GEPD-PHENOLIC CORE TOILET COMPARTMENTS

SECTION 10 21 13.17

PHENOLIC CORE TOILET COMPARTMENTS

PART 1 - GENERAL

1.1 SUMMARY
A. Section Includes:
1. Phenolic core compartment partitions for following applications:
a. Toilet enclosures.
b. Privacy screens.
c. Urinal screens.
B. Related Requirements:
1. Division 03 Section "Cast in Place Concrete" for compartment anchorage to concrete
substrates.
2. Division 04 Section "Unit Masonry" for compartment anchorage to masonry substrates.
3. Division 05 Section "Metal Fabrications" for miscellaneous structural and support metal
components required to secure compartments.
4. Division 06 Section "Rough Carpentry" for compartment anchorage to frame walls.

1.2 REFERENCES
A. ASTM International (ASTM):
1. ASTM A 240 - Standard Specification for Chromium and Chromium-Nickel Stainless Steel
Plate, Sheet, and Strip for Pressure Vessels and for General Applications.
2. ASTM A 666 - Standard Specification for Annealed or Cold-Worked Austenitic Stainless
Steel Sheet, Strip, Plate, and Flat Bar.
3. ASTM A 743/A 743M - Standard Specification for Castings, Iron-Chromium, Iron-
Chromium-Nickel, Corrosion Resistant, for General Application.
4. ASTM B 86 - Standard Specification for Zinc and Zinc-Aluminum (ZA) Alloy Foundry and
Die Castings.
5. ASTM B 221 - Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire,
Profiles, and Tubes.
6. ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building
Materials.
B. International Code Council (ICC)/American National Standards Institute (ANSI):
1. ICC/ANSI A117.1 - Accessible and Usable Buildings and Facilities, as applicable to toilet
compartments designated as accessible.
C. United States Department of Justice:
1. ADA - Americans with Disabilities Act, Excerpt from 28 CFR Part 36 - ADA Standards for
Accessible Design.
D. GREENGUARD Environmental Institute (GREENGUARD):
1. GREENGUARD certified low emitting products.

1.3 ACTION SUBMITTALS


A. Product Data: Manufacturer's data sheets for each type of product indicated. Include
fabrication details, description of materials and finishes.
1. Product Test Reports: When requested by Architect, submit documentation by qualified
independent testing agency indicating compliance of products with requirements.

Grifols Egypt For Plasma Derivatives 10 21 13.17 Page 1 of 6


GEPD-PHENOLIC CORE TOILET COMPARTMENTS

B. Shop Drawings: Include overall product dimensions, floor plan, elevations, sections, details,
and attachments to other work. Include choice of options with details.
C. Samples for Selection: Furnish samples of manufacturer's full range of colors for initial
selection.
D. Samples for Verification: Furnish physical sample of material in selected color.
1. Size: 2 by 2 inch (52 by 52 mm) minimum, in type of finish specified.
E. LEED Submittals:
1. Product Data for Credit MR 4: For products having recycled content, documentation
indicating percentages by weight of postconsumer and preconsumer recycled content.
Include breakout costs for each product with recycled content.
2. Laboratory Test Reports for Credit IEQ 4: For adhesives, documentation indicating that
products comply with the testing and product requirements of the California Department
of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from
Various Sources Using Small-Scale Environmental Chambers."

1.4 INFORMATIONAL SUBMITTALS


A. Warranty: Sample of special warranty.

1.5 CLOSEOUT SUBMITTALS


A. Maintenance and cleaning instructions.

1.6 QUALITY ASSURANCE


A. Manufacturer Qualifications: Approved manufacturer listed in this section, with minimum [5]
years experience in the manufacture of toilet compartments.
B. Manufacturer Qualifications: Approved manufacturer listed in this section, with minimum [5]
years experience in the manufacture of toilet compartments. Manufacturers seeking approval
must submit the following in accordance with Instructions to Bidders and Division 01
requirements:
1. Product data, including test data from qualified independent testing agency indicating
compliance with requirements.
2. Samples of each component of product specified.
3. List of successful installations of similar products available for evaluation by Architect.
C. Installers Qualifications: Experienced Installer regularly engaged in installation of toilet
compartments for minimum 3 years.
D. Source Limitations: Obtain toilet compartment components and accessories from single
manufacturer.
E. Accessibility Requirements: Comply with requirements of ICC/ANSI 117.1, and with
requirements of authorities having jurisdiction.
F. Surface-Burning Characteristics: As determined by testing identical products according to ASTM
E 84 by qualified testing agency. Identify products with appropriate markings of applicable
testing agency.
1. Flame-Spread Index: 30.
2. Smoke-Developed Index: 110.
G. Indoor Environmental Quality Certification: Provide certificate indicated that products have
been certified under the following programs, or a comparable certification acceptable to Owner:
1. GREENGUARD Indoor Air Quality Certified.
2. GREENGUARD Certified for Children and Schools.

Grifols Egypt For Plasma Derivatives 10 21 13.17 Page 2 of 6


GEPD-PHENOLIC CORE TOILET COMPARTMENTS

1.7 DELIVERY, STORAGE, AND HANDLING


A. Do not deliver toilet compartments to site until building is enclosed and HVAC systems are in
operation.
1. Deliver toilet compartments in manufacturer's original packaging.
2. Store laying flat.

1.8 WARRANTY
A. Special Manufacturer’s Warranty: Provide manufacturer's standard form in which manufacturer
agrees to repair or replace products that fail in materials or workmanship during the following
period after substantial completion:
1. Phenolic Core Toilet Partitions: Against delamination: 3 years.

PART 2 - PRODUCTS

2.1 MANUFACTURERS
A. Basis-of-Design Manufacturer: Subject to compliance with requirements.

2.2 MATERIALS
A. Phenolic Core: Compressed cellulose impregnated with phenolic resins. Provide smooth
material, without creases or ripples.
B. Zinc Aluminum Magnesium and Copper Alloy (Zamac): ASTM B 86.
C. Stainless Steel Sheet: ASTM A 240 or A 666, 300 series.
D. Stainless Steel Castings: ASTM A 743/A 743M.
E. Aluminum: ASTM B 221.

2.3 PHENOLIC CORE TOILET COMPARTMENTS


A. Toilet Compartment Type:
1. Overhead braced.
B. Privacy Screen Type:
1. Floor anchored.
2. Floor and ceiling anchored.
C. Urinal Screen Style:
1. Wall hung with wing bracket:
2. Floor anchored:
3. Wall hung with brackets:
D. Door, Panel, and Pilaster Construction, General: Form edges with 15 degree bevel without
crown molding. Finish edges smooth.
1. Provide exposed surfaces free of pitting, visible seams and fabrication marks, stains,
telegraphing of core material, or other imperfections.
2. Core Material: Manufacturer's standard solid resin core of thickness required to provide
finished thickness for doors, panels and pilasters.
E. Door Construction: 3/4 inch (19 mm) thick.
F. Panel Construction: 1/2 inch (13 mm) thick.
G. Pilaster Construction: 3/4 inch (19 mm) thick.
1. Provide pilaster with mechanically fastened leveling bar reinforcement with zinc-plated
jack bolt for leveling.

Grifols Egypt For Plasma Derivatives 10 21 13.17 Page 3 of 6


GEPD-PHENOLIC CORE TOILET COMPARTMENTS

H. Headrail: Extruded anodized aluminum headrail with anti-grip profile. Provide clamps for
attachment to pilaster and stainless steel brackets to secure to wall.
I. Shoes: 4 inches (102 mm) high minimum, Type 304 stainless steel with No. 4 satin brushed
finish. Provide concealed retainer clips to attach to pilaster.
J. Urinal-Screen Construction: Matching toilet compartment panel construction
K. Urinal-Screen Post: Manufacturer's standard post design of [material matching the thickness
and construction of pilasters][ or][ 1-3/4-inch- (44-mm-) square, aluminum tube with satin
finish]; with shoe[ and sleeve (cap)] matching that on the pilaster.
L. Brackets (Fittings):
1. Stirrup Type: Ear or U-brackets; [chrome-plated zamac][stainless steel].
2. Full-Height (Continuous) Type: Manufacturer's standard design; [aluminum][stainless
steel].
M. Phenolic Core Finish: Manufacturer's standard impregnated, with [one color][two colors] in
each room.
1. Color: As selected by Architect from manufacturer's full line.

2.4 HARDWARE
A. Hardware, Standard Duty: Manufacturer's standard chrome-plated zamac castings, including
corrosion-resistant, tamper-resistant fasteners:
1. Hinges: Self-closing surface mounted, through bolted, with gravity cams, adjustable to
hold doors open at any angle up to 90 degrees, with emergency access by lifting door.
2. Latch and Keeper: Surface-mounted slide latch with flat rubber-faced combination door
strike and keeper, with provision for emergency access, meeting requirements for
accessibility at accessible compartments.
3. Coat Hook: Combination hook and rubber-tipped stop, sized to prevent door from hitting
compartment-mounted accessories. Provide wall bumper where door abuts wall.
Provide formed L-shaped hook without stop at outswing doors.
4. Door Pull: Standard unit on outside of inswing doors. Provide pulls on both sides of
outswing doors.
B. Hardware, Heavy Duty: Manufacturer's heavy-duty stainless steel castings, including stainless
steel tamper-resistant fasteners:
1. Hinges: Self-closing surface mounted, through bolted, with gravity cams, adjustable to
hold doors open at any angle up to 90 degrees, with emergency access by lifting door.
Mount with stainless steel through-bolts.
2. Latch and Keeper: Surface-mounted slide latch with flat rubber-faced combination door
strike and keeper, with provision for emergency access, meeting requirements for
accessibility at accessible compartments.
3. Coat Hook: Combination hook and rubber-tipped stop, sized to prevent door from hitting
compartment-mounted accessories. Provide wall bumper where door abuts wall.
Provide formed L-shaped hook without stop at outswing doors. Mount with stainless
steel through-bolts.
4. Door Pull: Standard unit on outside of inswing doors. Provide pulls on both sides of
outswing doors.

2.5 FABRICATION
A. Overhead-Braced Units: Provide manufacturer's standard corrosion-resistant supports, leveling
mechanism, and anchors at pilasters to suit floor conditions. Provide shoes at pilasters to
conceal supports and leveling mechanism.

Grifols Egypt For Plasma Derivatives 10 21 13.17 Page 4 of 6


GEPD-PHENOLIC CORE TOILET COMPARTMENTS

B. Floor-Anchored Units: Provide manufacturer's standard corrosion-resistant anchoring


assemblies with leveling adjustment nuts at pilasters for structural connection to floor. Provide
shoes at pilasters to conceal anchorage.
C. Ceiling-Hung Units: Provide manufacturer's standard corrosion-resistant anchoring assemblies
with leveling adjustment nuts at pilasters for connection to structural support above finished
ceiling. Provide assemblies that support pilasters from structure without transmitting load to
finished ceiling. Provide sleeves (caps) at tops of pilasters to conceal anchorage.
D. Floor-and-Ceiling-Anchored Units: Provide manufacturer's standard corrosion-resistant
anchoring assemblies with leveling adjustment at tops and bottoms of pilasters. Provide shoes
and sleeves (caps) at pilasters to conceal anchorage.
E. Urinal-Screen Posts: Provide manufacturer's standard corrosion-resistant anchoring assemblies
with leveling adjustment at[ tops and] bottoms of posts. Provide caps, shoes, and covers at
posts to conceal anchorage.
F. Door Size and Swings: Unless otherwise indicated, provide 26-inch- (660-mm-) wide, in-
swinging doors for standard toilet compartments and 36-inch- (914-mm-) wide, out-swinging
doors with a minimum 32-inch- (813-mm-) wide clear opening for compartments designated as
accessible.

PART 3 - EXECUTION

3.1 EXAMINATION
A. Examine work area to verify that measurements, substrates, supports, and environmental
conditions are in accordance with manufacturer's requirements to allow installation.
1. Proceed with installation once conditions meet manufacturer's requirements.

3.2 INSTALLATION
A. General: Comply with manufacturer's written installation instructions. Install unit’s rigid,
straight, level, and plumb. Secure units in position with manufacturer's recommended
anchoring devices.
B. Install toilet partitions and screens in spaces with operating, temperature-controlled HVAC
systems. Shield partitions and screens from direct sunlight.
C. Clearances: Install with clearances indicated on Drawings. Where clearances are not indicated,
allow maximum 1/2 inch (13 mm) between pilasters and panels, and 1 inch (25 mm) between
panels and walls.
D. Stirrup Brackets: Secure panels to walls and to pilasters with no fewer than [two brackets
attached] [three brackets attached at midpoint and] near top and bottom of panel. Locate wall
brackets so holes for wall anchors occur in masonry or tile joints. Align brackets at pilasters
with brackets at walls.

3.3 ADJUSTING
A. Hardware Adjustment: Adjust and lubricate hardware according to hardware manufacturer's
written instructions for proper operation. Set hinges on in-swinging doors to hold doors open
approximately 15 degrees from closed position when unlatched. Set hinges on out-swinging
doors[ and doors in privacy screens] to return doors to fully closed position.

3.4 FINAL CLEANING


A. Remove packaging and construction debris and legally dispose of off-site.

Grifols Egypt For Plasma Derivatives 10 21 13.17 Page 5 of 6


GEPD-PHENOLIC CORE TOILET COMPARTMENTS

B. Clean partition and screen surfaces with materials and cleansers in accordance with
manufacturer's recommendations.

END OF SECTION