110 KV CURRENT TRANSFORMER
A Name of the Traction Sub-Station QLM TSS
B Name of the Equipment 110 KV CT
C Date of Testing 22/07/2022
RATIO TEST
Current Current
Sl. % Error % Error
injected recorded in Ratio C.T. Ratio Ratio found
No. specified obtained
in primary (A) secondary (A)
Equipment No. CT-15A Maker's Sl. No.725
200/5 A
1 40 1.000 200/5 40 40.00 5.0 0.00
2 80 2.000 200/5 40 40.00 5.0 0.00
3 120 3.000 200/5 40 40.00 5.0 0.00
4 160 4.050 200/5 40 39.51 5.0 -1.23
5 200 5.000 200/5 40 40.00 5.0 0.00
400/5 A
1 80 0.99 400/5 80 80.81 5.0 1.01
2 160 1.99 400/5 80 80.40 5.0 0.50
3 240 2.98 400/5 80 80.54 5.0 0.67
3 320 3.94 400/5 80 81.22 5.0 1.52
4 400 4.98 400/5 80 80.32 5.0 0.40