Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

HTW-2080 T5

MEDIUM-VOLTAGE RANGE
Powered by MITSUBISHI

SERVICE PRP / DCP ESP

POWER kVA 2092 2295

POWER kW 1673 1836

RATED SPEED r.p.m. 1.500

STANDARD VOLTAGE KV 11

AVAILABLE VOLTAGES KV 3,3 · 6 · 6,3 · 6,6 · 10

RATED AT POWER Cos Phi 0,8


FACTOR

MEDIUM-VOLTAGE RANGE OPEN SKID


HIMOINSA Company with quality certification ISO 9001
HIMOINSA gensets are compliant with EC mark which includes the following
directives: OPEN SKID
• 2006/42/CE Machinery safety.
• 2014/30/UE Electromagnetic compatibility.
• 2014/35/UE electrical equipment designed for use within certain voltage limits
• 2000/14/EC Sound Power level. Noise emissions outdoor equipment. (amended by
2005/88/EC) WATER-COOLED
• 97/68/EC Emissions of gaseous and particulate pollutants. (amended by 2012/46/EU)
• EN 12100, EN 13857, EN 60204
• IEC 62271-1 Common specificaction for high voltage switchgear and controlgear
standards
• IEC 60502-1 Power cables with extruded insulation for rated voltages from 1 kV
up to 30 kV
THREE PHASE
Ambient conditions of reference according to ISO 8528-1:2018 normative: 1000 mbar,
25ºC, 30% relative humidity.

Prime Power (PRP): 50 HZ


According to ISO 8528-1:2018, Prime power is the maximum power which a
generating set is capable of delivering continuously whilst supplying a variable
electrical load when operated for an unlimited number of hours per year under the
agreed operating conditions with the maintenance intervals and procedures being
carried out as prescribed by the manufacturer. The permissible average power output DIESEL
(Ppp) over 24 h of operation shall not exceed 70 % of the PRP.

Emergency Standby Power (ESP):


According to ISO 8528-1:2018, Emergency standby power is the maximum power
available during a variable electrical power sequence, under the stated operating
conditions, for which a generating set is capable of delivering in the event of a utility
power outage or under test conditions for up to 200 h of operation per year with the Himoinsa has the right to modify any feature without prior notice.
maintenance intervals and procedures being carried out as prescribed by the
manufacturers. The permissible average power output over 24 h of operation shall not Weights and dimensions based on standard products. Illustrations may
exceed 70 % of the ESP include optional equipment.
Continuous Power (COP): According to Standard ISO 8528-1:2018, this is the Technical data described in this catalogue correspond to the available
maximum power available for continuous loads for unlimited running hours a year information at the moment of printing.
between the maintenance times recommended by the manufacturer under the
environmental conditions established by the same. The illustrations and images are indicative and may not coincide in their
entirety with the product.
Data Center Power (DCP) : Complies with Uptime Institute: Tier III & IV. The
manufacturer declares a load factor for grid failure of 100% per 24h and an average Industrial design under patent.
load factor per year less than 75%. No overload margin available. It can be operated for
an unlimited number of hours per year. Applicable in countries with stable network. If
the model is for DCP application, inform Factory.
G2 class load acceptance in accordance with ISO 8528-5:2018

HIMOINSA HEADQUARTERS:
2022-JUL.-20 14:26

Fábrica: Ctra. Murcia - San Javier, Km. 23,6 | 30730 SAN JAVIER (Murcia) Spain
Tel.+34 968 19 11 28 Fax +34 968 19 12 17 Fax +34 968 19 04 20 |
[email protected] | www.himoinsa.com
Manufacture facilities:
SPAIN • FRANCE • INDIA • CHINA • USA • BRAZIL • ARGENTINA
Subsidiaries:Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
PORTUGAL Fax: +34 968 19
| POLAND 12 17 | Export
| GERMANY Fax +34
| UK 968 19 04 20| | UAE
| SINGAPORE E-mail:[email protected]
| PANAMA | | www.himoinsa.com
DOMINICAN REPUBLIC | ARGENTINA | ANGOLA | SOUTH AFRICA
HTW-2080 T5

Available Voltages

3,3 kV

Prime KVA 2103 Prime KW 1682 Amps 367,9


Standby KVA 2300 Standby KW 1840 Amps 402,4

6 kV

Prime KVA 2100 Prime KW 1680 Amps 202,1


Standby KVA 2300 Standby KW 1840 Amps 221,3

6,3 kV

Prime KVA 2098 Prime KW 1678 Amps 192,3


Standby KVA 2298 Standby KW 1834 Amps 210,6

6,6 kV

Prime KVA 2098 Prime KW 1678 Amps 183,5


Standby KVA 2300 Standby KW 1840 Amps 201,2

10 kV

Prime KVA 2092 Prime KW 1673 Amps 120,8


Standby KVA 2293 Standby KW 1834 Amps 132,4

11 kV

Prime KVA 2092 Prime KW 1673 Amps 109,8


Standby KVA 2295 Standby KW 1836 Amps 120,5

Rated at power factor (Cos Phi) : 0,8


2022-JUL.-20 14:26

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
HTW-2080 T5

Engine Specifications | 1.500 r.p.m.

Rated Output (PRP) / DCP kW 1747 Total oil capacity including L 230
tubes, filters
Rated Output (ESP) kW 1917
Total coolant capacity L 583
Manufacturer MITSUBISHI
Heat dissipated by coolant kW 1248
Model S16R F1PTAW2
Governor Type Electrical
Engine Type 4-stroke diesel
Air Filter Type Dry
Injection Type Direct
Turbocharged and
Aspiration Type after-cooled
Number of cylinders and 16-V
arrangement
Bore and Stroke mm 170 x 180
Displacement L 65,37
Cooling System Water
API CD or CF SAE
Lube Oil Specifications 30 or SAE 40
Compression Ratio 14,0:1

• Oil temperature sensor • 24V electrical system • LOP sender


• Low coolant level sensor • Standard air filter • Electronic governor
• Exhaust gas compensator • Standard fuel filter • Hot parts protection
• Diesel engine • Standard oil filter • Moving parts protection
• 4-stroke cycle • Radiator with pusher fan
• Water-cooled • HTW sender

Generator Specifications | STAMFORD

Manufacturer STAMFORD Self-excited,


Exciter system brushless
Model HV804R
Voltage regulator A.V.R. (Electronic)
Poles No. 4
Bracket type Double drive-shaft
Connection type (standard) Star
Coupling system Elastic Coupling
Insulation Class F class
Standard (Vacuum
Enclosure (according Coating type
IP23 impregnation)
IEC-34-5)

• Self-excited and self-regulated


• IP23 protection
• F class insulation
2022-JUL.-20 14:26

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
HTW-2080 T5

WEIGHT AND DIMENSIONS


Standard Version
Length (L) mm Ask
Height (H) mm Ask
Width (W) mm Ask
Weight with liquids in radiator Kg Ask
and sump
Autonomy (100% PRP) Hours Ask

APPLICATION DATA
EXHAUST SYSTEM NECESSARY AMOUNT OF AIR

Maximum exhaust temperature ºC 510 Intake air flow m³/h 10680

Exhaust Gas Flow m³/min 471 Cooling Air Flow m³/s 37

Maximum allowed back pressure kPa 600 Alternator fan air flow m³/s 3

Heat dissipated by exhaust pipe kW 1845

FUEL CONSUMPTION FUEL SYSTEM

Fuel Consumption ESP l/h 484,49 Fuel Oil Specifications Diesel

Fuel Consumption 100% PRP l/h 438 Maximum power suction pump mm Hg 75

Fuel Consumption 70 % PRP l/h 303,2 Maximum return feed pump mm Hg 150

Fuel Consumption 50 % PRP l/h 220

STARTING SYSTEM

Starting power kW 7,5 x 2

Starting power CV 10,2 x 2

Recommended battery Ah 300

Auxiliary Voltage Vdc 24

Open set version

• Steel chassis • Chassis with integrated fuel tank • Fuel transfer pump (Opcional).
• Emergency stop button • Fuel level gauge • Steel industrial silencer -15db(A)
attenuation (Opcional).
• Oil sump extraction kit • Fuel tank drain plug
• Steel residential silencer -35db(A)
• Anti-vibration shock absorbers attenuation. (Opcional).
2022-JUL.-20 14:26

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
HTW-2080 T5

Electrical system
• Maintenance-free and • Battery charger • Battery charger alternator with
anti-explosion battery ground connection
• Water Jacket Heater
• Battery Switch • Starter battery/ies installed
• Control panel and emergency (cables and bracket included)
• Medium voltage cubicle stop button
separated with overcurrent • Ground connection electrical
protections and measurement installation with connection
transformers ready for ground spike (not
supplied)
2022-JUL.-20 14:26

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
HTW-2080 T5
2022-JUL.-20 14:26

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
HTW-2080 T5
2022-JUL.-20 14:26

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
HTW-2080 T5
2022-JUL.-20 14:26

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
HTW-2080 T5
2022-JUL.-20 14:26

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com
HTW-2080 T5
2022-JUL.-20 14:26

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:[email protected] | www.himoinsa.com