Mic 2 Mkii Installation Instructions and Reference Handbook 4189320057 Uk
Mic 2 Mkii Installation Instructions and Reference Handbook 4189320057 Uk
MIC-2 MKII
DEIF A/S · Frisenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · [email protected] · www.deif.com
Document no.: 4189320057G
General information
Warnings
Warnings indicate a potentially dangerous situation, which could result in death, personal in- jury or damaged equipment, if
certain guidelines are not followed.
The DEIF unit is not to be opened by unauthorised personnel. If opened anyway, the warranty will be lost.
Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
The English version of this document always contains the most recent and up-to-date information about the product. DEIF does not
take responsibility for the accuracy of translations, and translations might not be updated at the same time as the English document. If
there is any discrepancy, the English version prevails.
Safety issues
Installing and operating the DEIF unit may imply work with dangerous currents and voltages. Therefore, the installation should only be
carried out by authorised personnel who understand the risks involved in working with live electrical equipment.
Be aware of the hazardous live currents and voltages. Do not touch any AC measurement in- puts as this could lead to injury
or death.
Factory settings
The DEIF unit is delivered from factory with certain factory settings. These are based on average values and are not necessarily the
correct settings for matching the engine/generator set in question. Precautions must be taken to check the settings before running the
engine/generator set.
The general purpose of this document is to give the user important information to be used in the installation of the unit.
Please make sure to read this document before starting to work with the DEIF unit and the genset to be controlled. Failure to
do this could result in human injury or damage to the equipment.
Intended users
These Installation Instructions are mainly intended for the person responsible for the design and installation. In most cases, this would
be a panel builder designer. Naturally, other users might also find useful information in the document.
2 www.deif.com
Content
Starting 4
Chapter 1 Introduction
1.1 MIC-2 MKII series meter Overview 5
1.2 Application Area 5
1.3 Function of MIC-2 MKII series meter 5
Chapter 2 Installation 7
2.1 Appearance and Dimensions 8
2.2 Installation Method 9
2.3 Wiring of MIC-2 MKII series meter 10
2.3.1 Terminal Strips 10
2.3.2 Power Requirement 10
2.3.3 Voltage Input Wiring 12
2.3.4 Current Input Wiring 13
2.3.5 Frequently Used Wiring Method 14
2.3.6 Communication 16
2.4 Wiring of the MIC-2 FCT & MIC-2 MKII FCT DIN 17
2.4.1 Voltage input wiring 17
2.4.2 Current input wiring 18
Chapter 5 Communication
5.1 Modbus Protocol Introduction 45
5.2 Communication Format 47
5.3 Data Address Table and Application Details 50
5.3.1 System Parameter Setting 51
5.3.2 System Status Parameter 52
5.3.3 Date and Time Table 53
5.3.4 Over/Under Limit Alarming Setting 54
5.3.5 I/O Modules Settings 55
5.3.6 Metering Parameter Address Table 59
www.deif.com 3
Starting
Congratulations!
You have purchased an advanced, versatile, multi-function power meter, the MIC-2 MKII. The MIC-2 MKII can work as a remote
terminal unit (RTU) that contributes to your system’s stability and reliability by providing real-time power quality monitoring and
analysis.
When you open the package, you will find the following items
1. MIC-2 MKII unit 1
2. Pluggable terminal 3
3. Installation clips 4
4. Rubber gasket 1
5. Quick start guide 1
Please read this manual carefully before operating or installing the MIC-2 MKII to avoid unnecessary trouble.
Variants available
MIC-2 MKII, front mounted
MIC-2 MKII DIN mounted
MIC-2 MKII FCT, Flexible Current Transformer input, front mounted
MIC-2 MKII FCT DIN, Flexible Current Transformer input, DIN mounted
4 www.deif.com
Overview
Energy management
The MIC-2 MKII is able to measure bidirectional, four quadrants kWh and kvarh. It provides maximum/minimum records for power
usage and power demand parameters. All power and energy parameters, including measurement tables, can be viewed remotely so
that users can monitor running load and energy usage status easily.
Harmonic accuracy 1 % when MIC-2 MKII FCT and MIC-2 MKII FCT DIN are including Flexible Current Transformer.
Easy to use
The MIC-2 MKII has a large, clear and easy to read LCD screen for displaying monitoring parameters. The unit screen with selectable
backlight duration can be read easily under poor lighting conditions. All metering data and setting parameters can be accessed
by using the front panel keys or via the communication port. Setting parameters are stored in the EEPROM so that content will be
maintained even the meter is powered off.
www.deif.com 5
Overview
According to the instrument model, the current input type is for 1/5 A CTs or Flexible Current Transformer. Check the instrument model
and connect the voltage and current inputs according to the following wiring diagrams.
6 www.deif.com
Installation – before you begin!
• Installation of the unit must be performed by qualified personnel only, who follow standard safety precautions through the
installation procedures. The personnel must have appropriate training and experience working with high voltage devices.
Appropriate safety gloves, safety glasses and protective clothing are recommended.
• During normal operation, dangerous voltage may flow through many parts of the unit, including terminals, and any connected CTs
(current transformers) and PTs (potential/voltage transformers), all I/Os (inputs and outputs) modules and their circuits. All primary
and secondary circuits can, at times, produce lethal voltages and currents. AVOID contact with any current-carrying surfaces.
• The unit and its I/O output channels are NOT designed as primary protection devices and may NOT be used as primary circuit
protection or in an energy-limiting capacity. The unit and its I/O output channels can only be used as secondary protection. AVOID
using the unit under situations where failure of the unit may cause injury or death. AVOID using the unit for any application where
risk of fire may occur.
• All unit terminals should be inaccessible after installation.
• Do NOT perform Dielectric (HIPOT) test to any inputs, outputs or communication terminals. High voltage testing may damage
electronic components of the unit.
• Applying more than the maximum voltage the unit and/or its modules can withstand will permenately damage the unit and/or its
modules. Please refer to the specifications for all devices before applying voltages.
• When removing unit for service, use shorting blocks and fuses for voltage leads and power supply to prevent harzardous voltage
conditions or damage to CTs. CT grounding is optional.
• DEIF recommends using a dry cloth to wipe the unit.
NOTE: IF THE EQUIPMENT IS USED IN A MANNER NOT SPECIFIED BY THE MANUFACTURER, THE PROTECTION
PROVIDED BY THE EQUIPMENT MAY BE IMPAIRED.
DISCONNECT DEVICE: The following part is considered the equipment disconnect device.
A SWITCH OR CIRCUIT BREAKER MUST BE INCLUDED IN THE END-USE EQUIPMENT OR BUILDING INSTALLATION.
THE SWITCH MUST BE IN CLOSE PROXIMITY TO THE EQUIPMENT AND WITHIN EASY REACH OF THE OPERATOR. THE
SWITCH MUST BE MARKED AS THE DISCONNECTING DEVICE FOR THE EQUIPMENT.
www.deif.com 7
2.1 Appearance and dimensions
The installation method is introduced in this chapter. Please read it carefully before beginning installation work.
Appearance
8 www.deif.com
2.2 Installation method
Environmental
Before installation, please check the environment, temperature and humidity to ensure the MIC-2 MKII is being placed where
optimum performance will occur.
Temperature
Operation: -25 to 70 ˚C
Storage: -40 to 85 ˚C
Humidity
5 % to 95 % non-condensing.
The MIC-2 MKII should be installed in a dry and dust free environment. Avoid exposing the unit to excessive heat, radiation and high
electrical noise source.
Installation steps
The MIC-2 MKII can be installed into a standard ANSI C39.1 (4” round) or an IEC 92 mm DIN (square) form.
1. Cut a square hole or round hole on the panel of the switch gear. The cutting size is shown in fig 2.3. – unit: mm (inches)
2. Remove the clips from the unit, and insert it into the square hole from the front side.
Panel
Panel
3. Put clips back into the unit from the backside and push the clips tightly so that the unit is fixed on the panel.
Panel
Figure 2.5: Use the clips to fix the unit on the panel
Note: The DIN rail meter has a quite other installation method, it must be installed on the 35 mm rail. You can refer to the other DIN
rail meters for the detailed installation method.
www.deif.com 9
2.3 Wiring of the MIC-2 MKII
DANGEROUS
Only qualified personnel to do the wire connection work. Make sure the power supply is cut off and all the wires are
powerless. Failure to observe this may result in severe injury or death.
NOTE
Make sure the voltage of power supply equals the auxiliary power required by the MIC-2 MKII. Make sure the auxiliary power
terminal of the MIC-2 MKII ground is connected to the safety earth of the switchgear.
10 www.deif.com
2.3 Wiring of the MIC-2 MKII & MIC-2 MKII DIN
The unit’s typical power consumption is very low and can be supplied by an independent source or by the measured load line. A
regulator or an uninterrupted power supply (UPS) should be used under high power fluctuation conditions. Terminals for the auxiliary
power supply are 11, 12 and 13 (L, N, and Ground). A switch or circuit breaker is to be included in a building installation. It must be
located in close proximity to the equipment, within easy reach of the operator, and clearly marked as the disconnecting device for the
equipment.
A fuse (typical 1A/250V AC) should be used in auxiliary power supply loop. No. 13 terminal must be connected to the ground terminal
of the switchgear. An isolated transformer or EMC filter should be used in the auxiliary power supply loop if there is a power quality
problem in the power supply.
Voltage input
Maximum input voltage for the MIC-2 MKII shall not exceed 400LN/690LL V AC rms for three phase or 400LN V AC rms for single
phase.
Potential Transformer (PT) must be used for high voltage systems. Typical secondary output for PTs equals 100V or 120V.
Please make sure to select an approprate PT to maintain the measurement accuracy of the unit. When connecting using the star
configuration wiring method, the PT’s primary side rated voltage should be equal to or close to the phase voltage of the system to
utilise the full range of the PT. When connecting using the delta configuration wiring method, the PT’s primary side rated voltage
should be equal to or close to the line voltage of the system. A fuse (typical 1A/250V AC) should be used in voltage input loop. The
wire of voltage input could be AWG16-12 or 1.3-2.0mm2.
Note: Under no circumstance should the secondary of the PT be shorted. The secondary of PT should be grounded at one end.
Please refer to the wiring diagram section for further details.
Current input
Current Transformers (CTs) are required in most engineering applications. The typical current rating for the secondary side of the CT
equals 5A. CTs must be used if the system rated current is over 5A. The accuracy of the CT should be better than 0.5% with rating
over 3VA is recommended in order to preserve the unit’s accuracy. Keep the wire between CTs and the MIC-2 MKII as short as
possible. The length of the wire may increase the risk of measurement errors.
Note: The secondary side of the CT should not be an open circuit in any circumstance when the power is turned on. There should not
be any fuse or switch in the CT loop. One end of the CT loop should be connected to the ground.
www.deif.com 11
2.3 Wiring of the MIC-2 MKII
Vn connection
Vn is the reference point of the MIC-2 MKII voltage input. Low wire resistance helps improve the measurement accuracy. Different
system wiring mode requires different Vn connection method. Please refer to the wiring diagram section for more details.
L1 L2 L3
L1 L2 L3
12 www.deif.com
2.3 Wiring of the MIC-2 MKII
L1 L2 L3
L1 L2 L3
L1 L2 L3
www.deif.com 13
2.3 Wiring of the MIC-2 MKII
L1 L2 L3
2CT
The difference between Fig 2.15 and Fig 2.16 is that no current flows through current input terminal I21 and I22. The unit should be
set to the I2 value which is calculated from formula i1+i2+i3=0. The current input mode of the unit should be set to 2CT.
L1 L2 L3
L1 L2 L3
14 www.deif.com
2.3 Wiring of the MIC-2 MKII
L1 L2 L3
L1 L2 L3
L1
L1 L2
www.deif.com 15
2.3 Wiring of the MIC-2 MKII
2.3.6 Communication
The MIC-2 MKII uses RS485 serial communication and the Modbus-RTU protocol. The terminals of communication are A, B, and S
(14, 15, 16). A is differential signal +, B is differential signal – and S is connected to a shield of twisted pair cable. Up to 32 devices
can be connnected on a RS485 bus. Use good quality shielded twisted pair cable, AWG22 (0.5 mm2) or higher. The overall length
of the RS485 cable connecting all devices should not exceed 1200m (4000ft). The unit is used as a slave device of masters like PC,
PLC, data collector or RTU.
If the master does not have RS485 communication port, a converter (such as a RS232/RS485 or a USB/RS485 converter) will be
required. Typical RS485 network topologies include line, circle and star (wye).The shield of each segment of the RS485 cable must
be connected to the ground at one end only.
Every A(+) should be connected to A(+), B(-) to B(-), or it will influence the network, or even damage the communication interface.
The connection topology should avoid “T” type which means there is a new branch and it does not begin from the beginning point.
Use a RS232/RS485 or USB/RS485 converter with optically isolated output and surge protection.
The default device address and the default baud rate of the DIN rail meter are 1 and 9600 respectively. Those two default values will
always be used for the first minute after the meter is powered on. The device address and the baud rate of the meter will change to
the user defined values after the first minute.
16 www.deif.com
2.4 Wiring of the MIC-2 MKII FCT & MIC-2 MKII FCT DIN
The following are the common installation methods when using the FCT flexible current transformers and their respective diagrams
and meter configurations.
www.deif.com 17
2.4 Wiring of the MIC-2 MKII FCT & MIC-2 MKII FCT DIN
For FCT Flexible Current Transformer wiring, connect the white cable to the I11 (I21 or I31) terminal, the shield to functional earth
and the brown cable to the I12 (I22 or I32) terminal. Refer to the following pictures below. The arrow on the FCT has to go towards
Load (Current Flow Direction).
Figure 2.31: 3LN, 3FCT Figure 2.32: 3LL, 3FCT Figure 2.33: 2LL, 3FCT
Single phase: 2 lines (single phase Single phase: 3 lines (single phase
with one line and a neutral) with 2 lines and a neutral)
LINE LINE
A N A N B
1A FUSE 1A FUSE
White White
1 I11 10 9 8 7 1 I11 10 9 8 7
Vn V3 V2 V1 Vn V3 V2 V1
Brown Brown
2 I12 2 I12
White
3 I21 3 I21
Brown
4 I22 4 I22
5 I31 5 I31
6 I32 6 I32
LOAD LOAD
18 www.deif.com
3.1 Display Panel and Keys (Only MIC-2 MKII & MIC-2 MKII FCT)
Detailed human-machine interface of the meter will be described in this chapter. This includes viewing real-time metering data and
setting parameters using different key combinations.
1
10
4
5 2
8 3
9
11 17
12
13 14 15 16
www.deif.com 19
3.1 Display Panel and Keys
SN Display Description
Shows different modes on the display area. “Meter” for real-time
measurement; “Max/Min” for statistic data; “Demand” for power demand
1 Display mode indication
data; “Harmonic” for harmonic data; “Setting” for parameters setting;
“Digital I/O” for expanded IO module data.
Main display area: displays metering data such as voltage, current,
power, power factor, frequency, unbalance, phase angle, etc. Displays
2 Four lines of “ ” digits in the metering area statistics such as maximum and minimum, demand data, display
settings and expanded I/O data.
Displays energy data and real-time clock. Also used for the setting
3 Four “ ” and five “ ” digits mode and digital I/O mode display.
Item Icons: “U” for voltage; “I” for current; “P” for active power; “Q”
for reactive power; “S” for apparent power; “PF” for power factor; “F”
4 Three “ ” digits for frequency; “ ” for phase angles; “DMD” for demand; "Mxx" for
expanded IO module type; and display setting page number.
Item Icons: “Unbalance” for unbalance of the voltage and current; “THD”
5 Unbalance, THD, TDD, MAX, MIN for total harmonics distortion; “TDD” for total demand distortion; “MAX”
for maximum and “MIN” for minimum
6 Load rate Displays the percentage of load current to the nominal current.
16 Current tariff
20 www.deif.com
3.2 Metering Data
Pressing H and V/A simultaneously will activate the display mode selection and the cursor will flash. Press P or E to move the cursor
right or left. To enter the metering mode, move the cursor to "Meter" then press V/A.
In the metering mode, pressing P and E simultaneously will enter the TOU mode.
In metering mode, the meter displays measurements such as voltage, current, power, power factor, phase angle, unbalance etc.
In the TOU mode, meter displays the energy, maximum demand and it's time in different tariffs.
Press V/A to read voltage and current in the metering area. The screen will roll to the next page when V/A is pressed again. It will go
back to the first screen if you press V/A at the last screen.
Note: When the meter is set to “2LL” or “3LL”, there is no phase voltage or neutral current display. Therefore, only the third screen
(line voltage and avg) and the the fourth screen (three phase current and avg) will be displayed.
When the meter is set to “1LN”, there are only phase A voltage and phase A current display, without line voltages or other displays.
When the meter is set to “1LL”, there are no phase C voltage and phase C current display.
Press P again to roll to the next page. It will go back to the first screen if you press P at the last screen.
www.deif.com 21
3.2 Metering Data
Note: When the meter is set to “2LL” or “3LL”, only the fifth screen (system power) and the sixth screen (system power factor &
frequency) will be displayed.
When the meter is set to “1LN”, there are only phase A power and phase A power factor display.
When the meter is set to “1LL”, there are no phase C power and phase C power factor display.
Press H to display phase angles and unbalance data. Press H again to toll to the next page. It will go back to the first screen if you
press H at the last screen.
When using "2LL" or "3LL" wiring setting mode, voltage stands for line to line voltage. Otherwise, voltage stands for line-to-neutral
voltage.
When the meter is set to “1LN”, there is only phase A current to phase A voltage angle display.
When the meter is set to “1LL”, there is no phase C voltage or current to phase A voltage angle factor display.
d) Energy:
Press E key to display energy and real time clock. Press E again to roll to the next page. It will go back to the first screen if you press
E at the last screen.
MIC-2 MKII can be set to record primary energy or secondary energy. The unit of energy is kWh for active energy, kvarh for reactive
energy and kVAh for apparent energy. The running time has a resolution of 0.01h. The meter begins accumulating time upon initial
powering up of the unit. The accumulated time is stored in the non-volatile memory. It can be reset via communication or from the
meter front.
22 www.deif.com
3.3 Statistics Data
Pressing H and V/A simultaneously will activate the display mode selection, and the cursor will flash. Press P or E to move the cursor
right or left. To enter the statistics data mode, scroll the cursor to "Max/Min", then press V/A.
In statistics data mode, the meter displays the maximum values and minimum values for voltage, current, power, power factor,
unbalance, demand, THD etc. User should note that time stamp for the parameters can be viewed only from the software through
communication. No commands are associated with the key H in "Max/Min" display mode.
When P is pressed again, the screen will roll to the next page, and will roll back to the first screen when pressed at the last page.
When E is pressed, the screen will roll back to the previous page, and will roll back to the last screen when pressed at the first page.
Press V/A to switch the view between maximum and minimum. For example, if the current display is the maximum phase voltage
value, when V/A is pressed, the display will show the minimum phase voltage value. If V/A is pressed again, the display will switch
back to show the maximum phase voltage value.
www.deif.com 23
3.4 Demand Data
Pressing H and V/A simultaneously will activate the display mode selection and the cursor will flash. Press P or E to move the
cursor right or left. To enter demand mode, move the cursor to "Demand", then press V/A.
In the demand data mode, the first screen displays the demand of active power, reactive power and apparent power, and the second
screen displays the current demand of phase A, phase B and phase C. When the meter is set to “1LL”, there is no phase C current
demand display. When the meter is set to “1LN”, there are no phase B and C current demand display.
As shown in the figure, system active power demand is 3.285 kW, system reactive power demand is 0 kvar, system apparent power
demand is 3.285 kVA.
24 www.deif.com
3.5 Harmonic Data
Pressing H and V/A simultaneously will activate the display mode selection, and the cursor will flash. Press P or E to move the cursor
right or left. To enter harmonic mode, move the cursor to “Harmonic”, then press V/A.
In the harmonic data mode, meter displays the harmonic ratio of voltage and current, THD, odd HD, even HD, THFF, CF and KF.
Press H to display power quality data. When H is pressed again, the screen will roll to the next page and will roll back to the first
screen when pressed at the last page.
Note: When the meter is set to “1LN”, there is only phase A display for voltage THD, voltage odd HD, voltage even HD, THFF, voltage
crest factor, current THD, current odd HD, current even HD, and current K factor.
1. The figure shows the rolling sequence when pressing P. If E is pressed, the sequence will reverse.
2. Harmonic is 2nd~63rd.
3. When the meter is set to “1LN”, there is only phase A display for voltage and current harmonic magnitude.
4. When the meter is set to “1LL”, there is no phase C display for voltage and current harmonic magnitude.
www.deif.com 25
3.6 Expanded I/O Module Data
Pressing H and V/A simultaneously will activate the display mode selection, and the cursor will flash. Press P or E to move the cursor
right or left. To access data from the expanded I/O modules, move the cursor to "Digital I/O", then press V/A to enter the expanded
I/O module data mode.
In the expanded I/O module data mode, the meter displays the data from expanded I/O modules, such as DI status, pulse counter
number, relay status, analogue input, and analogue output etc.
In this mode, the first page is module selection. You can choose to view the available modules that are attached to the meter. If no
expanded I/O modules are connected, the screen will display "NO IO".
a) Module Selection:
No commands are associated with the key H in the module selection screen.
Press P to move the cursor downwards, the cursor will move to the top when it reaches the bottom. If only one module is connected,
Pressing P will have no effect.
Press E to move the cursor upwards, the cursor will move to the bottom when it reaches the top. If only one module is connected,
Pressing E will have no effect.
Press V/A to select the module and enter the I/O module data selection mode.
As shown in the figure, three modules are connected, AXM-IO11, AXM-IO21, AXM-IO31, which are indicated by M11, M21, M31
respectively. The cursor points to M21, which indicates that AXM-IO21 is chosen now.
Press P to move the cursor downwards, the cursor will move to the top when it reaches the bottom. Please note that there are 3
parameters for AXM-IO1, 3 parameters for AXM-IO2 and 4 parameters for AXM-IO3.
Press E to move the cursor upwards, the cursor will move to the bottom when it reaches the top.
Press V/A to select the parameter and enter the display of the data.
The screen will roll to the next page each time P is pressed and will return to the first page when P is pressed at the last page. If only
one page exists, pressing P will have no effect.
The screen will roll to the last page each time E is pressed and will return to the last page when E is pressed at the first page. If only
one page exists, pressing E will have no effect.
26 www.deif.com
3.6 Expanded I/O Module Data
Note: The figure shows the rolling sequence for using key P. If using E key for rolling page, the sequence will reverse.
www.deif.com 27
3.7 Parameter Setting Mode
Pressing H and V/A simultaneously will activate the display mode selection, and the cursor will flash. Press P or E to move the
cursor right or left. To enter parameter setting mode, move the cursor to "Setting", then press V/A.
In the parameter setting mode, parameters such as system parameters, expanded I/O module parameters, alarm parameters and
Ethernet module parameters, can be read and modified.
a) Password Inquiry:
Parameter setting mode is password-protected. Before entering the password and getting into the parameter setting mode, the
meter's device communication address will display for 3 seconds. A four digit password (0000 to 9999) is required everytime
before accessing the parameter setting mode. The default password is 0000. After entering the password, press V/A to go to the
parameter selection page. The meter will be still in the password inquiry page if a wrong password is entered.
To input password:
There are four parameters to choose from in the parameter selection manual: system, expanded I/O module, Ethernet module and
alarm.
No commands are associated with the H key in the parameter selection manual.
Press P to move the cursor downwards, the cursor will move to the top when it reaches the bottom.
Press E to move the cursor upwards, the cursor will move to the bottom when it reaches the top.
Press V/A to select and modify the parameter. The figure shows the parameter selection page. “SYS” stands for system parameter,
“I/O” stands for expanded I/O module parameter, “NET” stands for Ethernet module parameter and “ALM” stands for alarm
parameter. As shown in the figure, the cursor points to the “SYS”, which means system parameter is selected.
28 www.deif.com
3.7 Parameter Setting Mode
Users can select and modify system parameter in the system parameter setting mode.
www.deif.com 29
3.7 Parameter Setting Mode
Note: The figure shows the rolling sequence for using the P key. If using the E key for rolling page, the sequence will reverse.
In the expanded I/O module parameter mode, user can choose to view the available modules that are attached to the meter and
modify their parameters. If no expanded I/O modules are connected, the screen will display "NO IO". To return to system parameter
setting mode main menu, press H (no commands are associated with other keys in this screen).
Press E to move the cursor upwards, the cursor will move to the bottom when it reaches the top.
Press V/A to select the module and enter the I/O module parameter setting mode.
30 www.deif.com
3.7 Parameter Setting Mode
Choose output energy type for DO1. Range from 0-4. 0: no output; 1:
import active energy; 2: export active power; 3: import reactive energy; 4:
export reactive energy.
Be aware that modules with current option cannot be set as voltage type
(i.e. option 2 and 3 are unavailable); modules with voltage option cannot
be set as current type (i.e. option 0 and 1 are unavailable).
www.deif.com 31
3.7 Parameter Setting Mode
If relay pulse control method is selected, the relay contact will close
for a preset period and open afterwards. The pulse width range is
50~3000 ms.
Note: The figure shows the rolling sequence for using key P. If using E key for rolling page, the sequence will reverse.
When the second communication protocol is set to BACnet, there is parameters display related to BACnet, while these pages only
show as modules successfully connecting with meter. If meter does not detect any module, it will show LOADING page. To set these
parameters, first select, then modify and save. On the one hand, if there is no extra BACnet module, setting will be meaningless and
not saved after shutting down. On the other hand, setting is valid and will be saved into BACnet module when a BAVnet module is
attached.
When second communication protocol is other protocol, parameters display is related to Ethernet. The condition is the same as
above.
32 www.deif.com
3.7 Parameter Setting Mode
Note: The figure shows the rolling sequence for using key P. If using E key for rolling page, the sequence will reverse.
IP
www.deif.com 33
3.7 Parameter Setting Mode
f) Alarm Parameter
In the alarm parameter mode, user can view and modify the parameters.
Press V/A to confirm the modification and return to parameter selection mode.
Note: The figure shows the rolling sequence for using key P. If using E for rolling page, the sequence will reverse.
34 www.deif.com
3.8 Page Recovery Function
The MIC-2 MKII has a page recovery function. This means that the meter stores current display page in the non-volatile memory
upon power loss and reloads the page when power recovers. If power goes off when viewing under the parameter setting mode, the
meter will show voltage display when power recovers. If power goes off when viewing under the expanded I/O module data mode,
and if this expanded I/O module is not connected when power recovers, the meter will show the voltage display page instead.
www.deif.com 35
4.1 Basic analogue measurements
The MIC-2 MKII contains very advanced metering tools and is able to measure almost all power metering and quality parameters
from a power system. Some advanced functions may not be accessible directly from the unit front; therefore, every unit comes with a
powerful software that helps accessing those information. This chapter is dedicated to introduce these functions and the software.
4.1 Basic Analogue Measurements
The MIC-2 MKII can measure voltage, current, power, frequency, power factor and demand etc. with high accuracy, shown as below:
Demand:
The MIC-2 MKII consists of several types of demand calculation: total active power demand, total reactive power demand, total
apparent power demand, phase L1 current demand, phase L2 current demand, and phase L3 current demand. When demand is
reset, demand memory registers are set as 0.
Demand calculating mode can be set as sliding window and thermal by the user. The figure 4-7 shows how it works.
When using the sliding window interval method, the user selects an interval from 1 to 30 minutes, which is the period of the
calculation. The demand updates every 1 minute.
Thermal demand method calculates the demand based on a thermal response which mimics the thermal demand meter. The user
selects the period for the calculation and the demand updates at the end of each period.
Energy:
MIC-2 MKII series meter measures and accumulates energy in different directions (import and export). For real-time energy
monitoring, it accumulates energy for kWh, kvarh and kVAh continuous (since its last reset).
Calculating mode:
1. The user can select different energy calculating modes, fundamental based or full-wave based either from the unit front or via
communication. Fundamental based calculating is to accumulate energy without taking harmonics into consideration while full-
wave based calculating is to accumulate energy including fundamental and harmonics.
Note: When fundamental based calculating mode is selected, PF calcuation will be based on the fundamental wave.
Info: Do not use the fundamental settings in a system where harmonics occur!
3. User can choose primary energy or secondary energy either by pressing keys from the meter front or via communication as shown
in figure 4-7.
36 www.deif.com
4.1 Basic analogue measurements
www.deif.com 37
4.2 Max/Min
The MIC-2 MKII logs maximum and minimum value statistics for phase/line voltages, currents, power, reactive power, apparent
power, power factor, frequency, demand, unbalance factor, THD as well as the time they occur. All data is stored in a non-volatile
memory so that statistic information can be preserved even when the unit is shut off. All maximum and minimum data can be
accessed via communication or from the unit front but time stamps can only be accessed via communication. Statistics can be
cleared via communication or from the unit front.
38 www.deif.com
4.3 Harmonics and power quality analysis
1. Harmonics
The MIC-2 MKII can measure and analyse THD, harmonics (2nd to 63rd for MIC-2 MKII), even HD, odd HD, crest factor, THFF, K
factor, etc. They are shown in figure 4-2.
2. Phase angle:
Phase angle indicates the angle between phase A voltage and other voltage/current parameters. Angle ranges from 0 to 360 degrees.
This function is to help user to find out the relationship between all input signals avoiding wrong wiring. When it is set to “2LL” or
“3LL”, it gives out the phase angles of u23, i1, i2, i3 corresponding to u12. For other settings, it gives out the phase angles of u2, u3,
i1, i2, i3 corresponding to u1. They are shown in figure 4-4.
www.deif.com 39
4.4 Over/Under limit alarming
The MIC-2 MKII has over/under limit alarming capability. When the monitored parameter goes over/under the preset limit and
stays at the level over the preset amount of time delay, the over/under limit alarm will be triggered. The over/under limit value and
its time stamp will be recorded in the alarming log. The meter can record up to 16 alarming records. When extended I/O modules
are attached, digital outputs (DO) and relay outputs (RO) can be triggered upon alarm conditions and used to activate downstream
devices such as beacon light and buzzer.
Before using the alarming function, alarm conditions such as logic dependency, target setpoint, time delay, etc. must be set correctly.
Settings can be accessed and modified from the software via communication connection as shown in Fig 4-5.
Parameter code: select target parameter for alarm monitoring For example: 0-frequency, 44-AI4 sampling data.
Comparison mode: set alarming condition 1: greater than, 2: equal to, 3: smaller than. For example: if you choose target parameter
to be “frequency”, condition to be “greater than” and setpoint to be “50”, alarm will be triggered when the frequency is greater than 50
Hz.
Note: setpoint value is the same as the actual value of the selected parameter.
Delay time: If the alarms condition lasts for the preset time period, the alarm signal will be triggered. The delay range is from 0 to 3000
(unit: 10 ms).
When it is set to 0, there is no delay, alarm will be triggered when the alarm condition is met. If it is set to 20, there will be a 200 ms
(20 x 10 ms) delay.
Output to relay: 0-alarming signal will not be sent to RO; if it is set as 1 and AXM-IO11 is connected, it will output to RO1 when alarm
triggers. RO1 will be turned off when all alarms output to RO1 are cleared. RO2~RO8 work in the same manner as RO1.
After setting up the alarming parameters, the user must also setup the global settings in order for the alarm to work properly.
40 www.deif.com
4.4 Over/Under limit alarming
2. Global settings
Register addresses for global alarm settings are from 1046H~104dH.Please refer to section 5.3 “Global alarming settings” for more
details.
“Global alarming enable” determines whether the alarming function of the meter is activated or not. The alarming function is enabled
when it is set as “1”.
When “Alarming flash enable“ is set as “1”, backlight will flash when alarm is triggered. * Only possible on MIC-2 MKII version.
“Alarming channel enable setting” determines whether the corresponding alarm group is enabled or not. There are 16 groups in all
and each one is corresponding to one bit of a 16-bit register. The corresponding bit must be set to “1” in order to activate the alarm
channel.
“Logical “AND” between alarming setting”: The 16 alarming records in MIC-2 MKII are divided into 8 pairs. Each pair has two alarm
groups. The two groups can be logically “AND” by controlling the logic check box. When two groups are “AND”, alarming triggers only
if both AND conditions are met. If the “AND” logic box is unchecked, the two alarm channels will work independently.
The 8 “AND” logic pairs are arranged as follows: 1st,2nd channel form Pair 1; 3rd,4th channel form Pair 2; 5th,6th channel form Pair
3; 7th,8th channel form Pair 4; 9rd,10th channel form Pair 5; 11th,12th channel form Pair 6; 13th,14th channel form Pair 7; 15th,16th
channel form Pair 8.
This function is controlled by the lower 8 bits of 16 bits register, each bit is corresponding to a pair. “1” means this function is enabled
and “0” means disabled.
“Alarming output to DO1 setting”: When “Digital output mode” is set to “1”, DO1 can be used as alarming output. A 16-bit register is
used to perform this function, its bit0~bit15 correspond to the 1st ~16th group respectively. When the related I/O module is connected
and is under alarming mode, and if the corresponding bit is set to 1 and the alarming condition is met, alarm signal will be sent to
DO1. DO1 will be turned off when all alarms correspond to DO1 are cleared. If related bit is set to 0, that alarm channel will not issue
alarm signal to DO1. DO2~DO4 work in the same manner DO1.
After completing the setup steps correctly, the alarming function can be used.
3. Setting Eeample
Here is an example of showing how to apply the logical “AND” function for a pair of alarm channels.
The conditions are as follows: I1 greater than 180A, delay 5s for the 1st alarm channel; U1 less than 9980V, delay 10s for the 2nd
alarm channel. No alarm signals will be sent to outputs. The CT primary value of I1 is 200A, and CT2 is 5A. The PT ratio for U1 is
10000:100. The following shows how all the related registers are to be set.
Global settings:
“Alarming channel enable setting (1048H)” set to 0003H to enable the first and the second channel.
“Logical “AND” between alarming setting (1049H)” set to 0001H to enable logic “AND” in Pair 1.
“Alarming output to DO1 setting (104aH)” set to 0, since no output to DO1.
“Alarming output to DO2 setting (104bH)” set to 0.
“Alarming output to DO3 setting (104cH)” set to 0.
“Alarming output to DO4 setting (104dH)” set to 0.
“Alarming flash enable (1047H)” set to 0 to disable backlight flashing when alarming occurred.
“Global alarming enable (1046H)” set to 1 to enable over/under limit alarming.
www.deif.com 41
4.4 Over/Under limit alarming
“Alarming status” indicates information of current alarm status. It is a 16-bit unsigned integer. Parameter code is stored in the higher
8 bits. Bit1 indicates whether logic “AND” is enabled or not, 1 means enabled and 0 means not. Bit0 indicates whether alarming is
occurred or recovered, 1 means occurred and 0 means recovered. Undefined bits are 0.
“Value” shows the recorded value of the selected parameter when alarm triggers and when it recovers.
“Time” indicates the time stamp with the accuracy of in milliseconds (ms).
Alarming event will set bit0 of “system status (102eH)” to be 1. At the same time, corresponding flags will be set to 1 to indicate new
data. The flag will be cleared after the data is read. Bit0 of “system status (102eH)” will be set to 0.
Note: Although no alarming records will be lost during unit power off, alarm status will start recording from the 1st alarm log entry
when the unit is powered on again.
42 www.deif.com
4.4 Over/Under limit alarming
Here is an example:
www.deif.com 43
4.4 Software
DEIF View with data logging is available for software download on http://www.deif.com/software/software-download
44 www.deif.com
5.1 Modbus protocol introduction
This chapter will mainly discuss how to handle the unit via the communication port using software. To master this chapter, you should
be familiar with Modbus and have read other chapters of this manual, and you a good understanding of the functions and applications
of this product.
This chapter includes: Modbus protocol, format of communication and data address table and MIC-2 MKII application details.
Transmission mode
The mode of transmission defines the data structure within a frame and the rules used to transmit data. The mode is defined in the
following which is compatible with Modbus RTU Mode*.
Framing
Address field
The address field of a message frame contains eight bits. Valid slave device addresses are in the range of 0~247 decimal. A master
addresses a slave by placing the slave address in the address field of the message. When the slave sends its response, it places its
own address in this address field of the response to let the master know which slave is responding.
Function field
The function code field of a message frame contains eight bits. Valid codes are in the range of 1~255 decimal. When a message is
sent from a master to a slave device the function code field tells the slave what kind of action to perform.
www.deif.com 45
5.1 Modbus protocol introduction
Data Field
The data field is constructed using sets of two hexadecimal digits, in the range of 00 to FF hexadecimal. The data field of messages
sent from a master to slave devices contains additional information which the slave must use to take the action defined by the function
code. This can include items like discrete and register addresses, the quantity of items to be handled, and the count of actual data
bytes in the field. For example, if the master requests a slave to read a group of holding registers (function code 03), the data field
specifies the starting register and how many registers are to be read. If the master writes to a group of registers in the slave (function
code 10 hexadecimal), the data field specifies the starting register, how many registers to write, the count of data bytes to follow in the
data field, and the data to be written into the registers.
If no error occurs, the data field of a response from a slave to a master contains the data requested. If an error occurs, the field
contains an exception code that the master application can use to determine the next action to be taken. The data field can be
nonexistent (of zero length) in certain kinds of messages.
The receiving device recalculates the CRC value during reception of the message, and compares the calculated value to the
actual value it received in the CRC field. If the two values are not equal, an error will be reported. CRC calculation is first started
by preloading the whole 16-bit register to 1’s. The process begins by applying successive 8-bit bytes of the message to the current
contents of the register. Only the eight bits of data in each character are used for generating the CRC. Start and stop bits, and the
parity bit, do not apply to the CRC. When generating the CRC, each 8-bit character is exclusive ORed with the register contents.
The result is shifted towards the least significant bit (LSB), with a zero filled into the most significant bit (MSB) position. The LSB is
extracted and examined, if the LSB equals to 1, the register is exclusive ORed with a preset, fixed value; if the LSB equals to 0, no
action will be taken. This process is repeated until eight shifts have been performed. After the last (eighth) shift, the next 8-bit byte is
exclusive ORed with the register’s current value, and the process repeats for eight more shifts as described above. The final contents
of the register, after all the bytes of the message have been applied, is the CRC value. When the CRC is appended to the message,
the low-order byte is appended first, followed by the high-order byte.
46 www.deif.com
5.2 Communication format
Explanation of frame
Data start Data start Data #of Data #of CRC 16 CRC 16
Addr Fun
reg HI reg LO regs HI regs LO HI LO
06H 03H 00H 00H 00H 21H 84H 65H
Table 5.3: Explanation of frame
The following query is to read the relay status for the meter with communication address 17.
Query
Relay start Relay start Relay #of Relay #of CRC 16 CRC 16
Addr Fun
reg HI reg LO regs HI regs LO HI LO
11H 01H 00H 00H 00H 02H BFH 5BH
Table 5.4: Read the status of Relay1 and Relay2 Query Message
Response
The MIC-2 MKII response includes the MIC-2 MKII address, function code, quantity of data byte, the data, and error checking. An
example response to read the status of Relay1 and Relay2 is shown as Table 5.5. The status of Relay1 and Relay2 are responding to
the last 2 bits of the data.
Relay1: bit0 Relay2: bit1
Function
Address Byte count Data CRC high CRC low
code
11H 01H 01H 02H D4H 89H
Table 5.5: Relay status responds
2. Read status of DI
Function Code 02
1=On 0=Off
DI1’s address is 0000H, DI2’s address is 0001H, and so on.
The following query is to read the status of 4 DIs of MIC-2 MKII with communication address 17.
Query
DI start DI start DI num CRC 16 CRC 16
Addr Fun DI num HI
addr HI addr LO LO HI LO
11H 02H 00H 00H 00H 04H 7BH 59H
Table 5.6: Read 4 DIs Query Message
www.deif.com 47
5.2 Communication format
Response
The MIC-2 MKII response includes the MIC-2 MKII address, function code, quantity of data characters, the data characters, and error
checking. An example response to read the status of 4 DIs is shown in Table in 5.7. The DI status corresponds to the last 4 bits of the
data.
DI1: bit0; DI2: bit1; DI3: bit2; DI4: bit3.
Address Function code Byte count Data CRC high CRC low
11H 02H 01H 03H E5H 49H
Table 5.7: Read status of DI
Query
This function allows the master to obtain the measurement results from the MIC-2 MKII. Table 5.8 is an example to read the 3
measured data (F, V1 and V2) from slave device number 17, the data address of F is 4000H, 4001H; V1’s address is 4002H, 4003,
and V2’s address is 4004H, 4005H.
Data start Data start Data #of Data #of CRC 16 CRC 16
Addr Fun
addr HI addr LO regs HI regs LO regs HI regs LO
11H 03H 40H 00H 00H 06H D2H 98H
Table 5.8: Read F, V1, V2 query message
Response
The MIC-2 MKII response includes the MIC-2 MKII address, function code, quantity of data byte, data, and error checking. An
example response to read F, V1 and V2 (F=42480000H (50.00Hz), V1=42C7CCCDH (99.9V), V2=42C83333H (100.1V)) is shown:
Byte Data1 Data1 Data 2 Data2 Data3 Data3 Data4 Data4
Addr Fun
count HI LO HI LO HI LO HI LO
11H 3H 0CH 42H 48H 00H 00H 42H C7H CCH CDH
Query
This message forces a relay to either turn “ON” or “OFF”. Any relay that exists within the MIC-2 MKII can be forced to either “ON” or
“OFF” status. The data value FF00H will set the relay on and the value 0000H will turn it off; all other values are illegal and will not
affect that relay.
The example below is a request to the MIC-2 MKII with the address of 17 to turn on Relay1.
Addr Fun DO addr HI DO addr LO Value HI Value LO CRC 16 HI CRC 16 LO
11H 05H 00H 00H FFH 00H 8EH AAH
Table 5.10: Control relay query message
Response
The normal response to the command request is to retransmit the message as received after the relay status has been altered.
Addr Fun Relay addr HI Relay addr LO Value HI Value LO CRC HI CRC LO
11H 05H 00H 00H FFH 00H 8EH AAH
Table 5.11: Control relay response message
48 www.deif.com
5.2 Communication format
Query
Function 16 allows the user to modify the contents of a multi-register. Some registers of the MIC-2 MKII can have their contents
changed by this message. The example below is a request to an MIC-2 MKII with the address of 17 to preset Ep_imp as
“17807783.3KWh”, while its HEX value is 0A9D4089H. Ep_imp data address is 4048H and 4049H.
Data start Data start Data #of Data #of
Addr Fun Byte Count
reg HI reg LO reg HI reg LO
11H 10H 40H 48H 00H 02H 04H
Response
The normal response to a preset multi-register request includes the MIC-2 MKII address, function code, data start register, the
number of registers, and error checking.
Data start Data start Data #of Data #of CRC16 CRC16
Addr Fun
reg hi reg lo reg hi Reg lo hi lo
11H 10H 40H 48H 00H 02H D6H 8EH
Table 5.13: Preset multi-register response message
www.deif.com 49
5.3 Data address table and application details
1. Data type:
“bit” refers to binary.
“word” refers to 16-bit unsigned integer using one data address and 2 bytes of memory, it varies from 0 to 65535.
“int” refers to 16-bit integer using one data address and 2 bytes of memory, it varies from -32768 to32767.
“dword” refers to 32-bit unsigned integer using two data addresses and 4 bytes of memory with high word at the front and low word at
the end, it varies from 0 to 4294967295. Rx=high word *65536+low word.
“float” refers to 32-bit single value using two data addresses and 4 bytes of memory, it varies from -1.175494E-38 to 3.402823E+38.
Important Note: Regions from “System parameters settings” to “Data logging 3 settings” are the regions that can be set and modified.
Please follow the rules when you communicate with the MIC-2 MKII.
1. When function code 10H is used, one communication command can only modify contents in one region, such as “System
parameters settings”, ”System status parameter”, “Date and Time table”, “Over/under limit alarming-Global settings”, “Over/under limit
alarming-Single settings”, “I/O Modules settings”, Data logging 1 settings,Data logging 2 settings,Data logging 3 settings. It can not be
accomplished in one communication order to modify contents in both of two or more regions above.
2. When function code 03H is used, the rules and limitations described above will not be applied.
50 www.deif.com
5.3.1 System parameter setting
System parameters determine how the meter works. Please refer to Chapter 3 and Chapter 4 for more details.
Function code: 03H for reading, 10H for writing. Data type: word. Format code: F1.
www.deif.com 51
5.3.2 System status parameter
“System status” indicates what events happened in the meter, what kinds of flags are read by user and to be the index of the storage
of the events. Flags should be cleared after being read by the controller, otherwise new data will not be stored properly.
Function code: 03H for reading, 10H for writing. Data type: word.
Please refer to Chapter 3 and Chapter 4 for more details about parameter settings.
52 www.deif.com
5.3.3 Date and time table
www.deif.com 53
5.3.4 Over/Under limit alarming setting
This setting consists of global alarming settings and single channel alarming settings. Global alarming settings contain settings of all
global variables. There are 16 groups of records with the same format. Function code: 03H for reading, 10H for writing. Please refer to
Chapter 4 for more details.
54 www.deif.com
5.3.4 Over/Under limit alarming setting
www.deif.com 55
5.3.5 I/O modules settings
I/O module setting changes will be made only if the corresponding I/O modules are installed, no changes will be made otherwise.
Please check the I/O module connection status before doing any settings. Function code: 03H for reading, 10H for writing. Please
refer to <<User’s manual of extended I/O Modules>>for more details.
AXM-IO11
Address Parameter Default Range Data type Property
Bit0: DI1, Bit1: DI2
Bit2: DI3, Bit3: DI4
109eH DI1~6 type 0 word R/W
Bit4: DI5, Bit5: DI6
0: DI,1: pulse counter
109fH DI pulse constant 0 1~65535 word R/W
0: control output,
10a0H Working mode of relay 1 and 2 0 word R/W
1: alarming output
10a1H Output mode of relay 1 and 2 0 0: latch, 1: pulse word R/W
10a2H Pulse width 50 50~3000ms word R/W
AXM-IO21
Address Parameter Default Range Data type Property
Bit0: DI7, Bit1: DI8
10a3H DI7~10 type 0 Bit2: DI9, Bit3: DI10 word R/W
0: DI,1: pulse counter
10a4H DI pulse constant 0 1~65535 word R/W
0: pulse output
10a5H Working mode of DO 0 word R/W
1: alarming output
10a6H DO pulse width 20 20~1000ms word R/W
0: none
1: consumption power
10a7H DO1 output 0 2: gererating power word R/W
3: absorption reactive power
4: generating reactive power
10a8H DO2 output 0 Same as above word R/W
10a9H AO 1,2 1 0: 0~20mA, 1: 4~20mA word R/W
56 www.deif.com
5.3.5 I/O modules settings
AXM-IO11
Address Parameter Default Range Data type Property
Bit0: DI1, Bit1: DI2
Bit2: DI3, Bit3: DI4
109eH DI1~6 type 0 word R/W
Bit4: DI5, Bit5: DI6
0: DI,1: pulse counter
109fH DI pulse constant 0 1~65535 word R/W
0: control output,
10a0H Working mode of relay 1 and 2 0 word R/W
1: alarming output
10a1H Output mode of relay 1 and 2 0 0: latch, 1: pulse word R/W
10a2H Pulse width 50 50~3000ms word R/W
AXM-IO21
Address Parameter Default Range Data type Property
Bit0: DI7, Bit1: DI8
10a3H DI7~10 type 0 Bit2: DI9, Bit3: DI10: word R/W
0: DI,1: pulse counter
10a4H DI pulse constant 0 1~65535 word R/W
0: pulse output
10a5H Working mode of DO 0 word R/W
1: alarming output
10a6H DO pulse width 20 20~1000ms word R/W
0: none
1: consumption power
10a7H DO1 output 0 2: gererating power word R/W
3: absorption reactive power
4: generating reactive power
10a8H DO2 output 0 Same as above word R/W
10a9H AO 1,2 1 or 2 0: 0~20mA, 1: 4~20mA, word R/W
AXM-IO31
Address Parameter Default Range Data type Property
Bit0: DI11,Bit1: DI12,
10aaH DI11~14 type 0 Bit2: DI13, Bit3: DI14 word R/W
0: DI, 1: pulse counter
10abH DI pulse constant 0 1~65535 word R/W
0: control output,
10acH Working mode of relay 3 and 4 0 word R/W
1: alarming output
10adH Output mode of relay 3 and 4 0 0: latch, 1: pulse word R/W
10aeH Pulse width 50 50~3000ms word R/W
10afH AI 1,2 1 or 2 0: 0~20mA, 1: 4~20mA, word R/W
AXM-IO12
Address Parameter Default Range Data type Property
Bit0: DI15, Bit1: DI16,
Bit2: DI17, Bit3: DI18,
10b0H DI15~20 type 0 word R/W
Bit4: DI19, Bit5: DI20
0-DI,1-pulse counter
10b1H DI pulse constant (high) 0 1~65535 word R/W
0: control output,
10b2H Working mode of relay 5 and 6 0 word R/W
1: alarming output
0: latch,
10b3H Output mode of relay 5 and 6 0 word R/W
1: pulse
10b4H Pulse width 50 50-3000ms word R/W
www.deif.com 57
5.3.5 I/O modules settings
AXM-IO22
Address Parameter Default Range Data type Property
Bit0: DI21, Bit1: DI22,
10b5H DI21~24 type 0 Bit2: DI23, Bit3: DI24 word R/W
0: DI, 1: pulse counter
10b6H DI pulse constant 0 1~65535 word R/W
0: pulse output,
10b7H Working mode of DO3,4 0 word R/W
1: alarming output
10b8H DO Pulse width 20 20~1000ms word R/W
0: none
1: consumption power
10b9H DO3 output 0 2: gererating power word R/W
3: absorption reactive power
4: generating reactive power
10baH DO4 output 0 Same as above word R/W
10bbH AO 3,4 1 0: 0~20mA, 1: 4~20mA word R/W
AXM-IO32
Address Parameter Default Range Data type Property
Bit0: DI25, Bit1: DI26,
10bcH DI25~28 type 0 Bit2: DI27, Bit3: DI28 word R/W
0: DI, 1: pulse counter
10bdH DI pulse constant 0 1~65535 word R/W
0: control output,
10beH Working mode of relay 7 and 8 0 word R/W
1: alarming output
10bfH Output mode of relay 7 and 8 0 0: latch, 1: pulse word R/W
10c0H Pulse width 50 50~3000 word R/W
10c1H AI 3,4 1 or 2 0: 0~20mA, 1: 4~20mA, word R/W
AO transforming select
Address Parameter Default Range Data type Property
10c2H AO1 transforming parameter 0 Refer to following table word R/W
10c3H AO2 transforming parameter 0 Refer to following table word R/W
10c4H AO3 transforming parameter 0 Refer to following table word R/W
10c5H AO4 transforming parameter 0 Refer to following table word R/W
58 www.deif.com
5.3.6 Metering parameter addresses
www.deif.com 59
5.3.6 Metering parameter addresses
60 www.deif.com
5.3.6 Metering parameter addresses
Function code: 03H for reading, 10H for writing. Data type: dword.
It can be set as primary energy or secondary energy according to user. Please refer to F7, F8, and F9 for more details about the relationship
between numerical value in register and the real physical value.
www.deif.com 61
5.3.6 Metering parameter addresses
Harmonics
THD, Harmonics, odd HD, even HD, Crest Factor, THFF, K factor etc are all stored
here. The data type is “word”. Voltage parameters refer to line voltage when it is
set to “2LL/3LL” and phase voltage for others. Function code: 03H for reading.
Voltage Harmonics, even HD, odd HD, Crest Factor are shown as below
Current Harmonics, even HD, odd HD, Crest Factor are shown as below
62 www.deif.com
5.3.6 Metering parameter addresses
DI Status
Current DI status, if related I/O module isn’t connected, the DI status will be set to 0. Function code: 02H for reading.
AXM-IO11
Address Parameter Range Data type
0000H DI1 1=ON,0=OFF bit
0001H DI2 1=ON,0=OFF bit
0002H DI3 1=ON,0=OFF bit
0003H DI4 1=ON,0=OFF bit
0004H DI5 1=ON,0=OFF bit
0005H DI6 1=ON,0=OFF bit
AXM-IO21
Address Parameter Range Data type
0006H DI7 1=ON,0=OFF bit
0007H DI8 1=ON,0=OFF bit
0008H DI9 1=ON,0=OFF bit
0009H DI10 1=ON,0=OFF bit
AXM-IO31
Address Parameter Range Data type
000aH DI11 1=ON,0=OFF bit
000bH DI12 1=ON,0=OFF bit
000cH DI13 1=ON,0=OFF bit
000dH DI14 1=ON,0=OFF bit
AXM-IO12
Address Parameter Range Data type
000eH DI15 1=ON,0=OFF bit
000fH DI16 1=ON,0=OFF bit
0010H DI17 1=ON,0=OFF bit
0011H DI18 1=ON,0=OFF bit
0012H DI19 1=ON,0=OFF bit
0013H DI20 1=ON,0=OFF bit
AXM-IO22
Address Parameter Range Data type
0014H DI21 1=ON,0=OFF bit
0015H DI22 1=ON,0=OFF bit
0016H DI23 1=ON,0=OFF bit
0017H DI24 1=ON,0=OFF bit
AXM-IO32
Address Parameter Range Data type
0018H DI25 1=ON,0=OFF bit
0019H DI26 1=ON,0=OFF bit
001aH DI27 1=ON,0=OFF bit
001bH DI28 1=ON,0=OFF bit
www.deif.com 63
5.3.6 Metering parameter addresses
MAX/MIN records
MAX/MIN value and time stamp. Function code: 03H for reading.
64 www.deif.com
5.3.6 Metering parameter addresses
MAX/MIN records
MAX/MIN value and time stamp. Function code: 03H for reading.
The addresses for the MIN value of the above parameters are located in 41e5H to 4293H. They have the same format as the MAX
value.
www.deif.com 65
5.3.6 Metering parameter addresses
Sequence component
U1 (U12), I1 consist of a real part and complex part. They have positive sequence, negative sequence and zero sequence. Data type
is “int”. Function code: 03H for reading.
Phase angle
All voltage and current’s phase angles corresponding to V1 (V12) are stored here. You can find out the phase sequence according to
them. Data type is “word”. Function code: 03H for reading.
66 www.deif.com
5.3.6 Metering parameter addresses
Alarming records
There are 16 groups of records with the same format. Function code: 03H for reading, 10H for writing. Please refer to Chapter 4 for
more details.
www.deif.com 67
5.3.6 Metering parameter addresses
AXM-IO11
Address Parameter Code Range Data type Property
4349H~434aH DI1 pulse counter number F1 0~4294967295 dword R
434bH~434cH DI2 pulse counter number F1 0~4294967295 dword R
434dH~434eH DI3 pulse counter number F1 0~4294967295 dword R
434fH~4350H DI4 pulse counter number F1 0~4294967295 dword R
4351H~4352H DI5 pulse counter number F1 0~4294967295 dword R
4353H~4354H DI6 pulse counter number F1 0~4294967295 dword R
AXM-IO21
Address Parameter Code Range Data type Property
4355H~4356H DI7 pulse counter number F1 0~4294967295 dword R
4357H~4358H DI8 pulse counter number F1 0~4294967295 dword R
4359H~435aH DI9 pulse counter number F1 0~4294967295 dword R
435bH~435cH DI10 pulse counter number F1 0~4294967295 dword R
AXM-IO31
Address Parameter Code Range Data type Property
435dH~435eH DI11 pulse counter number F1 0~4294967295 dword R
435fH~4360H DI12 pulse counter number F1 0~4294967295 dword R
4361H~4362H DI13 pulse counter number F1 0~4294967295 dword R
4363H~4364H DI14 pulse counter number F1 0~4294967295 dword R
AXM-IO12
Address Parameter Code Range Data type Property
4365H~4366H DI15 pulse counter number F1 0~4294967295 dword R
4367H~4368H DI16 pulse counter number F1 0~4294967295 dword R
4369H~436aH DI17 pulse counter number F1 0~4294967295 dword R
436bH~436cH DI18 pulse counter number F1 0~4294967295 dword R
436dH~436eH DI19 pulse counter number F1 0~4294967295 dword R
436fH~4370H DI20 pulse counter number F1 0~4294967295 dword R
AXM-IO22
Address Parameter Code Range Data type Property
4371H~4372H DI21 pulse counter number F1 0~4294967295 dword R
4373H~4374H DI22 pulse counter number F1 0~4294967295 dword R
4375H~4376H DI23 pulse counter number F1 0~4294967295 dword R
4377H~4378H DI24 pulse counter number F1 0~4294967295 dword R
AXM-IO32
Address Parameter Code Range Data type Property
4379H~437aH DI25 pulse counter number F1 0~4294967295 dword R
437bH~437cH DI26 pulse counter number F1 0~4294967295 dword R
437dH~437eH DI27 pulse counter number F1 0~4294967295 dword R
437fH~4380H DI28 pulse counter number F1 0~4294967295 dword R
68 www.deif.com
5.3.6 Metering parameter addresses
AI input value
The output of AI is mapped to the range of 0~4095 according to its sampling value using some algorithm. Data type is “word”.
Function code: 03H for reading. Please refer to <<User’s manual of expanded I/O modules>> for more details.
AO output
The output of AO is the actual value of output. Over/under limit or Data type is “float”. Function code: 03H for reading. Please refer to
<<User’s manual of expanded I/O modules>> for more details.
SOE Records
There are 20 groups of records with the same format. Function code: 03H for reading. Before gathering SOE records, the selected
I/O module must be SOE enabled. If the SOE enabled I/O module is not connected, SOE record logs will not be collected. Please
refer to <<User’s manual of expanded I/O modules>> for more details.
Current demand
Include real-time current demand, the maximum current demand and time of occurance. Function code: 03H for reading.
www.deif.com 69
5.3.6 Metering parameter addresses
Relay status
Function code: 01H for reading, 05H for controlling output.
AXM-IO11
Address Parameter Range Data type
0000H Relay1 1=ON,0=OFF bit
0001H Relay2 1=ON,0=OFF bit
XM-IO31
Address Parameter Range Data type
0002H Relay3 1=ON,0=OFF bit
0003H Relay4 1=ON,0=OFF bit
XM-IO12
Address Parameter Range Data type
0004H Relay5 1=ON,0=OFF bit
0005H Relay6 1=ON,0=OFF bit
70 www.deif.com