Double Earth Fault - Part 2
Double Earth Fault - Part 2
Double Earth Fault - Part 2
References
MV CB
Electrical distribution plant
Homopolar toroid
MV-LV
E2N 1600 4p
PR123/P LSIG
MCCB MCCB
LSIG LSIG
M
MCCB MCCB
LSIG LSIG
L L
A4
X K9 K10 K8 K6 K4 K10 K8 K6 K4
XV K9 K10 K8 K6 K4 K10 K8 K6 K4
K10
K10
K9
K8
K6
K4
K8
K6
K4
XK6 9 XK6 7 XK6 5 XK6 3 XK6 1 XK6 9 XK6 7 XK6 5 XK6 5 XK6 1
module PR120/K
module PR120/K
Signalling
Signalling
A1 K51 K51 K51 K51 K51 K51 K51 K51 K51 K51
K51 K51
IN1 p1 p2 p3 p4 IN1 p1 p2 p3 p4
PR123/P PR123/P
XK6 10 XK6 8 XK6 6 XK6 4 XK6 2 XK6 10 XK6 8 XK6 6 XK6 4 XK6 2
K7
K5
K3
K9
K7
K5
K3
XV K7 K5 K3 K9 K7 K5 K3
X K7 K5 K3 K9 K7 K5 K3
A4
Figure 7 – PR120/K (4 Outputs + 1 Input with common terminal) Figure 8 – PR120/K (4 Outputs with independent terminals)
W3
W4
W3
W4
K1
K2
K1
K2
XV K1 K2 W3 W4 XV K1 K2 W3 W4
X K1 K2 W3 W4 X13 K1 K2 W3 W4
+ +
– 24 V – 24 V
A4 A4 A13
11 13 15 17 19 21 23 25 1 2 7 8 11 13 15 17 19 21 23 25 1 2 7 8
K51 K51 K51 K51 K51 K51 K51 K51 K51 K51 K51 K51 K51 K51 K51 K51
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
12 14 14 18 20 22 24 26 10 PR021/K 12 14 14 18 20 22 24 26 10 PR021/K
PR123/P
k51
PR333/P
PR330/D-M module only
module or PR333/P with
For PR123/P with PR120/D-M
XV W1 X2 XV K2 K1 W3 W4
X W1 X2 X K2 K1 W3 W4
W2
(A) (B)
W1 +
– 24 V
W2
12 10 7 6 14 16 13 20 1 2 23 24
(A) (B)
D01 D02 D03 D04 D05 D06 D07 D07
A31
11 9 8 5 13 15 17 19 3 LD030 DO
Figure 10 – LD030 DO
PR120/K – PR021/K contact Monostable STDP −− and finally, to make the interlocking cabling between the
Maximum switching power (resistive load) 100W / 1250 VA signalling unit and the shunt opening release of the medium
Maximum switching voltage 130 V DC / 250 V AC voltage circuit-breaker. For example, when the K51/P1
Maximum switching current 5A
contact (PR120K) closes, the medium voltage shunt open-
Breaking capacity (resistive load) @ 30V DC 3.3 A
ing release receive the signal and command the opening of
@ 250V AC 5 A
Contact/coil insulation 2000V r.m.s. (1min@50Hz) the MV circuit-breaker (Figure 11).
It follows that:
XK6 7 − − the MV CB opens, since it is activated by the contact;
−− the LV CB opens. As already described above, the trip unit
X21/d10
-AR
is enabled to open the LV circuit-breaker because of Gext
K51
p1 (803) X21/d12 protection. In the most common plants, the LV circuit-
breaker must to open when the MV circuit breaker trips
XK6 8 due to the Gext protection.
K9
K9
K9
-XX 11
Caption -TR1 ˜ +
-XB11 2 K10
AR: REF 542 protection unit Transformer K10
BB1, BB3: auxiliary contacts -MO1 secondary winding
˜
K10
TR1: AC/DC converters L1
MO1: opening coil
-XB 8 Emax XK6 7
K51/p1: contact of PR120/K module internal CTs
Figure 11
Transformer K10
secondary winding K9
K10
L1 K9
Emax
internal CTs XK6 7
Figure 13 – Unrestricted fault
L2
Unrestricted fault is detected by both the homopolar toroid
and by the internal G, but, because of the settings, internal
K51
p1 G protection is faster than external G protection (Gext). The
L3 contact remains open because the protection “Gext” goes
into protection timing but the fault is extinguished before the
N
External protection timing phase ends.
toroid
PE XK6 8
It follows that:
K9
K10
Transformer K10
secondary winding
K10
L1
XK6 7
ACB internal MCCB internal
current sensors current sensors
L2
K51
p1
L3
N
External
toroid XK6 8
PE
K9
K9
K9