Calculation Notes of Sign Board of Joulze

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 17

Calculation Notes of

SIGN BOARD OF JOULZE

Sn Date Description
1 jun.2018 NEAIL UNIT
2
3
4

:‫المالك‬
KNAUF

:‫االستشاري االنشائي‬
‫البنيان مهندسون استشاريون‬
Table of Content

Title Page

Introduction 1

Design Criteria 1

Structural System 3

Loading Criteria 3

Load Breakdown 4

Load Combinations 5

Structural Material 6

Control of deflection & drift 6

Analysis and Results 7

Check on drift 81

Check of Connections 82

Structural Design Criteria


1. Introduction
This structural Report lists the criteria that will be used for the structural
design of a NEAIL UNIT. It includes; the codes of practice utilized, loading
criteria, and material sections; and gives a brief description of the
proposed structural system to be used.

Design is based on the use of international standards, mainly the egytian


building code. The following paragraphs describe in details the different
design aspects and parameters that will be utilized for designing and
detailing this project.

2. Design Criteria
2.1 Aim of Structural Design
2.1.1 Safety
The main concern of structural design is to design strong structure that
will safely carry the self-weight, and all superimposed dead and live
loads, also the equivalent wind loading through a strong connection to
the supporting beam without exceeding the allowable capacity limit.

2.1.2 Durability
This NEAIL UNIT must be designed to be utilized for many years to come
as possible. Prolonging the life time of steel structure is enhanced by
proper designer of bolted and welded connection to resist cyclic stresses
and by producing good quality welds. Protection against corrosion is
achieved by painting of elements and/or using of galvanized steel.

2.1.3 Facility of Construction


 Produced design of structural systems must be possible to
construct, and based on local construction techniques and
materials and prevailing site conditions.
 Producing design and details should not cause construction
difficulties during erection of form work.
 Construction tolerance and dimensions of members and
connections must be carefully observed and planned to facilitate
erection of steel structural system.
2.1.4 Cost effective and safe design
One of our targets of engineering requirement in this project to design
safe and functional structural, that demand minimum cost for material
and construction by:

 Structural system and required materials.


 Applicable facilities of construction.

2.2 Codes of Practice and Standards


Design will be based on the following codes of practice:

1. Egyptian steel Building code ECP(latest version).


2. Egyptian code of loads (ECP.2002)

3. Structural System
The NEAIL UNIT is supported on steel frames these steel frames will t

4. Loading Criteria
4.1 Dead Load
Self-weight of steel members (taken by sap200).

4.2 Wind Load


Wind density (Q)= 68 Kg/m2

q=0.5*10-3*v2*Ct*Cs

q =0.5*10-3*332*1.25*1*1=0.068 t/m2

K=1

Ce = 0.8(comp.) &0.8(suc.)

Pe=Ce*K*q

wl = 0.8*1*68/1000= 0.054 t/m2

Using reduction factor 0.7 (permeability)

F=0.7x0.054=.037 t/m2

5. Load Combinations
Load cases and combinations were generated according to ECP

D+wl (Eq.2.4.1-1)

D-wl (Eq.2.4.1-2)
4.5 Wind Load
Wind density (Q)= 70 Kg/m2

K = 1.1

Ce = 0.8(comp.) &0.5(suc.)

qz = 0.8*1.1*80/1000*2=0.14 t/m

qz = 0.5*1.1*80/1000*2=0.09 t/m

6. Load Breakdown
5.1 Dead Load
Dead Load from sap2000
Owchequred plate = 50/1000 *1 = 0.05 t/m

Owroof cover = 30/1000 *1 = 0.03 t/m

5.2 Live Load


Live Load =0.3*1= 0.3 t/m

5.3 Wind Load


qz = 0.5*1.1*80/1000*2=0.14 t/m

qz = 0.8*1.1*80/1000*2=0.09 t/m

7. Load Combinations
Load cases and combinations were generated according to ECP

D+F (Eq.2.4.1-1)

D + F+ H + L + T (Eq.2.4.1-2)

D + H + F + (Lr or R) (Eq.2.4.1-3)

D + H + F+ 0.75 (L+T) +.75 (Lr or R) (Eq.2.4.1-4)

D + H + F + (W or 0.7E) (Eq.2.4.1-5)

D + H + F + 0.75 (W or 0.7E) + 0.75L+ 0.75 (Lr or R) (Eq.2.4.1-6)

8. Structural Material
All structural Steel used is st37 with the following specifications:

Minimum yield strength Fy = 2.4 t/cm2

Minimum ultimate strength Fu= 3.6 t/cm2


9. Analysis and Results
 Analysis of Pargola is made by certified software (SAP2000 ver.19)

Nodes:
Element Sections:

Material Properties:

TABLE: Material Properties 03a - Steel Data


Material Fy Fu EffFy EffFu
Tonf/
Text cm2 Tonf/cm2 Tonf/cm2 Tonf/cm2
st37 2.40 3.60 2.40 3.60
Section Properties:
TABLE: Frame Section Properties 01 - General
SectionName Material Shape t3 t2 tf tw Area
Text Text Text m m m m m2
Box 100x100x2 st37 Box/Tube 0.1 0.1 0.002 0.002 0.000784
Box 40x40x2 st37 Box/Tube 0.04 0.04 0.002 0.002 0.000304
Box 60x60x2 st37 Box/Tube 0.06 0.06 0.002 0.002 0.000464
Box 80x40x2 st37 Box/Tube 0.08 0.04 0.002 0.002 0.000464

Primary Load Cases:


TABLE: Load Case Definitions
RunCas
Case Type DesTypeOpt DesignType Self weight e
Text Text Text Text Text Yes/No
DEAD LinStatic Prog Det Dead 1 Yes
MODA LinModa
L l Prog Det Other 0 Yes
w+ LinStatic Prog Det Wind 0 Yes
w- LinStatic Prog Det Wind 0 Yes

Load Combinations:
1 DL
2 DL+W
3 DL-W
Element Loads:
Wind +ve

Wind- ve
Joint Reactions:

Utilization Ratio:
TABLE: Joint Reactions
Joint OutputCase CaseType F1 F2 F3
Text Text Text Tonf Tonf Tonf
17 DL+wind Combination 0.0274 -0.0132 0.197
20 DL+wind Combination 0.0274 0.0132 0.197
23 DL+wind Combination -0.0274 -0.0132 0.1965
26 DL+wind Combination -0.0274 0.0132 0.1965
17 DL Combination 0.0057 -0.0022 0.0635
20 DL Combination 0.0057 0.0022 0.0635
23 DL Combination -0.0057 -0.0022 0.0629
26 DL Combination -0.0057 0.0022 0.0629
17 DL-wind Combination -0.0179 0.0095 -0.0913
20 DL-wind Combination -0.0179 -0.0095 -0.0913
23 DL-wind Combination 0.0179 0.0096 -0.0917
26 DL-wind Combination 0.0179 -0.0096 -0.0917
Straining Actions :
Axial force due to DL+WL

Axial force due to DL-WL


Moment due to DL+WL
Moment due to DL-WL

Design Due Sap


All Element Are Passed For Design Due Sap

Section Required
SectionName Material Shape t3 t2 tf
Text Text Text m m m
Box 100x100x4 st37 Box/Tube 0.1 0.1 0.004
Box 60x60x4 st37 Box/Tube 0.06 0.06 0.004

Sections Required

All Element Are Matched Section Required


Design of footing
1-Straining Actions