689 VRF 7.8.1.6 VRF SYSTEM
VRF/VRV Outdoor Unit:
Supply, lnstalla tion, testing & commissioning of variable refrigerant tlow
(VRF)/ variable refrigerant volume (VRV) air-cooler comprising condensing
units having following cooljng capacity bascd on indoor temperature 27'-30"C
DB / 19.5'-22"t WB and outdoor temperature 35"-40'C DB at high t'an speed
conditio[ suitable fbr installatjon & opemtion in tropicalized country like
Bangladesh including all mending good the damaged (all civil works) as per
detailed specifications & standard in accordance with fulllllment of ahove
specificalions and having relevant cenificales as mentioned below :
(1)Type:Compact weather proof outdoor type condensing unit.
(2).Compressor :DC Inverter scrool Compressor(only cooling)
(3) Refrigeranr : Refrigerant will be internationally accepted & recommended
and most commonly used gas (CFC freg). 13.00 Each
(4) Blower motor: well balance type direct driven centrifugal type blower fan.
(5) Power supply :380-440V .three phase ,50Hz AC Supply.
(6)Condensing pipe /coil:Made of copper .
(7) Energy Elficiency Ratio (EER) : 10.6 ( nrinimum)
(8)Sound Level :maximum 65dB at 1 meter
(9)Others Features :
(9.1)Well balanced in all respect having interlock with the fan couil unit.
(9.2)Compressor dully equipped with vibration isolator,thermostatic
&overload controls ,magnetic contactors and all other standard accessories
complete.
(9.3)Refrigerant copper pipe (from outdoor to indoor unit) with thermal
insulation ,refrigerant charging arrangement etc.(minimum length 10 meter)
(9.4)Reqd.Size PVC insulated &sheathed cable with ECC through water grade
690 VRF RA PVC pipecapacity
Cooling from outdoor to BTU/HR
: 228000 indoor unit. 1.00 Each
691 VRF RA Cooling capacity : 264000 BTU/HR 14.00 Each
692 VRF RA Cooling capacity : 288000 BTU/HR 5.00 Each
693 VRF RA Cooling capacity : 300000 BTU/HR 6.00 Each
694 VRF 7.9.1.1.2 VRF/VRV FAN COIL UNIT(INDOOR UNIT)
Supply ,installation ,testing &commissioning of the following capacity based
on indoor temperature 27-30 deg.C DB/19.5-22 deg.C WB and outdoor
temperature 35-40deg.C DB. ceiling mounted type ,variable Refrigerant Flow
Ducted unit consisting of thermo cabinet dynamically balanced centrifugal
blowers ,fan motors ,direct expansion type cooling coil,insulated drain tray
,electronic refrigerant flow control valve ,room temperature sensor & wired
remote controller ,infra-red sensor ,necessary supports as per the
specifications and drawings .The VRF system shall use R410A as refrigerant
.The unit shall operate when supplied with 220+_10%V,50Hz ,and single phase
electric power .Suitable for installation &operation in tropicalized country like
Bangladesh &as per detailed specifications &standard as mentioned below:
1.00 Each
(1)Direct Expansion system fan coil unit with well -balanced direct driven
centrifugal fan.
(2). Fancy & adjustable air circulating louver grill' removable & washable type
filter
(3)Condensing water drain out PVC Flexible pipe with necessary insulation.
(4)Thermostatic switch and Remote control switch .
(5) Sound Level (h):maximum 44 dB(A) at 1 meter
(6) Standard Major component shall be manufactured as per relevant
international standard &code.
Any brand manufacturcd or assenrbled in JAPAN / MALAYSIA / SOUTH KOREA
/ TAIWAN / THAILAND / USA / EU countries acceptcd / approved by the
Engineer-in-charge. in accordance rvifh fulfillment of the above specificrtions
695 VRF 7.9.1.3.2 Cooling capacity : 22,500-24,000 BTU/llR. 1.00 Each
C'elling mounted cassette type
696 VRF 7.9.1.5.4 Cooling capacity : 34,000-36,000 BTU/HR. 1.00 Each
Ducted Type
697 VRF 7.9.1.5.2 Celling mounted cassette type 57.00 Each
698 VRF 7.9.1.6.2 Cooling capacity : 46,000-48,000 BTU/HR. 73.00 Each
Celling mounted cassette type
699 VRF 7.9.1.7.1 Cooling capacity : 58000 BTU/HR. 40.00 Each
Celling mounted cassette type
700 VRF RA Ducted Type Units : Cooling Capacity : 96000BTU/HR , Air Flow Rate : 2800 cfm 5.00 Each
701 VRF RA Fresh Air Pre-Cooling Units , Ducted Type Units : Cooling Capacity : 6.00 Each
96000BTU/HR , Air Flow Rate : 1200 cfm ,ESP : 120 Pa
702 VRF RA Fresh Air Pre-Cooling Units , Ducted Type Units : Cooling Capacity : 4.00 Each
72000BTU/HR , Air Flow Rate : 900 cfm ,ESP : 100 Pa
703 VRF RA Fresh Air Pre-Cooling Units , Ducted Type Units : Cooling Capacity : 4.00 Each
48000BTU/HR , Air Flow Rate : 600 cfm ,ESP : 80 Pa
704 VRF 7.3.1 REFRIGERENT COPPER PIPES WITH THERMAL INSULATION 48.00 Meter
Supply & installation of copper refrigerant pipe complete with all necessary
pipe fitting such as bends, tees, reducers, sockets, gate valves etc.as per
drawing and direction. The concealed pipe shall be covered with pvc pipe with
nitrile rubber insulation having thickness l9 mm fbr VRF system and thickness
13 mm for split type unit and be installed with proper hangers supports, clamp
as per site condition and complying standard. Pipe work shall be tested into
the recommendation and direction of Engineer-in-charge.
Sl Code Ref. Description of works Qty. Unit Rate Amount
No. Clause in Tk. In Tk.
705 VRF 7.3.2 3/8"Dia. copper tube 600.00 Meter
706 VRF 7.3.3 1/2"Dia. copper tube 224.00 Meter
707 VRF 7.3.4 5/8"Dia. copper tube 1000.00 Meter
708 VRF 7.3.5 3/4"Dia. copper tube 264.00 Meter
709 VRF RA 7/8"Dia. copper tube 60.00 Meter
710 VRF 7.3.6 1"Dia. copper tube 300.00 Meter
711 VRF 7.3.7 1-1/8"Dia. copper tube 200.00 Meter
712 VRF 7.3.8 1-1/4"Dia. copper tube 48.00 Meter
713 VRF 7.3.9 1-3/8"Dia. copper tube 500.00 Meter
714 VRF RA 1-5/8"Dia. copper tube 80.00 Meter
715 VRF 7.4 REF NET JOINT 400.00 Set
Supply & fixing of Y shaped RefNet Joint made of pure copper with insulation
pressure tolerance not less 450 psi copper thickness should be 2 mm. Y
shaped RefNet joint as per actual requirement of site and as per direction of
716 VRF RA Supply of Wired Controller With IR Remote 182.00 Set
Central Monitoring Unit For VRF System:
Central Monitoring Unit shall monitor and control all indoor/ outdoor units of
the VRF AC system and set the desired temperature, speed of fan etc. This
central monitoring system for VRF shall communicate with Building
Management System over BAC net protocol
717 VRF RA Centralized Controller 11.00 set
CONTROL CABLE (For Communication Work).
718 VRF RA Supply of non-polar 2 core twisted pair solid core diameter 0.6mm cable. 150.00 Meter
719 VRF 4.33 Tray For Cable and Pipe : 2500.00 Meter
Supply, fitting. And fixing galvanized cable tray made of 18SWG (1.2mm) MS
Sheet evenly perforated with 7mm width capsule hole punch with self hanging
at top, joint clamp, including fabricating cost of electricity, tools and plants,
workshop charges, carriageof the same, cutting groves in the RCC or brick
work, mending good the damages with CC (1:2:4) etc. complete for all floors
accepted by the Engineer.
720 VRF 7.22.4 GALVANIZED IRON PIPES 100.00 Ft
Supply,installalion and testing of GI pipes of thc following sizes as per drawing
including supply and installation of Gl sockets, elbows, tees, traps, hangers,
unions and all other consumable etc. complete in all respect. The work shall
be complete as per instruction of Engineerin-charge and samples shall be
approved by the Engineer-in-Charge.
721 VRF Dia : 3" 140.00 Ft
722 VRF Dia : 2.5" 160.00 Ft
723 VRF Dia : 2" 220.00 Ft
724 VRF Dia : 1.5" 300.00 Ft
725 VRF Dia : 1" 300.00 Ft
726 VRF Dia : .75" 600.00 Ft
727 VRF 7.23.2 PIPE INSULATION (CONDENSATE DRAIN PIPING) 100.00 Ft
Supply and installation of insulalion on pipe surfaces as per drawing, technical
specifications and instructions of Engineer-incharge.
The insulation shall be 0 75" thick close-cell cross-linked polyethylene/
elastomeric type and shall be complete with adhesive backed with peel-off
paper.
728 VRF Dia : 3" 140.00 Ft
729 VRF Dia : 2.5" 160.00 Ft
730 VRF Dia : 2" 220.00 Ft
731 VRF Dia : 1.5" 300.00 Ft
732 VRF Dia : 1" 300.00 Ft
733 VRF Dia : .75" 600.00 Ft
734 VRF 7.21.2.1 Supply, installation, testing & commissioning of Fan including non return 14.00 Each
damper with all necessary accessories and fittings, Fixing for commissioning of
the equipment including all electrical & Civil works as follows technical
specification, drawing and time to time site instruction from Engineer-in-
charge.
735 VRF 7.21.2.2 Capacity :300 cfm ,ESP 100Pa 7.00 Each
736 VRF 7.21.2.5 Capacity :600 cfm ,ESP 200Pa 4.00 Each
737 VRF Capacity :1000 cfm ,ESP 300Pa 4.00 Each
738 VRF Capacity :1200 cfm ,ESP 500Pa 6.00 Each
739 VRF 7.21.2.20 CAR PARKING VENTILATION 3.00 Each
Exhaust Fan :Inline Ducted Axial Type
Capacity : 25000cfm ,ESP : 500Pa
740 VRF 7.21.2.20 Fresh Air Fan :Inline Ducted Axial Type 3.00 Each
Capacity : 25000cfm ,ESP : 500Pa
741 VRF 7.21.4.2 Jet Fan 12.00 Each
Supply, installation, testing & commissioning of Fan with VFD system
including with all necessary accessories and fittings, Fixing for commissioning
of the equipment including all electrical & Civil works as follows technical
specification, drawing and time to time site instruction from Engineer-in-
charge.
742 VRF 14.82.1 STAIRCASE PRESSURIZATION SYSTEM 18.00 Each
AIR LOUVER
Supply, installation, testing & commissioning of Louver made of Aluminium
of following size with all necessary accessories and fittings approved by
Engineer in charge
Sl Code Ref. Description of works Qty. Unit Rate Amount
No. Clause in Tk. In Tk.
743 VRF 7.21.4.2 PRESSURIZED FAN 2.00 Each
Supply, installation, testing & commissioning of Fan with VFD system
including with all necessary accessories and fittings, Fixing for commissioning
of the equipment including all electrical & Civil works as follows technical
specification, drawing and time to time site instruction from Engineer-in-
charge.
744 VRF 14.84.1 Duct 600.00 Sft
Supply, installation and testing of galvanized plain sheets duct
work of diffcrent sizes as per drawing and dctail technical specification
including supply of ducl hange./ isolator boxes,hanger rods. steel suppons and
all necessary malerials, duct materials and construction shall be completed
as per detail specification and SMACNA standards.Sample shall be approved
by Engineer-in-Charge. The work shall be completed as per drawing ard
instruction of Engineer- in-Charge.
745 VRF 14.84.2 Ducts made of 22SWC GP She 720.00 Sft
746 VRF 7.24.1.1 DUCT WITH ACCESSORIES 7000.00 Sft
METAL DUCTING
Supply, installation and testing of metal ducts of different sizes as per drawing
and detail technical spccification including supply of duct hanger/ isolator
boxes, hanger rods, steel supports, all other materialsand consumables. Duct
materials and construction shall he complete as per detail specification and
SMACNA standards. The work shall be complete as per instruction of Engineer-
in-charge and sample shall be approved by the Engirreer-in-Charge.
Ducts made of 24 SWC GP Sheet
747 VRF 7.24.1.2 Ducts made of 22SWC GP Sheet 6500.00 Sft
748 VRF 7.24.1.3 Ducts made of 20 SWC GP Sheets 3000.00 Sft
749 VRF 7.24.2.4 FLEXIBLE ROUND DUCT 200.00 Ft
Country of Manufacture: Malaysia
Dia 10"
750 VRF 7.24.3.1 ACOUSTIC LINING 2500.00 Ft
Supply and installation of Acoustic Duct Liner inside the ducl surface according
to the drawing and derail technical specification including supply of all
materials and consumables. The work shall be complete as per instruction of
Engineer-in-charge. and sample shall be approved by the Engineer-in-Charge.
Country of Manufacture: Malaysia/lndia
1" thick Acoustic duct liner
751 VRF 7.24.4 SPLITTER DAMPER 100.00 Each
Supply and installation of Splitter Damper as per drawing and detail technical
specification including supply of all materials aml consumables. The work shall
be complele as per instruction of Each Engineer-in-charge. and sample shall be
approved by the Engineer-inCharge.
752 VRF 7.24.5 MANUAL VOLUME CONTROL DAMPER 200.00 Each
Supply and installation ofOpposed Blade type Manual Vohjme ( ontrol Damper
as per technical specification including supply ofall materials and
consumables. The work shall be complete as per instruction of Engineer-in-
charge. and sample shall be approved by the Engineer-in-Charge.
753 VRF 7.24.6 FLEXIBLE DUCT JOINT CONNECTION 100.00 Each
Supply and installation of flexible ducts to make connection between
equipments viz FCU, AHU, FA-AHU , HRU-FA/AHU ,EAF and Ducts as per
drawing and detail technical specification including supply of all matcrials and
consumahles. Ihe rvork shall be complete as per instruction of Engineer-in-
charge. and sample shall be approved by the Engineer -in-Charge .
754 VRF 7.24.7 FRESH/EXHAUST AIR LOUVER 100.00 Each
Supply and installation of Fresh Air louver constructed of extruded aluminium/
galvanized steel sheet, complete with bird/ rodent screen. The work shall he
complete as per instruction of Engineer-in-chargc. and sample shall he
approved by the Engineer-inCharge
755 VRF 7. 25.1 DUCT INSULATION 2000.00 Sq.Ft
Supply and installation of insulation on the outside surl'ace of melal ducts as
per drawing and detail technical specification including supply ofall materials
and consumables. The work shall be complete as per instruction of Engincer-in-
charge. and samples shall be approved by the Engineer-in-Charge. The
insulation shall be fire retardanl Close call Nitrilc Ruhber class O. It shall be
adhesive backed with peel-off paper. The insulation shall have a maximum
allowable 'K' value of 0.04 W/mo C with Self Adhesiv and Alu Foil Outside.
Density: 50 kg/m3 ,Thermal Conductivity : 0.0362W/m.k.
Country of Manufacturere: Malaysia/China/India
756 VRF 7.25.2 lnsulation shall be 1.0" thick 5000.00 Sq.Ft
757 VRF 7.19.4.2 LOUVER, DIFFUSER & CRILLE 60.00 Each
Supply, installation, testing & commissioning of Louver, Diffuser , Damper &
Grille with complete all necessary accessories and Ftittings, Fixing for
commissioning of the equipment as fbllows technical specification. drawing
and time to time site instruction by the Engineer-in-charge.
All louver/Grill shall he constructcd wilh extruded aluntinium with powder
coat paint finish complele with face margin and fixing accessories. Neck
velocity shall not be more than 500 ft/min at a pressure drop of 0.08 inch WC
Fresh Air Grill
250x100mm
758 VRF 7.19.4.12 1200x400mm 60.00 Each
Sl Code Ref. Description of works Qty. Unit Rate Amount
No. Clause in Tk. In Tk.
759 VRF 7.19.7.1 Air Diffuser With Damper : 130.00 Each
150x150 mm
760 VRF 7.19.7.6 400x400 mm 80.00 Each
761 VRF 7.19.3.3 Exhaust Air Diffuser 68.00 Each
750x500mm
762 VRF 7.20.1.2 Fire Damper 8.00 Each
Supply, installation, testing & commissioning of I .5 Hours fire rating damper
20 GA.lntcrlocking steel blades LlL listed fusible link (165oF standard)roll
formed steel frame 20GA. Negator stainless steel closer spring.
Clountry of Origin: USA/UK/ EU/Japan
Country of Manufacture : Malaysia /lndia
550x2500mm
763 VRF RA MOTORIZED FIRE DAMPER 6.00 Each
Size : 1500x500mm
764 VRF 1.14.1.1 SURFACE CONDUIT WIRING (NYY)(THROUGH PVC CONDUIT) 3000.00 meter
Surface conduit wiring with the following pVC insulated and sheathed
stranded cable (NYY) / XLPE insulated and pVC sheathed stranded cable (2Xy)
& pVC insulated Green / Yellow bi-colour ECC wire (BYA) through pVC conduit
of reputed manufacturer complete with fixing materials, other accessories
etc. as required including mending the damages good. All electrical contacts
shall be of brass / copper connected through connector or soldering (no
twisting sharr be allowed) and cables shal be manufactured and tested
according to IEC / BS / VDE standards along with relevant BDS standard as per
detailed specification mentioned in Annexure- 1 . The work shaI be caried out
as per direction & approval ofthe Engineer ln Charge.
Cables manufactured by Govt. of Bangladcsh owned / shared company ltd.
(Eastern cables) approved by the Engineer In Charge.
1C-4x2.5sqmm (NYY) with 2.5 sqmm (BYA) ECC wire through pVC pipe of
765 VRF 1.14.1.2 1C-4x4sqmm (NYY) with 4 sqmm (BYA) ECC wire through pVC pipe of 348.00 meter
minimum inner dia 30 mm having wall thickness of 1.9 mm
766 VRF 1.14.1.3 1C-4x6sqmm (NYY) with 6 sqmm (BYA) ECC wire through pVC pipe of 200.00 meter
minimum inner dia 40 mm having wall thickness of2.2 mm
767 VRF 1.14.1.4 1C-4x 10 sqmm (NYY) with 10 sqmm (BYA) ECC wire through PVC pipe of 140.00 meter
minimum inner dia 40 mm having wall thickness of 2.2 mm
768 VRF 1.14.1.5 1C-4x 16sqmm (NYY) with 16 sqmm (BYA) ECC wire through PVC pipe of 150.00 meter
minimum inner dia 40 mm having wall thickness of 2.2 mm
769 VRF 1.14.1.6 1C-4x 25sqmm (NYY) with 16 sqmm (BYA) ECC wire through PVC pipe of 600.00 meter
minimum inner dia 50 mm having wall thickness of 2.5 mm
770 VRF 1.16.1.1 1C-2xl.5sqmm (BYA) cable with 1.5sqmm (BYA) ECC wire through PVC pipe of 300.00 meter
minimum inner dia l6mm having wall thickness of 1.5 mm
771 VRF RA Electrical Control Panel For VRF Indoor ,Outdoor & Fans 17.00 Each
772 VRF 7.2.1.2.2 SPLIT TYPE AIR COOLER 1.00 Each
Supply, inslallation, testing & commissioning of split type air-cooler with
inverter comprising condensing and evaporating units having following cooling
capacity based on indoor temperature 27-30 deg.C DB / 19.5-22 deg.C WB
and outdoor temperature 35-40deg .C DB at high fan speed condition suitable
for installation & operation in tropicalized country like Bangladesh & as per
detailed specifications & standard as mentioned below:
OUTDOOR UNIT / CONDENSING UNIT
(1 ). Type : Compact weather proof outdoor q/Pe condensing unit (2).
Compressor : Hermitically sealed reciptocating / rotary compressor. (3).
Refrigerant : lntemationally accepted & recommended and most commonly
used gas (CFC free) (4). Blower motor : Well balanced type direct driven
centrifugal type blower fan (5). Power supply : (5.1). 200-250 V, single phase,
50 Hz AC supply [up to 30000 BTU/HR(5.2). 380-440 v 3-phase.50 Hz. AC supplv
[above 30000 BTU/HR (6). Condensing pipe / coil : Made of copper 7).
EER/COP : For upto 60000 BTU/HR EER should he minimum 9.23
(BTU/HR)/WATT and COP Should be minimum 2.70 (w/W) For above 60000
BTU/HR EER shouLd be minimum 10.5 (BTU/HR)/WATT and COP should be
minimum:3.08 (W/W)(8). Others features (8.1). Well balanced in all tespect
having interlock with the fan coil unit.
(8.2). Compressor dully equipped with vibration isolator, thermostatic &
overload controls, magnetic contactors and all other stanrlard accessories
complete. (8.3). Refrigerant copper pipe (From outdoor to indoor unit] with
thermal insulation, refrigerant charging arrangenrent etc.(Minm length10 mtr)
(8.4). Reqd. size PVC insulated & sheathed cable wirh EC( through water grade
PVC pipe from outdoor to indoor unit. (8.5) Sound level : maximum 65 dB(A)
at 1 merer
772 VRF 7.2..2.1.2 INDOOR UNIT /(lnverter
Wall mounted FAN COILType)
UNIT 1.00 Each
773 VRF 7.20.2.7 Supply and installation of opposed blade type volume control damper 1.00 Each
constructed with 18 BWG sheet steel painted with two coats of synthetic
black paint.
The damper shall have adjustable locking arrangement with worm gear
operable from outside duct work and shall be flanged end type suitable to
mount on flanged end duct work. Volume control dampers shall be as per
layout drawings and direction of Engineer-in-Charge.
400 x 200 mm

774 VRF 7.20.2.8 500 x 250 mm 1.00 Each


775 VRF RA Shop drawing & As-Bult drawing 1.00 LS
Sl Code Ref. Description of works Qty. Unit Rate Amount
No. Clause in Tk. In Tk.
776 VRF RA Testing Commissioning and Balancing works 1.00 LS
777 VRF RA Operation and maitenance for 1 year 1.00 Year