2 Endress+Hauser
Deltapilot M PROFIBUS PA Table of contents
Table of contents
1 Document information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Document function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.1 Product identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.3 CE mark, Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.1 Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.2 Storage and transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.3 Installation conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.4 General installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.5 Installing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.6 Mounting of the profile seal for universal process mounting adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.7 Closing the housing cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.8 Post-installation check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.1 Connecting the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.2 Connecting the measuring unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.3 Potential equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.4 Overvoltage protection (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.5 Post-connection check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.1 Operating options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.2 Operation without an operating menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
6.3 Operation with an operating menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.4 PROFIBUS PA communication protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Endress+Hauser 3
Document information Deltapilot M PROFIBUS PA
1 Document information
1.1 Document function
These Operating Instructions contain all the information that is required in various phases of
the life cycle of the device: from product identification, incoming acceptance and storage, to
mounting, connection, operation and commissioning through to troubleshooting, maintenance
and disposal.
Symbol Meaning
DANGER!
DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
seriousor fatal injury.
A0011189-DE
WARNING!
WARNING This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
seriousor fatal injury.
A0011190-DE
CAUTION!
CAUTION This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minoror medium injury.
A0011191-DE
NOTICE!
NOTICE This symbol contains information on procedures and other facts which do not result in
personalinjury.
A0011192-DE
4 Endress+Hauser
Deltapilot M PROFIBUS PA Document information
Symbol Meaning
Allen key
A0011221
Hexagon wrench
A0011222
Symbol Meaning
Permitted
Indicates procedures, processes or actions that are permitted.
A0011182
Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011184
Tip
Indicates additional information.
A0011193
Reference to documentation
A0015482
Reference to page
A0015484
Reference to graphic
A0015487
A0018343
Visual inspection
A0015502
Indicates how to navigate to the parameter using the display and operating module
A0015502
Endress+Hauser 5
Document information Deltapilot M PROFIBUS PA
Indicates how to navigate to the parameter using operating tools (e.g. FieldCare)
A0015502
Symbol Meaning
A, B, C, D, ... Views
Symbol Meaning
Safety instructions
Observe the safety instructions contained in the associated Operating Instructions.
A0019159
6 Endress+Hauser
Deltapilot M PROFIBUS PA Basic safety instructions
Endress+Hauser 7
Basic safety instructions Deltapilot M PROFIBUS PA
8 Endress+Hauser
Deltapilot M PROFIBUS PA Identification
3 Identification
3.1 Product identification
The following options are available for identification of the measuring device:
• Nameplate specifications
• Order code with breakdown of the device features on the delivery note
• Enter serial numbers from nameplates in W@M Device Viewer
(www.endress.com/deviceviewer): All information about the measuring device is displayed.
For an overview of the technical documentation provided, enter the serial number from the
nameplates in the W@M Device Viewer (www.endress.com/deviceviewer).
4 Installation
4.1 Incoming acceptance
• Check the packaging and the contents for damage.
• Check the shipment, make sure nothing is missing and that the scope of supply matches your
order.
Endress+Hauser 9
Installation Deltapilot M PROFIBUS PA
4.2.2 Transport
! WARNING
Incorrect transportation
Housing, diaphragm and capillaries may become damaged, and there is a risk of injury!
‣ Transport the measuring device to the measuring point in its original packaging or by the
process connection.
‣ Follow the safety instructions and transport conditions for devices weighing more than 18
kg (39.6 lbs).
‣ Do not use capillaries as a carrying aid for the diaphragm seals.
! WARNING
Risk of damage to process connection!
Risk of injury!
‣ Sensor modules with PVDF process connections with threaded connection must be installed
with the mounting bracket provided!
10 Endress+Hauser
Deltapilot M PROFIBUS PA Installation
! WARNING
Material fatigue from pressure and temperature!
Risk of injury if parts burst! The thread can become loose if exposed to high pressure and
temperatures.
‣ The integrity of the thread must be checked regularly and the thread may need to be
re-tightened with the maximum tightening torque of 7 Nm (5.16 lbf ft). Teflon tape is
recommended for sealing the ½" NPT thread.
4.5 Installing
• Due to the orientation of the Deltapilot M, there may be a shift in the zero point, i.e. when the
container is empty or partially full, the measured value does not display zero. You can correct
this zero point shift ä 26, Section "Function of the operating elements" or ä 39,
Section 8.3 "Position zero adjustment".
• The local display can be rotated in 90° stages.
• Endress+Hauser offers a mounting bracket for installing on pipes or walls.
ä 15, Section 4.5.6 "Wall and pipe mounting (optional)".
• Keep the pressure compensation and GORE-TEX® filter (1) free from contamination.
Endress+Hauser 11
Installation Deltapilot M PROFIBUS PA
• The device must be installed as follows in order to comply with the cleanability requirements
of the ASME-BPE (Part SD Cleanibility).:
4.5.2 FMB50
Level measurement
• Always install the device below the lowest measuring point.
• Do not install the device at the following positions:
– in the filling curtain
– in the tank outflow
– in the suction area of a pump
– or at a point in the tank that can be affected by pressure pulses from the agitator
• The calibration and functional test can be carried out more easily if you mount the device
downstream of a shutoff device.
• Deltapilot M must be included in the insulation for media that can harden when cold.
12 Endress+Hauser
Deltapilot M PROFIBUS PA Installation
4.5.3 FMB51/FMB52/FMB53
• When mounting rod and cable versions, make sure that the probe head is located at a point
as free as possible from flow. To protect the probe from impact resulting from lateral
movement, mount the probe in a guide tube (preferably made of plastic) or secure it with a
clamping fixture.
• In the case of devices for hazardous areas, comply strictly with the safety instructions when
the housing cover is open.
• The length of the extension cable or the probe rod is based on the planned level zero point.
The height of the protective cap must be taken into consideration when designing the layout
of the measuring point. The level zero point (E) corresponds to the position of the process
isolating diaphragm.
Level zero point = E; top of the probe = L.
17 (0.67)
E
L
Endress+Hauser 13
Installation Deltapilot M PROFIBUS PA
A0018793
Fig. 1: Mounting with a suspension clamp
1 Extension cable
2 Suspension clamp
3 Clamping jaws
14 Endress+Hauser
Deltapilot M PROFIBUS PA Installation
NOTICE
Distorted measurement results.
The seal is not allowed to press on the process isolating diaphragm as this could affect the
measurement result.
‣ Ensure that the seal is not touching the process isolating diaphragm.
1 2
A0017743
Fig. 2:
1 Process isolating diaphragm
2 Seal
Mounting bracket
See operating instructions.
Endress+Hauser 15
Installation Deltapilot M PROFIBUS PA
5
4
3
2
1
7
r ³ 120 (4.72)
A0028494
Fig. 3: "Separate housing" version
1 In the case of the "separate housing" version, the sensor is delivered with the process connection and cable ready
mounted.
2 Cable with connection jack
3 Pressure compensation
4 Connector
5 Locking screw
6 Housing mounted with housing adapter, included
7 Mounting bracket provided, suitable for pipe and wall mounting (for pipes from 1 1/4" up to 2" diameter)
Maßeinheit mm (in)
16 Endress+Hauser
Deltapilot M PROFIBUS PA Installation
Endress+Hauser 17
Installation Deltapilot M PROFIBUS PA
A0028497
Fig. 4: Closing the cover
The cover for the electronics compartment is tightened by hand at the housing until the stop.
The screw serves as DustEx protection (only available for devices with DustEx approval).
O Are the measuring point identification and labeling correct (visual inspection)?
18 Endress+Hauser
Deltapilot M PROFIBUS PA Electrical connection
5 Electrical connection
5.1 Connecting the device
! WARNING
Supply voltage might be connected!
Risk of electric shock and/or explosion!
‣ Ensure that no uncontrolles processes are activated in the system.
‣ Switch off the supply voltage before connecting the device.
‣ When using the measuring device in hazardous areas, installation must comply with the
corresponding national standards and regulations and the Safety Instructions or Installation
or Control Drawings.
‣ A suitable circuit breaker must be provided for the device in accordance with
IEC/EN61010.
‣ Devices with integrated overvoltage protection must be grounded.
‣ Protective circuits against reverse polarity, HF influences and overvoltage peaks are
integrated.
Connect the device in the following order:
1. Check that the supply voltage corresponds to the supply voltage indicated on the nameplate.
2. Switch off the supply voltage before connecting the device.
3. Remove housing cover.
4. Guide the cable through the gland. Preferably use a twisted, shielded two-wire cable.
5. Connect the device in accordance with the following diagram.
6. Screw down the housing cover.
7. Switch on the supply voltage.
Endress+Hauser 19
Electrical connection Deltapilot M PROFIBUS PA
1
4
- +
2
A0029967
PROFIBUS PA electrical connection
1 External ground terminal
2 Grounding terminal
3 Supply voltage: 9 to 32 VDC (Segment coupler)
4 Terminals for supply voltage and signal
1 Signal +
2 Not assigned
4 3 3 Signal –
4 Earth
1 2
A0011175
20 Endress+Hauser
Deltapilot M PROFIBUS PA Electrical connection
For further information on the network structure and grounding and for further bus system
components such as bus cables, see the relevant documentation, e.g. Operating Instructions
BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning" and the PNO
Guideline.
Electronic version
PROFIBUS PA, 9 to 32 V DC
version for non-hazardous areas
5.2.3 Terminals
• Supply voltage and internal ground terminal: 0.5 to 2.5 mm2 (20 to 14 AWG)
• External ground terminal: 0.5 to 4 mm2 (20 to 12 AWG)
Endress+Hauser 21
Electrical connection Deltapilot M PROFIBUS PA
For further information on the cable specifications, see Operating Instructions BA00034S
"PROFIBUS DP/PA: Guidelines for planning and commissioning", the PNO Guideline 2.092
"PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).
22 Endress+Hauser
Deltapilot M PROFIBUS PA Operation
6 Operation
6.1 Operating options
6.1.1 Operation without an operating menu
1
damp 2 on
not used 3
delta p on:Ö
on: off:SW 4
only on:P2=High off:SW 5 off
on SW
off HW
Address
– + E
Endress+Hauser 23
Operation Deltapilot M PROFIBUS PA
24 Endress+Hauser
Deltapilot M PROFIBUS PA Operation
2
1 Zero
Display
3
1
damp 2 on
not used 3
delta p on:Ö off:SW 4
only on:P2= High off:SW 5 off
on SW
off HW
Address
on
5 4
1 2 3 4 5 off
SW / P2=High
damping
SW /
10 9 8 7 6
A0023126
Fig. 5: PROFIBUS PA electronic insert
1 Green LED to indicate successful operation
2 Operating key for position zero adjustment (Zero) or reset
3 Slot for optional local display
4 DIP-switch for bus address SW / HW
5 DIP-switch for hardware address
6+7 DIP switch only for Deltabar M
8 Not used
9 DIP switch for switching damping on/off
10 DIP switch for locking/unlocking parameters relevant to the measured value
Endress+Hauser 25
Operation Deltapilot M PROFIBUS PA
4 SW/
(Deltabar)
5 SW/P2= High
(Deltabar)
1) The value for the delay time can be configured via the operating menu ("Setup" -> "Damping").
Factory setting: = 2 s or as per order specifications.
"Zero" Reset
pressed for at least All parameters are reset to the order configuration.
12 seconds
26 Endress+Hauser
Deltapilot M PROFIBUS PA Operation
If operation is locked by means of the DIP switch, you can only unlock operation again by means
of the DIP switch. If operation is locked by means of the operating menu, you can only unlock
operation again using the operating menu.
Operator Operators are responsible for the devices during normal "operation". This is usually limited to
reading process values either directly at the device or in a control room. If the work with the
devices extends beyond value read-off tasks, the tasks involve simple, application-specific
functions that are used in operation. Should an error occur, these users simple forward the
information on the errors but do not intervene themselves.
Service Service engineers usually work with the devices in the phases following device commissioning.
engineer/technician They are primarily involved in maintenance and troubleshooting activities for which simple
settings have to be made at the device.
Technicians work with the devices over the entire life cycle of the product.
Thus, commissioning and advanced settings and configurations are some of the tasks they have
to carry out.
Expert Experts work with the devices over the entire product life cycle, but their device requirements
are often extremely high. Individual parameters/functions from the overall functionality of the
devices are required for this purpose time and again.
In addition to technical, process-oriented tasks, experts can also perform administrative tasks
(e.g. user administration).
"Experts" can avail of the entire parameter set.
Operator Language Only consists of the "Language" parameter (000) where the operating language
for the device is specified.
The language can always be changed even if the device is locked.
Endress+Hauser 27
Operation Deltapilot M PROFIBUS PA
Operator Display/operat. Contains parameters that are needed to configure the measured value display
(selecting the values displayed, display format, etc.).
With this submenu, users can change the measured value display without
affecting the actual measurement.
Service Setup Contains all the parameters that are needed to commission measuring
engineer/technic operations. This submenu has the following structure:
ian • Standard setup parameters
A wide range of parameters, which can be used to configure a typical
application, is available at the start. The measuring mode selected determines
which parameters are available.
After making settings for all these parameters, the measuring operation
should be completely configured in the majority of cases.
• "Extended setup" submenu
The "Extended setup" submenu contains additional parameters for more
in-depth configuration of the measurement operation to convert the
measured value and to scale the output signal.
This menu is split into additional submenus depending on the measuring
mode selected.
Service Diagnosis Contains all the parameters that are needed to detect and analyze operating
engineer/technic errors. This submenu has the following structure:
ian • Diagnostic list
Contains up to 10 error messages currently pending.
• Event logbook
Contains the last 10 error messages (no longer pending).
• Instrument info
Contains information on the device identification.
• Measured values
Contains all the current measured values
• Simulation
Is used to simulate pressure, level and alarm/warning.
• Reset
Expert Expert Contains all the parameters of the device (including those in one of the
submenus). The "Expert" submenu is structured by the function blocks of the
device. It thus contains the following submenus:
• System
Contains general device parameters that neither affect measurement nor
integration into a distributed control system.
• Measurement
Contains all the parameters for configuring the measurement.
• Communication
Contains the parameters of the PROFIBUS PA interface.
• Application
Contains all the parameters for configuring the functions that go beyond the
actual measurement (e.g. totalizer).
• Diagnosis
Contains all the parameters that are needed to detect and analyze operating
errors.
28 Endress+Hauser
Deltapilot M PROFIBUS PA Operation
Direct access (119) Use this function to enter a parameter code for direct access.
Entry
User input:
• Enter the desired parameter code.
Menu path: Factory setting:
Expert Direct access 0
1. 2. 3.
4. 5. 6.
A0028500
Endress+Hauser 29
Operation Deltapilot M PROFIBUS PA
Functions:
• 8-digit measured value display including sign and decimal point.
• Bar graph as graphic display of the standardized value of the Analog Input Block (see also
operating instructions)
• Three keys for operation
• Simple and complete menu guidance as parameters are split into several levels and groups
• Each parameter is given a 3-digit parameter code for easy navigation
• Possibility of configuring the display to suit individual requirements and preferences, such as
language, alternating display, display of other measured values such as sensor temperature,
contrast setting.
• Comprehensive diagnostic functions (fault and warning message etc.)
F 3
1
4
– + E 6
7 5
A0030013
Fig. 6: Display
1 Main line
2 Value
3 Symbol
4 Unit
5 Bar graph
6 Information line
7 Operating keys
The following table illustrates the symbols that can appear on the onsite display. Four symbols
can occur at one time.
Symbol Meaning
Lock symbol
The operation of the device is locked. To unlock the device, ä 33, Locking/unlocking
operation.
Communication symbol
Data transfer via communication
30 Endress+Hauser
Deltapilot M PROFIBUS PA Operation
Symbol Meaning
– Confirm entry
F – Jump to the next item
– Selection of a menu item and activation of the editing mode
ESC functions:
O S and
– Exit the edit mode for a parameter without saving the changed value.
– You are in a menu at a selection level. Each time you press the keys simultaneously,
you go up a level in the menu.
Endress+Hauser 31
Operation Deltapilot M PROFIBUS PA
Deutsch
English
4 5 0 0 . 0 0 0 mbar
32 Endress+Hauser
Deltapilot M PROFIBUS PA Operation
The new value for the upper range value is 50.0 mbar (0.75 psi).
6 5 . 0 0 0 mbar – You exit the edit mode for the parameter with .
– You can get back to the editing mode with or .
Confirm
Abort
Confirm
Endress+Hauser 33
Operation Deltapilot M PROFIBUS PA
Zero
Display 2 + 8 = 10
1
damp 2 on
not used 3
delta p on:Ö off:SW 4
only on:P2= High off:SW 5 off
on SW
on
off HW SW
Address
– + E off
HW
1 2 3 4 5 6 7 8
Address
1 2
A0030184
Fig. 7: Setting the device address via DIP switches
1 If necessary, remove onsite display (optional)
2 Set the hardware address via the DIP switches
Hardware addressing
A hardware address is set as follows:
1. Set the DIP switch 8 (SW/HW) to "Off".
2. Set the address with DIP switches 1 to 7.
3. The change of address takes effect after 10 seconds. The device is restarted.
34 Endress+Hauser
Deltapilot M PROFIBUS PA Commissioning without an operating menu
DIP switch 1 2 3 4 5 6 7
Software addressing
A software address is set as follows:
1. Set the DIP switch 8 (SW/HW) to "On" (factory setting).
2. The device is restarted.
3. The device reports its current address. Factory setting: 126
4. Set the address via the configuration program.
See the next section for information on how to enter a new address via FieldCare.
For other operating programs, see the corresponding operating manual.
! WARNING
Exceeding the maximum allowable working pressure!
Risk of injury due to bursting of parts! Warning messages are generated if pressure is too high.
‣ If a pressure smaller than the minimum permitted pressure or greater than the maximum
permitted pressure is present at the device, the following messages are output in succession
(depending on the setting in the "Alarm behavior" (050) parameter):
"S140 Working range P" or "F140 Working range P"
"S841 Sensor range" or "F841 Sensor range"
"S971 Adjustment"
Use the device only within the sensor range limits.
NOTICE
Shortfall of the allowable working pressure!
Output of messages if pressure is too low.
‣ If a pressure smaller than the minimum permitted pressure or greater than the maximum
permitted pressure is present at the device, the following messages are output in succession
(depending on the setting in the "Alarm behavior" (050) parameter):
"S140 Working range P" or "F140 Working range P"
"S841 Sensor range" or "F841 Sensor range"
Endress+Hauser 35
Commissioning without an operating menu Deltapilot M PROFIBUS PA
"S971 Adjustment"
Use the device only within the sensor range limits.
Yes No
1)
Applied pressure for position adjustment has been Applied pressure for position adjustment has not been
accepted. accepted. Observe the input limits.
36 Endress+Hauser
Deltapilot M PROFIBUS PA Commissioning with an operating menu (onsite display/FieldCare)
! WARNING
Exceeding the maximum allowable working pressure!
Risk of injury due to bursting of parts! Warning messages are generated if pressure is too high.
‣ If a pressure smaller than the minimum permitted pressure or greater than the maximum
permitted pressure is present at the device, the following messages are output in succession
(depending on the setting in the "Alarm behavior" (050) parameter):
"S140 Working range P" or "F140 Working range P"
"S841 Sensor range" or "F841 Sensor range"
"S971 Adjustment"
Use the device only within the sensor range limits.
NOTICE
Shortfall of the allowable working pressure!
Output of messages if pressure is too low.
‣ If a pressure smaller than the minimum permitted pressure or greater than the maximum
permitted pressure is present at the device, the following messages are output in succession
(depending on the setting in the "Alarm behavior" (050) parameter):
"S140 Working range P" or "F140 Working range P"
"S841 Sensor range" or "F841 Sensor range"
"S971 Adjustment"
Use the device only within the sensor range limits.
Endress+Hauser 37
Commissioning with an operating menu (onsite display/FieldCare) Deltapilot M PROFIBUS PA
8.2 Commissioning
Commissioning comprises the following steps:
1. Function check ä 37
2. Selecting the language, measuring mode and pressure unit ä 38
3. Position adjustment ä 39
4. Configuring measurement:
– Pressure measurement ä 51 ff
– Level measurement ä 40 ff
Language selection
38 Endress+Hauser
Deltapilot M PROFIBUS PA Commissioning with an operating menu (onsite display/FieldCare)
Corrected press. (172) Displays the measured pressure after sensor trim and position adjustment.
Display
Menu path:
Setup Corrected press. (172) If this value is not equal to "0", it can be corrected to "0" by the position adjustment.
Pos. zero adjust (007) Position adjustment – the pressure difference between zero (set point) and the
(Gauge pressure sensor) measured pressure need not be known.
Options
Example:
– Measured value = 2.2 mbar (0.032 psi)
Menu path:
– Correct the measured value via the "Pos. zero adjust (007) (Gauge pressure sensor)"
Setup Pos. zero adjust (007)
parameter with the "Confirm" option. This means that you are assigning the value
(Gauge pressure sensor)
0.0 to the pressure present.
– Measured value (after pos. zero adjust) = 0.0 mbar
Options
• Confirm
• Abort
Factory setting:
Abort
Endress+Hauser 39
Commissioning with an operating menu (onsite display/FieldCare) Deltapilot M PROFIBUS PA
Calib. offset (192) (008) Position adjustment – the pressure difference between the set point and the measured
(absolute pressure sensor) pressure must be known.
Entry
Example:
– Measured value = 982.2 mbar (14.25 psi)
Menu path:
– You correct the measured value with the value entered (e.g. 2.2 mbar (0.032 psi))
Setup Calib. offset (192)
via the "Calib. offset (192)" parameter. This means that you are assigning the value
980.0 (14.21 psi) to the pressure present.
– Measured value (after calib. offset) = 980.0 mbar (14.21 psi)
Factory setting:
0.0
Calibration is "In pressure" Via the "Unit before – Calibration with reference The measured value
performed by entering lin (025)" pressure (wet calibration), display and the
two pressure-level parameter: %, level, see ä 41 "Level before lin. (019)"
value pairs. volume or mass – Calibration without parameter display the
units. reference pressure (dry measured value.
calibration), see ä 42
40 Endress+Hauser
Deltapilot M PROFIBUS PA Commissioning with an operating menu (onsite display/FieldCare)
Example:
In this example, the level in a tank should be measured in "m". The maximum level is 3 m (9.8
ft). The pressure range is due to the filling height and the density.
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• The tank can be filled and emptied.
The values entered for "Empty calib. (028)/Full calib. (031)" and the pressures present at the
device must be at least 1% apart. The value will be rejected, and a warning message displayed,
if the values are too close together. Further limit values are not checked; i.e. the values entered
must be appropriate for the sensor and the measuring task so that the measuring device can
measure correctly.
Description
Endress+Hauser 41
Commissioning with an operating menu (onsite display/FieldCare) Deltapilot M PROFIBUS PA
Description
Enter the level value, here 3 m (9.8 ft) for example. A0017658
The pressure value present is assigned to the upper Fig. 9: Calibration with reference pressure –
level value by confirming the value. wet calibration
11 Result:
The measuring range is set for 0 to 3 m (9.8 ft).
The measured variables %, level, volume and mass are available for this level mode.
See operating instructions "Unit before lin (025)".
42 Endress+Hauser
Deltapilot M PROFIBUS PA Commissioning with an operating menu (onsite display/FieldCare)
of 0 liters corresponds to a pressure of 50 mbar (0.72 psi) since the device is mounted below the
start of the level measuring range.
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• This is a theoretical calibration i.e. the pressure and volume values for the lower and upper
calibration point must be known.
• The values entered for "Empty calib. (028)/Full calib. (031)", "Empty pressure (029)/Full
pressure (032)" must be at least 1% apart. The value will be rejected, and a warning message
displayed, if the values are too close together. Further limit values are not checked; i.e. the
values entered must be appropriate for the sensor and the measuring task so that the
measuring device can measure correctly.
• Due to the orientation of the device, there may be pressure shifts in the measured value, i.e.
when the container is empty or partly filled, the measured value is not zero. For information
on how to perform position adjustment, see ä 39, "Position zero adjustment".
Description
Menu path: Setup Extended Setup Level Fig. 10: Calibration without reference pressure –
Unit before lin (025) dry calibration
A See Table, Steps 7 + 8.
B See Table, Steps 9 + 10.
Endress+Hauser 43
Commissioning with an operating menu (onsite display/FieldCare) Deltapilot M PROFIBUS PA
Description
12 Result:
The measuring range is set for 0 to 1000 l (264
gal).
The measured variables %, level, volume and mass are available for this level mode.
See operating instructions "Unit before lin (025)".
44 Endress+Hauser
Deltapilot M PROFIBUS PA Commissioning with an operating menu (onsite display/FieldCare)
Example:
In this example, the volume in a tank should be measured in liters. The maximum volume of
1000 liters (264 gal) corresponds to a level of 4.5 m (14.8 ft). The minimum volume of 0 liters
corresponds to a level of 0.5 m (1.6 ft) since the device is mounted below the start of the level
measuring range.
The density of the medium is 1 g/cm3 (1 SGU).
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• The tank can be filled and emptied.
The values entered for "Empty calib. (028)/Full calib. (031)" and the pressure values present at
the device must be at least 1% apart. The value will be rejected, and a warning message
displayed, if the values are too close together. Further limit values are not checked; i.e. the
values entered must be appropriate for the sensor and the measuring task so that the measuring
device can measure correctly.
Description
5 Select a volume unit via the "Unit before lin (025)" A0031027
Fig. 12: Calibration with reference pressure –
parameter, here "l" (liter) for example.
wet calibration
Menu path: Setup Extended Setup Level A See Table, Step 8.
Unit before lin (025) B See Table, Step 9.
B See Table, Step 9.
Endress+Hauser 45
Commissioning with an operating menu (onsite display/FieldCare) Deltapilot M PROFIBUS PA
Description
12 Result:
The measuring range is set for 0 to 1000 l (264
gal).
The measured variables %, level, volume and mass are available for this level mode operating
instructions "Unit before lin (025)".
46 Endress+Hauser
Deltapilot M PROFIBUS PA Commissioning with an operating menu (onsite display/FieldCare)
• The values entered for "Empty calib. (028)/Full calib. (031)", "Empty height (030)/Full height
(033)" must be at least 1% apart. The value will be rejected, and a warning message displayed,
if the values are too close together. Further limit values are not checked; i.e. the values
entered must be appropriate for the sensor and the measuring task so that the measuring
device can measure correctly.
• Due to the orientation of the device, there may be pressure shifts in the measured value, i.e.
when the container is empty or partly filled, the measured value is not zero. For information
on how to perform position adjustment, see ä 39, "Position zero adjustment".
Endress+Hauser 47
Commissioning with an operating menu (onsite display/FieldCare) Deltapilot M PROFIBUS PA
Description
48 Endress+Hauser
Deltapilot M PROFIBUS PA Commissioning with an operating menu (onsite display/FieldCare)
Description
The measured variables %, level, volume and mass are available for this level mode operating
instructions "Unit before lin (025)".
Endress+Hauser 49
Commissioning with an operating menu (onsite display/FieldCare) Deltapilot M PROFIBUS PA
8.5 Linearization
See operating instructions.
50 Endress+Hauser
Deltapilot M PROFIBUS PA Commissioning with an operating menu (onsite display/FieldCare)
Due to the orientation of the device, there may be pressure shifts in the measured value, i.e. the
measured value is not zero in a pressureless condition. For information on how to perform
position adjustment, see ä 39. Calibration is possible only using FieldCare.
Description
1 Select the "Pressure" measuring mode via the "Measuring mode (005)" parameter.
2 Select a pressure unit via the "Press. eng. unit (125)" parameter, here "mbar" for example.
3 Where necessary scale the "Output value (Out Value)" of the Analog Input Block, see operating instructions,
parameter descriptions for "Proc value scale" and "Output scale".
4 Result:
The measuring range is configured for 0 to +300 mbar (4.35 psi).
Endress+Hauser 51