Professional Documents
Culture Documents
HVAC Specification Detail Guide: A Guide To Specifying ROCKWOOL Insulations For HVAC Applications
HVAC Specification Detail Guide: A Guide To Specifying ROCKWOOL Insulations For HVAC Applications
HVAC Specification Detail Guide: A Guide To Specifying ROCKWOOL Insulations For HVAC Applications
Detail Guide
A guide to specifying ROCKWOOL insulations
for HVAC applications
1. General
■ Insulation materials should have a Euroclass of either A1,
A2, or B, should have a FIGRA RCT of less than 1.0, and
should not have a potential to flashover. The Lambda value
of the Insulation must also be quoted, both manufactured
and aged value.
■ F
or all mineral wool insulation products, test evidence
must be available showing that the fibres from which the
products are made are not classified as a possible human
carcinogen, as detailed by European Directive 97/69/EC
and the Approved Supply List of CHIP98.
2
2. Specialist thermal insulation sub-contractor
Include for all thermal insulation to be carried out by an approved Specialist Thermal Insulation Contractor selected
from the list of preferred Specialist Contractors scheduled elsewhere in this specification. Specialist Thermal Sub-
Contractor shall be a member of the :-
3. Scope
This specification covers the thermal insulation of pipes, ductwork and equipment generally in the temperature range of
0°C to 250°C. The specification is for guidance purposes only and should be read in conjunction with recommendations
given in BS 5970 and BS 5422.
The following British Standards are applicable to this thermal insulating specification:
■ BS5422:2009 Method for specifying thermal insulating materials for pipes, tanks, vessels, ductwork and equipment
operating within the temperature range -40°C to +700°C.
■ BS 5970:2001 Code of practice for thermal insulation of pipework and equipment (in the temperature range –100ºC
to +870ºC).
■ BS EN 14303:2009 Thermal insulation products for building equipment and industrial installations. Factory made
mineral wool products (MW).
■ BS 874:1986 Methods for determining thermal insulating properties with definitions of thermal insulating terms.
■ BS 476 - Part 4:1970 Fire tests on building materials and structures. Non-combustibility test for materials.
■ BS 476 - Part 6:1989 Fire tests on building materials and structures. Method of test for fire propagation of products.
■ BS 476 - Part 4:1970 Fire tests on building materials and structures. Method of test to determine the classification of
the surface spread of flame of products.
3
4. Internal services - concealed from view (false ceilings/voids/chases)
4.1 Heating/HWS
Pipes to be insulated with ...... *mm thick ROCKWOOL RockLap H&V Pipe Sections, having a nominal density not less
than 120 kg/m3 , with a factory applied facing which is a laminate of close mesh reinforcement between two layers of
foil including integral lap for fixing. The whole to comply with BS5422:2009 and BS 5970 water vapour permeance
and Building Regulations Class 0 definition. Fixing to be in accordance with manufacturer’s instructions, by peeling
protective tape from self-adhesive lap and pressing lap smoothly over joint. Where adjacent Sections abut, approved 75
mm wide aluminium tape to be used to maintain integrity of the vapour barrier.
*insert required thickness
Insulation as 4.1. Attention to be paid to maintaining integrity of the vapour barrier. At termination points, insulation
edges to be over-taped and returned to the piping surface. Where the insulation abuts pipe supports, the insulation is
to be taped to all supports.
To be insulated with ROCKWOOL Ductwrap/Ductslab, nominal density 45 kg/m3, having a factory applied reinforced
aluminium foil facing. Joints to be securely taped with 75 mm minimum wide soft aluminium self adhesive tape. The
insulation on the underside of the ducting to be additionally secured by suitable insulation hangers @ 300 mm centres.
■ 19 - 22 swg x 50 mm mesh galvanised wire netting. Where a vapour barrier is required, care to be taken when
applying wire mesh support to avoid damaging the aluminium foil.
or
or
■ Subject to the client’s approval, alternative fixings can be used in place, or alongside the above.
For below ambient operating temperatures a vapour barrier is required, provision should be made, at exposed edges,
to carry the aluminium foil to the duct surface.
Where support pins/hangers puncture the foil, they should be sealed using aluminium foil tape to maintain the vapour
barrier.
Ductslab of the same density and facing as Ductwrap can be used where aesthetic or mechanical requirements prevail.
All valves and flanges on heating, HWS, CWS and chilled water pipework to be insulated with oversize ROCKWOOL
RockLap H & V Pipe Sections. Finish and thickness to be as adjacent pipework services.
4
5. Internal services – exposed to view
5.1 Heating/HWS
Generally as 4.1. Should the exposed pipework be liable to mechanical damage, i.e. sited at low level, the insulation to
be protected with 22 gauge stucco embossed aluminium cladding secured with pop rivets. Aluminium securing bands
may be omitted under cladding.
As specification 4.2. Where the insulation is protected with sheeting, care should be taken to ensure that the vapour
barrier is not punctured by the rivets. Aluminium banding and seals may be used as an alternative to pop rivets.
As specification 4.3. Where aluminium cladding is used at low level, wire netting reinforcement to be omitted.
As specification 4.4. Where insulation is finished with aluminium cladding, valve and flange boxes to be protected with
purpose made aluminium covers.
6.1 Heating/HWS
To be insulated as specification 4.1, finished and protected with 22 gauge stucco embossed aluminium sheeting,
secured by means of pop rivets at 225 mm centres.
To be insulated as specification 4.2, finished and protected with 22 gauge stucco embossed aluminium sheeting
secured by means of aluminium banding and seals at 450 mm centres. Alternatively, if pop rivets are used, care should
be taken to avoid puncturing the vapour barrier.
To be insulated with ROCKWOOL semi-rigid slabs, nominal density 45 kg/m3 , finished and protected with 22 gauge
stucco embossed aluminium cladding secured with pop rivets at 225 mm centres. For high velocity and circular
ductwork, insulation to be ROCKWOOL Lamella Mats.
To be insulated with purpose made removable 22 gauge stucco embossed aluminium boxes, lined with ROCKWOOL
ProRox WM960.
To be insulated with ROCKWOOL Lamella Mat finished and protected with 22 gauge stucco embossed aluminium
cladding secured with pop rivets at 225 mm centres. Domed tops of calorifiers to be finished in segments. Manway
chests, flanges and covers of heat exchangers to be enclosed in removable stucco embossed aluminium covers lined
with ROCKWOOL ProRox WM960.
Boiler flues and chimneys to be insulated as described in BS 5970 with a minimum of 50 mm thick ROCKWOOL ProRox
WM960, finished generally as in Specification 6.1.
5
7. External services
7.1 Heating/HWS
Generally as specification 4.1. Please select the finish from the list of alternatives below.
Alternative Finishes
e) S
elf Adhesive Weather Resistant Zero Perm Multi-Layer Laminate:
Apply multi-layer laminate directly over ducts and pipework, ensuring 75 mm overlap for a complete vapour barrier.
Fixed and installed in accordance with BS5790.
f) Polyisobutylene:
Polyisobutylene, minimum thickness 0.8 mm.
Fixed and installed in accordance with BS5790.
6
8. Insulation thickness tables
BS5422:2009
Scotland
7
Table 6 (BS5422:2009)
Minimum insulation thickness for chilled and cold water steel pipes to control condensation on a high emissivity outer surface (0.9) with an ambient
temperature of +25°C and a relative humidity of 80%
17 8 20 12 20 14 20
21 9 20 12 20 14 20
27 9 20 12 20 15 20
33 9 20 13 20 16 20
42 10 20 14 20 17 20
48 10 20 14 20 18 20
60 11 20 15 20 18 20
76 11 20 15 20 19 20
89 11 20 16 20 20 20
102 12 25 16 25 20 25
114 12 25 16 25 21 25
140 12 25 17 25 21 25
169 12 25 17 25 22 25
219 13 25 18 25 23 25
245 13 25 18 25 23 25
273 13 25 18 25 24 25
324 13 25 19 25 24 25
356 13 30 19 30 24 30
406 14 30 19 30 25 30
456 14 40 20 40 25 40
508 14 40 20 40 25 40
558 14 40 20 40 26 40
610 14 40 20 40 26 40
NOTE 1 - Thicknesses given are calculated specifically against the criteria noted in the table.
These thicknesses may not satisfy other design requirements. In situations where the ambient air temperature is greater
than 25ºC and/or the relative humidity exceeds 80%, these thicknesses will not be sufficient to control condensation.
NOTE 2 - These thicknesses only apply where the vapour barrier has a dark, matt finish.
8
Table 7 (BS5422:2009)
Minimum insulation thickness for chilled and cold water steel pipes to control condensation on a high emissivity outer surface (0.9) with an ambient
temperature of +25°C and a relative humidity of 80%
10 7 20 10 20 12 20
12 7 20 10 20 13 20
15 8 20 11 20 13 20
22 9 20 12 20 15 20
28 9 20 12 20 15 20
35 10 20 13 20 16 20
42 10 20 14 20 17 20
54 10 20 14 20 18 20
76 11 20 15 20 19 20
108 12 25 16 25 21 25
NOTE 1 - Thicknesses given are calculated specifically against the criteria noted in the table.
These thicknesses may not satisfy other design requirements. In situations where the ambient air temperature is greater
than 25ºC and/or the relative humidity exceeds 80%, these thicknesses will not be sufficient to control condensation.
NOTE 2 - These thicknesses only apply where the vapour barrier has a dark, matt finish.
9
Table 8 (BS5422:2009)
Minimum insulation thickness for chilled and cold water steel pipes to control condensation on a low emissivity outer surface (0.05) with an ambient
temperature of +25°C and a relative humidity of 80%
17 16 20 22 25 28 30
21 17 20 24 25 30 35
27 19 20 26 30 33 35
33 20 25 27 30 35 35
42 21 25 30 30 37 40
48 22 25 31 35 39 40
60 24 25 33 35 42 45
76 26 30 36 40 44 45
89 27 30 37 40 47 50
102 28 30 39 40 49 50
114 29 30 40 40 51 55
140 31 35 42 45 53 55
169 32 35 45 45 57 60
219 34 35 48 50 61 65
245 36 40 50 50 63 65
273 37 40 51 55 65 65
324 38 40 53 55 68 70
356 39 40 54 55 70 70
406 40 45 56 60 72 75
456 41 45 58 60 75 75
508 42 45 60 60 77 80
558 44 45 61 65 78 80
610 45 45 63 70 80 90
NOTE 1 - Thicknesses given are calculated specifically against the criteria noted in the table.
These thicknesses may not satisfy other design requirements. In situations where the ambient air temperature is greater
than 25ºC and/or the relative humidity exceeds 80%, these thicknesses will not be sufficient to control condensation.
10
Table 9 (BS5422:2009)
Minimum insulation thickness for chilled and cold water steel pipes to control condensation on a low emissivity outer surface (0.05) with an ambient
temperature of +25°C and a relative humidity of 80%
NOTE 1 - Thicknesses given are calculated specifically against the criteria noted in the table.
These thicknesses may not satisfy other design requirements. In situations where the ambient air temperature is greater
than 25ºC and/or the relative humidity exceeds 80%, these thicknesses will not be sufficient to control condensation.
Table 10 (BS5422:2009)
Indicative thickness of insulation for cooled and chilled water systems to control heat gain – low emissivity outer surfaces (ε = 0.05)
NOTE 1 - Insulation thicknesses in this table have been calculated according to BS EN ISO 12241:2008 using
standardised assumptions: horizontal pipe in still air at 25ºC, emissivity of outer surface of insulated system as specified.
NOTE 2 - Thicknesses derived solely against the criteria noted in this table may not necessarily satisfy other design
requirements such as control of condensation.
NOTE 3 - Heat gain relates to the specified thickness and temperature.
11
Table 11 (BS5422:2009)
Indicative thickness of insulation for cooled and chilled water systems to control heat gain – high emissivity outer surfaces (ε = 0.9)
NOTE 1 - Insulation thicknesses in this table have been calculated according to BS EN ISO 12241:2008 using
standardised assumptions: horizontal pipe in still air at 25ºC, emissivity of outer surface of insulated system as specified.
NOTE 2 - Thicknesses derived solely against the criteria noted in this table may not necessarily satisfy other design
requirements such as control of condensation.
NOTE 3 - Heat gain relates to the specified thickness and temperature.
12
Table 12 (BS5422:2009)
Minimum insulation thickness for condensation control on ductwork carrying chilled air in ambient conditions: indoor still air temperature +25°C, relative
humidity 80%, dewpoint temperature 21.3°C
Ductwrap
NOTE 1 - Thicknesses given are calculated specifically against the criteria noted in the table.
These thicknesses may not satisfy other design requirements. In situations where the ambient air temperature is greater
than 25ºC and/or the relative humidity exceeds 80%, these thicknesses will not be sufficient to control condensation.
Ductslab
NOTE 1 - Thicknesses given are calculated in accordance with BS EN ISO 12241:2008 based on 0.6m vertical flat
surface of rectangular duct but are also adequate for horizontal surfaces.
NOTE 2 - Thicknesses given are calculated specifically against the criteria noted in the table These thicknesses may not
satisfy other design requirements.
NOTE 3 - Refer to Annex B, Table B. 1 for surface emissivities of common finishing materials. In situations where the
ambient air temperature is greater than 25ºC and/or the relative humidity exceeds 80%, these thicknesses will not be
sufficient to control condensation.
13
Table 13 (BS5422:2009)
Indicative thickness of insulation for ductwork carrying warm air to control heat loss.
Ductwrap
Ductwrap
Table 14 (BS5422:2009)
Indicative thickness of insulation for chilled and dual-purpose ducting to control heat transfer.
Ductwrap
Ductwrap
14
Table 15 (BS5422:2009)
Indicative thickness of insulation for non-domestic heating services to control heat loss – low emissivity outer surfaces (ε =0.05)
NOTE 1 - Insulation thicknesses in this table have been calculated according to BS EN ISO 12241:2008 using
standardised assumptions: horizontal pipe in still air at 15°C, emissivity of outer surface of insulated system as specified.
NOTE 3 - The thicknesses in this table are applicable to pipes serving commercial solar hot water panels.
15
Table 16 (BS5422:2009)
Indicative thickness of insulation for non-domestic heating services to control heat loss – high emissivity outer surfaces (ε =0.9)
NOTE 1 - Insulation thicknesses in this table have been calculated according to BS EN ISO 12241:2008 using
standardised assumptions: horizontal pipe in still air at 15°C, emissivity of outer surface of insulated system as specified.
NOTE 3 - The thicknesses in this table are applicable to pipes serving commercial solar hot water panels.
16
Table 17 (BS5422:2009)
Indicative thickness of insulation for non-domestic hot water service areas to control heat loss – low emissivity outer surfaces
Outside diameter of steel pipe Thickness of ROCKWOOL Rocklap H&V Pipe Section (mm)
on which insulation thickness
has been based (mm) Calculated thickness (mm) Advised thickness (mm) Heat loss (W/m)
17.2 26 30 6.6
21.3 28 30 7.13
26.9 30 30 7.83
33.7 32 35 8.62
42.4 33 35 9.72
48.3 34 35 10.21
60.3 36 40 11.57
76.1 38 40 13.09
88.9 38 40 14.58
114.3 39 40 17.2
139.7 40 40 19.65
168.3 41 45 22.31
219.1 41 45 27.52
273 42 45 32.4
NOTE 1 - Insulation thicknesses in this table have been calculated according to BS EN ISO 12241:2008 using
standardised assumptions: horizontal pipe at 60°C in still air at 15°C, emissivity of outer surface of insulated system as
specified.
17
Table 18 (BS5422:2009)
Indicative thickness of insulation for non-domestic hot water service areas to control heat loss – high emissivity outer surfaces
Outside diameter of steel pipe Thickness of ROCKWOOL Rocklap H&V Pipe Section (mm)
on which insulation thickness
has been based (mm) Calculated thickness (mm) Advised thickness (mm) Heat loss (W/m)
17.2 31 35 6.6
21.3 33 35 7.13
26.9 35 35 7.83
33.7 37 40 8.62
42.4 38 40 9.72
48.3 40 40 10.21
60.3 42 45 11.57
76.1 44 45 13.09
88.9 44 45 14.58
114.3 45 45 17.2
139.7 46 50 19.65
168.3 47 50 22.31
219.1 48 50 27.52
273 49 50 32.4
NOTE 1 - Insulation thicknesses in this table have been calculated according to BS EN ISO 12241:2008 using
standardised assumptions: horizontal pipe at 60°C in still air at 15°C, emissivity of outer surface of insulated system as
specified.
18
Table 19 (BS5422:2009)
Indicative thickness of insulation for domestic heating and hot water systems having low emissivity outer surfaces
Outside diameter of copper Thickness of ROCKWOOL Rocklap H&V Pipe Section (mm)
pipe on which insulation
thickness has been based (mm) Calculated thickness (mm) Advised thickness (mm) Heat loss (W/m)
8 8 20 7.06
10 10 20 7.23
12 13 20 7.35
15 14 20 7.89
22 17 20 9.12
28 19 20 10.07
35 20 20 11.08
42 21 25 12.19
54 22 25 14.12
NOTE 1 - Insulation thicknesses in this table have been calculated according to BS EN ISO 12241:2008 using standardised
assumptions: horizontal pipe at 60°C in still air at 15°C, emissivity of outer surface of insulated system as specified.
NOTE 2 - Heat loss relates to the specified thickness and temperature.
NOTE 3 - This table is applicable to pipes serving solar hot water panels.
Table 20 (BS5422:2009)
Indicative thickness of insulation for domestic heating and hot water systems having high emissivity outer surfaces
Outside diameter of copper Thickness of ROCKWOOL Rocklap H&V Pipe Section (mm)
pipe on which insulation
thickness has been based (mm) Calculated thickness (mm) Advised thickness (mm) Heat loss (W/m)
8 11 20 7.06
10 13 20 7.23
12 16 20 7.35
15 18 20 7.89
22 21 25 9.12
28 23 25 10.07
35 24 25 11.08
42 25 25 12.19
54 27 30 14.12
NOTE 1 - Insulation thicknesses in this table have been calculated according to BS EN ISO 12241:2008 using standardised
assumptions: horizontal pipe at 60°C in still air at 15°C, emissivity of outer surface of insulated system as specified.
NOTE 2 - Heat loss relates to the specified thickness and temperature.
NOTE 3 - This table is applicable to pipes serving solar hot water panels.
19
Table 22 (BS5422:2009)
Minimum insulation thickness to control the surface temperature of a non-metallic surface with a surface emissivity of 0.90 and design cold face
temperature of 59°C
NOTE 1 - Insulation thicknesses in this table have been calculated according to BS EN ISO 12241:2008 using standardised
assumptions: horizontal pipe in still air at 20°C. Surface emissivity corresponding to outer surface specified.
NOTE 2 - Maximum heat loss values for intermediate operating temperatures may be deduced by interpolation.
NOTE 3 - Heat loss measured in Watts per metre (W/m) relates to the specified thickness and temperature.
NOTE 4 - The thermal conductivity of insulation materials increases with mean temperature and for any given material. The use of a
different thermal conductivity can be required for each operating temperature.
NOTE 5 - These thicknesses may not satisfy other design requirements, in particular those for control of surface temperature (see Table
22, Table 23 and Table 24).
NOTE 6 - To simplify the use of this table the values shaded have been adjusted to avoid the specification of apparently anomalous
results given by the calculation method in BS EN ISO 12241, due to the transition from turbulent to laminar flow.
20
Table 23 (BS5422:2009)
Minimum insulation thickness to control the surface temperature of a metallic surface with a surface emissivity of 0.05 and design cold face temperature of 50°C
NOTE 1 - Insulation thicknesses in this table have been calculated according to BS EN ISO 12241:2008 using standardised
assumptions: horizontal pipe in still air at 20°C. Surface emissivity corresponding to outer surface specified.
NOTE 2 - Maximum heat loss values for intermediate operating temperatures may be deduced by interpolation.
NOTE 3 - Heat loss measured in Watts per metre (W/m) relates to the specified thickness and temperature.
NOTE 4 - The thermal conductivity of insulation materials increases with mean temperature and for any given material. The use of a
different thermal conductivity can be required for each operating temperature.
NOTE 5 - These thicknesses may not satisfy other design requirements, in particular those for control of surface temperature (see Table
22, Table 23 and Table 24).
NOTE 6 - To simplify the use of this table the values shaded have been adjusted to avoid the specification of apparently anomalous
results given by the calculation method in BS EN ISO 12241, due to the transition from turbulent to laminar flow.
21
Table 24 (BS5422:2009)
Minimum insulation thickness to control the surface temperature of a non-metallic surface with a surface emissivity of 0.90 and design cold face
temperature of 50°C
NOTE 1 - Insulation thicknesses in this table have been calculated according to BS EN ISO 12241:2008 using standardised
assumptions: horizontal pipe in still air at 20°C. Surface emissivity corresponding to outer surface specified.
NOTE 2 - Maximum heat loss values for intermediate operating temperatures may be deduced by interpolation.
NOTE 3 - Heat loss measured in Watts per metre (W/m) relates to the specified thickness and temperature.
NOTE 4 - The thermal conductivity of insulation materials increases with mean temperature and for any given material. The use of a
different thermal conductivity can be required for each operating temperature.
NOTE 5 - These thicknesses may not satisfy other design requirements, in particular those for control of surface temperature (see Table
22, Table 23 and Table 24).
NOTE 6 - To simplify the use of this table the values shaded have been adjusted to avoid the specification of apparently anomalous
results given by the calculation method in BS EN ISO 12241, due to the transition from turbulent to laminar flow.
22
Table 24 (BS5422:2009)
Minimum insulation thickness to control the surface temperature of a metallic surface with a surface emissivity of 0.05 and design cold face temperature of 55ºC
NOTE 1 - Thicknesses given are calculated specifically against the criteria noted in the table, Adopting these thicknesses may not
necessarily satisfy other design requirements.
NOTE 2 - To simplify the use of this table the values shaded have been adjusted to avoid the specification of apparently anomalous
results given by the calculation method in BS EN ISO 12241, due to the transition from turbulent to laminar flow.
23
Table 24 (BS5422:2009)
Minimum insulation thickness to control the surface temperature of a metallic surface with a surface emissivity of 0.18 and design cold face temperature of 55°C
NOTE 1 - Thicknesses given are calculated specifically against the criteria noted in the table, Adopting these thicknesses may not
necessarily satisfy other design requirements.
NOTE 2 - To simplify the use of this table the values shaded have been adjusted to avoid the specification of apparently anomalous
results given by the calculation method in BS EN ISO 12241, due to the transition from turbulent to laminar flow.
24
Table 24 (BS5422:2009)
Minimum insulation thickness to control the surface temperature of a metallic surface with a surface emissivity of 0.26 and design cold face temperature of 55°C
NOTE 1 - Thicknesses given are calculated specifically against the criteria noted in the table, Adopting these thicknesses may not
necessarily satisfy other design requirements.
NOTE 2 - To simplify the use of this table the values shaded have been adjusted to avoid the specification of apparently anomalous
results given by the calculation method in BS EN ISO 12241, due to the transition from turbulent to laminar flow.
25
Table 25 (BS5422:2009)
Heat loss from bare surfaces calculated in accordance with BS EN ISO 12241:2008 (black steel pipes)
Operating conditions:
Ambient still air: 20ºC
Surface emissivity: 0.07
Height of flat surfaces: 0.6m
Surface orientation: horizontal
26
Table 26 (BS5422:2009)
Heat loss from bare surfaces calculated in accordance with BS EN ISO 12241:2008 (copper pipes – commercial grade, scoured to a shine)
Operating conditions:
Ambient still air: 20ºC
Surface emissivity: 0.07
Height of flat surfaces: 0.6m
Surface orientation: horizontal
27
Table 27 (BS5422:2009)
Heat loss from bare surfaces calculated in accordance with BS EN ISO 12241:2008 (copper pipes – oxidised)
Operating conditions:
Ambient still air: 20ºC
Surface emissivity: 0.70
Height of flat surfaces: 0.6m
Surface orientation: horizontal
28
Table 28 (BS5422:2009)
Minimum insulation thickness to protect steel pipes against freezing under selected industrial process conditions
NOTE 1 - Thicknesses given are calculated specifically against the criteria noted in the table These thicknesses may not
satisfy other design requirements.
NOTE 2 - Some of the insulation thicknesses given are too large to be applied in practice but a selection is included
to highlight the difficulty in protecting small diameter pipes against freezing. To provide the appropriate degree of
frost protection to certain sizes of pipes, it may be necessary to provide additional heat to the system, for example by
circulating the water or heat tracing.
NOTE 3 - Assumed densities (ƿ) and heat capacities (cp) are as follows:
29
Table 29 (BS5422:2009)
Minimum insulation thickness required to give protection against freezing under specified commercial and institutional conditions
15 13.6 48 50 269
22 20.2 10 20 36 40
28 26.2 4 20 15 20
35 32.6 1 20 8 20
42 39.6 0 20 4 20
54 51.6 0 20 1 20
76.1 73.1 0 25 0 25
108 105 0 25 0 25
Calculated Advised Calculated Advised
Steel pipes thickness (mm) thickness (mm) thickness (mm) thickness (mm)
NOTE 1 - Thicknesses given are calculated specifically against the criteria noted in the table These thicknesses may not
satisfy other design requirements.
NOTE 2 - Some of the insulation thicknesses given are too large to be applied in practice but a selection is included
to highlight the difficulty in protecting small diameter pipes against freezing. To provide the appropriate degree of
frost protection to certain sizes of pipes, it may be necessary to provide additional heat to the system, for example by
circulating the water or heat tracing.
NOTE 3 - Assumed densities (ƿ) and heat capacities (cp) are as follows:
30
Table 30 (BS5422:2009)
Minimum insulation thickness to protect against freezing for domestic cold water systems [12 h]
15 13.6 41 45 48 50
22 20.2 9 20 10 20
28 26.2 4 20 4 20
35 32.6 1 20 1 20
42 39.6 0 20 0 20
54 51.6 0 20 0 20
76.1 73.1 0 25 0 25
108 105 0 25 0 25
Calculated Advised Calculated Advised
Steel pipes thickness (mm) thickness (mm) thickness (mm) thickness (mm)
21.3 16 27 30 30 30
26.9 21.6 9 20 10 20
33.7 27.2 4 20 4 20
42.4 35.9 1 20 1 20
48.3 41.8 0 20 0 20
60.3 53 0 20 0 20
76.1 68.8 0 25 0 25
88.9 80 0 25 0 25
NOTE 1 - Thicknesses given are calculated specifically against the criteria noted in the table These thicknesses may not
satisfy other design requirements.
NOTE 2 - Some of the insulation thicknesses given are too large to be applied in practice but a selection is included
to highlight the difficulty in protecting small diameter pipes against freezing. To provide the appropriate degree of
frost protection to certain sizes of pipes, it may be necessary to provide additional heat to the system, for example by
circulating the water or heat tracing.
NOTE 3 - Assumed densities (ƿ) and heat capacities (cp) are as follows:
31
Table 31 (BS5422:2009)
Minimum insulation thickness to protect against freezing for domestic cold water systems [8 h]
15 13.6 14 20 15 20
22 20.2 3 20 3 20
28 26.2 0 20 0 20
35 32.6 0 20 0 20
42 39.6 0 20 0 20
54 51.6 0 20 0 20
76.1 73.1 0 25 0 25
108 105 0 25 0 25
Calculated Advised Calculated Advised
Steel pipes thickness (mm) thickness (mm) thickness (mm) thickness (mm)
21.3 16 10 20 11 20
26.9 21.6 3 20 3 20
33.7 27.2 1 20 1 20
42.4 35.9 0 20 0 20
48.3 41.8 0 20 0 20
60.3 53 0 20 0 20
76.1 68.8 0 25 0 25
88.9 80 0 25 0 25
NOTE 1 - Thicknesses given are calculated specifically against the criteria noted in the table These thicknesses may not
satisfy other design requirements.
NOTE 2 - Some of the insulation thicknesses given are too large to be applied in practice but a selection is included
to highlight the difficulty in protecting small diameter pipes against freezing. To provide the appropriate degree of
frost protection to certain sizes of pipes, it may be necessary to provide additional heat to the system, for example by
circulating the water or heat tracing.
NOTE 3 - Assumed densities (ƿ) and heat capacities (cp) are as follows:
32
Ductwork
9. Braithwaite tank insulation – within buildings
Insulated with an initial layer of 40 mm thick ROCKWOOL HVAC/RWA45 Slabs secured by manufacturer approved
adhesive and insulation hangers, followed by a further layer of 40 mm thick ROCKWOOL Ductslab secured to the
first layer by adhesive and previously applied insulation hangers. Finish to insulation to be factory applied reinforced
aluminium foil, joints in surface covering to be secured with 75 mm wide aluminium foil self adhesive tape, to maintain a
vapour barrier. Particular attention to be given to the vapour barrier where the self adhesive insulation hangers protrude
through the mineral wool insulation and its factory applied finish (second layer). Further finish should be according to
location i.e. external as specification 7.2; plant rooms as specification 6.2.
Full guidance relating to ductwork fire requirements and the Fire Duct System are available from the ROCKWOOL
Technical Department. The ROCKWOOL publication ‘Fire Duct System’ is available on request.
Typical specification
Ductwork shall be in accordance with B&ES Specification DW/144. Ducts to be fire protected with the correct
thickness of high density single layer ROCKWOOL fire rated ductwork system. Insulation system shall be
independently tested and carry current valid certification to provide fire protection fully in accordance with
the requirements of duct ‘Type A’ and duct ‘Type B’ of BS476: 24. (The fire resistance of test specimens shall
be the duration, in minutes, of heating in accordance with 5.1.1 until failure occurs according to one or more
of the performance criteria, i.e. stability, insulation, integrity, or until the test is terminated, whichever is the
shortest time). And in accordance with BS9999 (The fire resistance of ductwork, when tested from either side,
should be not less than the fire resistance required for the elements of construction in the area through which it
passes. The supporting hangers should be capable of supporting the ductwork for not less than the period of
fire resistance of the ductwork).
33
Welded pin fixing method 1
1. All ductwork to be insulated with …..*mm ROCKWOOL Fire Duct slab, having a factory applied reinforced
aluminium foil to one face and complying with Building Regulations Class “0” requirements.
2. The Fire Duct Slab to be affixed to the duct using 2.5 mm diameter welded steel pins and 38 mm spring steel
washers in accordance with ROCKWOOL manual “Fire Duct System”.
3. The foil facing is to be removed from any surface to which FIREPRO® glue is to be applied.
4. All corner joints are to be fixed with pigtail screws at 250 mm maximum centres. Screw length is to be 2 x slab
thickness.
5. All cross joints are to be filled with FIREPRO® Glue and held tightly closed.
6. For duct sizes up to 1500 x 1500 mm, drop rods and bearers are to be at 1500 mm maximum centres and to be
M10 steel rod and 30 x 30 x 3 mm steel angle respectively. Ductwork is to be in accordance with B&ES Specification
DW144.
7. Drop rods and exposed bearers are to be insulated with ……mm Fire Duct Slab or Fire Duct Hanger Strip, as
appropriate. Rebates or cover pieces are to be used at duct flange and bearer locations according to site conditions
and subject to ROCKWOOL approval.
8. Where a vapour barrier is required, all exposed Fire Duct edges and penetrations through the foil should be sealed
using soft self-adhesive aluminium foil tape.
2. The Fire Duct Slab to be affixed to the duct using 2.5 mm diameter welded steel pins and 38 mm spring steel
washers in accordance with ROCKWOOL manual “Fire Duct System”.
3. All corner joints are to be fixed with pigtail screws at 250 mm maximum centres. Screw length is to be 2 x slab
thickness.
4. A
ll joints are to be filled with FIREPRO® Glue and held tightly closed. Nails to be used at corner joints for this
purpose.
5. For duct sizes up to 1500 x 1500 mm, drop rods and bearers are to be at 1500 mm maximum centres and to be
M10 steel rod and 30 x 30 x 3 mm steel angle respectively. Ductwork is to be in accordance with B&ES Specification
DW144.
6. Drop rods and exposed bearers are to be insulated with ……mm Fire Duct Slab or Fire Duct Hanger Strip, as
appropriate. Rebates or cover pieces are to be used at duct flange and bearer locations according to site conditions
and subject to ROCKWOOL approval.
7. Where a vapour barrier is required, all exposed Fire Duct edges and penetrations through the foil should be sealed
using soft self-adhesive aluminium foil tape.
34
Welded pin fixing method 3
1. All ductwork to be insulated with …..*mm ROCKWOOL Fire Duct slab, having a factory applied reinforced
aluminium foil to one face and complying with Building Regulations Class “0” requirements.
2. The Fire Duct Slab to be affixed to the duct using 2.5 mm diameter welded steel pins and 38 mm spring steel
washers in accordance with ROCKWOOL manual “Fire Duct System”.
3. All corner joints are to be fixed with pigtail screws at 250 mm maximum centres. Screw length is to be 2 x slab
thickness.
4. A
ll cross joints are to be covered with centrally positioned 100 mm wide strips of Fire Duct Slab of the same
thickness as the insulation. The cover strips are to be fixed along both edges using pigtail screws, as described
above.
5. F
or duct sizes up to 1500 x 1500 mm, drop rods and bearers are to be at 1500 mm maximum centres and to be
M10 steel rod and 30 x 30 x 3 mm steel angle respectively. Ductwork is to be in accordance with B&ES Specification
DW144.
6. Drop rods and exposed bearers are to be insulated with ……mm Fire Duct Slab or Fire Duct Hanger Strip, as
appropriate. Rebates or cover pieces are to be used at duct flange and bearer locations according to site conditions
and subject to ROCKWOOL approval.
7. Where a vapour barrier is required, all exposed Fire Duct edges and penetrations through the foil should be sealed
using soft self-adhesive aluminium foil tape.
Alternatively the ROCKWOOL Fire Duct system can be fixed using the mitre-joint fixing method-please see
ROCKWOOL Fire Duct System brochure for further information.
Fire resistance - Performance summary – Fire Duct Slab, Section and PSM
Joint Option A - Rebated protection Joint Option B - Protection using ‘T’ section Joint Option C - Protection using block cover strip
35
12. Acoustic treatment of ducts and pipes
Techwrap2
General - 25 mm ROCKWOOL Techwrap2 to be applied to ducts. The polymeric mass layer should be positioned
outermost from the sound source and overlapped at all joints. Techwrap2 should be cut 25 mm oversize and a 25 mm
strip of ROCKWOOL stone wool removed to create an overlap. All cutting operations can be completed using a sharp
knife. 75 mm wide plain aluminium foil self-adhesive tape should be used to seal the joints.
Fixings - Welded steel pins should be used to fix Techwrap2 to the duct. However, subject to the manufacturer’s
approval, adhesive applied insulation hangers may be used in place of welded pins. Particular attention should be paid
to support of the Techwrap2 at joint locations and where sagging may occur, eg in ‘soffit’ areas. The number of pins
required will depend upon size and orientation of the duct. However, where pins are employed at Techwrap2 edges,
4 number are recommended at 1000 mm edges and 7 number at 2000 mm edges. Additional ‘lines’ of pins should be
at nominal 300 mm spacings. Where a vapour barrier is required, support pins and hangers, which penetrate the foil,
should be sealed using aluminium tape.
For soil-vent and rainwater pipes, ductwork etc. where they pass within a building and a high level of acoustic insulation
is required use ROCKWOOL Techtube.
13. Construction type pipework and trunking penetrations - insulated fire sleeves
14. Firestop solution for large voids in walls and floors - ROCKWOOL Ablative Coated Batt
FIREPRO® Ablative Coated Batts are manufactured by spraying specially produced, high density ROCKWOOL insulation
with an additional fire protection ablative coating.
This is a fully automated process to ensure an even coating thickness.
ROCKWOOL Ablative Coated Batts are available in either 50mm or 60mm thicknesses.
36
Installation
FIREPRO® Ablative Coated Batts are manufactured by spraying specially produced, high density ROCKWOOL insulation
with an additional fire protection ablative coating.
This is a fully automated process to ensure an even thickness of coating.
To install, the Batts are simply cut and a bead of Acoustic Intumescent Sealant applied around the external edges.
They are then friction fitted between the services and the wall or floor edges to completely seal the void. Where butt
joints are required between cut sections of adjacent batts, Acoustic Intumescent Sealant and/or FIREPRO® Glue is
applied to both mating edges in order to form a fire tight bond between individual pieces of insulation. Contact the
Technical Solutions team on 01656 862621 for specific details on blank seals and dampers.
All joints, including those around the perimeter of the Batt, are then pointed with FIREPRO® Acoustic Intumescent
Sealant to complete the seal.
Plastic pipes (PVC, ABS and HDPE etc) must be sleeved with FIREPRO® Insulated Fire Sleeves at the point at which
they pass through the Ablative Coated Batt. Similarly, to achieve fire resistance insulation (I) with metal pipes such as
steel or copper, the pipes must be lagged with a 1m length of ROCKWOOL Fire Tube or Pipe Section (minimum 40mm
wall thickness) protruding equal distances from both faces of the Ablative Coated Batt. The joint between the Ablative
Coated Batt and the pipe insulation must be pointed with the FIREPRO® Sealant. Where the pipe has been thermally
lagged with a combustible insulation, this must be cut away and replaced with the ROCKWOOL insulation, as above.
Ensure the integrity of any vapour control layer is re-instated as necessary. The joint between the Batt and Fire Sleeve or
Fire Tube must be pointed with the FIREPRO® Sealant.
Fire performance
ROCKWOOL Ablative Coated Batt has been tested to the dedicated fire resistance standard for penetration seals -
prEN 1366-3. The independently prepared assessment, detailing the full scope of fire performance, is available from the
ROCKWOOL Technical Solutions Team. Ablative Coated
Batt fire resistance tests were conducted using ROCKWOOL Acoustic Intumescent Sealant Sealant and/or ROCKWOOL
FIREPRO® Glue.
Independant tests have proved the capability of a single 50mm Batt to provide up to 2 hours fire resistance integrity,
insulation ratings are dependent upon the service penetration. Where 4 hour integrity and insulation are required we
recommend the use of our 60mm Coated Batt.
Independent tests have proved the capability of a single 60 mm Batt to provide up to 4 hours fire resistance integrity
and up to 2 hours insulation when used with all of the services listed in the Ablative Coated Batt Datasheets and also
as a blank seal. Even for extreme requirements, where 4 hours integrity and insulation are required to maintain the
performance of a masonry wall, a solution can also be accomplished with a double Batt solution.
Acoustic data
60mm batt: Tested for head of wall: 50mm batt: Tested for head of wall:
Rw = up to 52db (2 x Coated Batts) Rw = up to 48db (2 x Coated Batts)
Rw = up to 38db (1 x Coated Batts) Rw = up to 37db (1 x Coated Batts)
The correct use of Coated Batt within concealed The correct use of Coated Batt within concealed
cavities and voids will reduce the level of cavities and voids will reduce the level of
transmitted sound: transmitted sound:
Rw = up to 52 db (2 x Coated Batts) – Rw = up to 52 db (2 x Coated Batts) –
incorporating 48mm O/D PVC /15mm copper pipe incorporating
penetrations. 48mm O/D PVC /15mm copper pipe penetrations.
Rw = up to 34 db (1x Coated Batts) – incorporating Rw = up to 34 db (1x Coated Batts) – incorporating
48mm O/D PVC /15mm copper pipe penetrations. 48mm O/D PVC /15mm copper pipe penetrations.
37
Sustainability Fire resistance
When it comes to our approach to sustainability,
it is, simply put, a matter of living our purpose
to address the challenges of modern living in a Acoustic comfort
sustainable manner.
Durability
Environment
Made from a renewable and plentiful naturally occurring resource, ROCKWOOL
insulation saves fuel costs and energy in use and relies on trapped air for its
thermal properties.
ROCKWOOL insulation does not contain (and has never contained) gases that
have ozone depletion potential (ODP) or global warming potential (GWP).
Interested?
For further information, contact the Technical Solutions Team on 01656 868490
or email [email protected]
Visit www.rockwool.co.uk to view our complete range of products and services.
38
Legal disclaimer
The ROCKWOOL Trademark
ROCKWOOL® - our trademark
The ROCKWOOL trademark was initially registered in Denmark
as a logo mark back in 1936. In 1937, it was accompanied with a
word mark registration; a registration which is now extended to
more than 60 countries around the world.
The ROCKWOOL trademark is one of the largest assets in the
ROCKWOOL Group, and thus well protected and defended by
us throughout the world.
If you require permission to use the ROCKWOOL logo for your
business, advertising or promotion. You must apply for a Trade
Mark Usage Agreement.
To apply, write to: [email protected].
Trademarks
The following are registered trademarks of the ROCKWOOL
Group: ROCKWOOL®, ROCKCLOSE®
RAINSCREEN DUO SLAB®, HARDROCK®, ROCKFLOOR®
FLEXI®, BEAMCLAD®, FIREPRO®
Disclaimer
ROCKWOOL Limited reserves the right to alter or amend the
specification of products without notice as our policy is one
of constant improvement. The information contained in this
brochure is believed to be correct at the date of publication.
Whilst ROCKWOOL will endeavour to keep its publications up
to date, readers will appreciate that between publications there
may be pertinent changes in the law, or other developments
affecting the accuracy of the information contained in this
brochure. The applications referred to within the brochure do
not necessarily represent an exhaustive list of applications.
ROCKWOOL Limited does not accept responsibility for the
consequences of using ROCKWOOL in applications different
from those described within this brochure. Expert advice should
be sought where such different applications are contemplated,
or where the extent of any listed application is in doubt.
© ROCKWOOL 2020. All rights reserved.
39
January 2021
ROCKWOOL Limited
Pencoed
Bridgend
CF35 6NY
Tel: 01656 862 621
[email protected] Revision No - v1.
rockwool.co.uk © ROCKWOOL 2021. All rights reserved.