time 60ms 40ms

Isolation transformer Inbuilt at UPS Output


Inverter Overload At 25°C: 105% ~ 125%- 5min; 125% ~ 150%-1min; 150%- more
Capability the utility mode than 200ms
Inverter Overload
Capability the battery
mode At 25°C :105% ~125%-60~ 30 s; >125%- more than 200ms

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 17


Specifications
Item
10kVA (3-in 1-out) 20kVA (3-in 1-out)
Upper limit: +10%, +15% or +20%; default: +20%
Bypass Voltage range
Lower limit: -10%, -20%, -30% or -40%; default: -40%
Bypass
Separate Bypass Yes
Manual Bypass Inbuilt
ECO Mode > 94% > 94%
Mains efficiency (RL) > 91% > 91%
Efficiency
Inverter
Efficiency(DC-AC) 88% 88%

Type Sealed, lead-acid, Tubular,LI-ION

No's of Batteries 12(1), 16, 20; 16 by default 24(1), 32, 40; 32 by default
Battery
Rated Voltage 144Vdc ~ 240Vdc 288Vdc ~ 480Vdc
Battery Fuse Disconnector Inbuilt
Battery charging capacity 8A 13A
Mains - Battery 0ms
Transfer Time Inverter- Bypass Synchronous transfer: ≤0ms
Asynchronous transfer (default): ≤20ms
UPS Parallel Numbers 4
Noise < 65dB
Panel display mode Graphical LCD display
Operating
0°C ~ 50°C (2)
temperature
Storage -40°C ~ +70°C (battery excluded); -25°C ~ +55°C (battery
Ambient temperature included)
Conditions
Relative
5%RH ~ 95%RH, non-condensing
humidity
Altitude ≤3000m; derating when higher than 3000m
W*D*H (mm) 550 X 620 X 700 550 X 620 X700
Weight (Kg) 138 158
Mechanical Ventilation Forced -air cooled
Parameters Ingress protection IP21
Color Powder coated Black Texture finish
Cable entry Bottom

Note: (1) UPS power will derate to 70% of the total capacity
(2) UPS power will derate to 80% at 40 deg and 70% at 50 deg

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 18


Chapter 2 Installation and Commissioning

This chapter briefly introduces the mechanical installation of the UPS, cable connection and commissioning of the
single UPS.

Each site has its peculiarity, so this chapter provides the guidance with general installation procedures and methods for
the installation engineer who should conduct the installation according to the actual conditions.

1. The UPS should be installed by a qualified engineer according to the information contained in this
chapter. If any problem is found, please get in touch with Vertiv local service center immediately.
2. The UPS shall not be powered on without approval of the commissioning engineer.
3. For other equipment which is not introduced in this manual, the detailed information about
mechanical installation and electrical installation are delivered with the equipment.

2.1 Unpacking and Inspection

The UPS adopts the carton box. Open carton box as shown in the figure 2-1. Visually inspect the UPS appearance for
transportation damage. If any problem is found, please notify the carrier immediately. Check the accessories and
models against the delivery list. If any problem is found, please notify the dealer immediately.

Figure 2-1 Unpacking the UPS

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 19


2.2 Equipment’s Accessories

This section describes the parts, which are supplied along with the UPS. These parts must be examined on receipt
of the system.

2.2.1 UPS

The UPS is mounted on a wooden base palette and fixed on to the same. The unit is wrapped in polythene sheets
and enclosed in a corrugated box. The UPS cabinet can be moved by human, or forklift or other similar lifting
equipment.

2.3 Installation Preparation

2.3.1 Location

To extend the UPS life, the chosen place must offer:


• Convenient wiring
• Adequate operator access area
• Good ventilation to meet the heat dissipation requirements
• No corrosive gas, such as sulfur dioxide and so on
• No excessive moisture or heat source
• No excessive dust
• Compliance with fire-fighting requirements
• Operating temperature compliant with the specifications, see Table 1-2 for details

2.3.2 Environmental Requirement

UPS room The UPS is designed for indoor installation, which should be installed in a clean and well-ventilated
environment, to keep the ambient temperature within the specifications.
The internal fans provide forced air cooling for the UPS. Cooling air enters the UPS through the ventilation holes
on the front panel and exhausts the hot air through the back-ventilation holes. Therefore, do not obstruct the
ventilation holes. Maintain at least 200mm clearances between the front, rear of the UPS and the wall or adjacent
equipment (see Figure 2-2), to avoid obstructing the UPS ventilation and heat dissipation. Otherwise, the UPS
internal temperature will rise, which will shorten the UPS life.
If necessary, an indoor exhaust fan should be installed to keep the indoor temperature from rising. An air filter
should be used in a dusty environment where the UPS is to be operated.

Space Reserved

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 20


Figure 2-2 Installation Clearances (Top view of rack installation)

1.The UPS should be installed only on the concrete surface or other non-flammable surfaces.
2.As shown in Figure 2-5, the demonstration of the clearance between the rear panel of the cabinet and the wall is
500mm. The clearance should not be less than 200mm, it needs to be considered according to the actaul situation for
the sake of maintenance convenience.

Battery Room
A small amount of hydrogen and oxygen will be generated at the end of battery charging; therefore, you must ensure
that the fresh air ventilation of battery installation environment meets the EN50272-2001 requirements.

The battery ambient temperature should keep constant, for the ambient temperature is the main factor to affect the
battery capacity and life. The battery standard operating temperature is 20°C, operation above this temperature will
shorten the battery life, and operation below this temperature will reduce the battery capacity. If the battery average
temperature in operation rises from 20°C to 30°C, the battery life will be reduced by 50%; if the battery temperature in
operation exceeds 40°C, the battery life will be decreased exponentially. In general, the allowed ambient temperature
of the battery is 15°C ~ 25°C. The battery should be kept away from heat and ventilation holes.

When the UPS uses an external battery, you must install a battery protective device (such as fuse or circuit breaker) in
areas near the battery and use the shortest wiring distance for the connection between the protective device and the
battery.

Storage Environment
When the UPS does not need to be installed immediately, the UPS must be stored indoors to be protected from the
excessive moisture or over-temperature environment. The battery requires dry and low temperature, well-ventilated
environment for storage, and the most suitable storage temperature is 20°C ~ 25°C.

Battery Hazards

During the battery storage, the battery must be periodically charged according to the battery
instructions. When charging the battery, you can connect the UPS to the mains temporarily to charge
and activate the battery.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 21


2.4 Selecting Power Cables

I/O cables and battery cables are required for connection. When connecting the cables, you should follow the local
wiring regulations, take the environment situation into account, and refer to Table 3B of IEC60950-1.
The max. current in different operating modes is listed in Table 2-1, the recommended min. cable CSA is listed in
Table 2-2. Select the appropriate cables according to Table 2-1 and Table 2-2.
Table 2-1 Max steady state AC and DC current

Rated Current
UPS Max Input Phase Current Max Output Phase Current Max.battery
Power(kVA) 220V 230V 240V 220V 230V 240V discharging
current (A)
10(3-in 20 20 20 46 44 42 58
1-out)
20(3-in 44 43 42 91 88 85 58
1-out)

When the battery cables are selected, the maximum allowable voltage drop is 4Vdc according to the current value
shown in this table. Do not ring the cables to avoid increasing the electromagnetic interference (EMI).
1: The input mains current of the rectifier and the bypass.
2: Non-linear load (switch mode power) affects the neutral cable design of the output and the bypass. The neutral
cable current may exceed the rated phase current, up to1.732 times as large as the rated current.

Table 2-2 Single UPS cable CSA (unit: mm2, ambient temperature: 25 deg C)

Model Input Output Bypass Neutral PE Battery Battery PE


Cable
10(3-in 10 10 10 10 10 10 10
1-out)
20(3-in 10 10 10 10 10 10 10
1-out)

The recommended I/O MCB capability of the UPS is listed in Table 2-4; select the MCBs according to your
requirements.

1. The UPS is high leakage current equipment, it is not recommended to use the MCB with leakage current
protection.
2. The specified upstream breakers below are required to obtain the conditional short-circuit current rating, Icc
at 10kA symmetrical rms. The specified upstream breakers should comply with an IEC 60947 series Standard.

Table 2-3 UPS I/O MCB Selection

MODEL Recommended Battery Recommended Recommended


capability of input Fuse/MCB capability of capability of
external MCB Selection output external Maintenance bypass external
MCB MCB
10(3-in 1-out) 32A (mains) 63A 63A 63 A
63A (bypass)
20(3-in 1-out) 63A (mains) 63A 125A 125A
125A (bypass)

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 22


1. The 3-in 3-out bypass MCB (125A) is used to connect the bypass input upon split-bypass configuration. The main
MCB can be used only upon common input configuration.
2. The battery CB should use the 250Vdc or above.

2.5 Connecting Battery Cables

1. Before connecting the battery cables, confirm that the actual battery cell number and capacity are consistent with
the parameter settings on the LCD menus.
2. It is prohibited to reverse the polarity of the battery cables.
3. Before replacing the battery module and connecting the battery cables, disconnect the DC battery MCB, power off
the UPS completely, and conduct isolation protection on the terminals.
4. It is recommended that the battery cable should not be longer than three meters. Otherwise, the UPS cannot
operate normally.

2.6 Single UPS Commissioning

2.6.1 Start-up Interface


If the system is first start-up, only mains input mode can be used, and the LCD screen will display the start-up
interface, see figure 2-3.

Figure 2-3 Start up interface

2.6.2 Normal Mode Start-Up


1. Close the external output MCB and input MCB of the UPS one by one.
2. The rectifier runs in normal state for about 30 seconds, the start-up of the rectifier is finished.
3. Finish and check the parameter settings of the single UPS.

a) At main menu screen, press the or key to select 'Settings', and press the key to enter the interface shown
in Figure 2-4.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 23


Figure 2-4 Main menu screen

b) Press the or key to select and set corresponding parameters (taking 'Output' as an example). As shown in
Figure 2-5.

Figure 2-5 Output interface screen

4. After setting corresponding parameters, press the power button for two seconds, and the LCD prompts a dialogue
box shown in Figure 2-6.

Figure 2-6 Turning on UPS

After selecting 'YES', the run indicator (green) blinks, the inverter starts, and the run indicator turns on.
5. Measure whether the inverter output voltage is normal.
6. If the battery is not connected, the alarm indicator is yellow. If the battery is connected, the alarm indicator turns
off.

2.6.3 Battery Mode Start-Up


1. Close the battery MCB and press the power button on the UPS front panel for two seconds, the LCD displays the
startup screen. The alarm indicator will be yellow, and the buzzer will beep continuously after the rectifier finishes
the startup.
2. Press the power button for two seconds, the LCD prompts a dialogue box shown in Figure 2-7.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 24


Figure 2-7 Turning on UPS

After selecting 'YES', the inverter starts, and the run indicator (green) is on.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 25


Chapter 3 Parallel UPS Installation and Commissioning

This chapter introduces the features, requirements, installation and commissioning of the parallel system.

The UPS parallel system provides the user with N + X (2 ≤ N + X ≤ 4, X=0 or 1) parallel configuration, N stands for
the basic parallel sets, X stands for the redundant sets.

3.1 Features

1. The software and the hardware of each UPS in parallel system are the same as those of the single UPS. The basic
parameters of the parallel system can be set through the LCD (Refer to 3.5.2 Parallel System Parameters Setting for
details), and the detailed parameters can be set through the background software (For service engineers only).
2. The parallel cables form a ring connection (Refer to 3.4.2 Connecting Parallel Cables for details) to provide
reliability and redundancy for the system. The intelligent parallel logic provides the user with maximum flexibility. For
example, each UPS in the parallel system can be switched off or on in random order; seamless transfer can be achieved
between Normal mode and Bypass mode, and the transfer is automatically recoverable: that is, after the overload is
removed, the system will return to the original operation mode automatically.
3. The total load of the parallel system can be queried through the LCD of each UPS.

3.2 Requirements

A UPS system composed of multiple parallel-connected UPSs is equivalent to a large UPS system. Nevertheless, it
provides increased system reliability. To ensure equal utilization of all UPSs and compliance with relevant wiring
regulations, the following requirements must be met:

1. All single UPSs must have the same capacity. The 10kVA//20kVA UPS must be connected to the same bypass
source.
2. The bypass input power (10kVA/20kVA only) and the rectifier input power must be connected to the same neutral
line input terminal.
3. If a residual current detector (RCD) is required, it must be set correctly and installed before the same neutral line
input terminal, or it must monitor the protective earth current of the system. Refer to 'Warning: high leakage current' of
Safety Precautions before Contents.
4. The outputs of all single UPSs must be connected to the same output bus.
5. Because the UPS parallel system is not fitted with any auxiliary contact detection devices for the output MCB of the
UPS, removing the single UPS from the parallel system before maintenance and adding the single UPS into the
parallel system after maintenance must be conducted strictly following the procedures provided in 5.2 Transfer
Procedures Between Operation Modes. Failure to observe this may affect the reliability of the load power supply.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 26


3.3 Connecting Power Cables

Each single UPS of the parallel system needs to configure the MCB and cables respectively, refer to 2.4 Connecting
Power Cables for the specification. The recommended configurations of the total power cables are listed in Table 3-1
and Table 3-2 for the parallel system.

3.3.1 Connecting Power Cables

The power cables of the UPS are connected to the I/O terminal block of the rear panel of the UPS, the layout of the I/O
terminal block is shown in 2.6.1 Connecting I/O Cables.
Table 3-1 Input & Output cable CSA for 10 kVA parallel system (unit:mm2, ambient temperature: 25 deg C)

3-in 1-out
Total input Total input Total output Total
Parallel Phase line neutral cable for grounding
UPS for parallel line for parallel cable for
number system parallel system parallel
system system
2 Units 10 35 25 35
3 Units 10 70 50 70
4 Units 16 120 70 120

Table 3-2 Input & Output cable CSA for 20 kVA parallel system (unit:mm2, ambient temperature: 25 deg C)

3-in 3-out 3-in 1-out


Single Single Total Grounding Total Total Grounding
Parallel Input cable output neutral cable for output neutral cable for
UPS for parallel cable for line for parallel cable for line for parallel
number system parallel parallel system parallel parallel system
system system system system
2 Units 25 25 25 25 50 50 50
3 Units 35 35 35 35 70 70 70
4 Units 50 50 50 50 95 95 95

3.3.2 Connecting Parallel Cables

The parallel system provides parallel cable option. The parallel cables form a ring connection through the parallel ports
on the rear panel of the UPS. Taking 20kVA model for example, the cable connection schematic diagram of 3 + 1
parallel system is shown in Figure 3-1.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 27


Figure 3-1 Cabel Connection schematic diagram of 2 + 1 parallel system (20kVA)

1. The Vertiv parallel cables must be used for the parallel system.
2. If the parallel communication fault occurs during the parallel commissioning or operation just shut off the system
and check whether the connection of the parallel cables is correct.
3. During parallel system operation, do not unplug the parallel cables to avoid system damage risk.

3.3.3 Connecting Battery Cables

In the parallel system, the 20kVA UPS can either share the battery strings or use the battery strings independently. The
10kVA UPS can only use the battery strings independently.

Using battery string independently

When each UPS of the parallel system uses the battery string independently, the battery cables connection of each UPS
in the parallel system is the same with that of the single UPS, refer to 2.5 Connecting Battery Cables for the
installation method. The schematic diagram of battery strings in 1 + 1 parallel system with independent battery strings
is shown in Figure 3-2 (a) and (b). Refer to 2.4 Connecting Power Cables to configure an MCB.

Make sure that the LCD settings are correct when using the battery strings independently for the parallel system, refer
to 3.5.2 Parallel System Parameters Settings for details.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 28


(a)

(b)
Figure 3-2 Connection Principle Diagram upon using battery string independently in (a) 10kVA and (b) 20kVA
respectively

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 29


Sharing battery strings (20kVA only)
Using the shared battery strings in the parallel system can save investment in equipment for the users.

1. If the battery strings (four standard battery modules, option) are shared in parallel system, the backup time of the
battery module ranges from two minutes to three minutes at full load.
2. To ensure the abundant backup time of the battery, it is recommended to use the external battery cabinet with big
capacity.

Wiring
Power off the parallel system completely, disconnect the battery MCBs of all single UPSs, and then use battery cables
(refer to 2.4 Connecting Power Cables for the cables and the MCBs) to connect '+', 'N', '-' and 'PE' terminals of the
battery strings respectively to 'BAT+', 'BAT-', 'BAT N' and 'PE' terminals of the corresponding I/O terminal block of
the UPS in the parallel system through each battery MCB, as shown in Figure 3-3.

Figure 3-3 Connection diagram fof shared battery string in 1+1 parallel system

Refer to Figure 3-4 to configure the positive battery string and negative battery string.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 30


Figure 3-4 Internal connection diagram for positive battery string and negative battery string

Close the battery MCB of each UPS.

3.4 Commissioning of Parallel Cables

3.4.1 Check Before Start-Up

1. Check and confirm that power distribution mode of the is correct; that connections of the power cables and the signal
cables are correct and there is no short circuit.
2. Check that the battery installation and cable connection is correct and there is no short circuit, and that the positive
pole and negative pole of the battery are correct. Especially when each UPS of the 20kVA parallel system shares the
battery strings, check these items carefully.
3. Check all the working status of the parallel system, ensure that the phase sequence of the main, bypass
(10kVA/20kVA) and output of each UPS is correct and consistent, that the connection of the parallel cable is reliable,
and that the user load is not connected during power-on.
4. Measure and confirm that the mains voltage and frequency are normal.
5. The output terminals of the UPS is energized upon the start-up. If the load is connected with the output terminals,
make sure that the power to the load is safe.

The output terminals of the UPS will be live upon start-up. When bypass of the single UPS in the parallel system is not
consistent, the system fault may occur, check and confirm the bypass before power-on.

3.4.2 Parallel System Parameters Setting

The parallel parameters for all the UPSs in the parallel system should be set. As shown in Figure 3-5.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 31


Figure 3-5 Setting for parallel parameters

The user can change these settings according to actual needs, for instance two units are connected in parallel then in
the settings System parallel num will be 2; refer to Appendix 1 LCD Parameters Setting for details. After the
change, press the last item 'Sync parallel parameters' to validate the setting.

3.4.3 Power-On Commissioning for Parallel System

1. Set the parallel parameters of each UPS in the parallel system, then commission the inverter. The specific
commissioning procedures are as follows:

a) Make sure that the output MCBs of all UPSs in the parallel system are open, and then close the external input
MCB of each UPS in the parallel system, the UPS is powered on at the same time.

b) The LCD displays the self check screen, and the alarm indicator (red) and run indicator (green) are on at the
same time for about five seconds.

c) After the rectifier has been in normal operation state for about 30 seconds, the rectifier start-up is finished.

d) Refer to 3.5.2 Parallel System Parameters Setting for the parallel parameters setting for each UPS. Note whether
there is an alarm of 'Parallel comm. Fail', if yes, clear the fault according to Table 4-5. Carry out the following
procedures if the UPS is running normally.

e) Press the power button of one UPS for 2 seconds, then press the Enter key to start the UPS. The run indicator
(green) will blink, after 20 seconds, the inverter will start, and the run indicator will turn on.

f) If the battery is not connected, the alarm indicator will be solid on, and the buzzer will beep every second. If the
battery is connected, the alarm indicator will turn off.

g) If the UPS is working normally, press the power button for two seconds to turn off the inverter.

h) Repeat the preceding step a) ~ step g) to power on and commission the inverter of other UPSs respectively.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 32


1. Carry out the parallel commissioning after each UPS is working normally.

2. After confirming that the inverter of each UPS is normal, commission the parallel system, the specific procedures
are as follows:

a) Close the external output MCB and input MCB of each UPS, and all UPSs are powered on at the same time. After
the start of the rectifier is finished, press the power button of one UPS for two seconds, the run indicator (green) will
be on. Measure whether the inverter output voltage is normal.

b) Start the inverter of the second UPS, check whether there is an alarm on the LCD, and confirm that the UPS parallel
works normally.

c) Follow the methods to start the inverter of the third or the fourth UPS to connect the UPS into the parallel system.

3. If the user needs to add one UPS in the parallel system, follow the commissioning procedures below:

a) Check and confirm that the power distribution mode, each power cable and signal cable of the added UPS are well
connected without short circuit. Check that the battery installation and cables connection are correct without short
circuit, and that the positive and negative are correct.

b) Repeat steps a) to h) in Part 1 to complete the single unit commissioning of the added UPS. Then completely power
off the UPS.

c) Ensure that the connection of power cable and signal cable is reliable.

d) For any online UPS, enter the interface shown in Figure 3-7. Set the system parallel No. from 'N' to 'N+1', then click
the 'Sync parallel parameters'.

e) Close the external I/O switches of the added UPS, normally start the inverter after the rectifier start-up. Then check
that the LCD has no alarm, and that the UPS parallel system works normally.

1. For 1+1 parallel system, when one UPS is faulty and needs to be replaced on line, the above operation steps are
available too. The difference is no need to change parallel No., just click the 'Sync parallel parameters' for the online
UPS.
2. Clicking the 'Sync parallel parameters' to achieve the synchronization of the items in parallel settings interface, and
the parameters will affect the parallel system. The user should manually set other parameters according to actual
needs.
3. When adding a single unit in the parallel system, first ensure the parallel cables connection is correct, then power
on the single unit.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 33


3.5 Installation and Commissioning for a Dual Bus System (for 20kVA system only)

3.5.1 Introduction

The dual bus system consists of two independent UPS systems; each UPS system consists of one or two
parallel-connected single UPSs, or more parallel-connected single UPSs.

The dual bus system has high reliability, which is suitable for the load with many input terminals. For single UPS input
load, you can add a static trigger switch (STS, optional) to start the standard Load Bus Synchronization (LBS) system.

Place the UPSs side by side, and connect the UPSs as follows:

The dual bus system adopts the LBS system to realize the output synchronization of the two independent (or parallel)
UPS systems. One is the master system, and the other is the slave system. The operation mode of the dual bus system
contains master system and/or slave system running in Normal mode or Bypass mode. The schematic diagram of the
LBS system built by two UPSs is shown in Figure 3-6.

Figure 3-6 LBS System Schematic Diagram

3.5.2 Connecting LBS Cable

The appearance of the LBS port is the same as the parallel port. For the dual bus system formed by the parallel UPS, it
is recommended to prepare two LBS cables used to connect any two parallel/LBS ports of the two-parallel system,
which is used for reliable connection.LBS connection is applicable for only 20kVA.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 34


Figure 3-7 LBS Cable Connection (20kVA)

3.5.3 Setting Parameters Of LBS

The LBS parameters setting interface is shown in Figure 3-8.


Procedures for setting LBS parameters:

Through the 'Settings' -> 'System' -> 'LBS', you can set the LBS according to actual needs.

There are three items of LBS for selection: Disable, Slave, Master.

Figure 3-8 LBS Parameter Setting Interface

The LBS is the load synchronous system, which is used to implement the output voltage phase synchronization of the
two sets of UPS system. Two sets of UPS system can be two single UPS or two sets of UPS parallel system.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 35


You can manually set the 'Master' and 'Slave' through the LCD.

The UPS which is set to LBS master can send synchronization signal to LBS salve according to the own inverter
voltage phase. After the slave receives the synchronization signal sent by the master, the slave will adjust its
inverter voltage phase to realize the inverter voltage phase is synchronized with the master.

Through the above to realize the inverter voltage phase synchronization of two sets of UPS system and realize the
reliable transfer between the two sets of UPS output voltage and STS, then provide the reliable uninterrupted power
supply to the load.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 36


Chapter 4 Operation and Display Panel

This chapter introduces the fucntion and use of the components of the UPS operation and display panel, and provides
LCD display options information, including LCD screen types, detailed menu messages, prompt windows messsge and
UPS alarm list.

4.1 Introduction

The operation and display panel is located on the front panel of the UPS. Through the operation and display panel, you
can conduct the operation and control on the UPS and query all the UPS parameters, UPS and battery states, and alarm
message.
As shown in Figure 4-1, the operation and display panel provide LCD, menu keys, LED indicators (run indicator and
alarm indicator).

Figure 4-1 LCD Screen

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 37


1. The device has a gravity sensor function; thus, the LCD display direction will be changed according to the
device layout mode.

4.1.1 LED Indicator


The LED indicators are composed of run indicator and alarm indicator. Table 4-1 gives the indicator description.
Table 4-1 Definition of Indicators

Indica Colou
State Description
tor r
On UPS has Output
Run
Green Blinki
indicat Inverter is Starting
ng
or
Off UPS has no output, Inverter is starting
Yello
Alarm On Alarm Occurs
w
indicat
Red On Fault Occurs
or
/ Off No Alarm, No Fault

4.1.2 Audible Alarm (Buzzer)


UPS activity is accompanied by the two kinds of sound listed in Table 4-2.
Table 4-2 Description of audible alarm

Alarm sound Meaning


Sound is generated when the UPS critical alarm appears, such as
One beep every 0.5 second Inverter overload
Sound is generated when the UPS critical alarm appears, such as
One beep every second
battery low voltage
One beep every 3.3 second Sound is generated when the UPS general alarm appears
Sound is generated when the UPS fault appears, such as fuse or
Continuous beep
hardware failure.

4.1.3 LCD and Functional Keys


The operator control and display panel provides five control keys, as described in Table 4-3.
Table 4-3 Description of Control Keys

Control key Silkscreen Description

Confirm Used to confirm or enter

Up Used to page up, turn left or add value, etc.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 38


Down Used to page down, turn right or reduce value, etc.

Used to back, escape, cancel or forbid operation


Escape
Power

Power Used to power on, power off or transfer to Byapss mode

It is required to hold and press the preceding keys for 2s to initiate the key function.

Figure 4-2 LCD Screen

LCD provides you with the user-friendly interface and the 320 × 240 dot matrix image display. The user-friendly
and menu-driven LCD allows you to easily browse through the UPS input, output, parameters of the load and the
battery, learn about the current UPS status and alarm message, perform functional settings and control operation.
The LCD also stores historical alarm records that can be retrieved for reference and diagnosis.

4.2 Initial Start-Up Guidance

When the UPS is the initial start-up, the interface shown in Figure 4-3 will appear to guide the user to set basic
parameters of the UPS.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 39


Figure 4-3 Initial start-up guidance (1)

Initial start-up guidance (1)


Welcome page
Click Next to start the guidance.
Language, date and time page
At this page, you can set the language, date and time you need.

Figure 4-4 Initial start-up guidance (2)

Battery parameter page

At this page, you can set the battery cell number and total Ah.
For 10kVA model, the 'Battery series' are 12, 16, and 20 selectable. See left diagram in Figure 4-5.

For 20kVA model, the 'Battery series' are 24, 32, and 40 selectable. See right diagram in Figure 4-5.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 40


Figure 4-5 Initial start-up guidance (3)

If there is an external battery module, the 'Local battery total Ah' will not appear, see Figure 4-6.

Figure 4-6 Initial start-up guidance (3)

Output page
As shown in Figure 4-8, you can set output voltage, output frequency, and output phase.
For 10kVA model, the 'Output phase No.' cannot be set, because the model only has single phase output. See left
diagram in Figure 4-7.
For 20kVA model, the 'Output phase No.' can be set to 'single' or '3 phases'. See right diagram in Figure 4-7.

Figure 4-7 Initial start-up guidance (4)

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 41


For output page, all the settings must unplug the REPO terminal (forcible output shutdown), otherwise the
interface shown in Figure 4-8 will appear

Figure 4-8 Prompt of removing REPO terminal

Finish page
For 10kVA model, the interface shown in Figure 4-9 will appear. Click Finish to enter the Flow page, then the user can
operate the UPS normally.

Figure 4-9 Initial start-up guidance (5)

For 20kVA model, the interface shown in Figure 4-10 will appear. It means that the functional keys and LCD are
invalid; the user cannot continue the operation. Please power off the UPS based on the prompt shown in Figure
4-10, confirm that the actual wiring method of the output terminal is the same as that of the setting method, then
power on the UPS again.
After the start-up, the user can operate the UPS normally,

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 42


Figure 4-10 Initial start-up guidance (5)

4.3 LCD Menu Structure

Figure 4-11 LCD Menu Structure

4.4 LCD Screen Types

4.4.1 Start Screen

Upon UPS start-up, the UPS executes the system self-test, and the start screen will appear and remain for about 10
seconds, as shown in Figure 4-12.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 43


Figure 4-12 Start Screen

4.4.2 Flow Screen

After the self-test of the UPS, the flow screen shown in Figure 4-13 will appear.

The flow screen is the total status view of the UPS, includes input, bypass, rectifier, battery, inverter and output, etc.
The working modes with color display while the invalid modes with gray display.

Figure 4-13 Flow Screen

4.4.3 Main Menu Screen

The main menu screen is composed of six icons: Status, Settings, Control, Log, About, Maintain. As shown in Figure
4-14.

Figure 4-14 Main Menu Screen

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 44


At main menu screen, press the key to back to the flow screen. Press the or key to switch the

cursor to select the submenu you need, then press the key to confirm it.

4.4.4 Submenu Screen

The submenu screen contains the UPS parameters and item settings. After entering the submenu screen, if there is a

tab control, just move the cursor to the tab. Now, you can press the or key to switch the tab. Press

the key to move the cursor to a certain item.

After entering the submenu screen, if there is no tab control, then the cursor will stop at a certain Item.

Press the key to back to the previous screen.


For details about the submenu screen, see following pages.

Status page
The Status page contains the Input, Bypass, Battery, Output and Load. See below

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 45


Settings page

The Settings page contains the Output, Battery, Parallel, Monitor, System, and Outlet. For details about the
parameters setting, refer to Appendix 1 LCD Parameters Setting. See below:

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 46


Control Page
The Control page contains the Turn ON/OFF/to BYPASS, and Manual battery test, etc.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 47


See below:

Log page
The Log page contains the Current and History. See below:

About page
The About page contains the Product, Network, and Efficiency. See below:

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 48


Maintain page

The Maintain page needs correct password and for Vertiv service engineer operation only.

4.4.5 Default Screen

During the UPS operation, if there is no alarm within two minutes, the default screen shown in Figure 4-15 will appear.
At the default screen, if there is an alarm or a fault, or the user press any key, the Flow screen will appear again.

Figure 4-15 Default Screen

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 49


4.5 Prompt Window

A prompt window is displayed during the operation of the system to alert you to certain conditions and/or to require
your confirmation of a command or other operation. Table 4-4 lists the prompts and meanings.
Table 4-4 Prompts and meaning

Prompt Meaning
System setting is different, please When the parallel parameters are different, the prompt will
check appear
If the user wants to change some important settings under
Cannot set this online, please shut
condition of output (output voltage, output frequency, output phase
down output
No.), the prompt will appear
Incorrect password, please input The prompt will appear when the user incorrectly input the
again Settings password
Operation failed, condition is not The prompt will appear when the user wants to execute a
met certain operation but the condition is not met
The prompt will appear when the user successfully changes the
Password changed OK
Settings password
Fail to change password, please The prompt will appear when the user tries to change the
try again Settings password but input two different new passwords
The time cannot be earlier than The prompt will appear when the user set the time of 'Turn on
system time delay' or 'Turn off delay'is earlier than the current system time
When users press the power button (or execute the command
Turn on failed, condition is not
of 'Turn on/Turn off/to Bypass' under 'Control' page), the
met
prompt will appear
Cannot set this on line, please If the user wants to change output phase No. under condition
unplug REPO of output, the prompt will appear
The prompt will appear when the output phase is changed. The
Please disconnect power, check
system requries the user to power off and check the cables
output: 1 phase, 3 phase, then
connection, then power on the UPS again to guarantee the
power UPS on
safety

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 50


4.6 UPS Alarm Message List

Table 4-5 gives all UPS alarm messages based on the 'Current' and 'History' menus.
Table 4-5 Alarams and meaning

Alarm Explanation
Communication Internal commuication is abnormal, please check the communication cables are
fail connected correctly or not
Rectifier fault The rectifier is faulty and off
DC/DC fault The discharger is faulty, because the bus voltage exceeds the setting range
when discharger starts or soft starts
DC bus abnormal The inverter is off when DC bus voltage is faulty. The load will transfer to bypass if
the bypass is available
Charger fault The charger output voltage is abnormal, and the charger is off
Aux. power fault The auxiliary power output voltage exceeds the normal range
Input backfeed
The mains relay short circuit, and the difference between mains
Battery mode.
and battery voltage is less than the setting range

The inverter is off when the inverter output voltage and current exceed the
Inverter fault
setting range. If bypass is available, the UPS will transfer to bypass mode,
otherwise the system will power off
Output short Check that the output cables are not shorted
Bypass backfeed
The bypass relay is shorted or the SCR is damaged
battery mode.
Output off,
voltage is not When there is no output, the system detects that the output has a voltage
zero
Inverter relay
The inveter relay is shorted
welded
The parallel online number is different from the setting number. Please check
Parallel No.
that the parallel number at 'Settings' page is the same as the actual online
abnormal
number, and that the parallel cables are normal
The local UPS and its online frequency configuration is different or the parallel
Parallel comm
address is conflicted. Please check that the parallel system paramerte setting is the
Fault
same as the local parameter setting
Parallel cable
Connection Detect the parallel cables are loosened
abnormal
Input neutral lost The AC input mains N line is not detected. Please check that the input N line is
opened or loosened

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 51


Alarm Explanation
Input ground lost Check that the PE line is well connected, and the alarm can be cleared on line
The mains AC input phase is reversed. Normally, phase B lags phase A of 120
Input phase
degrees, and phase C lags phase B of 120 degrees.
Reversed
Check that the UPS mains input phase sequence is correct. If not, just modify it
The retifier and charger are off due to the mains voltage and frequency
Input abnormal exceeding normal renage. Check that the rectifier input phase voltage and
frequency exceed the normal range or that the mains has power-off
The output power is larger than the rectifier overload point. Check that the input
Rectifier overload
volatge meets the output load, mains input 176V ~ 100V, the load 100% ~ 50%
linear derating
The battery positive and negative are reversed. Please reconnect the battery
Battery reversed
and check the battery cables connection
Battery low This alarm occurs when the battery reaches the EOD. After the pre-warning, the
pre-warning battery capacity allows two minutes discharge at full load. The user can set the time
ranging from 2min~30min, (2 min by default). Please shut down the load timely

When battery is connected, the system checks that the battery voltage exceeds
Battery voltage
the normal setting range. Check that the battery terminal voltage exceeds the normal
Abnormal
range
No battery Check the battery and battery cables connection
Battery series not The actual connected battery cells are different from the setting cells. Please change
Qualified to the same
The battery capacity is less than 25% of the initial capacity. Battery replacement is
Battery aged
recommended
The battery low voltage is detected when the battery has manual or peroidical
Battery test fail
self-test. Battery replacement is recommended
Battery ambient temperature too high. Check that the battery ambient
Battery overtemp
temperature is higher than setting value 40 ~ 60℃ (default: 50℃)
Battery cabinet
The battery cabinet is not connected to the system
not connected
At least one fan is faulty. Check that the fan is blocked or the cables connection is
Fan fault
loosened
Internal heat sink temperature too high, and the inverter is off. Only each
module heat sink temperature decreased to the setting value can you silence
the alarm. The system can automatically start after overtemperature fault is
System overtemp solved.
If overtemperature, please check:
1. Ambient temperature too high or not
2. Dust is blocked or not
3. Fan fault or not

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 52


Alarm Explanation
Inverter load capacity is larger than the rated value, overload delay time is up,
inverter shuts down. If bypass is available, the system will transfer to the bypass
Inverter overload mode, otherwise the output is failure. Check that the actual inverter load capacity, if
overloaded, just reduce the load capacity, and the system will transfer to the inverter
mode after five minutes with alarm cleared
The bypass voltage phase sequence is reversed. Normally, phase B lags phase A of
Bypass phase
120 degrees, and phase C lags phase B of 120 degrees.
Reversed
Check that the UPS bypass input phase sequence is correct. If not, just modify it
Bypass The bypass current exceeds the rated value. Overload delay time is up, inverter shuts
Overcurrent down
Parallel bypass The bypass phase number is different from the output phase number under
cable connection 'Monitor'. Please check that the bypass cables connection is the same as the
abnormal configured phase number
Maybe caused by bypass voltage and frequency outside of range, bypass
power-off and incorrect bypass cables connection.
Byapss abnormal
1. Check that the bypass voltage and frequency are within the setting range.
2. Check the bypass cables connection
The ECO mode is available, and the bypass voltage and frequency are outside of the
Bypass abnormal
setting range. Check that the bypass input voltage and frequency are within the
in ECO mode
setting range
The output and enclosure are shorted. Check whether the output cables
Output LPE short
connection and the enclosure are shorted or not
Output pending Remote shutdown is enabled, and the system will be off
The system is in standby state, and the dry cntact shutdown is enabled. Check
Output disabled
whether the shutdown dry contact is enabled or not
Version
The version between monitoring board and DSP board is incompatible
Incompatible
Short circuit between bus and enclosure or between battery and enclosure.
Electric leak
Check whether the bus and battery cables connection are shorted with the
Alarm
enclosure or not
On maintenance
bypass The dry contact in maintenance bypass state is activated

Battery mode The UPS is on battery, and the inverter starts


Bypass mode The UPS is on bypass
System overload The parallel system load capacity is larger than the max. load capacity outputed by
parallel sets. Confirm the parallel system load capacity, if overloaded, just reduce it
Loss of After the parallel redundancy is enabled, the system load capacity is larger than the
Redundancy rated load of (online set minus one)

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 53


Alarm Explanation
Load sharing
Load sharing is abnormal in parallel system
Abnormal
System parallel
Check that parallel setting parameters of each unit are the same
settings async
Local parallel
Check that the Settings page is the same between this local unit and other units
settings async
Check whether the LBS cables are nromal, the system is in stand-by state, or system
LBS abnormal
on bypass and the bypass unable to trace
REPO Shutdown caused by the REPO terminal Normally Closed contact open
Bypass phase During parallel connection, the bypass phase sequence is not the same. Check
Reversed the parallel bypass cables connection
System battery In parallel system, all the devices powered by the battery inverter have battery low
low pre-warning voltage pre-warning
Battery test
The battery peroidical self-test and manual self-test started
started
Battery test
The battery peroidical self-test or manual self-test finished
Stopped
The inverter is off due to EOD. Check the mains power-off state and recover the
EOD turn off
mains in time
Guaranteed Under forced EOD mode, the battery discharging finished, then system shuts
Shutdown down
During the UPS operation, the system checks that the heat sink temperaure
exceeds the setting range.
Shutdown due to If overtemperature, please check:
Overtemp 1. Ambient temperature too high or not
2. Dust is blocked or not
3. Fan fault or not
Remote
Dry contact activicated at any mode shutdown
shutdown
Remote
Remotely power on
power-on
Remote shut-off Remotely power off
Load off due to
shutdown on Shutdown in battery mode
battery
Output off due to The bypass is abnormal, and the bypass is in standby state from working state.
bypass abnormal Check that thebypass input is normal
Battery to The UPS is powered by the mains instead of the battery

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 54


Alarm Explanation
utility transition
Manual power-on Set power-on via LCD panel
Manual shutdown Set shutdown via LCD panel
Operating on
The UPS output state is on inverter
inverter

Battery series set


The battery cells changed (10kVA)
to 12 (12~20)
Battery series set
The battery cells changed (20kVA)
to 24 (24~40)
Restore factory
Under UPS stadby state, set 'Restore Factory Defaults' function via the Miantain
defaults
page

Output phase No.


The output phase is changed from 3-phase to 1-phase
set to 1
Output phase No.
The output phase is changed from 1-phase to 3-phase
set to 3
UPS is out of
The UPS is out of service
service
Turn on
programmable The programmable outlet status is changed from Turn Off to Turn On
outlet
Turn off
programmable The programmable outlet status is changed from Turn On to Turn Off
outlet
System parallel
settings start Manually set the 'Sync parallel paremters' command to activate the event
sync
Local settings
Local parameters are successfully synchronized
sync OK
System settings
All the parameters are successfully synchronized
sync OK
Load off due to
The inverter short circuit or the bypass short circiut. Please check it
output short
Output off due to
overload & The output is off due to output overload and bypass abnormal. Please check it
bypass abnormal

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 55


Alarm Explanation
The parallel online number and the configured number are different. Please
Parallel No.
check that the parallel number under Setting page is the same as the actual
Abnormal
online number, and that the parallel cables are normal
In Settings->Output->Frequency selection, 'Auto, BypDisa; 50Hz, BypDisa; 60Hz,
Bypass disabled
BypDisa' is set, the LCD will generate BypDisa alarm
After the intelligent sleep mode is enabled, the system has N sets of inverter
start-up. When the system meets the sleep requirment (Condition of entering
sleep mode: Shared large battery string (If no large battery string, the sleep mode
will cause the battery charging failure, host sleep enable, inverter side no fault or
alarm, rectifier side no fault or alarm, with battery but large battery no charging
On intelligent need, rectifier not on battery mode, wait for 1h after exiting the former sleep, not
sleep mode master and the local unit ID number except sleep module has no start-up command
within 5 minutes). When the N minus 2 units' rated load is larher than the existing
system rated load capacity, the unit with the largest ID number starts to enter sleep
mode (inverter off), at this time, the N minus 1 units are working in inverter mode.
The N minus 3 units are larger than the current system rated load capacity, and the
unit with the largest ID number keeps sleep mode
Battery cabinet The system detects the number of battery cabinet is over six, then reports the battery
Connect abnormal cabinet connection is abnormal
Battery cabinet The battery cabinet group number is specified, but the communication cables
not connected are not connected
Battery EOD Battery end of discharge
Faults cleared Press the 'Clear faults' button under 'Control', then the system will record this event
Manual shut off After the user shuts the UPS output, then the system will record this event
In parallel system, the alarm occurs when UPS's self-adapting output frequency is
System warning
inconsistent. Solution: Power on again
The alarm occurs when model identification is incorrect. Solution: Contact
System fault
service manager

If the alarm is caused through setting the software value by Vertiv authorized engineer, and when you wish to
change the setting values, please get in touch with the Vertiv local customer service center.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 56


Chapter 5 UPS Operation Instructions

This chapter gives a detailed description of the UPS operation procedures.

During the operation, the buzzer alarm may appear, at this point, you can press the key for three seconds to
silence the audible alarm.

Warning: Hazardous mains and/or battery voltage exists behind the protective cover
1. No user accessable parts are located behind the protective covers that require a tool for removal.
2. Only qualified service personnel are authorized to remove such covers.
3. If maintenance for rack is needed, notice that the neutral line is live.

5.1 UPS Start-Up

The start-up procedures can be performed after the installation is finished, the system has been commissioned by
authorized engineer and the external input MCBs are closed.

Important
This procedure results in mains voltage being applied to the UPS output terminals. Confirm that the load
power is safe, if there is a load to be connected with the UPS output terminal. Ensure that the load is isolated
with the UPS output terminal, if the load is not ready for accepting the power.

The start-up mode of the single UPS includes normal mode start-up and battery mode start-up; refer to 2.6.2 Normal
Mode Start-Up and 2.6.3 Battery Mode Start-Up for details.

5.2 Transfer Procedures Between Operating Modes

The Inverter operation mode includes Normal mode (mains inverter) and Battery module (battery inverter).

5.3 Transfer from Normal Mode to Battery Mode

In case of mains failure, the UPS will transfer to Battery mode. If you wish to transfer the UPS from Battery mode to
Normal mode, wait few seconds for mains input recovery. Ten seconds later, the rectifier will restart automatically,
and the inverter will restore the power.

5.4 Transfer from Inverter Mode to Bypass Mode

In standby mode, press and hold the power button. If the rectifier and inverter are normal, the interface shown in
Figure 5-1 will appear, select 'YES' to turn on the UPS.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 57


Figure 5-1 Turning on UPS

In Inverter mode, press and hold the power button. If the bypass is normal, the interface shown in Figure 5-2 will
appear. Select 'To the Bypass' and click OK to transfer the UPS to Bypass mode; select 'Turn off UPS' and click
OK to turn off the UPS.

Figure 5-2 Bypass Normal Interface

In Inverter mode, press and hold the power button. If the bypass is abnormal, then the interface shown in Figure 5-3
will appear, select 'YES' to shut down the UPS output.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 58


Figure 5-3 Bypass abnormal interface

In Bypass mode, the load accepts the power not from the pure power outputted by the inverter, but from the mains
power directly.

For the detailed information of the Normal mode, Bypass mode, Battery and Maintenance Bypass mode, please refer to
section 1.5 UPS State and Operation Mode.

5.4.1 Transfer from Bypass Mode to Inverter Mode

In Bypass mode, press and hold the power button.


If the ECO mode is not turned on, the interface shown in Figure 5-4 will appear.

Figure 5-1 ECO Mode not turned on

Select 'Turn on UPS' and click OK to transfer to the Inverter mode, see Figure 5-5.
Select 'Turn off UPS' and click OK to shut down the UPS output.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 59


Figure 5-2 Bypass to inverter Mode

If the ECO turned on, the interface shown in Figure 5-6 will appear. Select 'YES' to shut down the UPS output.

Figure 5-3 ECO turned on interface Mode

5.4.2 Transfer from Inverter Mode to Maintenance Bypass

When the UPS is running in Normal mode, you can use this procedure to make the load transfer from inverter
output to maintenance bypass.

Important
1. Before performing this procedure, you should check the LCD information first, and make sure, the bypass
is normal and synchronizes with the inverter. Otherwise, it may result in the load power interruption for a
while.

1. Through the LCD settings page, change the Dry connect 3 to 'Maintain mode'. See Figure 5-7.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 60


Figure 5-4 Changing dry contact 3 to “Maintain Mode”

2. Connect one end of the maintenance bypass signal cable to Dry Contact Port 3 of the UPS and the other end to the
NO/NC Auxiliary contact.
3. Remove the screws securing the Bracket of the maintenance bypass switch.
4. Turn Off Inverter.
5. Confirm that the UPS has transferred to internal bypass mode.
6. After confirmation, close the maintenance bypass switch

Note: Dry contact port 4 can achieve the same function as dry contact port 3 via the steps mentioned above.

5.4.3 Transfer from Maintenance Bypass to Inverter Mode

After UPS maintenance, you can use this procedure to transfer the load from the maintenance bypass to the inverter.

Important
In Maintenance bypass mode, After UPS maintenance, the UPS must be manually transferred to bypass
mode and the output switch must be closed. Failure in doing so may cause equipment damage.

1. Close the mains input MCB and bypass input MCB on the rear panel of the UPS. The UPS will turn on and operate in
Bypass mode.
2. Confirm that the UPS is in Bypass mode, then close the output MCB on the rear panel of the UPS.
3. Open the maintenance bypass MCB on the rear panel of the UPS.
4. Fix Bracket of the maintenance bypass switch to its original position, then fasten the fixing screws.
5. Press the power button, and the UPS transfers to Inverter mode.

5.5 REPO

Located at rear of the UPS, the REPO port is designed to switch off the UPS in emergency conditions (such as fire,
flood). The system will turn off the rectifier, inverter and stop powering the load immediately (inverter and bypass
output included), and the battery stops charging or discharging. Just unplug the terminal connecting to the REPO if
you need emergency power-off.

If the mains input is present, the UPS control circuit will remain active; however, the output is closed. To remove all

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 61


mains power from the UPS, the external main input MCB should be disconnected.

5.6 Auto Restart

When the mains power failure, the UPS draws power from the battery to supply the load until the batteries are
depleted, then the UPS will shut down.

The UPS will automatically restart and recover output power supply:

• After the mains power is restored.


• The UPS Auto Restart function is enabled.
• After the Auto Restart is delayed (default: 10s). During the Auto Restart delay, the UPS will charge the
battery to provide a safety margin for equipment shutdown if input power fails again.

If the Auto Restart function is disabled, you can restart the UPS manually by pressing the power button.

5.7 Language Selection

The LCD menus are available in two languages: Chinese, English. Procedures for selecting the language:

1. At the main menu screen, press the or key to switch the cursor to select 'Settings', then press the

key to confirm it. See Figure 5-9.

Figure 5-5 Main menu

2. Press the key to move the cursor to 'Monitor', see Figure 5-10.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 62


Figure 5-6 Monitor Interface

3. Press the key to highlight the language, see Figure 5-11.

Figure 5-7 Language Selection

4. Press the or key to select the language you need, then press the key to confirm it. At this
time, the LCD contents will be the language selected by you. See Figure 5-12.

Figure 5-8 Changing Language

5. Press the key for several times to back to the main menu screen.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 63


5.8 Changing Current Date and Time

Procedures for changing the system date and time:

1. At the main menu screen, press the or key to switch the cursor to select 'Settings', then press the

key to confirm it. See Figure 5-13.

Figure 5-9 Main menu screen

2. Press the key to move the cursor to 'Monitor', see Figure 5-14.

Figure 5-10 Monitor Interface

3. Press the key, and press the or key to highlight the date and time, see Figure 5-15.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 64


Figure 5-11 Selection of date and time

4. Press the key, move the cursor and press the or key to change the date and time you need.
See Figure 5-16.

Figure 5-12 Changing date and time

5. Press the key to confirm it, and then press the key several times to back to the main menu screen.

5.9 Setting Password

1. After powering on the UPS, at the main menu screen, press the or key to move the cursor to select
'Settings'. See Figure 5-17.

Figure 5-13 Main menu

2. Press the key, the interface shown in Figure 5-18 will appear.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 65


Figure 5-14 Inputting password

The user can observe the following procedures to change password:

1. Press the key to move the cursor to the 'Monitor', see Figure 5-19.

Figure 5-15 Monitor Interface

2. Press the key, then press the key to select the 'Change settings password', see Figure 5-20.

Figure 5-16 Changing setting password

3. Press the key, the interface shown in Figure 5-21 will appear.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 66


Figure 5-17 Password for settings

4. Input the existing password, press the key to confirm it, then the system requires to input a new password.
See Figure 5-22.

Figure 5-18 Inputting new password

5. After inputting the new password, press the key to confirm it, then the system requires confirming the new
password, see Figure 5-23.

Figure 5-19 Confirming new password

6. After the confirmation, press the key and the system prompts that the password changing is successful, see
Figure 5-24.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 67


Figure 5-20 Password changed ok

Only through the correct password (default: 111111) verification can you conduct the parameters of the UPS.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 68


Chapter 6 Communication

This chapter briefly introduces the UPS communication.

The communication ports include: intelligent card port, dry contact port, built-in port, 32 port, control port and
USB port

It is recommended to make the signal cable length be less than 3m and keep away from the power cable.

6.1 Installing Intelligent Card

6.1.1 Intelligent Card Port

UPS provides an intelligent card port (see Figure 6-1, taking 20kVA model for example), which is used to install
the communication device options, including SIC card and RDU-SIC card. The intelligent card port and USB port
can be used at the same time.

Intelligent Card Port

Figure 6-1 Intelligent card installation (20kVA, rear view)

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 69


6.1.2 Intelligent Card Option

SIC card

SIC card is a network management card, which makes the intelligent devices (such as UPS, air conditioner, static
transfer system (STS), sever power management system (SPM), and so on) produced by Vertiv have network
communication capability. The SIC card can also be used with the Network Shutdown designed by Vertiv to
provide safe automatic shutdown function for the computer, in which the Network Shutdown has been installed, to
protect data and reduce loss.

Refer to the corresponding user manual for the installation and operation guide.

RDU-SIC card
The RDU-SIC card is a network management card. It can make the intelligent equipment (such as UPS, PDU and
so on) developed by Vertiv have the capacity of network communication. The SIC card can also connect to the
environment monitoring equipment, including IRM series or 1-Wire series temperature sensor, temperature &
humidity sensor or dry contact signal input & detecting sensors. In case of an intelligent equipment alarm, it
notifies the user by multiple ways: recording, sending a Trap message, sending an E-Mail or sending an SMS.

The RDU-SIC card provides four approaches to monitor the intelligent equipment and equipment room
environment:

• Web browser. Monitor your intelligent equipment and equipment room environment through the Web
server function provided by the SIC card
• Network management system (NMS). Monitor your intelligent equipment and equipment room
environment through the SNMP agent function provided by the SIC card
• RDU-Manager. RDU-Manager is a piece of management software for equipment room. You can use
RDU-Manager to monitor your intelligent equipment and equipment room environment through the
TCP/IP interface provided by the SIC card
• Centralized management software (Nform). Monitor your intelligent equipment through the Velocity
Server service function provided by the SIC card

The SIC card can also work with the Network Shutdown computer safe shutdown program developed by Vertiv to
provide automatic safe shutdown function for your computer installed with Network Shutdown, so as to prevent
data loss.

Refer to the corresponding user manual for the installation and operation guide

RS485 card
RS485 card should be used together with S600 Model provided by Vertiv to realize the signal transform from
RS232 to RS485.

Refer to the corresponding user manual for the installation and operation guide.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 70


RS232 card
The RS232 card should be used together with the Liebert® S600 series UPS of Vertiv. It only supports RS232 protocol
communication, and the maximum length of the communication cable cannot exceed 15 meters.

6.2 Connection Cables for Dry Contact Port

The UPS provides five dry contact ports. The silkprints of the five dry contact ports are 1 ~ 12. The pin layout of each
dry contact port is shown in Figure 6-2, and the port description is shown in Table 6-1.

Figure 6-2 Pin layout of dry contact ports

Table 6-1 Description of the dry contact ports


SilkPrint Port Name Pin No Pin Name Meaning
1 Output 1 LOW-BATTERY/ Default: LOW-BATTERY can be set
port1 ON_BATTERY / via the LCD settings page. When
ON_BYPASS/UPS_FAULT the system has as alarm, short Pin
1 and Pin 2
2 GND GND
2 Output 3 LOW-BATTERY/ Default: UPS_FAULT, can be set
Port2 ON_BATTERY / via the LCD settings page. When
ON_BYPASS/UPS_FAULT the system has as alarm, short
Pin 3 and Pin 4
4 GND GND
3 Input 5 Battery mode shutdown/Any Default: Maintain mode, can be
port 1 mode shutdown (Remote set via the LCD settings page.
Comms Shutdown)/maintain When Pin 5 and Pin 6 are shorted,
mode the function is valid
6 GND GND
4 Input 7 Battery mode shutdown/Any Default: Maintain mode, can be
port 2 mode shutdown (Remote set via the LCD settings page.
Comms Shutdown)/ When Pin 7 and Pin 8 are shorted,
Maintain mode the function is valid
8 GND GND
5 REPO input 9 +5V REPO power supply, 5Vdc 100mA
port* 10 REPO Coil -NC NC, ECO activated when Pin 9
and Pin 10 opened
11 REPO Coil -NO Trigger REPO when Pin 11 and
Pin 12 closed
12 GND REPO Ground

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 71


The I/O dry contact port capacity: 125Vdc, 0.5A; 30Vdc, 1A. Pin11 and Pin12 reserves the corresponding
terminals for configuring the REPO function. The REPO device also needs the shielded cable to connect to the
Normally Open remote REPO switch between the two terminals. If not necessary, you should disconnect Pin9 and
Pin10. Pin9 and Pin10 have been shorted before delivery.

The EPO action of the UPS will close the rectifier, inverter and static bypass, but it cannot disconnect the UPS mains
input inside. If you want to disconnect the UPS completely, just disconnect the upstream input MCB when generating
the EPO.

In emergency conditions, close the REPO switch (prepared by users) to shut down the rectifier and inverter, and the
UPS is powered off. In normal condition, the REPO switch cannot cut off the UPS input power. If a switch of
electronic control tripping function is adopted at the UPS input, the REPO switch can help the switch trip and thus cut
off the UPS input power. The position of the REPO switch is shown in Figure 1-3, and the REPO cable connection is
shown in Figure 6-3.

Figure 6-3 Repo cable connection

The cable connection procedures are as follows:

1. Loosen the '11' and '12' connection terminals of the REPO port.

2. Insert the two ends of the copper core cables with the insulation leather peeled into the '11' and '12' connection
terminals of the REPO port and press down the terminals. The REPO cable is complete. Ensure that the REPO cable is
firmly connected to avoid no action or wrong action of the REPO caused by accidental dropping or infirm contact.
3. For parallel UPSs, when connecting the REPO cable, users should parallel connect '11' of the REPO port with one
end of the electronic switch, and parallel connect '12' with the other end of the electronic switch.

When the REPO switch at the user end closes, the UPS will generate an alarm and cut off the output immediately, and
the UPS will not return to the normal operation state automatically. At this point, you must change the REPO switch
state, and power on the UPS manually.

1. It is recommended to use 0.82mm2 ~ 0.33mm2 (signal cable of 18AWG ~ 33AWG) copper core cable.
2. If the switch you have configured is of electronic control tripping function, when the REPO signal takes action, you
need to close the switch before restart the UPS.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 72


6.3 Connecting USB

The methods to connect the USB communication cable are as follows:

Insert one end of the USB communication cable to the USB port (see Figure 1-3) on the rear panel of the UPS and
connect the other end to the USB port of the computer. After the connection, you need to install the USB drive
program in the installation disk.

6.4 Connecting Serial Port Communication Cables

The methods to connect the serial port communication cable are as follows:

Insert one end of the DB9 serial port communication cable to the DB9 serial port (see port 5 in Figure 1-3) on the rear
panel of the UPS, and connect the other end to the DB9 port of the computer.

The pin function of DB9 is listed below:

Pin No Function
2 Send Data
3 Receive Data
5 Common Terminal

6.5 Connecting Control Port

The control port adopts the standard RJ45 port, which supports the Modbus/Jbus port and connects the Vertiv
temperature/temperature & humidity sensor.

The user can select Modbus/Jbus protocol function or sensor function via the 'Settings' on the LCD.

6.6 Connecting Built-In Ethrenet Port

The built-in Ethernet port supports the HTTP protocol. The user can connect one end of the net cable to the Ethernet
port of the UPS and connect the other end to the built-in Ethernet port of the computer. The user can remotely access
the UPS via the IE, Chrome and Firefox, so as to monitor the UPS in real time.

Connect net cables: Connect one end of the net cable to the Ethernet port of the UPS and connect the other end to the
built-in Ethernet port (or the switch port, Router port) of the computer.

Set network parameters: The user should change the parameters (IP address, subnet mask, gateway address) of the
computer or the UPS, so as to make the computer communicate the UPS well.

To change the network parameters of the UPS, operate them via the 'Settings'->’Monitor’, as shown in Figure 6-4.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 73


Webpage monitoring function
Open the browser (like IE), input the IPv4 address at the address bar to the login interface.

After inputting the correct user name and password (default name: user, password: 111111), you can monitor the UPS
working status.

Figure 6-4 Changing UPS Network Parameters

Browser support

To obtain the best user experience, it is recommended to use the Internet Explorer (IE9 or above), or the Chrome,
FireFox (latest version required)

Screen resolution

The display with resolution of 1024*768 or above is recommended.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 74


Chapter 7 Maintenance

This chapter focuses on the UPS maintenance, including the fan maintenance, battery maintenance, UPS cleaning,
UPS state check, UPS function check

Never maintain the UPS on line. Ensure that the UPS has been completely powered off when performing the UPS
Internal maintenance.

7.1 Fan Maintenance

Before the fan is completely stopped, do not insert your fingers or some tools into the fan so as to avoid device
damage or personal injury.

The UPS fans are expected to run for 20000 hours ~ 40000 hours continuously. The higher the ambient temperature,
the shorter the fan life is.

During the UPS operation, please verify the fan status once every half year by confirming that air blows out from the
ventilation holes on the rear panel.

7.2 Battery Maintenance

1. Never reverse-connect the battery, otherwise the fire will occur.


2. Never open the battery to prevent physical injury because of the electrolyte. If you accidentally touch the electrolyte,
wash the area immediately with plenty of clean water and go to hospital.

The internal battery module of the UPS is sealed, lead-acid, maintenance-free battery. The battery life depends on the
ambient temperature, charge and discharge times. High ambient temperature and deep discharge shortens the battery
life.

To ensure the battery life, it is required to:


• Keep the ambient temperature ranging from 15°C to 25°C
• Prevent small current discharge. Continuous battery operation time exceeding 24 hours is strictly prohibited
• Charge the battery for at least 12 hours, if the battery hasn't been charged for three months at specified
ambient temperature, or two months at high ambient temperature

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 75


1. Check regularly the screws at the battery connection parts, fasten it immediately if not tight.
2. Make sure that the safety equipment is complete and that the function is normal, especially that the settings of the
battery management parameters are normal.
3. Measure and record the internal temperature of the battery room.
4. Check whether the battery ports are damaged or hot, and whether the chassises and the covers are damaged

If liquid leakage and damage to the battery are found, place the battery in the nti-vitriol tank, and deal with it
according to the local regulations.

The waste lead-acid battery is dangerous waste material. It is one of the national emphases to control the waste
battery pollution. Its storage, transportation, usage and disposal must follow the national and local law and other
criterions about the dangerous waste material and the waste battery pollution prevention.

According to the related regulations, recycle the waste lead-aid battery, and other disposal methods are prohibited.
Throwing away randomly the waste lead-aid battery and other improper disposal methods can result in serious
environment pollution, which will be investigated the legal responsibility.

As the provider of the lead-acid battery, Vertiv has built perfect service network and recycle system for the waste
battery to assist users to deal with the waste battery by law. Contact Vertiv or the nearest service center for the
detailed information of the recycle system about the waste battery.

Vertiv is not liable for the environment results caused by failure to comply with the notices in this section or to use
the waste battery recycle system provided by Vertiv.

7.3 Cleaning UPS


Clean the UPS periodically, especially the ventilation holes, to ensure free airflow inside the UPS. If necessary, clean
the UPS with a vacuum cleaner. Confirm that the ventilation holes are unobstructed.

7.4 Checking UPS Status

UPS functions check procedures may cause power interruption to load!

It is recommended to check the UPS operation status once every half year.
Check the following items:

1. Check if the UPS is faulty: Is the alarm indicator on? Is the UPS giving any alarm?

2. Check if the UPS is operating in Bypass mode. Normally, the UPS operates in Normal mode; if it is operating in
Bypass mode, you should find out the reason, such as operator intervention, overload, internal fault, and so on.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 76


3. Check if the battery is discharging: When AC mains is normal, the battery should not discharge; if the UPS
operates in Battery mode, you should find out the reason, such as mains failure, battery test, operator intervention,
and so on.

7.5 Checking UPS Function


It is recommended to check the UPS functions once every half year. Backup the load data before conducting the UPS
functions check. Procedures are as follows:

1. Press the power button to check if the buzzer beeps, indicators are on and the LCD display is normal.

2. Press the ESC key to check again if the indicators are on, the LCD display is normal and the UPS has been
transferred to the inverter mode.

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 77


Chapter 8 Options

The Chapter introduces the options of the UPS.

8.1 Option List

Table 8-1 Option list

No. Option name Remark Model


Available in two lengths.
1 324922020702
Parallel Cables 1M parallel cable.
2 3M parallel cable 324922020703
3 LBS Cable 2M LBS cable 324922020704
4 SNMP 931602351817
5 MODBUS 000002354066

8.2 Communication Cables

Communication cable is compulsory in parallel system. See Table 8-5 for cable description. Refer to 3.4.2 Connecting
Parallel Cables for the methods to connect the parallel cables.

Type Name Description Appearance


324922020702 Parallel For N + 1 parallel system, N + 1
communiation communication cables (1m) are
cable needed.
For example, two communication
cables
are needed in 1 + 1 parallel system;
three communicatio cables are
needed in 2 + 1 parallel system;
four communication cables are
needed in 3 + 1 parallel system
Parallel For N + 1 parallel system, N + 1
communiation communication cables (3m) are
cable needed.
For example, two communication
cables
324922020703 are needed in 1 + 1 parallel system;
three communicatio cables are
needed in 2 + 1 parallel system;
four communication cables are
needed in 3 + 1 parallel system

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 78


Dual Bus Ports

The LBS cables are compulsory in dual bus system. See Table 8-7 for the dual bus parts.

Type Name Description Appearance


324922020704 LBS Cable Be used to form LBS system.
Two
LBS cables are recommended

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 79


Appendix 1 LCD Parameter Settings

Menu Item Setting Range Default Setting


Auto restart Disable, Enable Enable
Auto restart delay 0~999 seconds 10; Single unit only
Guaranteed shutdown Disable, Enable Disable
Remote control Disable, Enable Enable
Remote power on delay 0~999 seconds 0
Remote shutdown delay 0~999 seconds 0
Redundant NO, YES YES
System LBS select Disable, Master, Slave Disable; /20kVA only
IT system compatibility Disable, Enable Disable
Dry contact 1 (Output) Low battery, On bypass, Low battery
On battery, UPS fault
Dry contact 2 (Output) Low battery, On bypass, UPS Fault
On battery, UPS fault
Dry contact 3 (Input) Battery mode shutdown, Maintain mode
Any mode shutdown,
Maintain mode
Dry contact 4 (Input) Battery mode shutdown, Maintain mode
Any mode shutdown,
Maintain mode
Voltage selection 220V, 230V, 240V 220V
Startup on bypass Disable, Enable Disable
Frequency Selection Auto, BypEna; Auto, Auto, BypEna
BypDisa;
50Hz, BypDisa; 60Hz,
BypDisa
Output Inverter sync range ±0.5Hz, ±1.0Hz, ±2.0Hz, ±3.0Hz
±3.0Hz, ±4.0Hz, ±5.0Hz
Bypass voltage upper +10%, +15%, +20% +20%
limit
Bypass voltage lower -10%, -20%, -30%, -40% -40%
limit
Bypass frequency range ±5Hz, ±10Hz ±10Hz
Run mode Normal, ECO mode Normal

Menu Item Setting Range Default Setting


ECO voltage range ±5%, ±10%, ±15% ±10%
ECO frequency range ±1Hz, ±2Hz, ±3Hz ±3Hz
Output ECO requalification time 5, 15, 30
30 (min)
Output phase No. 1 phase, 3 phases 3 phases (/20kVA)
Voltage selection 220V, 230V, 240V 220V
Frequency selection Auto, BypEna; Auto, Auto, BypEna
BypDisa;
50Hz, BypDisa; 60Hz,
Parallel BypDisa
Run mode Normal, ECO mode Normal
Redundant NO, YES YES
System parallel No. 1~4 1
Output phase No. 1 phase, 3 phases 3 phases (/20kVA)
Sync parallel parameters Button Button
Shared battery Disable, Enable Disable; /20kVA only
Local/Parallel battery 7~3000Ah 9Ah (5/6/10kVA)

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 80


total Ah 18Ah (16/20kVA)
External battery cabinet Auto test, 0~10 Auto test
vgroup No.
Low battery time 2~30 (min) 2
Battery replaced time YYYY-MM-DD 2000-01-01 0:00:00
HH:MM:SS
Battery Battery test interval Disable, 8 weeks, 12 Disable
weeks,
16 weeks,20 weeks,26
weeks
Battery test weekday Sunday, Monday, Tuesday, Wednesday
Wednesday, Thursday,
Friday, Saturday
Battery test time HH:MM:SS 0:00:00
Battery series 10kVA: 12, 16, 16 (10kVA),
20 32 (20kVA)
20kVA: 24, 32, 40
Discharge protect time 1~4320 (min) 4320
Equal charge enable NO, YES NO
Temperature Disable, Enable Disable
Compensation
Replace battery Button Button
Menu Item Setting Range Default Setting
Turn on outlet Appear only when outlet off
Turn off outlet Appear only when outlet off
Reboot outlet Appear only when outlet off
Outlet Turn off when UPS YES, NO NO
overload on battery
Turn off when UPS on 0~4320 (min) 2
battery for
Turn off when backup 0~4320 (min) 0
time less than
Turn off when battery 20~80% 30%
capacity less than
Turn on when power 0~4320 (min)
returns for
Language English, Chinese English
Date YYYY-MM-DD 2016-10-0
Time HH:MM:SS 00:00:00
Display orientation Auto-rotate, horizontal, Auto-rotate
Vertical
Audible Alarm Disable, Enable Enable
MONITOR Control port protocol Modbus, Sensor Sensor
Modbus address 1~128 1
IPv4 address 192.168.1.10
Subnet mask ddd.ddd.ddd.ddd ( 'd' is a 255.255.255.0
Gateway address decimal number) 192.168.1.1
Change settings password The password is numeric 111111
only and can be set from 0
to 9. The password length
is 6

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 81


Appendix 2 Glossary

AC Alternating current
CB Circuit breaker
CSA Cross sectional area
DC Direct current
DIP Dual-in-line Package
DSP Digital Signal Processor
EMC Electromagnetic compatibility
EMI Electromagnetic interference
EOD End-of-discharge
EPO Emergency power off
I/O Input/output
IGBT Integrated gate bipolar transistor
LBS Load bus synchronizer
LCD Liquid crystal display
LED Light-emitting diode
MCB Master Circuit Breaker
NMS Network Management System
PE Protective Earth
RCCB Residual current circuit breaker
RCD Residual current detector
REPO Remote emergency power off
SCR Silicon-controlled rectifier
SNMP Simple network monitoring protocol
STS Static transfer switch
UPS Uninterruptible power system

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 82


Appendix 3 Hazardous Substances or Elements Announcement

Hazardous substances or elements


Parts Plumbum Hydrargyru Cadmium Chrome6+ PBB PBDE
Pb Hg Cd Cr6+ PBB PBDE
Cables × ○ ○ ○ ○ ○
This table is made following the regulation of SJ/T 11364.
○: Means the content of the hazardous substances in all the average quality materials of the parts is within the
limits specified in GB/T 26572
×: Means the content of the hazardous sustances in at least one of the average quality materilals of the parts is
outsides the limits specified in GB/T 26572
Applicable scope: Liebert® S600 10kVA ~ 20kVA UPS

Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual 83

You might also like