Field Devices Europe

01

SPP110
Pressure Transmitter Wet Media 0-10 V
SPP110 Pressure transmitters are intended for use in HVAC pipe systems to monitor the pressure . SPP110 is an electronic pressure transmitter that converts the measured pressure into an electric 010 V signal . SPP110 is delivered with 2 m (6 .6 ft) cable and a G1/2 adapter nut . Medium: any medium suitable with stainless steel .

SPECIFICATIONS
Part number . . . . . . . . . . . . . . . . . . . . . . . see table Range . . . . . . . . . . . . . . . . . . . . . . . . . . . see table Max . operating pressure 2 * nominal pressure range Signal output . . . . . . . . . . . . . . . . . . . . . . . .010 V Power . . . . . . . . . . . . . . . . . . . . . . . 24 V AC 10% 1536 V DC Accuracy Total of linearity, hysteresis & repeatability . . . . . . . . 0 .5 % FS Zero point residual voltage . . . . . . . . . . . . < 50 mV Temperature influence Medium and ambient temperature . . .40 to 105C (40 to 212 F) TC zero point . . . . . . . . . . . . . . . . .< 0 .02%FS/K TC sensivity . . . . . . . . . . . . . . . . . <0 .018%FS/K Load resistance . . . . . . . . . . . . . . . . . . > 10 kOhm Current consumption, typical . . . . . . . . . . . . 15 mA Ambient temperature Operation . . . . . . . . . . 40 to 105C (40 to 221F) Storage . . . . . . . . . . . 40 to 115C (40 to 239F) Materials Connection box . . . . . . . . . . . . . . .polyamid plastic Mebrane . . . . . . . . . . . . . . . . . . . . . . stainless steel Enclosure rating . . . . . . . . . . . . . . . . . . . . . . . IP 65 Weight . . . . . . . . . . . . . . . . . max . 130 g (0 .287 lb .) Standards EMC . . . . . . . . . . . . . . . . EN 50081-1, EN 50082-1

DIMENSIONS mm (in)
2000 (6.6 ft)

G1/4

95 (3.74)

27 (1.06)

SW22 G1/4
6 (0.24)

G1/4 G1/2

12 (0.47)

Field Devices Europe SPP110 MOUNTING


Pressure measurement with liquids The tapping point should be at the side, near the bottom of the pipe . Do not measure the pressure from the top of the pipe (where it may be affected by airlocks) or the bottom (where it may be affected by dirt) . Always evacuate the system . Pressure measurement with condensing gases The tapping point should be at the top so that no condensate reaches the sensor . Remote mounting If the temperature of the medium is lower than 40C (40F) or higher than +105C (221F), the sensor should be fitted remotely, taking care that no condensate can reach the sensor .
Condensate or liquide

02

MOUNTING

WIRING
0...10V SPP110

1. Y 2. GO 3. G

UG=24VAC 10% / 1536 VDC

Part number

Description kPa

Range PSI kPa

Max pressure PSI

0-047-0202-0 0-047-0204-0 0-047-0206-0 0-047-0208-0 0-047-0210-0 0-047-0212-0 0-047-0214-0

SPP110-100kPa SPP110-250kPa SPP110-600kPa SPP110-1000kPa SPP110-1600kPa SPP110-2500kPa SPP110-4000kPa

0-100 0-250 0-600 0-1000 0-1600 0-2500 0-4000

0-14 .50 0-36 .26 0-87 .02 0-145 .04 0-232 .06 0-362 .59 0-580 .15

200 500 1 .200 2 .000 3 .200 5 .000 8 .000

29 .01 72 .52 174 .05 464 .12 725 .19 1160 .30
2009 Schneider Electric. All rights reserved.

290 .08

On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes. Schneider Electric Telephone Europe: Malm, Sweden +46 40 38 68 50 Telephone Asia Pacific: Singapore +65 6776 3166 www.schneider-electric.com/buildings