Galmovfr Q&A
Galmovfr Q&A
Manufacturing Corporation
rd
50 East 153 Street, Bronx, N.Y. 10451
Phone (718) 292-9000 Fax (718) 292-2034 10/8/2003
* The Fault Monitor is a patented door lock and gate switch protection device used to meet
ASME A17.1 RULE 210.15 and CAN/CSA-B44-M90 RULE 3.12.1.5.
If 120 volts AC is available and 200 to 230 volts AC is not available, G.A.L. can provide a
500 VA single phase step-up transformer from 120 volts AC to 220 volts AC.
Q5: What type of input signals does it require and what type of output contacts does it provide.?
A: The input signals (door open, door close and nudging) can be either dry contacts or voltage
signals ranging from 12 to 230 volts AC or DC, 30 milliamps.
The output contacts, such as the open and close limits, are rated at 230 volts, 10 amp AC.
Q8: What is the difference between the PAO2 and the PUO4 parameters?
A: The PAO2 plugs into the drive and can be left attached to it. It cannot be hand-held,
adjustments can only be made from the car top. This unit uses arrows to scan up or down
through the parameters. For example, when reaching parameter # 25 on the digital display, high
speed open can be changed by scanning up or down to the desired speed indicated on the
display.
The PUO4 is hand-held and can be used inside the elevator for door adjustments.
The desired parameter is entered directly from the numbers keypad, the digital display shows the
numbered entered. For example, parameter # 25 is entered for high speed open and its present
value displayed when the READ button is pressed. That value can then be changed to the exact
new speed by entering the new number and pressing the WRITE button.
This parameter unit also has uploading and downloading capabilities. This is desirable when all
doors in a group of elevators are to operate exactly the same. After adjusting one set of doors to
the desired operation, this information can than be transferred to all the other cars for the same
operation.