Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

PNNL-32278

Model Specification of
Droop-Controlled, Grid-
Forming Inverters
(GFMDRP_A)
December 2021

Prepared for the U.S. Department of Energy


under Contract DE-AC05-76RL01830
DISCLAIMER

This report was prepared as an account of work sponsored by an agency of the


United States Government. Neither the United States Government nor any agency
thereof, nor Battelle Memorial Institute, nor any of their employees, makes any
warranty, express or implied, or assumes any legal liability or responsibility
for the accuracy, completeness, or usefulness of any information, apparatus,
product, or process disclosed, or represents that its use would not infringe
privately owned rights. Reference herein to any specific commercial product,
process, or service by trade name, trademark, manufacturer, or otherwise does not
necessarily constitute or imply its endorsement, recommendation, or favoring by
the United States Government or any agency thereof, or Battelle Memorial
Institute. The views and opinions of authors expressed herein do not necessarily
state or reflect those of the United States Government or any agency thereof.

PACIFIC NORTHWEST NATIONAL LABORATORY


operated by
BATTELLE
for the
UNITED STATES DEPARTMENT OF ENERGY
under Contract DE-AC05-76RL01830

Printed in the United States of America

Available to DOE and DOE contractors from the


Office of Scientific and Technical Information,
P.O. Box 62, Oak Ridge, TN 37831-0062;
ph: (865) 576-8401
fax: (865) 576-5728
email: [email protected]

Available to the public from the National Technical Information Service


5301 Shawnee Rd., Alexandria, VA 22312
ph: (800) 553-NTIS (6847)
email: [email protected] <https://www.ntis.gov/about>
Online ordering: http://www.ntis.gov
Contributors
Wei Du, PNNL
Robert H. Lasseter, University of Wisconsin-Madison
Song Wang, PacifiCorp
Songzhe Zhu, GridBright
Christian Hardt, SMA Solar Technology AG
Hongtao Ma, NERC
Yuan Liu, PNNL
Zhenyu Huang, PNNL
Francis K. Tuffner, PNNL
Renke Huang, PNNL
1.0 Objective
This document describes a positive-sequence phasor model of droop-controlled, grid-forming
(GFM) inverter-based resources (IBRs). It can be considered as an initial model for evaluating
the impacts of GFM IBRs on the transients and dynamics of transmission systems.

2.0 Grid-Forming Inverter Concept


A grid-forming inverter behaves as a controllable voltage source behind a coupling reactance as
shown in Fig. 1. The internal voltage magnitude E and angular frequency ω are controlled by
the droop controller.
E δE V δV
XL AC
E
ω Grid

P, Q, I φ
Fig. 1 Basic model of grid-forming inverter.
The coupling reactance, XL, is important for the droop controller design. By properly sizing XL,
for example, between 0.05 and 0.15 pu on an inverter rating base, the inverter output active
power, P, and reactive power, Q, can be approximately decoupled. As shown by (1) to (3), P is
approximately linear with the phase angle difference δP, and Q is approximately linear with E.
The well-developed droop control is based on this decoupling characteristic.

 p =  E − V (1)

EV EV
P= sin  p  p (2)
XL XL
E 2 − EV cos  p E(E − V )
Q=  (3)
XL XL

3.0 Positive-Sequence Phasor Model of Droop-Controlled,


Grid-Forming Inverters
This section will introduce the positive-sequence phasor model of droop-controlled, grid-forming
inverters, including the inverter main circuit representation, the droop control, and the fault
current limiting function. This model applies to energy storage systems and photovoltaic (PV)
systems.

3.1 Inverter Main Circuit Representation


The inverter main circuit is modeled as a voltage source behind the coupling reactance XL, as
shown in Fig. 2 (a). The grid-forming controller will adjust the internal voltage magnitude E and

1
phase angle δE. When interfacing with the network solver, the voltage source will be converted
to its Norton equivalent current source, as shown in Fig. 2 (b).
XL V δV V δV

P, Q, I φ P, Q, I φ

E δE IN φN YL

(a) (b)
Fig. 2 Inverter equivalent circuits. (a) Inverter internal voltage source and the coupling
reactance. (b) Norton equivalent current source.

3.2 Grid-Forming Droop Control Model


Fig. 3 (a) and (b) show the P-f droop control and Q-V droop control, which regulate the inverter
internal voltage magnitude and phase angle during normal operations. Table 1 shows the
inverter and controller parameters.
Table 1 Parameters of the Droop-Controlled, Grid-Forming Inverters on the Inverter Rating Base
Symbol Description Typical Value Normal Range
XL Inverter coupling reactance 0.15 pu 0.05 pu–0.25 pu
mq Q-V droop gain 0.05 pu 0 pu–0.20 pu
Initialized by power
Vset Voltage set point NA
flow
kpv Proportional gain of the voltage controller 0 pu 0 pu–0.01pu
kiv Integral gain of the voltage controller 5.86 pu/s 3 pu/s–15 pu/s
Emax Upper limit of the output of the voltage loop 1.15 pu 1 pu–1.25 pu
Emin Lower limit of the output of the voltage loop 0 pu 0 pu
mp P-f droop gain 0.01 pu 0.005 pu–0.05 pu
Initialized by power
Pset Power set point NA
flow
Pmax Upper limit of the inverter active power output 1 pu 1 pu–1.5 pu
Should be negative when
Pmin Lower limit of the inverter active power output 0 pu representing energy
storage systems
Proportional gain of the overload mitigation
kppmax 0.01 pu 0.005 pu–0.05 pu
controller
kipmax Integral gain of the overload mitigation controller 0.1 pu/s 0.05 pu/s–0.2 pu/s
ω0 Rated angular frequency 376.99 rad/s NA
Time constant of the low-pass filter for P
TPf 0.01 s 0.01 s–0.1 s
measurement
Time constant of the low-pass filter for Q
TQf 0.01 s 0.01 s–0.1 s
measurement
Time constant of the low-pass filter for V
TVf 0.01 s 0.01 s–0.1 s
measurement
Qmax Upper limit of the inverter reactive power output 1 pu 0.5 pu–1 pu
Qmin Lower limit of the inverter reactive power output -1 pu -0.5 pu– -1 pu
Voltage control mode selection. The controller can
0: Regulate the inverter
VFlag either regulate the point of interconnection (POI) 1
internal voltage E
voltage V or the inverter internal voltage E
VFlag=1 3 pu 1 pu – 5 pu
kpqmax Proportional gain of the Qmax and Qmin controller
VFlag=0 0.1 pu 0 pu – 0.5 pu
VFlag=1 20 pu/s 3 pu/s – 30 pu/s
Kiqmax Integral gain of the Qmax and Qmin controller
VFlag=0 10 pu/s 3 pu/s – 30 pu/s
Imax Inverter maximum output current 2 pu 1.5 pu–3 pu

2
The P-f droop control ensures that the phase angles of multiple grid-forming inverters are
synchronized during normal operations. When two grid-forming inverters operate in parallel
under P-f droop control, any disturbance causes an increase in the output power of one inverter.
This, causes its P-f droop control to reduce the angular frequency ω of the internal voltage so
that the phase angle, δdroop, is reduced, preventing the inverter from further increasing its output
power. This negative-feedback control mechanism guarantees the synchronization when
multiple grid-forming inverters work in parallel. In addition, the controller shown in Fig. 3 (a) also
prevents the output power of the inverter from exceeding Pmax or dropping below Pmin. The P-f
droop control also achieves load sharing between grid-forming inverters.
The Q-V droop control prevents large circulating reactive power between grid-forming inverters.
As shown in Fig. 3 (b), the Q-V droop control can either directly regulate the inverter internal
voltage Edroop, or regulate the point of interconnection (POI) voltage V by regulating Edroop
through a proportional-integral controller. The VFlag will determine which control mode will be
selected. In addition, there is a Qmax and Qmin controller to prevent the inverter reactive power
output from exceeding Qmax or dropping below Qmin.

Pinv ω δdroop
-
mp ω0 1/s
+ ++
Pset
+ ω
0 +
Pmax ω0
kppmax
+- +
0 +
kipmax/s
Pinv +
+
kipmax/s
0
Pmin +- kppmax ++
0
(a)

3
VFlag Emax
Vset Edroop
0
Qinv +
mq - Emin
+
Emax
Vref + Edroop
0 1 kpv
Qmax - ++
+- kpqmax + Emin
Vinv Emax
0 +
kiqmax/s kiv/s
Qinv +
Emin
+
kiqmax/s
0
Qmin +- +
+
kpqmax
0
(b)
Fig. 3 Droop control. (a) P-f droop control and overload mitigation control. (b) Q-V droop control.
When interacting with the transmission network solver, the per unit values of P, Q, V on the
system rating base returned by the network solver need to be converted to the per unit values
on the inverter rating base and pass through a low-pass filter as shown by (4) to (6), where Sbase
is the base value of the system rating, Mbase is the base value of the inverter rating, and Pinv ,
Qinv , and Vinv are the per unit values of inverter output active power, reactive power, and voltage
magnitude on the inverter rating base. The outputs of the controller, Edroop and δdroop, are used to
determine the inverter internal voltage EδE.
1 S
Pinv = P base
1 + TPf s M base (4)

1 S
Qinv = Q base
1 + TQf s M base (5)

1
Vinv = V
1 + TVf s (6)

3.3 Fault Current Limiting Function


During normal operations, the droop control will control the inverter voltage magnitude and
phase angle. However, during short circuit faults, the fault current limiting function will be
activated to limit the output current of the inverter. Fig. 4 shows the fault current limiting function.
The inverter works in the droop control mode during normal operations and keeps monitoring its
output current Iφ. The output current Iφ is calculated using (7) in each simulation step. When
the magnitude of the output current I is smaller than the inverter maximum current limit Imax , the
inverter internal voltage is governed by the droop control so that EδE = Edroopδdroop. However,
once I exceeds Imax because of severe faults, the inverter internal voltage EδE will be
calculated based on the inverter terminal voltage VδV, the coupling reactance XL, and the new
current phasor Imax φ as shown by Fig. 4. By doing so the magnitude of the inverter output

4
current I will be limited at Imax during faults, but its phase angle φ will remain unchanged
compared to the case without the fault current limiting function. Once the fault is cleared, the
inverter output current will drop below Imax so that the operation mode will autonomously switch
back to the droop control mode.

Edroop  droop − V V


I  = (7)
jX L

Edroop δdroop I < Imax


E δE
I Imax
V δV+jXLImax φ
Fig. 4 Fault current limiting function.

4.0 Interface with the Transmission Network Solver


When interfacing with the transmission network solver, the inverter internal voltage source
needs to be converted to its Norton equivalent circuit for the network solution, as shown in Fig. 2
(a) and (b). Equation (8) and (9) are used for the conversion.

E E
I N  N = (8)
jX L
1
YL = (9)
XL

The flowchart in Fig. 5 shows the process of how the developed positive-sequence phasor
model interacts with the transmission network solver.

5
P, Q, V δV, I φ
Droop Control
(Fig. 3)

Edroop δdroop
V δV, I Fault Current Limiting
(Fig. 4)

E δE
Inverter Internal
Voltage Source

Eq. (7)-(8)
Norton Equivalent
Circuit (Fig. 2)

IN φ N , Y L

Network Solver

No
Converged ?

Yes

Fig. 5 Interaction between the grid-forming inverter model and the transmission network solver.

References

[1] Y. Lin et al., "Research roadmap on grid-forming inverters," National Renewable Energy Lab.(NREL),
Golden, CO (United States), 2020.
[2] R. Lasseter, Z. Chen, and D. Pattabiraman, "Grid-Forming Inverters: A Critical Asset for the Power Grid,"
IEEE Journal of Emerging and Selected Topics in Power Electronics, pp. 1-1, 2019, doi:
10.1109/JESTPE.2019.2959271.
[3] R. H. Lasseter et al., "CERTS Microgrid Laboratory Test Bed," IEEE Transactions on Power Delivery, vol.
26, no. 1, pp. 325-332, 2011
[4] M. C. Chandorkar, D. M. Divan, and R. Adapa, "Control of parallel connected inverters in stand -alone AC
supply systems," in Industry Applications Society Annual Meeting, 1991 .
[5] B. J. Pierre et al., "Bulk Power System Dynamics with Varying Levels of Synchronous Generators and Grid-
Forming Power Inverters," in the 46th IEEE Photovoltaic Specialists Conference, Chicago, Illinois, USA,
2019.
[6] M. E. Elkhatib, W. Du, and R. H. Lasseter, "Evaluation of Inverter-based Grid Frequency Support using
Frequency-Watt and Grid-Forming PV Inverters," in 2018 IEEE Power & Energy Society General Meeting
(PESGM)
[7] W. Du, Y. Liu, R. Huang, K. F. Tuffner, J. Xie, and Z. Huang, "Positive-Sequence Phasor Modeling of
Droop-Controlled, Grid-Forming Inverters with Fault Current Limiting Function," IEEE PES Innovative
Smart Grid Technologies (ISGT) North America (NA) Meeting, 2022.

6
Pacific Northwest
National Laboratory
902 Battelle Boulevard
P.O. Box 999
Richland, WA 99354
1-888-375-PNNL (7665)

www.pnnl.gov

You might also like