ACCOMPLISHMENT REPORT
ENGINEERING DEPARTMENT
WEEK 3
November 22 - December 6, 2022
Submitted by:
Submitted to:
RONALDO D. VALENZUELA
Engineering Supervisor
ARNOLD S. DEPASUCAT
Mill and Boiler superintendent
Main Steam
Sampling Atomizing Pingrate
450
Psi Superheater Tubes
Steam Drum
Downcomer Upriser
Shell Thickness 60 mm
End Thickness 50 mm
Mass 40 tonnes
The steam drum water level controls, regulate the feed water supply, to
maintain a near constant level of water in the boiler steam drum under varying
load conditions. The control is further complicated by fluctuation in the main
steam flow, plus swell and shrink of steam drum water level during load
changes.
Elements Definition
LT204A LHS Steam Drum Level Transmitter
LT204B RHS Steam Drum Level Transmitter
ES204 Steam Drum Level Transmitter
LY204 Steam drum Level Transmitter Signal Averager
FT201 Feed Water Flow Transmitter
LC204 Steam Drum Level Controller
LC201 Feed Water Flow Controller
LCV201 Feed Water Regulating Valve(B138)
Note: The Feed Water Flow Controller setpoint cannot be adjusted by the
operator in this mode of operation.
ii) RHS Steam Drum Level Transmitter LT204B selected for service.
Failure of RHS transmitter is indicated on the controller. A lowinput
failure turns off the Steam Drum level > Low interlock. This will generate
a Low Steam Drum level MFT trip of the Oil Burner and a direct MCC
trip of Bagasse Feeders. A high input failure activates the Drum Level
High Alarm.
iii) Average of LHS and RHS transmitters selected for service.
Failure of the LHS or RHS transmitter.The controller input will be the
average of the good drum level signal and the failed drum level signal
(0% for low input 100% forhigh input). The Drum Level High Alarm or
Drum Level Low Alarm may be triggered.
WARNING: In this mode the average signal does not provide a correct level
signal and the Steam Drum level selector must be selected to the healthy level
transmitter immediately to ensure correct and safe operation of boiler.
On low input failure of both the LHS and the RHS transmitters, the
failure is indicated on the controller and the Steam Drum Level > Low
interlock is turned off. This will generate a Low Steam Drum Level MFT
trip of the Oil Burners and a direct MCC trip of Bagasse Feeders.
On high input failure of both the LHS and RHS transmitters, the failure
will be indicated on the controller and the Drum Level High Alarm will be
raised.
On low input failure of one transmitter and high input failure of theother
the input to the controller will be 50% and no alarms will be raised.