ATS

LOW VOLTAGE AUTOMATIC


TRANSFER SWITCH

ATS-WST-5

ATS Controller

“Seamless
switching between sources
for uninterrupted supply &
power outage protection”

High speed 2 Position closed / Open High-end utilization Bypass mode


load transfer > 30 Sec transition category: AC33A/33B operation
with Neutral Overlapping

www.elmeasure.com
ATS-WN3 Series Power Transfer Switch

Overview
The ATS-WN3 Series Power Transfer Switch is available in the conventional,
three-position transfer configuration and closed or delayed transition modes
of operation. Additionally, switched or overlapping neutral options provide for
reliable operation of ground fault protection systems and reduction of voltage
transients from unbalanced load switching.

ATS-WN3 Automatic Transfer Switches are the standard of the industry. High
speed transfer of loads between alternate sources of power, regardless of
ampacity size, is achieved by a reliable, field proven solenoid operating
mechanism. When combined with a programmable microprocessor
controller with LCD display, they offer the most advanced method of
transferring all types of loads, such as, motors, electronic drives, UPS’s and
microprocessor based systems. Automatic transfer switces
are available open or enclosed, in ampacity sizes from 16 through 6300
ATS-WN3-630A-4P Series Opened
amperes with the largest selection of optional accessories offered anywhere.
Transition Tranfer Switches

Product Type: Open Transition Transfer Switch, Closed-Transition Transfer Switch,


Delayed-Transition Transfer Switch, Bypass-Isolation Transfer Switch.

ATS-WN3CT-1000A-4P Series Closed


Transition Tranfer Switches
Features
Transfer Model : ATSE ; Class : PC
Utilization Category : AC-33A / AC-33B
IECEE & CCC certified to GB/T 14048.11-2008 & EN/IEC 6094-7-6-1:2005+A1:2014
Automatic Transfer Switching Equipment.
Rated up to 690/400 VAC, sizes from 63 through 6300 amperes.
Optimal Design of 800 through 6300 amperes Driven by Dual-driving mechanism.
Delayed Transition ATS-WN3 Series Automatic Transfer Switch has 3 positions, conventional
two-position transfer configuration, plus closed and delayed transition modes of operation.
All configurations available with either automatic or non-automatic control.
The transfer switch shall be electrically operated and mechanically held. The switch shall be
mechanical & electrical interlocked.
Fast Contact time 30-100msec.
High withstand and close-on with reliable and
field-proven solenoid operating mechanism
ensures maximum performance.
The switch can positively locked and unaffected by momentary outages, so that contact
pressure is maintained at a constant value and contact temperature rise is minimized for
maximum reliability and operating life.
Where neutral conductors must be switched as shown on the plans, the ATS shall be
provided with fully rated overlapping neutral transfer contacts. The neutrals of the normal
and emergency power sources shall be connected together only during the transfer and
retransfer operation and remain connected together until power source contacts close on the
source to which the transfer is being made. The overlapping neutral contacts shall not overlap
for a period greater than 100 milliseconds. Neutral switching contacts which do not overlap
are not acceptable.
Arc quenching grids, enclosed arc chambers,and wide contact air gap.
Segmented silver tungsten alloy contacts with separate arcing contacts on all sizes.
Delayed-Transition Transfer Switch.
Overlapping neutral conductor (options).
Closed Transition Transfer Switches, Source momentarily parallel time of less than 100
milliseconds, Closed transition operation (no power interruption) during transfer (manual
mode) and retransfer when sources are within specified parameters.
Switch position indicators and true source acceptability lights.
Standard ground conductor connections.
Four auxiliary contacts, two contacts closed when switch is in normal position and two
contacts closed when switch is in emergency position.
Local/remote serial communications capability for interfacing with ATS-WN3
communication products.
ATS-WN3BCT- 2000A-4P ATS-WN3MCT-1000A-3P ATS-WN3CT-630A-4P
Closed Transition Transfer Switches Manual Closed Transition Transfer Switches Closed Transition Transfer Switches
with Maintenance Bypass with Exetherm IR sensors.

Ampere Interrupting Capacity (AIC) Ratings


Ampere Rating 16-125 160-250 300-630 800-1250 1600-2600 3200-6300

Utilization Category AC-33/AB AC-33A/B AC-33A/B AC-33A/B AC-33A/B AC-33A/B

Withstand short time rating(kA) 25-35 25-35 50-65 65-80 80-100 80-100

Rated conditional short circuit current (kA) FUSE 200 200 200 200 200 200

Low voltage (A) AC690/400 AC690/400 AC690/400 AC690/400 AC690/400 AC690/400

Impulse withstand voltage (kV) 8 8 8 8 8 8

Rated insulation voltage (V) 1000 1000 1000 1000 1000 1000
ATS-WN3 B Series Automatic Transfer Bypass-lsolation Switch
Features
Transfer Model : ATSE ; Class : PC High withstand and close-on.
Utilization Category : AC-33A / AC-33B Reliable and field-proven solenoid operating mechanism ensures
maximum performance.
IECEE & CCC GB/T 14048.11-2008 & EN/IEC 6094-7-6-
The switch can positively locked and unaffected by momentary
1:2005+A1:2014 Automatic Transfer Switching Equipment.
outages, so that contact pressure is maintained at a constant value
CE certified to EN/IEC 60947-6-1:2005. Tested & complied.
and contact temperature rise is minimized for maximum reliability
Rated up to 690/400 VAC, sizes from 63 through 6300 and operating life.
amperes.
Where neutral conductors must be switched as shown on the
Available in bypass-isolation configuration. The bypass and plans, the ATS shall be provided with fully rated overlapping
isolation features allow power transfer switches to be neutral transfer contacts. The neutrals of the normal and
inspected, tested, and maintained without any interruption emergency power sources shall be connected together only
of power to the load. during the transfer and retransfer operation and remain
connected together until power source contacts close on the
Allows bypass-isolation without load interruption.
source to which the transfer is being made. The overlapping neutral
Bypass switch and transfer switch have identical electrical contacts shall not overlap for a period greater than 100
ratings. milli seconds. Neutral switchingcontacts which do not overlap are
Bypass contacts carry current only during bypass mode. not acceptable.
Arc quenching grids, enclosed arc chambers, and wide contact
Transfer switch is draw out design for ease of maintenance.
air gap.
Bypass and isolation handles are permanently mounted. The
Segmented silver tungsten alloy contacts with separate arcing
bypass switch has dead front quick-make, quick-break
contacts on all sizes.
operation for transferring of loads between live sources.
Delayed-Transition Transfer Switch.
Bypass switch is fully rated for use as a manual 3-position
transfer switch. Overlapping neutral conductor (options).

Bypass and isolation functions are simple, requiring a total of Closed Transition Transfer Switches, Source momentarily parallel
two operating handles. time of less than 100 milliseconds, Closed transition operation (no
power interruption) during transfer and retransfer when sources
Mechanical indicators show bypass and transfer switch are within specified parameters.
positions.
Switch position indicators and true source acceptability lights.
Delayed Transition ATS-WN3 B Series Automatic Transfer
Standard ground conductor connections.
Switch has 3 positions, conventional two-position transfer
configuration, plus closed and delayed transition modes of Four auxiliary contacts, two contacts closed when switch is in
operation. All configurations available with either automatic normal position and two contacts closed when switch is in
or non-automatic control. emergency position.
The transfer switch shall be electrically operated and Components accessible for inspection and maintenance without
mechanically held. The switch shall be mechanical & removal of the switch or the power conductors.
electrical interlocked. Local/remote serial communications capability for interfacingwith
Front replaceable main and arcing contacts. ATS-WN3 B communication products.
ATS-W2H Series Power Transfer Switch

Overview
ATS-W2H series switches are built for standard applications requiring
ATS-WST-5

the dependability and ease of operation found in a power contactor


switch.
ATS Controller

Features
Transfer Model : ATSE : Class : PC
Utilization Category : AC-33A / AC-33B
IECEE & CCC GB/T 14048.11-2008 & EN/IEC 6094-7-6-1:2005+A1:2014
Automatic Transfer Switching Equipment.
Rated up to 400 VAC, sizes from 63 through 250 Amperes.
Transition ATS-W2H Series Automatic Transfer Switch has 2 positions,
conventional two-position transfer configuration, and delayed transition
modes of operation. All configurations available with either automatic or
non-automatic control.

Mechanical interlocked contactor mechanism.


Electrically operated, mechanically held.
Designed for emergency and standby applications.
Available in standard or delayed transition mode. ATS-W2H 250A Serias Power Tranfer Switch
250A, 4P
Timer and voltage / frequency settings adjustable without disconnection
from the power section.

LED indicators for ease of viewing and long life.


Processor and digital circuitry isolated from line voltage.
Input is opto isolated for high electrical immunity to transients and noise.
Communications network interface.
Four auxiliary contacts, two contacts closed when switch is in normal
position and two contacts closed when switch is in emergency position.
Local/remote serial communications capability for interfacing with
ATS-W2H communication products.
Opened transition tranfer swiches.
Overlapping neutral conductor (options).
ATS-WS1 High Speed Dual Power Transfer Switches

Overview
ATS-WS1 High Speed Dual-Power Series switches are PC-level two stage
ATS-WST-5

tranfser switches design to meet stringent transfer time requirements.


With a transfer time of only 3-8msec, the series are appropriate for use the
ATS Controller

active and standby power share the same voltage and phases.

Features
Transfer Model : ATSE : Class : PC
Utilization Category : AC-33A / AC-33B
IECEE & CCC GB/T 14048.11-2008 & EN/IEC 6094-7-6-1:2005+A1:2014
Automatic Transfer Switching Equipment.
Rated up to 400 VAC, sizes from 63 through 500 amperes.
ATS-WS1 Series Automatic Transfer Switch has 2 positions, convential
two-position transfer configuration, and delayed transition modes of
operation. All configurations available with either automatic or
non-automatic control.
Mechanical interlocked contactor mechanism.
Electrically operated, mechanically held.
Designed for emergency and standby applications.
Available in standard break before make (opened transition transfer).
Timer and voltage / frequency settings adjustable without disconnection
from the power section.
Processor and digital circuitry isolated from line voltage.
Input is opto isolated for high electrical immunity to transients and noise.
Communications network interface.
Four auxiliary contacts, two contacts closed when switch is in normal
position and two contacts closed when switch is in emergency position.
Local/remote serial communications capability for interfacing with
ATS-WS1 communication products.
Opened transition tranfer switches.
Overlapping neutral conductor (options).
Dimension for ATS-W2H Opened transition ATS WN3CT Closed Transition Non-Bypass
ATS Type WIDTH HEIGHT DEPTH ATS Type WIDTH HEIGHT DEPTH
2P 146 188.5 114 63A-100A, 125A, 160A, 200A, 3P 425 260 159.3
20A, 32A, 40A, 63A, 250A, 260A, 300A, 400A
3P 167 188.5 114 4P 425 260 159.3
80A, 100A, 125A
4P 188 188.5 114 3P 550 320 179.8
500A-630A
160A, 200A, 250A 3P 207 188.5 114 4P 550 320 179.8
4P 242 188.5 114 3P 585 394 230
800A
4P 585 394 230
ATS-WS1 Opened Transition 3P 644 394 275
ATS Type WIDTH HEIGHT DEPTH 1000A-1250A
4P 644 394 275
2P 200 171 133
3P 724 394 285
20A, 32A, 40A, 63A 3P 222 193 133 1600A
4P 724 394 285
4P 244 282.5 133
3P 946 502 295
2P 216 187 133 2000A
4P 946 502 295
3P 246 217 133
80A, 100A, 125A 3P 1130 485 315
4P 276 247 133 2600-3200A
4P 1130 485 315
2P 227 197 133
3P 1200 560 304
3P 262 232 133 4000-5000A
160A, 200A, 250A 4P 1200 560 304
4P 287 267 133
3P 1300 600 350
2P 232 216.5 133 6300A
4P 1300 600 350
300A, 400A 3P 277.5 262 133
4P 323 307.5 133
2P 27.5 265.5 150 Dimension for ATS WN3-CT Closed
3P 335.5 325.5 150
Transition with Bypass
500A
4P 395.5 385.5 150 ATS Type WIDTH HEIGHT DEPTH
63A-100A, 125A, 160A, 200A, 3P
250A, 260A, 300A, 400A, 500A 550 753 591
ATS-WS1 Opened Transition 4P
3P
ATS Type WIDTH HEIGHT DEPTH 630A, 800A, 1000A, 1250A 710 765 725
4P
3P 224 196 133
20A, 32A, 40A, 63A 3P
4P 246 196 133 1600A-2000A 790 765 740
4P
3P 248 200 133
80A, 100A, 125A 3P
4P 278 200 133 2600A 950 765 760
4P
3P 263 200 133
160A, 200A, 250A 3P
4P 298 255 133 3200A, 4000A, 5000A 1150 765 815
4P
3P 350 255 133
300A, 400A 3P
4P 410 304 133 6300A 1200 800 850
4P
3P 345 304 133
500A-630A
4P 405 395 133
3P 405 395 133
800A
4P 470 395 133 Dimension for ATS-WN3B Opened
1000A
3P 450 395 150 Transition with Bypass
4P 530 395 150 ATS Type WIDTH HEIGHT DEPTH
3P 450 395 150 63A-100A, 125A, 160A, 200A, 3P 550 753 591
1250A
4P 530 395 150 250A, 260A, 300A, 400A, 500A 4P 550 753 591
3P 510 395 150 3P 710 765 725
1600A 630A-800A
4P 610 395 150 4P 710 765 725
3P 730 508 150 3P 770 765 725
2000A 1000A-1250A
4P 730 508 150 4P 770 765 725
3P 890 508 150 3P 860 765 740
2600A-3200A 1600A-2000A
4P 890 508 150 4P 860 765 740
3P 1058 508 150 3P 1010 765 760
4000A-5000A 2600A
4P 1058 508 150 4P 1010 765 760
3P 1170 585 150 3P 1180 765 815
6300A 3200A, 4000A, 5000A
4P 1170 585 150 4P 1180 765 815
3P 1210 800 850
6300A
4P 1210 800 850

Note: The ATS dimension is without enclosure.


Microprocessor ATS Controller
Real-Time Measurement and Monitoring.
Microprocessor based ATS controller is ideal for complex on-site power systems that support ultra-critical
applications such as data centers, large hospitals, financial centers and other operations where the stakes are high.
ATS controller collects real-time single or three-phase power information from
engine-generators, utility, paralleling switchgear and automatic transfer switches. With Power Technologies CLOUD
real time measurement, monitoring and control it help to have remote monitoring and assets controls.
The ATS Controller is used with all sizes of Power Transfer Switches from 20 through 6300 amperes.
It represents the most advanced digital controller in the industry and includes, as standard, all of the
voltage, frequency, control, timing and diagnostic functions required for most emergency and standby power
applications.
Capable of detecting two-way three-phase voltage, frequency and load current and controlling ATS applicable for
two and three sectional power ATS switch.
This type of system can be applied to A utility power/B utility power, A utility power/B generation, A generation/
B utility power, A generation/B generation.

LCD display in English and convenient man-machine interface, designed with buttons, easy to learn,
and easy to use.
Accurately capture and display parameters such as two-way three-phase voltage, frequency, and load current.
With overvoltage, undervoltage, open phase, inverse phase sequence and under frequency protection.
Provided with ATS current overload protection (with current transformer).
Designed with auto/manual switching; In manual mode, a user can force ATS switch A power in ON state for power
supply, B power in ON state for power supply, or disconnect and place in the OFF position: all parameters can be
programmed on-site.
Combined key command is used to prevent operation of non-specialist.
Provided with auto ON & reset and auto ON & no reset features.
Applicable for one breaking position, two breaking positions and nonbreaking position switch.
I/O pluggable terminal block is used for ease to reliable connection.
Provided with RS-485 isolated communication interface as standard communication protocol, and characterized by
remote controlling, remote signaling and remote metering, capable of remote controlling of state/stop of generator
sets and ON/OFF of any power set of ATS.
Designed with modular structure, flame retardant ABS casing, and pluggable terminal block, for embedded
installation method, allowing a compact structure and ease for installation and maintenance.
ATS-WST 9 ATS Control System
The ATS-WST 9 microprocessor automatic transfer control system controls all operational functions of the ATS. Each
ATS-WST 9 is programmed at the factory to control customer specified options as well as standard switch features.

Setup, alarm acknowledgement, and review of actual data are easily accomplished using the controller’s soft keys and
display. The intuitive, interactive menu guides the user through controller setup and the entering of configuration data,
including communications and timing set points, adjustable control parameters (interlocks, alarms, and security) and
event logging.

Real-time metering of voltage (phase-to-phase and phase-to-neutral) and frequency of both sources is standard, and
metering of current and power is available. Real-time metering of voltage (phase-to-phase and phase-to-neutral) and
frequency of both sources is standard, and metering of current, power is available and historical trending. All metering can be
accessed through the menu.

The controller senses Source 1 (usually the electric utility source) and Source 2 (usually the engine generator source)
voltages and, by means of easy-to-see LEDs, indicates switch position and source availability. Through the menu, the
user can also review operational data such as active time delays, transfer inhibits, metered values, fault and alarm reports,
event records, and configuration settings. The controller also automatically displays the status of monitored conditions in color
coded banners at the top of the screen including faults and alarms, inhibits, and informational messages.

System type can set as: S1 (Mains) & S2 (Mains), S1 (Mains) & Scheduled Run & Scheduled Not Run (can be set as start
S2 (Generator), S1 (Generator) & S2 (Mains), S1 (Generator) & genset once a day/week/month whether with load or not).
S2 (Generator). Can control two generators to work as Cycle Run mode,
132x64 LCD with backlight, multilingual interface (including Master Run mode and Balance Run mode.
English, Chinese or other languages), push-button operation. Widely power supply range DC(8~35)V allows the
Collect and display 2-way 3-phase Voltage, Frequency and controller can bear 80V instantaneous current.
Phase. Large terminal space allows the controller can bear
Collect and display Active Power, Reactive Power, Apparent maximum 625V input voltage.
Power, Power Factor and Current. With RS485 isolated communication interface. With
S1/S2 separated over current warning/ trip alarm. “remote controlling, remote measuring, remote
NEL (Non-essential Load) trip function. communication, remote regulating” function by the
Display continuous power supply time and S1/S2 total ModBus communication protocol.
power supply time. Can remote start/stop the genset and remote control the
Automatic/Manual mode. In manual mode, can force the ATS to close or open.
switch to close or open. Suitable for various AC systems (3 phase 4-wires,
Sync Transfer function; in addition, Voltage Difference. 3-phase 3-wires, single-phase 2-wire, and 2-phase 3-wire).
Frequency Difference and Phase Difference can be Modular design, flame retardant plastic casing
displayed. pluggable terminal, built-in mounting, compact structure
Over/under voltage, loss of phase, reverse phase sequence, with easy installation.
over/under frequency protection. Protection Level : IP55 Gasket.
Phase Sequence Transfer function.
Automatic/Manual mode. In manual mode, can force the ATS-WST-9
switch to close or open.
All parameters can be set on site. Passwords authentication
ensures authorized staff operation only.
The genset can be Manual Test on site to achieve start/stop
operation.
ATS Controller has function of automatic Re-closing.
Closing output signal can be set as on intervals or as
continuous output.
Applicable for PC Three-stage, PC Two-stage, CB and CC
switch.
Applicable for 2 isolated neutral line.
Real-time clock (RTC); Event log Function (Event log can
record 99 items circularly).
ATS-WST-8B Series Dual Power Bypass Microprocessor controller.

ATS-WST-8B Control System


ATS-WST-8B is an intelligent dual power bypass switch module which integrates programmable function with
automatic measurement, LCD display and digital communication. It is with qualities of digitalization, intelligence, and
network. Measurement and control automation are realized for reducing human operation mistakes, so it is the ideal device
for dual power bypass switch.

ATS-WST-8B is composed of micro-processor, which is the core in the controller, and can precisely detect 2-way 3-phase
power, making correct judgment for abnormal power statuses (over voltage, under voltage, loss of phase, over frequency, under
frequency) and outputting free voltage control signals. After overall consideration about its bypass switch application, it can
be used directly on single and dual bypass switches, and manual or remote-control switches. It is with compact structure,
advanced circuit, simple wiring, and high reliability, and can be widely used in electrics, telecommunications, petroleum, coal,
metallurgy, railway, municipal administration, intelligent building fields, electric installations, service power supply and
debug system.

System type can set as: S1 Mains S2 Mains, S1 Mains S2 All parameters can be set on site. Password validation
Gen, S1 Gen S2 Mains, S1 Gen S2 Gen. is applied to prevent wrong operations for non-
4.3 inch’s solid color 240x128 pixel LCD display with professionals.
white backlit, multilingual interface (including English, The genset can be tested manually on site to achieve
Simpli fied Chinese and other languages), push-button start/stop operation.
operation. Real-time clock (RTC), event log function which can record
Collect and display voltage, frequency and phase sequence 200 items circularly.
of 2-way 3-phase. Black box record function, which can record 5 events
Collect and display active power, reactive power, apparent circularly, 60 data of 50s before each event record
power, power factor and current of load. and 10s after each event record.
Display position of main switch (working, testing, insulated) Scheduled routing start & scheduled not start function
and position of bypass switch (working, testing, insulated), for the genset, which can be set as start once a day/week/
Independent S1/S2 over current warning or trip alarm month and running with load or not.
funtions. Can control two generators to work in the mode of
NEL (Non-essential Load) trip function. circular running, master running and balanced running.
Display S1/S2 total kW energy, total kvar energy. Wide DC power supply range, which allows the
Display S1/S2 accumulated close times of main switch and controller to bear instantaneous 80V DC current input.
bypass switch. Large terminal space allows the controller to bear
Display continuous power supply time at present and last maximum 625VAC voltage input.
time, and S1/S2 total power supply time. Dual isolated RS485 communication interface having the
Can realize synchronous switchover function, and functions of “remote control, remote measuring, remote
display voltage difference, frequency difference and phase communication, remote regulating” by the ModBus-RTU
difference of 2 circuits. communication protocol, which can remotely start/
For energy-accumulated ATS, it shall close when switch PF stop the genset and control the breaker to close or open.
(close is prepared well) signal is active. Suitable for multiples of AC systems (3-phase 4-wire,
Over/under voltage, over/under frequency, over current, 3-phase 3-wire, single-phase 2-wire and 2-phase 3-wire).
loss of phase, inverse phase sequence protection functions. Modular design, flame retardant ABS plastic casing,
Automatic/Manual mode switchover; In manual mode, pluggable terminals, built-in mounting compact
close or open can be controlled manually. structure and easy installation.

ATS-WST-9
Registered Office Sale Offices
BENGALURU BENGALURU
PLOT NO.: 47-P, HARDWARE PARK, KIADB, #57, EBENEZER ENCLAVE, NORRIS ROAD, NEAR
HUVINAYAKANAHALLI, JALA HOBLI, YELAHANKA TALUK, NANJAPPA CIRCLE LANGFORD TOWN,
BENGALURU - 562 149. KARNATAKA INDIA BENGALURU - 560 025. KARANATAKA, INDIA

Manufacturing Units COIMBATORE


# 150, RA J ILLAM, NVM LAYOUT NEW SIDDHAPUDHUR
UNIT I COIMBATORE - 641 019. TAMIL NADU, INDIA
PLOT NO.: 47-P, HARDWARE PARK, KIADB,
HUVINAYAKANAHALLI, JALA HOBLI, YELAHANKA TALUK,
BENGALURU - 562 149. KARNATAKA, INDIA CHENNAI
# 945, GROUND FLOOR, MIG, FIRST MAIN ROAD, TNHB
COLONY, VELACHERY,
CHENNAI – 600 042. TAMIL NADU, INDIA
UNIT II
GOWTHAM GARDEN NO. 4, VEERAPANDI
COIMBATORE - 641 019. TAMIL NADU, INDIA
SECUNDERABAD
# 51, 1ST FLOOR, CHANDRAGIRI COLONY, NEAR RTA,
THRIMUGHERRY,
UNIT III SECUNDERABAD - 500 015. TELANGANA, INDIA
#764, 4TH PHASE, 707, YELAHANKA NEW TOWN,
BENGALURU - 560 064. KARNATAKA, INDIA
MUMBAI
# 101, MILLENIUM PLAZA BEHIND SAKINAKA
TELEPHONE EXCHANGE, ANDHERI - KURLA ROAD
SAKINAKA, ANDHERI (EAST)
MUMBAI - 400 072. MAHARASTRA, INDIA
Service Hotline:
[email protected]
DELHI
+91 639-1010-320 # G-10, G-11, GROUND FLOOR, BAISOYA COMPLEX,
NAYABANS, SECTOR-15,
Monday to Friday 8:00 am. to 5:00 pm. IST NOIDA – 201301. INDIA.

PC/ATES/V2/1118

You might also like