TECHNICAL SELECTION

Software version: ELCA World v. 1.7.1.0


User: Marco Pellizzari
Database version: 1.8.1.0
Print data:14/07/2022 10:13

TECHNICAL SELECTION
TR-W-Z /5D1C
High efficiency water cooled chiller

Code TR-W-Z /5D1C


Version -
Size 5D1C
Power supply V/ph/Hz 400/3/50
ELCA_Engine ver.4.7.1.0
INDEX
Data Book
TR-W-Z 1A00 - 6D00_202207_EN R134a

1 TECHNICAL SELECTION pg.3

1.1 Performance at design conditions pg.3

1.2 Efficiencies pg.4

1.3 Part load data pg.4

1.4 Exchangers pg.4

1.5 Compressors pg.5

1.6 Noise data pg.6

1.7 Operating limits pg.7

1.8 Electrical data pg.7

1.9 Weight & dimensions pg.8

2
1 TECHNICAL SELECTION TR-W-Z /5D1C
Software version: ELCA World v. 1.7.1.0
Database version: 1.8.1.0
User: Marco Pellizzari
Print data:14/07/2022 10:13
Calculation type:EUROPEAN GROSS
DR code:84,6

1.1 PERFORMANCE AT DESIGN CONDITIONS


RUNNING CONDITIONS

HEAT EXCHANGER USER SIDE

Fluid type WATER


Glycol % 0
Fouling factor h ft2 °F /Btu 0,000102
Fluid inlet temperature (cooling mode) °F 53,60
Fluid outlet temperature (cooling mode) °F 44,60
Water flow m³/h 635,8
Pressure drop at the heat exchanger kPa 68,9
Available unit head kPa 0,00
HEAT EXCHANGER SOURCE SIDE

Fluid WATER
Glycol % 0
Fouling factor h ft2 °F /Btu 0,000250
Fluid inlet temperature (cooling mode) °F 86,00
Fluid outlet temperature (cooling mode) °F 95,00
Water flow m³/h 732,3
Pressure drop at the heat exchanger kPa 53,8
Available unit head kPa 0,00

COOLING (Gross value)

Capacity control % 84,6


Cooling capacity RT 1050
Compressor power input kW 568,9
Total power input kW 568,9
EER kW/kW 6,490
ESEER CALCULATED kW/kW 10,20
*Unit selected at DIFFERENT compressor speed rotation from
Note nominal one.
COOLING MODE (GROSS VALUE) - MAX PERFORMANCE

Cooling capacity RT 1241


Compressor power input kW 697,3
Total power input kW 697,3
EER kW/kW 6,261

The performance shown are obtained from theoretical calculations and tolerances will apply.Rpt.version:1.0.6.0

3
TECHNICAL SELECTION TR-W-Z /5D1C
Software version: ELCA World v. 1.7.1.0
Database version: 1.8.1.0
User: Marco Pellizzari
Print data:14/07/2022 10:13
Calculation type:EUROPEAN GROSS
DR code:84,6

1.2 EFFICIENCIES
ESEER (GROSS VALUE)

Load % 100 75 50 25
Temp. evaporator inlet °F 53,60 51,35 49,10 46,85
Temp. evaporator outlet °F 44,60 44,60 44,60 44,60
Evaporator water flow m³/h 637,0 637,0 637,0 637,0
Condenser input temperature °F 86,00 78,80 71,60 64,62
Condenser output temperature °F 95,00 85,38 75,89 66,72
Condenser fluid flow m³/h 732,6 732,6 732,6 732,6
Cooling capacity RT 1052 789,1 526,0 263,0
Total power input kW 563,2 343,9 180,9 66,90
EER kW/kW 6,570 8,070 10,20 13,80
ESEER CALCULATED kW/kW 10,20

1.3 PART LOAD DATA


COOLING PARTIAL LOADS

Load % 100,0 90,0 80,0 70,0 60,0 50,0 40,0 30,0 20,0 10,0
Temp. evaporator inlet °F 53,60 52,70 51,80 50,90 50,00 49,10 48,20 47,30 46,40 45,50
Temp. evaporator outlet °F 44,60 44,60 44,60 44,60 44,60 44,60 44,60 44,60 44,60 44,60
Evaporator water flow m³/h 635,8 635,8 635,8 635,8 635,8 635,8 635,8 635,8 635,8 635,8
Pressure drop kPa 68,7 68,7 68,7 68,7 68,7 68,7 68,7 68,7 68,7 68,7
Condenser input temperature °F 86,00 86,90 87,80 88,70 89,60 90,50 91,40 92,30 93,20 94,10
Condenser output temperature °F 95,00 95,00 95,00 95,00 95,00 95,00 95,00 95,00 95,00 95,00
Condenser fluid flow m³/h 732,3 732,3 732,3 732,3 732,3 732,3 732,3 732,3 732,3 732,3
Pressure drop kPa 53,6 53,6 53,6 53,6 53,6 53,6 53,6 53,6 53,6 53,6
Cooling load kWh 3693 3324 2954 2585 2216 1846 1477 1108 739 369
Total power input kW 568,9 510,7 453,6 396,7 339,8 282,7 225,8 168,9 112,0 56,00
EER kW/kW 6,490 6,510 6,510 6,520 6,520 6,530 6,540 6,560 6,600 6,590

1.4 EXCHANGERS
HEAT EXCHANGER USER SIDE

Typology FLOODED
Quantity N° 1
Type of connections VICTAULIC
Diameter of connections 12"
Min flow m³/h 320,0
Max flow m³/h 756,0
Heat exchanger water content l 1480
Minimum water content admitted in the plant l 5000

The performance shown are obtained from theoretical calculations and tolerances will apply.Rpt.version:1.0.6.0

4
TECHNICAL SELECTION TR-W-Z /5D1C
Software version: ELCA World v. 1.7.1.0
Database version: 1.8.1.0
User: Marco Pellizzari
Print data:14/07/2022 10:13
Calculation type:EUROPEAN GROSS
DR code:84,6

HEAT EXCHANGER SOURCE SIDE

Typology FLOODED
Quantity N° 1
Type of connections VICTAULIC
Diameter of connections 12"
Min flow m³/h 415,0
Max flow m³/h 1000
Water content l 2002

1.5 COMPRESSORS
COMPRESSORS

Compressor type CENTRIFUGAL


Compressors nr. N° 6
No. Circuits N° 1
Number of capacity steps N° 0
Min. capacity step %
Regulation STEPLESS
Oil charge kg 0,00
F.L.I. - Max absorbed power kW 5x138+1x120
F.L.A. - Max absorbed current A 5x216+1x187
L.R.A. - Locked rotor amperes for single compressor A -

REFRIGERANT

Refrigerant R134a
Theoretical refrigerant charge kg 1739
GWP100 value (from IPCC AR5) 1300
CO2 equivalent t 2261

The performance shown are obtained from theoretical calculations and tolerances will apply.Rpt.version:1.0.6.0

5
TECHNICAL SELECTION TR-W-Z /5D1C
Software version: ELCA World v. 1.7.1.0
Database version: 1.8.1.0
User: Marco Pellizzari
Print data:14/07/2022 10:13
Calculation type:EUROPEAN GROSS
DR code:84,6

1.6 NOISE DATA


SOUND DATA COLD

Frequencies Hz 63 125 250 500 1000 2000 4000 8000


Sound power (spectrum) dB 90 89 93 98 96 95 92 92
Total sound power level in cooling dB(A) 102
Sound pressure level (spectrum) dB 69 68 72 77 75 74 71 71
Total sound Pressure dB(A) 81

Note

Distance m 1
Average sound pressure level at 1 m distance, unit in a free field
on a reflective surface; non-binding value calculated from the
Note sound power level.
Sound power on the basis of measurements taken in compliance
with ISO 9614.

The performance shown are obtained from theoretical calculations and tolerances will apply.Rpt.version:1.0.6.0

6
TECHNICAL SELECTION TR-W-Z /5D1C
Software version: ELCA World v. 1.7.1.0
Database version: 1.8.1.0
User: Marco Pellizzari
Print data:14/07/2022 10:13
Calculation type:EUROPEAN GROSS
DR code:84,6

1.7 OPERATING LIMITS

*Unit selected at DIFFERENT compressor speed rotation from


Note nominal one.

1.8 ELECTRICAL DATA


Power supply V/ph/Hz 400/3/50
F.L.I. - Max absorbed power kW 810,0
F.L.A. - Max absorbed current A 1267
S.A. - Inrush current A -

The performance shown are obtained from theoretical calculations and tolerances will apply.Rpt.version:1.0.6.0

7
TECHNICAL SELECTION TR-W-Z /5D1C
Software version: ELCA World v. 1.7.1.0
Database version: 1.8.1.0
User: Marco Pellizzari
Print data:14/07/2022 10:13
Calculation type:EUROPEAN GROSS
DR code:84,6

1.9 WEIGHT & DIMENSIONS


A mm 6610
B mm 2400
H mm 2450
Operating weight kg 21350
R1 mm 1000
R2 mm 5800
R3 mm 1500
R4 mm 1000

The performance shown are obtained from theoretical calculations and tolerances will apply.Rpt.version:1.0.6.0

8