Si - 71a Skyair K
Si - 71a Skyair K
Service
Manual
[Applied Models]
lSkyair : Cooling Only
lSkyair : Heat Pump
Si-71A
Split-System
Air Conditioners
Skyair R(Y)K&F Series
Cooling Only
FHC35K FHK35F FHB35F FH35F
50K 45F 45F 45F
60K 60F 60F 60F
FHYC71K 71F FHYB71F 71F
100K 100F 100F
125K 125F 125F
140K FUY71FJ FVY71F FVY71L
FAY71F(A) 100FJ 100F 100L
100F(A) 125FJ 125F 125L
R35G R71K
50G 100K
60G 125K
140K
Heat Pump
FHYC35K FHYK35FJ FHYB35F FHY35F
50K 45FJ 45F 45F
60K 60FJ 60F 60F
71K 71FJ 71F 71F
100K 100F 100F
125K 125F 125F
140K FUY71FJ FVY71F FVY71L
FAY71F 100FJ 100F 100L
100F 125FJ 125F 125L
RY35F RY71K
50G 100K
60G 125K
140K
Table of Contents i
Si-71A
3DUW#6 ([SODQDWLRQ#RI#)LHOG#6HW111111111111111111111111111111111111111111111111111 4:
1. Method of Field Set (Reset after Maintenance Inspection/Repair) .......18
1.1 Explanation.............................................................................................18
1.2 Field Setting ...........................................................................................19
1.3 Initial Setting Contents ...........................................................................21
1.4 Local Setting Mode No. ..........................................................................22
1.5 Detailed Explanation of Setting Modes ..................................................24
1.6 Centralized Group No. Setting ...............................................................29
2. Settings Concerning Maintenance ........................................................30
2.1 Indoor Unit PCB .....................................................................................30
2.2 Outdoor Unit Switches / Setting Jumper ................................................40
3. Existence of DIP Switch, Jumper and BS .............................................42
3.1 Reference Table.....................................................................................42
3.2 Emergency Operation ............................................................................43
3.3 Maintenance Mode Setting.....................................................................44
3DUW#7 ([SODQDWLRQ#RI#)XQFWLRQ#2SHUDWLRQ1111111111111111111111111111111111 78
1. Function Outline ....................................................................................46
1.1 Indoor Unit..............................................................................................46
1.2 Outdoor Unit ...........................................................................................48
2. Operation Flowchart (RY71 - 140K)......................................................49
2.1 Cooling/Program Dry Operation .............................................................49
2.2 Heating ...................................................................................................51
3. Electric Function Parts ..........................................................................53
3.1 Indoor Unit..............................................................................................53
3.2 Outdoor Unit ...........................................................................................56
4. Thermistor Temperature and Resistance Conversion Table ................61
4.1 Table ......................................................................................................61
5. Function Details ....................................................................................62
5.1 Indoor Unit..............................................................................................62
5.2 Outdoor Unit ...........................................................................................65
ii Table of Contents
Si-71A
iv Table of Contents
Si-71A
,QGH[ 111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111 L
'UDZLQJV#)#)ORZ#&KDUWV 1111111111111111111111111111111111111111111111111111111111111111 Y
Table of Contents v
Si-71A
vi Table of Contents
Si-71A Introduction
1. Introduction
1.1 Safety Cautions
Cautions and „ Be sure to read the following safety cautions before conducting repair work.
Warnings „ The caution items are classified into “ Warning” and “ Caution”. The “ Warning” items are
especially important since they can lead to death or serious injury if they are not followed closely. The
“ Caution” items can also lead to serious accidents under some conditions if they are not followed.
Therefore, be sure to observe all the safety caution items described below.
„ About the pictograms
This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown inside or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown inside or near the symbol.
„ After the repair work is complete, be sure to conduct a test operation to ensure that the equipment
operates normally, and explain the cautions for operating the product to the customer
1.1.1 Caution in Repair
Warning
Be sure to disconnect the power cable plug from the plug socket before disassembling
the equipment for a repair.
Working on the equipment that is connected to a power supply can cause an electrical
shook.
If it is necessary to supply power to the equipment to conduct the repair or inspecting the
circuits, do not touch any electrically charged sections of the equipment.
If the refrigerant gas discharges during the repair work, do not touch the discharging
refrigerant gas.
The refrigerant gas can cause frostbite.
When disconnecting the suction or discharge pipe of the compressor at the welded
section, release the refrigerant gas completely at a well-ventilated place first.
If there is a gas remaining inside the compressor, the refrigerant gas or refrigerating
machine oil discharges when the pipe is disconnected, and it can cause injury.
If the refrigerant gas leaks during the repair work, ventilate the area. The refrigerant gas
can generate toxic gases when it contacts flames.
The step-up capacitor supplies high-voltage electricity to the electrical components of the
outdoor unit.
Be sure to discharge the capacitor completely before conducting repair work.
A charged capacitor can cause an electrical shock.
Do not start or stop the air conditioner operation by plugging or unplugging the power
cable plug.
Plugging or unplugging the power cable plug to operate the equipment can cause an
electrical shock or fire.
vii
Introduction Si-71A
Caution
Do not repair the electrical components with wet hands.
Working on the equipment with wet hands can cause an electrical shock.
Be sure to provide the grounding when repairing the equipment in a humid or wet place,
to avoid electrical shocks.
Be sure to turn off the power switch and unplug the power cable when cleaning the
equipment.
The internal fan rotates at a high speed, and cause injury.
Be sure to check that the refrigerating cycle section has cooled down sufficiently before
conducting repair work.
Working on the unit when the refrigerating cycle section is hot can cause burns.
Use the welder in a well-ventilated place.
Using the welder in an enclosed room can cause oxygen deficiency.
viii
Si-71A Introduction
Warning
When connecting the cable between the indoor and outdoor units, make sure that the
terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section can cause an
electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.
Damaged or modified power cable can cause an electrical shock or fire.
Placing heavy items on the power cable, and heating or pulling the power cable can
damage the cable.
Do not mix air or gas other than the specified refrigerant (R22) in the refrigerant system.
If air enters the refrigerating system, an excessively high pressure results, causing
equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leak and repair it before charging the
refrigerant. After charging refrigerant, make sure that there is no refrigerant leak.
If the leak cannot be located and the repair work must be stopped, be sure to perform
pump-down and close the service valve, to prevent the refrigerant gas from leaking into
the room. The refrigerant gas itself is harmless, but it can generate toxic gases when it
contacts flames, such as fan and other heaters, stoves and ranges.
When replacing the coin battery in the remote controller, be sure to disposed of the old
battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.
Caution
Installation of a leakage breaker is necessary in some cases depending on the conditions
of the installation site, to prevent electrical shocks.
Do not install the equipment in a place where there is a possibility of combustible gas
leaks.
If a combustible gas leaks and remains around the unit, it can cause a fire.
Be sure to install the packing and seal on the installation frame properly. For integral units only
If the packing and seal are not installed properly, water can enter the room and wet the
furniture and floor.
If the power cable and lead wires have scratches or deteriorated, be sure to replace
them.
Damaged cable and wires can cause an electrical shock, excessive heat generation or
fire.
Do not use a joined power cable or extension cable, or share the same power outlet with
other electrical appliances, since it can cause an electrical shock, excessive heat
generation or fire.
Caution
Check to see if the parts and wires are mounted and connected properly, and if the
connections at the soldered or crimped terminals are secure.
Improper installation and connections can cause excessive heat generation, fire or an
electrical shock.
ix
Introduction Si-71A
Caution
If the installation platform or frame has corroded, replace it.
Corroded installation platform or frame can cause the unit to fall, resulting in injury.
Check the grounding, and repair it if the equipment is not properly grounded.
Improper grounding can cause an electrical shock.
Be sure to measure the unsulation resistance after the repair, and make sure that the
resistance is 1 Mohm or higher.
Faulty insulation can cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage can cause the water to enter the room and wet the furniture and floor.
Caution A “caution” is used when there is danger that the reader, through
incorrect manipulation, may damage equipment, loose data, get an
Caution unexpected result or has to restart (part of) a procedure.
Warning
Reference A “reference” guides the reader to other places in this binder or in this
manual, where he/she will find additional information on a specific topic.
x
Si-71A
3DUW#4
,PSURYHG#3RLQWV#DQG
)XQFWLRQV
1. 1999 New Models Functions...................................................................2
1.1 Cooling Only and Heat Pump...................................................................2
2. Present Model’s Functions......................................................................4
2.1 Cooling Only and Heat Pump...................................................................4
Cooling Only
Items Improved Points and Functions Ceiling Suspended Floor Standing Wall Mounted
Cassette type Note 1
FUY71~125FJV1 FVY71~125LVE FAY71, 100FAVE
Model Type Indoor Units New New New
Outdoor Units Present Present Present
Main Improvement Appearance Improved O O O
(Indoor Unit)
Reduction of Dimensions or Weight O O O
Reduction of Operation sound O O O
For Comfortable Auto Restart { { {
Air Conditioning
Fan Operation Mode { { {
LCD Remote Controller (Option) { { {
(LCD = Liquid Crystal Display)
Auto Swing Function { { {
Ceiling Soiling Prevention — — —
Program Dry { { {
High Fan Speed Mode — — {
High Ceiling Application { — —
Low Ambient Temperature Kit (Option) { { {
Timer Selector { { {
For Easy Drain Pump Kit { — —
Construction and
Maintenance Urtra Long Life Filter — — —
Long Life Filter { O —
Mold Resistant Treatment for Filter { { {
Filter Sign { { {
Mold Resistant Drain Pan { — {
Emergency Operation { { {
Self Diagnoses Function { { {
For flexible Control Double Remote Control { { {
Group Control by 1 Remote Controller { { {
Control by External Command { { {
Remote/Centralized Control { { {
O: Improved Points and Functions
{: Holding Functions
—: No Functions
Note: 1. FAY71, 100FAVE are able to connect to R71KVAL and R100KVAL only in K series.
Heat Pump
Items Improved Points and Functions Ceiling Suspended Cassette Type Floor Standing
FUY71~125FJV1 FVY71~125LVE
Model Type Indoor Units New New
Outdoor Units Present Present
Main Improvement Appearance Improved O O
(Indoor Unit)
Reduction of Dimensions or Weight O O
Reduction of Operation Sound O O
For Comfortable Automatic Cool / Heat Change-over { {
Air Conditioning
Auto Restart { {
Fan Operation Mode { {
LCD Remote Controller (Option) { {
Auto Swing Function { {
Draft Preventive Function { —
Ceiling Soiling Prevention — —
Program Dry { {
High Fan Speed Mode — —
High Ceiling Application { —
Hot Start { {
Low Ambient Temperature Kit (Option) { {
Timer Selector { {
For Easy Drain Pump Kit { —
Construction and
Maintenance Urtra Long Life Filter — —
Long Life Filter { O
Mold Resistant Treatment for Filter { {
Filter Sign { {
Mold Resistant Drain Pan { —
Emergency Operation { {
Self Diagnoses Function { {
For Flexible Double Remote Control { {
Control
Group Control by 1 Remote Controller { {
Control by External Command { {
Remote/Centralized Control { {
O: Improved Points and Functions
{: Holiding Functions
—: No Functions
Cooling Only
Items Improved Points and Functions Ceiling Mounted Cassette Ceiling Suspended
Wired type Wireless type
35~60 71~140 35~60 71~140 35~60 71~125
Model Type Indoor Units New New New New Present Present
Outdoor Units New New New New New New
Main Appearance Improved O O O O — —
Improvement
(Indoor Unit) Reduction of Dimensions or Weight O O O O — —
Reduction of Operation Sound O O O O — —
*60 only *71 only *60 only *71 only
For Comfortable Auto Restart { { { { { {
Air Conditioning
Fan Operation Mode { { { { { {
LCD Remote Controller (Option) { { { { { {
(LCD = Liquid Crystal Display)
Auto Swing Function { { { { — —
Ceiling Soiling Prevention { { { { — —
Program Dry { { { { { {
High Fan Speed Mode — — — — — —
High Ceiling Application { { { { { {
Low Ambient Temperature Kit (Option) — { — { — {
Timer Selector { { { { { {
For Easy Drain Pump Kit { { { { — —
Construction and
Maintenance Urtra Long Life Filter O O O O — —
Long Life Filter { { { { { {
Mold Resistant Treatment for Filter { { { { { {
Filter Sign { { { { { {
Mold Resistant Drain Pan { { { { { {
Emergency Operation { { { { { {
Self Diagnoses Function { { { { { {
For flexible Double Remote Control { { { { { {
Control
Group Control by 1 Remote Controller { { { { { {
Cotnrol by External Command { { — — { {
Remote/Centralized Control { { — — { {
O: Improved Points and Functions
{: Holding Functions
—: No Functions
Items Improved Points and Functions Ceiling Mounted Built-in Ceiling Mounted Wall Floor
Cassette Corner Mounted Standing
35~60 71~125 35~60 71 71, 100 71~125
Model type Indoor Units Present Present Present Present Present Present
Outdoor Units New New New New New New
Main Appearance Improved — — — — — —
Improvement
(Indoor Unit) Reduction of Dimensions or Weight — — — — — —
Reduction of Operation Sound — — — — — —
For Comfortable Auto Restart { { { { { {
Air Conditioning
Fan Operation Mode { { { { { {
LCD Remote Controller (Option) { { { { { {
(LCD = Liquid Crystal Display)
Auto Swing Function — — { { { {
Ceiling Soiling Prevention — — { { — —
Program Dry { { { { { {
High Fan Speed Mode — — — — { —
High Ceiling Application — — { { — —
Low Ambient Temperature Kit (Option) — { — { { {
Timer Selector { { { { { {
For Easy Drain Pump Kit { { { { — —
Construction and
Maintenance Urtra Long Life Filter — — — — — —
Long Life Filter { { { { — —
Mold Resistant Treatment for Filter { { { { { {
Filter Sign { { { { { {
Mold Resistant Drain Pan { { { { { —
Emergency Operation { { { { { {
Self Diagnoses Function { { { { { {
For Flexible Double Remote Control { { { { { {
Control
Group Control by 1 Remote Controller { { { { { {
Cotnrol by External Command { { { { { {
Remote/Centralized Control { { { { { {
O: Improved Points and Functions
{: Holding Functions
—: No Functions
Heat Pump
Items Improved Points and Functions Ceiling Mounted Cassette Ceiling Suspended
Wired Type Wireless Type
35~60 71~140 35~60 71~140 35~60 71~125
Model Type Indoor Units New New New New Present Present
Outdoor Units New New New New New New
Main Appearance Improved O O O O { {
Improvement
(Indoor Unit) Reduction of Dimensions or Weight O O O O { {
Reduction of Operation Sound O O O O — —
*60 only *71 only *60 only *71 only
For Comfortable Automatic Cool / Heat Change-over { { { { { {
Air Conditioning
Auto Restart { { { { { {
Fan Operation Mode { { { { { {
LCD Remote Controller (Option) { { { { { {
Auto Swing Function { { { { { {
Draft Preventive Function { { { { { {
Ceiling Soiling Prevention { { { { — —
Program Dry { { { { { {
High Fan Speed Mode — — — — — —
High Ceiling Application { { { { { {
Hot Start { { { { { {
Low Ambient Temperature Kit { { { { { {
Timer Selector { { { { { {
For Easy Drain Pump Kit { { { { — —
Construction and
Maintenance Urtra Long Life Filter O O O O — —
Long Life Filter { { { { { {
Mold Resistant Treatment for Filter { { { { { {
Filter Sign { { { { { {
Mold Resistant Drain Pan { { { { { {
Emergency Operation { { { { { {
Self Diagnoses Function { { { { { {
For Flexible Double Remote Control { { { { { {
Control
Group Control by 1 Remote Controller { { { { { {
Cotnrol by External Command { { — — { {
Remote/Centralized Control { { — — { {
O: Improved Points and Functions
{: Holiding Functions
—: No Functions
Items Improved Points and Functions Ceiling Mounted Built-in Ceiling Mounted Wall Floor
Cassette Corner Mounted Standing
35~60 71~125 35~60 71 “71, 100” 71~125
Model Type Indoor Units Present Present Present Present Present Present
Outdoor Units New New New New New New
Main Appearance Improved { { { { { {
Improvement
(Indoor Unit) Reduction of Dimensions or Weight { { { { { {
Reduction of Operation Sound { { { { { {
For Comfortable Automatic Cool / Heat Change-over { { { { { {
Air Conditioning
Auto Restart { { { { { {
Fan Operation Mode { { { { { {
LCD Remote Controller (Option) { { { { { {
Auto Swing Function — — { { { {
Draft Preventive Function — — { { { —
Ceiling Soiling Prevention — — { { — —
Program Dry { { { { { {
High Fan Speed Mode — { — — { —
High Ceiling Application — — { { — —
Hot Start { { { { { {
Low Ambient Temperature Kit { { { { { {
Timer Selector { { { { { {
For Easy Drain Pump Kit { { { { — —
Construction and
Maintenance Urtra Long Life Filter — — — — — —
Long Life Filter { { { { — —
Mold Resistant Treatment for Filter { { { { { {
Filter Sign { { { { { {
Mold Resistant Drain Pan { { { { { —
Emergency Operation { { { { { {
Self Diagnoses Function { { { { { {
For flexible Double Remote Control { { { { { {
Control
Group Control by 1 Remote Controller { { { { { {
Cotnrol by External Command { { { { { {
Remote/Centralized Control { { { { { {
O: Improved Points and Functions
{: Holiding Functions
—: No Functions
3DUW#5
5HPRWH#&RQWUROOHU
2SHUDWLRQ
1. Wired Remote Controller.......................................................................10
1.1 Wired Remote Controller........................................................................10
2. Wireless Remote Controller ..................................................................12
2.1 Wireless Remote Controller ...................................................................12
3. Wireless Remote Controller ..................................................................14
3.1 Wireless Remote Controller ...................................................................14
Fig.3
BRC1B61
Remote Controller
Fig.4
BRC1B62
Remote Comtroller
Fig1,2
Fig1,2
FHYC-K FAY-F
Part 3
Explanation of Field Set
1. Method of Field Set
(Reset after Maintenance Inspection/Repair) .....................................18
1.1 Explanation.............................................................................................18
1.2 Field Setting ...........................................................................................19
1.3 Initial Setting Contents ...........................................................................21
1.4 Local Setting Mode No. ..........................................................................22
1.5 Detailed Explanation of Setting Modes ..................................................24
1.6 Centralized Group No. Setting ...............................................................29
2. Settings Concerning Maintenance ........................................................30
2.1 Indoor Unit PCB .....................................................................................30
2.2 Outdoor Unit Switches / Setting Jumper ................................................40
3. Existence of DIP Switch, Jumper and BS .............................................42
3.1 Reference Table.....................................................................................42
3.2 Emergency Operation ............................................................................43
3.3 Maintenance Mode Setting.....................................................................44
Notes: (Field setting must be made from the remote controller in accordance with the installation conditions.)
„ Setting can be made by changing the “Mode number”, “FIRST CODE NO.”, and “SECOND CODE NO.”.
„ Refer to the following procedures for Field setting.
Procedure 1. Press the “ “ button for 4 seconds or more on nomal mode to change to “FIELD SETTING
MODE”
2. Press the “ “ button and choose the desired “MODE NO.”.
3. If the unit is under group control, it is unified set (factory set).However, if setting on each indoor unit
bases or confirming after the setting, use the MODE NO. in the ( ) for the setting.
Under group control, press the “ “ button and select the indoor unit no. that you are setting to set
on each indoor unit bases.
(Unnecessary at unified setting of group control and the UNIT NO. is not displayed)
4. Press the “ “ upper part of the button and select the “FIRST CODE NO.”.
5. Press the “ “ lower part of the button and select the “SECOND CODE NO.”.
6. Press the “ “ button once to FIX the change of the setting.
7. Press the “ “ button for about one second and return to the “NORMAL MODE”
Note: If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be changed.
Refer to the instruction manual (optional hand book) for each optional accessory.
Procedure 1. When in the normal mode, push the “ “ button for a minimum of four seconds, and the
FIELD SET MODE is entered.
2. Select the desired MODE NO. with the “ “ button.
3. Push the “ “ button and select the FIRST CODE NO.
4. Push the “ “ button and select the SECOND CODE NO.
5. Push the “ “ button and the present settings are SET.
6. Push the “ “ button to return to the NORMAL MODE.
Note: A heat pump type indoor unit is used for cooling only twin system in case of using ceiling mounted cassette
and ceiling suspended types.
Example To set the filter sign time to “filter contamination - heavy” for all units in a group:
Set mode No. to “10,” setting switch No. to “0,” and setting position No. to “02.”
Table
Mode Setting Setting Description Setting Position No. *Note 2
No. Switch
Note 1 No. 01 02 03
10(20) 0 Filter contamination - heavy / light Urtra-Long- Light Approx. Heavy Approx. —
(Setting of operating hours for filter Life Type 10,000 5,000
sign indication) (Change setting hours hours
when reducing filter sign indication
time to half due to quick soiling of Long-Life Approx. Approx.
filter) Type 2,500 1,250
hours hours
Standard Approx. Approx.
Type 200 hours 100 hours
1 Long-life filter type (Setting of filter sign indication Long-Life Filter Urtra-Long-Life Filter Setting Description
time) (1) Urtra-Long-Life Filter
(Change setting when Urtra-long-life filter is (2)
installed)
3 Estimation of filter operating hour ON OFF —
(Change setting when filter sign indication is not
used)
11(21) 0 No. of Sky Air indoor units connected for Pair Twin Triple
simultaneous ON-OFF multi system
(Change setting when simultaneous operation
multi system is used) *Note 3
1 Simultaneous operation multi-unit individual Unified Individual —
setting
2 Indoor unit fan OFF when cooling/heating is OFF — Fan OFF —
12(22) 3 Change to set fan speed when heater thermostat Fan Speed LL Set Fan Speed —
is OFF *Note 5
5 Automatic restart after power outage reset OFF ON —
*Note 6
13(23) 0 High Ceiling-mounted built-in multi-flow N H S
Ceiling cassette type, Ceiling suspended
cassette type
Ceiling-suspended type, wall-mounted 2.7 m or Lower 2.7~3.5 m —
typ
Fan speed increase (wall-mounted type) Standard Slight Increase Normal Increase
1 Air flow direction selection (Change setting when F T W
blocking kit is installed) *Note 4
3 Air flow direction adjustment (Change setting Installed Not Installed —
when decorative air outlet panel is installed)
4 Setting of air flow direction adjustment range Upward Standard Downward
5 On-site fan speed change by air outlet (When Standard Option 1 Option 2
using phase control)
6 External static pressure setting (To be set Standard (Standard) High Static Pressure Low Static Pressure
according to connected duct resistance) (High (High Ceiling Setting)
ceiling setting in the case of FHYK)
Notes: 1. Setting is made in all units in a group. To set for individual indoor units or to check the setting, use the
mode Nos. (with “2” in upper digit) in parentheses ( ).
2. The setting position No. is set to “01” at the factory, except for the following cases in which “02” is set.
„ Setting of air flow direction adjustment range
„ Automatic restart after power outage.
„ Remote control thermostat
„ Filter sign indication (only for ceiling-mounted duct type)
3. When installing Sky Air simultaneous operation multi-unit, set to either “twin” or “triple.”
Only when the factory setting is changed, it is necessary to make a setting using a remote controller.
4. For further details, see the installation instruction.
5. Since drafts may result, carefully select the installation location.
6. When power returns, units resume the settings made before the power outage.
Caution When “auto restart after power outage reset” is set, be sure to turn off air conditioners, then cut off the
power supply before conducting maintenance, inspection and other work. If the power supply is cut off with
the power switch left ON, air conditioners will automatically start operating when the power supply is turned
on.
7. Do not set any items other than those listed in the above table.
8. Functions that indoor units are not equipped with will not be displayed.
9. When returning to normal mode, “88” may be displayed on the LCD section of the remote controller due
to initialization operation.
Setting Table
Mode No. First Code No. Second Code No. Setting
11(21) 0 01 Pair (1)
02 Twin (2)
03 Triple (3) Note
Example
Note: 1. If set incorrectly, a connection mistake malfunction (remote controller display UA) will result. (3 minutes
after turning the power ON is required for detection.)
2. If different models are used in combination, designate the unit that is equipped with the most functions
as the main unit.
Setting Table
Mode No. First Code No. Second Code No. Setting
13 (23) 1 01 F : 4-direction air flow
02 T : 3-direction air flow
03 W : 2-direction air flow
Explanation If several wireless remote controller units are used together in the same room (including the case where
both group control and individual remote controller control are used together), be sure to set the addresses
for the receiver and wireless remote controller. (For group control, see the attached installation manual for
the indoor unit.) If using together with a wired remote controller, you have to change the main/sub setting or
the receiver.
Setting The Through the small opening on the back of the receiver, set the wireless address switch (SS2) on the printed
Receiver circuit board according to the table below.
Unit No. No.1 No.2 No.3
Wireless Address Switch
(SS2)
When using both a wired and a wireless remote controller for 1 indoor unit, the wired controller should be
set to MAIN. Therefore, set the MAIN/SUB switch (SS1) of the receiver to SUB.
MAIN SUB
MAIN/SUB Switch (SS1)
After completing setting, seal off the opening of the address switch and the MAIN/SUB switch with the
attached sealing pad.
Address can be set from 1 to 6, but set it to 1 ~ 3 and to same address as the receiver. (The receiver
does not work with address 4 ~ 6.)
4. Press the “ “ button to enter the setting.
5. Hold down the “ “ button for at least 1 second to quit the FIELD SET MODE and return to
the normal display.
Multiple Settings When the indoor is being operating by outside control (central remote controller, etc.), it sometimes does
A/b not respond to ON/OFF and temperature setting commands from this remote controller. Check what setting
the customer wants and make the multiple setting as shown below.
Remote Controller Indoor Unit
Multiple Setting Remote Controller Display Controlled by other Air For other than on Left
Conditioners and Devices
A: Standard All items Displayed. Commands other than ON/
OFF and Temperature
Setting Accepted. (1 LONG
BEEP or 3 SHORT BEEPS
Emitted)
b: Multi System Operations Remain All Commands Accepted (2 SHORT BEEPS)
Displayed Shortly after
Execution.
After Setting Stick the Unit No. label at decoration panel air discharge outlet as well as on the back of the wireless
remote controller.
PRECAUTIONS
Set the Unit No. of the receiver and the wireless remote controller to be equal. If the setting differs, the
signal from the remote controller cannot be transmitted.
1. Do not use any settings not listed in the table.
2. For group control with a wireless remote controller, initial settings for all the indoor units of the group are
equal. (For group control, refer to the installation manual attached to the indoor unit for group control.)
Setting Table
Mode No. First Code No. Second Code No. Setting
11(21) 2 01 —
02 Fan OFF
Setting Table
Mode No. Setting Switch No. Setting Position No. Setting
10 (20) 1 01 Long-Life Filter
02 Urtra-Long-Life Filter (1)
03 Urtra-Long-Life Filter (2)
Setting Table
Mode No. First Code No. Second Code No. Setting
12(22) 3 01 LL Fan Speed
02 Set Fan Speed
Procedure 1. Insert a “ - “ screwdriver into the recess between the upper and lower part of remote controller and,
working from the 2 positions, pry off the upper part. (The remote controller PC board is attached to the
upper part of remote controller.)
Insert the screwdriver here and gently work off the upper part of remote controller.
2. Tum the MAIN/SUB CHANGEOVER SWITCH on one of the two remote controller PC boards to “S”.
(Leave the switch of the other remote controller set to “M”.)
Centralized Group 1. If the inspection/test button is pushed for 4 seconds or more when in the normal mode, operation enters
No. Setting by the “field set mode.”
Remote Controller. 2. Using the temperature control buttons, set the mode No. to “00.”
3. Push the inspection/test button to inspect the group No. display.
4. Using the programming time button, set the group No. for each group. (Group No. rises in the order of
1-00, 1-01, ...1-15, 2-00 ...4-15, etc. The unified ON/OFF controller however displays only the range of
group numbers selected by the switch for setting each address.)
5. Push the timer ON/OFF button and enter the selected group No.
6. Push the inspection/test button and return to the normal mode.
∗ If the address has to be set individually for each unit for power consumption counting, etc., set the mode
No. to “30.”
FHC35K~
FHC60KVE, KV1C
FHYC35~
FHYC125KVE, V1C
FHB35~
FHB60FJV1, FV1
FHYB35~FHYB71F
FHK35~
FHK60FJV1, FV1
FHYK35~
FHYK71FJV1, FV1
FAY71, FAY100FVE
FAY71,
FAY100FAVE
FVY-L
FUY71~FUY125FJ
RY100·RY125K
RY140K
Note: Note 1
DIP Switch and BS Detail
PUMP
SS1
ON
1
2
O
F
F
BS1
OFF
(SL042)
Note: Note 2
BS button (Pump down / Forced defrosting)
Pressing the BS button forcibly operates the air conditioner in the cooling mode.
1. To conduct a pump-down operation (sending refrigerant to outdoor unit), press the BS button to forcibly
operate the equipment in the cooling mode, then operate the unit for about 1 minute to stabilize the
system. After stabilizing system, close the liquid pipe stop valve on the outdoor unit, and after the
pressure decreases and the low pressure switch activates, close the gas pipe stop valve.
2. Forced defrost
To activate the defrost operation during the heating operation, press the BS button. This will activate
the forced defrost operation (cooling operation).
When the defrost cancel conditions are met, the equipment automatically switches off the defrost
operation.
Emergency You can operate the system manually by changing the setting of the emergency switch (SS1) on the indoor
Operation of Indoor unit’s PC board from “Normal” to “Emergency.” When switched however the equipment cannot regulate
Units temperature. The table below contains a list by model of actuators for manually operating indoor units in
time of emergency.
Model Fan Drain Raising
FH(Y)C { {
FH(Y) { {
FUY { {
FVY~F, FVY~L { —
FH(Y)B { {
FH(Y)K { {
FAY { {
„ Method of switching in time of emergency
Emergency Turn off the power supply and set the emergency switch to “Heat” for heating or “Cool” for cooling.
Operation of Operation will be started manually when you turn the power back on. (“Heat” cannot be set for a cooling
Outdoor Units only air-conditioner.)
Concerning If a safety device should be actuated during emergency operation, all actuators are turned OFF. If you
Emergency reset after waiting for 3 minutes, operation will start again. Emergency operation cannot be carried out if the
Operation PC board itself is defective.
Note: For emergency operation, be sure to set emergency operation for both the indoor and outdoor units. Do not
attempt to operate the equipment from the remote controller during emergency operation. Emergency
operation is computer-controlled, and therefore cannot be carried out if the microcomputer is not operating
properly.
The table below contains a list of actuators for manually operating the equipment in time of emergency.
Actuator Cooling Heating
Compressor ON ON
4-WAY VALVE OFF ON
Outdoor Unit Fan H Fan Speed H Fan Speed
Electronic Expansion Valve 200 Pulses 200 Pulses
Indoor Unit Fan H Fan Speed H Fan Speed
Drain Pump ON ON
During emergency heating operation, defrosting is carried out for 3 minutes every hour. (4-way valve and
outdoor unit fan are turned OFF.)
Table
Mode No. Function Content and Operation Method Example of Remote Controller Display
41 Sensor Date Select the display sensor with the
Display programming time up-down button
Display sensor
34 Suction
35 Heat exchange
3DUW#7
([SODQDWLRQ#RI
)XQFWLRQ#2SHUDWLRQ
1. Function Outline ....................................................................................46
1.1 Indoor Unit..............................................................................................46
1.2 Outdoor Unit ...........................................................................................48
2. Operation Flowchart (RY71 - 140K)......................................................49
2.1 Cooling/Program Dry Operation .............................................................49
2.2 Heating ...................................................................................................51
3. Electric Function Parts ..........................................................................53
3.1 Indoor Unit..............................................................................................53
3.2 Outdoor Unit ...........................................................................................56
4. Thermistor Temperature and Resistance Conversion Table ................61
4.1 Table ......................................................................................................61
5. Function Details ....................................................................................62
5.1 Indoor Unit..............................................................................................62
5.2 Outdoor Unit ...........................................................................................65
1. Function Outline
1.1 Indoor Unit
Thermostat Control
Monitoring Function
Program Dry
(SF001)
FH(Y)K, FH(Y)B,
FHY~F, FVY~L
(Input) (Output)
Indoor Unit
Fan Operation
Defrosting
(SF002)
All models
(Input) (Output)
Outdoor Unit
*1
PS for High Pressure Protection 4-way Valve Control Motor Operated Valve
*1
Defrosting Start Temperature
Changeover Switch
*1
Forced Defrosting Pump Down Frosting Avoidance Control
Switch
*1
Overload Control
Practice Function
Note: Items indicated by “*1” are not available for cooling only air-conditioners.
Power Switch ON
Initializing of Electronic
Expansion Valve
(See Section 5. 2. 4.)
Is safety NO
device in normal Error Indication A
condition?
YES
B
Thermostat
ON Judgment Thermostat OFF
Thermostat ON
Startup Control
(See Section 5. 2. 11.)
Is discharge YES
thermistor disconnected?
(See Section 5. 2. 7.)
NO Is
cumulative retry total 6? NO
(See Section
5. 2. 5.)
Is thermistor NO Simulated Operation
in normal condition? (See Section 5. 2. 10.) YES
(SF027)
To ∗1 To ∗2
∗1 (Continued) ∗2 (Continued)
NO
NO
Thermostat OFF A B
NO (See Section
5. 2. 2.)
NO
C D
(SF028)
Note: For items indicated with reference section numbers 5.2.1 through 5.2.19, see the explanation of outdoor
unit functions detail on pages 65 through 72.
2.2 Heating
Power Switch ON
Initializing of
Electronic Expasion Valve
(See Section 5. 2. 4.)
Is safety device NO
in normal condition? Error Indication A
YES
B
Thermostat
ON Judgment Thermostat OFF
Thermostat ON
Startup Control
(See Section 5. 2. 16.)
Is discharge
thermistor disconnected? YES
(See Section
5. 2. 7.)
NO Is cumulative
retry total 6? NO
(See Section
5. 2. 5.)
Is thermistor NO Simulated Operation
in normal condition? (See Section 5. 2. 10.) YES
Thermostat OFF
YES Shutdown (See Section
Due to Error 5. 2. 2.)
(SF029)
To ∗1 To ∗2
∗1 (Continued) ∗2 (Continued)
Defrost Control
(See Section 5. 2. 19.) Is cumulative
retry total 6? NO
(See Section
5. 2. 5.)
Optimal discharge pipe
temperature control YES
(See Section 5. 2. 4.) Thermostat OFF
(See Section Error Indication Thermostat OFF
5. 2. 2.) (See Section
5. 2. 2.)
∆Tr=[Indoor unit B
suction temperature] – YES A B
[Remote controller preset
temperature]≤0
Thermostat OFF
NO (See Section
5. 2. 2.)
Operation stop
using remote controller YES
(See Section B
5. 2. 2.)
NO
(SF030)
C D
Note: For items indicated with reference section numbers 5.2.1 through 5.2.19, see the explanation of outdoor
unit functions and operations on pages 65 through 72.
FH(Y)C~KVE, KV1C
Capacity 35 50 60 71 100 125 140 Remarks
Wired Remote Controller BRC1B51·61 (C) (EC9505) Optional
Accessory
Wireless Remote HEAT PUMP USE : BRC7C612W (C) Optional
Controller COOLING ONLY USE : BRC7C613W (C) Accessory
Electronic Control Unit FHYC : EC9743 FHC : EC9744
Fan Motor (Temperature KFP-220-45B D17P90H23
Protector 130°C) 6P 45W 6P 90W
Fan Motor Capacitor 3.5µF 5µF
Swing Flap Motor MP35HCA (3P007482-1)
(with Limit Switch)
Float Switch FS-0211B
Drain Pump PLD-12230DM-1
FH(Y)K~F(J)
Capacity 35 45 60 71 Remarks
Wired Remote Controller BRC1B51·61 (EC9505) Optional
Accessory
Electronic Control Unit FHYK, FHK71:EC9516 FHK35~60:EC9521
Fan Motor (Temperature BP-NRTW BP-NRTW BP-NRTW
Protector 120°C) 4P 20W 4P 25W 4P 45W
Fan Motor Capacitor 2µF 2.5µF
Swing Flap Motor MT8-L [3PA07312-1]
(with Limit Switch)
Float Switch FS-0406C
Drain Pump CJV-0927
FH(Y)B~F
Capacity 35 45 60 71 100 125 Remarks
Wired Remote Controller BRC1B52·62 (EC9505) Optional
Accessory
Electronic Control Unit FHYB:EC9514 FHB:EC9520 EC9515
Fan Motor (Temperature CA- CA- CA- V1:CA- A37P135 A37P225
Protector 152°C) 0513D 0514D 0516D 0515D G20 C20
4P 65W 4P 85W 4P 110W 4P 125W 4P 135W 4P 225W
VAL:CA-
4526D
4P 125W
Fan Motor Capacitor 4µF 5µF 5µF V1:3µF V1:5µF
VAL:5µF VAL:10µF
Float Switch FS-0406D
Drain Pump CJV-0929
FH(Y)~F
Capacity 35 45 60 71 100 125 Remarks
Wired Remote Controller BRC1B51·52·61·62 (EC9505) Optional
Accessory
Electronic Control Unit FHY~FJV1:EC9513 FHY~FVE:EC9543
FH~FJV1/FVE:EC9519 FH~FJV1/FVE:EC9522
Fan Motor (Temperature D09P57A23A D10P/30E23A
Protector 130°C) 4P 57W 4P 130W
Fan Motor Capacitor 2µF 3µF 6µF
Swing Flap Motor FHY~F(J):MTL8-L [3PA07121-1]
Drawing No. given inside brackets[ ].
FAY~F
Capacity 71 100 Remarks
Wired Remote Controller BRC1B51·61 (EC9505) Optional
Accessory
Electronic Control Unit EC9654
Fan Motor 4P 46W 4P 49W
Fan Motor Capacitor 2µF
Swing Flap Motor MT8 [3SB40350-1]
(with Limit Switch)
FAY~FA
Capacity 71 100 Remarks
Wired Remote Controller BRC1B51·61 (EC9505) Optional
Accessory
Electronic Control Unit EC9905
Fan Motor 4P 37W 4P 46W
Fan Motor Capacitor 1.5µF
Swing Flap Motor MT8 [3SB40350-1]
(with Limit Switch)
FVY~F
Capacity 71 100 125 Remarks
Control Panel BRC1B61(EC9505)
Electronic Control Unit EC9517
Fan Motor Upper V1:AP-NOT V1:AP-NOT V1:AP-NOT
(Temperature 6P 13W 6P 27W 6P 27W
Protector VAL:AP-NOT VAL:AP-NOT VAL:AP-NOT
120°C) 6P 13W 6P 27W 6P 27W
Lower V1:AP-NOT V1:AP-NOT V1:AP-NOT
6P 20W 6P 27W 6P 56W
VAL:AP-NOT VAL:AP-NOT VAL:AP-NOT
6P 20W 6P 27W 6P 56W
Fan Motor Upper 2.5µF 4µF 4µF
Capacitor
Lower 3µF 4µF 6µF
Swing Motor MT8-L [3PA07279-1]
Drawing No. given inside brackets[ ].
FVY~L
Capacity 71 100 125 Remarks
Control Panel BRC1B61(EC9505)
Electronic Control Unit FVY:EC98115 FV:EC98114
Fan Motor (Temperature AP-NOT AP-NOT AP-NOT
Protector 130°C) 6P 30W 6P 60W 6P 90W
Fan Motor Capacitor 7µF 8µF
Swing Motor MT8-L [3P027592-1]
Drawing No. given inside brackets[ ].
FUY~FJ
Capacity 71 100 125 Remarks
Wired Remote Controller BRC1B51·61(EC9505) Optional
Accessory
Wireless Remote HEAT PUMP USE : BRC7C528W Optional
Controller COOLING ONLY USE : BRC7C529W Accessory
Electronic Control Unit EC98107
Fan Motor (Temperature D16P45R23 D17P90J23
Protector 130°C) 6P 45W 6P 90W
Fan Motor Capacitor 3.5µF 6µF
Swing Flap Motor MT8-L(Drg. No. 3PA07572-1)
(with Limit Switch)
Float Switch FS-0211B
Drain Pump PJV-0744
RY
RY71KY1 RY71KV1 RY100KY1 RY125KY1
M1C Compressor JT95BC-YE JT95BC-V1 JT125BC-YE JT160BC-YE
J1HC Crank Case Heater 33W
S1PH Pressure Switch for Maintaining ACB-DB82
High Pressure OFF : 30+0-1 (kg/cm²G)
ON : 22±1.5 (kg/cm²G)
S2PH Pressure Switch for Maintaining ACB-CB57 —
High Pressure OFF : 24±1 (kg/cm²G)
ON : 19±1 (kg/cm²G)
S1LP Pressure Switch for Low 20PS-1164-1
Pressure Control OFF : –23±15 (cmHg)
ON : 0.5±0.3 (kg/cm²G)
K1M Magnetic Switch HOE-20F-TRA1 HOE-26F-TRA1 HOE-20F-TRA1
F1C Overcurrent Relay 7.5A 22A 10A 13A
M1F Outdoor Unit Fan (Upper) 70W 90W 95W
M2F Outdoor Unit Fan (Lower) — 65W
Q1L Outdoor Unit Fan Motor Safety OFF : 135±5°C
Q2L Thermostat ON : Below 120°C
C1R Capacitor for MF1 6µF
C2R Capacitor for MF2 — 6µF
A1P Outdoor Unit Control PC Board∗ EC9526 EC9525 EC9530
A2P Outdoor Control PC Board —
(Models for the FJ Type Only)
R1T Thermistor (for Outdoor Air) ST9303
R2T Thermistor (for Heat Exchanger) ST8604A
R3T Thermistor (for Discharge Pipe) ST8606
T1R Transformer TR21H16R2
Y1R 4-way Changeover Valve V26-110B V38-110B VH40100
Y1E Electronic Expansion Valve DKV18D93 (Main Unit) EKV24D34 EKV26D35
(Main Unit)
DKV-MOZS130BO (Coil) EKV-MOZS107BO (Coil)
K1S Starting Relay — CLK-15J02-P15 —
C3R, M1C Capacitor — 46µF+23µF —
C4R
C5R Starting Capacitor — 50µF —
∗ Figures inside parentheses are for E unit (anti-corrosion specifications).
RY140KY1 RY140KTAL
M1C Compressor JT170BC-YE JT170BC
J1HC Crank Case Heater 33W
S1PH Pressure Switch for Maintaining ACB-DB82
High Pressure OFF : 30+0-1 (kg/cm²G)
ON : 22±1.5 (kg/cm²G)
S1LP Pressure Switch for Low 20PS-1164-1
Pressure Control OFF : –23±15 (cmHg)
ON : 0.5±0.3 (kg/cm²G)
K1M Magnetic Switch HOE-20F-TRA1 HOE-35F-TRA1
F1C Overcurrent Relay 15A 28A
M1F Outdoor Unit Fan (Upper) 100W
M2F Outdoor Unit Fan (Lower) 65W
Q1L Outdoor Unit Fan Motor Safety OFF : 135±5°C
Q2L Thermostat ON : Below 120°C
C1R Capacitor for M1F 6µF
C2R Capacitor for M2F 6µF
A1P Outdoor Unit Control PC Board EC9641
A2P Outdoor Control PC Board —
(Models for the FJ Type Only)
R1T Thermistor (for Outdoor Air) ST9303
R2T Thermistor (for Heat Exchanger) ST8604A
R3T Thermistor (for Discharge Pipe) ST8606
T1R Transformer TR21H16R2 TR21M16R2
Y1R 4-way Changeover Valve VH40100
Y1E Electronic Expansion Valve EKV30D36
EKV-MOZS107BO (Coil)
K1S Starting Relay —
C3R, M1C Capacitor —
C4R
C5R Starting Capacitor —
R
R71KY1(E) R71KV1(E) R100KY1(E) R100KV1(E)
M1C Compressor JT90BC-YE JT90BC-V1 JT118BC-YE JT118BC-V1
J1HC Crank Case Heater 33W
S1PH Pressure Switch for Maintaining ACB-DB82
High Pressure OFF : 30+0-1(kg/cm²G)
ON : 22±1.5 (kg/cm²G)
S1LP Pressure Switch for Low 20PS-1164-1
Pressure Control OFF : –23±15 (cmHg)
ON : 0.5±0.3 (kg/cm²G)
K1M Magnetic Switch HOE-20F-TRA1 HOE-26F-TRA1 HOE-20F-TRA1 HOE-26F-TRA1
F1C Overcurrent Relay 7.5A 22A 10A 33A
M1F Outdoor Unit Fan (Upper) 70W 90W
M2F Outdoor Unit Fan (Lower) — 65W
Q1L Outdoor Unit Fan Motor Safety OFF : 135±5°C
Q2L Thermostat ON : Below 120°C
C1R Capacitor for M1F 6µF
C2R Capacitor for M2F — 6µF
A1P Outdoor Unit Control PC Board∗ EC9524 (EC9534) EC9523 (EC9533) EC9528 (EC9538) EC9527 (EC9537)
A2P Outdoor Control PC Board —
(Models for the FJ Type Only)
R1T Thermistor (for Outdoor Air) ST9303
R2T Thermistor (for Heat Exchanger) ST8604A
R3T Thermistor (for Discharge Pipe) ST8606
T1R Transformer TR21H16R2
Y1E Electronic Expansion Valve DKV18D93 (Main unit) EKV24D34 (Main unit) EKV24D34
DKV-MOZS130BO (Coil) EKV-MOZS107B0 (Coil)
K1S Starting Relay — CLK-15J02-P15 — CLK-15J02-P14
C3R, M1C Capacitor — 46µF+23µF — 46µF+23µF
C4R
C5R Starting Capacitor — 50µF — 75µF
∗ Figures inside parentheses are for E unit (anti-corrosion specifications).
R
R71KVAL R100KVAL R125KTAL
M1C Compressor JT85BC-VH JT118-VH JT150BC
J1HC Crank Case Heater 33W
S1PH Pressure Switch for Maintaining ACB-DB82
High Pressure OFF : 30+0-1(kg/cm²G)
ON : 22±1.5 (kg/cm²G)
S1LP Pressure Switch for Low 20PS-1164-1
Pressure Control OFF : –23±15 (cmHg)
ON : 0.5±0.3 (kg/cm²G)
K1M Magnetic Switch HOE-26F-TRA1
F1C Overcurrent Relay 22A 26A 22A
M1F Outdoor Unit Fan (Upper) 75W 85W
M2F Outdoor Unit Fan (Lower) — 80W
Q1L Outdoor Unit Fan Motor Safety OFF : 135±5°C
Q2L Thermostat ON : Below 120°C
C1R Capacitor for M1F 6µF
C2R Capacitor for M2F — 6µF
A1P Outdoor Unit Control PC Board∗ EC9523 EC9527 EC9528
A2P Outdoor Control PC Board —
(Models for the FJ Type Only)
R1T Thermistor (for Outdoor Air) ST9303
R2T Thermistor (for Heat Exchanger) ST8604A ST9604A ST8604A
R3T Thermistor (for Discharge Pipe) ST8606
T1R Transformer TR21H16R2
Y1E Electronic Expansion Valve DKV18D93 (Main Unit) EKV24D34 (Main Unit) EKV26D35
DKV-MOZS130B0 (Coil) EKV-MOZS107B0 (Coil)
K1S Starting Relay CLK-15J02-P15 CLK-15J02-P14 —
C3R, M1C Capacitor 46µF+23µF —
C4R
C5R Starting Capacitor 50µF+50µF 75µF+75µF —
∗ Figures inside parentheses are for E unit (anti-corrosion specifications).
5. Function Details
5.1 Indoor Unit
Thermostat Control Existing cooling/heating preset temperature range has been changed.
Draft Avoidance Draft is circumvented by delaying transfer of the flap to the Po0 (horizontal) position for a certain amount of
Control 1 time when defrosting and in the heating mode with the thermostat OFF.
Draft Avoidance When hot start is canceled or when cold air prevention control is finished, if the fan speed is set to “H,” the
Control 2 fan turns at L speed for a certain amount of time, thus avoiding draft while the flap is moving.
Air Flow Volume The air flow volume of an indoor unit is varied to prevent shutdown due to a rise in the high pressure level.
Shift Control (Air volume up at heating operation)
1. When indoor unit suction air temperature is 25°C or higher
ON condition Tc≥60°C
Reset condition Tc<50°C
Note that the air flow volume is varied for a preset time when the thermostat is ON.
2. When indoor unit suction air temperature is lower than 25°C
ON conditionTc≥60°C
Reset conditionTc<59°C
Freeze Prevention The thermostat turns OFF under the following temperature conditions to prevent freezing of the indoor unit
Control heat exchanger.
„ The motorized valve is controlled to maintain the indoor unit heat exchanger temperature (Te) above
0°C.
„ The outdoor unit fan speed is reduced to prevent freeze prevention control from activating during
cooling operation under low outside air temperature. (For details, see the section on cooling operation
under low outside air temperature.)
Outdoor Unit If the indoor unit is for both a heat pump and cooling only type, this function differentiates whether the
Identification outdoor unit is functioning as a heat pump or cooling only unit, and automatically decides the which
Function operation modes can be set.
Auto-restart If there is a power cut when the unit is operating, it will automatically resume the same operating mode
Function when the power is restored.
Caution When performing maintenance and the power supply is to be shut off, be sure to turn the remote
controller’s ON/OFF switch OFF first.
Shutting the power supply switch off while the ON/OFF switch is still ON is dangerous because the “power
failure automatic reset function” will cause the indoor fan to start turning immediately, or the outdoor unit
fan to automatically start turning three minutes after the power supply is turned back on.
Note: Following functions are for R(Y)71~140K only. Please refer “Split G series” manual for smaller size outdoor
units.
∗ Regarding ∆Tr
In cooling operation
∆Tr = Indoor unit suction air temperature (Tr) - Temperature set by remote controller
In heating operation
∆Tr = Temperature set by remote controller - Tr
Compressor
Shutdown
Operation
Electronic About 10 seconds after turning on the power supply, the electronic expansion valve’s opening is tightened
Expansion 520 pulses to close it all the way.
Valve Initialize
Discharge Pipe The optimal discharge pipe temperature for present operation is calculated according to indoor unit heat
Temperature exchange temperature, outdoor unit heat exchange temperature, and outdoor air temperature, with the
electronic expansion valve being controlled so that the discharge pipe temperature approaches the optimal
discharge pipe temperature.
Optimal discharge pipe temperature - discharge pipe temperature <0°C (superheat operation)
→ Motor operated valve is opened
Optimal discharge pipe temperature - discharge pipe temperature >0°C (wet operation)
→ Motor operated valve is closed.
Wet Operation Cooling : Discharge pipe temperature < outdoor unit heat exchanger temperature +10°C
Protection Control 15 minutes in succession
Heating : Discharge pipe temperature < indoor unit heat exchanger temperature +10°C
15 minutes in succession
and the electronic expansion valve openning is 50 pulses or less.
Time Chart
∗Units operate with the starting air flow volume for up to 3 minutes.
∗ The motorized valve is fully open while the solenoid valve is ON.
„ When the solenoid valve turns OFF at T2 ≤ 95°C, the motorized valve remains fully open for 2 minutes.
After starting control ends, if the outdoor air temperature falls below (33.5 - 0.5 × room suction
temperature), the indoor unit fan speed is switched to “L.” The differential is 3°C.
Fan Control
Solenoid Valve
Control (In the Case
of R(Y)140 K)
Solenoid valve :
ON condition
In range (1) or Discharge pipe temperature (T2) > Outdoor unit heat exchanger temperature (Tc) +30°C
OFF condition
In range (2) or T2 < Tc R 18°C
5.2.18 Outdoor Unit Fan Control (Heating Overload Frosting Prevention Control)
The air flow volume of an outdoor unit fan is varied in either one of the following two patterns according to
the indoor unit heat exchanger temperature (Tc).
In the Case of RY
5.2.19 Defrosting
Control During heating, a defrosting request is made by the indoor unit when defrosting conditions have been
realized. The control method are as following.
„ Temperature conditions
3DUW#8
7URXEOHVKRRWLQJ
1. Maintenance Inspections ......................................................................77
1.1 Optimal Operation Condition ..................................................................77
2. How to Handle Request for Maintenance .............................................80
2.1 Flow Chart ..............................................................................................80
3. Troubleshooting Based on Equipment Condition..................................81
3.1 Troubleshooting Based on Equipment Condition ...................................81
3.2 Equipment does not Operate .................................................................82
3.3 Fan Operates, but Compressor does not. ..............................................83
3.4 Cooling/Heating Operation Starts but Stops Immediately. .....................84
3.5 After Equipment Shuts Down, It cannot be Restarted for a While..........85
3.6 Equipment Operates but does not Provide Cooling. ..............................86
3.7 Equipment Operates but does not Provide Heating. ..............................87
3.8 Equipment Discharges White Mist .........................................................88
3.9 Equipment Produces Loud Noise or Shakes..........................................89
3.10 Equipment Discharges Dust...................................................................90
3.11 Remote Controller LCD Displays "88". ...................................................91
4. Procedure of Self-Diagnosis by Remote Controller ..............................92
4.1 The INSPECTION/TEST Button.............................................................92
4.2 Self-Diagnosis by Wired Remote Controller...........................................93
4.3 Fault Diagnosis by Wireless Remote Controller.....................................94
4.4 Remote Controller Display Malfunction Code and Contents ..................96
5. Procedure of Self-Diagnosis by LED.....................................................97
5.1 Troubleshooting by LED on The Indoor Unit’s .......................................97
5.2 Troubleshooting by LED on The Outdoor Unit’s PC Board ....................97
6. Troubleshooting by Remote Controller Display / LED Display..............98
6.1 Explanation for Symbols.........................................................................98
6.2 Malfunction Code and LED Display Table..............................................99
6.3 Failure of Indoor Unit PC Board ...........................................................101
6.4 Malfunction of Drain Water Level System (Float Type)........................102
6.5 Indoor Unit Fan Motor Lock..................................................................103
6.6 Swing Flap Motor Malfunction / Lock ...................................................104
6.7 Failure of Capacity Setting ...................................................................105
6.8 Malfunction of Heat Exchange Temperature Sensor System ..............106
6.9 Malfunction of Suction Air Temperature Sensor System......................107
6.10 Actuation of Safety Device ...................................................................108
6.11 High Pressure System (HPS) Malfunction ...........................................109
6.12 Low Pressure System (LPS) Malfunction.............................................110
6.13 Malfunction of Electronic Expansion Valve ..........................................111
6.14 Discharge Pipe Temperature Malfunction ............................................112
6.15 Malfunction of High Pressure Switch....................................................113
6.16 Malfunction of Outdoor Temperature Sensor System ..........................114
6.17 Malfunction of Discharge Pipe Temperature Sensor System...............115
6.18 Malfunction of Heat Exchanger Temperature Sensor System .............116
6.19 Lack of Gas Malfunction.......................................................................117
Troubleshooting 75
Si-71A
76 Troubleshooting
Si-71A Maintenance Inspections
1. Maintenance Inspections
1.1 Optimal Operation Condition
Guide Lines for The operation value guide lines when operating under standard conditions by pushing the test run button
Optimal Operation on the remote controller are as given in the table below. RY71~125K are used as example outdoor units in
Condition the table.
Indoor Unit Fan: “H” Operation
High Pressure Low Pressure Discharge Suction Indoor Unit Outdoor Unit
(Mpa) (Mpa) Pipe Temperature Side: Side:
Temperature (°C) Differential Differential
(°C) Between Between
Suction Suction
Temperature Temperature
and and
Discharge Discharge
Temperature Temperature
(°C) (°C)
Cooling 50Hz 1.62~1.91 0.39~0.59 60~95 0~14 8~18 7~12
(16.5~19.5) (4.0~6.0)
60Hz 1.72~2.1 0.34~0.54 70~115 -2~10
(17.5~20.5) (3.5~5.5)
Heating 50Hz 1.42~1.86 0.29~0.44 55~95 -4~4 14~30 2~6
(14.5~19.0) (3.0~4.5)
60Hz 1.62~2.01 0.29~0.44 60~115 -6~2
(16.5~20.5) (3.0~4.5)
Standard Conditions
Indoor Unit Conditions Outdoor Unit Conditions
Cooling Operation 27°C DB/19°C WB 35°C DB
Heating Operation 20°C DB 7°C DB/6°C WB
„ During or after maintenance, when the power supply is turned back on, operation restarts automatically
by the “auto restart function.” Please exercise the proper caution.
Troubleshooting 77
Maintenance Inspections Si-71A
Correlation of Air- What happens in comparison to normal values is summarized in the table below.
Conditioner’s (Measured from 15 ~ 20 minutes or more after operation starts.)
Operation Status
and Pressure /
Running Current When Cooling
Air-Conditioner Status Low Pressure High Pressure Running Current
Air Filter Fouling Lower Lower Lower
Short Circuit of Indoor Unit Inlet/Outlet Lower Lower Lower
Air
Outdoor Unit Fin Fouling Higher Higher Higher
Short Circuit of Outdoor Unit Inlet/Outlet Higher Higher Higher
Air
Air Mixed in Refrigerant Higher Higher Higher
Water Mixed in Refrigerant ∗1 Lower Lower Lower
Dirt Mixed in Refrigerant ∗2 Lower Lower Lower
Lack of Refrigerant (Gas) Lower Lower Lower
Unsatisfactory Compression ∗1 Higher Lower Lower
When Heating
Air-Conditioner Status Low Pressure High Pressure Running Current
Air Filter Fouling Higher Higher Higher
Short Circuit of Indoor Unit Inlet/Outlet Higher Higher Higher
Air
Outdoor Unit Fin Fouling Lower Lower Lower
Short Circuit of Outdoor Unit Inlet/Outlet Lower Lower Lower
Air
Air Mixed in Refrigerant Higher Higher Higher
Water Mixed in Refrigerant ∗1 Lower Lower Lower
Dirt Mixed in Refrigerant ∗2 Lower Lower Lower
Lack of Refrigerant (Gas) Lower Lower Lower
Unsatisfactory Compression ∗3 Higher Lower Lower
Note: 1. ∗1. Water in the refrigerant freezes inside the capillary tube or expansion valve, and is basically the
same phenomenon as pump down.
2. ∗2. Dirt in the refrigerant clogs filters inside the piping, and is basically the same phenomenon as pump
down.
3. ∗3.Pressure differential between high and low pressure becomes slight.
78 Troubleshooting
Si-71A Maintenance Inspections
Refrigerant
Saturation Curve
(kg/cm2) MPa R-22
20.4 2.0
15.3 1.5
Gauge Pressure
10.2 1.0
R22
5.1 0.5
0 0
--40 --20 0 20 40 60 80 100 120 140
Temperature C (SG001)
Troubleshooting 79
How to Handle Request for Maintenance Si-71A
Turn the power supply Ask for the character Refer to "Remote controller display
Wait until code of the malfunction
power failure switch ON or replace malfunction code and contents".
the fuse. code.
is over.
YES (1) The operation circuit fuse is
Units equipped with liquid disconnected or is making poor contact.
crystal remote controllers only (2) The operation swich is broken or its
YES YES Is the remote contact is defective.
controller's operation (3) The high pressure switch is broken.
Is there a NO The power supply switch is NO lamp blinking? NO
OFF or the switch's fuse is (4) The fan motor's magnetic switch is
Doesn't run at all power broken.
burnt. Units equipped with wireless
failure? remote controllers only (5) The fan motor's overcurrent relay is
Is the operation lamp of the being actuated or is broken.
indoor unit's signal receiving (6) The compressor's overcurrent relay is
section blinking? broken.
(7) The compressor's protective thermostat
Ask for the character is broken.
Nomal code of the malfunction (8) The electrical system insulation is
code. defective.
(9) The compressor's magnetic switch's
YES contact is defective.
Runs Units equipped with liquid
(10) The compressor is broken.
crystal remote controllers only
Is the remote
The fan comes on Set the remote controller's operation (11) Thermostat is broken.
controller's temperature Doesn't run lamp blinking? NO (12) The cool/heat selector is broken.
but the setting to:
compressor Machines equipped with (13) The operation switch is broken.
(1)When wireless remote (14) The compressor's magnetic swich is
doesn't run. cooling:Minimum controllers only. broken.
(2)When
heating:Maximum Is the operation lamp of the
(15) Over-charged with refrigerant.
indoor unit's signal receiving
(16) Air is mixed inside the refrigerant
Ask for the character section blinking?
circuit.
code of the malfunction
(17) The pressure switch is broken.
code.
(18) The outdoor unit fan motor's magnetic
switch is broken.
YES
Units equipped with liquid (19) The outdoor unit fan motor's auxiliary
crystal remote controllers only relay is broken.
Is the remote
controller's operation (20) The outdoor unit's heat exchanger is
Cooling starts but lamp blinking? NO Cooling
dirty.
stops right away. Units equipped with wireless (21) There is something blocking the
remote controllers only outdoor unit's air flow.
Is the operation lamp of (22) Malfunction of the outdoor unit's fan.
the indoor unit's signal
receiving section Heating (23) The indoor unit's air filter is dirty.
blinking? (24) The indoor unit's heat exhanger is
dirty.
(25) There is something blocking the indoor
Nomal unit's air flow.
(26) Malfunction of the indoor unit's fan.
Did you allow 3 minutes to YES
The unit won't run Try turning the elapse after turning ON? NO
again for a while Operation switch OFF (27) Overcurrent relay (for compressor)
Runs
and On. (28) Compressor's protective themostat
after stopping.
(29) The causes for the overcurrent relay
(for compressor) being actuated are:
(29)-1 Power supply voltage is lower than
prescribed.
Operation is (29)-2 High pressure is too high.
normal. (29)-3 The power supply cord is too small.
(29)-4 The compressor is broken.
Is there something causing the
indoor load to be large, such as (30) The causes for the compressor's
an open window or door? protective thermostat
(30)-1 Internal leak of the-4way valve
YES (No substantial difference between
The unit runs but Temperature NO suction and discharge temperature.
doesn't cool the Measure the suction
/disharge temperature. differential is 8~18˚C (30)-2 Unsatisfactory compression from
room. the compressor
(Temperature differential (30)-3 Defective refrigerant
=suction temperature - discharge temperature) (30)-4 Malfunction of the expansion valve
(30)-5 Unsatisfactory refrigerant circulation
Operation is
normal.
Is there something causing the
indoor heat load to be large, such
as an open window or door?
YES
The units runs but Temperature NO
doesn't heat the Measure the suction
/discharge temperature. differential is 14~30˚C OK.We'll be right over.
room.
(Temperature differential
=discharge temperature - suction temperature)
(Maintenance required)
(SF004)
80 Troubleshooting
Si-71A Troubleshooting Based on Equipment Condition
Troubleshooting 81
Troubleshooting Based on Equipment Condition Si-71A
Error Detection
Method
Error Generating
Condition
Troubleshooting
Is power
switch OFF or fuse YES
Turn on power switch or replace fuse.
for remote switch
blown?
NO
Is there YES
power outage? Wait until power returns.
NO
Is operation YES
switch pressed Normal. Equipment starts operation 3
repeatedly? minutes later (3-min standby).
NO Is operation
lamp on LCD YES
Diagnose based on error code on
remote controller remote controller.
flashing?
Is thermostat YES NO
changed and reset Normal. Equipment starts operation 3
again? minutes later (3-min standby).
NO
Wireless
remote controller
Is operation lamp YES
Is outdoor Diagnose based on error code on
on indoor unit signal remote controller.
unit operating in NO receiving section
individual operation flashing?
mode?
YES NO
NO
Previous operation
Normal.
mode is still in effect.
Does remote
controller indicate
"other unit in cooling YES Not all units are in the
Normal. Set units to the same
operation" or "other same operation mode. operation mode.
unit in heating
operation"?
(SF031)
NO
82 Troubleshooting
Si-71A Troubleshooting Based on Equipment Condition
Error Detection
Method
Error Generating
Condition
Troubleshooting
Does YES
equipment operate? Normal.
NO
Is
operation lamp YES
on remote controller Diagnose based on error code on
flashing? remote controller.
NO
Is operation
lamp on indoor unit
located near wireless YES
remote controller signal
receiving section
flashing?
NO
Is outside
temperature above YES
Equipment cannot be operated in this
allowed operating condition.
range?
NO
(SF032)
Troubleshooting 83
Troubleshooting Based on Equipment Condition Si-71A
Error Detection
Method
Error Generating
Condition
Troubleshooting
Is the
Is the type operation lamp
of remote controller LC YES
of remote controller Diagnose based on the error code on
LC or wireless? flashing? remote controller
Wireless
Is the
operation lamp
of indoor unit YES
photo-sensing
section
flashing?
NO
[ Heating: Indoor unit
Cooling: Outdoor unit ]
Does the NO
fan rotate? Malfunction of fan motor
Check the magnetic switch and aux.
switch for fan motor
YES
Is the YES
filter soiled? Cleaning
NO
NO
NO
(SF033)
84 Troubleshooting
Si-71A Troubleshooting Based on Equipment Condition
Error Detection
Method
Error Generating
Condition
Troubleshooting
Is there
any temperature
difference between NO
Expansion valve malfunction
inlet and outlet of
expansion
valve?
YES
Is there
any temperature
difference between NO
suction side and Four-way valve malfunction
delivery side of
four-way
valve?
YES
Malfunction of compressor Check compressor
(SF034)
Troubleshooting 85
Troubleshooting Based on Equipment Condition Si-71A
Error Detection
Method
Error Generating
Condition
Troubleshooting
NO
NO
Possible causes as follows
* Incorrect selection of model Additional unit installation should be
* Affection of direct sun considered
Does
any frost generate Is the
around inlet port of YES operation current YES
indoor unit heat exchanger less than specified
or outlet port of level?
expansion
valve?
NO
NO
NO
Possible causes as follows
* Refrigerant overcharge
Is the level * Soiled heat exchanger
of high pressure higher YES Check each item
* Short circuit of discharge air
than normal level? * Disturbing item in air flow
* Malfunction of fan motor of
outdoor unit
NO
86 Troubleshooting
Si-71A Troubleshooting Based on Equipment Condition
Error Detection
Method
Error Generating
Condition
Troubleshooting
NO
NO
NO
* Incorrect selection of model
* Affection of sunlight Additional unit installation should be
considered
Is the
operation current less YES Gas shortage possibly
generates trouble. After vacuum drying, charge correct
than specified amount of refrigerant.
level?
NO
NO
* Refrigerant overcharge
Is the level * Soiled heat exchanger
of high pressure lower YES * Short circuit of discharge air
* Disturbing item in air flow Check each item
than normal level?
* Malfunction of fan motor of
outdoor unit
NO
* Insufficient compression of
compressor
* Insufficient circulation of Check each item
refrigerant
* Faulty expansion valve
(SF036)
Troubleshooting 87
Troubleshooting Based on Equipment Condition Si-71A
Error Detection
Method
Error Generating
Condition
Troubleshooting
Is the room
temperature higher than YES
Continue unit operation.
set value in cooling
operation?
NO
Is white fog NO
coming out from Normal
the unit?
YES
It may be necessary to
remove the source of humid Remove the source of humid
condition. condition.
Is the heat YES
exchanger of indoor Cleaning of heat exchanger is
unit soiled? necessary.
NO
NO
NO
(SF037)
88 Troubleshooting
Si-71A Troubleshooting Based on Equipment Condition
Error Detection
Method
Error Generating
Condition
Troubleshooting
Does the
noise generate YES
with vibration of Insert shock absorber in mounting
unit mounting section, or strengthen the mounting
section? section.
Continuous
NO slight noise of YES
"shoo....." during Normal. The sound is flushing noise of
cooling or gas (refrigerant) inside air conditioning
defrosting unit
Is the NO NO
piping secured? Insert cushion materials to the pipe
support such as saddle.
Sound
of "shoo..."
[Power supply side] YES generates just after YES
operation start or stop, Normal. The noise is a sound
or defrosting start generated at the time of gas
or stop. (refrigerant) flow change or stop
Creak
NO during heating YES
Normal. Creak generates by
and after operation shrinkage of resin parts due to
stop temperature change.
Is
the noise
flushing sound from YES NO
pressure reducing Normal.
valve or capillary
tube? * Excess charge of
refrigerant
NO * Air intrudes into
refrigerant system After vacuum drying, charge correct
* Flushing noise due to amount of refrigerant.
refrigerant shortage.
(Sound of shoo...) (SF038)
Troubleshooting 89
Troubleshooting Based on Equipment Condition Si-71A
Error Detection
Method
Error Generating
Condition
Troubleshooting
Does
the trouble
generate at the
time of operation start YES
Dust collected inside the indoor unit
again after extended are blown out.
period of Cleaning for inside of indoor unit is
operation? necessary.
NO
(SF039)
90 Troubleshooting
Si-71A Troubleshooting Based on Equipment Condition
3.11 ;;".
;;
Remote Controller LCD Displays ";;
Error Detection
Method
Error Generating
Condition
Possible Cause
Troubleshooting
Trouble
generates just after YES
The unit is checking to confirm that
power supply ON remote controller is normal.
Indication appears for short time.
NO
Is the
position of (SS 1) YES
on indoor unit PCB at Turn the switch to "Ordinary", and
"Emergency"? reset power supply.
NO
Troubleshooting 91
Procedure of Self-Diagnosis by Remote Controller Si-71A
Explanation By turning the remote controller’s inspection /test button ON, you can change the mode as shown in the
figure on the right.
„ When in the inspection mode, malfunction contents can be cleared by continuing to press the ON/OFF
button for 5 seconds.
(Let you know completion timing by blinking.)
„ To carry out a test run, follow the procedure below.
1. Open the gas side stop valve all the way
2. Open the liquid side stop valve all the way.
3. Energize the crank case heater for 6 hours.
4. Enter the test run mode.
5. Continue to operate by the operation switch for 3 minutes.
6. Enter the normal mode.
7. Check the functions according to the operation manual.
92 Troubleshooting
Si-71A Procedure of Self-Diagnosis by Remote Controller
Explanation If operation stops due to malfunction, the remote controller’s operation LED blinks, and malfunction code is
displayed. (Even if stop operation is carried out, malfunction contents are displayed when the inspection
mode is entered.) The malfunction code enables you to tell what kind of malfunction caused operation to
stop. See page 96 for malfunction code and malfunction contents.
Troubleshooting 93
Procedure of Self-Diagnosis by Remote Controller Si-71A
∗2 Number of beeps
Continuous beep : Both upper and lower digits matched.(Malfunction code confirmed)
2 short beeps: Upper digit matched.
1 short beep : Lower digit matched.
5. Press the MODE selector button.
The right “0” (lower digit) indication of the malfunction code flashes.
6. Malfunction code lower digit diagnosis
Press the UP or DOWN button and change the malfunction code lower digit until the continuous
malfunction code matching buzzer (*2) is generated.
„ The lower digit of the code changes as shown below when the UP and DOWN buttons are pressed.
94 Troubleshooting
Si-71A Procedure of Self-Diagnosis by Remote Controller
Troubleshooting 95
Procedure of Self-Diagnosis by Remote Controller Si-71A
Note 1: Operation when a malfunction occurs may differ according to the model.
96 Troubleshooting
Si-71A Procedure of Self-Diagnosis by LED
Foreword Troubleshooting can be carried out by service monitor LED (green). (Blinks when normal)
ò : LED on ó : LED off ñ : LED blinks — : No connection with troubleshooting
Microcomputer Transmission Normal Contents/Processing
Normal Monitor Monitor
H1P (LED-A) H2P (LED-B)
ñ ñ Normal → Outdoor unit
Note: 1. If LED-B is off, the transmission wiring between indoor and outdoor unit may be incorrect or
disconnected. Before performing the previously described troubleshooting, check the transmission
wiring.
2. Troubleshoot by turning off the power supply for a minimum of 5 seconds, turning it back on, and then
rechecking the LED display.
Note: 1. Check troubleshoot by turning off the power supply for a minimum of 5 seconds, turning it back on, and
then rechecking the LED display.
2. Turn off the power supply for a minimum of 5 seconds, and when turning it back on after disconnecting
transmission wiring No. 2, if the outdoor unit’s LED-A blinks, the indoor unit’s PC board is defective.
3. Previous malfunction data is displayed on the malfunction detection monitor. After inspecting, turn off
the power supply once.
4. Switch 2 of the 3 power supply cables and recheck.
General 1. When disconnecting the fasten terminal from the PC board, hold down the PC board with your finger
Precautions When and do not apply excessive force. Also, do not hold the neck of the fasten terminal and pull the lead
Performing wire.
Maintenance 2. Do not use a mega tester on the secondary side (transformer secondary side) of the electronic circuitry.
3. Even when not energized, beware of static electricity when touching parts or pattern. (If handling PC
board when dry [winter], be sure to discharge the electrostatic charge by grounding. Do not touch any
other grounded metal parts with your fingers.)
Troubleshooting 97
Troubleshooting by Remote Controller Display / LED Display Si-71A
98 Troubleshooting
Si-71A Troubleshooting by Remote Controller Display / LED Display
Indoor Unit
Indoor Unit Indoor Unit LED Remote Location of Malfunction Contents of Malfunction Details of
Malfunctions Display Controller Malfunction
Note 2 Display (Reference
Page)
H1P H2P Other PC Board
than PC
Board Outdoor Indoor Remote
Unit Unit Controller
ñ ñ *Note 1 — — — — Normal → to outdoor unit —
ñ ó refer to p.97.)
ò —
ó —
Outdoor Unit
Outdoor Unit Outdoor Unit LED Remote Location of Malfunction Contents of Malfunction Details of
Malfunctions Display Controller Malfunction
Display (Reference
A 1 2 Other PC Board Page)
(H1P) (H2P) (H3P) than PC
Board Outdoor Indoor Remote
Unit Unit Controller
ñ ó ó Note 1∗ — — — — Normal → to indoor unit —
Troubleshooting 99
Troubleshooting by Remote Controller Display / LED Display Si-71A
System
System Outdoor Unit LED Remote Location of Malfunction Contents of Malfunction Details of
Malfunctions Display Controller Malfunction
Display (Reference
A 1 2 Other PC Board Page)
(H1P) (H2P) (H3P) than PC
Board Outdoor Indoor Remote
Unit Unit Controller
— 83 • — — — Short of gas malfunction 117
ñ ó ò 84 • … — — Reverse phase 118
100 Troubleshooting
Si-71A Troubleshooting by Remote Controller Display / LED Display
Remote Controller $4
Display
Malfunction When data could not be correctly received from the E²PROM
Decision E²PROM : Type of nonvolatile memory. Maintains memory contents even when the power supply is turned
Conditions off.
Troubleshooting
YES
Normal reset? Could be outside
cause (noise, etc.)
other than
malfunction
NO
Indoor unit PC
board
replacement
(SF005)
Troubleshooting 101
Troubleshooting by Remote Controller Display / LED Display Si-71A
Remote Controller $6
Display
Malfunction When rise of water level is not a condition and the float switch goes OFF.
Decision
Conditions
Troubleshooting
NO
Is the
short-circuit
Is drain raising NO connector NO
mechanism connected to X15A on Short-circuit
connected? the indoor unit connector
PC board? connection
YES
YES
Continuity check of
short-circuit
connector
NO Short-circuit
Is there continuity? connector
replacement
YES Indoor unit PC
Is a drain board replacement
pump connected NO
to the indoor unit Connect drain pump
PC board?
YES
YES
Set to“emergency” Remove the float switch
and check the from X15A, short-circuit
voltage X15A, and restart
operation.
Does display NO
of malfunction Float switch replacement
“A3”appear?
102 Troubleshooting
Si-71A Troubleshooting by Remote Controller Display / LED Display
Remote Controller $9
Display
Method of Detection by failure of signal for detecting number of turns to come from the fan motor
Malfunction
Detection
Malfunction When number of turns can’t be detected even when output voltage to the fan is maximum
Decision
Conditions
Troubleshooting
Are
X20A and NO
X26A properly Connect correctly.
connected?
YES
With
X26A
unplugged
and the power
supply turned on, NO
is there about 12 Indoor unit PC board
VDC between replacement
pins 1 and
3 of
X26A?
YES
(SF007)
Troubleshooting 103
Troubleshooting by Remote Controller Display / LED Display Si-71A
Remote Controller $:
Display
Method of Utilizes ON/OFF of the limit switch when the motor turns.
Malfunction
Detection
Malfunction When ON/OFF of the microswitch for positioning cannot be reversed even though the swing flap motor is
Decision energized for a specified amount of time (about 30 seconds).
Conditions
Troubleshooting
Are the
connectors
correctly connected NO
to X29A and X14A Connect correctly.
on the PC
board?
YES
Is the limit
switch's transfer NO
connector correctly Connect correctly.
connected?
YES
Disconnect X14A,
turn the power
supply off once and
Does the swing YES back on, and check
flap motor swing? if the limit switch has
continuity when the
power supply is
turned back on.
NO
NO
220-240 VAC?
YES
(SF008)
104 Troubleshooting
Si-71A Troubleshooting by Remote Controller Display / LED Display
Remote Controller $-
Display
Method of Capacity is determined according to resistance of the capacity setting adaptor and the memory inside the
Malfunction IC memory on the indoor unit PC board, and whether the value is normal or abnormal is determined.
Detection
Troubleshooting
Is
the
capacity
setting adaptor NO
plugged into X23A Plug a capacitor setting adaptor
of the indoor that matches the capacity of the
unit PC unit into X23A. (See note)
board?
YES
Is AJ
displayed on the YES
Indoor unit PC board
remote controller? replacement
NO
(SF009)
Note: Capacity is factory set in the data IC on the PC board. A capacity setting adaptor that matches the capacity
of the unit is required in the following case.
If the indoor PC board installed at the factory is for some reason changed at the installation site, the
capacity will not be contained in the replacement PC board.
If you connect a capacity setting adaptor to a PC board in which the capacity is memorized, the capacity
setting for the PC board will become the capacity setting of the adaptor. (Priority of capacity setting
adaptor)
Troubleshooting 105
Troubleshooting by Remote Controller Display / LED Display Si-71A
Method of Malfunction detection is carried out by temperature detected by heat exchanger sensor.
Malfunction
Detection
Malfunction When the heat exchanger thermistor becomes disconnected or shorted while the unit is running.
Decision
Conditions
Troubleshooting
Is
the thermistor NO
normal? Heat exchanger
(See note) senser
replacement
YES
If contact is OK,
replace outdoor
unit PC board.
(SF010)
Note: Measure the resistance while referring to the thermistor temperature and resistance conversion table.
Thermistor temperature and resistance conversion table.
Temperature Suction, heat exchanger(indoor) Temperature Suction, heat exchanger(indoor)
outdoor air, outdoor unit suction pipe outdoor air, outdoor unit suction pipe
sensor (kΩ) sensor (kΩ)
-6.0 90.8 28.0 17.6
-4.0 81.7 30.0 16.2
-2.0 73.5 32.0 14.8
0.0 66.3 34.0 13.6
2.0 59.8 36.0 12.5
4.0 54.1 38.0 11.5
6.0 48.9 40.0 10.6
8.0 44.3 42.0 9.8
10.0 40.2 44.0 9.1
12.0 36.5 46.0 8.4
14.0 33.2 48.0 7.8
16.0 30.2 50.0 7.2
18.0 27.5 52.0 6.9
20.0 25.1 54.0 6.2
22.0 23.0 56.0 5.7
24.0 21.0 58.0 5.3
26.0 19.2
106 Troubleshooting
Si-71A Troubleshooting by Remote Controller Display / LED Display
Method of Malfunction detection is carried out by temperature detected by suction air temperature sensor.
Malfunction
Detection
Malfunction When the suction air temperature sensor’s thermistor becomes disconnected or shorted while the unit is
Decision running.
Conditions
Troubleshooting
Disconnect the
suction air
temperature sensor
(R1T) from X19A on
the indoor unit PC
board and measure
the resistance.
Is
the thermistor NO
normal? Suction air
(See note) temperature
sensor
replacement
YES
If contact is OK.
replace outdoor
unit PC board.
(SF011)
Note: Measure the resistance while referring to the thermistor temperature and resistance conversion table.
Thermistor temperature and resistance conversion table.
Temperature Suction, heat exchanger(indoor) Temperature Suction, heat exchanger(indoor)
outdoor air, outdoor unit suction pipe outdoor air, outdoor unit suction pipe
sensor (kΩ) sensor (kΩ)
-6.0 90.8 28.0 17.6
-4.0 81.7 30.0 16.2
-2.0 73.5 32.0 14.8
0.0 66.3 34.0 13.6
2.0 59.8 36.0 12.5
4.0 54.1 38.0 11.5
6.0 48.9 40.0 10.6
8.0 44.3 42.0 9.8
10.0 40.2 44.0 9.1
12.0 36.5 46.0 8.4
14.0 33.2 48.0 7.8
16.0 30.2 50.0 7.2
18.0 27.5 52.0 6.9
20.0 25.1 54.0 6.2
22.0 23.0 56.0 5.7
24.0 21.0 58.0 5.3
26.0 19.2
Troubleshooting 107
Troubleshooting by Remote Controller Display / LED Display Si-71A
Remote Controller (3
Display
Method of Actuation of each safety device is detected by safety device input circuit.
Malfunction (Safety device unified detection)
Detection
Troubleshooting
Is
the safety
device's lead
wire correctly NO
connected to the Connect correctly.
outdoor unit PC
board?
YES
Find safety device
which is not
energized.
Temperature of
compressor
discharge pipe is
abnormally high.
Is the fan turning correctly? Remove obstacles so the fan turns correctly, or
replace the fan.
Has draft passage been Provide draft passage
provided?
Fan motor
replacement
108 Troubleshooting
Si-71A Troubleshooting by Remote Controller Display / LED Display
Romote Controller (6
Display
Method of Continuity of the high pressure switch is detected by the safety device circuitry.
Malfunction
Detection
Malfunction Case where high pressure switch is actuated when the compressor is operating
Decision
Conditions
Troubleshooting
Are
HPS's
for control
and safety
connected to the NO
outdoor unit PC Connect correctly
board?
(See note)
YES
Do
the HPS's
for control and NO
safety have Replace HPS without continuity.
continuity?
YES
Is
high pressure YES
during operation Malfunction of refrigerant piping circuit
abnormally
high?
NO
(SF013)
Note: Some models are not equipped with an HPS for control or safety.
Troubleshooting 109
Troubleshooting by Remote Controller Display / LED Display Si-71A
Remote Controller (7
Display
Method of Continuity of the low pressure switch is detected by the safety device circuitry.
Malfunction
Detection
Malfunction Case where low pressure switch is actuated when the compressor is operating
Decision
Conditions
Troubleshooting
Is
LPS
for safety
connected to the NO
Connect correctly
outdoor unit PC
board?
YES
Does
the LPS for NO
safety have Replace HPS without continuity.
continuity?
YES
Is low
pressure YES
during operation Malfunction of refrigerant piping circuit
abnormally
low?
NO
(SF014)
110 Troubleshooting
Si-71A Troubleshooting by Remote Controller Display / LED Display
Method of With electronic expansion valve malfunction detection, coil current is detected and open and short circuits
Malfunction are detected.
Detection
Troubleshooting
YES
Normal reset? Could be outside cause (noise, etc.)
other than malfunction.
NO
Is
resistance
of electronic NO
expansion valve's Failure of electronic expansion valve
coil normal?
(40-50Ω)
YES
(SF015)
Troubleshooting 111
Troubleshooting by Remote Controller Display / LED Display Si-71A
Remote Controller )6
Display
Method of Malfunction is detected according to temperature detected by discharge pipe temperature sensor.
Malfunction
Detection
Troubleshooting
Is
the amount NO
of refrigerant Charge with the proper amount
correct? of refrigerant.
YES
Has
the sensor
come off the NO
Correctly place the sensor in
discharge pipe the discharge pipe port.
port?
YES
Is
electronic NO
expansions valve
fitted?
YES
Is
electronic
expansion valve NO
disconnected from Check refrigerant piping circuit
valve body? clogging.
YES
112 Troubleshooting
Si-71A Troubleshooting by Remote Controller Display / LED Display
Remote Controller +6
Display
Method of Continuity of the high pressure switch is detected by the safety device circuitry.
Malfunction
Detection
Malfunction When the compressor is off and the high pressure switch doesn’t have continuity
Decision
Conditions
Troubleshooting
Are
HPS's
for control
and safety NO
connected to the Connect correctly
outdoor unit PC
board?
YES
Do
the HPS's
for control and NO
safety have Replace HPS without
continuity? continuity.
YES
(SF017)
Troubleshooting 113
Troubleshooting by Remote Controller Display / LED Display Si-71A
Malfunction Case where the outdoor temperature sensor has a short or open circuit
Decision
Conditions
Troublshooting
Disconnect the
outdoor temperature
sensor (R1T) from
X4A on the outdoor
unit PC board and
measure the
resistance.
Is
the thermistor NO
normal? Outdoor temperature sensor replacement
(See note)
YES
(SF018)
Note: Measure the resistance while referring to the thermistor temperature and resistance conversion table.
Thermistor temperature and resistance conversion table.
Temperature Suction, heat exchanger(indoor) Temperature Suction, heat exchanger(indoor)
outdoor air, outdoor unit suction pipe outdoor air, outdoor unit suction pipe
sensor (kΩ) sensor (kΩ)
-6.0 90.8 28.0 17.6
-4.0 81.7 30.0 16.2
-2.0 73.5 32.0 14.8
0.0 66.3 34.0 13.6
2.0 59.8 36.0 12.5
4.0 54.1 38.0 11.5
6.0 48.9 40.0 10.6
8.0 44.3 42.0 9.8
10.0 40.2 44.0 9.1
12.0 36.5 46.0 8.4
14.0 33.2 48.0 7.8
16.0 30.2 50.0 7.2
18.0 27.5 52.0 6.9
20.0 25.1 54.0 6.2
22.0 23.0 56.0 5.7
24.0 21.0 58.0 5.3
26.0 19.2
114 Troubleshooting
Si-71A Troubleshooting by Remote Controller Display / LED Display
Remote Controller -6
Display
Malfunction Case where the discharge pipe temperature sensor has a short or open circuit
Decision
Conditions
Troubleshooting
Disconnect the
discharge pipe
temperature
sensor(R3T) from
X6A on the outdoor
unit PC board and
measure the
resistance.
Is
the thermistor NO
normal? Dischange pipe
(See note) temperature sensor
rep;acement
YES
If contact is OK,
replace outdoor unit
PC board.
(SF019)
Note: Measure the resistance while referring to the thermistor temperature and resistance conversion table.
Thermistor temperature and resistance conversion table.
Temperature Discharge pipe sensor(kΩ) Temperature Discharge pipe sensor(kΩ)
-6.0 866.8 28.0 175.8
-4.0 782.7 30.0 161.5
-2.0 707.6 32.0 148.4
0.0 640.4 34.0 136.6
2.0 579.9 36.0 125.8
4.0 525.6 38.0 115.3
6.0 477.0 40.0 106.5
8.0 433.4 42.0 98.8
10.0 394.2 44.0 91.3
12.0 358.9 46.0 84.4
14.0 327.1 48.0 78.1
16.0 298.5 50.0 72.3
18.0 272.6 52.0 67.1
20.0 249.2 54.0 62.2
22.0 228.1 56.0 57.8
24.0 208.9 58.0 53.7
26.0 191.5
Troubleshooting 115
Troubleshooting by Remote Controller Display / LED Display Si-71A
Remote Controller -9
Display
Malfunction Case where the heat exchanger temperature sensor has a short or open circuit
Decision
Conditions
Troubleshooting
Is
the thermistor NO
normal? Heat exchanger temperature
(See note) sensor replacement
YES
(SF020)
Note: Measure the resistance while referring to the thermistor temperature and resistance conversion table.
Thermistor temperature and resistance conversion table.
Temperature Suction, heat exchanger (indoor) Temperature Suction, heat exchanger (indoor)
outdoor air, outdoor unit suction pipe outdoor air, outdoor unit suction pipe
sensor (kΩ) sensor (kΩ)
-6.0 90.8 30.0 16.2
-4.0 81.7 32.0 14.8
-2.0 73.5 34.0 13.6
0.0 66.3 36.0 12.5
2.0 59.8 38.0 11.5
4.0 54.1 40.0 10.6
6.0 48.9 42.0 9.8
8.0 44.3 44.0 9.1
10.0 40.2 46.0 8.4
12.0 36.5 48.0 7.8
14.0 33.2 50.0 7.2
16.0 30.2 52.0 6.9
18.0 27.5 54.0 6.2
20.0 25.1 56.0 5.7
22.0 23.0 58.0 5.3
24.0 21.0
26.0 19.2
28.0 17.6
116 Troubleshooting
Si-71A Troubleshooting by Remote Controller Display / LED Display
Remote Controller 83
Display
Malfunction Microcomputer decides whether there is a lack of gas and detects malfunction.
Decision „ Stop due to malfunction does not occur even though a malfunction is determined to have occurred.
Conditions
Troubleshooting
Is the
amount of NO
refrigerant correct? Charge with the proper amount
of refrigerant.
YES
(SF021)
Troubleshooting 117
Troubleshooting by Remote Controller Display / LED Display Si-71A
Remote Controller 84
Display
Method of Reverse phase detection circuit detects the phase of each phase and determines whether it is normal or
Malfunction reverse phase.
Detection
Troubleshooting
Is U1
displayed on the NO
remote controller? Could be outside cause (noise,
etc.) other than malfunction.
YES
(SF022)
118 Troubleshooting
Si-71A Troubleshooting by Remote Controller Display / LED Display
Remote Controller 87
Display
Method of Microcomputer checks if transmission between indoor and outdoor units is normal.
Malfunction
Detection
Malfunction When transmission is not carried out normally for a certain amount of time
Decision
Conditions
NO (ON or OFF)
Is H1P blinking?
Check of YES
indoor unit Turn the power
microcom- supply off once and
puter then back on.
normal
H1P
NO
Is H1P blinking? Failure of indoor unit PC board or
malfunction of power supply system
YES
Resets normally.
Could be outside
cause (noise, etc.).
NO YES
Is H2P blinking? Is H2P on? Failure of indoor unit PC board.
YES
Is indoor-
outdoor NO
To outdoor unit transmission Wire correctly.
(next page) wire wired
correctly?
YES
Failure of indoor unit PC board.
(SF023)
Troubleshooting 119
Troubleshooting by Remote Controller Display / LED Display Si-71A
Troubleshooting 2
Continued from
previous page
NO (ON or OFF)
Is H1P blinking?
YES
Is H1P blinking? Resets normally.
Could be outside cause (noise, etc.).
NO
YES
Is H1P on? Failure of indoor unit PC board
NO (OFF)
YES
Is H1P blinking? Failure of indoor unit PC board
NO
Failuer of indoor unit PC board or
malfunction of power supply system
Resets normally.
Could be outside cause (noise, etc.)
(SF024)
120 Troubleshooting
Si-71A Troubleshooting by Remote Controller Display / LED Display
Remote Controller 88
Display
Method of Microcomputer checks if transmission between indoor unit and remote controller is normal.
Malfunction
Detection
Malfunction When transmission is not carried out normally for a certain amount of time
Decision
Conditions
Troubleshooting
YES YES
Malfunction could be
produced by noise.
Check the
surrounding area and
restart operation.
Using
multicore
transmission wiring YES
between indoor unit Change to
and remote double-core
controller independent cable.
NO
Failure of remote
controller PC board or
replacement of
defective indoor unit
PC board
(SF025)
Troubleshooting 121
Troubleshooting by Remote Controller Display / LED Display Si-71A
6.23 Transmission Error Between Main Remote Controller and Sub Remote
Controller
Remote Controller 8;
Display
Method of In case of controlling with 2- remote controller, check the system using microcomputer if signal
Malfunction transmission between indoor unit and remote controller (main and sub) is normal.
Detection
Supposed Causes „ Transmission error between Main remote controller and Sub remote controller
„ Connection among “Sub” remote controllers
„ Faulty remote controller PCB
Troubleshooting
SS-1switch
Controlling NO on remote controller NO
with 2-remote Turn the SS-1switch of one remote
PCB is turned controller to "Main".
controller to "Main" Turn OFF the power supply, and
restart operation
YES YES
Both SS-1
switches on remote NO
controllers are turned Turn OFF the power once and restart
to "Sub" operation.
Replace remote controller PCB if any
error is generated.
YES
(SF041)
122 Troubleshooting
Si-71A Troubleshooting by Remote Controller Display / LED Display
Remote Controller 8$
Display
Troubleshooting
Is
the
remote YES
controller connected Connect the remote controller
to more than correctly.
one indoor
unit?
NO
Is
the outdoor unit NO
using for Twin Check setting "No. of Connected Twin
system? System Indoor Units" of indoor unit.
(Note1)
YES
Is the
setting of
Pair/Twin/Triple NO
Set correctly
setted
correctly?
YES
Are
the Is the
microcomputer indoor-indoor
normal montiors NO and indoor-outdoor NO
(LED A) of all indoor Connect correctly
jumper correctly
unit PC boards connected?
blinking?
YES
YES Is the
power supply NO
Are PC board correctly Connect correctly
the connected?
transmission
normal montiors NO YES
(H2P) of all indoor
unit PC boards Is there
blinking? 220-240 VAC
between No.1 and NO
No.3 of X2M Replace the transformer.
YES (indoor Unit)?
YES
Turn the power off Wiring could be incorrect; recheck.
once, then back on,
and restart operation.
Is the
indoor-indoor
NO and indoor-outdoor NO
Operating normally? Connect correctly.
jumper correctly
connected?
YES
YES
Indoor unit PC board replacement
Operates normally
(SF026)
Troubleshooting 123
Troubleshooting by Remote Controller Display / LED Display Si-71A
124 Troubleshooting
Si-71A
3DUW#9
5HPRYDO#3URFHGXUH
1. For FHYC71K......................................................................................127
1.1 Removal of Switch Box Cover..............................................................127
1.2 Removal of Fan Motor..........................................................................128
1.3 Removal of Suction Grille.....................................................................129
1.4 Removal of Air Filter.............................................................................130
1.5 Removal of Decoration Cover ..............................................................131
1.6 Removal of Decoration Panel...............................................................132
1.7 Removal of Horizontal Vane.................................................................133
1.8 Removal of Swing Motor ......................................................................135
1.9 Removal of Switch Box Cover..............................................................137
1.10 Removal of Fan Motor..........................................................................138
1.11 Removal of Drain Pan ..........................................................................139
1.12 Removal of Drain Pump and Drain Hose .............................................140
2. For FHY71F ........................................................................................142
2.1 Removal of Air Filter and Suction Grille ...............................................142
2.2 Removal of Electrical Parts and PC Boards.........................................143
2.3 Removal of Horizontal Blade................................................................145
2.4 Removal of Fan Rotor an Motor ...........................................................146
2.5 Removal of Fan Bearing.......................................................................148
2.6 Removal of Bottom Panel and Drain Pan.............................................149
2.7 Removal of Swing Motor ......................................................................152
3. For FUY71/100/125FJ.........................................................................153
3.1 Removal of Air Filter.............................................................................153
3.2 Removal of Suction Grille.....................................................................154
3.3 Removal of Fan ....................................................................................155
3.4 Removal of Fan Motor..........................................................................157
3.5 Removal of Drain Pan ..........................................................................158
3.6 Removal of Drain Pump .......................................................................160
3.7 Removal of Swing Motor ......................................................................161
3.8 Removal of Air Flow Control Blade ......................................................162
4. For FAY71F (A)...................................................................................163
4.1 Removal of Air Filter.............................................................................163
4.2 Removal of Slide Panel, Operation Display Cover, and Front Grille ....164
4.3 Removal of Electrical Parts Box ...........................................................165
4.4 Removal of PC Board...........................................................................166
4.5 Removal of Swing Louvre Unit .............................................................167
4.6 Removal of Fan Motor..........................................................................168
4.7 Removal of Drain Pan ..........................................................................169
4.8 Removal of Heat Exchanger ................................................................171
4.9 Removal of Fan Rotor ..........................................................................172
5. For FVY71L~125L...............................................................................173
5.1 Removal of Suction Grille and Air Filter ...............................................173
5.2 Removal of Electric Parts and Remote Controller................................175
5.3 Removal of Fan Rotor and Fan Motor..................................................177
5.4 Removal of Swing Motor ......................................................................178
1. For FHYC71K
1.1 Removal of Switch Box Cover
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1. Removing the cover from the
control PCB side
1 Loosen the 1 screw, and pull
the cover toward the inside
and pull it down.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1. Removing the switch box
1 Remove the 5 screws, and
pull the switch box down.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1 Push the two buttons ∗When closing, push up the grille
simultaneously and pull the slowly.
suction grille down slowly.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1 Open the suction grille. (See
the removal procedure of
suction grille.)
2 Disengage the hooks of the
air filter by pulling the filter
downward at an angle, and
remove the filter.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1 To remove the decoration
cover, pull the inside part
(suction grille side) down.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1 Loosen the 4 retaining Structure of mounting fixture
screws from the decoration
panel.
2 The decoration panel is
attached with 4 mounting
fixtures.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1 Locate 9 screws on the ∗Remove seal materials in the
decoration panel under the following sequence. d→f,c→e
seal materials.
∗Number of screws
No. of screws
Seal material c : 7 pcs
Seal material d : 9 pcs
Seal material e : 7 pcs
Seal material f : 9 pcs
Total : 32 pcs
Reassembly
∗Check to make sure the heat
insulation is installed in the air outlet
section as shown below. (Improper
heat insulation installation results in
condensation of water.)
Seal material
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1 Remove the decoration ∗Only the decoration cover needs to
cover located immediately be removed to take out the swing
below the cooling pipe. motor.
Caution
∗Caution during swing motor
installation
1 After installing the swing
motor, be sure to turn on the
power switch for reset (for
initializing the vane
positions).
2 Be sure to engage the gears
on the motor side and panel
sides. (Improper gear
engagement results in faulty
swing operation and
abnormal noise.)
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1. Removing the cover from the
control PCB side
1 Loosen the 1 screw, and pull
the cover toward the inside
and pull it down.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1. Removing the switch box
1 Remove the 5 screws, and
pull the switch box down.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1 Drain water from the drain
hole.
2 Remove the 5 drain pan
mounting screws.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1 Removing the drain pump
1 Remove the drain pan. Caution
∗Be sure to install the pipe clip during
installation to prevent water leaks.
2. For FHY71F
2.1 Removal of Air Filter and Suction Grille
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1 The air filter is mounted
behind the suction grille.
2 Push the 2 tabs and open
the suction grilles.
3 Push the air filter installation
panel from 2 places in the
direction of the arrow, and
pull the air filter out toward
yourself.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Remove the air filter according to
the procedures for removing the air
filter and suction grille.
1 After removing the reinforce
stay (1 installation screw),
loosen the 2 screws of the
control box cover and
remove the control box
cover.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1 Remove the left side panel
according to the procedure
for removing the fan bearing.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1 Push the 2 tabs of the fan
housing toward the inside
with your fingers, and pull
out the fan housing.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Remove the fan rotor according to
the procedures for removing the fan
rotor and fan motor.
1 Remove the left side panel
installation screw.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Remove the air filter according to
its removal procedure.
1 Remove the right side panel
installation screw.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Remove the right side panel
according to the procedures for
removing the bottom panel and
drain pan.
1 Disconnect the connector
connected to the swing
motor.
3 Remove the swing motor. When installing match the position with
the horizontal blade shaft.
3. For FUY71/100/125FJ
3.1 Removal of Air Filter
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1 Opening suction grille
Push two tabs on suction
grille toward the center of
grille at the same time.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1. Unhook two drop-prevention
strings while supporting
suction grille with hand.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1. Remove two mounting
screws to dismount switch
box cover.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Poins
1. Removing fan motor
a. Disconnect connector
b. Remove lead wire
retaining plate
Caution
∗Fan motor can be removed without
removing the lead wire retaining plate.
However, when washing the heat
exchanger, this plate should be
removed and protect the lead wires.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Remove suction grille according to
the Removal of air filter and that of
suction grille.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1. Drain pump is located at
piping side.
Cut clamp material of hose, Caution
and disconnect hose from ∗When reconnect drain hose with the
pump. pump, secure hose at joint using
clamping material such as Tielap.
(Clamping material should be normally
included in the stock items.)
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Remove suction grille according to
the Removal of suction grille
1. Swing motor is located at the
diagonal position of piping.
2. Remove two mounting
screws for swing motor
cover.
3. Remove swing motor cover
by holding two tabs on the
cover.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1. To remove horizontal blade,
press down tabs located at
both end of blade and pull
them forward.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
4.2 Removal of Slide Panel, Operation Display Cover, and Front Grille
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1 Remove the left and right The wiring diagram is applied to the
side panels. (1 white screw right side panel, and troubleshooting
each on left and right) list is applied to the left side panel.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Remove the left and right side The left and right side panels have to
panels, operation display cover and be taken off in order to remove the
front grille according to the front grille.
procedures for their removal.
1 Remove the
(1) thermistor,
(2) heater connector
and
(3) rubber clip
connected to the PC board.
2 Remove the 2 screws
fastening the electrical parts
box to the units.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Remove the outer panels
according to the procedure for
removing the electrical parts box.
1 Disconnect the front side
wiring connector connected
to the PC board.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Remove the electrical parts box
according to its removal procedure.
1 Remove the horizontal
blade.
3 Remove the swing motor You can replace the swing motor
from the swing Louvre unit. without removing the swing Louvre
unit.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Remove side panels and other Use 2.5 mm hexagon nut driver.
external casing, and electrical parts
box according to their removal
procedures.
1 Loosen the hexagon set
screw fastening the fan rotor
and fan motor.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗If removing the drain pan: Carry The bottom panel is fastened to the
out pump down, disconnect the unit installation plate by 3 screws.
transmission piping and wiring, and
remove the main unit.
∗Remove side panels, operation
display cover and front cover
according to their removal
procedures.
1 Remove the bottom panel.
4 Remove the drain pan. 1 Pull left side toward yourself. 2 Move
the drain hose to the right until it comes
off.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Before dismounting a heat
exchanger, make sure to proceed
pump down refrigerant to outdoor Top plate
unit and disconnect the connection
pipe and wiring, then remove the
indoor unit.
1 Dismount top plate
(SR186)
2 Remove the 3 setting screws There is a hock right hand side behind
for heat exchanger and one the heat exchanger.
screw for pipe fixing box.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Remove the heat exchanger You can also remove the auxiliary
according to its removal procedure. electric heater without removing the
heat exchanger.
1 Remove the 2 screws of the
left side panel.
Reference
If you have enough space to pull
the fan rotor out from the left side,
you can remove it without
dismounting the heat exchanger.
5. For FVY71L~125L
5.1 Removal of Suction Grille and Air Filter
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
Removing air filter
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1 To remove switch box cover,
dismount screw (A), loosen
screw (B) and slide the cover
to right side.
Remove suction air
thermistor from bell mouth.
3 Disconnect remote
controller cord from switch
box.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
Removing fan rotor
1 Turn bell mouth in CW to
remove it.
2 Remove hexagon nut and
turning stopper plate to
disassemble fan rotor. Caution
When reassembling be sure to clamp
wires.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1 Disconnect harness for
swing motor and one for limit
switch at connector section.
2 Remove four screws to
dismount discharge
assembly.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
Removing switch box
1 Disconnect connector for
swing motor and one for limit
switch.
2 Remove heat exchanger
thermistor from PCB.
3 Remove three mounting
screws to dismount switch
box and air partition plate.
6. For R(Y)71K
6.1 Removal of External Casing
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1 Remove the 8 top plate
screws.
2 Remove the screw of the
front piping cover.
3 Remove the screw of the
front casing and remove by
pushing downward.
4 Remove the 4 screws of the
side piping cover.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Remove the front piping cover,
etc., according to the procedure for
removing the external casing.
1 Remove the 4 screws and
disconnect the 8 tabs
fastening the air discharge
grille on the top/bottom and
left/right, and remove the air
discharge grille.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Remove the top plate, front casing
and side casing according the
procedure for removing the
external casing, etc.
1 Disconnect the connectors
from the PC board.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Remove the top plate, front casing <In case of cooling only model> If the lead wire is clamped by the
and side casing according the piping, etc., remove the clamp.
procedure for removing the
external casing, etc.
1 Remove the discharge pipe,
heat exchanger and air
thermistor. (If not removing,
disconnect the connector
from the PC board.)
1) Remove the discharge
pipe thermistor.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Make sure the refrigerant is
completely empty.
1 Remove the electronic
expansion valve cover.
Procedure Waring Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Make sure the refrigerant is
completely empty.
1 Remove the external casing,
etc., and electrical parts
according to their removal
procedures.
2 Remove the 4-way valve.
Note:
When installing, first braze weld the 4-
way valve and attached piping, then
install the valve.
Be sure to check the position angle of
the piping when brazing.
Procedure Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
∗Remove the external casing, etc.,
according to its removal procedure.
1 Remove the compressor
sound-proofing.
3DUW#:
$SSHQGL[
1. Piping Diagrams..................................................................................192
1.1 Piping Diagrams ...................................................................................192
2. Wiring Diagram ...................................................................................203
2.1 Indoor Unit............................................................................................203
2.2 Outdoor Units (50Hz) ...........................................................................216
2.3 Outdoor Units (60Hz) ...........................................................................220
2.4 Outdoor Unit (HeaT Pump) ..................................................................223
Appendix 191
Piping Diagrams Si-71A
1. Piping Diagrams
1.1 Piping Diagrams
FHC35K / FHK35K / FHB35K / FH35F + R35G, FHC50K / FHK50K / FHB50K / FH45F + R50G, FHC60K / FHK60K /
FHB60K / FH60F + R60G
192 Appendix
Si-71A Piping Diagrams
FHYC100K / FHYB100K / FH100K / FAY100K / FVY100F + R100K, FHYC125K / FHYB125K / FH125K / FVY125F + R125K
FUY71FJ + R71K
DU427-6109A
Appendix 193
Piping Diagrams Si-71A
DU428-6141A
3D018539
194 Appendix
Si-71A Piping Diagrams
3D000191
3D000222
Appendix 195
Piping Diagrams Si-71A
3D000192
3D000224
196 Appendix
Si-71A Piping Diagrams
Appendix 197
Piping Diagrams Si-71A
DU427-6108B
198 Appendix
Si-71A Piping Diagrams
DU428-6140
FUY71FJ + RY71K
DU427-6108B
Appendix 199
Piping Diagrams Si-71A
DU428-6140
3D018540
200 Appendix
Si-71A Piping Diagrams
RY140KY1(Twin System)
3D000187
3D000216
Appendix 201
Piping Diagrams Si-71A
3D000188
3D000217
202 Appendix
Si-71A Wiring Diagram
2. Wiring Diagram
2.1 Indoor Unit
Appendix 203
Wiring Diagram Si-71A
FHK35FV1~FHK71FV1
DU427-5405
204 Appendix
Si-71A Wiring Diagram
FHB35FV1~FHB60FV1
DU423-5175A
Appendix 205
Wiring Diagram Si-71A
FH35FVE~FH125FVE
DU423-5172B
206 Appendix
Si-71A
Appendix
R1T R2T
1 — RED 2 — WHITE 3 — BLACK A1P A2P A3P
t˚ t˚
33H FLOAT SWITCH RECEIVER/DISPLAY UNIT(ATTACHED A1P SS1 H1P
A1P PRINTED CIRCUIT BOARD TO WIRLESS REMOTE CONTROLLER) X19A X18A BS
T1R TRANSFORMER(220-240V/22V) A2P PRINTED CIRCUIT BOARD SS2 H2P
FHYC35KVE~FHYC140KVE
TO OUTDOOR SS1
GRN
C1R CAPACITOR(M2F) A3P PRINTED CIRCUIT BOARD UNIT NOTE)4 NOTE)4 H3P
1 RED X1M NOTE)6
HAP LIGHT EMISSION DIODE BS PUSH BUTTON(ON/OFF) 2 WHT T C X24A X2A
X10A T1R X11A X24A H4P
(SERVICE MONITOR GREEN) H1P LIGHT EMISSIONV DIODE 3 BLK t˚ P2 X1A X1A
HBP LIGHT EMISSION DIODE (SERVICE MONITOR-RED) X27A P1
(SERVICE MONITOR GREEN) H2P X5A WIRED REMOTE RECEIVER/DISPLAY UNIT
LIGHT EMISSION DIODE H05 VV-U 4G1.5 X
X2M C1R
(SERVICE MONITOR-GREEN) RyP P1 P2 CONTROLLER
M1A MOTOR(SWING FLAP) ( TO 35-60 TYPE 2M
)
OUTDOOR UNIT P C
M2F MOTOR(INDOOR FAN) H3P LIGHT EMISSION DIODE SS1
WHT
GRN/YLW
YLW
H05 VV-U 4G2.0 X20A
M3P MOTOR(DRAIN PUMP) (SERVICE MONITOR-RED) TO 71-140 TYPE RED M
( ) RC 1~
Q1F THERMO SWITCH(M2F EMBEDDED) H4P LIGHT EMISSION DIODE OUTDOOR UNIT X25A
BLK
RED M M2F
R1T THERMISTOR(AIR) (SERVICE MONITOR-ORANGE)
1~
RED
R2T THERMISTOR(COIL) SS1 SELECTOR SWITCH(MAIN/SUB) M3P
X36A M
RyP MAGNETIC RELAY(M3P) SS2 SELECTOR SWITCH
SS1 SELECTOR SWITCH (WIRELESS ADDRESS SET) IN CASEOF SIMULTANEOUS
M1A OPERATION SYSTEM
(EMERGENCY) ADAPTOR FOR WIRING X30A X33A X35A 33H INDOOR UNIT INDOOR UNIT
HAP HBPX15A
X1M TERMINAL STRIP RyC MAGNETIC RELAY (MASTER) (SLAVE)
T1R
X2M TERMINAL STRIP RyF MAGNETIC RELAY TERMINALS FOR 1 1
PC PHASE CONTROL CIRCUIT CONNECTOR FOR OPTIONAL PARTS OPERATION INDICATOR
2 2
RC SIGNAL RECEIVER X30A CONNECTOR C1R
3 3
TC SIGNAL TRANSMISSION (INTERFACE ADAPTOR X2M
FAN
OPERATION
OPERATION
COMPRESSOR
3D005668B
207
Wiring Diagram
Wiring Diagram Si-71A
FHYK35FJV1~FHYK70FJV1
DU423-5174
208 Appendix
Si-71A Wiring Diagram
FHYB35FV1~FHYB71FV1
DU423-5173A
Appendix 209
Wiring Diagram Si-71A
FHYB100FV1 / FHYB125FV1
DU428-5353A
210 Appendix
Si-71A Wiring Diagram
FHY35FVE~FHY125FVE
DU423-5172B
Appendix 211
Wiring Diagram Si-71A
FAY71F(A)VE / FAY100F(A)VE
DU427-5410D
212 Appendix
Si-71A Wiring Diagram
FVY71FV1~FVY125FV1
DU427-5403
Appendix 213
Wiring Diagram Si-71A
3D013404A
214 Appendix
Si-71A Wiring Diagram
3D013540A
Appendix 215
Wiring Diagram Si-71A
R35GV1
DW523-555-1A
R50GV1
216 Appendix
Si-71A Wiring Diagram
R60GV1
R71KV1
DU427-5399C
Appendix 217
Wiring Diagram Si-71A
R100KV1
DU428-5349E
R71KY1
DU427-5401B
218 Appendix
Si-71A Wiring Diagram
R100KY1 / R125KY1
DU428-5351D
R140KY1
Appendix 219
Wiring Diagram Si-71A
R50GVAL
R60GVAL
3D005750
220 Appendix
Si-71A Wiring Diagram
R71KVAL
3D014723A
R100KVAL
3D014724A
Appendix 221
Wiring Diagram Si-71A
R125KTAL
3D014725
R140KTAL
POWER SUPPLY R S T
3~60Hz (NOTE 2)
220V
S1LP
L Y1E
R1T R2T R3T
M
t˚ t˚ t˚ A1P
C1R
T1R X1M R S T
C2R R X4A X5A X6A X23A X10A X24A X20A X1M
A1P
RED
RED F1U TC 1
T X21A F1C WHT 2
K1M BLU 3
BLK
F1C X12A Q2L
X1M
K1M PRC
SWITCH BOX Q1L T1R
X11A
t˚
F1C H
X9A
RED BLU A1P X7A X1A
S1PH
X1 X2
RyC RC
Ry Ry Ry Ry
F2 F1 F3 F4 SD
HH
HH
H
C
K1M
WHT
RED
BLK
RED
RED
BLU
BLK
BLK
BLU
S
U V W WHT F2U BS1 SS1 H1P
M M M H2P
1~ 1~ 3~
M1F M2F M1C HAP
WHT
WHT
YLW
YLW
3D000105A
222 Appendix
Si-71A Wiring Diagram
RY35FV1A
3D001431A
RY50GV1A
3D000794
Appendix 223
Wiring Diagram Si-71A
RY60GV1A
RY71KV1
224 Appendix
Si-71A Wiring Diagram
RY71KY1
DU427-5397B
RY100KY1 / RY125KY1
DU428-5347D
Appendix 225
Wiring Diagram Si-71A
RY140KY1
3D000102A
RY140KTAL
3D000104A
226 Appendix
Si-71A
,QGH[
1XPHULFV Emergency Operation of Outdoor Units ................ 43
1999 New Models Functions ....................................2 Existence of DTP Switch, Jumper and BS ............ 42
4-way Valve Control ...............................................65
)
$ F3 ........................................................................ 112
A1 .........................................................................101 Failure of Capacity Setting .................................. 105
A3 .........................................................................102 Failure of Field Setting Switch ............................. 123
A6 .........................................................................103 Failure of Indoor Unit PC Board .......................... 101
A7 .........................................................................104 Fan Speed Changeover
Abnormally High Discharge Pipe Temperature ......66 When Thermostat is OFF ............................... 28
Actuation of Safety Device ...................................108 Fan Speed OFF When Thermostat is OFF ........... 27
Air Flow Direction Setting .......................................25 Fan Start Control in Heating Operation ................. 70
Air Flow Volume Shift Control ................................63 Fault Diagnosis by Wireless Remote Controller .... 94
AJ .........................................................................105 Field Setting
Auto-restart Function ..............................................64 Wired Remote Controller ................................ 19
Wireless Remote Controller ............................ 20
% Filter Sign Setting .................................................. 25
BRC1B61 ...............................................................10 Forced Fan ON ..................................................... 44
BRC1B62 ...............................................................10 Freeze Prevention Control .............................. 63, 68
BRC7C612W ..........................................................14 Function Outline .................................................... 46
BRC7C613W ..........................................................12
BRC7C64W ............................................................14 +
BRC7C69W ............................................................12 H3 ........................................................................ 113
BS button (Pump down / Forced defrosting) ..........42 H9 ........................................................................ 114
High Pressure Protection Control
& in Cooling Operation ...................................... 67
C4 .........................................................................106 High Pressure Protection Control
C9 .........................................................................107 in Heating Operation ...................................... 70
Ceiling Type Setting Switch High Pressure System (HPS) Malfunction .......... 109
for Air Flow Adjustment ...................................24 How to Handle Request for Maintenance ............. 80
Centralized Group No. Setting ...............................29 HPS/LPS Detection Function ................................ 66
Compressor Shutdown Operation ..........................65
Cooling Start Control ..............................................67 ,
Correlation of Air-Conditioner’s Operation Status Individual Setting ................................................... 44
and Pressure / Running Current .....................78 Indoor Unit Fan Motor Lock ................................. 103
Initial Setting Contents .......................................... 21
'
Defrosting ...............................................................72 -
Detailed Explanation of Setting Modes ..................24 J3 ........................................................................ 115
DIP Switch and BS Detail .......................................42 J6 ........................................................................ 116
Discharge Pipe High Temperature Thermostat
OFF Control ....................................................66 /
Discharge Pipe Temperature Malfunction ............112 Lack of Gas Malfunction ................................ 66, 117
Draft Avoidance Control 1 ......................................62 Local Setting Mode No.
Draft Avoidance Control 2 ......................................63 10(20) ............................................................. 22
11(21) ............................................................. 22
( 12(22) ............................................................. 22
E0 .........................................................................108 13(23) ............................................................. 22
E3 .........................................................................109 Low Outside Temperature Control
E4 .........................................................................110 in Cooling Operation (Year-round Cooling) .... 69
E9 .........................................................................111 Low Pressure System (LPS) Malfunction ............ 110
Electric Function Parts ...........................................53
Electronic Expansion Valve Control .......................66 0
Emergency Operation ......................................43, 66 MAIN/SUB CHANGEOVER SWITCH ................... 28
Emergency Operation of Indoor Units ....................43
Index i
Si-71A
Main/Sub Setting 1
When Using 2 Remote Controllers .................28 No. of Connected Twin System Indoor Units ........ 24
MAIN/SUB Switch (SS1) ........................................25
Maintenance Inspections .......................................77 2
Maintenance Mode Setting Operation Flowchart (RY71 - 140K)
40 .....................................................................44 Cooling/Program Dry Operation ..................... 49
41 .....................................................................44 Heating ........................................................... 51
43 .....................................................................44 Operation, Stop and Thermostat Control .............. 65
44 .....................................................................44 Optimal Operation Condition ................................. 77
45 .....................................................................44 Outdoor Unit Fan Control (Heating Overload
Malfunction Code Frosting Prevention Control) .......................... 71
A1 ....................................................................96 Outdoor Unit Fan Tap ........................................... 67
A3 ....................................................................96 Outdoor Unit Identification Function ...................... 63
A6 ....................................................................96
A7 ....................................................................96 3
AJ ....................................................................96 Present Model’s Functions ...................................... 4
C4 ....................................................................96 Procedure of Self-Diagnosis by LED ..................... 97
C9 ....................................................................96 Procedure of Self-Diagnosis
E0 ....................................................................96 by Remote Controller ..................................... 92
E1 ....................................................................96
E3 ....................................................................96 5
E4 ....................................................................96 Refrigerant Saturation Curve ................................ 79
E9 ....................................................................96 Remote Controller Display Malfunction Code
F3 ....................................................................96 and Contents .................................................. 96
H3 ....................................................................96 Removal of 4-Way Valve and Coil ....................... 187
H4 ....................................................................96 Removal of Air Filter ............................ 130, 153, 163
H9 ....................................................................96 Removal of Air Filter and Suction Grille .............. 142
J3 .....................................................................96 Removal of Air Flow Control Blade ..................... 162
J5 .....................................................................96 Removal of Bottom Panel and Drain Pan ........... 149
J6 .....................................................................96 Removal of Compressor ..................................... 188
PJ ....................................................................96 Removal of Decoration Cover ............................. 131
U0 ....................................................................96 Removal of Decoration Panel ............................. 132
U1 ....................................................................96 Removal of Drain Pan ......................... 139, 158, 169
U4 ....................................................................96 Removal of Drain Pump ...................................... 160
U5 ....................................................................96 Removal of Drain Pump and Drain Hose ............ 140
U8 ....................................................................96 Removal of Electric Parts
UA ....................................................................96 and Remote Controller ................................. 175
UC ...................................................................96 Removal of Electrical Parts and PC Boards ........ 143
Malfunction Code and LED Display Table .............99 Removal of Electrical Parts Box .................. 165, 184
Malfunction Hysteresis ...........................................44 Removal of Electronic Expansion Valve
Malfunction of Discharge Pipe Temperature and Solenoid Valve ...................................... 186
Sensor System ..............................................115 Removal of External Casing ................................ 180
Malfunction of Drain Water Level System Removal of Fan ................................................... 155
(Float Type) ...................................................102 Removal of Fan Bearing ..................................... 148
Malfunction of Electronic Expansion Valve ..........111 Removal of Fan Motor ................. 128, 138, 157, 168
Malfunction of Heat Exchange Removal of Fan Rotor ......................................... 172
Temperature Sensor System ........................106 Removal of Fan Rotor an Motor .......................... 146
Malfunction of Heat Exchanger Removal of Fan Rotor and Fan Motor ................. 177
Temperature Sensor System ........................116 Removal of Heat Exchanger ....................... 171, 179
Malfunction of High Pressure Switch ...................113 Removal of Horizontal Blade ............................... 145
Malfunction of Outdoor Removal of Horizontal Vane ............................... 133
Temperature Sensor System ........................114 Removal of Outdoor Unit Fan and Fan Motor ..... 181
Malfunction of Suction Air Removal of Outdoor Unit PC Board .................... 183
Temperature Sensor System ........................107 Removal of PC Board ......................................... 166
Malfunction of Transmission Removal of Slide Panel, Operation Display Cover,
(Between Indoor and Outdoor Unit) ..............119 and Front Grille ........................................... 164
Malfunction of Transmission (Between Removal of Suction Grille ............................ 129, 154
Indoor Unit and Remote Controller) ..............121 Removal of Suction Grille and Air Filter .............. 173
Method of Field Set ................................................18 Removal of Swing Louvre Unit ............................ 167
Multiple Settings .....................................................27 Removal of Swing Motor ............. 135, 152, 161, 178
Removal of Switch Box Cover ..................... 127, 137
ii Index
Si-71A
6
Safety Cautions ...................................................... vii
Self-Diagnosis by Wired Remote Controller ...........93
Sensor Date Display ..............................................44
Settings Concerning Maintenance .........................30
Simulated Operation Function ................................67
Solenoid Valve Control in Cooling Operation .........69
Standard Conditions ...............................................77
Swing Flap Motor Malfunction / Lock ...................104
7
T2 Disconnection Thermostat OFF Control ...........66
The INSPECTION/TEST Button ............................92
Thermistor Temperature
and Resistance Conversion Table ..................61
Thermostat Control ................................................62
Troubleshooting Based on Equipment Condition
After Equipment Shuts Down,
It cannot be Restarted for a While. .....85
Cooling/Heating Operation Starts
but Stops Immediately. .......................84
Equipment Discharges Dust. ...........................90
Equipment Discharges White Mist ...................88
Equipment does not Operate ...........................82
Equipment Operates but does not
Provide Cooling. .................................86
Equipment Operates but does not
Provide Heating. .................................87
Equipment Produces Loud Noise or Shakes ...89
Fan Operates, but Compressor does not. .......83
Remote Controller LCD Displays "88". ............91
Troubleshooting by LED on The Indoor Unit’s .......97
Troubleshooting by LED
on The Outdoor Unit’s PC Board ....................97
Troubleshooting by Remote Controller Display /
LED Display ....................................................98
8
U0 .........................................................................117
U1 .........................................................................118
U4 .........................................................................119
U5 .........................................................................121
U8 .........................................................................122
UA ........................................................................123
Unit No. Change .....................................................44
Urtra-Long-Life Filter Sign Setting ..........................28
:
Wired Remote Controller ........................................10
Wireless Address Switch (SS2) .............................25
Wireless Remote Controller ...................................12
Wireless Setting
(Address and MAIN/SUB Setting) ...................25
Index iii
Si-71A
iv Index
Si-71A
'UDZLQJV#)#)ORZ#&KDUWV
1XPHULFV How to Handle Request for Maintenance ............. 80
4-way Valve Control ...............................................65
,
$ Indoor Unit Fan Motor Lock ................................. 103
Actuation of Safety Device ...................................108
After Setting ...........................................................27 /
Lack of Gas Malfunction ...................................... 117
& Low Pressure System (LPS) Malfunction ............ 110
Centralized Group No. Setting
by Remote Controller. .....................................29 0
Compressor Shutdown Operation ..........................65 MAIN/SUB CHANGEOVER SWITCH ................... 28
Cooling Start Control ..............................................67 Main/Sub Setting
When Using 2 Remote Controllers ................ 28
' MAIN/SUB Switch (SS1) ....................................... 25
Defrosting Maintenance Inspections ...................................... 77
Control .............................................................73 Malfunction of Discharge Pipe
Defrost complete condition ..............................73 Temperature Sensor System ....................... 115
Heating total capacity ......................................72 Malfunction of Drain Water Level System
Temperature conditions ...................................73 (Float Type) .................................................. 102
DIP Switch and BS Detail ......................................42 Malfunction of Electronic Expansion Valve ......... 111
Discharge Pipe Temperature Malfunction ............112 Malfunction of Heat Exchange
Temperature Sensor System ....................... 106
( Malfunction of Heat Exchanger
Emergency Operation ............................................66 Temperature Sensor System ....................... 116
Example of Remote Controller Display ..................44 Malfunction of High Pressure Switch .................. 113
Malfunction of Outdoor
) Temperature Sensor System ....................... 114
Failure of Capacity Setting ...................................105 Malfunction of Suction Air
Failure of Field Setting Switch .............................123 Temperature Sensor System ....................... 107
Failure of Indoor Unit PC Board ...........................101 Malfunction of Transmission
Fan Control ............................................................69 (Between Indoor and Outdoor Unit)
Fan Start Control in Heating Operation ..................70 Troubleshooting 1 ......................................... 119
Fault Diagnosis by Wireless Remote Controller .....94 Troubleshooting 2 ......................................... 120
Field Setting Malfunction of Transmission (Between
Wired Remote Controller .................................19 Indoor Unit and Remote Controller) ............. 121
Wireless Remote Controller .............................20 Method of switching in time of emergency ............ 43
Freeze Prevention Control .............................. 63, 68 Multiple Settings .................................................... 27
Function Details
Draft Avoidance Control 1 ...............................62 1
Draft Avoidance Control 2 ...............................63 No. of Connected Twin System Indoor Units ........ 24
Thermostat Control ..........................................62
Function Outline 2
FH(Y)C, FH(Y), FAY, FUY ...............................46 Operation Flowchart (RY71 - 140K)
FH(Y)K, FH(Y)B, FHY~F, FVY~L ....................47 Cooling/Program Dry Operation ..................... 49
Outdoor unit .....................................................48 Heating ........................................................... 51
Outdoor Unit Fan Control (Heating Overload
* Frosting Prevention Control) .......................... 71
Group No. Setting Example ...................................29 Outdoor Unit Switches / Setting Jumper
RY100·125K ................................................... 40
+ RY140K .......................................................... 41
High Pressure Protection Control
in Cooling Operation .......................................67 5
High Pressure Protection Control Refrigerant Saturation Curve ................................ 79
in Heating Operation .......................................70 Removal of 4-Way Valve and Coil ...................... 187
High Pressure System (HPS) Malfunction ...........109 Removal of Air Filter ............................ 130, 153, 163
Removal of Air Filter and Suction Grille ...............142 Equipment Operates but does not
Removal of Air Flow Control Blade ......................162 Provide Cooling. ................................ 86
Removal of Bottom Panel and Drain Pan ............149 Equipment Operates but does not
Removal of Compressor ......................................188 Provide Heating. ................................ 87
Removal of Decoration Cover ..............................131 Equipment Produces Loud Noise or Shakes .. 89
Removal of Decoration Panel ..............................132 Fan Operates, but Compressor does not. ...... 83
Removal of Drain Pan ......................... 139, 158, 169 Remote Controller LCD Displays "88". ........... 91
Removal of Drain Pump .......................................160
Removal of Drain Pump and Drain Hose .............140 :
Removal of Electric Parts Wireless Address Switch (SS2) ............................ 25
and Remote Controller ..................................175
Removal of Electrical Parts and PC Boards .........143
Removal of Electrical Parts Box .................. 165, 184
Removal of Electronic Expansion Valve
and Solenoid Valve .......................................186
Removal of External Casing ................................180
Removal of Fan ....................................................155
Removal of Fan Bearing ......................................148
Removal of Fan Motor ................ 128, 138, 157, 168
Removal of Fan Rotor ..........................................172
Removal of Fan Rotor an Motor ...........................146
Removal of Fan Rotor and Fan Motor ..................177
Removal of Heat Exchanger ....................... 171, 179
Removal of Horizontal Blade ...............................145
Removal of Horizontal Vane ................................133
Removal of Outdoor Unit Fan and Fan Motor ......181
Removal of Outdoor Unit PC Board .....................183
Removal of PC Board ..........................................166
Removal of Slide Panel, Operation Display Cover,
and Front Grille ............................................164
Removal of Suction Grille ........................... 129, 154
Removal of Suction Grille and Air Filter ...............173
Removal of Swing Louvre Unit .............................167
Removal of Swing Motor ............. 135, 152, 161, 178
Removal of Switch Box Cover ..................... 127, 137
Reverse Phase ....................................................118
6
Self-Diagnosis by Wired Remote Controller ...........93
Setting from the remote controller ..........................26
Setting The Address of
Wireless Remote Controller ............................26
Setting The Receiver .............................................25
Solenoid Valve Control
(In the Case of R(Y)140 K) .............................70
Solenoid Valve Control in Cooling Operation .........69
Swing Flap Motor Malfunction / Lock ...................104
7
The INSPECTION/TEST Button ............................92
Thermostat Control ................................................65
Transmission Error Between Main Remote
Controller and Sub Remote Controller ..........122
Troubleshooting Based on Equipment Condition
After Equipment Shuts Down,
It cannot be Restarted for a While. .....85
Cooling/Heating Operation Starts
but Stops Immediately. .......................84
Equipment Discharges Dust. ...........................90
Equipment Discharges White Mist ...................88
Equipment does not Operate ...........................82
l For further improvement, specifications or designs are subject to change without prior notice.