MRXBOXAB-ECO (3 5) - AESW - MVHR For Wall Mounting
MRXBOXAB-ECO (3 5) - AESW - MVHR For Wall Mounting
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 31. 08. 22. Document Number 671861
1
Installation Manual MRXBOXAB-ECO3-AE(OH)SW & MRXBOXAB-ECO5-AE(OH)(CV/SC/SW)
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 31. 08. 22. Document Number 671861
2
Installation Manual MRXBOXAB-ECO3-AE(OH)SW & MRXBOXAB-ECO5-AE(OH)(CV/SC/SW)
3.3.1 Option 1 - Solid Wall 3.4 Condensate Drain
The MVHR unit fixed to a solid wall construction using the The MVHR unit inside the enclosure is fitted with a straight coupling to
mounting bracket provided. allow 21.5mm overflow pipe (not supplied) to be attached using solvent
5 Solid Wall Mounted Unit Installation cement, the pipe should be passed through the flexible adhesive backed
cover plate before the solvent cement is applied.
The pipe can then be inserted into the coupling of the MVHR unit and
the cover plate slid along the length to bond against the base panel of
the enclosure preventing noise breakout (Figure 7).
Min 5 o Drop
MVHR-DRAIN
Condensate drain,
uninsulated drain
pipe with min 5o fall
running to SVP. Collar
Condensate drain,
uninsulated drain pipe with
min 5° fall running to SVP.
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 31. 08. 22. Document Number 671861
3
Installation Manual MRXBOXAB-ECO3-AE(OH)SW & MRXBOXAB-ECO5-AE(OH)(CV/SC/SW)
10 "T" Piece CONTRAP & MVHR Drain Connection
Whole Dwelling Ventilation Rates
Ducting must be installed in such a way that resistance to airflow is (For sanitary accommodation only, as an alternative, the purge
minimised. Bends should be kept to a minimum. ventilation provisions given in ADF 2010 can be used where security is
not an issue. In this case ‘minimum high extract rate’ for the sanitary
A minimum distance of 300mm between the appliance and any bends accommodation should be omitted from the step 2 calculation).
in ductwork is recommended. Step 3: The required airflow rates are as follows:
Ideally 150mm diameter or 204 x 60mm rectangular ducting should be •The maximum whole dwelling extract ventilation rate (e.g. boost)
used (Figures 12 & 13). should be at least the greater of step 1 and step 2. Note that the
Ducting joints must be sealed with silicone type sealant and shall be maximum individual room extract rate should be at least those
given in ADF 2010 - Extract Ventilation Rates table.
adequately and reliably fixed to the appliance.
•The minimum air supply rate should be at least the whole building
3.7 Ventilation Flow Rates ventilation rate found in step 1.
ADF 2010 - Extract Ventilation Rates For Scotland refer to BRE Digest 398.
Room Minimum High rate Minimum Low Rate For further information refer to “Domestic Ventilation Compliance
Guide” www.planningportal.gov.uk/buildingregulations/approved
Kitchen 13 l/s documents/partl/compliance.
Total extract rate
Utility Room 8 l/s should be at least
Bathroom 8 l/s the whole dwelling
ventilation rate given
Sanitary 6 l/s in table 2.
Accommodation
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 31. 08. 22. Document Number 671861
4
Installation Manual MRXBOXAB-ECO3-AE(OH)SW & MRXBOXAB-ECO5-AE(OH)(CV/SC/SW)
3.9 Dimensions
11 Unit Dimensions
Ø150.0 = =
55
7 25
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 31. 08. 22. Document Number 671861
5
Installation Manual MRXBOXAB-ECO3-AE(OH)SW & MRXBOXAB-ECO5-AE(OH)(CV/SC/SW)
Nuaire wall
mounted unit.
MVHR-DRAIN
Condensate drain, uninsulated
drain pipe with min 5o fall running to SVP.
*Insulated
Exhaust air from extract duct.
kitchen/bathroom to
outside via air brick.
Top of ceiling void.
Minimum distance as specified
in building regulations.
Air supply
to bedrooms
Air supply via Air Valve
Extract in ceilings.
to lounge
Intake air air from
via Air Valve
from outside kitchen/
in ceilings.
via air brick. bathroom
via Air Valve
All duct between MVHR in ceilings.
unit and atmosphere to
*Insulated
be insulated*.
supply duct.
Nuaire wall
mounted unit.
MVHR-DRAIN
Condensate drain, uninsulated
drain pipe with min 5o fall running to SVP.
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 31. 08. 22. Document Number 671861
6
Installation Manual MRXBOXAB-ECO3-AE(OH)SW & MRXBOXAB-ECO5-AE(OH)(CV/SC/SW)
4.0 ELECTRICAL INSTALLATION 14 PCB Details
For good EMC engineering practice, any sensor cables or switched
live cables should not be placed within 50mm of other cables or on
EXTRA
EXTRA FANF
CTCT
Kitchen Switch
Red
Black
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 31. 08. 22. Document Number 671861
7
Installation Manual MRXBOXAB-ECO3-AE(OH)SW & MRXBOXAB-ECO5-AE(OH)(CV/SC/SW)
5.0 COMMISSIONING 5.2 Status Indication
The filters fitted inside the unit are protected with a plastic film. The status of the unit is indicated by a series of LED’s on the front cover.
The variants are listed below.
Prior to commissioning remove the covers (Figure 20), take off the
film and replace. The display on the unit control panel will not indicate when a
higher speed setting has been triggered by an external source, such
1. For the required air flow rates please refer to the design specification as an ES-PIR2 etc.
for the property, follow 2.4, or refer to building regulations ADF
2010. 19 Unit Control On Front Panel (Standard Configuration Only)
2. The unit is supplied with independent control for both normal and Speed 1
boost airflows (Figure 18).
Speed 2
3. Correct commissioning is essential to ensure the ventilation air flow
rates are met. It also ensures the unit is not over ventilating and Speed 3
causing excessive power consumption.
Supply Fan Fault
4. Commissioning should be carried out in accordance with building
regulations document “Domestic ventilation compliance guide”. Extract Fan Fault
www.planningportal.gov.uk/building regulations/approved
documents/partf/associated. A calibrated moving vane Frost Protection
anemometer and hood will be required to carry out commissioning. Filter Change
5. Adjustment valves should be locked in place to prevent further
adjustment. HX Bypass
(AB units only)
6. Once commissioned the home owner / tenant should be informed
that the unit should not be adjusted as it will have a detrimental
effect on the indoor air quality and could result in condensation and 5.3 Integral Automatic HX Bypass
mould growth. The clear panel covering the control has an adhesive Intake and extract temperatures are monitored at the point the
panel which should be exposed and sealed post commissioning to airflows enter the unit, if the range falls within the set parameters the
prevent tampering. bypass damper is opened automatically to target an indoor comfort
temperature all year round.
7. Speed 1 is limited to never exceed speed 2, when commissioning
speed 2 should always be set first. The extract temperature is an average from all wet rooms. If this
exceeds 25°C the unit may go into bypass depending on outside
18 Unit Control On Front Panel (Standard Configuration Only) temperatures.
5.4 Summer / Winter Switch
When the switch position is set to Summer the integral automatic
summer bypass is fully operational, in the alternative Winter position
the HX bypass is disabled to ensure the unit is constantly in heat
recovery mode.
5.5 Speed 3 Operation (SW Units Only)
Speed 3 will be non-operational if the intake temperature is greater
than the extract temperature.
5.6 Frost Protection
Post commissioning remove
Ventilation Controls adhesive backing and seal
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 31. 08. 22. Document Number 671861
8
Installation Manual MRXBOXAB-ECO3-AE(OH)SW & MRXBOXAB-ECO5-AE(OH)(CV/SC/SW)
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 31. 08. 22. Document Number 671861
9
Installation Manual MRXBOXAB-ECO3-AE(OH)SW & MRXBOXAB-ECO5-AE(OH)(CV/SC/SW)
NOTES
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 31. 08. 22. Document Number 671861
10
Installation Manual MRXBOXAB-ECO3-AE(OH)SW & MRXBOXAB-ECO5-AE(OH)(CV/SC/SW)
NOTES