STEEL PLATE (TK.

400
AS PER DETAIL)
PL 03 2/2 M16 BOLT
GRADE 8.8

50
30

100
55 65

50
6 50X200 C24 TIMBER M12 BOLT (GRADE
178X102X19 UB
8.8) @ 400 C/C
STAGGERED

305X102X33 UB

- TYPICAL BEAM 1/4 - BEAM 2/3 - TYPICAL FLITCH BEAM DETAILS


- -
Scale - 1:10 Scale - 1:10

RIDGE BEAM
(203X102X23UB)
MILD STEEL ANGLE IRON BRACKET.(75X75X6).
TO BE FIXED TO TIMBER JOIST USING
M8 G8.8 BOLTS AND TO BE FIXED TO
STEEL BEAM USING SELF DRILLING SCREWS

NOTE -EVERY OTHER


JOIST TO BE FIXED TO
MILD STEEL ANGLE IRON BRACKET.(100X100X8).TO
THE STEEL BEAM USING
BE FIXED TO TIMBER COLUMN USING M10 G8.8
THIS DETAIL Client
BOLTS AND TO BE FIXED TO STEEL BEAM USING
SELF DRILLING SCREWS)
SOUTH LONDON LOFTS

DETAIL 01- TYPICAL


Project 16D, ST. MARY'S ROAD, SE15 2DW
TIMBER JOIST STEEL
Job Title LOFT CONVERSION
BEAM CONNECTION

300
Drawing Title CONNECTION DETAILS

WEB STIFFENERS Date Drawing No.


2/2 M12 BOLT M12 BOLT GRADE
254 X 102 X 28 UB (BEAM 6) MAY 2022 INT-SLL-2022-41-DWG-04
GRADE 8.8 8.8 AT 300mm C/C
Rev. no. Date Issue

00 27.05.2022 FOR CONSTRUCTION


8mm STIFFENER PLATE
WELDED ON BOTH 01 22.10.2022 FOR CONSTRUCTION
SIDES BY 6mm FILLET MILD STEEL ANGLE IRON BRACKET.(100X100X8).
6 6 TO BE FIXED TO TIMBER COLUMN USING 02 07.02.2023 FOR CONSTRUCTION
WELDS
M10 G8.8 BOLTS AND TO BE FIXED TO
STEEL BEAM USING SELF DRILLING SCREWS) 03 03.03.2023 FOR CONSTRUCTION

203X102X23 UB (BEAM 5) Suitability FOR CONSTRUCTION


(BEAM 6 IS SUPPORTED ON BEAM 5)
Ref Archt. Dwg. 2022/200/32
8mm STIFFENER
PLATE WELDED ON INTELLECT CIVIL & CONSTRUCTION LTD.
BOTH SIDES 178X102X19UB (BEAM 3)
Scale 1:50
STEEL BEAM EDGE 305X102X33 UB(BEAM 4)
TYPICAL TIMBER 1:50

STRENGTHENING BEAM 4 & BEAM 6 CONNECTION COLUMN TIMBER 1m 0 1m 2m

- 1:75 Scale 1:75


DETAIL -
Scale - 1:10 BEAM CONNECTION
1.5m 0 1.5m 3m
Scale - 1:10
STRUCTURAL MEMBERS
Timber Beams
T4-T6 2No. 50 X 150 C24
T7-T10 2No. 50 X 200 C24
T11-T13 2No. 50 X 175 C24
T14-T18 2No. 50 X 200 C24
T19-T20 2No. 50 X 150 C24
T10 T22-T25 2No. 50 X 200 C24
T26-T27 2No. 50 X 150 C24
T28-T29 2No. 50 X 200 C24
T1,3 ARE FLITCH BEAMS OF SIZE
2/50X200 C24 + 10X200 S275
T14 T2,21 ARE FLITCH BEAMS OF SIZE
2/50X200 C24 + 6X200 S275
T25 to be supported by timber struts in
400 c/c (load bearing strut wall)
T28 T29
All timbers C24 grade (unless stated)
Minimum bearing of all Timber beams to
be 50mm, unless stated otherwise
Steel Beams
T27 BEAM 1,4 : 305 X 102 X 33 UB
BEAM 2,3 : 178 X 102 X 19 UB
T15 BEAM 5 : 203 X 102 X 23 UB
BEAM 6** : 254 X 102 X 28 UB
**Beam 6 is placed in a separate
C3 elevation to hang Beam 4
BELOW RIDGE BEAM : 203 X 102 X 23 UB
T26 Steel Columns
T17 C1, C3 : 3X 100 X 50 C24 Timber Col.
T16 C2 : 100 X 100 C24 Timber Col.
C1 C3 Bearer Plates
BELOW BELOW
800 X 100 X 75 MS Plate
T19 T20
RIDGE BEAM 1200 X 100 X 100 MS Plate
T18
C2 BELOW Client
(HANGING COL.)
SOUTH LONDON LOFTS
T21

Project 16D, ST. MARY'S ROAD, SE15 2DW

Job Title LOFT CONVERSION


T23 T24
Drawing Title PROPOSED ROOF FRAMING PLAN

Date Drawing No.


MAY 2022 INT-SLL-2022-41-DWG-03
Rev. no. Date Issue
T22 00 27.05.2022 FOR CONSTRUCTION

01 22.10.2022 FOR CONSTRUCTION

02 03.03.2023 FOR CONSTRUCTION


C2
BELOW
LEGEND Suitability FOR CONSTRUCTION
T25
C2 TIMBER BEAM Ref Archt. Dwg. 2022/200/32
BELOW
STEEL BEAM
INTELLECT CIVIL & CONSTRUCTION LTD.
LOAD BEARING WALL
- PROPOSED ROOF FRAMING PLAN EXTENSION/NEW WALL 1:50
Scale 1:50
-
Scale - 1:50
M.S. BEARER PLATE 1m 0 1m 2m
ALL ROOF JOISTS (FLAT & SLOPING) SHALL BE 50X200
1:75 Scale 1:75
C24 @ 300 C/C, UNLESS NOTED OTHERWISE.
1.5m 0 1.5m 3m
WEB STIFFENERS STRUCTURAL MEMBERS
2/2 M12 BOLT
254 X 102 X 28 UB (BEAM 6) GRADE 8.8
Timber Beams
T4-T6 2No. 50 X 150 C24
T7-T10 2No. 50 X 200 C24
T11-T13 2No. 50 X 175 C24
6 6 T14-T18 2No. 50 X 200 C24
T19-T20 2No. 50 X 150 C24
T9 T10 T22-T25 2No. 50 X 200 C24
203X102X23 UB (BEAM 5) T26-T27 2No. 50 X 150 C24
BEAM 5 (BEAM 6 IS SUPPORTED ON BEAM 5) T28-T29 2No. 50 X 200 C24
T1,3 ARE FLITCH BEAMS OF SIZE

BEAM 6
REFER 2/50X200 C24 + 10X200 S275
DETAIL 01 BEAM 4 178X102X19UB (BEAM 3) T2,21 ARE FLITCH BEAMS OF SIZE
2/50X200 C24 + 6X200 S275
T25 to be supported by timber struts in
305X102X33 UB(BEAM 4) 400 c/c (load bearing strut wall)
All timbers C24 grade (unless stated)

50X200 C24 FLOOR


- BEAM 4 & BEAM 6 CONNECTION Minimum bearing of all Timber beams to

BEAM 2
be 50mm, unless stated otherwise
-
JOISTS @ 400 C/C Scale - 1:10 Steel Beams
BEAM 1,4 : 305 X 102 X 33 UB
T1 T2 BEAM 2,3 : 178 X 102 X 19 UB
BEAM 5 : 203 X 102 X 23 UB
BEAM 6** : 254 X 102 X 28 UB
**Beam 6 is placed in a separate

BEAM 3
C3 elevation to hang Beam 4
ABOVE RIDGE BEAM : 203 X 102 X 23 UB
Steel Columns
T12
C1, C3 : 3X 100 X 50 C24 Timber Col.
C2 : 100 X 100 C24 Timber Col.
C1 C3
Bearer Plates
50X200 C24 ABOVE ABOVE
FLOOR JOISTS T4 800 X 100 X 75 MS Plate
@ 400 C/C T5 1200 X 100 X 100 MS Plate
T6
Client
BEAM 1
C2 ABOVE SOUTH LONDON LOFTS
REFER (HANGING COL.)
DETAIL 01
Project 16D, ST. MARY'S ROAD, SE15 2DW

Job Title LOFT CONVERSION


50X200 C24 FLOOR
JOISTS @ 400 C/C Drawing Title PROPOSED LOFT FRAMING PLAN

Date Drawing No.


T3
MAY 2022 INT-SLL-2022-41-DWG-02
Rev. no. Date Issue

01 22.10.2022 FOR CONSTRUCTION

02 23.01.2023 FOR CONSTRUCTION

03 07.02.2023 FOR CONSTRUCTION


C2 C2
04 11.02.2023 FOR CONSTRUCTION
ABOVE ABOVE
05 03.03.2023 FOR CONSTRUCTION
LEGEND
T7 T8 Suitability FOR CONSTRUCTION
TIMBER BEAM Ref Archt. Dwg. 2022/200/32

- PROPOSED LOFT FRAMING PLAN STEEL BEAM


INTELLECT CIVIL & CONSTRUCTION LTD.
- LOAD BEARING WALL
Scale - 1:50
Scale 1:50
EXTENSION/NEW WALL 1:50

ALL FLOOR JOISTS SHALL BE 2 Nos. 50X175 M.S. BEARER PLATE


1m 0 1m 2m
C24 @ 400 C/C, UNLESS NOTED OTHERWISE.
1:75 Scale 1:75

1.5m 0 1.5m 3m
STEELWORK STRUCTURAL NOTES: GENERAL NOTES AND HEALTH AND SAFETY : TEMPORARY WORKS & STABILITY
1. All workmanship is to comply with BS EN 1993-1-1 and 1. New Timber Floor
· The lengths and spans used in these calculations · The contractor is entirely responsible for maintaining
BS EN 1090-2 and the latest edition of the National a) Structural timbers to be a minimum of 40mm clear
of chimney breasts. Floor joists to be 25mm (min) are for design purposes only and should not be used the stability and structural integrity of all existing and
Structural Steelwork Specification (NSSS) for building
clear of existing ceiling joists. as a basis for ordering materials/fabrication proposed structures, within and adjacent to, the
construction, and all clauses, including appendices are
b) Structural timbers to be a minimum stress grade of purposes. Note, the design span in these works from the date for possession/commencement
deemed to be part of this specification.
C24 calculations is not the same as clear span. of the site until practical completion of the works.
2. All structural steel sections are to be of specified grade c) Trimmers: double/treble floor joists where there is a
complying to applicable code from the following list; BS · All lengths and spans used in these calculations · The contractor shall produce a full method
stud partition wall. Multiple joists to be bolted should be verified on site prior to commencement of statement and temporary works proposals prior to
4-1:2005, BS EN 10210-2:2006, BS EN 10025-2:2004. together with M12 bolts with large washers at
any construction works. Contractor and/or steel commencement of any works on site.
3. All bolts are to be grade 8.8 black bolts to BS 4190 600mm centres staggered
fabricator to take their dimensions on site.
unless noted otherwise on the structural drawings. d) Provide 1200mm long G.M.S straps @800 c/c · Design , installation and removal of the temporary
screwed into masonry wall and notched and · Builder/contractor is to check that the Structural works to be carried out by the contractor as per the
4. Site welding shall not be permitted.
screwed into joists at floor level. Engineers proposal (i.e. location of steel contractors temporary works procudure , ususally
5. Setting out dimensions are to be obtained from the e) Herringbone or solid strutting at 1800c/c beams/trimmers etc) is feasible and necessary based on BS5975
Architect's drawings. The steelwork fabricator shall alternatively to be secured to joists. before ordering materials. Open up top of walls etc
obtain all necessary dimensions from site. to determine existing spans & necessity of
6. The contractor is to carry out a full site survey to 2. Floor Beam
steels/beams.
a) Steel beam bearing plates or padstones to be
establish the lengths of all steel members connecting to
bedded on sand and cement centrally located · All specified structural elements (i.e. steel beams,
existing structure prior to preparation of fabrication
under steel beam and flush with inner face of steel column, timber beams/trimmers, etc) to be
drawings.
brickwork. Pocket in party/flank wall to be made installed in single continuous length unless stated
7. No splices are permitted in any elements. good with concrete or masonry. otherwise.
8. All welding is to comply with BS EN 1011 parts 1 & 2. All b) Internal partitions assumed to be load bearing in
structural design are to be verified on site by the · All load bearing walls, foundations and structural
welds are to be 6mm fillet welds or full-strength butt
contractor for their capacity to bear the extra loads elements are to be exposed and checked on site
welds unless noted otherwise on the drawings.
proposed - prior to construction. with the building control officer, prior to the
9. Where endplates, capping plates, baseplates, etc. are c) Existing foundations should be checked to commencement of works for suitability.
shown at the end of a steel element, these are to be determine if adequate to bear any proposed
welded to the steel element with a 6mm fillet weld. That · Any deviation from the design assumptions is to be
additonal loads.
weld is to extend around the entire contract perimeter reported to the Architect/ Engineer prior to
between the plate and steel element. commencement of works.
3. Carpentry Specification
10. Minimum connection between steel elements to be 4no. a) All timber materials and workmanship to be in · The existing building is assumed to be in good
M16 bolts with 15mm thick end plate unless noted accordance with BS 5268: Part 2 Structural Use of structural order and any defects are to be reported
otherwise. Timber to the Architect/Engineer.
b) All concealed timbers to be treated with pre-injected
11. Where any different steel materials or steel materials wood preservatives, plus all cut ends to be painted · The temporary stability of the structure during all
with different finishes (e.g. Painted steel, Galvanized c) All timber to be treated by vacuum pressure stages of the construction work is the responsibility
steel, Stainless steel, etc.) in contact or are connected impregnation of organic or water born preservative of the contractor.
together, all contact surfaces between them are to be to a dry salt retention in accordance with the
isolated to prevent contact and corrosion.
· The contractor is responsible for all of the temporary
manufacturers recommendations.
works for the project, for the full duration of the
12. The contractor is to design and detail all connections d) No notches, holes or rebates to be cut in any Client
project. Contractors shall provide proper
(including those between steel and other materials), not member without the written agreement of the
structural engineer. conventional needles and props, ensuring that loads SOUTH LONDON LOFTS
already detailed on the Structural Engineer's drawings, in
e) Double joists and rafters to be bolted together are adequately transferred to the ground.
accordance with the appropriate, current Eurocode,
British Standards (if still applicable) or other applicable @600mm centres with 12mm diametre bolts and · The dimensions used in the calculations are not cut
standard and building regulation where such exists. 50x50x3mm washer plates. lengths of steel. the contractor is responsible for
f) All fixings in roof space (nails/screws/bolts and taking site dimensions and applying appropriate Project 16D, ST. MARY'S ROAD, SE15 2DW
13. Detailing of steelwork (if requested by the client) hangers) are to be galvanized unless noted bearing lengths, which will be a 100mm minimum,
-All steelwork elements shall be detailed by the otherwise.
or as indicated on the drawings.
contractor. Job Title LOFT CONVERSION
· Due to the weight of the steel members (up to
-The contractor is to prepare a full 3D model of all Note: 110kg), the contractor shall make provision for lifting
steelwork in the building on a specialist detailing
Drawing Title GENERAL NOTES
1. Existing rafters to be strengthened - 50x150 C24 off transport and moving them to the location for
package to ensure that all elements, junctions, timbers to be fixed using timberlock screws or nails erection. Appropriate lifting equipment shall be Date Drawing No.
dimensions, etc. fit together correctly and do not project or M8 bolts onto existing rafters (@ 400c/c.) to provided, e.g. hoist's, crane's, genie lifts etc. MAY 2022 INT-SLL-2022-41-DWG-01
outside of the structural zones. provide 50mm air gap Sufficient man-power shall be available to ensure
2. double floor joists under partitions and chimney Rev. no. Date Issue
-A full set of fabrication drawings shall be provided by that the steelwork can safely be erected. All the
trimming
the contractor for comment by the Architect/Structural lifting activities to be carried out as per the lifting 00 27.05.2022 FOR CONSTRUCTION
3. all walls used to support proposed loads to be
Engineer. operations and lifting equipment regulations 1998
checked on site for their adequacy and agreed with 01 22.10.2022 FOR CONSTRUCTION
-The contractor must allow time and costs for at least the building inspector prior to the commencement of (loler)
three submissions/resubmissions of fabrication works
drawings followed by comments from the design team
within their programme.
-The contractor's programme must allow at least 10 Suitability FOR CONSTRUCTION
working days between the Engineer's receipt of a full
set of fabrication drawings and the Engineer returning Ref Archt. Dwg. 2022/200/32
comments. This time period applies to each
submission/re-submission of fabrication drawings.
INTELLECT CIVIL & CONSTRUCTION LTD.
14. All bolt pockets, spaces below base plates, etc. at
column bases and beam bearings to be completely filled Scale 1:50
with Fosroc Conbextra grout. 1:50

1m 0 1m 2m

1:75 Scale 1:75

1.5m 0 1.5m 3m