4 566

Electrohydraulic actuators SKC32..


for valves SKC82..
with a 40 mm stroke SKC62..
SKC60
SKC32.. Operating voltage AC 230 V, 3-position control signal
SKC82.. Operating voltage AC 24 V, 3-position control signal
SKC6.. Operating voltage AC 24 V, control signal DC 0…10 V, 4…20 mA or
0...1000
SKC6.. Choice of flow characteristic, position feedback, stroke calibration,
LED status indication, override control
SKC62UA with functions choice of direction of operation, stroke limit control,
sequence control with adjustable start point and operating range,
operation of frost protection monitors QAF21.. and QAF61..
Positioning force 2800 N
Actuator versions with or without spring-return function
For direct mounting on valves; no adjustments required
Manual adjuster and position indicator
Optional functions with auxiliary switches, potentiometer and stem heater
SKC..U are UL-approved

CM1N4566en
2016-04-13 Building Technologies
Use

For the operation of Siemens 2-port and 3-port valves, types VVF.. and VXF.. with a 40
mm stroke as control and safety shut-off valves in heating, ventilation and air
conditioning systems.
Types

Type Operating Positioning Spring-return Positioning time Enhanced


voltage signal Function Time Opening Closing functions
SKC32.60
AC 230 V
SKC32.61 yes 18 s
SKC82.60
3-position 120 s
SKC82.60U *
SKC82.61
yes 18 s 120 s
SKC82.61U *
AC 24 V
Standard electronics SKC62 DC 0...10 V,
yes 20 s
SKC62U * 4...20 mA,
20 s
SKC60 or
Enhanced electronics SKC62UA * 0...1000 yes 20 s yes 1)
1)
Direction of operation, stroke limit control, sequence control, signal addition
* UL-approved versions

Accessories Type Description For actuator Mounting location


ASC1.6 Auxiliary switch SKC6.. 1 x ASC 1.6
ASC9.3 Dual auxiliary switches 1 x ASC9.3 and
ASZ7.3 Potentiometer 1000 SKC32.. 1 x ASZ7.3 or
ASZ7.31 Potentiometer 135 SKC82.. 1 x ASZ7.31 or
ASZ7.32 Potentiometer 200 1 x ASZ7.32
ASZ6.6 Stem heater AC 24 V SKC.. 1 x ASZ6.6

Ordering When ordering please specify the quantity, product name and type code.
Example: 1 actuator, type SKC32.60 and
1 potentiometer, 135 , type ASZ7.31
Delivery The actuator, valve and accessories are supplied in separate packaging and not
assembled prior to delivery.
Spare parts See overview, section «Replacement parts», page 18.

2/18

Siemens Electrohydraulic actuators for valves CM1N4566en


Building Technologies 2016-04-13
Equipment combinations

3
Valve type DN PN-class kvs [m /h] data sheet
Two-port valves VV... (control valves or safety shut-off valves)):
1)
VVF21... Flange 100 6 124…160 4310
VVF22... Flange 100 6 160 4401
1)
VVF31... Flange 100…150 10 124…315 4320
VVF32... Flange 100…150 10 160…400 4402
1)
VVF40... Flange 100…150 16 124…315 4330
VVF42... Flange 100…150 16 125…400 4403
1)
VVF41... Flange 65…150 16 49…300 4340
VVF45.. Flange 65…150 16 49…300 4345
VVF43.. Flange 65…150 16 50…400 4404
VVF53.. Flange 65…150 25 63…400 4405
VVF61... Flange 65…150 40 49…300 4382
Three-port valves VX... (control valves for «mixing» and« diverting»):
1)
VXF21... Flange 100 6 124…160 4410
VXF22... Flange 100 6 160 4401
1)
VXF31... Flange 100…150 10 124…315 4420
VXF32... Flange 100…150 16 160…400 4402
1)
VXF40... Flange 100…150 16 124…315 4430
VXF42... Flange 100…150 16 125…400 4403
1)
VXF41... Flange 65…150 16 49…300 4440
VXF43.. Flange 65…150 16 63…400 4404
VXF53.. Flange 65…150 25 63…400 4405
VXF61... Flange 65…150 40 49…300 4482
For admissible differential pressures pmax and closing pressures ps, refer to the relevant
valve data sheets.
1)
Valves are phased-out

Note Third-party valves with strokes between 12…40 mm can be motorized, provided
they are «closed with the de-energized» fail-safe mechanism and provided that the
necessary mechanical coupling is available. For SKC32.. and SKC82.. actuators the Y1
signal must be routed via an additional freely-adjustable end switch (ASC9.3) to limit
the stroke.
We recommend that you contact your local Siemens office for the necessary
information.
Rev. no. Overview table, see page 18.

Technology
4567Z01

4567Z02

1
Principle of
electro-hydraulic
2
actuators 3 1 Manual adjuster
4
5 2 Pressure cylinder
6 3 Suction chamber
7
8 4 Return spring
9
10
5 Solenoid valve
11 6 Hydraulic pump
12 7 Piston
8 Pressure chamber
9 Position indicator (0 to 1)
10 Coupling
11 Valve stem
12 Plug

Valve closed Valve open

3/18

Siemens Electrohydraulic actuators for valves CM1N4566en


Building Technologies 2016-04-13
Opening the valve The hydraulic pump (6) forces oil from the suction chamber (3) to the pressure chamber
(8) and thereby moving the pressure cylinder (2) downwards. The valve stem (11)
retracts and the valve opens. Simultaneously the return spring (4) is compressed.

Closing the valve Activating the solenoid valve (5) allows the oil in the pressure chamber to flow back into
the suction chamber. The compressed return spring moves the pressure cylinder
upwards. The valve stem extends and the valve closes

Manual operation mode For manual operation, swing out the crank so that the display window becomes visible.
By rotating the crank or the manual adjustment knob, the display window shows the
engagement bar and/or the scale dial with stroke indication.

Turning the manual adjuster (1) clockwise moves the pressure cylinder downwards and
opens the valve. Simultaneously the return spring is compressed.
In the manual operation mode the control signals Y and Z can further open the valve
but cannot move to the «0%» stroke position of the valve. To retain the manually set
position, switch off the power supply or disconnect the control signals Y and Z. In the
display window the red indicator dial is visible.
Note: Controller in When setting the controller for a longer time period to manual operation, we
manual operation recommend adjusting the actuator with the manual adjuster to the desired position. This
guarantees that the actuator remains in this position for that time period. Attention: Do
not forget to switch back to automatic operation after the controller is set back to
automatic control.

Automatic mode Turn the manual adjuster counterclockwise to the end stop. The pressure cylinder
moves upward to the «0%» stroke position of the valve. In the display window the red
scale disappears and the crank can be swing closed.

Minimal volumetric flow The actuator can manually be adjusted to a stroke position > 0 % allowing its use in
applications requiring constantly a minimal volumetric flow.

Spring-return facility The SKC32.61, SKC82.61.. and SKC62.. actuators, which feature a spring-return
function, incorporate a solenoid valve which opens if the control signal or power fails.
The return spring causes the actuator to move to the «0 %» stroke position and closes
the valve.

SKC32../SKC82.. The actuator is controlled by a 3-position signal either via terminals Y1 or Y2 and
3-position control signal generates the desired stroke by means of above described principle of operation.
Voltage on Y1 piston extends valve opens
Voltage on Y2 piston retracts valve closes
No voltage on Y1 and Y2 piston / valve stem remain in the respective position

SKC62.., SKC60 The valve is either controlled via terminal Y or override control Z. The positioning signal
Y control signal Y generates the desired stroke by means of above described principle of operation.
DC 0...10 V and/or Signal Y increasing: piston extends valve opens
DC 4...20 mA, 0…1000 Signal Y decreasing: piston retracts valve closes
Signal Y constant: piston / valve stem remain in the respective position
Override control Z see description of override control input, page 8

Frost protection monitor A frost protection thermostat can be connected to the SKC6.. actuator. The added
Frost protection signals from the QAF21.. and QAF61.. require the use of SKC62UA actuators. Notes
thermostat on special programming of the electronics are described under «Enhanced electronics»
on page 5 «Connection diagrams» for operation with frost protection thermostat or frost
protection monitor refer to page 15.

4/18

Siemens Electrohydraulic actuators for valves CM1N4566en


Building Technologies 2016-04-13
4567Z03
Standard electronics
SKC62.., SKC60

Calib.

Z
Status
1 Connection terminals
2 Mode DIL switches
0...10V ok
4...20mA green
calib.

3 LED status indication


error
red valve
Calib.
Status jam

4 Slot for calibration

DIL switches Positioning signal Y Flow characteristic


SKC62.., SKC60 Position feedback U
ON ON
ON DC 4…20 mA lin = linear
4567Z05

4567Z07
12 12

ON ON
OFF *) DC 0…10 V log = equal percentage
4567Z06

4567Z08
12 12

*) Factory setting:
All switches OFF V100
Relationship
between control

li n
l og
signal Y and V0
0 10 V
4 20 mA
volumetric flow

Enhanced electronics
SKC62UA
1 Connection terminals
2 DIL switches
Calib.

3 LED status indication


Z
Status
0...10V ok

4 Stroke calibration
4...20mA green
calib.

error

Calib.
Status
red valve
jam 5 Rotary switch Up
(factory setting 0)
6 Rotary switch Lo

DIL switches Direction of operation Sequence control Control signal Y Flow characteristic
SKC62UA or stroke limit control Position feedback U
Sequence control
ON reverse-acting Signal addition DC 4...20 mA lin = linear
QAF21../QAF61..

log = equal
OFF * direct-acting Stroke limit control DC 0...10 V
percentage

* Factory settings: all switches Relationship V100

OFF between control


lin

signal Y and
l og

volumetric flow V0
0
4
10 V
20 mA

5/18

Siemens Electrohydraulic actuators for valves CM1N4566en


Building Technologies 2016-04-13
Selection of direction of With normally-closed valves, «direct-acting» means that with a signal input of 0 V,
operation the valve closes (applies to all Siemens valves listed under
SKC62UA «equipment combinations» on page 3)
With normally-open valves, «direct-acting» means that with a signal input of 0 V, the
valve is open.

Direct acting Reverse-acting

Stroke
(10 V)
0% 100 %
100 %
Y

Re
Y

ver
se
ct

-a
i re
100 %

c
tin
D
0%

g
(10 V) 0% Y
0V 10 V
Input DC 0...10 V Input DC 10...0 V 4 mA 20 mA
DC 4...20 mA DC 20...4 mA 0 1000
0...1000 1000...0

Note The mechanical spring-return function is not affected by the direction of operation
selected.

Stroke limit control Setting the stroke limit control Setting the sequence control
and sequence control The rotary switches LO and UP can be used The rotary switches LO and UP can be used
SKC62UA to apply an upper and lower limit to the stroke to determine the starting point or the operating
in increments of 3%, up to a maximum of 45% range of a sequence.

Position Lower stroke Position Upper stroke Position Starting point for Position Operating range
of LO limit of UP limit of LO sequence control of UP of sequence
control
0 0% 0 100 % 0 0V 0 10 V
1 3% 1 97 % 1 1V 1 10 V *
2 6% 2 94 % 2 2V 2 10 V **
3 9% 3 91 % 3 3V 3 3 V ***
4 12 % 4 88 % 4 4V 4 4V
5 15 % 5 85 % 5 5V 5 5V
6 18 % 6 82 % 6 6V 6 6V
7 21 % 7 79 % 7 7V 7 7V
8 24 % 8 76 % 8 8V 8 8V
9 27 % 9 73 % 9 9V 9 9V
A 30 % A 70 % A 10 V A 10 V
B 33 % B 67 % B 11 V B 11 V
C 36 % C 64 % C 12 V C 12 V
D 39 % D 61 % D 13 V D 13 V
E 42 % E 58 % E 14 V E 14 V
F 45 % F 55 % F 15 V F 15 V

* Operating range of QAF21.. (see below)


** Operating range of QAF61.. (see below)
*** The smallest adjustment is 3 V; control with 0…30 V is only possible via Y.

Stroke control with Setting the signal addition


QAF21.. / QAF61.. The operating range of the frost protection
signal addition monitor (QAF21.. or QAF61..) can be defined
Calib.
with rotary switches LO and UP.
SKC62UA only Position Sequence control Position QAF21../ QAF61..
of LO start point of UP operating range
0 1 QAF21..
Lo Up 0 2 QAF61..

6/18

Siemens Electrohydraulic actuators for valves CM1N4566en


Building Technologies 2016-04-13
Calibration In order to determine the stroke positions 0 % and 100 % in the valve, calibration is
SKC62.., SKC60 required on initial commissioning:
Prerequisites
Mechanical coupling of the actuator SKC6.. with a Siemens valve
Actuator must be in «Automatic operation» enabling stroke calibration to
capture the effective 0 % and 100 % values
AC 24 V power supply
Housing cover removed
Calibration
1. Short-circuit contacts in calibration slot 01124

green LED flashes;


(e.g. with a screwdriver)
position feedback U
2. Actuator moves to «0 %» stroke position (1)
inactive
(valve closed)
3. Actuator moves to «100 %» stroke position (2)

4567Z09
0%

(valve open) 1

Stroke
2 3
4. Measured values are stored
100% t

Normal operation
5. Actuator moves to the position (3) as green LED is lit permanently;
indicated by signals Y or Z position feedback U active, the values
correspond to the actual positions

A lit red LED indicates a calibration error.


The calibration can be repeated any number of times.
Indication of The LED status indication indicates operational status with dual-colored LED and is
operating state visible with removed cover.
SKC62.., SKC60 LED Indication Function Remarks, troubleshooting
Green Lit Normal operation Automatic operation; everything o.k.

Flashing Calibration in progress Wait until calibration is finished (LED stops


flashing, green or red LED will be lit)
Red Lit Faulty stroke calibration Check mounting
Restart stroke calibration (by short-circuiting
calibration slot)
Internal error Replace electronics
Flashing Inner valve jammed Check valve

Both Dark No power supply Check mains network, check wiring


Electronics faulty Replace electronics

As a general rule, the LED can assume only the states shown above (continuously red
or green, flashing red or green, or off).

7/18

Siemens Electrohydraulic actuators for valves CM1N4566en


Building Technologies 2016-04-13
Override control Override control input can be operated in following different modes of operation
input Z Z-mode
SKC62.., SKC60 no function fully open closed override with Signal addition
0…1000 SKC62UA only

Connections
Transfer

linear or equal- linear or equal- linear or equal-


percentage percentage percentage
Z-contact not Z-contact connected Z-contact connected Z-contact connected Z-contact is
connected directly to G directly to G0 to M via resistor R connected to R of
Valve stroke follows Y-input has no effect Y-input has no effect Starting position at the frost protection
Y-input 50 / end position monitor QAF21.. or
at 900 QAF61..
Y-input has no effect Valve stroke follows
signals Y and R(Z)

Note Shown operation modes are based on the factory setting «direct acting»
Y-input has no effect in Z-mode.

Accessories

SKC.. ASZ6.6
stem heater

for media below 0 °C


mount between valve and actuator
SKC32.., SKC82.. ASC9.3 ASZ7.3..
double auxiliary switch potentiometer
4561Z05

adjustable switching points ASZ7.3: 0…1000


ASZ7.31: 0…135
ASZ7.32: 0…200

8/18

Siemens Electrohydraulic actuators for valves CM1N4566en


Building Technologies 2016-04-13
SKC62.., SKC60 ASC1.6
auxiliary switch

switching point 0…5 % stroke

See section «Technical data» on page 12 for more information.

Engineering notes

Conduct the electrical connections in accordance with local regulations on electrical


installations as well as the internal or connection diagrams.

Caution Safety regulations and restrictions designed to ensure the safety of people and
property must be observed at all times!

The plant operator must also ensure compliance with applicable guidelines on
cable insulation when using a safety limiter. Failure to comply may cause the
safety limiter function to fail.

4567Z11
Caution For media below 0 °C the ASZ6.6 stem heater is required
to keep the valve from freezing. For safety reasons the
stem heater is designed for an operating voltage of
AC 24 V / 30 W.
For this case, do not insulate the actuator bracket and the
valve stem, as air circulation must be ensured. Do not
touch the hot parts without prior protective measures to
avoid burns.
Non-observance of the above may result in accidents and
fires!
Recommendation: Above 140 °C insulating the
valves is strictly recommended.
Observe admissible temperatures, refer to «Use» on page 2 and «Technical data» on
page 12

If an auxiliary switch is required, its switching point should be indicated on the plant
schematic.
Every actuator must be driven by a dedicated controller (refer to
«Connection diagrams», page 15).

9/18

Siemens Electrohydraulic actuators for valves CM1N4566en


Building Technologies 2016-04-13
Mounting instructions

Mounting Instruction 74 319 0324 0 for fitting the actuator to the valve are by packed in
the actuator packaging. The instructions for accessories are enclosed with the
accessories themselves.
Accessories Installation instructions Accessories Mounting instructions
ASC1.6 G4563.3 4 319 5544 0 ASZ7.3.. 74 319 0247 0
ASC9.3 G4561.3 4 319 5545 0 ACT control unit M4568 74 319 0554 0
SKC.. M3240 74 319 0324 0 QAF21.. 74 319 0399 0
SKC.. 74 319 0326 0 ASZ6.6 M4501.1 74 319 0750 0

Orientation
90° 90°

Commissioning notes

When commissioning the system, check the wiring and functions, and set any auxiliary
switches and potentiometers as necessary, or check the existing settings.

Cylinder with valve Cylinder with valve


stem connector fully stem connector fully
retracted 0 extended 0

stroke = 0% 1 stroke = 100 % 1


4566Z12

4566Z13
The manual adjuster must be rotated counterclockwise to the end stop.
This causes the Siemens valves, types VVF.. and VXF.. to close (stroke = 0 %).

Automatic operation For automatic operation, the crank (2) on the manual adjustment knob (1) must be
engaged. If not engaged, turn the crank counter-clockwise until the display window (3)
neither shows the scale (4) nor the crank engagement bar.

1
2
4564Z16
4564Z14

Engaged crank (2) on the Display window with invisible scale dial and crank
manual adjustment knob (1) engagement bar

10/18

Siemens Electrohydraulic actuators for valves CM1N4566en


Building Technologies 2016-04-13
Manual operation For manual operation, swing out the crank (2) so that the display window (3) becomes
visible. By rotating the crank or the manual adjustment knob (1), the display window
shows the engagement bar and/or the scale dial with stroke indication.

4564Z17
4564Z15
Swung-out crank, Display window with scale dial (4) and stroke
display window (3) indication

Maintenance notes

The SKC.. actuators are maintenance-free.


When servicing the actuator:
Switch off pump of the hydronic loop
Interrupt the power supply to the actuator
Close the main shutoff valves in the system
Release pressure in the pipes and allow them to cool down completely
If necessary, disconnect electrical connections from the terminals
The actuator must be correctly fitted to the valve before recommissioning.
Recommendation SKC6..: trigger stroke calibration.
Repair «Replacement parts», see page 18.

A damaged housing or cover represents an injury risk

NEVER uninstall an actuator from the valve


Uninstall the valve-actuator combination (actuating device) as a complete
device
Use only properly trained technicians to uninstall the unit
Send the actuating device together with an error report to your local Siemens
representative for analysis and disposal
Properly mount the new actuating device (valve and actuator)

Parts could fly ultimately resulting in injuries from uninstalling an actuator with a
damaged valve housing due to the tensioned return spring.

Disposal

The device is considered an electronics device for disposal in terms of European


Directive 2012/19/EU and may not be disposed of as domestic garbage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.

Warranty

Technical data on specific applications are valid only together with Siemens products
listed under "Equipment combinations", page 3. Siemens rejects any and all warranties
in the event that third-party products are used.

11/18

Siemens Electrohydraulic actuators for valves CM1N4566en


Building Technologies 2016-04-13
Technical data

SKC32.. SKC82.. SKC6..


Power supply Operating voltage AC 230 V AC 24 V AC 24 V
Voltage tolerance 15 % 20 % 20 %
SELV / PELV
Frequency 50 or 60 Hz
Max. Power consumption at SKC32.60: SKC82.60, ..60U SKC60
50 Hz 18 VA / 14 W 15 VA / 12 W 17 VA / 13 W
SKC32.61: SKC82.61, ..61U SKC62..
24 VA / 18 W 19 VA / 14 W 21 VA / 15 W
External supply cable fuse min. 0.5 A, slow min. 1.6 A, slow
max. 6 A, slow max. 10 A, slow
Signal inputs Control signal DC 0...10 V,
3-position DC 4...20 mA,
0...1000
Terminal Y Voltage DC 0…10 V
Input impedance 100 k
Current DC 4…20 mA
Input impedance 240
Signal resolution < 1%
Hysteresis 1 %
Terminal Z Resistor 0…1000
Override control Z not connected, priority terminal Y No function
Z connected directly to G max. stroke 100 %
Z connected directly to G0 min. stroke 0 %
Z connected to M via 0...1000 stroke proportional to R
Position Terminal U voltage DC 0...9.8 V ±2 %
feedback load impedance > 10 k
current DC 4...19.6 mA ±2 %
load impedance < 500
Connecting Cable cross-sectional area 0.5 … 2.5 mm2 / AWG 21 … 14
cable
Functional Data Positioning time at 50 Hz 1)
opening SKC32.6.. 120 s SKC82.6.. 120 s 120 s
Closing SKC32.6.. 120 s SKC82.6.. 120 s 20 s
Spring-return time 1) SKC32.61 18 s SKC82.61 18 s SKC62.. 20 s

Positioning force 2800 N


Nominal stroke 40 mm
Max. permissible medium -25…220 (350) °C
temperature < 0 °C: requires stem heater ASZ6.6
1)
At room temperature (23°C), low ambient temperatures or high p may prolong these times
Electrical Cable entry 4 x M20 ( 20,5 mm)
connections ..U with knockouts for standard ½” conduit connectors (Ø 21.5 mm)
Standards, Product standard EN 60730-x
directives and
approvals
Electromagnetic compatibility For use in residential, commercial, light-industrial and industrial
(Applications) environments
EU conformity (CE) A5W00007751 1)
RCM-conformity (EMC) A5W00007895 1)
AC 230 V
EAC conformity Eurasia conformity for all SKC..
UL certification: UL, cUL
AC 230 V -
AC 24 V UL 873, http://ul.com/database

12/18

Siemens Electrohydraulic actuators for valves CM1N4566en


Building Technologies 2016-04-13
SKC32.. SKC82.. SKC6..
Environmental The product environmental declarations CE1E4566en01 1) and
compatibility CE1E4566en02 1) contain data on RoHS compliance, materials
composition, packaging, environmental benefit and disposal.
Dimensions / Dimensions refer to «Dimensions», page 17
Weight Weight (packing excluded) SKC32.60 9.80 kg SKC82.60 9.80 kg SKC60/62 9.85 kg
SKC32.61 9.85 kg SKC82.60U 10.10 kg SKC62U/UA 10.15 kg
SKC82.61 9.85 kg
SKC82.61U 10.15 kg
Materials Actuator housing, bracket Die-cast aluminum
Housing box and
Plastic
manual adjuster
1)
The documents can be downloaded from http://siemens.com/bt/download.

Accessories SKC32.., SKC82.. SKC6..


ASC1.6 Switching capacity AC 24 V,
Auxiliary switch 10 mA...4 A resistive,
2 A inductive
ASC9.3 Switching capacity per AC 250 V, 6 A resistive, 2.5 A inductive
double auxiliary auxiliary switch
switch
ASZ7.3 Change in overall resistance ASZ7.3 0…1000
Potentiometer of potentiometer at nominal ASZ7.31 0…135
stroke ASZ7.32 0…200
min. current in sliding contact 0,05 mA
expected lifetime 250'000 full lifts
max. current in sliding contact 2,5 mA
expected lifetime 100'000 full lifts
ASZ6.6 Operating voltage AC 24 V ± 20 %
stem heater Power consumption 40 VA / 30 W
Inrush current Max. 8 A (B Series)

SKC62UA enhanced functions

Direction of operation Direct-acting, reverse-acting DC 0...10 V / DC 10...0 V


DC 4...20 mA / DC 20...4 mA
0...1000 / 1000...0
Stroke limit control Range of lower limit 0...45 % adjustable
Range of upper limit 100...55 % adjustable
Sequence control Terminal Y
Starting point of sequence 0...15 V adjustable
Operating range of sequence 3...15 V adjustable
Signal addition Z connected to R of
Frost protection monitor QAF21.. 0...1000 , added to Y signal
Frost protection monitor QAF61.. DC 1.6 V, added to Y signal

13/18

Siemens Electrohydraulic actuators for valves CM1N4566en


Building Technologies 2016-04-13
Ambient conditions and protection data
Classification to Automatic action: Type 1AA / Type 1AC / Modulation Action
IEC/EN 60730 Pollution degree: 2
Housing protection as per IP54
IEC/EN 60529
Environmental conditions
Transportation Class 2K3
(in transport packaging) Temperature -30...65 °C
to IEC/EN 60721-3-2 Humidity 5...95 % (no condensation)
Operation Class 3K5
to IEC/EN 60721-3-3 Temperature -15...55 °C
Humidity 5...95 % (no condensation)
Storage Class 1K3
to IEC/EN 60721-3-1 Temperature -15...55 °C
Humidity 5...95 % (no condensation)

Internal diagrams

SKC32.61 Cm1 end switch


n solenoid valve for spring-
AC 230 V, 3-Position
return
c1, c2 ASC9.3 double auxiliary
switch
a, b, c ASZ7.. potentiometer
Y1 Positioning signal «open»
SKC32.60 Y2 Positioning signal «close»
AC 230 V, 3-Position 21 spring-return function
N neutral conductor

SKC82.61 Cm1 end switch


n solenoid valve for spring-
AC 24 V, 3-Position
return
c1, c2 ASC9.3 double auxiliary
switch
a, b, c ASZ7.. potentiometer
Y1 Positioning signal «open»
SKC82.60 Y2 Positioning signal «close»
AC 24 V, 3-Position 21 spring-return function
G System potential

SKC60, SKC62 U position indication


DC 0 ...10 V

SKC62U U oder
4 ... 20 mA
Ausgang
Z override control
SKC62UA
voll offen
Eingang Y positioning signal
Zwangsteuerung

AC 24 V, DC 0…10 V, 0 ...100 %
(Signalpriorität) M measuring neutral
G0 operating voltage AC 24 V:
4…20 mA, 0…1000 Y
DC 0 ...10 V
oder 0 ...100 %
Eingang
Valve Seat
4 ... 20 mA
Detection
Hub system neutral (SN)
M Valve Jam G operating voltage AC 24 V:
Detection
system potential (SP)
G0 Switching without power as
MMI
a spring return function
G

Ventil

14/18

Siemens Electrohydraulic actuators for valves CM1N4566en


Building Technologies 2016-04-13
Connection terminals

SKC6.. G0 operating voltage AC 24 V: system neutral (SN)


G operating voltage AC 24 V: system potential (SP)
Y Positioning signal DC 0...10 (30) V or DC 4...20 mA
M Measuring neutral (= G0)
U
Position indication DC 0...10 V or DC 4...20 mA
Z
Override control (functionality see page 8)

01804
3
Auxiliary switch
ASC1.6

c1

4 5

Connection diagrams

SKC32.. SKC32.61 SKC32.60


AC 230 V AC 230 V AC 230 V
3-Position max. 6 A max. 6 A

(L) (L)

F1 (Y1) (Y2) (N) (Y1) (Y2) (N)


N1 N1

0% 0%

N N
F1 safety limiter (eg L Phase Y1 Positioning signal «open»
temperature limiter) N neutral Y2 Positioning signal «close»
N1, N2 controller 21 Spring-return function
Y1, Y2 actuators

15/18

Siemens Electrohydraulic actuators for valves CM1N4566en


Building Technologies 2016-04-13
SKC82.. SKC82.61, SKC82.61U SKC82.60, SKC82.60U
AC 24 V
AC 24 V AC 24 V
3-Position SN SN

0% 0%

Y1 Y2 N1 Y1 Y2 G0
G0
F1

G G N1

SP SP
AC 24 V AC 24 V
SP SP

0% 0%

N1 Y1 Y2 G
Y1 Y2 G
F1
G0
G0 N1

SN SN
F1 safety limiter (eg SP Systempotential AC 24 V Y1 Positioning signal «open»
temperature limiter) SN System neutral Y2 Positioning signal «close»
N1, N2 controller 21 Spring-return function
Y1, Y2 actuators
SKC6.. SKC60 AC 230 V
AC 24 V
AC 24 V
DC 0…10 V, 4…20 mA, SP
0…1000 G M

1 3 2 F2 1 3 2 F3 R M F4

M
N1

G M U Z

SN
N

16/18

Siemens Electrohydraulic actuators for valves CM1N4566en


Building Technologies 2016-04-13
SKC62 AC 230 V

SKC62U AC 24 V
SP
SKC62UA
G M
F1
1 3 2 F2 1 3 2 F3 R M F4

M
N1

G M U Z

SN
N

Y1 actuator
N1 controller
F1 safety limiter (eg temperature limiter)
F2 frost protection thermostat
terminals: 1 – 2 frost hazard / sensor is interrupted (thermostat closes with frost)
1 – 3 normal operation
F3 temperature detector
F4 Frost protection monitor with 0…1000 signal output, e.g. QAF21.. or QAF61.. (only SKB62UA) *
G (SP) System potential AC 24 V
G0 (SN) System neutral
* Only with sequence control and the appropriate selector switch settings (see page 5ff)

When using the safety limiter F1, ensure that no mistakes may occur on cable
Warning
insulation that may cancel out the temperature limiter function (applies to both 230 V as
well as 24 V types).
For SN earthing (e.g. PELV) comply under all circumstances with the note above.

Dimensions

All dimensions in mm

** SKC..U: with knockouts for standard ½” conduit connectors (Ø 21.5 mm)


= > 100 mm , minimum clearance from ceiling or wall for mounting,
= > 200 mm , connection, operation, maintenance etc.

17/18

Siemens Electrohydraulic actuators for valves CM1N4566en


Building Technologies 2016-04-13
Replacement parts

Order numbers for replacement parts

Cover Hand control 1) Clamp Stem connection Control unit

Actuator type
SKC32.60 410455828 426855108 410355768 417856498
SKC32.61 410455828 426855108 410355768 417856498
SKC82.60 410455828 426855108 410355768 417856498
SKC82.60U 410455828 426855108 410356058 417856498
SKC82.61 410455828 426855108 410355768 417856498
SKC82.61U 410455828 426855108 410356058 417856498
SKC62 410455828 426855108 410355768 417856498 466857488
SKC62U 410455828 426855108 410356058 417856498 466857488
SKC60 410455828 426855108 410355768 417856498 466857598
SKC62UA 410455828 426855108 410356058 417856498 466857518
1) hand control, blue with mechanical parts

Revision numbers

Type reference Valid from rev. No. Type reference Valid from rev. No.
SKC32.60 ..D SKC82.61U ..D
SKC32.61 ..D SKC62 ..G
SKC82.60 ..D SKC62U ..G
SKC82.60U ..D SKC60 ..G
SKC82.61 ..D SKC62UA ..G

Published by:
Siemens Switzerland Ltd.
Building Technologies Division
International Headquarters
Gubelstrasse 22
6301 Zug
Switzerland
Tel. +41 41-724 24 24 © Siemens Switzerland Ltd 2002
www.siemens.com/buildingtechnologies Delivery and technical specifications subject to change
18/18

Siemens Electrohydraulic actuators for valves CM1N4566en


Building Technologies 2016-04-13

You might also like