MAA-TGAC-ANC-CALC-00015 Rev.0

Download as pdf or txt
Download as pdf or txt
You are on page 1of 44

The Client: The Consultant: The Main Contractor:

Project Title: MARSA AL ARAB ANCILLARY

TS Ref. No. MAA-TGAC-ANC-CALC-00015


Calculation Submittal Rev. No. 0

Subm. Date: 7-Feb-2023


Subcontractor: TECHNICAL GLASS

Discipline: Structural Architectural MEP Others

Name of Subcontractor: TECHNICAL GLASS & ALUMINIUM


Design Calculation Report For GFRC Panel & Secondary Steel
Subject of Submittal: Supports Fixing (GRC Entrance Frame & Soffit Ceiling Panel -
AN-01, 02 & 03)
Location of Application:

Enclosure:
Pre-Qualification of Subcontractor Calculation Project Quality Plan/Procedures Certificate Material Subm.
Test Results Sketch Project Safety Plan Guarantee Others

Originator's: M/s Extra Co. Date: 7-Feb-2023

Consultant's Comments:

A - Approved

B - Approved As Noted

and Resubmit as Required

C - Not Approved

Consultant's Signature: Date:

WITH RESPECT TO AVAILABLE INFORMATION WITH K & A TILL DATE:


Corrections or comments made relative to submittals during this review do not relieve the contractor from compliance with the contract
requirements and specifications. This check is only for review of general conformance with the design concept of the project and general
compliance with the information given in the contract documents.
DESIGN CALCULATION REPORT FOR GFRC PANEL AND
SECONDARY STEEL SUPPORTS FIXINGS

[GRC ENTRANCE FRAME & SOFFIT CEILING PANEL-AN-01,02 & 03]

Client: MARSA AL ARAB RESIDENCE LLC

Main Contractor: ASGC GROUP

Sub-Contractor: EXTRA CO INDUSTRIES L.L.C

Design Lead Consultant: KILLA ARCHITECTURAL DESIGN

Project: MARSA AL ARAB QUAY WALL VILLAS

DUBAI, U.A.E

EXTRA CO PRECAST BUSINESS UNIT, RAK – UAE

EXT-W656-TS-CAL-02

REV 00

06/02/2023

Page 1 of 43
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

TABLE OF CONTENTS

S.NO CONTENTS PAGE NO


Introduction
1 3
Design Criteria & Reference
2 3
Material Properties
3 4
Loads
4 5
Load Combination
5 5

6 Limits of Deformation 7

Appendix-I Design and Analysis of GRC Panel 8

Appendix-2 Design and Analysis of Steel Bracket 15

Appendix-3 Wind Load Calculation 37

Appendix-4 Drawings 40

Page 2 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

ASSUMPTIONS AND DATA:

1. INTRODUCTION:
The calculation will verify the adequacy of GFRC FRAME CLADDING [GRC CANOPY] (For Conservative
design we considered worst case scenario for all panel and its supporting steel brackets in withstanding
the applied design loads as per project specification & design standards.

2. DESIGN:
Generally, all the design has been carried out in accordance with relevant Standards with a particular
reference to the following codes of practice.
- PCI MNL 128 Recommended Practice for Glass Fibre Reinforced Concrete Panels – for Load
Factors, Load Combinations& Deflection.
- CEM-FIL GRC Technical Data.
- "Practical Design Guide" for GRC Prepared by International GRCA Technical Committee.
- Specification for Structural Steel Buildings (ANSI/AISC 360-10) - 2010.
- BS 5950 as per Design Specifications – for the design of Steel Sections and Fixings.
- BS 6399, BS 6180 and BS EN 1991: Part 1-1 for Live Load as per Specifications.
- ASCE 7 -05 Minimum Design Loads for Buildings and other structures.
- IBC 2009 International building code for calculating Seismic Force for Cladding Components.
- Design of Stainless-Steel connection based on "SCI 291 Structural Design of Stainless Steel".

3. MATERIAL PROPERTIES:

3.1 PROPERTIES OF GRC PANEL:

Fiber Content = 5% (PCI Manual-128, Table 4-GFRC Properties)

Density = 21 kN/m3 (PCI Manual-128, Table 4-GFRC Properties)

Compressive Strength = 50 N/mm2 (PCI Manual-128, Table 4-GFRC Properties)

Tensile strength (UTS) = 8 N/mm2 (PCI Manual-128, Table 4-GFRC Properties)

Bending Strength (MOR) = 21 N/mm2 (PCI Manual-128, Table 4-GFRC Properties)

LOP = 7 N/mm2 (PCI Manual-128, Table 4-GFRC Properties)

Young’s Modulus = 18000 N/mm2 (PCI Manual-128, Table 4-GFRC Properties)


Page 3 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

Poisson’s ratio = 0.24 (PCI Manual-128, Table 4-GFRC Properties)

Interlaminar Shear Strength = 3 N/mm2 (PCI Manual-128, Table 4-GFRC Properties)

In plane Shear Strength = 8 N/mm2 (PCI Manual-128, Table 4-GFRC Properties)

3.2 PROPERTIES OF STEEL:

Modulus of elasticity ES = 210000 MPa

Poisson ratio μS = 0.3

Yield strength = 275 MPa

Unit weight ɤS = 78.6 kN/m3

- Steel Sections and Brackets – All connection plates and built-up sections to be used are
Min of S275JR grade (GI) PẎ=275Mpa and Fu=450Mpa.
- All bolts used as panel rod are Grade SS316-(A4-70) bolts having minimum grade of Fyb = 450Mpa and
Fub =700Mpa

Page 4 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

4.LOADS
4.LOADS
a) DEAD LOAD:
- Weight of Glass Fibre Reinforced Concrete (GRC)

- Unit Weight of GRC – 21kN/m3

- The weight of the GRC panel will be calculated by STAAD Pro by the use of Self weight

command.

b) WIND LOAD:

The design wind pressure is calculated according to ASCE 7-16[C/C-Canopy Structures & Wall Cladding]

Design wind pressure,


POSITIVE/DOWNWARD NEGATIVE/UPWARD
S.NO GRP AREA
PRESSURE LOAD PRESSURE LOAD

1 Vertical Wall GRC Cladding 1.2 kN/m2 1.68 kN/m2

2 Horizontal Roof Canopy GRC Cladding 1.12 kN/m2 1.74 kN/m2

-Refer to Appendix-3 for detailed wind load calculation with reference sheets.

5. LOADS AND LOAD COMBINATIONS (GFRC PANEL AS PER PCI MNL 128):

Basic Load Cases:

1. DEAD LOAD (DL)

2. PRESSURE WIND LOAD (WL1)

3. SUCTION WIND LOAD (WL2)

Page 5 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

Service Load Combinations:

4. 1.0DL + 1.0WL1

5. 1.0DL + 1.0WL2

Ultimate Load Combinations: (as per PCI MNL 128)

6. 1.4 DL - from Equation (5-2) 0.75[1.4D+1.7W]

7. 1.05 DL + 1.275 WL1

8. 1.05 DL + 1.275 WL2

9. 0.9 DL + 1.3 WL1 - from Equation (5-3) 0.9D+ 1.3W

10. 0.9 DL + 1.3 WL2

-Note that we used load factors and combinations according to PCI MNL 128 "Recommended Practice
for Glass Fiber Reinforced Concrete Panels", as per Section 034900-GFRC of the Global Project
Specifications.

STEEL BRACKET (AS PER ASCE 7-05):

Basic Load Cases:

1. DEAD LOAD (DL)

2. PRESSURE WIND LOAD (WL1)

3. SUCTION WIND LOAD (WL2)

Service Load Combinations:

4. 1.0DL + 1.0WL1

5. 1.0DL + 1.0WL2

Page 6 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

Ultimate Load Combinations:

6. 1.4 DL

7. 1.2 DL + 1.6 WL1

8. 1.2 DL + 1.6 WL2

6. DEFLECTION LIMIT:
FOR GRC PANEL:
According to PCI MNL 128 (5.5) deflection due to service loads are limited to L/240.

FOR STEEL BRACKET: [IBC 2012 TABLE 1604.3]


According to IBC 2012 (Table 1604.3), deflection due to service loads for GRC Brittle Finish (for
simply supported structures) are limited to L/240.
According to IBC 2012 (Table 1604.3), deflection due to service loads for GRC Brittle Finish (for
cantilever structures) are limited to 2L/240.

Page 7 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

APPENDIX -1

DESIGN AND ANALYSIS OF GRC PANEL

[FRAME & CANOPY PANEL]

Page 8 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

GRP PANEL DETAILS:

3D Isometric View of GFRC Panels

Page 9 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

12mm GRC Skin thickness has been assigned in the highlighted modelled plates
ASSIGNMENT OF LOADS:

Dead Load (DL)


Page 10 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

Pressure Wind Load (WL1)

Suction Wind Load (WL2)


Page 11 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

LIMITING STRESS (STRENGTH) DETERMINATION:


fu = Ø s f'u - PCI MNL 128 Equation (5-8)
where,
fu = Limiting Flexural Stress
Ø = 0.75, strength reduction factor
s = 1.0, shape factor for single skin
f'u = Assumed aged ultimate flexural strength for design
f'max= 1200psi = 8.27 Mpa - PCI MNL 128 Equation (5-9)

fu = Ø s f'u = 0.75 x 1.0 x 8.27 Mpa = 6.20 Mpa

Allowable Shear In-Plane = 725 psi = 5 Mpa

Allowable Shear Interlaminar = 400 psi = 2.75 Mpa

Note: As per GRC Laboratory Tests of Extra Co allowable Flexural Yield Strength Varies from 7Mpa to
11Mpa [Test Result Attached]. For Conservative design we are checking the panel for minimum flexural
strength of 6.2 Mpa.

Page 12 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

CHECK STRESSES @ ULTIMATE COMBINATIONS:

MODELLED PLATES (12mm GRC Skin Thickness)

a) Comparing Max Von Mis Stress to Limiting Stress fu

Max allowable Limiting Stress fu = 6.2 MPa

Maximum Von Mis Stress @ Ultimate = 2.34 N/mm2 (as per attached contour for load case 7
(1.2 DL + 1.6 WL1).

fu = 6.2 MPa > 2.34 MPa (OK)

- The 12mm thickness of GRC is safe and adequate!

Page 13 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

CHECK FOR DEFLECTION:

Allowable deflection = L/240 (As per PCI -5.5)


= 2900 mm / 240
= 12.1 mm
Maximum Absolute deflection (Service Load Combination) = 1.14 < 12.1 mm Hence Safe.

Page 14 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

APPENDIX -2

SECONDARY STEEL DESIGN

Page 15 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
Job No Sheet No Rev
1
Part
Software licensed to
Job Title Ref

By Date06-Feb-23 Chd

Client File STEEL BRACKET.std Date/Time 06-Feb-2023 16:37

Job Information
Engineer Checked Approved

Name:
Date: 06-Feb-23

Project ID
Project Name

Structure Type SPACE FRAME

Number of Nodes 16 Highest Node 21


Number of Elements 12 Highest Beam 14

Number of Basic Load Cases 3


Number of Combination Load Cases 5

Included in this printout are data for:


All The Whole Structure

Included in this printout are results for load cases:


Type L/C Name

Combination 6 1.4 DL
Combination 7 1.2 DL + 1.6 WL1
Combination 8 1.2 DL + 1.6 WL2

Section Properties
Prop Section Area Iyy Izz J Material
(cm2) (cm4) (cm4) (cm4)
1 CH100X50X10 13.000 32.300 208.000 2.428 STEEL
2 C75X40X5 8.818 12.200 75.300 1.198 STEEL

Primary Load Cases


Number Name Type

1 DEAD LOAD (DL) Dead


2 PRESSURE WIND LOAD (WL1) Wind
3 SUCTION WIND LOAD (WL2) Wind

Print Time/Date: 06/02/2023 16:42 STAAD.Pro V8i (SELECTseries 6) 20.07.11.45 Print Run 1 of 7

Page 16 of 43
Job No Sheet No Rev
2
Part
Software licensed to
Job Title Ref

By Date06-Feb-23 Chd

Client File STEEL BRACKET.std Date/Time 06-Feb-2023 16:37

Combination Load Cases


Comb. Combination L/C Name Primary Primary L/C Name Factor

4 1.0 DL + 1.0 WL1 1 DEAD LOAD (DL) 1.00


2 PRESSURE WIND LOAD (WL1) 1.00
5 1.0 DL + 1.0 WL2 1 DEAD LOAD (DL) 1.00
3 SUCTION WIND LOAD (WL2) 1.00
6 1.4 DL 1 DEAD LOAD (DL) 1.40
7 1.2 DL + 1.6 WL1 1 DEAD LOAD (DL) 1.20
2 PRESSURE WIND LOAD (WL1) 1.60
8 1.2 DL + 1.6 WL2 1 DEAD LOAD (DL) 1.20
3 SUCTION WIND LOAD (WL2) 1.60

Entity Color Legend


0.360m
CH100X50X10
C75X40X5
Default Plate Color
Default Solid Color

0.300m

Y
X
Z Load 3

WHOLE STRUCTURE WITH DIMENSION

Print Time/Date: 06/02/2023 16:42 STAAD.Pro V8i (SELECTseries 6) 20.07.11.45 Print Run 2 of 7

Page 17 of 43
Job No Sheet No Rev
3
Part
Software licensed to
Job Title Ref

By Date06-Feb-23 Chd

Client File STEEL BRACKET.std Date/Time 06-Feb-2023 16:37

CH100X50X10
0.360m
CH100X50X10
CH100X50X10

CH100X50X10
CH100X50X10
CH100X50X10

C75X40X5
C75X40X5
0.300m
C75X40X5

Y
X
Z C75X40X5 Load 3
C75X40X5
C75X40X5

SECTION PROPERTY

-0.208 kN

0.019-0.208
kN kN
0.019 kN

-0.208 kN

0.019-0.208
kN kN
0.019 kN

-0.674 kN
-0.674 kN

-0.019 kN
-0.674 kN
-0.019 kN
-0.674 kN

Y
X
Z Load 1
-0.019 kN
-0.019 kN

DEAD LOAD(DL)

Print Time/Date: 06/02/2023 16:42 STAAD.Pro V8i (SELECTseries 6) 20.07.11.45 Print Run 3 of 7

Page 18 of 43
Job No Sheet No Rev
4
Part
Software licensed to
Job Title Ref

By Date06-Feb-23 Chd

Client File STEEL BRACKET.std Date/Time 06-Feb-2023 16:37

-0.482 kN

-0.394 kN

-0.181 kN
0.331 kN
-0.230 kN
0.893 kN
-0.482 kN

-0.394 kN

-0.181 kN
0.331 kN
-0.230 kN
0.893 kN

-0.131 kN
0.409 kN
0.131 kN kN
-0.275
0.905 kN

Y
X -0.131 kN
Z Load 2
0.409 kN
0.131 kN kN
-0.275
0.905 kN

PRESSURE WIND LOAD (WL1)

-0.331 kN
0.181 kN -0.893 kN
0.230 kN

0.482 kN
0.394 kN

-0.331 kN
0.181 kN -0.893 kN
0.230 kN

0.482 kN
0.394 kN

-0.409 kN
-0.905 kN
0.275
0.131 kNkN kN
-0.131

Y
X -0.409 kN
Z -0.905 kN Load 3
0.275
0.131 kNkN kN
-0.131

SUCTION WIND LOAD (WL2)

Print Time/Date: 06/02/2023 16:42 STAAD.Pro V8i (SELECTseries 6) 20.07.11.45 Print Run 4 of 7

Page 19 of 43
Job No Sheet No Rev
5
Part
Software licensed to
Job Title Ref

By Date06-Feb-23 Chd

Client File STEEL BRACKET.std Date/Time 06-Feb-2023 16:37

Steel Design (Track 2) Beam 1 Check 1


<check>
1 ST C75X40X5 (JAPANESE SECTIONS)
PASS Eq. H1-1b 0.280 8
0.39 T 0.42 0.30 0.00

Print Time/Date: 06/02/2023 16:42 STAAD.Pro V8i (SELECTseries 6) 20.07.11.45 Print Run 5 of 7

Page 20 of 43
Job No Sheet No Rev
6
Part
Software licensed to
Job Title Ref

By Date06-Feb-23 Chd

Client File STEEL BRACKET.std Date/Time 06-Feb-2023 16:37

Utilization Ratio
Beam Analysis Design Actual Allowable Ratio Clause L/C Ax Iz Iy Ix
Property Property Ratio Ratio (Act./Allow.) (cm2) (cm4) (cm4) (cm4)
1 C75X40X5 C75X40X5 0.280 1.000 0.280 Eq. H1-1b 8 8.818 75.300 12.200 1.200
2 CH100X50X10CH100X50X10 0.183 1.000 0.183 Eq. H1-1b 7 13.000 208.000 32.300 2.510
5 C75X40X5 C75X40X5 0.237 1.000 0.237 Eq. H1-1b 8 8.818 75.300 12.200 1.200
6 C75X40X5 C75X40X5 0.000 1.000 0.000 Sec. G1 6 8.818 75.300 12.200 1.200
7 CH100X50X10CH100X50X10 0.111 1.000 0.111 Eq. H1-1b 7 13.000 208.000 32.300 2.510
8 CH100X50X10CH100X50X10 0.000 1.000 0.000 Sec. G1 6 13.000 208.000 32.300 2.510
9 C75X40X5 C75X40X5 0.280 1.000 0.280 Eq. H1-1b 8 8.818 75.300 12.200 1.200
10 CH100X50X10CH100X50X10 0.183 1.000 0.183 Eq. H1-1b 7 13.000 208.000 32.300 2.510
11 C75X40X5 C75X40X5 0.237 1.000 0.237 Eq. H1-1b 8 8.818 75.300 12.200 1.200
12 C75X40X5 C75X40X5 0.000 1.000 0.000 Sec. G1 6 8.818 75.300 12.200 1.200
13 CH100X50X10CH100X50X10 0.111 1.000 0.111 Eq. H1-1b 7 13.000 208.000 32.300 2.510
14 CH100X50X10CH100X50X10 0.000 1.000 0.000 Sec. G1 6 13.000 208.000 32.300 2.510

0.183
0.111
5.65e-005

0.183
0.111
5.65e-005

0.28
0.237
4.26e-005

Y
X
Z 0.28 Load 3
0.237
4.26e-005

DESIGN UTILIZATION RATIO

Print Time/Date: 06/02/2023 16:42 STAAD.Pro V8i (SELECTseries 6) 20.07.11.45 Print Run 6 of 7

Page 21 of 43
Job No Sheet No Rev
7
Part
Software licensed to
Job Title Ref

By Date06-Feb-23 Chd

Client File STEEL BRACKET.std Date/Time 06-Feb-2023 16:37

Reaction Summary
Horizontal Vertical Horizontal Moment
Node L/C FX FY FZ MX MY MZ
(kN) (kN) (kN) (kNm) (kNm) (kNm)
Max FX 1 8:1.2 DL + 1.6 WL2 2.102 1.642 -0.394 -0.302 0.418 0.000
Min FX 1 7:1.2 DL + 1.6 WL1 -2.102 1.642 0.486 -0.199 -0.418 0.000
Max FY 3 7:1.2 DL + 1.6 WL1 -1.958 1.944 0.612 -0.400 -0.524 0.000
Min FY 3 8:1.2 DL + 1.6 WL2 1.958 -0.859 -0.703 0.170 0.524 0.000
Max FZ 3 7:1.2 DL + 1.6 WL1 -1.958 1.944 0.612 -0.400 -0.524 0.000
Min FZ 3 8:1.2 DL + 1.6 WL2 1.958 -0.859 -0.703 0.170 0.524 0.000
Max MX 3 8:1.2 DL + 1.6 WL2 1.958 -0.859 -0.703 0.170 0.524 0.000
Min MX 3 7:1.2 DL + 1.6 WL1 -1.958 1.944 0.612 -0.400 -0.524 0.000
Max MY 3 8:1.2 DL + 1.6 WL2 1.958 -0.859 -0.703 0.170 0.524 0.000
Min MY 3 7:1.2 DL + 1.6 WL1 -1.958 1.944 0.612 -0.400 -0.524 0.000
Max MZ 1 6:1.4 DL 0.000 1.916 0.053 -0.292 0.000 0.000
Min MZ 1 6:1.4 DL 0.000 1.916 0.053 -0.292 0.000 0.000

Print Time/Date: 06/02/2023 16:42 STAAD.Pro V8i (SELECTseries 6) 20.07.11.45 Print Run 7 of 7

Page 22 of 43
EasyFix4 v. 4.8.2 - Concrete 2128e2458

Project: Date: 2023-02-06 Page: 1/6


Subject: Organization:
Address: Address:
Calculations made by: Contact:

Checked by: ................................................................. 2021-01-06


Notes

Input data
Anchor type and size R-KERII+R-STUDS-10130-A4FL
High performance resin for use with metric threaded rods -
steel grade A4-70
Nominal depth (hnom) 60 mm (hef = 60 mm)
Base material Cracked concrete (C20/25) Temp. short/long None
Reinforcement No reinforcement
Longitudinal edge reinf. Without edge reinforcement or stirrups
Installation Hammer drilling, Installation conditions: Dry concrete
Lever arm None
Fixture Baseplate (x=200 mm, y=125 mm)
Declared thickness: tfix = 10 mm
Recommended thickness: 7 mm (Calculated)
Material: S275 (acc. to S275) fyk=275 MPa, γ=1.1
Steel profile PFC 100x50x10 (h=100 mm, b=50 mm)
Proof EOTA TR029
ETA-21/0242 v.11/03/2021
Working life of 50 years

Design loads

N 710 N
Mx 530 Nm
My 400 Nm
Vx 1.95 kN
Vy 2.11 kN
Ms 0 kNm

*Not a real scale

Page
National regulations, environmental and application conditions must be considered when designing the anchorage. 23 of 43
EasyFix4 v. 4.8.2 - Concrete 2128e2458

Project: Date: 2023-02-06 Page: 2/6


Subject: Organization:
Address: Address:
Calculations made by: Contact:

Resulting anchor forces

Anchor N V Vx Vy

1 1.372 kN 648.6 N 605.2 N 233.3 N


2 184.8 N 1.02 kN 605.2 N 821.7 N
3 3.135 kN 437.3 N 369.8 N 233.3 N
4 1.948 kN 901.1 N 369.8 N 821.7 N
Max. concrete compressive stress: 2.473 MPa
eNEd - Resulting tension force in (-27 mm, 28 mm): 6.64 kN
eCEd - Resulting compression force in (58 mm, -51 mm): 3.16 kN
N - Tension force
V - Shear force
Vx - Shear force x
Vy - Shear force y

Tensile load (EOTA TR029, Section 5.2.2)

Steel failure
βN1 = 14.3%
calculated for anchor: 3

41 kN 1.87 21.93 kN 3.13 kN

Combined pullout-concrete cone failure βN2 = 30.1%

20.73 kN 11 MPa 15 MPa 1.0 11 MPa 10 mm 60 mm 32400 mm²

79200 mm² 90 mm 180 mm ∞ 1.0 1.0 27 mm 0.77

16 mm 0.85 0.655 2.3 1.0 1.0 33.18 kN 1.5

22.12 kN 6.64 kN

Page
National regulations, environmental and application conditions must be considered when designing the anchorage. 24 of 43
EasyFix4 v. 4.8.2 - Concrete 2128e2458

Project: Date: 2023-02-06 Page: 3/6


Subject: Organization:
Address: Address:
Calculations made by: Contact:

Concrete cone failure βN3 = 37.3%

16.73 kN 7.2 25 MPa 60 mm 32400 mm² 79200 mm² 90 mm 180 mm

∞ 1.0 1.0 27 mm 0.77 16 mm 0.85 0.655

26.77 kN 1.5 17.85 kN 6.64 kN

Splitting failure βN4 = 33%

16.73 kN 7.2 25 MPa 60 mm 32400 mm² 79200 mm² 90 mm 180 mm

∞ 1.0 1.0 27 mm 0.77 16 mm 0.85 0.655

1.129 30.23 kN 1.5 20.15 kN 6.64 kN

Shear load (EOTA TR029, Section 5.2.3)

Steel failure without lever arm


βV1 = 8%
calculated for anchor: 2

20 kN 1.56 12.82 kN 1.02 kN

Page
National regulations, environmental and application conditions must be considered when designing the anchorage. 25 of 43
EasyFix4 v. 4.8.2 - Concrete 2128e2458

Project: Date: 2023-02-06 Page: 4/6


Subject: Organization:
Address: Address:
Calculations made by: Contact:

Steel failure with lever arm βV2 = ND

Concrete pry-out failure


βV3 = 7.5%
calculated for anchor: 2

16.73 kN 7.2 25 MPa 60 mm 32400 mm² 19800 mm² 90 mm 180 mm

∞ 1.0 1.0 0 mm 1.0 0 mm 1.0 1.0

2.0 20.45 kN 1.5 13.63 kN 1.02 kN

Concrete edge failure βV4 = ND

Utilisation

Tension Shear Combined


βN βV α βNα + βVα
37.3% 8% 1.5 25%
correct connection

Hints for the calculations and the program

- According to the current guidelines for the design of anchorages, the calculations in EasyFix4 base on the assumption
that the base plate is rigid, which means that redistribution of loads on the anchors due to elastic deformation of the base

Page
National regulations, environmental and application conditions must be considered when designing the anchorage. 26 of 43
EasyFix4 v. 4.8.2 - Concrete 2128e2458

Project: Date: 2023-02-06 Page: 5/6


Subject: Organization:
Address: Address:
Calculations made by: Contact:

Hints for the calculations and the program

plate is not taken into account. In the software, the recommended thickness of the base plate can be determined, however
the correctness of the installation of the rigid base plate must be checked and confirmed separately.
- The size of the holes in the base plate must not be larger than it is allowed in the table with installation parameters.
Otherwise, all gaps in the holes between the anchors and the fixed element must be filled, e.g. by filling the gaps with
resin of adequate compressive strength.
- Preparation of holes and installation of fasteners must be performed in accordance with the installation instruction,
taking into account the entered input data.
- The information and data contained in EasyFix4 apply only to Rawlplug products. The results of the calculations carried
out with the use of the Software are based on data entered by the User, who is exclusively responsible for the correctness
of the input data and any errors. In addition, the User is exclusively responsible for the verification and recognition of the
calculation results by a competent person, in particular with regard to compliance with applicable standards and
regulations.

Installation data for R-KERII+R-STUDS-10130-A4FL

Thread diameter d 10 mm


Hole diameter in substrate d0 12 mm
Min. hole depth in substrate h0 65 mm
Nominal depth hnom 60 mm
Calculated min. substrate thickness hmin 150 mm
Installation torque Tinst 20 Nm
Anchor length L 130 mm
Fixture thickness tfix 10 mm
Hole diameter in fixture df 12 mm
Amount of resin per one mount (normal loss) 5 ml

Page
National regulations, environmental and application conditions must be considered when designing the anchorage. 27 of 43
EasyFix4 v. 4.8.2 - Concrete 2128e2458

Project: Date: 2023-02-06 Page: 6/6


Subject: Organization:
Address: Address:
Calculations made by: Contact:

Fixture shape

Page
National regulations, environmental and application conditions must be considered when designing the anchorage. 28 of 43
EasyFix4 v. 4.8.2 - Concrete 2128e2458

Project: Date: 2023-02-06 Page: 1/7


Subject: Organization:
Address: Address:
Calculations made by: Contact:

Checked by: ................................................................. 2021-01-06


Notes

Input data
Anchor type and size R-KERII+R-STUDS-10130-A4FL
High performance resin for use with metric threaded rods -
steel grade A4-70
Nominal depth (hnom) 60 mm (hef = 60 mm)
Base material Cracked concrete (C20/25) Temp. short/long None
Reinforcement No reinforcement
Longitudinal edge reinf. Without edge reinforcement or stirrups
Installation Hammer drilling, Installation conditions: Dry concrete
Lever arm None
Fixture Baseplate (x=140 mm, y=100 mm)
Declared thickness: tfix = 10 mm
Recommended thickness: 7 mm (Calculated)
Material: S275 (acc. to S275) fyk=275 MPa, γ=1.1
Steel profile (h=75 mm, b=40 mm)
Proof EOTA TR029
ETA-21/0242 v.11/03/2021
Working life of 50 years

Design loads

N 710 N
Mx 0 kNm
My 400 Nm
Vx 1.95 kN
Vy 2.11 kN
Ms 530 Nm

*Not a real scale

Page
National regulations, environmental and application conditions must be considered when designing the anchorage. 29 of 43
EasyFix4 v. 4.8.2 - Concrete 2128e2458

Project: Date: 2023-02-06 Page: 2/7


Subject: Organization:
Address: Address:
Calculations made by: Contact:

Resulting anchor forces

Anchor N V Vx Vy

1 2.242 kN 3.215 kN 2.582 kN -1.915 kN


2 100.4 N 3.935 kN 2.582 kN 2.97 kN
3 2.242 kN 2.5 kN -1.607 kN -1.915 kN
4 100.4 N 3.377 kN -1.607 kN 2.97 kN
Max. concrete compressive stress: 1.797 MPa
eNEd - Resulting tension force in (-32 mm, 0 mm): 4.68 kN
eCEd - Resulting compression force in (59 mm, 0 mm): 2.85 kN
N - Tension force
V - Shear force
Vx - Shear force x
Vy - Shear force y

Tensile load (EOTA TR029, Section 5.2.2)

Steel failure
βN1 = 10.3%
calculated for anchor: 1

41 kN 1.87 21.93 kN 2.24 kN

Combined pullout-concrete cone failure βN2 = 37.3%

20.73 kN 11 MPa 15 MPa 1.0 11 MPa 10 mm 60 mm 32400 mm²

48000 mm² 90 mm 180 mm 40 mm 0.833 1.0 32 mm 0.738

0 mm 1.0 0.738 2.3 1.0 1.0 18.88 kN 1.5

12.59 kN 4.68 kN

Page
National regulations, environmental and application conditions must be considered when designing the anchorage. 30 of 43
EasyFix4 v. 4.8.2 - Concrete 2128e2458

Project: Date: 2023-02-06 Page: 3/7


Subject: Organization:
Address: Address:
Calculations made by: Contact:

Concrete cone failure βN3 = 46.2%

16.73 kN 7.2 25 MPa 60 mm 32400 mm² 48000 mm² 90 mm 180 mm

40 mm 0.833 1.0 32 mm 0.738 0 mm 1.0 0.738

15.24 kN 1.5 10.16 kN 4.68 kN

Splitting failure βN4 = 40.9%

16.73 kN 7.2 25 MPa 60 mm 32400 mm² 48000 mm² 90 mm 180 mm

40 mm 0.833 1.0 32 mm 0.738 0 mm 1.0 0.738

1.129 17.21 kN 1.5 11.47 kN 4.68 kN

Shear load (EOTA TR029, Section 5.2.3)

Steel failure without lever arm


βV1 = 30.7%
calculated for anchor: 2

20 kN 1.56 12.82 kN 3.94 kN

Page
National regulations, environmental and application conditions must be considered when designing the anchorage. 31 of 43
EasyFix4 v. 4.8.2 - Concrete 2128e2458

Project: Date: 2023-02-06 Page: 4/7


Subject: Organization:
Address: Address:
Calculations made by: Contact:

Steel failure with lever arm βV2 = ND

Concrete pry-out failure


βV3 = 62.3%
calculated for anchor: 1

16.73 kN 7.2 25 MPa 60 mm 32400 mm² 9000 mm² 90 mm 180 mm

40 mm 0.833 1.0 0 mm 1.0 0 mm 1.0 1.0

2.0 7.75 kN 1.5 5.16 kN 3.21 kN

Concrete edge failure


βV4 = 50.6%
calculated for anchors: 1, 3

3.89 kN 1.7 10 mm 0.122 0.076 60 mm 25 MPa 7200 mm²

10800 mm² 40 mm 1.0 1.0 2.103 2 mm 0.965 0.965

1.0 11.83 kN 1.5 7.89 kN 3.99 kN

Page
National regulations, environmental and application conditions must be considered when designing the anchorage. 32 of 43
EasyFix4 v. 4.8.2 - Concrete 2128e2458

Project: Date: 2023-02-06 Page: 5/7


Subject: Organization:
Address: Address:
Calculations made by: Contact:

Utilisation

Tension Shear Combined


βN βV α βNα + βVα
46.2% 62.3% 1.5 80.5%
correct connection

Hints for the calculations and the program

- According to the current guidelines for the design of anchorages, the calculations in EasyFix4 base on the assumption
that the base plate is rigid, which means that redistribution of loads on the anchors due to elastic deformation of the base
plate is not taken into account. In the software, the recommended thickness of the base plate can be determined, however
the correctness of the installation of the rigid base plate must be checked and confirmed separately.
- The size of the holes in the base plate must not be larger than it is allowed in the table with installation parameters.
Otherwise, all gaps in the holes between the anchors and the fixed element must be filled, e.g. by filling the gaps with
resin of adequate compressive strength.
- Preparation of holes and installation of fasteners must be performed in accordance with the installation instruction,
taking into account the entered input data.
- The information and data contained in EasyFix4 apply only to Rawlplug products. The results of the calculations carried
out with the use of the Software are based on data entered by the User, who is exclusively responsible for the correctness
of the input data and any errors. In addition, the User is exclusively responsible for the verification and recognition of the
calculation results by a competent person, in particular with regard to compliance with applicable standards and
regulations.

Installation data for R-KERII+R-STUDS-10130-A4FL

Thread diameter d 10 mm


Hole diameter in substrate d0 12 mm
Min. hole depth in substrate h0 65 mm
Nominal depth hnom 60 mm
Calculated min. substrate thickness hmin 150 mm
Installation torque Tinst 20 Nm
Anchor length L 130 mm
Fixture thickness tfix 10 mm
Hole diameter in fixture df 12 mm
Amount of resin per one mount (normal loss) 5 ml

Page
National regulations, environmental and application conditions must be considered when designing the anchorage. 33 of 43
EasyFix4 v. 4.8.2 - Concrete 2128e2458

Project: Date: 2023-02-06 Page: 6/7


Subject: Organization:
Address: Address:
Calculations made by: Contact:

Page
National regulations, environmental and application conditions must be considered when designing the anchorage. 34 of 43
EasyFix4 v. 4.8.2 - Concrete 2128e2458

Project: Date: 2023-02-06 Page: 7/7


Subject: Organization:
Address: Address:
Calculations made by: Contact:

Fixture shape

Page
National regulations, environmental and application conditions must be considered when designing the anchorage. 35 of 43
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

CHECK FOR DEFLECTION:

Allowable deflection = 2L/240 (As per IBC)


= 2(360) mm / 240
= 3 mm
Maximum Absolute deflection (Service Load Combination) = 0.2 < 3 mm Hence Safe.

Page 36 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

APPENDIX -3

WIND PRESSURE CALCULATION

Page 37 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

WIND LOAD CALCULATION SHEET [FOR GFRC-CANOPY STRUCTURE]


The design wind pressure is calculated according to ASCE 7-05 & 16[C/C-Canopy Structures & Wall
Cladding]

Design Wind Pressure p = qh[(GCp) - (GCpi)] [From Eq 6.22; 6.5.12.4.1 Buildings with h (8m) < 18.3m]

Where,

Velocity Pressure qz = 0.613 Kz Kzt Kd V2 I [From Eq 6.15; 6.5.10-Velocity Pressure]

Velocity Pressure Exposure Co-efficient, Kz = 1.13 [From Sec;6.5.6.6(Page-26 & Table 6-3]

Topographic Factor Kzt = 1.0 [From Sec;6.5.7.2(Page-26)]

Wind Directionality Factor Kd = 0.85 [From Sec;6.5.4.4(Page-25 & Table 6-4]

Basic Wind Speed V = 45 m/s [From Project Specification]

Importance Factor I = 1.0 [From Sec;6.5.5(Page-25 & Table 6-1]

Building Exposure Categories BE = D [From Sec;6.5.6.3]

Building Occupancy Category BO = II [From Table 1-1]

Building Height [Max-Top Cladding] h=8m

Effective Wind Area of Panel Ea = Minimum Considered for Worst Case Scenario

Internal Pressure Co-efficient GCpi = + 0 (Open Building) [From Fig; 6-5(Page-47)]

External Pressure Co-efficient GCp zone4 = +1, -1.4 (maximum of Zone 4 & 5 [From Fig; 6-11A]

Velocity Pressure qz = 0.613 Kz Kzt Kd V2 I = 0.613 x 1.13 x 1.0 x 0.85 x (45)2 x 1.0 = 1.2 kN/m2

Page 38 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
EXTRA CO INDUSTRIES L.L.C
Precast Business Unit, PO. Box-21391, RAK, U.A.E.

Tel.: +971-7-2589339 | Fax: +971-7-2589073. | [email protected]| www.extraco.ae |[email protected]


STRUCTURAL CALCULATION SHEET
Document No : EXT-W656-TS-CAL-01 Prepared by :CHANDRA MOHAN Rev :00
Project Name : MARSA AL ARAB QUAY WALL VILLAS Date: 6th FEB 2023
Contractor : ASGC GROUP Sheet No:

CASE-1: [VERTICAL FACE]

DESIGN WIND PRESSSURE;

Design Wind Pressure ppositive = qh [(GCp) - (GCpi)] = 1.2[(1) – (0)] = 1.2 kN/m2

Design Wind Pressure pnegative = qh [(GCp) - (GCpi)] = 1.2[(-1.4) – (0)] = -1.68 kN/m2

CASE-2: [ HORIZONTAL FACE]


Wind Load on Canopy Based on ASCE 7-16 Section 30.11
p = qh [(GCp)]

Where,
GCp = Net pressure coefficient (From Figure 30.11-1A, 30.11-1B of ASCE 7-16) = -1.4, +0.9

DESIGN WIND PRESSURE;

Upward (negative) Wind Pressure, Pupward = 1.24 (-1.4) = 1.74 kN/m2

Downward (Positive) Wind Pressure Pdownward = 1.24 (0.9) = 1.12 kN/m2

For Conservative Design we will consider maximum wind force on both directions as 1.75 kN/m2 on

vertical & horizontal face of cladding.

Page 39 of 43
EXT-W656-TS-CAL-02| Rev. 00|6th FEB 2023
TECHNICAL SUBMITTAL
Project: 2020 – MARSA AL ARAB Ref. No.:
300-ANC-ASGC-ARC-SDG-
004823-R1
Contract: P300/CA/ASGC-KILLA/105/21 Date:
Shop Drawing for Ancillaries Entrance Gate House GRC Indicated Elevations, GRC Indicated Plan & Section Details, GRC
Description: Blowup Details - D1 To D8 Attention:
BIM – Building Information Model MES – Method Statement SCH – Schedule Submittal Code:
CAL – Calculation MND – Manufacturers Data SHD – Shop Drawing 1 – Approval
CER – Certificate MRP – Monthly Report SSB – Sample Submittal 2 – Information
COS – Compliance Statement OTH – Others TED – Technical Data
Type code: DOC – Document PPL – Proposal TNS – Technical Submittal
DRP – Daily Report PRQ – Pre-Qualification TRP – Test Reports
DWG – Drawings SAM – Samples WAR – Weekly Report
GUA – Guarantee SAR – Site Accident Report WRP – Warranty
MAS – Material Submittal
A – Approved B – Approved as noted C – Not approved/Resubmit D – Rejected
Status code: (Work can proceed) (Work can proceed incorporating the comments) (Revise & Resubmit)

Sr. Doc Ref. Rev. Rev date Description Type Submittal Status
No. code code code
(by KLD)

1.

2.

3.

4.

5.

6.

Digital Copy: Yes No Download link:


Submitted by (Contractor’s PM):
Name: Signature: Date:
Received by (KLD):
Name: Signature: Date:

BELOW PORTION FOR KLD USE ONLY


Comments

KLD ARC: See attached comments.

KLD Representative:
Name: MH(KLD) Signature: Date:
Received by (Contractor):
Name: Signature: Date:
Corrections or comments made relative to submittals during this review do not relieve the contractor from compliance with the contract requirements and
specifications. This check is only for review of general conformance with the design concept of the project and general compliance with the information
given in the contract documents and no time and/or cost implication shall be granted due to the Engineer 's /PM instruction.

Note: Continue on next page if more than 6 documents.

Page 40 of 43
Form no.KLD-SF31/CPL/15-Sep-2019/Rev.0 Page 1 of 1
S4
1 2 A B
KLD ARC: ALL
BRACKETS MUST
S1 BE CONCEALLED
ROOF TOW ROOF TOW
8.625 m FFL 8.625 m FFL

KLD ARC:
KEY PLAN:
EIFS cladding - White APPROVAL IS ONLY
RAL 9003 FOR GRC PANELS, 12 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35
36 38 40 41
37 39
42 43 44 45 46 47 48 49 50 51 52 53 54 56 57
55

GRC TOP GRC TOP LOUVERS AND A


B
C
E
G
D
F

DOORS ARE TO BE
H

7.800 m FFL 7.800 m FFL


J
K
L
M
N
P
Q

REVIEWED AND T S
U V
W
X

Brown metalic/ anodized powder APPROVED MAA2 MAA1


coated Aluminium cladding
SEPARATELY GENERAL NOTES:
GRC profile white frame 1- ALL DIMENSIONS ARE IN MILLI METERS UNLESS NOTED
RAL 9003 OTHERWISE. DIMENSIONS SHALL NOT BE OBTAINED BY
SCALLING DRAWINGS
GRC profile white frame RAL 9003 2- ALL LEVELS SHOWN ARE IN METERS.
Brown metalic/ anodized 3- LEVEL 0.000 = 0.000 DMD
powder coated Aluminium 2
Brown metalic/ anodized frames and louvers DRAWING REFERENCES
powder coated Aluminium
DESCRIPTION DWG. REF. No REV
frames and louvers
Brown metalic/ anodized
powder coated Aluminium
WA-01 door - to match louvers
AN010203GF01
Sliding window
DF- 01 ARCHITECTURAL MAA-KLD-AN01-AR-GA-ZZ-1001 04
Brown metalic/ anodized Clear Galss Hinged Door AN010203GF01
ARCHITECTURAL MAA-KLD-AN01-AR-EL-XX-2001 04
powder coated Aluminium refer to door elevations
1 IFC-FACADE
IFC-FACADE
MAA-INH-AN01-AF-DE-GF-0213
MAA-INH-AN01-AF-DE-GF-0212
00
00
frame - to match louvers
IFC-FACADE MAA-INH-AN01-AF-DE-GF-0211 00
IFC-FACADE MAA-INH-AN01-AF-DE-GF-0210 00

EIFS cladding - White RAL 9003 Stone Tiles Steps to match IFC-FACADE MAA-INH-AN01-AF-SE-GF-0010 00
Stone Tiles from Landscape LEGEND
Stone Tiles Steps to match
Stone Tiles from Landscape
GROUND FLOOR LEVEL GROUND FLOOR LEVEL
5.000 m FFL 5.000 m FFL

SHOP DRAWING REVIEW


1 ELEVATION - 01 2 ELEVATION - 02 The following document has been reviewed in terms of
technical content. This does not include dimensional
GENERAL COMMENTS: checking or checking of quantities. It also does not
- All fixing subject to approved include checking associated information that is not
called up on the drawing.
structural calculation.
- All steel finishes should be in P
accordance with corrosion A. Accepted
A.
Approved
B. Accepted
B.
Subject
Approvedto
C. Accepted
C.
Subject
Rejectedto
– D.D.Not
Accepted
For –
01 26/10/22 AR FOR APPROVAL
00 16/09/22 AR FOR APPROVAL
protection table in specification Comment
with - No
Comments
Resubmission
Comment
Resubmit
Resubmit /
Information
Not in Scope Rev Date Name Description
[ie...C5-m (H0)] PROJECT:

S4 2 1 B S2 A Name: MARSA AL ARAB


MH(KLD) AG CLIENT:

Date:
ROOF TOW ROOF TOW Inhabit ME
Inhabit AsiaLimited
ME
02/11/2022
8.625 m FFL 8.625 m FFL
S3

PROJECT MANAGEMENT:
EIFS cladding - White RAL 9003

GRC TOP GRC TOP


7.800 m FFL 7.800 m FFL

EIFS cladding - White RAL 9003


GRC profile white MAIN CONTRACTOR (DESIGN& BUILT):
frame RAL 9003
Level 5, Building 13, Bay Square.
GRC profile white frame RAL 9003 Bussiness Bay P.O. Box 13164, Dubai,
2 Tel (+971) 4 425 8097,
Brown metalic/ anodized Fax (+971) 4 425 8060
powder coated Aluminium www.asgcgroup.com
frames and louvers
Brown metalic/ anodized MAIN CONSULTANT
WA-01
powder coated Aluminium
frames and louvers
AN010203GF02
KILLA ARCHITECTURAL
DF- 07
AN010203GF03
DESIGN
OFFICE 3103, BURJ AL SALAM TOWER,
Sliding window SHEIKH ZAYED ROAD, PO BOX 26642, DUBAI, UAE
TEL: +971 4 3554447
Hinged double Door d e sign EMAIL: [email protected]
Brown metalic/ anodized WEB: www.killadesign.com

powder coated Aluminium


with louvers integrated 1 SUB CONTRACTOR
Window frame to match louvers
EXTRA CO
INDUSTRIES L.L.C
Precast Business Unit
www.extraco.ae
EIFS cladding - White RAL 9003 [email protected]
TEL. : +971-7-2589339 | FAX : +971-7-2589073
PO.Box 21391, RAK, U.A.E. | [email protected]

Stone Tiles Steps to match


Stone Tiles from Landscape PROJECT NO: ASGC-300
GROUND FLOOR LEVEL GROUND FLOOR LEVEL
5.000 m FFL 5.000 m FFL Stage:
SD

Drawing
Title: ANCILLARIES
ENTRANCE GATE HOUSE
GRC INDICATED ELEVATIONS
1 OF 3

Scale: Plot No./Area:


As PLOT NO:- 3660492
indicated
Date: Drawn By: Checked By: Format:

26/10/2022 AR MRN A1

PROJECT CODE: ORIGINATOR: BUILDING / ZONE:

3 ELEVATION - 03 4 ELEVATION - 04 MAA EXT AN01

DISCIPLINE / TRADE: SUB-DISCIPLINE/


SUB-TRADE : LEVEL : DWG NO.:

AR FC 00 of 43
Page 41 2001
KLD ARC: ALL
BRACKETS MUST KLD ARC:
BE CONCEALLED APPROVAL IS ONLY
FOR GRC PANELS,
LOUVERS AND
D1 DOORS ARE TO BE
REVIEWED AND
APPROVED
SEPARATELY

F S F S
A A
KEY PLAN:

ENTRANCE GATE ENTRANCE GATE A


12 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35
36 38 40 41
37 39
42 43 44 45 46 47 48 49 50 51 52 53 54 56 57
55

HOUSE HOUSE
B
C
D
E
F
G
H

770020

770020
770025 770025

GF-001 GF-001

770020

770020
770025 770025

K
L

270281

270281
M
N

770014

770014
P

4.25 m² 4.25 m² Q
T S
U V
W
X

MAA2 MAA1
+5.000 FFL STAFF TOILET +5.000 FFL STAFF TOILET
GF-002 GF-002 GENERAL NOTES:
+4.900 SSL +4.900 SSL
1.70 m² 1.70 m²
OUTSIDE

OUTSIDE
1- ALL DIMENSIONS ARE IN MILLI METERS UNLESS NOTED
OTHERWISE. DIMENSIONS SHALL NOT BE OBTAINED BY
SCALLING DRAWINGS
7700 14

7700 14
770025

770025
270281 270281

2- ALL LEVELS SHOWN ARE IN METERS.


270281 270281
270281

270281
770020

770020
770025 770025
7700 14 770014
14 14
770020

770020
770025 770025

3- LEVEL 0.000 = 0.000 DMD

DRAWING REFERENCES
DESCRIPTION DWG. REF. No REV

B B
SHOP DRAWING REVIEW
The following document has been reviewed in terms of
technical content. This does not include dimensional
ARCHITECTURAL MAA-KLD-AN01-AR-GA-ZZ-1001 04
checking or checking of quantities. It also does not ARCHITECTURAL MAA-KLD-AN01-AR-EL-XX-2001 04
include checking associated information that is not
called up on the drawing.
D2 IFC-FACADE MAA-INH-AN01-AF-DE-GF-0213 00
IFC-FACADE MAA-INH-AN01-AF-DE-GF-0212 00
P IFC-FACADE MAA-INH-AN01-AF-DE-GF-0211 00
IFC-FACADE MAA-INH-AN01-AF-DE-GF-0210 00
A. Accepted
A. B. Accepted
B. C. Accepted
C. – D.D.Not
Approved Subject
Approvedto Subject
Rejectedto Accepted
For – IFC-FACADE MAA-INH-AN01-AF-SE-GF-0010 00
Comment
with - No Comment Resubmit /
Information
Comments Not in Scope
Resubmission Resubmit
LEGEND

1 1 SECTIONAL PLAN - 1 2 Name:


AG 1 2 REFLECTED CEILING PLAN - 2 2
Date:
Inhabit ME
Inhabit AsiaLimited
ME
02/11/2022

MH(KLD)

1 2 2 A B
+8.675 TOW
ROOF LELEL ROOF LELEL ROOF LELEL ROOF LELEL
8.625 m 8.625 m 8.625 m 8.625 m

D4 D7
D3

GRC TOP LEVEL GRC TOP LEVEL GRC TOP LEVEL


7.800 m 7.800 m 7.800 m GRC TOP LEVEL
GRC BOTTOM 7.800 m (AN-01) GRC BOTTOM
7.700 m 7.700 m
01 26/10/22 AR FOR APPROVAL
00 16/09/22 AR FOR APPROVAL
Rev Date Name Description
PROJECT:

MARSA AL ARAB

CLIENT:

D5 REFER TO SD-2003 GENERAL


FOR COMMENTS COMMENTS: D6
275700
770020

770025
770020

770025

- All fixing
270281

770014
200015

subject to
PROJECT MANAGEMENT:
approved
GRC BOTTOM
structural GRC BOTTOM
calculation.
UPN 100 UPN 100
6.625 m (AN-01) 6.625 m (AN-01)
- All steel
finishes should
MAIN CONTRACTOR (DESIGN& BUILT):
be in accordance DF- 07
AN010203GF03 Level 5, Building 13, Bay Square.

GF-003 with corrosion Bussiness Bay P.O. Box 13164, Dubai,


Tel (+971) 4 425 8097,
protection table Fax (+971) 4 425 8060
www.asgcgroup.com
in specification MAIN CONSULTANT

[ie...C5-m (H0)] KILLA ARCHITECTURAL


DESIGN
OFFICE 3103, BURJ AL SALAM TOWER,
REFER TO SD-2003 SHEIKH ZAYED ROAD, PO BOX 26642, DUBAI, UAE
TEL: +971 4 3554447
FOR COMMENTS d e sign EMAIL: [email protected]
WEB: www.killadesign.com

SUB CONTRACTOR

EXTRA CO
INDUSTRIES L.L.C
Precast Business Unit
www.extraco.ae TEL. : +971-7-2589339 | FAX : +971-7-2589073
[email protected] PO.Box 21391, RAK, U.A.E. | [email protected]

D8 PROJECT NO: ASGC-300


Stage:
SD

Drawing
Title: ANCILLARIES
ENTRANCE GATE HOUSE
GROUND FLOOR LELEL HSA-M8x92/27/40
GROUND FLOOR GROUND FLOOR GRC INDICATED PLAN & SECTION DETAILS
5.000 m FFL 5.000 m FFL GROUND FLOOR LEVEL 5.000 m FFL 2 OF 3
TYP FFL
Scale: Plot No./Area:
As PLOT NO:- 3660492
indicated
Date: Drawn By: Checked By: Format:

26/10/2022 AR MRN A1

PROJECT CODE: ORIGINATOR: BUILDING / ZONE:

S1 SECTION S2 SECTION S3 SECTION S4 SECTION MAA EXT AN01

DISCIPLINE / TRADE: SUB-DISCIPLINE/


SUB-TRADE : LEVEL : DWG NO.:

AR FC 00 of 43
Page 42 2002
This bolt will not
work in block wall

Indicate Material
Indicate Material

KEY PLAN:

12 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35
36 38 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 56 57
37 39 55

A
B
C
D
E
F
G
H
J
K
L

check the installation M


P
N

show dimension
Q
T S
U V

of this panel W
X

MAA2 MAA1

GENERAL NOTES:
1- ALL DIMENSIONS ARE IN MILLI METERS UNLESS NOTED
OTHERWISE. DIMENSIONS SHALL NOT BE OBTAINED BY
SCALLING DRAWINGS
2- ALL LEVELS SHOWN ARE IN METERS.
3- LEVEL 0.000 = 0.000 DMD

DRAWING REFERENCES
DESCRIPTION DWG. REF. No REV
KLD ARC: PLEASE
CLARIFY, DESIGN
DRAWINGS SHOW
THE ENTIRE SHELF
D1 BLOW UP DETAIL D3 BLOW UP DETAIL IS GRC D4 BLOW UP DETAIL ARCHITECTURAL
ARCHITECTURAL
MAA-KLD-AN01-AR-GA-ZZ-1001
MAA-KLD-AN01-AR-EL-XX-2001
04
04
IFC-FACADE MAA-INH-AN01-AF-DE-GF-0213 00
IFC-FACADE MAA-INH-AN01-AF-DE-GF-0212 00
PERFORATED TOP
IFC-FACADE MAA-INH-AN01-AF-DE-GF-0211 00
PANEL IS NOT IFC-FACADE MAA-INH-AN01-AF-DE-GF-0210 00
ACCEPTABLE IFC-FACADE MAA-INH-AN01-AF-SE-GF-0010 00

LEGEND

UPN 100

Check if additional steel is


Check how to fix and required same as the MS
tighten the nut. May channel to fix this bolt. Need
required cut on the steel. coordination with the steel
check if this dimension is Need coordination with contractor if required.
structurally fine steel contractor

D2 BLOW UP DETAIL D5 BLOW UP DETAIL

01 26/10/22 AR FOR APPROVAL


00 16/09/22 AR FOR APPROVAL
This bolt will not
GENERAL work in block wall
Rev
PROJECT:
Date Name Description

COMMENTS: MARSA AL ARAB


- All fixing
subject to CLIENT:

approved
structural UPN 100
calculation.
- All steel
PROJECT MANAGEMENT:
finishes should MH(KLD)

be in accordance
with corrosion
protection table
in specification
MAIN CONTRACTOR (DESIGN& BUILT):
[ie...C5-m (H0)] D6 BLOW UP DETAIL Level 5, Building 13, Bay Square.
Bussiness Bay P.O. Box 13164, Dubai,
Tel (+971) 4 425 8097,
Fax (+971) 4 425 8060
SHOP DRAWING REVIEW www.asgcgroup.com

The following document has been reviewed in terms of MAIN CONSULTANT

technical content. This does not include dimensional KILLA ARCHITECTURAL


checking or checking of quantities. It also does not DESIGN
OFFICE 3103, BURJ AL SALAM TOWER,

include checking associated information that is not d e sign


SHEIKH ZAYED ROAD, PO BOX 26642, DUBAI, UAE
TEL: +971 4 3554447
EMAIL: [email protected]

GRC TOP LEVEL called up on the drawing. WEB: www.killadesign.com

SUB CONTRACTOR
7.800 m (AN-01)
P EXTRA CO
INDUSTRIES L.L.C
Precast Business Unit
A. Accepted
A. B. Accepted
B. C. Accepted
C. – D.D.Not www.extraco.ae
[email protected]
TEL. : +971-7-2589339 | FAX : +971-7-2589073
PO.Box 21391, RAK, U.A.E. | [email protected]
Approved Subject
Approvedto Subject
Rejectedto Accepted
For –
GROUND FLOOR LEVEL Comment
with - No Comment Resubmit /
Information
Comments Not in Scope
TYP FFL Resubmission Resubmit PROJECT NO: ASGC-300
Stage:
SD

Name: Drawing
Title: ANCILLARIES
AG ENTRANCE GATE HOUSE
GRC BLOWUP DETAILS - D1 TO D8
3 OF 3

Scale: Plot No./Area:


As
Date: indicated
PLOT NO:- 3660492
Inhabit ME
Inhabit AsiaLimited
ME
02/11/2022 Date: Drawn By: Checked By: Format:

26/10/2022 AR MRN A1

PROJECT CODE: ORIGINATOR: BUILDING / ZONE:

MAA EXT AN01

D7 BLOW UP DETAIL D8 BLOW UP DETAIL DISCIPLINE / TRADE: SUB-DISCIPLINE/


SUB-TRADE : LEVEL : DWG NO.:

AR FC 00 of 43
Page 43 2003