Utility:

MVAsc = 1000MVA
Transformer 1:
MVAsc = 170 / 0.15 = 1133.33 MVA

MVAsc @ 150KV = 1000 MVA 13.8KV Bus


Generator:
MVAsc = 100 / 0.2 = 500 MVA
1/ (1 / 1000 + 1 /1133.33) = 531.25 MVA 500 MVA
Transnformer 2:
MVAsc = 30 / 0.15 = 200 MVA
531.25 + 500 = 1031.25 MVA

6.6KV Bus
Transformer 3:
MVAsc = 2 / 0.1 = 20 MVA
1/ (1 / 1031.25 + 1 / 200) = 167.51 MVA Motor 1:
MVAsc = 10 / 0.2 = 50 MVA

167.51 + 50 = 217.51 MVA


50 MVA

1/ (1 / 217.51 + 1 / 20) = 18.31 MVA


400V Bus 18.31 + 5 + 6 = 29.31MVAsc
Motor 2:
MVAsc = 1 / 0.2 = 5 MVA The three phase
If = 29.31/(1.732*(0.4)) = 42.3 kA.
Motor 3: 5 MVA 6 MVA
MVAsc = 0.6 / 0.1 = 6 MVA