LT-DC-LE130733-1-CI-503, RevF
LT-DC-LE130733-1-CI-503, RevF
14
REVISIONS
L&T CONSTRUCTION
CONTRACTOR
WATER & RENEWABLE ENERGY
LT DC LE130733 1 CI 503 1 of 28 F
PROJECT :SAGARDIGHI THERMAL POWER PROJECT , UNIT 3 & 4 (2x500 MW) PHASE-II PLANT WATER
LTCD-WET-EDRC-C&I
SYSTEM(SGPWS-2)
LARSEN & TOUBRO LTD
PREPARED BY : RSK
CLIENT: WEST BENGAL POWER DEVELOPMENT CORPORATION LIMITED
CHECKED BY : SK
REVISION NO: F
DOC NO :LT-DC-LE130733-1-CI-503 DOCUMENT NAME: INPUT/OUTPUT LIST-INTAKE PUMPHOUSE
DATE: 17/09/2014
SL INST /EQPT ALARM
INST / EQPT DESCRIPTION SERVICE DESCRIPTION REF. P&ID NO/ SLD NO SOURCE DESTINATION TYPE OF I/O TRIP REMARKS
NO TAG NO. INDICATION
INPUT/OUTPUT DETAILS
PROCESS INPUT/OUTPUT LIST
DIGITAL INPUT - (FIELD INSTRUMENTS, MOV's & LT Pumps)
LT-DG-LE130733-01-
1 PS-001 Pressure Switch VT Pump discharge (VT-01) FIELD PLC DI
M003.REV.D
Differential Pressure
4 DPIS-001 Strainer inlet/Outlet - do - FIELD PLC DI TWS VENDOR SCOPE
Switch
DT Pump discharge valve 001 LT-DG-LE130733-01-
5 XL-MBFV-001-LR Motorised valve 001 FIELD PLC DI
Local/Remote feedback M003.REV.A
DT Pump discharge valve 001
6 XL-MBFV-001-DIS Motorised valve 001 - do - FIELD PLC DI
distrubance feedback
DT Pump discharge valve 001
7 XL-MBFV-001-LSO Motorised valve 001 - do - FIELD PLC DI
LSO feedback
DT Pump discharge valve 001
8 XL-MBFV-001-LSC Motorised valve 001 - do - FIELD PLC DI
LSC feedback
DT Pump discharge valve 002
9 XL-MBFV-002-LR Motorised valve 002 - do - FIELD PLC DI
Local/Remote feedback
DT Pump discharge valve 002
10 XL-MBFV-002-DIS Motorised valve 002 - do - FIELD PLC DI
distrubance feedback
DT Pump discharge valve 002
11 XL-MBFV-002-LSO Motorised valve 002 - do - FIELD PLC DI
LSO feedback
DT Pump discharge valve 002
12 XL-MBFV-002-LSC Motorised valve 002 - do - FIELD PLC DI
LSC feedback
VT Pump discharge valve 003
13 XL-MBFV-003-LR Motorised valve 003 - do - FIELD PLC DI
Local/Remote feedback
VT Pump discharge valve 003
14 XL-MBFV-003-DIS Motorised valve 003 - do - FIELD PLC DI
distrubance feedback
VT Pump discharge valve 003
15 XL-MBFV-003-LSO Motorised valve 003 - do - FIELD PLC DI
LSO feedback
VT Pump discharge valve 003
16 XL-MBFV-003-LSC Motorised valve 003 - do - FIELD PLC DI
LSC feedback
VT Pump discharge valve 004
17 XL-MBFV-004-LR Motorised valve 004 - do - FIELD PLC DI
Local/Remote feedback
VT Pump discharge valve 004
18 XL-MBFV-004-DIS Motorised valve 004 - do - FIELD PLC DI
distrubance feedback
VT Pump discharge valve 004
19 XL-MBFV-004-LSO Motorised valve 004 - do - FIELD PLC DI
LSO feedback
VT Pump discharge valve 004
20 XL-MBFV-004-LSC Motorised valve 004 - do - FIELD PLC DI
LSC feedback
VT Pump discharge valve 005
21 XL-MBFV-005-LR Motorised valve 005 - do - FIELD PLC DI
Local/Remote feedback
25 XL-HOPV-001-LR Hydrauli valve 001 Header Valve 001 Local/Remote - do - FIELD PLC DI
28 XL-HOPV-001-LSC Hydrauli valve 001 Header Valve 001 Close feedback - do - FIELD PLC DI
29 XL-HOPV-001-LSO Hydrauli valve 001 Header Valve 001 Open feedback - do - FIELD PLC DI
31 XL-HOPV-001-LOK Hydrauli valve 001 Header Valve 001 Locked - do - FIELD PLC DI
32 XL-HOPV-001-OLT Hydrauli valve 001 Header Valve 001 Overload Trip - do - FIELD PLC DI
33 XL-HOPV-001-OLL Hydrauli valve 001 Header Valve 001 Oil Level Low - do - FIELD PLC DI
75 HS-DTP01-ST Desilt pump1 Desilt pump1 Start command - do - PLC 415V Swgr DO
76 HS-DTP01-SP Desilt pump1 Desilt pump1 stop command - do - PLC 415V Swgr DO
77 HS-DTP02-ST Desilt pump2 Desilt pump2 Start command - do - PLC 415V Swgr DO
78 HS-DTP02-SP Desilt pump2 Desilt pump2 stop command - do - PLC 415V Swgr DO
80 RTD1-VT1-R WDG Vertical Pump1 VT Pump1 R2-Phase Winding - do - FIELD PLC RTD
81 RTD1-VT1-R WDG Vertical Pump1 VT Pump1 R3-Phase Winding - do - FIELD TS RTD As per clause no 7.03.04 ,
V.IIF/S-II:8, One set of RTD's
shall be wired to Temperature
82 RTD1-VT1-R WDG Vertical Pump1 VT Pump1 R4-Phase Winding - do - FIELD TS RTD Scanner of Motor feeder panel.
83 RTD1-VT1-Y WDG Vertical Pump1 VT Pump1 Y1-Phase Winding - do - FIELD PLC RTD
84 RTD1-VT1-Y WDG Vertical Pump1 VT Pump1 Y2-Phase Winding - do - FIELD PLC RTD
85 RTD1-VT1-Y WDG Vertical Pump1 VT Pump1 Y3-Phase Winding - do - FIELD TS RTD As per clause no 7.03.04 ,
V.IIF/S-II:8, One set of RTD's
shall be wired to Temperature
86 RTD1-VT1-Y WDG Vertical Pump1 VT Pump1 Y4-Phase Winding - do - FIELD TS RTD Scanner of Motor feeder panel.
87 RTD1-VT1-B WDG Vertical Pump1 VT Pump1 B1-Phase Winding - do - FIELD PLC RTD
88 RTD1-VT1-B WDG Vertical Pump1 VT Pump1 B2-Phase Winding - do - FIELD PLC RTD
89 RTD1-VT1-B WDG Vertical Pump1 VT Pump1 B3-Phase Winding - do - FIELD TS RTD As per clause no 7.03.04 ,
V.IIF/S-II:8, One set of RTD's
shall be wired to Temperature
90 RTD1-VT1-B WDG Vertical Pump1 VT Pump1 B4-Phase Winding - do - FIELD TS RTD Scanner of Motor feeder panel.
91 RTD1-VT1-DE Vertical Pump1 VT Pump1 Driving End Bearing1 - do - FIELD PLC RTD
95 RTD2-VT2-R WDG Vertical Pump 2 VT Pump 2 R1-Phase Winding - do - FIELD PLC RTD
96 RTD2-VT2-R WDG Vertical Pump 2 VT Pump 2 R2-Phase Winding - do - FIELD PLC RTD
97 RTD2-VT2-R WDG Vertical Pump 2 VT Pump 2 R3-Phase Winding - do - FIELD TS RTD As per clause no 7.03.04 ,
V.IIF/S-II:8, One set of RTD's
shall be wired to Temperature
98 RTD2-VT2-R WDG Vertical Pump 2 VT Pump 2 R4-Phase Winding - do - FIELD TS RTD Scanner of Motor feeder panel.
99 RTD2-VT2-Y WDG Vertical Pump 2 VT Pump 2 Y1-Phase Winding - do - FIELD PLC RTD
100 RTD2-VT2-Y WDG Vertical Pump 2 VT Pump 2 Y2-Phase Winding - do - FIELD PLC RTD
101 RTD2-VT2-Y WDG Vertical Pump 2 VT Pump 2 Y3-Phase Winding - do - FIELD TS RTD As per clause no 7.03.04 ,
V.IIF/S-II:8, One set of RTD's
shall be wired to Temperature
102 RTD2-VT2-Y WDG Vertical Pump 2 VT Pump 2 Y4-Phase Winding - do - FIELD TS RTD Scanner of Motor feeder panel.
103 RTD2-VT2-B WDG Vertical Pump 2 VT Pump 2 B1-Phase Winding - do - FIELD PLC RTD
104 RTD2-VT2-B WDG Vertical Pump 2 VT Pump 2 B2-Phase Winding - do - FIELD PLC RTD
105 RTD2-VT2-B WDG Vertical Pump 2 VT Pump 2 B3-Phase Winding - do - FIELD TS RTD As per clause no 7.03.04 ,
V.IIF/S-II:8, One set of RTD's
shall be wired to Temperature
106 RTD2-VT2-B WDG Vertical Pump 2 VT Pump 2 B4-Phase Winding - do - FIELD TS RTD Scanner of Motor feeder panel.
107 RTD2-VT2-DE Vertical Pump 2 VT Pump 2 Driving End Bearing1 - do - FIELD PLC RTD
108 RTD2-VT2-DE Vertical Pump 2 VT Pump 2 Driving End Bearing2 - do - FIELD TS RTD
111 RTD3-VT3-R WDG Vertical Pump 3 VT Pump 3 R1-Phase Winding - do - FIELD PLC RTD
112 RTD3-VT3-R WDG Vertical Pump 3 VT Pump 3 R2-Phase Winding - do - FIELD PLC RTD
113 RTD3-VT3-R WDG Vertical Pump 3 VT Pump 3 R3-Phase Winding - do - FIELD TS RTD As per clause no 7.03.04 ,
V.IIF/S-II:8, One set of RTD's
shall be wired to Temperature
114 RTD3-VT3-R WDG Vertical Pump 3 VT Pump 3 R4-Phase Winding - do - FIELD TS RTD Scanner of Motor feeder panel.
115 RTD3-VT3-Y WDG Vertical Pump 3 VT Pump 3 Y1-Phase Winding - do - FIELD PLC RTD
116 RTD3-VT3-Y WDG Vertical Pump 3 VT Pump 3 Y2-Phase Winding - do - FIELD PLC RTD
117 RTD3-VT3-Y WDG Vertical Pump 3 VT Pump 3 Y3-Phase Winding - do - FIELD TS RTD As per clause no 7.03.04 ,
V.IIF/S-II:8, One set of RTD's
shall be wired to Temperature
118 RTD3-VT3-Y WDG Vertical Pump 3 VT Pump 3 Y4-Phase Winding - do - FIELD TS RTD Scanner of Motor feeder panel.
119 RTD3-VT3-B WDG Vertical Pump 3 VT Pump 3 B1-Phase Winding - do - FIELD PLC RTD
120 RTD3-VT3-B WDG Vertical Pump 3 VT Pump 3 B2-Phase Winding - do - FIELD PLC RTD
121 RTD3-VT3-B WDG Vertical Pump 3 VT Pump 3 B3-Phase Winding - do - FIELD TS RTD As per clause no 7.03.04 ,
V.IIF/S-II:8, One set of RTD's
shall be wired to Temperature
122 RTD3-VT3-B WDG Vertical Pump 3 VT Pump 3 B4-Phase Winding - do - FIELD TS RTD Scanner of Motor feeder panel.
123 RTD3-VT3-DE Vertical Pump 3 VT Pump 3 Driving End Bearing1 - do - FIELD PLC RTD
124 RTD3-VT3-DE Vertical Pump 3 VT Pump 3 Driving End Bearing2 - do - FIELD TS RTD
10 VCB-I/C1-CL 11KV Incomer -1 CB Close Command - do - PLC 11 KV Swgr DO Redundant Digital Output as per
Clause 8.01.01 (iv) Contract
11 VCB-I/C1-OP 11KV Incomer -1 CB Open Command - do - PLC 11 KV Swgr DO technical specifications.
LT-DG-LE130733-01- 11KV
13 VCB-I/C1-VT 11KV Incomer -1 R -Phase Voltage PLC AI 4-20mA
E402.REV.C (page 1 of 3) Swgr
11KV
14 VCB-I/C1-AT 11KV Incomer -1 R -Phase Current - do - PLC AI 4-20mA
Swgr
11KV
15 VCB-I/C1-VT 11KV Incomer -1 Y -Phase Voltage - do - PLC AI 4-20mA
Swgr
Analog inputs from CT of each
11KV
16 VCB-I/C1-AT 11KV Incomer -1 Y -Phase Current - do - PLC AI 4-20mA phase & VT of each phase. As per
Swgr
the clause 3.01.05
11KV
17 VCB-I/C1-VT 11KV Incomer -1 B -Phase Voltage - do - PLC AI 4-20mA
Swgr
11KV
18 VCB-I/C1-AT 11KV Incomer -1 B -Phase Current - do - PLC AI 4-20mA
Swgr
11KV
19 VCB-I/C1-WT 11KV Incomer -1 Watt Trasducer Input - do - PLC AI 4-20mA
Swgr
29 VCB-I/C2-CL 11KV Incomer -2 VCB Incomer-2 Close Command - do - PLC 11 KV Swgr DO Redundant Digital Output as per
Clause 8.01.01 (iv) Contract
30 VCB-I/C2-OP 11KV Incomer -2 VCB Incomer-2 Open Command - do - PLC 11 KV Swgr DO technical specifications.
LT-DG-LE130733-01- 11KV
32 VCB-I/C2-VT 11KV Incomer -2 R -Phase Voltage PLC AI 4-20mA
E402.REV.C (page 1 of 3) Swgr
11KV
33 VCB-I/C2-AT 11KV Incomer -2 R -Phase Current - do - PLC AI 4-20mA
Swgr
11KV
34 VCB-I/C2-VT 11KV Incomer -2 Y -Phase Voltage - do - PLC AI 4-20mA
Swgr
Analog inputs from CT of each
11KV
35 VCB-I/C2-AT 11KV Incomer -2 Y -Phase Current - do - PLC AI 4-20mA phase & VT of each phase. As per
Swgr
the clause 3.01.05
11KV
36 VCB-I/C2-VT 11KV Incomer -2 B -Phase Voltage - do - PLC AI 4-20mA
Swgr
11KV
37 VCB-I/C2-AT 11KV Incomer -2 B -Phase Current - do - PLC AI 4-20mA
Swgr
11KV
38 VCB-I/C2-WT 11KV Incomer -2 Watt Trasducer Input - do - PLC AI 4-20mA
Swgr
50 VCB-BC-CL 11KV Bus Coupler VCB Close Command - do - PLC 11 KV Swgr DO Redundant Digital Output as per
Clause 8.01.01 (iv) Contract
51 VCB-BC-OP 11KV Bus Coupler VCB Open Command - do - PLC 11 KV Swgr DO technical specifications.
LT-DG-LE130733-01- 11KV
53 VCB-BC-VT 11KV Bus Coupler R -Phase Voltage PLC AI 4-20mA
E402.REV.C (page 1 of 3) Swgr
11KV
54 VCB-BC-AT 11KV Bus Coupler R -Phase Current - do - PLC AI 4-20mA
Swgr
11KV
55 VCB-BC-VT 11KV Bus Coupler Y -Phase Voltage - do - PLC AI 4-20mA Analog inputs from CT of each
Swgr
phase & VT of each phase. As per
11KV the clause 3.01.05
56 VCB-BC-AT 11KV Bus Coupler Y -Phase Current - do - PLC AI 4-20mA
Swgr
11KV
57 VCB-BC-VT 11KV Bus Coupler B -Phase Voltage - do - PLC AI 4-20mA
Swgr
11KV
58 VCB-BC-AT 11KV Bus Coupler B -Phase Current - do - PLC AI 4-20mA
Swgr
11KV Bus A -PT 11KV
59 11KV-BUSA-VT Bus PT transducer Output - do - PLC AI 4-20mA
Transducer Swgr
11KV
60 11KV-BUSA-TP 11KV Bus A MCB Bus MCB Trip - do - PLC DI
Swgr
11KV Analog inputs from each BUS PT
61 11KV-BUSA-UV 11KV Bus A MCB Bus Undervoltage Relay - do - PLC DI & since fuse fail not avail, Digital
Swgr
Input for MCB trip feedback as
RIVER WATER INTAKE PUMP HOUSE INPUT OUTPUT LIST per clause 3.01.05 (d). Please
accept.
PROJECT :SAGARDIGHI THERMAL POWER PROJECT , UNIT 3 & 4 (2x500 MW) PHASE-II PLANT WATER
LTCD-WET-EDRC-C&I
SYSTEM(SGPWS-2)
LARSEN & TOUBRO LTD
PREPARED BY : RSK
CLIENT: WEST BENGAL POWER DEVELOPMENT CORPORATION LIMITED
CHECKED BY : SK
REVISION NO: F
DOC NO :LT-DC-LE130733-1-CI-503 DOCUMENT NAME: INPUT/OUTPUT LIST-INTAKE PUMPHOUSE
DATE: 17/09/2014
SL INST /EQPT ALARM
INST / EQPT DESCRIPTION SERVICE DESCRIPTION REF. P&ID NO/ SLD NO SOURCE DESTINATION TYPE OF I/O TRIP REMARKS
NO TAG NO. INDICATION Analog inputs from each BUS PT
INPUT/OUTPUT DETAILS & since fuse fail not avail, Digital
Input for MCB trip feedback as
11KV Bus B -PT 11KV per clause 3.01.05 (d). Please
62 11KV-BUSB-VT Bus PT transducer Output - do - PLC AI 4-20mA
Transducer Swgr accept.
11KV
63 11KV-BUSB-TP 11KV Bus A MCB Bus MCB Trip - do - PLC DI
Swgr
11KV
64 11KV-BUSB-UV 11KV Bus A MCB Bus Undervoltage Relay - do - PLC DI
Swgr
HT TRANSFORMER FEEDERS (11/3.3KV & 11/0.415KV)
LT-DG-LE130733-01- 11KV
1 VCB3-OP 11/3.3 KV AUX T/f -1 Circuit Breaker Open feedback PLC DI
E402.REV.C (page 1 of 3) Swgr
11KV
2 VCB3-CL 11/3.3 KV AUX T/f -1 Circuit Breaker Close feedback - do - PLC DI
Swgr
CB in Local/Remote, 11KV
3 VCB3-LR 11/3.3 KV AUX T/f -1 - do - PLC DI
Test/Service, Spring Charge Swgr
11KV Revised as per clause no.
4 VCB3-PO 11/3.3 KV AUX T/f -1 CB Protection operated - do - PLC DI 3.01.05, V.IIE/S-III : 59 & 60
Swgr
w.r.t. Incomer and Bus coupler,
11KV Bus tie, Bus PT of 11 kV switch
5 VCB3-DCF 11/3.3 KV AUX T/f -1 DC Supply failed - do - PLC DI
Swgr gear
11KV
6 VCB3-UV 11/3.3 KV AUX T/f -1 CB tripped due to Undervoltage - do - PLC DI
Swgr
11KV
7 VCB3-TCU 11/3.3 KV AUX T/f -1 CB Trip Circuit Unhealthy - do - PLC DI
Swgr
CB Restricted Earth Fault 11KV
8 VCB3-REF 11/3.3 KV AUX T/f -1 - do - PLC DI
operated Swgr
11KV
11 VCB3-AT 11/3.3 KV AUX T/f -1 R -Phase Current - do - PLC AI 4-20mA
Swgr
11KV
12 VCB3-AT 11/3.3 KV AUX T/f -1 Y -Phase Current - do - PLC AI 4-20mA
Swgr
11KV
13 VCB3-AT 11/3.3 KV AUX T/f -1 B -Phase Current - do - PLC AI 4-20mA
Swgr
11KV
14 VCB3-WT 11/3.3 KV AUX T/f -1 Watt Trasducer Input - do - PLC AI 4-20mA
Swgr
LT-DG-LE130733-01- 11KV
15 VCB4-OP 11/3.3 KV AUX T/f -2 Circuit Breaker Open feedback PLC DI
E402.REV.C (page 1 of 3) Swgr
11KV
16 VCB4-CL 11/3.3 KV AUX T/f -2 Circuit Breaker Close feedback - do - PLC DI
Swgr
CB in Local/Remote, 11KV
17 VCB4-LR 11/3.3 KV AUX T/f -2 - do - PLC DI
Test/Service, Spring Charge Swgr
11KV Revised as per clause no.
19 VCB4-PO 11/3.3 KV AUX T/f -2 CB Protection operated - do - PLC DI 3.01.05, V.IIE/S-III : 59 & 60
Swgr
w.r.t. Incomer and Bus coupler,
11KV Bus tie, Bus PT of 11 kV switch
20 VCB4-DCF 11/3.3 KV AUX T/f -2 DC Supply failed - do - PLC DI
Swgr gear
11KV
26 VCB4-AT 11/3.3 KV AUX T/f -2 R -Phase Current - do - PLC AI 4-20mA
Swgr
11KV
27 VCB4-AT 11/3.3 KV AUX T/f -2 Y -Phase Current - do - PLC AI 4-20mA
Swgr
11KV
28 VCB4-AT 11/3.3 KV AUX T/f -2 B -Phase Current - do - PLC AI 4-20mA
Swgr
11KV
29 VCB4-WT 11/3.3 KV AUX T/f -2 Watt Trasducer Input - do - PLC AI 4-20mA
Swgr
LT-DG-LE130733-01- 11KV
30 VCB2-OP 11/0.415 KV DIS T/f -1 Circuit Breaker Open feedback PLC DI
E402.REV.C (page 1 of 3) Swgr
11KV
31 VCB2-CL 11/0.415 KV DIS T/f -1 Circuit Breaker Close feedback - do - PLC DI
Swgr
CB in Local/Remote, 11KV
32 VCB2-LR 11/0.415 KV DIS T/f -1 - do - PLC DI
Test/Service, Spring Charge Swgr
11KV Revised as per clause no.
33 VCB2-PO 11/0.415 KV DIS T/f -1 CB Protection operated - do - PLC DI 3.01.05, V.IIE/S-III : 59 & 60
Swgr
w.r.t. Incomer and Bus coupler,
11KV Bus tie, Bus PT of 11 kV switch
34 VCB2-DCF 11/0.415 KV DIS T/f -1 DC Supply failed - do - PLC DI
Swgr gear
11KV
35 VCB2-UV 11/0.415 KV DIS T/f -1 CB tripped due to Undervoltage - do - PLC DI
Swgr
11KV
36 VCB2-TCU 11/0.415 KV DIS T/f -1 CB Trip Circuit Unhealthy - do - PLC DI
Swgr
CB Restricted Earth Fault 11KV
37 VCB2-REF 11/0.415 KV DIS T/f -1 - do - PLC DI
operated Swgr
11KV
40 VCB2-AT 11/0.415 KV DIS T/f -1 R -Phase Current - do - PLC AI 4-20mA
Swgr
11KV
41 VCB2-AT 11/0.415 KV DIS T/f -1 Y -Phase Current - do - PLC AI 4-20mA
Swgr
11KV
42 VCB2-AT 11/0.415 KV DIS T/f -1 B -Phase Current - do - PLC AI 4-20mA
Swgr
11KV
43 VCB2-WT 11/0.415 KV DIS T/f -1 Watt Trasducer Input - do - PLC AI 4-20mA
Swgr
LT-DG-LE130733-01- 3.3KV
1 VCB-I/C1-OP 3.3KV Incomer -1 Circuit Breaker Open feedback PLC DI
E402.REV.C (page 1 of 3) Swgr
3.3KV
2 VCB-I/C1-CL 3.3KV Incomer -1 Circuit Breaker Close feedback - do - PLC DI
Swgr
CB in Local/Remote, 3.3KV
3 VCB-I/C1-LR 3.3KV Incomer -1 - do - PLC DI Revised as per clause no.
Test/Service, Spring Charge Swgr
3.01.05, V.IIE/S-III : 59 & 60
3.3KV
4 VCB-I/C1-PO 3.3KV Incomer -1 CB Protection operated - do - PLC DI w.r.t. Incomer and Bus coupler,
Swgr
Bus tie, Bus PT of 3.3 KV switch
3.3KV gear
5 VCB-I/C1-DCF 3.3KV Incomer -1 DC Supply failed - do - PLC DI
Swgr
3.3KV
6 VCB-I/C1-UV 3.3KV Incomer -1 CB tripped due to Undervoltage - do - PLC DI
Swgr
3.3KV
7 VCB-I/C1-TCU 3.3KV Incomer -1 CB Trip Circuit Unhealthy - do - PLC DI
Swgr
9 VCB-I/C1-CL 3.3KV Incomer -1 CB Close Command - do - PLC 3.3KV Swgr DO Redundant Digital Output as per
Clause 8.01.01 (iv) Contract
10 VCB-I/C1-OP 3.3KV Incomer -1 CB Open Command - do - PLC 3.3KV Swgr DO technical specifications.
LT-DG-LE130733-01- 3.3KV
12 VCB-I/C1-VT 3.3KV Incomer -1 R -Phase Voltage PLC AI 4-20mA
E402.REV.C (page 1 of 3) Swgr
3.3KV
13 VCB-I/C1-AT 3.3KV Incomer -1 R -Phase Current - do - PLC AI 4-20mA
Swgr
3.3KV
14 VCB-I/C1-VT 3.3KV Incomer -1 Y -Phase Voltage - do - PLC AI 4-20mA
Swgr
Analog inputs from CT of each
3.3KV
15 VCB-I/C1-AT 3.3KV Incomer -1 Y -Phase Current - do - PLC AI 4-20mA phase & VT of each phase. As per
Swgr
the clause 3.01.05
3.3KV
16 VCB-I/C1-VT 3.3KV Incomer -1 B -Phase Voltage - do - PLC AI 4-20mA
Swgr
3.3KV
17 VCB-I/C1-AT 3.3KV Incomer -1 B -Phase Current - do - PLC AI 4-20mA
Swgr
3.3KV
18 VCB-I/C1-WT 3.3KV Incomer -1 Watt Trasducer Input - do - PLC AI 4-20mA
Swgr
26 VCB-I/C2-OP 3.3KV Incomer -2 VCB Incomer-2 Open Command - do - PLC 3.3KV Swgr DO
27 VCB-I/C2-CL 3.3KV Incomer -2 VCB Incomer-2 Close Command - do - PLC 3.3KV Swgr DO Redundant Digital Output as per
Clause 8.01.01 (iv) Contract
28 VCB-I/C2-OP 3.3KV Incomer -2 VCB Incomer-2 Open Command - do - PLC 3.3KV Swgr DO technical specifications.
29 VCB-I/C2-CL 3.3KV Incomer -2 VCB Incomer-2 Close Command - do - PLC 3.3KV Swgr DO
LT-DG-LE130733-01- 3.3KV
30 VCB-I/C2-VT 3.3KV Incomer -2 R -Phase Voltage PLC AI 4-20mA
E402.REV.C (page 1 of 3) Swgr
3.3KV
31 VCB-I/C2-AT 3.3KV Incomer -2 R -Phase Current - do - PLC AI 4-20mA
Swgr
3.3KV
32 VCB-I/C2-VT 3.3KV Incomer -2 Y -Phase Voltage - do - PLC AI 4-20mA
Swgr
Analog inputs from CT of each
3.3KV phase & VT of each phase. As per
33 VCB-I/C2-AT 3.3KV Incomer -2 Y -Phase Current - do - PLC AI 4-20mA
Swgr the clause 3.01.05
3.3KV
34 VCB-I/C2-VT 3.3KV Incomer -2 B -Phase Voltage - do - PLC AI 4-20mA
Swgr
3.3KV
35 VCB-I/C2-AT 3.3KV Incomer -2 B -Phase Current - do - PLC AI 4-20mA
Swgr
3.3KV
36 VCB-I/C2-WT 3.3KV Incomer -2 Watt Trasducer Input - do - PLC AI 4-20mA
Swgr
47 VCB-BC-OP 3.3KV Bus Coupler VCB Open Command - do - PLC 3.3KV Swgr DO
48 VCB-BC-CL 3.3KV Bus Coupler VCB Close Command - do - PLC 3.3KV Swgr DO Redundant Digital Output as per
Clause 8.01.01 (iv) Contract
49 VCB-BC-OP 3.3KV Bus Coupler VCB Open Command - do - PLC 3.3KV Swgr DO technical specifications.
50 VCB-BC-CL 3.3KV Bus Coupler VCB Close Command - do - PLC 3.3KV Swgr DO
LT-DG-LE130733-01- 3.3KV
51 VCB-BC-VT 3.3KV Bus Coupler R -Phase Voltage PLC AI 4-20mA
E402.REV.C (page 1 of 3) Swgr
3.3KV
52 VCB-BC-AT 3.3KV Bus Coupler R -Phase Current - do - PLC AI 4-20mA
Swgr
3.3KV
53 VCB-BC-VT 3.3KV Bus Coupler Y -Phase Voltage - do - PLC AI 4-20mA Analog inputs from CT of each
Swgr
phase & VT of each phase. As per
3.3KV the clause 3.01.05
54 VCB-BC-AT 3.3KV Bus Coupler Y -Phase Current - do - PLC AI 4-20mA
Swgr
3.3KV
55 VCB-BC-VT 3.3KV Bus Coupler B -Phase Voltage - do - PLC AI 4-20mA
Swgr
3.3KV
56 VCB-BC-AT 3.3KV Bus Coupler B -Phase Current - do - PLC AI 4-20mA
Swgr
LT-DG-LE130733-01- 3.3KV
1 VCB1-OP 3.3KV Motor Feeder-1 Circuit Breaker Open feedback PLC DI
E402.REV.C (page 2 of 3) Swgr
3.3KV
2 VCB1-CL 3.3KV Motor Feeder-1 Circuit Breaker Close feedback - do - PLC DI
Swgr
CB in Local/Remote, 3.3KV Revised as per clause no.
3 VCB1-LR 3.3KV Motor Feeder-1 - do - PLC DI 3.01.05, V.IIE/S-III : 59 & 60
Test/Service, Spring Charge Swgr
w.r.t. Incomer and Bus coupler,
3.3KV Bus tie, Bus PT of 3.3KV switch
4 VCB1-PO 3.3KV Motor Feeder-1 CB Protection operated - do - PLC DI
Swgr gear
3.3KV
5 VCB1-DCF 3.3KV Motor Feeder-1 CB DC Supply failed - do - PLC DI
Swgr
3.3KV
6 VCB1-UV 3.3KV Motor Feeder-1 CB tripped due to Undervoltage - do - PLC DI
Swgr
7 VCB1-OP 3.3KV Motor Feeder-1 VT Pump- 1 Start Command - do - PLC 3.3KV Swgr DO
DIGITAL OUTPUTS
8 VCB1-CL 3.3KV Motor Feeder-1 VT Pump- 1 Stop Command - do - PLC 3.3KV Swgr DO
3.3KV
9 VCB1-AT 3.3KV Motor Feeder-1 R -Phase Current - do - PLC AI 4-20mA
Swgr Load current on each phase as
3.3KV per Clause no. 3.01.05(e), V.IIE/S-
10 VCB1-AT 3.3KV Motor Feeder-1 Y -Phase Current - do - PLC AI 4-20mA
Swgr III : 60 w.r.t. 3.3 KV Motor
3.3KV Feeders.
11 VCB1-AT 3.3KV Motor Feeder-1 B -Phase Current - do - PLC AI 4-20mA
Swgr
18 VCB2-ST 3.3KV Motor Feeder-2 VT Pump- 2 Start Command - do - PLC 3.3KV Swgr DO
DIGITAL OUTPUTS
19 VCB2-SP 3.3KV Motor Feeder-2 VT Pump- 2 Stop Command - do - PLC 3.3KV Swgr DO
3.3KV
20 VCB2-AT 3.3KV Motor Feeder-2 R -Phase Current - do - PLC AI 4-20mA
Swgr Load current on each phase as
3.3KV per Clause no. 3.01.05(e), V.IIE/S-
21 VCB2-AT 3.3KV Motor Feeder-2 Y -Phase Current - do - PLC AI 4-20mA
Swgr III : 60 w.r.t. 3.3 KV Motor
3.3KV Feeders.
22 VCB2-AT 3.3KV Motor Feeder-2 B -Phase Current - do - PLC AI 4-20mA
Swgr
LT-DG-LE130733-01- 3.3KV
23 VCB3-OP 3.3KV Motor Feeder-3 Circuit Breaker Open feedback PLC DI
E402.REV.C (page 2 of 3) Swgr
3.3KV
24 VCB3-CL 3.3KV Motor Feeder-3 Circuit Breaker Close feedback - do - PLC DI
Swgr
CB in Local/Remote, 3.3KV Revised as per clause no.
25 VCB3-LR 3.3KV Motor Feeder-3 - do - PLC DI 3.01.05, V.IIE/S-III : 59 & 60
Test/Service, Spring Charge Swgr
w.r.t. Incomer and Bus coupler,
3.3KV Bus tie, Bus PT of 11 kV switch
26 VCB3-PO 3.3KV Motor Feeder-3 CB Protection operated - do - PLC DI
Swgr gear
3.3KV
27 VCB3-DCF 3.3KV Motor Feeder-3 CB DC Supply failed - do - PLC DI
Swgr
3.3KV
28 VCB3-UV 3.3KV Motor Feeder-3 CB tripped due to Undervoltage - do - PLC DI
Swgr
29 VCB3-ST 3.3KV Motor Feeder-3 VT Pump- 3 Start Command - do - PLC 3.3KV Swgr DO
DIGITAL OUTPUTS
30 VCB3-SP 3.3KV Motor Feeder-3 VT Pump- 3 Stop Command - do - PLC 3.3KV Swgr DO
LT-DG-LE130733-01- 415V
1 ACB-I/C1-OP 415V Incomer -1 Circuit Breaker Open feedback PLC DI
E402.REV.C (page 3 of 3) Swgr
415V
2 ACB-I/C1-CL 415V Incomer -1 Circuit Breaker Close feedback - do - PLC DI
Swgr
CB in Local/Remote, 415V
3 ACB-I/C1-LR 415V Incomer -1 - do - PLC DI Revised as per clause no.
Test/Service, Spring Charge Swgr
3.01.05, V.IIE/S-III : 59 & 60
415V
5 ACB-I/C1-PO 415V Incomer -1 CB Protection operated - do - PLC DI w.r.t. Incomer and Bus coupler,
Swgr
Bus tie, Bus PT of 415V switch
415V gear
6 ACB-I/C1-DCF 415V Incomer -1 DC Supply failed - do - PLC DI
Swgr
415V
7 ACB-I/C1-UV 415V Incomer -1 CB tripped due to Undervoltage - do - PLC DI
Swgr
415V
8 ACB-I/C1-TCU 415V Incomer -1 CB Trip Circuit Unhealthy - do - PLC DI
Swgr
11 ACB-I/C1-CL 415V Incomer -1 CB Close Command - do - PLC 415V Swgr DO Redundant Digital Output as per
Clause 8.01.01 (iv) Contract
12 ACB-I/C1-OP 415V Incomer -1 CB Open Command - do - PLC 415V Swgr DO technical specifications.
30 ACB-I/C2-OP 415V Incomer -2 VCB Incomer-2 Open Command - do - PLC 415V Swgr DO
31 ACB-I/C2-CL 415V Incomer -2 VCB Incomer-2 Close Command - do - PLC 415V Swgr DO Redundant Digital Output as per
Clause 8.01.01 (iv) Contract
32 ACB-I/C2-OP 415V Incomer -2 VCB Incomer-2 Open Command - do - PLC 415V Swgr DO technical specifications.
33 ACB-I/C2-CL 415V Incomer -2 VCB Incomer-2 Close Command - do - PLC 415V Swgr DO
52 ACB-BC-OP 415V Bus Coupler VCB Open Command - do - PLC 415V Swgr DO
53 ACB-BC-CL 415V Bus Coupler VCB Close Command - do - PLC 415V Swgr DO Redundant Digital Output as per
Clause 8.01.01 (iv) Contract
54 ACB-BC-OP 415V Bus Coupler VCB Open Command - do - PLC 415V Swgr DO technical specifications.
55 ACB-BC-CL 415V Bus Coupler VCB Close Command - do - PLC 415V Swgr DO
LT-DG-LE130733-01- 415V
56 ACB-BC-VT 415V Bus Coupler R -Phase Voltage PLC AI 4-20mA
E402.REV.C (page 3 of 3) Swgr
415V
57 ACB-BC-AT 415V Bus Coupler R -Phase Current - do - PLC AI 4-20mA
Swgr
415V
58 ACB-BC-VT 415V Bus Coupler Y -Phase Voltage - do - PLC AI 4-20mA Analog inputs from CT of each
Swgr
phase & VT of each phase. As per
415V the clause 3.01.05
59 ACB-BC-AT 415V Bus Coupler Y -Phase Current - do - PLC AI 4-20mA
Swgr
415V
60 ACB-BC-VT 415V Bus Coupler B -Phase Voltage - do - PLC AI 4-20mA
Swgr
415V
61 ACB-BC-AT 415V Bus Coupler B -Phase Current - do - PLC AI 4-20mA
Swgr
415V Bus A -PT 415V
62 415V-BUSA Bus PT transducer Output - do - PLC AI 4-20mA
Transducer Swgr
415V
63 415V-BUSA 415V Bus A MCB Bus MCB Trip - do - PLC DI
Swgr
415V Analog inputs from each BUS PT
64 415V-BUSA 415V Bus A MCB Bus Undervoltage Relay - do - PLC DI & since fuse fail not avail, Digital
Swgr
input for MCB trip feedback as
415V Bus B -PT 415V per clause 3.01.05 (d). Please
65 415V-BUSB Bus PT transducer Output - do - PLC AI 4-20mA
Transducer Swgr accept.
415V
66 415V-BUSB 415V Bus A MCB Bus MCB Trip - do - PLC DI
Swgr
415V
67 415V-BUSA 415V Bus A MCB Bus Undervoltage Relay - do - PLC DI
Swgr
LT-DG-LE130733-01- 415V
1 ACB-I/C1-OP MLDB Incomer -1 Circuit Breaker Open feedback PLC DI
E402.REV.C (page 1 of 3) Swgr
415V
2 ACB-I/C1-CL MLDB Incomer -1 Circuit Breaker Close feedback - do - PLC DI
Swgr
CB in Local/Remote, 415V Revised as per clause no.
3 ACB-I/C1-L/R MLDB Incomer -1 - do - PLC DI 3.01.05, V.IIE/S-III : 59 & 60
Test/Service, Spring Charge Swgr
w.r.t. Incomer and Bus coupler,
415V Bus tie, Bus PT of 11 kV switch
4 ACB-I/C1-DCF MLDB Incomer -1 DC Supply failed - do - PLC DI
Swgr gear
415V
5 ACB-I/C1-TCU MLDB Incomer -1 CB Trip Circuit Unhealthy - do - PLC DI
Swgr
415V
6 ACB-I/C1-PO MLDB Incomer -1 CB Protection Operated - do - PLC DI
Swgr
7 ACB-I/C1-OP MLDB Incomer -1 CB Open Command - do - PLC 415V Swgr DO Redundant Digital Output as per
Clause 8.01.01 (iv) Contract
8 ACB-I/C1-CL MLDB Incomer -1 CB Close Command - do - PLC 415V Swgr DO technical specifications.
415V
9 ACB-I/C1-AT MLDB Incomer -1 AT Current Feedback - do - PLC AI Revised
Swgr
LT-DG-LE130733-01- 415V
10 ACB-I/C2-OP MLDB Incomer -2 Circuit Breaker Open feedback PLC DI
E402.REV.C (page 1 of 3) Swgr
415V
11 ACB-I/C2-CL MLDB Incomer -2 Circuit Breaker Close feedback - do - PLC DI
Swgr
CB in Local/Remote, 415V Revised as per clause no.
12 ACB-I/C2-L/R MLDB Incomer -2 - do - PLC DI 3.01.05, V.IIE/S-III : 59 & 60
Test/Service, Spring Charge Swgr
w.r.t. Incomer and Bus coupler,
415V Bus tie, Bus PT of 11 kV switch
13 ACB-I/C2-DCF MLDB Incomer -2 CB DC Supply failed - do - PLC DI
Swgr gear
415V
14 ACB-I/C2-PO MLDB Incomer -2 CB Protection Operated - do - PLC DI
Swgr
415V
15 ACB-I/C2-TCU MLDB Incomer -2 CB Trip Circuit Unhealthy - do - PLC DI
Swgr
16 ACB-I/C2-OP MLDB Incomer -2 ACB Incomer-2 Open Command - do - PLC 415V Swgr DO Redundant Digital Output as per
Clause 8.01.01 (iv) Contract
17 ACB-I/C2-CL MLDB Incomer -2 ACB Incomer-2 Close Command - do - PLC 415V Swgr DO technical specifications.
415V
18 ACB-I/C2-AT MLDB Incomer -2 AT Current Feedback - do - PLC AI Revised
Swgr
DCDB CHARGER
LT-DG-LE130733-01-
1 DCDB-CHG1-FLT DCDB CHARGER -1 Float Charger Fault (AC Supply) DCDB PLC DI
E485. REV.C (page 1 of 1)
Float Cum Boost Charger Fault
2 DCDB-CHG1-FLT DCDB CHARGER -1 - do - DCDB PLC DI
(DC Supply)
4 DCDB-CHG2-FLT DCDB CHARGER -2 Float Charger Fault (AC Supply) - do - DCDB PLC DI
1 HT-TRF1-OL 11/3.3 KV/HT TRF -1 Oil Temperature Alarm AUX TRF PLC DI
2 HT-TRF1-OL 11/3.3 KV/HT TRF -1 Oil Temperature Trip - do - AUX TRF PLC DI
3 HT-TRF1-WDG 11/3.3 KV/HT TRF -1 Winding Temperature Alarm - do - AUX TRF PLC DI
4 HT-TRF1-WDG 11/3.3 KV/HT TRF -1 Winding Temperature Trip - do - AUX TRF PLC DI
8 HT-TRF1-MOG 11/3.3 KV/HT TRF -1 MOG Oil Level Low Alarm - do - AUX TRF PLC DI
11 HT-TRF2-OL 11/3.3 KV/HT TRF -2 Oil Temperature Alarm - do - AUX TRF PLC DI
12 HT-TRF2-OL 11/3.3 KV/HT TRF -2 Oil Temperature Trip - do - AUX TRF PLC DI
13 HT-TRF2-WDG 11/3.3 KV/HT TRF -2 Winding Temperature Alarm - do - AUX TRF PLC DI
14 HT-TRF2-WDG 11/3.3 KV/HT TRF -2 Winding Temperature Trip - do - AUX TRF PLC DI
18 HT-TRF2-MOG 11/3.3 KV/HT TRF -2 MOG Oil Level Low Alarm - do - AUX TRF PLC DI
21 LT-TRF1-WD-AL 11/0.415 KV/HT TRF -1 Widning Temperature High Alarm MCC PLC DI
22 HT-TRF1-WD-TP 11/0.415 KV/HT TRF -1 Winding Temperature High Trip - do - MCC PLC DI
DIST
23 LT-TRF1-WDG 11/0.415 KV/HT TRF -1 Widning Temperature - do - PLC AI
TRF
24 LT-TRF2-WD-AL 11/0.415 KV/HT TRF -2 Widning Temperature High Alarm - do - MCC PLC DI
25 HT-TRF2-WD-TP 11/0.415 KV/HT TRF -2 Winding Temperature High Trip - do - MCC PLC DI
DIST
26 LT-TRF1-WDG 11/0.415 KV/HT TRF -2 Widning Temperature - do - PLC AI
TRF
LIST OF LEGENDS