21 14resa Installm 2015-1
21 14resa Installm 2015-1
Models:
14/20RESA
14/20RESAL
Controllers:
RDC2
DC2
TP-6803 1/15j
California Proposition 65
WARNING
Engine exhaust from this product contains chemicals
known to the State of California to cause cancer, birth
defects, or other reproductive harm.
4 TP-6803 1/15
Safety Precautions and Instructions
Heavy Equipment
WARNING
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Do not use lifting eyes.
Lift the generator set using lifting bars
inserted through the lifting holes on
the skid.
TP-6803 1/15 9
Service Assistance
10 TP-6803 1/15
Section 1 Installation
WARNING
1
1
1 2
tp6733
REAR VIEW
1. Air intake
2. Exhaust outlet
1.7.3 Connecting the Fuel Supply Figure 1-8 Holding Fuel Valve to Tighten Fuel
Connections
The dimension drawing in Section 2 shows the location
of the fuel inlet connection. Have the fuel supplier install Open the manual fuel valves and test all fuel
rigid gas piping and a manual fuel shut-off valve. The connections using soapy water. If a leak is found, close
fuel supply line should line up with the generator set fuel the fuel valves, clean the fittings, and apply fresh
inlet and end about 12 inches away to allow connection sealant. Check for fuel leaks again with the generator
with a section of flexible fuel line. Use flexible sections to set running.
prevent fuel line breakage caused by vibration.
Protect all fuel lines from machinery or equipment
Note: Do not bend the flexible fuel line to make up for contact, adverse weather conditions, and environmental
misalignment of the fuel supply line and the damage.
generator set fuel inlet.
17. Run the generator set and check the operation. Figure 1-9 Fuel System, 14RESA/RESAL Equipped
with Fuel Block (built before June 26,
18. Press the OFF button to to shut down the generator 2014)
set.
For natural gas and LPG fuel, orifice fittings are used in
the fuel line. See Figure 1-10. The natural gas orifice
fitting is silver in color and stamped NG. The LPG fitting
is gold in color and stamped LPG. The fittings are
threaded. A straight-blade screwdriver is required to
remove and replace the fittings.
NG LPG
11. Reconnect the generator set engine starting Conversion from LPG to Natural Gas
battery leads, negative (--) lead last.
To convert from LPG to natural gas, repeat the steps
12. Reconnect the utility power to the generator. above, removing the LPG fuel orifice and installing the
NG fitting. Connect DSAI leads 65 and N3 together for
13. Start the generator set by pressing the RUN button natural gas.
on the generator set controller.
Figure 1-12 14RESA/RESAL Fuel System Showing Orifice Fittings (generators built after June 26, 2014)
2. Hose fitting
2. Disconnect the power to the battery charger. 3. Regulator
4. Regulator vent tubes (vent to the outside of the controller)
3. Disconnect the generator set engine starting
Figure 1-13 Fuel Regulator and LPG Orifice,
battery, negative (--) lead first.
20RESA/RESAL
4. Turn off the fuel supply.
1.8.4 Regulator Vent Hose
5. Remove the hose clamp and fuel hose from the
hose fitting. See Figure 1-13. Model 20RESA/RESAL generators are equipped with
fuel regulator vent hoses. Drill or punch two holes in the
6. Insert the LPG orifice into the hose fitting. See enclosure at the locations shown on the template in
Figure 1-13. Appendix B. It may be convenient to cut openings for the
electrical leads at the same time as shown on the
7. Slide the hose onto the hose fitting and secure it
template and in Section 1.9.2.
with the clamp.
Insert the open ends of the hoses through the holes to
8. Connect and turn on the new fuel supply.
the outside of the enclosure as shown in Figure 1-14.
9. Reconnect the generator set engine starting
battery leads, negative (--) lead last.
Row Temp. Rating Copper (Cu) Only Cu/Aluminum (Al) Combinations Al Only
1 60_C (140_F) Use No. * AWG, 60_C wire or Use 60_C wire, either No. * AWG Cu, or No. * Use 60_C wire, No. * AWG or
or use No. * AWG, 75_C wire AWG Al or use 75_C wire, either No. * AWG use 75_C wire, No. * AWG
75_C (167_F) Cu or No. * AWG Al
2 60_C (140_F) Use No. * AWG, 60_C wire Use 60_C wire, either No. * AWG Cu or No. * Use 60_C wire, No. * AWG
AWG Al
3 75_C (167_F) Use No. *[ AWG, 75_C wire Use 75_C wire, either No. *[ AWG Cu or No. Use 75_C wire, No.*[ AWG
*[ AWG Al
4 90_C (194_F) Use No. *[ AWG, 90_C wire Use 90_C wire, either No. *[ AWG Cu or No. Use 90_C wire, No.*[ AWG
*[ AWG Al
* The wire size for 60_C (140_F) wire is not required to be included in the marking. If included, the wire size is based on ampacities for the
wire given in Table 310-16 of the National Electrical Coder, in ANSI/NFPA 70, and on 115% of the maximum current that the circuit carries
under rated conditions. The National Electrical Coder is a registered trademark of the National Fire Protection Association, Inc.
[ Use the larger of the following conductors: the same size conductor as that used for the temperature test or one selected using the
guidelines in the preceding footnote.
Figure 1-15 Terminal Markings for Various Temperature Ratings and Conductors
The National Electrical Coder is a registered trademark of the National Fire Protection Association, Inc.
ADV--8424
3
Note: See Appendix B for a full-scale template
with dimensions.
1. Optional emergency stop switch location. Do not use to
route wiring.
2. Utility voltage electrical lead entry point
3. ATS signal electrical lead entry point
4. 1/2 NPT female fuel inlet
1. Drill holes for the conduit fittings. See Figure 1-16 7. When connections to the terminal block are
and Appendix B for the recommended electrical complete, replace the cover plate.
inlet locations. Feed the cables through the
openings. 4
2. Connect the leads from the transfer switch 3 5
emergency source lugs to the L1, L2, and L3
connections on the generator set terminal block as 2
applicable for single or three-phase applications. 6
See Figure 1-18 and Figure 1-19.
3-Phase
Connect the ATS or remote start/stop switch. Connect Note: Connections 3 and 4 on the generator set are not
the load leads from the generator set to the Emergency used with the Model RXT transfer switch.
source lugs on the ATS. Route low-voltage
communication leads through separate conduit from the Engine start connection for other transfer
AC power and load leads. All connections must comply switches or a remote start/stop switch
with applicable state and local codes.
Connect the engine start leads from the transfer switch
Note: Do not use the Kohlerr Model RRT transfer or remote start switch to terminals 3 and 4 on the
switch with the 14/20RESA or 14/20RESAL terminal block. See Figure 1-22. Route the engine start
generator set. leads through separate conduit from the AC power and
load leads.
1
2
Generator Set
GND Interface Board on the
4 Model RXT Transfer Switch
A A A RXT
RBUS B
B B
Note: Generator set terminal block connections 3 and 4 are NOT USED with the Model RXT ATS.
1. Generator set terminal block. See Figure 2-4 for location. Check the decal on the generator set for terminal block connections.
2. Connect one end of each cable shield to GROUND at the generator set.
3. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable. See Section 1.10.2, Cable Specifications.
4. Leave one end of each cable shield disconnected. If accessory modules (PIM, LCM or load shed kit) are connected, see Section
1.10.3.
Figure 1-21 Model RXT Transfer Switch Communication Connection to Generator Set Terminal Block
A
2 ATS
B
(with engine
PWR
start contacts)
COM
4
3
tp6803
1. Generator Set Terminal Block. See the dimension drawings in Section 2 for location. Check the decal on the generator set for terminal
block connections.
2. Engine start leads 3 and 4. See the ATS manual for cable size specifications.
Figure 1-22 Engine Start Connections with Transfer Switch Models other than Model RXT
1.10.2 Communication Cable and use the second pair for the PWR and COM
Specifications connections.
D For the longer cable runs shown in the last two rows of
RBUS Connections A and B Figure 1-23, use 12 or 14 AWG cable for PWR and
For the RBUS communication connections A and B to COM, and use the 20 AWG communication cable
the Model RXT transfer switch, optional PIM and/or specified above for the A and B connections only. In
optional LCM or load shed kit, use 20 AWG shielded, this case, single-pair communication cable such as
twisted-pair communication cable. Belden #9402 Belden #8762 can be used for the A and B
(two-pair) or Belden #8762 (single-pair) or equivalent connections.
cable is recommended.
1.10.3 System Connections with
For outdoor installations, including those with buried
cables and/or conduit, use outdoor-rated Belden Accessory Modules
#1075A or equivalent 20 AWG shielded, twisted-pair See Figure 1-24 through Figure 1-28 for connection
communication cable. options with accessory modules. Accessory modules
can include one Model RXT transfer switch, one
PWR and COM Connections programmable interface module (PIM) and/or one load
control module (LCM) or load shed kit. Note the cable
For the PWR and COM connections, the cable size and shield connections shown in Figure 1-24.
maximum cable length depends on the number of
modules connected. See Figure 1-23. The maximum cable length depends on the number of
optional modules connected. See Figure 1-23 for the
D For short cable runs shown in the first two rows of
maximum cable lengths with 1, 2, or 3 modules per cable
Figure 1-23, use one pair in the two-pair run.
communication cable for the A and B connections,
Figure 1-23 Total Cable Lengths for PWR and COM Connections
4
2
GND 3
RXT
Generator Set
A A A A
RBUS B B B B
4
3
PIM
1
A A
B B
PWR PWR
COM COM
5
A
B LCM
or load
PWR
shed kit
COM
1. Generator set terminal block. See Figure 2-4 for location. Check the decal on the generator set for terminal block connections.
2. Connect one end of each cable shield to GROUND at the generator set.
3. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable.
4. Connect shields together as shown.
5. Leave one end of each cable shield disconnected at the last device.
GND 3
RXT
Generator Set
A A A A
RBUS B B B B
4
3
PIM
1
A A
B B
PWR PWR
COM COM
5
A
B
LCM
or load
PWR
shed kit
COM
1. Generator set terminal block. See Figure 2-4 for location. Check the decal on the generator set for terminal block connections.
2. Connect one end of each cable shield to GROUND at the generator set.
3. Communication cable Belden #8762 or equivalent 20 AWG shielded, twisted-pair cable (one pair).
4. Connect shields together as shown.
5. Leave one end of each cable shield disconnected at the last device.
6. 12 AWG or 14 AWG leads for PWR and COM.
Figure 1-25 Accessory Module Connections with 12--14 AWG Power Leads
Terminal
Block
LCM
Notes: or load
shed kit
D See Figure 2-4 for terminal block location on generator set. Check
the decal on the generator set for terminal block connections.
Figure 1-26 Accessory Module Connections (three cable runs with one module each)
3
1
2 A
B
SHIELDED
CABLE
Generator Set PWR
COM
A
RBUS
B
3
PWR
12 VDC
COM
A
4
B
3 SHIELDED
CABLE
PWR
COM
tp6803
1. Generator Set Terminal Block. See the dimension drawings in Section 2 for location. Check the decal on the generator set for terminal
block connections.
2. Splice.
3. Connect all of the shield leads on this end to GROUND at the generator set.
PIM
Notes:
D See Figure 2-4 for terminal block location on generator
set. Check the decal on the generator set for terminal
block connections.
D See Section 1.10.2, Cable Specifications.
D See Figure 1-24 for communication connection detail (A
and B, PWR and COM). Connect the cable shield to LCM
ground at the generator set. or load
shed kit
D Use splices or wire nuts to collect multiple leads for
connection to the generator set terminal block. See
Figure 1-27. tp6809
Figure 1-28 Accessory Module Connections (two cable runs with one and two modules shown)
Explosion.
Can cause severe injury or death.
Relays in the battery charger
cause arcs or sparks.
Locate the battery in a well-ventilated
area. Isolate the battery charger from
explosive fumes.
Battery short circuits. Explosion can cause severe injury Use the following procedure to install and connect the
or death. Short circuits can cause bodily injury and/or battery.
equipment damage. Disconnect the battery before generator
set installation or maintenance. Remove all jewelry before
servicing the equipment. Use tools with insulated handles. Battery Installation Procedure
Remove the negative (--) lead first when disconnecting the
battery. Reconnect the negative (--) lead last when 1. Ensure that the starting battery is fully charged
reconnecting the battery. Never connect the negative (--) before placing the battery in service.
battery cable to the positive (+) connection terminal of the
starter solenoid. Do not test the battery condition by shorting 2. Clean the battery posts and/or adapters if
the terminals together. necessary.
Connecting the battery and the battery charger. 3. Install the battery post adapters, if needed.
Hazardous voltage can cause severe injury or death.
Reconnect the battery correctly, positive to positive and 4. Place the battery in the housing.
negative to negative, to avoid electrical shock and damage to
the battery charger and battery(ies). Have a qualified 5. Connect the positive (+) lead to the engine starting
electrician install the battery(ies). battery.
Starting batteries are usually the lead-acid type. Use a
6. Connect the negative (--) lead to the engine starting
12-volt group 51 battery with a minimum rating of 500
battery.
cold cranking amps at 0_F. The generator set uses a
negative ground with a 12-volt engine electrical system. Refer to the generator set operation manual and the
See Figure 1-29 for battery connections. Make sure battery manufacturer’s instructions for battery
that the battery is correctly connected and the terminals maintenance instructions.
are tight.
When power is applied to the RDC2/DC2 controller (that
Note: The generator set will not start and circuit board is, when the battery is connected), you will be prompted
damage may occur if the battery is connected in to set the date and time, and then to set the exerciser.
reverse. See Section 1.14 and the generator set operation
manual for instructions.
See the dimension drawing in Section 2 for the engine
starting battery location on the air intake side of the If the battery is disconnected for service or replacement,
generator set. Standard battery cables provide easy the exercise settings on the RDC2/DC2 controller are
connection to the battery. lost. Set the exerciser after installing and connecting the
battery. See Section 1.14, Set Exerciser.
4
1. Load control circuit board
2. Power relays
3. Customer connection to power relays
4. 120 VAC power supply connection
GM79141C
1 2
To install the carburetor heater, follow the instructions
provided with the kit. Figure 1-40 shows the installed
carburetor heater kit installed for a 14 kW generator set.
Figure 1-41 shows the location for the carburetor heater
kit on a 20 kW generator set.
For 120 volt models, plug the carburetor heater into one
of the 120 VAC receptacles provided. tp6195
240 volt kits use a 3-pin power connector. Generator 1. Carburetor heater (air cleaner removed to show heater)
2. Carburetor heater power cord
sets built after 10/9/2013 have a knockout in the
bulkhead for the 240 VAC power connector. See Figure 1-40 14RESA/RESAL Carburetor Heater
Figure 1-42.
GM57969-C
tt1482b
2
1. Carburetor heater location under air cleaner. Insert from the
back of the generator set.
2. Carburetor heater
Optional 120 VAC and 240 VAC battery heater kits are
available. The heater is thermostatically controlled.
See Figure 1-43.
Wrap the heater around the battery and secure the cord
using cable ties. See Figure 1-44. Plug the power cord
into an AC receptacle. 3
For 120 volt models, plug the carburetor heater into one
of the 120 VAC receptacles on the generator set.
GM92406
240 volt kits use a 3-pin power connector. Generator
sets built after 10/9/2013 have a knockout in the
bulkhead for the 240 VAC power connector. The 240 Note: Adapter harness for multiple accessories not shown.
volt battery heater kit includes an adapter harness that 1. Battery heater
allows connection of up to three accessories. 2. Battery (not included in battery heater kit)
3. Power cord for 240 volt kits
OnCue Plus
OnCue Plus is available separately as a loose kit. Use
category 5E network cable to connect the RDC2
controller to the customer-supplied Ethernet router or GM84094
modem. Route the cable with other low-voltage signal
wiring (for example, the RBUS communication leads or 1. Ethernet cable for optional OnCue Plus connection
engine start leads to the transfer switch), in separate
Figure 1-45 Network Connection for OnCue Plus
conduit from the AC load leads. If the network cable is
longer than 100 meters (328 ft.), use a repeater or
switch. OnCue Plus Wireless
The OnCue Plus Wireless kit allows connection of the
Recommended: Use a laptop computer to verify the
generator set to the Internet through the customer’s
network connection before connecting to the generator
wireless router without running a network cable from the
set.
generator to the customer’s Ethernet router. The
OnCue Plus Wireless kit includes OnCue Plus and a
Checking the network connection wireless access point that mounts inside the generator
1. Check for and turn OFF any wireless connections enclosure. Follow the instructions in TT-1618, provided
to the laptop. with the kit, to install and set up the wireless access
point.
2. Connect the network cable to the laptop. Connect
the other end of the network cable to the
customer’s router or modem.
Generator set operation. Carbon monoxide can cause Oil Level. Maintain the oil level at or near, not over, the
severe nausea, fainting, or death. Carbon monoxide is an full mark on the dipstick.
odorless, colorless, tasteless, nonirritating gas that can cause
death if inhaled for even a short time. Avoid breathing exhaust Operating Area. Check for obstructions that could
fumes when working on or near the generator set. Never block the flow of cooling air. Keep the air intake area
operate the generator set inside a building. Never operate the clean. Do not leave rags, tools, or debris on or near the
generator set where exhaust gas could seep inside or be generator set.
drawn into a potentially occupied building through windows, air
intake vents, or other openings.
Carbon monoxide symptoms. Carbon monoxide can
cause severe nausea, fainting, or death. Carbon monoxide
is a poisonous gas present in exhaust gases. Carbon
monoxide is an odorless, colorless, tasteless, nonirritating gas
that can cause death if inhaled for even a short time. Carbon
monoxide poisoning symptoms include but are not limited to
the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms and carbon monoxide
poisoning is possible, seek fresh air immediately and remain
active. Do not sit, lie down, or fall asleep. Alert others to the
possibility of carbon monoxide poisoning. Seek medical
attention if the condition of affected persons does not improve
within minutes of breathing fresh air.
Next Exercise:
08:31a 12Dec2011
tp6803
Use the full-scale drawing in Figure 1 to mark the openings for the electrical conduit, if desired. See Section 1.9.2 for
more information.
SCALE: 1:1
Note: Dimensions are in mm.
Two 13 mm holes are needed for 20 kW models only. GM78090-B
Figure 1 Template, Drilled or Punched Openings for Regulator Vent Tubes (20 kW only) and Electrical Conduit