PRODUCT RATING SUMMARY

RATING DEFINITION
Standby — These ratings are applicable for
supplying continuous electrical power (at
variable load) in the event of a utility power
failure. No overload is permitted on these
ratings. The alternators on these models
are peak continuous rated (as defined in
ISO 8528-3).

Prime — These ratings are applicable for


supplying continuous electrical power
(at variable load) in lieu of commercially
purchased power. There is no limitation
to the annual hours of operation and GEP
models can supply 10% overload power for
1 hour in 12 hours.

Content
50 Hz 3–Phase
400, 1103, 1104, 1006, 1106, 1306, 2206, 2506 and 2806 Series Engines ...............................................................2

60 Hz 3–Phase
400, 1103, 1104, 1006, 1306, 2506 and 2806 Series Engines...................................................................................2

50 Hz Single Phase
400, 1100 and 1006 Series Engines..........................................................................................................................4

60 Hz Single Phase
400, 1103, 1104 and 1006 Series Engines.................................................................................................................4

Variants
'A' Variant - optimised for low fuel consumption (BSFC)
'C' Variant - Low Emissions - EU Stage II emissions compliant
Exclusively from your Cat® dealer

3-PHASE DIESEL GENERATING SET RATINGS – 50 Hz, 308-415V


Model Engine Model Standard Generator RPM Standby kVA (kW) Prime kVA (kW)
400 Series
GEP9.5-2 403D-11G LL1114D 1500 9.5 (7.6) 8.5 (6.8)
GEP13.5-4 403D-15G LL1014H 1500 13.8 (11.0) 12.5 (10.0)
GEP18-4 404D-22G1 LL1014L 1500 18.0 (14.4) 16.5 (13.2)
GEP22-4 404D-22G LL1014N 1500 22.0 (17.6) 20.0 (16.0)
1103 Series
GEP33-3 1103A-33G1 LL1014S 1500 33.0 (26.4) 30.0 (24.0)
GEP33-4 1103C-33G2/3 LL1014S 1500 33.0 (26.4) 30.0 (24.0)
GEP50-4 1103C-33TG2/3 LL2014C 1500 49.8 (39.8) 45.0 (36.0)
GEP50-7 1103A-33TG1 LL2014C 1500 50.0 (40.0) 45.0 (36.0)
GEP55-3 1103A-33TG2 LL2014D 1500 52.0 (41.6) 47.0 (37.6)
GEP65-9 1103A-33TG2 LL2014H 1500 65.0 (52.0) 60.0 (48.0)
1104 Series
GEP44-9* 1104A-44G LL2014C 1500 44.0 (35.2) 40.0 (32.0)
GEP55-4 1104C-44TG2/3 LL2014D 1500 55.0 (44.0) 50.0 (40.0)
GEP65-4 1104C-44TG2/3 LL2014H 1500 65.0 (52.0) 60.0 (48.0)
GEP65-11* 1104A-44TG1 LL2014H 1500 65.0 (52.0) 60.0 (48.0)
GEP88-3 1104A-44TG2 LL2014L 1500 88.0 (70.4) 80.0 (64.0)
GEP88-4 1104C-TAG1 LL2014L 1500 88.0 (70.4) 80.0 (64.0)
GEP110-4 1104C-TAG2 LL3014B 1500 110.0 (88.0) 100.0 (80.0)
1006 Series
GEP150-1 1006TAG LL3014F 1500 150.0 (120.0) 135.0 (108.0)
GEP165-1 1006TAG2 LL3014H 1500 165.0 (132.0) 150.0 (120.0)
1106 Series
GEP150-4 1106C-E66TAG2 LL3014F 1500 150.0 (120.0) 135.0 (108.0)
GEP165-4 1106C-E66TAG3 LL3014H 1500 165.0 (132.0) 149.7 (119.8)
GEP200-4 1106C-E66TAG4 LL5014F 1500 200.0 (160.0) 180.0 (144.0)
1306 Series
GEH220-2 1306C-E87TAG4 LL5014F 1500 220.0 (176.0) 200.0 (160.0)
GEH250-2 1306C-E87TAG4 LL5014H 1500 250.0 (200.0) 230.0 (184.0)
GEH275-2 1306C-E87TAG6 LL5014J 1500 275.0 (220.0) 250.0 (200.0)
2206 Series
GEP400-3 2206A-E13TAG2 LL6114B 1500 400.0 (320.0) 350.0 (280.0)
GEP400-4 2206C-E13TAG2 LL6114B 1500 400.0 (320.0) 350.0 (280.0)
GEP450-3 2206A-E13TAG3 LL6114D 1500 450.0 (360.0) 400.0 (320.0)
GEP450-4 2206C-E13TAG3 LL6114D 1500 450.0 (360.0) 400.0 (320.0)
2506 Series
GEP500-1 2506A-E15TAG1 LL6114D 1500 500.0 (400.0) 450.0 (360.0)
GEP500-2 2506C-E15TAG1 LL6114D 1500 500.0 (400.0) 450.0 (360.0)
GEP550-1 2506A-E15TAG2 LL6114F 1500 550.0 (440.0) 500.0 (400.0)
GEP550-2 2506C-E15TAG2 LL6114F 1500 550.0 (440.0) 500.0 (400.0)

*Latin American Models. All ratings at 0.8 pf


Exclusively from your Cat® dealer

3-PHASE DIESEL GENERATING SET RATINGS – 50 Hz, 308-415V


Model Engine Model Standard Generator RPM Standby kVA (kW) Primie kVA (kW)
2806 Series
GEP605-1 2806A-E18TAG1 LL6114G 1500 605.0 (484.0) 550.0 (440.0)
GEP605-2 2806C-E18TAG1 LL6114G 1500 605.0 (484.0) 550.0 (440.0)
GEP650-2 2806C-E18TAG1A LL6114K 1500 650.0 (520.0) 591.0 (472.8)
GEP660-1 2806A-E18TAG1A LL6114K 1500 660.0 (528.0) 600.0 (480.0)
GEP700-1 2806A-E18TAG2 LL7024H 1500 700.0 (560.0) 635.0 (508.0)

All ratings at 0.8 pf

3-PHASE DIESEL GENERATING SET RATINGS – 60 Hz, 480V


Model Engine Model Standard Generator RPM Standby kVA (kW) Prime kVA (kW)
400 Series
GEP13.5-4 403D-15G LL1014H 1800 16.2 (13.0) 15.0 (12.0)
GEP18-4 404D-22G1 LL1014L 1800 21.3 (17.0) 19.4 (15.5)
GEP22-4 404D-22G LL1014N 1800 25.0 (20.0) 22.5 (18.0)
1103 Series
GEP33-3 1103A-33G1 LL1014S 1800 37.5 (30.0) 33.8 (27.0)
GEP50-7 1103A-33TG1 LL2014C 1800 56.3 (45.0) 50.0 (40.0)
GEP55-3 1103A-33TG2 LL2014D 1800 62.5 (50.0) 56.3 (45.0)
GEP65-9 1103A-33TG2 LL2014H 1800 75.0 (60.0) 68.8 (55.0)
1104 Series
GEP44-9* 1104-44G LL2014C 1800 50.0 (40.0) 45.0 (36.0)
GEP65-11* 1104A-44TG1 LL2014C 1800 75.0 (60.0) 68.8 (55.0)
GEP88-3 1104A-44TG2 LL2014L 1800 100.0 (80.0) 90.0 (72.0)
GEP110-4 1104C-TAG2 LL3014B 1800 125.0 (100.0) 113.0 (90.4)
1006 Series
GEP150-1 1006TAG LL3014F 1800 165.0 (132.0) 150.0 (120.0)
1106 Series
GEP200-4 1106C-E66TAG4 LL5014F 1800 218.8 (175.0) 196.9 (157.5)
1306 Series
GEH220-2 1306C-E87TAG4 LL5014F 1800 250.0 (200.0) 225.0 (180.0)
2506 Series
GEP563-1 2506A-E15TAG3 LL6114D 1800 563.0 (450.4) 513.0 (410.4)
GEP625-1 2506A-E15TAG4 LL6114F 1800 625.0 (500.0) 563.0 (450.4)
2806 Series
GEP750-1 2806A-E18TAG3 LL7024J 1800 750.0 (600.0) 675.0 (540.0)

*Latin American Models. All ratings at 0.8 pf


Exclusively from your Cat® dealer

SINGLE PHASE DIESEL GENERATING SET RATINGS – 50 Hz, 220-240V


Model Engine Model Standard Generator RPM Standby kVA (kW) Prime kVA (kW)

400 Series
GEP7.5SP2 403D-15G LLB1114D 1500 7.5 (7.5) 6.8 (6.8)
GEP11SP4 403D-15G LLB1014H 1500 11.0 (11.0) 10.0 (10.0)
GEP14SP4 404D-22G1 LLB1014L 1500 14.0 (14.0) 13.0 (13.0)
GEP16SP4 404D-22G LLB1014N 1500 16.5 (16.5) 15.0 (15.0)
1103 Series
GEP26SP3 1103A-33G1 LLB1014S 1500 26.0 (26.0) 24.0 (24.0)
GEP26SP4 1103C-33G2/3 LLB1014S 1500 26.0 (26.0) 24.0 (24.0)
GEP35SP4 1103C-33TG2/3 LL2014H 1500 35.0 (35.0) 32.0 (32.0)
GEP35SP9 1103A-33TG1 LL2014H 1500 35.0 (35.0) 32.0 (32.0)
GEP50SP9 1103A-33TG2 LL2014J 1500 50.0 (50.0) 45.0 (45.0)
1104 Series
GEP35SP11* 1104A-44G LL2014H 1500 35.0 (35.0) 32.0 (32.0)
GEP50SP4 1104C-44TG2/3 LL2014J 1500 50.0 (50.0) 45.0 (45.0)
GEP50SP11* 1104A-44TG1 LL2014J 1500 50.0 (50.0) 45.0 (45.0)
GEP80SP4 1104C-TAG2 LL3014F 1500 80.0 (80.0) 72.0 (72.0)

*Latin American Models. All ratings at 1.0 pf

SINGLE PHASE DIESEL GENERATING SET RATINGS – 60 Hz, 240V


Engine Standard Standby Prime
Model RPM
Model Generator kVA (kW) kVA (kW)
400 Series
GEP11SP4 403D-15G LLB1014H 1800 13.0 (13.0) 12.0 (12.0)
GEP14SP4 404D-22G1 LLB1014L 1800 17.0 (17.0) 15.5 (15.5)
GEP16SP4 404D-22G LLB1014N 1800 20.0 (20.0) 18.0 (18.0)
1103 Series
GEP35SP9 1103A-33TG1 LL2014H 1800 40.0 (40.0) 36.0 (36.0)
GEP35SP11 1104A-44G LL2014H 1800 40.0 (40.0) 36.0 (36.0)
GEP50SP9 1103A-33TG2 LL2014J 1800 55.0 (55.0) 50.0 (50.0)
1104 Series
GEP35SP11* 1104A-44G LL2014H 1800 40.0 (40.0) 36.0 (36.0)
GEP50SP11* 1104A-44TG1 LL2014J 1800 50.0 (50.0) 45.0 (45.0)
GEP80SP4 1104C-44TAG2 LL3014F 1800 80.0 (80.0) 72.0 (72.0)

*Latin American Models.

Information contained in this publication may be considered confidential. www.OlympianPower.com


www.Cat-ElectricPower.com
Market: International Discretion is recommended when distributing.
Materials and specifications are subject to change without notice. © 2010 Caterpillar