Fmr67 Manual
Fmr67 Manual
Operating Instructions
Micropilot FMR67
HART
Free space radar
Micropilot FMR67 HART
Serial number
2. www.endress.com/deviceviewer Endress+Hauser
Operations App
3.
A0023555
2 Endress+Hauser
Micropilot FMR67 HART Table of contents
Table of contents
Endress+Hauser 3
Table of contents Micropilot FMR67 HART
14 Maintenance . . . . . . . . . . . . . . . . . . . . . . 85
14.1 Exterior cleaning . . . . . . . . . . . . . . . . . . . . . . 85
14.2 Replacing seals . . . . . . . . . . . . . . . . . . . . . . . 85
4 Endress+Hauser
Micropilot FMR67 HART Important document information
1.2 Symbols
Symbol Meaning
DANGER!
DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will
result in serious or fatal injury.
WARNING!
WARNING This symbol alerts you to a dangerous situation. Failure to avoid this situation can
result in serious or fatal injury.
CAUTION!
CAUTION This symbol alerts you to a dangerous situation. Failure to avoid this situation can
result in minor or medium injury.
NOTE!
NOTICE This symbol contains information on procedures and other facts which do not result in
personal injury.
Symbol Meaning
Direct current
Alternating current
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a
grounding system.
Symbol Meaning
Torx screwdriver
A0013442
A0011220
Endress+Hauser 5
Important document information Micropilot FMR67 HART
Symbol Meaning
Cross-head screwdriver
A0011219
Allen key
A0011221
Hexagon wrench
A0011222
Symbol Meaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation.
A Reference to page.
Reference to graphic.
1. , 2. , 3. … Series of steps.
Result of a step.
Visual inspection.
Symbol Meaning
1. , 2. , 3. … Series of steps
A, B, C, ... Views
Hazardous area
- Indicates a hazardous area.
6 Endress+Hauser
Micropilot FMR67 HART Important document information
Symbol Meaning
Safety instructions
Observe the safety instructions contained in the associated Operating Instructions.
1.3 Documentation
Document Purpose and content of the document
Brief Operating Instructions Guide that takes you quickly to the 1st measured value
KA01253F The Brief Operating Instructions contain all the essential information
from incoming acceptance to initial commissioning.
For an overview of the scope of the associated Technical Documentation, refer to the
following:
• The W@M Device Viewer: enter the serial number from the nameplate
(www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate
or scan the 2-D matrix code (QR code) on the nameplate.
Endress+Hauser 7
Important document information Micropilot FMR67 HART
PN Nominal pressure
FieldCare Scalable software tool for device configuration and integrated plant asset management
solutions
Operating tool The term "operating tool" is used in place of the following operating software:
• FieldCare / DeviceCare, for operation via HART communication and PC
• SmartBlue (app), for operation using an Android or iOS smartphone or tablet.
8 Endress+Hauser
Micropilot FMR67 HART Important document information
Endress+Hauser 9
Basic safety instructions Micropilot FMR67 HART
Residual risks
Due to heat transfer from the process as well as power loss in the electronics, the
temperature of the electronics housing and the assemblies it contains (e.g. display module,
main electronics module and I/O electronics module) may rise to 80 °C (176 °F). When in
operation, the sensor may reach a temperature close to the medium temperature.
Danger of burns from contact with surfaces!
‣ For elevated fluid temperature, ensure protection against contact to prevent burns.
10 Endress+Hauser
Micropilot FMR67 HART Basic safety instructions
NOTICE
Loss of degree of protection by opening of the device in humid environments
‣ If the device is opened in a humid environment, the degree of protection indicated on
the nameplate is no longer valid. This may also impair the safe operation of the device.
2.5.1 CE mark
The measuring system meets the legal requirements of the applicable EC guidelines. These
are listed in the corresponding EC Declaration of Conformity together with the standards
applied.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
Endress+Hauser 11
Basic safety instructions Micropilot FMR67 HART
BC ATEX II 1/2G Ex ia/db [ia Ga] IIC T6 Ga/Gb XA01552F XA01552F XA01552F
BD ATEX II 1/2/3G Ex ia/ic [ia Ga] IIC T6 Ga/Gb/Gc XA01550F XA01550F XA01550F
4) 4)
BE ATEX II 1D Ex ta IIIC Da * * * 4)
BL ATEX II 1/2/3G Ex ia/ec [ia Ga] IIC T6 Ga/Gb/Gc XA01550F XA01550F XA01550F
B2 ATEX II 1/2G Ex ia IIC T6 Ga/Gb, 1/2D Ex ia IIIC T85°C Da/Db XA01555F XA01555F XA01555F
B3 ATEX II 1/2G Ex ia/db [ia Ga] IIC T6, Ga/Gb 1/2D Ex ta/tb IIIC T85°C Da/Db XA01556F XA01556F XA01556F
CD CSA DIP Cl.II,III Div.1 Gr.E-G [Ex ia] XA01613F XA01613F XA01613F
C2 CSA IS Cl.I,II,III Div.1 Gr.A-G, Ex ia, NI Cl.1 Div.2 [Ex ia] XA01612F XA01612F XA01612F
C3 CSA XP Cl.I,II,III Div.1 Gr.A-G, Zn0/1, NI Cl.I Div.2 [Ex ia] XA01613F XA01613F XA01613F
FB FM IS Cl.I,II,III Div.1 Gr.A-G, AEx ia, NI Cl.1 Div.2 XA01615F XA01615F XA01615F
FC FM XP-IS Cl.I Div.1 Gr.A-D, AIS Cl.I Div.1 Gr.A-D XA01616F XA01616F XA01616F
FD FM XP-IS Cl.I Div.1 Gr.A-D, Zn0/1, DIP-IS Cl.II,III Div.1 Gr.E-G, NI Cl.I Div.2 XA01616F XA01616F XA01616F
GC EAC Ga/Gb Ex ia/db [ia Ga] IIC T6...T3 X XA01618F XA01618F XA01618F
4) 4)
GE EAC Ex ta IIIC Da * * * 4)
I3 IEC Ex ia/db [ia Ga] IIC T6 Ga/Gb, Ex ta/tb IIIC T85°C Da/Db XA01556F XA01556F XA01556F
4) 4)
JA JPN Ex ia IIC T6 Ga XA01631F XA01631F XA01631F 4)
12 Endress+Hauser
Micropilot FMR67 HART Basic safety instructions
J2 JPN Ex ia IIC T6 Ga/Gb, JPN Ex ia IIIC T85°C Da/Db XA01728F 4) XA01728F 4) XA01728F 4)
J3 JPN Ex d [ia] IIC T6 Ga/Gb, JPN Ex ta/tb IIIC T85°C Da/Db XA01729F 4) XA01729F 4) XA01729F 4)
N2 NEPSI Ex ia IIC T6 Ga/Gb, NEPSI Ex iaD 20/21 T85 XA01629F XA01629F XA01629F
N3 NEPSI Ex ia/d [ia Ga] IIC T6 Ga/Gb, NEPSI Ex tD A20/A21 IP6X T85°C XA01630F XA01630F XA01630F
8A FM/CSA IS+XP-IS Cl.I,II,III Div.1 Gr.A-G, AIS Cl.I,II,III Div.1 Gr.A-G XA01612F XA01612F XA01612F
XA01615F XA01615F XA01615F
XA01616F XA01616F XA01616F
* 4)
Endress+Hauser 13
Product description Micropilot FMR67 HART
3 Product description
3 3 3
2.1 2.2
2.2
1 1 1
A0032714
3 3 3
4 4 4
2.1
2.2
2.3
1 1
1
A0032782
14 Endress+Hauser
Micropilot FMR67 HART Product description
4
3
2
9
1
6
7
8
A0012422
Endress+Hauser 15
Incoming acceptance and product identification Micropilot FMR67 HART
16 Endress+Hauser
Micropilot FMR67 HART Incoming acceptance and product identification
4.2.1 Nameplate
92 (3.62)
2
1
Order code: 3 10
Ser. no.: 4
Ext. ord. cd.: 8
5
26
47 (1.85)
25
Tp max = 24 MWP: 6 9
23 LN = 7
Ta: 22 15
Mat.: 21
20
FW: 18 Dev.Rev.: 16 11
if modification
19 17 13 X = see sep. label
12
Date: 14
mm (in)
A0019444
Up to 33 characters of the extended order code are indicated on the nameplate. If the
extended order code contains additional characters, these cannot be displayed.
However, the complete extended order code can also be displayed via the device
operating menu: Extended order code 1 to 3 parameter
Endress+Hauser 17
Storage, Transport Micropilot FMR67 HART
5 Storage, Transport
A0032300
18 Endress+Hauser
Micropilot FMR67 HART Installation
6 Installation
1 2 3
A0016883
• Recommended distance A wall - nozzle outer edge: ~ 1/6 of the container diameter.
However, the device must not under any circumstances be mounted closer than
20 cm (7.87 in) to the container wall.
If the container wall is not smooth (corrugated iron, welding seams, joints, etc.) it is
recommended to maintain the largest possible distance from the wall. Where necessary
use an alignment unit to avoid interference reflections from the container wall
→ 25.
• Not in the center (2) as interference can cause signal loss.
• Not above the filling curtain (3).
• The use of a weather protection cover (1) is recommended to protect the transmitter
from direct sunlight or rain.
• In applications with strong dust emissions, the integrated purge air connection can
prevent the antenna from becoming clogged .
Endress+Hauser 19
Installation Micropilot FMR67 HART
A0031814
Avoid the location of internal fittings (limit switches, temperature sensors, struts etc.)
inside the signal beam. Take into account the beam angle .
20 Endress+Hauser
Micropilot FMR67 HART Installation
A0031817
Metal deflector plates, installed at an angle to scatter the radar signals, help prevent
interference echoes.
Endress+Hauser 21
Installation Micropilot FMR67 HART
α
W= 2 . D . tan_
2
D
α
W
A0031824
The beam angle is defined as the angle α where the energy density of the radar waves
reaches half the value of the maximum energy density (3dB width). Microwaves are also
emitted outside the signal beam and can be reflected off interfering installations.
22 Endress+Hauser
Micropilot FMR67 HART Installation
FMR67
A0032084
A0032083
Beam angle α 6° 4°
Endress+Hauser 23
Installation Micropilot FMR67 HART
1) or an integer that is a multiple of this value; it should be noted here that the microwave transparency
decreases significantly with increasing window thickness.
øD
A0032209
24 Endress+Hauser
Micropilot FMR67 HART Installation
Note the following if the antenna does not project out of the nozzle:
• The end of the nozzle must be smooth and free from burrs. The edge of the nozzle
should be rounded if possible.
• Mapping must be performed.
• Please contact Endress+Hauser for applications with nozzles that are higher than
indicated in the table.
Process connection with UNI flange Material Pressure rating Suitable for
Alignment unit 1)
XCA UNI 4" / DN100 / 100A Aluminum max. 14.5lbs / PN1 / 1K • 4" 150lbs
• DN100 PN16
• 10K 100A
XDA UNI 6" / DN150 / 150A Aluminum max. 14.5lbs / PN1 / 1K • 6" 150lbs
• DN150 PN16
• 10K 150A
XEA UNI 8" / DN200 / 200A Aluminum max. 14.5lbs / PN1 / 1K • 8" 150lbs
• DN200 PN16
• 10K 200A
XFA UNI 10" / DN250 / 250A Aluminum max. 14.5lbs / PN1 / 1K • 10" 150lbs
• DN250 PN16
• 10K 250A
Endress+Hauser 25
Installation Micropilot FMR67 HART
A0032097
øD
A0032206
26 Endress+Hauser
Micropilot FMR67 HART Installation
Note the following if the antenna does not project out of the nozzle:
• The end of the nozzle must be smooth and free from burrs. The edge of the nozzle
should be rounded if possible.
• Mapping must be performed.
• Please contact Endress+Hauser for applications with nozzles that are higher than
indicated in the table.
A None
A0032098
Endress+Hauser 27
Installation Micropilot FMR67 HART
1 1
A0032099
6.4.3 Use
In applications with strong dust emissions, the integrated purge air connection can prevent
the antenna from becoming clogged. Pulse operation is recommended.
Purge air pressure range
• Pulse operation :
Max. 6 bar (87 psi)
• Continuous operation:
200 to 500 mbar (3 to 7.25 psi)
Purge air connection
• Tool:
– Open-ended wrench 13 mm (G 1/4")
– Open-ended wrench 14 mm (NPT)
– Open-ended wrench 17 mm (NPT "adapter")
• remains stable for a minimum of torque: 6 Nm (4.4 lbf ft)
• Max. torque: 7 Nm
Always use dry purge air.
A0032207
28 Endress+Hauser
Micropilot FMR67 HART Installation
If process temperatures are high, the device should be included in the usual container
insulation system (2) to prevent the electronics from heating as a result of thermal
radiation or convection. The insulation should not be higher than the neck of the device
(1).
2.
max. 350°
1. 3.
8 mm 8 mm
A0032242
2.
1.
3 mm
A0021430
1. Loosen the screw of the securing clamp of the electronics compartment cover using
an Allen key (3 mm) and turn the clamp 90 ° counterclockwise.
2. Unscrew cover and check lid gasket, replace if necessary.
Endress+Hauser 29
Installation Micropilot FMR67 HART
2.
1.
A0036401
1.
3 mm
2. 2,5 Nm
A0021451
Are the measuring point identification and labeling correct (visual inspection)?
30 Endress+Hauser
Micropilot FMR67 HART Electrical connection
7 Electrical connection
A B
+
1 1 -
2 2
+
-
1 3
A0036498
3 4
2 5
1 6
+ + 1
I
- - 2
A0036499
Endress+Hauser 31
Electrical connection Micropilot FMR67 HART
3
4
A B
+
3 3 -
4 4
+ +
- 1 -
2 1
+ 2
-
2
1 5
A0036500
3 4
2 5
1 6
+ + 1
I
- - 2
+ 3 Y
- 4
7
A0036501
32 Endress+Hauser
Micropilot FMR67 HART Electrical connection
3
4
A B
+
3 3 -
4 4
+ +
- 1 -
2 1
+ 2
-
2
1 5
A0036500
3 4
2 5
1 6
+ + 1
I
- - 2
+ + 3 Y
- - 4
7
8
A0036502
Endress+Hauser 33
Electrical connection Micropilot FMR67 HART
+
3+ 1
2
Ri + 3+
-
Ri
4-
A0015909
4-
13 Connection of a relay A0015910
HART
• A normal device cable suffices if only the analog signal is used.
• A shielded cable is recommended if using the HART protocol. Observe grounding concept
of the plant.
34 Endress+Hauser
Micropilot FMR67 HART Electrical connection
2 not connected
1 2 3 Signal -
A0011175
4 Ground
2 Signal +
2 4 3 Not connected
A0011176
4 Screen
Endress+Hauser 35
Electrical connection Micropilot FMR67 HART
A: • Non- 14 to 35 V 3) R [W]
2-wire; hazardous
4-20 mA • Ex nA 500
HART • Ex ic
• CSA GP
Ex ia / IS 14 to 30 V 3)
• Ex d(ia) / 14 to 35 V 3) 4)
XP
• Ex ic(ia) 0
• Ex nA(ia) 10 20 30 35 U0 [V]
• Ex ta / DIP 14 25
A0031745
Ex ia + Ex 14 to 30 V 3)
d(ia) / IS + XP
B: • Non- 16 to 35 V 3) R [W]
2-wire; hazardous
4-20 mA • Ex nA 500
HART, • Ex nA(ia)
switch • Ex ic
outpu • Ex ic(ia)
• Ex d(ia) / XP
• Ex ta / DIP
• CSA GP
0
• Ex ia / IS 16 to 30 V 3)
• Ex ia + Ex 10 20 30 35 U0 [V]
16 27
d(ia) / IS + A0031746
XP
36 Endress+Hauser
Micropilot FMR67 HART Electrical connection
C: All 16 to 30 V 3) R [W]
2-wire; 4-20
mA HART, 500
4-20 mA
0
10 20 30 35 U0 [V]
16 27
A0031746
Technical data
Endress+Hauser 37
Electrical connection Micropilot FMR67 HART
Required tools/accessories:
• For devices with a cover lock: Allen key AF3
• Wire stripper
• When using stranded cables: One ferrule for every wire to be connected.
2.
3 mm
1.
A0021490
1. Loosen the screw of the securing clamp of the connection compartment cover using
an Allen key (3 mm) and turn the clamp 90 ° clockwise.
2. Afterwards unscrew connection compartment cover and check lid gasket, replace if
necessary.
38 Endress+Hauser
Micropilot FMR67 HART Electrical connection
Connecting
1.
3.
10 (0.4)
2.
3.
10 (0.4)
A0036418
15 Dimensions: mm (in)
1. Push the cable through the cable entry . To ensure tight sealing, do not remove the
sealing ring from the cable entry.
2. Remove the cable sheath.
3. Strip the cable ends over a length of 10 mm (0.4 in). In the case of stranded cables,
also fit ferrules.
4. Firmly tighten the cable glands.
5. Connect the cable in accordance with the terminal assignment.
34
1
2
3
4
1
2
A0034682
6. If using shielded cables: Connect the cable shield to the ground terminal.
Endress+Hauser 39
Electrical connection Micropilot FMR67 HART
1. 2.
≤ 3 (0.12)
A0013661
16 Dimensions: mm (in)
1.
3 mm
2. 2,5 Nm
A0021491
If supply voltage is present, is the device ready for operation and do values appear on the display
module?
40 Endress+Hauser
Micropilot FMR67 HART Operation options
8 Operation options
8.1 Overview
A0036312 A0036313
Format for displaying measured variables and status variables can be individually configured
Permitted ambient temperature for the display: –20 to +70 °C (–4 to +158 °F)
The readability of the display may be impaired at temperatures outside the temperature
range.
Operating local operation with 3 push buttons (, , ) external operation via touch control; 3
elements optical keys: , ,
Endress+Hauser 41
Operation options Micropilot FMR67 HART
1 2
A0036314
42 Endress+Hauser
Micropilot FMR67 HART Operation options
Requirements
2
A0036790
This operation option is only available for devices with Bluetooth module. There are the
following options:
• The device has been ordered with a Bluetooth module:
Feature 610 "Accessory Mounted", option NF "Bluetooth"
• The Bluetooth module has been ordered as an accessory (ordering number: 71377355)
and has been mounted. See Special Documentation SD02252F.
1 2 3
A0034939
Endress+Hauser 43
Operation options Micropilot FMR67 HART
2 3 6 8
1 4 5 7
A0036169
1
A0032466
44 Endress+Hauser
Micropilot FMR67 HART Operation options
Endress+Hauser 45
Operation options Micropilot FMR67 HART
1) If operating via operating tools (e.g. FieldCare), the "Language" parameter is located under "Setup →
Advanced setup → Display"
2) Only if operating via an FDT/DTM system
3) only available with local operation
4) only available if operating via DeviceCare or FieldCare
5) On entering the "Expert" menu, an access code is always requested. If a customer specific access code has
not been defined, "0000" has to be entered.
46 Endress+Hauser
Micropilot FMR67 HART Operation options
Without access With access code Without access With access code
code code
(from the factory) (from the factory)
Operator --
Maintenance
If an incorrect access code is entered, the user obtains the access rights of the Operator
role.
The user role with which the user is currently logged on is indicated by the Access
status display parameter (for display operation) or Access status tooling parameter
(for tool operation).
Endress+Hauser 47
Operation options Micropilot FMR67 HART
The locking of the write access via local operation can be disabled by entering the device-
specific access code.
1. After you press , the input prompt for the access code appears.
2. Enter the access code.
The -symbol in front of the parameters disappears; all previously write-
protected parameters are now re-enabled.
48 Endress+Hauser
Micropilot FMR67 HART Operation options
ON
CDI WP OFF
XXXXXXXXXXXXX 4. WP
2. 3.
3 mm
1.
A0026157
A0036086
Endress+Hauser 49
Operation options Micropilot FMR67 HART
4. Setting the write protection switch (WP) on the main electronics module to the ON
position enables hardware write protection. Setting the write protection switch (WP)
on the main electronics module to the OFF position (factory setting) disables
hardware write protection.
If the hardware write protection is enabled: The Hardware locked option is
displayed in the Locking status parameter. In addition, on the local display the
-symbol appears in front of the parameters in the header of the operational
display and in the navigation view.
XXXXXXXXX
20.50
XX XX
A0015870
50 Endress+Hauser
Micropilot FMR67 HART Operation options
If the user attempts to access the operating menu while the keypad lock is active, the
message Keylock on appears.
Endress+Hauser 51
Operation options Micropilot FMR67 HART
2
1 2.1
2.3
2.2
1.1 2.6 2.4
1.3 2.5
OPEN
OPEN
1.2 3
ESC
1.4
3.1
E
3.2
5 4
User 20
ABC_
0 1 2 3 4
DEFG HIJK
LMNO PQRS TUVW 5 6 7 8 9
XYZ Aa1
A0012635
52 Endress+Hauser
Micropilot FMR67 HART Operation options
Symbol Meaning
Display/operation
Is displayed:
• in the main menu next to the selection "Display/operation"
A0018367
• in the header, if you are in the "Display/operation" menu
Setup
Is displayed:
• in the main menu next to the selection "Setup"
A0018364
• in the header, if you are in the "Setup" menu
Expert
Is displayed:
• in the main menu next to the selection "Expert"
A0018365
• in the header, if you are in the "Expert" menu
Diagnostics
Is displayed:
• in the main menu next to the selection "Diagnostics"
A0018366
• in the header, if you are in the "Diagnostics" menu
Status signals
"Failure"
A0032902
A device error is present. The measured value is no longer valid.
"Function check"
A0032903
The device is in service mode (e.g. during a simulation).
"Out of specification"
The device is operated:
S • Outside of its technical specifications (e.g. during startup or a cleaning)
A0032904
• Outside of the configuration carried out by the user (e.g. level outside configured
span)
"Maintenance required"
A0032905
Maintenance is required. The measured value is still valid.
Symbol Meaning
Display parameter
Marks display-only parameters which can not be edited.
A0013148
Device locked
• In front of a parameter name: The device is locked via software and/or hardware.
A0013150
• In the header of the measured value screen: The device is locked via hardware.
Endress+Hauser 53
Operation options Micropilot FMR67 HART
Symbol Meaning
Measured values
Level
A0032892
Distance
A0032893
Current output
A0032908
Measured current
A0032894
Terminal voltage
A0032895
A0032896
Measuring channels
Measuring channel 1
1
A0032897
Measuring channel 2
2
A0032898
Status "Alarm"
The measurment is interrupted. The output assumes the defined alarm value. A
A0018361 diagnostic message is generated.
Status "Warning"
The device continues measuring. A diagnostic message is generated.
A0018360
54 Endress+Hauser
Micropilot FMR67 HART Operation options
Key Meaning
Minus key
For menu, submenu
Moves the selection bar upwards in a picklist.
A0018330
For text and numeric editor
In the input mask, moves the selection bar to the left (backwards).
Plus key
For menu, submenu
Moves the selection bar downwards in a picklist.
A0018329
For text and numeric editor
In the input mask, moves the selection bar to the right (forwards).
Enter key
For measured value display
• Pressing the key briefly opens the operating menu.
• Pressing the key for 2 s opens the context menu.
For menu, submenu
• Pressing the key briefly
Opens the selected menu, submenu or parameter.
A0018328
• Pressing the key for 2 s for parameter:
If present, opens the help text for the function of the parameter.
For text and numeric editor
• Pressing the key briefly
– Opens the selected group.
– Carries out the selected action.
• Pressing the key for 2 s confirms the edited parameter value.
Minus/Enter key combination (press and hold down the keys simultaneously)
+
A0032910
Reduces the contrast (brighter setting).
Plus/Enter key combination (press and hold down the keys simultaneously)
+
A0032911
Increases the contrast (darker setting).
Endress+Hauser 55
Operation options Micropilot FMR67 HART
1 1
2 20 2 User
0 1 2 3 4 ABC_ DEFG HIJK
5 6 7 8 9 LMNO PQRS TUVW
3 3
XYZ Aa1
4 4
A0013941 A0013999
1 Editing view
2 Display area of the entered values
3 Input mask
4 Operating elements
Input mask
The following input symbols are available in the input mask of the numeric and text editor:
A0016619
Confirms selection.
A0013985
A0016621
A0013986
A0014040
Toggle
Aa1 • Between upper-case and lower-case letters
• For entering numbers
A0013981
• For entering special characters
56 Endress+Hauser
Micropilot FMR67 HART Operation options
Confirms selection.
A0013985
A0013987
A0013986
A0014040
A0032907
A0018324
A0018326
A0032906
Endress+Hauser 57
Operation options Micropilot FMR67 HART
XXXXXXXXXX
Setup
Conf.backup disp
Env. curve 50
Keylock on kg/h
A0033110-EN
2. Press + simultaneously.
The context menu is closed and the operational display appears.
58 Endress+Hauser
Micropilot FMR67 HART Operation options
E (2s)
2x +
E -
+ + -
+
+
E
+ + -
A0014277
Endress+Hauser 59
System integration via HART protocol Micropilot FMR67 HART
The allocation of the device variables can be changed in the operating menu:
Expert → Communication → Output
In a HART multidrop loog only one device may use the output current for signal
transmission. For all other devices the follwing must be set:
• "Current span" parameter = "Fixed current" option
• "Fixed current" parameter = 4 mA
60 Endress+Hauser
Micropilot FMR67 HART Commissioning via SmartBlue (app)
10.1 Requirements
Device requirements
Commissioning via SmartBlue is only possible if the device has a Bluetooth module.
System requirements SmartBlue
SmartBlue is available as download for Android devices from the Google Play Store and for
iOS devices from the iTunes Store.
• iOS devices:
iPhone 4S or higher from iOS9.0; iPad2 or higher from iOS9.0; iPod Touch 5th
generation or higher from iOS9.0
• Devices with Android:
from Android 4.4 KitKat and Bluetooth® 4.0
Initial password
The ID of the Bluetooth module serves as the initial password used to establish the first
connection to the device. It can be found:
• on the information sheet which is supplied with the device. This serial number specific
sheet is also stored in W@M.
• on the nameplate of the Bluetooth module.
2
A0036790
All login data (including the password changed by the user) are not stored in the
device but in the Bluetooth module. This must be taken into account when the module
is removed from one device and inserted into a different device.
10.2 Commissioning
Download and install SmartBlue
1. To download the app, scan the QR code or enter "SmartBlue" in the search field
A0033202
24 Download link
Endress+Hauser 61
Commissioning via SmartBlue (app) Micropilot FMR67 HART
2. Start SmartBlue
A0029747
25 SmartBlue pictogram
A0029502
26 Livelist
Only one point-to-point connection can be established between one sensor and one
smartphone or tablet.
4. Perform login
admin
A0029503
27 Login
62 Endress+Hauser
Micropilot FMR67 HART Commissioning via SmartBlue (app)
8. By wiping from the side, additional information (e.g. main menu) can be dragged
into the image
A0029504
28 Main menu
2
1 3
5
A0029486
Endress+Hauser 63
Commissioning via SmartBlue (app) Micropilot FMR67 HART
2
1 3
5
A0029487
64 Endress+Hauser
Micropilot FMR67 HART Commissioning via wizard
A0027720
If the wizard is cancelled before all necessary parameters have been set, the device
may be in an undefined state. A reset to the default settings is recommended in this
case.
4) DeviceCare is available for download at www.software-products.endress.com. The download requires a registration in the Endress+Hauser
software portal.
Endress+Hauser 65
Commissioning via operating menu Micropilot FMR67 HART
XXXXXXXXX
20.50
XX XX
Main menu 0104-1
1. Display language
English
Operation
Setup
Display language 0104-1
2. Ã English
Deutsch
Español
Français
Display language 0104-1
3. Ã English
Deutsch
Español
Français
Hauptmenü 0104-1
4. Sprache
Deutsch
Betrieb
Setup
A0029420
66 Endress+Hauser
Micropilot FMR67 HART Commissioning via operating menu
R
BD
100%
D
E F
L
0%
A0016934
Endress+Hauser 67
Commissioning via operating menu Micropilot FMR67 HART
It is strongly recommended to adjust the maximum filling and draining speed to the
actual process.
68 Endress+Hauser
Micropilot FMR67 HART Commissioning via operating menu
Endress+Hauser 69
Commissioning via operating menu Micropilot FMR67 HART
Language English
70 Endress+Hauser
Micropilot FMR67 HART Commissioning via operating menu
Endress+Hauser 71
Commissioning via operating menu Micropilot FMR67 HART
72 Endress+Hauser
Micropilot FMR67 HART Diagnostics and troubleshooting
Device does not respond. Supply voltage does not match Connect the correct voltage.
the value indicated on the
nameplate.
The cables do not contact the Ensure electrical contact between the cable
terminals properly. and the terminal.
Values on the display invisible Contrast setting is too weak or • Increase contrast by pressing and
too strong. simultaneously.
• Decrease contrast by pressing and
simultaneously.
Duplicating of the parameters Display with backup is not Connect display (with the backup) and
from one device to another via recognized if no data backup restart the device.
the display doesn't work. has been performed at the
Only the "Save" and "Abort" device before.
options are available.
HART communication does not Communication resistor Install the communication resistor(250 Ω)
function. missing or incorrectly installed. correctly.
CDI communication does not Wrong setting of the COM port Check the setting of the COM port on the
work. on the computer. computer and change it if necessary.
Device not accessible via No Bluetooth connection Enable Bluetooth function onsmartphone or
SmartBlue tablet.
Login via SmartBlue not Device is being put into Enter initial password (ID of the Bluetooth
possible operation for the first time module) and change.
Device cannot be operated via Incorrect password entered Enter correct password
SmartBlue
Password forgotten Contact Endress+Hauser Service
(www.addresses.endress.com)
Endress+Hauser 73
Diagnostics and troubleshooting Micropilot FMR67 HART
Device is not visible in the No Bluetooth Enable Bluetooth® function on smartphone or tablet
live list connection
Bluetooth® function of sensor disabled, perform
recovery sequence
Device is not visible in the The device is already Only one point-to-point connection is established
live list connected with between a sensor and a smartphone or tablet
another smartphone/
tablet
Device is visible in the live list Android end device Is the location function enabled for the app, was it
but cannot be accessed via approved the first time?
SmartBlue
GPS or positioning function must be activated for
certain Android versions in conjunction with
Bluetooth®
Device is visible in the live list Apple end device Log in as standard
but cannot be accessed via Enter user name "admin"
SmartBlue Enter initial password (ID of the Bluetooth module)
paying attention to lower/upper case
Login via SmartBlue not Device is being put Enter initial password (ID of the Bluetooth module) and
possible into operation for the change; paying attention to lower/upper case
first time
Device cannot be operated via Password forgotten Contact the Endress+Hauser Service department
SmartBlue (www.addresses.endress.com)
Measured value If measured distance (Setup • Check and adjust Empty calibration parameter
incorrect → Distance) matches the real if necessary.
distance: • heck and adjust Full calibration parameter if
Calibration error necessary.
• Check and adjust linearization if necessary
(Linearization submenu).
Level correction set incorrectly Enter correct value in Level correction parameter.
No change of measured Interference echo from • Carry out tank mapping (Confirm distance
value on filling / installations, nozzle or build- parameter).
emptying up on the antenna. • If possible, align antenna in the direction of the
solid surface in order to prevent interference
echoes.
• If necessary, clean antenna (purge air).
• If necessary, select a better mounting position
and/or larger antenna.
74 Endress+Hauser
Micropilot FMR67 HART Diagnostics and troubleshooting
During filling/emptying Signal is weakened (e.g. by • Carry out tank mapping (Confirm distance
or measurement, the fluidisation of the surface, parameter).
measured value jumps extreme dust formation) - the • Increase integration time (Expert → Sensor
sporadically to a higher interference echoes are → Distance → Integration time)
level. sometimes stronger. Strong • Optimize alignment of antenna
build-up, filling stream in path • If necessary, select a better mounting position
of beam. and/or larger antenna.
• If necessary, clean antenna (purge air).
Error message F941 or Level echo is too weak. • Optimize alignment of antenna
S941 "Echo lost" • If necessary, select a better mounting position
Possible causes:
and/or larger antenna.
• Fluidisation of the surface
• Extreme dust formation
• Angle or repose
Device displays a level Interference echo Carry out mapping over entire measuring range
when the tank is empty. when the silo is empty (Confirm distance
parameter).
Wrong slope of the level Bin property or process • Select the correct option in Bin type parameter.
throughout the complete propertis incorrect • Enter the actual values in "Max. filling speed
measuring range solid" parameter and "Max. draining speed
solid" parameter.
Endress+Hauser 75
Diagnostics and troubleshooting Micropilot FMR67 HART
2 1
XXXXXXXXX S XXXXXXXXX S
20.50 S801
Supply voltage
3
4
X XX i Menu
5
A0029426-EN
1 Status signal
2 Status symbol (symbol for event level))
3 Status symbol with diagnostics event
4 Event text
5 Operating elements
Status signals
"Alarm" status
The measurement is interrupted. The signal outputs take on the defined alarm condition.
A diagnostic message is generated.
"Warning" status
The device continues to measure. A diagnostic message is generated.
76 Endress+Hauser
Micropilot FMR67 HART Diagnostics and troubleshooting
Diagnostics event
↓ ↓ ↓
3-digit number
If two or more diagnostic messages are pending simultaneously, only the message with the
highest priority is shown. Additional pending diagnostic messages can be shown in the
Diagnostic list submenu.
Past diagnostic messages that are no longer pending are shown as follows:
• On the local display:
in the Event logbook submenu
• In FieldCare:
via the "Event List /HistoROM" function.
Operating elements
Plus key
Opens the message about the remedial measures.
Enter key
Opens the operating menu.
Endress+Hauser 77
Diagnostics and troubleshooting Micropilot FMR67 HART
XXXXXXXXX S XXXXXXXXX S
20.50 S801
Supply voltage
X XX i Menu
1.
Diagnostic list S
Diagnostics 1
1 S801 Supply voltage
Diagnostics 2
Diagnostics 3
2.
3.
A0029431-EN
The user is in the Diagnostics menu at an entry for a diagnostics event, e.g. in Diagnostic
list submenu or in Previous diagnostics.
1. Press .
The message for the remedial measures for the selected diagnostic event opens.
2. Press + simultaneously.
The message for the remedial measures closes.
78 Endress+Hauser
Micropilot FMR67 HART Diagnostics and troubleshooting
A tool tip with remedial measures for the diagnostic event appears.
Endress+Hauser 79
Diagnostics and troubleshooting Micropilot FMR67 HART
80 Endress+Hauser
Micropilot FMR67 HART Diagnostics and troubleshooting
Diagnostic of sensor
Diagnostic of electronic
Diagnostic of configuration
Endress+Hauser 81
Diagnostics and troubleshooting Micropilot FMR67 HART
Diagnostic of process
5) This submenu is only available for operation via local display. In the case of operation via FieldCare, the event list can be displayed with the "Event
List / HistoROM" functionality of FieldCare.
82 Endress+Hauser
Micropilot FMR67 HART Diagnostics and troubleshooting
Navigation path
Diagnostics → Event logbook → Event list
A maximum of 100 event messages can be displayed in chronological order.
Die Ereignishistorie umfasst Einträge zu:
• Diagnostic events
• Information events
In addition to the operation time of its occurrence, each event is also assigned a symbol
that indicates whether the event has occurred or is ended:
• Diagnostic event
– : Event has occurred
– : Event has ended
• Information event
: Event has occurred
I1089 Power on
Endress+Hauser 83
Diagnostics and troubleshooting Micropilot FMR67 HART
1) Contains information on the Heartbeat wizards which are available in the latest DTM version for
DeviceCare and FieldCare.
2) Contains information on the Bluetooth interface.
The firmware version can explicitly be ordered via the product structure. In this way it
is possible to ensure compatibility of the firmware version with an existing or planned
system integration.
84 Endress+Hauser
Micropilot FMR67 HART Maintenance
14 Maintenance
The measuring device requires no special maintenance.
Endress+Hauser 85
Repairs Micropilot FMR67 HART
15 Repairs
86 Endress+Hauser
Micropilot FMR67 HART Repairs
002847-A
6 3
4 1 5
Additional information: www.endress.com/deviceviewer
A0014979
15.3 Return
The measuring device must be returned if it is need of repair or a factory calibration, or if
the wrong measuring device has been delivered or ordered. Legal specifications require
Endress+Hauser, as an ISO-certified company, to follow certain procedures when handling
products that are in contact with the medium.
To ensure safe, swift and professional device returns, please refer to the procedure and
conditions for returning devices provided on the Endress+Hauser website at
http://www.endress.com/support/return-material
15.4 Disposal
Observe the following notes during disposal:
• Observe valid federal/national regulations.
• Ensure proper separation and reuse of the device components.
Endress+Hauser 87
Accessories Micropilot FMR67 HART
16 Accessories
Accessory Description
222 (8.74)
A0015466
4)
38
35°
65°
(6.1
156
A0015472
Enclosed",
The weather protection cover can be ordered together with the device (product structure, feature 620 "Accessory
option PB "Weather Protection Cover").
Alternatively, it can be separately ordered as an accessory; order code 71162242.
88 Endress+Hauser
Micropilot FMR67 HART Accessories
Accessories Description
Adjustable
flange seal
4° ød
øD
1
2
h
±8°
hmax
hmin
A0032292
(temperature,
The material properties and process conditions of the adjustable flange seal must be compatible with the properties
pressure, resistance) of the process.
Recommended screw length 100 mm (3.9 in) 100 mm (3.9 in) 110 mm (4.3 in)
Material EPDM
Endress+Hauser 89
Accessories Micropilot FMR67 HART
Accessories Description
Compatible with • ASME 3" 150lbs ASME 4" 150lbs ASME 6" 150lbs
• JIS 80A 10K
Recommended screw length 100 mm (3.9 in) 100 mm (3.9 in) 110 mm (4.3 in)
Material EPDM
90 Endress+Hauser
Micropilot FMR67 HART Accessories
Accessories Description
Mounting bracket
adjustable
260 (10.2)
99.5 (3.9)
9(0.4)
ø9(0.4)
65 (2.6)
122 (4.8)
48(1.9)
12(0.5)
35(1.4) 100 (3.9) 16 (0.6)
A0032295
•• Risk
There is no conductive connection between the mounting bracket and the transmitter housing.
of electrostatic charge.
• Integrate the mounting bracket in the local potential equalization system.
• Only to be fastened at stable materials (e.g. metal, brick, concrete) using suitable fastening material (to be
supplied by customer).
Endress+Hauser 91
Accessories Micropilot FMR67 HART
Accessories Description
2.
1.
4.
3.
A0019128
• Material:
– Plastic PBT
– 316L/1.4404
– Aluminum
• Degree of protection: IP68 / NEMA 6P and IP66 / NEMA 4x
• Suitable for display modules:
– SD02 (push buttons)
– SD03 (touch control)
• Connecting cable:
– Cable supplied with device up to 30 m (98 ft)
– Standard cable supplied by customer up to 60 m (196 ft)
• Ambient temperature range: –40 to 80 °C (–40 to 176 °F)
• Ambient temperature range (option): –50 to 80 °C (–58 to 176 °F) 1)
• IfL, the remote display should be used, order the device version "Prepared for display FHX50" (feature 030, version
M or N). For the FHX50, you must select option A: "Prepared for display FHX50" under feature 050 "Measuring
device version".
• If the device version "Prepared for display FHX50" was not originally ordered and a FHX50 display is to be
retrofitted, you must select version B "Not prepared for display FHX50" under feature 050: "Measuring device
version" when ordering the FHX50. In this case, a retrofit kit for the device is supplied with the FHX50. The kit
can be used to prepare the device so that the FHX50 can be used.
FHX50
Use of the FHX50 may be restricted for transmitters with an approval. A device can only be retrofitted with the
if the option L, M or N ("Prepared for FHX50") is listed under Basic specifications, item 4 "Display, operation"
in the Safety Instructions (XA) for the device.
Also pay attention to the Safety Instructions (XA) of the FHX50.
92 Endress+Hauser
Micropilot FMR67 HART Accessories
Accessory Description
A0021734
Technical data
• Resistance per channel: 2 * 0.5 Ωmax
• Threshold DC voltage: 400 to 700 V
• Threshold impulse voltage: < 800 V
• Capacitance at 1 MHz: < 1.5 pF
• Nominal arrest impulse voltage (8/20 μs): 10 kA
• Suited for wire cross-sections: 0.2 to 2.5 mm2 (24 to 14 AWG)
Endress+Hauser 93
Accessories Micropilot FMR67 HART
Accessory Description
Bluetooth module
A0036493
When using the Bluetooth module the minimum supply voltage increases by up to 3 V.
Ordering with device
The Bluetooth module is preferably ordered with the device. See product structure, feature 610 "Accessory
Mounted", option NF "Bluetooth". A separate order is only necessary in case of retrofitting.
94 Endress+Hauser
Micropilot FMR67 HART Accessories
Commubox FXA195 For intrinsically safe HART communication with FieldCare via the USB interface.
HART
For details refer to Technical Information TI00404F
Accessory Description
Commubox FXA291 Connects Endress+Hauser field devices with CDI interface (= Endress+Hauser
Common Data Interface) to the USB interface of a computer.
Order code: 51516983
Accessory Description
HART Loop Converter Evaluates the dynamic HART variables and converts them to analog current signals
HMX50 or limit values.
Order code: 71063562
Accessory Description
Accessories Description
Connect Sensor Fully integrated, battery-powered gateway for simple applications with SupplyCare Hosting.
FXA30/FXA30B Up to 4 field devices with 4 to 20 mA communication (FXA30/FXA30B), serial Modbus
(FXA30B) or HART (FXA30B) can be connected. With its robust design and ability to run for
years on the battery, it is ideal for remote monitoring in isolated locations. Version with LTE
(USA, Canada and Mexico only) or 3G mobile transmission for worldwide communication.
BA01710S.
For details, see "Technical Information" TI01356S and Operating Instructions
Accessories Description
Fieldgate Fieldgates enable communication between connected 4 to 20 mA, Modbus RS485 and
FXA42 Modbus TCP devices and SupplyCare Hosting or SupplyCare Enterprise. The signals are
transmitted either via Ethernet TCP/IP, WLAN or mobile communications (UMTS). Advanced
automation capabilities are available, such as an integrated Web-PLC, OpenVPN and other
functions.
BA01778S.
For details, see "Technical Information" TI01297S and Operating Instructions
Endress+Hauser 95
Accessories Micropilot FMR67 HART
Accessories Description
SupplyCare Inventory management software that visualizes levels, volumes, masses, temperatures,
Enterprise pressures, densities or other tank parameters. The parameters are recorded and transmitted
SCE30B by means of gateways of the type Fieldgate FXA42.
This Web-based software is installed on a local server and can also be visualized and
operated with mobile terminals such as a smartphone or tablet.
BA00055S
For details, see "Technical Information" TI01228S and Operating Instructions
Accessories Description
SupplyCare Inventory management software that visualizes levels, volumes, masses, temperatures,
Hosting SCH30 pressures, densities or other tank parameters. The parameters are recorded and transmitted
by means of gateways of the type Fieldgate FXA42, FXA30 and FXA30B.
SupplyCare Hosting is offered as a hosting service (Software as a Service, SaaS). In the
Endress+Hauser portal, the user is provided with the data over the Internet.
BA00050S.
For details, see "Technical Information" TI01229S and Operating Instructions
Accessory Description
Field Xpert SFX350 Field Xpert SFX350 is a mobile computer for commissioning and maintenance. It
enables efficient device configuration and diagnostics for HART and FOUNDATION
fieldbus devices in the non-Ex area.
Accessory Description
Field Xpert SFX370 Field Xpert SFX370 is a mobile computer for commissioning and maintenance. It
enables efficient device configuration and diagnostics for HART and FOUNDATION
fieldbus devices in the non-Ex area and the Ex area.
DeviceCare SFE100 Configuration tool for HART, PROFIBUS and FOUNDATION Fieldbus devices
96 Endress+Hauser
Micropilot FMR67 HART Accessories
Graphic Data Manager The graphic data manager Memograph M provides information on all the relevant
Memograph M process variables. Measured values are recorded correctly, limit values are
monitored and measuring points analyzed. The data are stored in the 256 MB
internal memory and also on an SD card or USB stick.
RN221N Active barrier with power supply for safe separation of 4 to 20 mA current circuits.
Provides bi-directional HART transmission.
RNS221 Transmitter supply for 2-wire sensors or transmitters exclusively for non-Ex areas.
Provides bi-directional communication using the HART communication sockets.
Endress+Hauser 97
Operating menu Micropilot FMR67 HART
17 Operating menu
Setup → 115
Level → 119
Distance → 119
‣ Level → 126
98 Endress+Hauser
Micropilot FMR67 HART Operating menu
‣ Linearization → 132
Diameter → 137
Level → 139
Level → 140
Endress+Hauser 99
Operating menu Micropilot FMR67 HART
Diagnostics → 168
Timestamp → 168
100 Endress+Hauser
Micropilot FMR67 HART Operating menu
Timestamp → 169
Diagnostics 1 to 5 → 170
Timestamp → 170
Device ID → 173
Manufacturer ID → 174
Distance → 175
Endress+Hauser 101
Operating menu Micropilot FMR67 HART
‣ Simulation → 181
102 Endress+Hauser
Micropilot FMR67 HART Operating menu
Language → 156
Setup → 115
Level → 119
Distance → 119
‣ Mapping → 122
Distance → 119
Endress+Hauser 103
Operating menu Micropilot FMR67 HART
‣ Level → 126
‣ Linearization → 132
Diameter → 137
‣ Edit table
Level → 139
104 Endress+Hauser
Micropilot FMR67 HART Operating menu
‣ Display → 156
Language → 156
Endress+Hauser 105
Operating menu Micropilot FMR67 HART
Header → 159
Separator → 160
Backlight → 161
‣ Administration → 165
Diagnostics → 168
106 Endress+Hauser
Micropilot FMR67 HART Operating menu
Diagnostics 1 to 5 → 170
Device ID → 173
Manufacturer ID → 174
Distance → 175
Endress+Hauser 107
Operating menu Micropilot FMR67 HART
‣ Simulation → 181
108 Endress+Hauser
Micropilot FMR67 HART Operating menu
Setup → 115
Level → 119
Distance → 119
‣ Level → 126
Endress+Hauser 109
Operating menu Micropilot FMR67 HART
‣ Linearization → 132
Diameter → 137
Level → 139
Level → 140
110 Endress+Hauser
Micropilot FMR67 HART Operating menu
‣ Display → 156
Language → 156
Endress+Hauser 111
Operating menu Micropilot FMR67 HART
Header → 159
Separator → 160
Backlight → 161
‣ Administration → 165
Diagnostics → 168
Timestamp → 168
112 Endress+Hauser
Micropilot FMR67 HART Operating menu
Timestamp → 169
Diagnostics 1 to 5 → 170
Timestamp → 170
Device ID → 173
Manufacturer ID → 174
Distance → 175
Endress+Hauser 113
Operating menu Micropilot FMR67 HART
‣ Simulation → 181
‣ Heartbeat → 186
114 Endress+Hauser
Micropilot FMR67 HART Operating menu
Navigation Setup
Device tag
Description Enter a unique name for the measuring point to identify the device quickly within the
plant.
Distance unit
Factory setting m
Bin type
Description Optimizes the signal filters for the respective bin type. Note: 'Workbench test' deactivates
all filters. This option should exclusively be used for tests.
Endress+Hauser 115
Operating menu Micropilot FMR67 HART
Additional information Workbench test deactivates all filters. This option is intended for tests only.
Additional information By specifying the maximum filling and draining speed the signal evaluation is
automatically optimized for the process.
The filling and draining speed can be set separately as filling and draining may may
be different processes.
When selecting the No filter / test option all filters of the signal evaluation are
deactivated. This option is intended for tests only.
116 Endress+Hauser
Micropilot FMR67 HART Operating menu
Additional information By specifying the maximum filling and draining speed the signal evaluation is
automatically optimized for the process.
The filling and draining speed can be set separately as filling and draining may may
be different processes.
When selecting the No filter / test option all filters of the signal evaluation are
deactivated. This option is intended for tests only.
Empty calibration
Endress+Hauser 117
Operating menu Micropilot FMR67 HART
Additional information
0%
A0019488
The measuring range starts at the point at which the radar beam hits the tank or silo
bottom. In the case of dished boiler ends or conical outlets levels below this point can
not be measured.
Full calibration
Description Distance between minimum level (0%) and maximum level (100%).
Additional information
100%
0%
A0019489
118 Endress+Hauser
Micropilot FMR67 HART Operating menu
Level
Additional information
L
0%
A0019484
Distance
Description Distance between lower edge of flange or thread and medium surface.
Signal quality
Confirm distance
Description Specify, whether the measured distance matches the real distance. Depending on the
selection the device automatically sets the range of mapping.
Endress+Hauser 119
Operating menu Micropilot FMR67 HART
120 Endress+Hauser
Micropilot FMR67 HART Operating menu
Present mapping
Record map
Selection • No
• Record map
• Overlay map
• Factory map
• Delete partial map
Factory setting No
Endress+Hauser 121
Operating menu Micropilot FMR67 HART
Confirm distance
Description → 119
Description → 121
Record map
Description → 121
Distance
Description → 119
122 Endress+Hauser
Micropilot FMR67 HART Operating menu
Endress+Hauser 123
Operating menu Micropilot FMR67 HART
Locking status
Description Indicates the write protection with the highest priority that is currently active.
Description Shows the access authorization to the parameters via the operating tool.
Additional information The access authorization can be changed via the Enter access code parameter
(→ 125).
If additional write protection is active, this restricts the current access authorization
even further. The write protection status can be viewed via the Locking status
parameter (→ 124).
124 Endress+Hauser
Micropilot FMR67 HART Operating menu
Additional information The access authorization can be changed via the Enter access code parameter
(→ 125).
If additional write protection is active, this restricts the current access authorization
even further. The write protection status can be viewed via the Locking status
parameter (→ 124).
Additional information • For local operation, the customer-specific access code, which has been defined in the
Define access code parameter (→ 165), has to be entered.
• If an incorrect access code is entered, the user retains his current access authorization.
• The write protection affects all parameters marked with the -symbol in this document.
On the local display, the -symbol in front of a parameter indicates that the parameter
is write-protected.
• If no key is pressed for 10 min, or the user switches from the navigation and editing
mode back to the measured value display mode, the device automatically locks the write-
protected parameters after another 60 s.
Please contact your Endress+Hauser Sales Center if you lose your access code.
Endress+Hauser 125
Operating menu Micropilot FMR67 HART
"Level" submenu
Medium type
Additional information This parameter determines the value of several other parameters and strongly
influences the complete signal evaluation. Therefore, it is strongly recommended not
to change the factory setting.
Medium property
Selection • Unknown
• DC 1.4 ... 1.6
• DC 1.6 ... 1.9
• DC 1.9 ... 2.5
• DC 2.5 ... 4
• DC 4 ... 7
• DC 7 ... 15
• DC > 15
Factory setting Depending on the Medium type (→ 126) and Medium group parameters.
Solid Unknown
Others Unknown
For dielectric constants (DC values) of many media commonly used in various
industries refer to:
• the Endress+Hauser DC manual (CP01076F)
• the Endress+Hauser "DC Values App" (available for Android and iOS)
126 Endress+Hauser
Micropilot FMR67 HART Operating menu
Additional information By selecting the maximum expected filling and draining speed the signal evaluation is
automatically optimized for the process.
The filling and draining speeds can be set separately as the filling and draining
procedures may be different.
With the No filter / test option all signal evaluation filters are deactivated. This
option should exclusively be used for tests.
Max. filling speed liquid is preset by Tank type. It can, however, be adjusted to the
process in the vessel at any time. If Tank type is changed again, it may be necessary
to repeat the fine adjustment.
Endress+Hauser 127
Operating menu Micropilot FMR67 HART
Additional information By selecting the maximum expected filling and draining speed the signal evaluation is
automatically optimized for the process.
The filling and draining speeds can be set separately as the filling and draining
procedures may be different.
With the No filter / test option all signal evaluation filters are deactivated. This
option should exclusively be used for tests.
Max. draining speed liquid is preset by Tank type. It can, however, be adjusted to
the process in the vessel at any time. If Tank type is changed again, it may be
necessary to repeat the fine adjustment.
Level unit
Factory setting %
Additional information The level unit may differ from the distance unit defined in the Distance unit parameter
(→ 115):
• The unit defined in the Distance unit parameter is used for the basic calibration (Empty
calibration (→ 117) and Full calibration (→ 118)).
• The unit defined in the Level unit parameter is used to display the (unlinearized) level.
128 Endress+Hauser
Micropilot FMR67 HART Operating menu
Blocking distance
Additional information The blocking distance can be used to suppress interference echos in the vicinity of the
antenna.
BD
A0023041
Level correction
Additional information The value specified in this parameter is added to the measured level (before linearization).
Tank/silo height
Description Total height of the tank or silo (measured from the process connection)
Endress+Hauser 129
Operating menu Micropilot FMR67 HART
Additional information If the parametrized measuring range differs significantly from the tank or silo height, it is
recommended to enter the tank or silo height. Example: Continuous level monitoring in
the upper third of a tank or silo.
0%
H
A0019868
For tanks with conical outlet, Tank/silo height should not be changed as in this type
of applications Empty calibration (→ 117) is usually not much less-than the tank
or silo height.
130 Endress+Hauser
Micropilot FMR67 HART Operating menu
"Linearization" submenu
2
A
L
100%
L 1 B L‘
0%
M L‘
L
100%
L2
C L1
0%
L‘1 L‘2 L‘
L
100%
h
D
0%
M L‘
L
100%
h
E
0%
M L‘
L
100%
h
0%
M L‘
L
100%
G d
0%
M L‘
L
100%
H d
0%
M L‘
A0019648
42 Linearization: Transformation of the level and (if relevant) the interface height into a volume or weight;
the transformation is dependent on the shape of the vessel.
1 Selection of linearization type and unit
2 Configuration of the linearization
A Linearization type (→ 134) = None
B Linearization type (→ 134) = Linear
C Linearization type (→ 134) = Table
D Linearization type (→ 134) = Pyramid bottom
E Linearization type (→ 134) = Conical bottom
F Linearization type (→ 134) = Angled bottom
G Linearization type (→ 134) = Horizontal cylinder
H Linearization type (→ 134) = Sphere
L Level before linearization (measured in distance units)
L' Level linearized (→ 136) (corresponds to volume or weight)
M Maximum value (→ 137)
d Diameter (→ 137)
h Intermediate height (→ 137)
Endress+Hauser 131
Operating menu Micropilot FMR67 HART
‣ Linearization
Diameter → 137
‣ Edit table
Level → 139
132 Endress+Hauser
Micropilot FMR67 HART Operating menu
‣ Linearization
Diameter → 137
Level → 139
Level → 140
Endress+Hauser 133
Operating menu Micropilot FMR67 HART
Description of parameters
Linearization type
Selection • None
• Linear
• Table
• Pyramid bottom
• Conical bottom
• Angled bottom
• Horizontal cylinder
• Sphere
Additional information
A B
100%
100%
0% 0%
C/D E
100% 100%
0% 0%
F/G
100%
0%
A0021476
43 Linearization types
A None
B Table
C Pyramid bottom
D Conical bottom
E Angled bottom
F Sphere
G Horizontal cylinder
134 Endress+Hauser
Micropilot FMR67 HART Operating menu
Endress+Hauser 135
Operating menu Micropilot FMR67 HART
Custom-specific units
Free text
Factory setting %
Additional information The selected unit is only used to be indicated on the display. The measured value is not
transformed according to the selected unit.
It is also possible to configure a distance-to-distance linearization, i.e. a
transformation from the level unit to a different distance unit. To do so, select the
Linear linearization mode. In order to define the new level unit, select the Free text
option in the Unit after linearization parameter and enter the required unit into the
Free text parameter (→ 136).
Free text
Level linearized
Additional information The unit is defined by the Unit after linearization parameter → 135.
136 Endress+Hauser
Micropilot FMR67 HART Operating menu
Maximum value
Diameter
Factory setting 2m
Additional information The unit is defined in the Distance unit parameter (→ 115).
Intermediate height
Factory setting 0m
Endress+Hauser 137
Operating menu Micropilot FMR67 HART
Additional information
H
0%
A0013264
H Intermediate height
Table mode
Selection • Manual
• Semiautomatic
• Clear table
• Sort table
Before entering a linearization table, the values for Empty calibration (→ 117)
and Full calibration (→ 118) must be set correctly.
If values of the table need to be changed after the full or empty calibration have been
changed, a correct evaluation is only ensured if the existing table is deleted and the
complete table is entered again. To do so delete the existing table (Table mode
(→ 138) = Clear table). Then enter a new table.
138 Endress+Hauser
Micropilot FMR67 HART Operating menu
The factory setting for the level unit is "%". If you want to enter the linearization table
in physical units, you must select the appropriate unit in the Level unit parameter
(→ 128) beforehand.
If a decreasing table is entered, the values for 20 mA and 4 mA of the current output
are interchanged. That means: 20 mA refers to the lowest level, whereas 4 mA refers
to the highest level.
Table number
User entry 1 to 32
Factory setting 1
Level (Manual)
Description Enter level value of the table point (value before linearization).
Factory setting 0%
Endress+Hauser 139
Operating menu Micropilot FMR67 HART
Level (Semiautomatic)
Description Displays measured level (value before linearization). This value is transmitted to the table.
Customer value
Factory setting 0%
Activate table
Selection • Disable
• Enable
140 Endress+Hauser
Micropilot FMR67 HART Operating menu
Additional information Use the unit which has been defined for the measured value output:
• without linearization: Level unit (→ 128)
• with linearization: Unit after linearization (→ 135)
Endress+Hauser 141
Operating menu Micropilot FMR67 HART
Additional information
100%
B
A
C
0%
t
min
A0013269
• The unit for the slope of the ramp is "percentage of the measuring range per minute" (%/
min).
• For a negative slope of the ramp: The measured value is continuously decreased until it
reaches 0%.
• For a positive slope of the ramp: The measured value is continuosly increased until it
reaches 100%.
Blocking distance
Additional information Signals in the blocking distance are only evaluated if they have been outside the blocking
distance when the device was switched on and move into the blocking distance due to a
142 Endress+Hauser
Micropilot FMR67 HART Operating menu
level change during operation. Signals which are already in the blocking distance when the
device is switched on, are ignored.
If required, a different behavior for signals in the blocking distance can be defined by
the Endress+Hauser service.
BD
A0023041
Endress+Hauser 143
Operating menu Micropilot FMR67 HART
144 Endress+Hauser
Micropilot FMR67 HART Operating menu
Factory setting 0
Code incorrect
Description Indicates that a wrong unlocking code has been entered. Select procedure.
Endress+Hauser 145
Operating menu Micropilot FMR67 HART
Additional information Definition of the current range for the process variables
Process variable 4 mA value 20 mA value
1)
Level linearized 0 % or the associated 100 % 2) or the associated linearized value
linearized value
Distance 0 (i.e. level is at the reference Empty calibration (→ 117) (i.e. level is at
point) 0 %)
146 Endress+Hauser
Micropilot FMR67 HART Operating menu
Current span
Description Determines the current range used to transmit the measured value. ‘4…20mA’: Measured
variable: 4 …20 mA ‘4…20mA NAMUR’: Measured variable: 3.8 … 20.5 mA ‘4…20mA US’:
Measured variable: 3.9 … 20.8 mA ‘Fixed current’: Measured variable transmitted via
HART only Note: Currents below 3.6 mA or above 21.95 mA can be used to signal an
alarm.
Selection • 4...20 mA
• 4...20 mA NAMUR
• 4...20 mA US
• Fixed current
Fixed current Constant current, defined in the Fixed current parameter (→ 147).
• In the case of an error, the output current assumes the value defined in the Failure
mode parameter (→ 148).
• If the meausred value is out of the measuring range, diagnostic message Current
output is issued.
In a HART multidrop loop only one device can use the analog current to transmit a
signal. For all other devices one must set:
• Current span = Fixed current
• Fixed current (→ 147) = 4 mA
Fixed current
Factory setting 4 mA
Endress+Hauser 147
Operating menu Micropilot FMR67 HART
Damping output
Description Reaction time of the output signal on fluctuation in the measured value.
Additional information Fluctuations of the measured value affect the output current with an exponential delay,
the time constant τ of which is defined in this parameter. With a small time constant the
output reacts immediately to changes of the measrued value. With a big time constant the
reaction of the output is more delayed. For τ = 0 (factory setting) there is no damping.
Failure mode
Description Defines which current the output assumes in the case of an error. ‘Min.’: < 3.6mA ‘Max.’: >
21.95mA ‘Last valid value’: Last valid value before occurrence of the error. ‘Actual value’:
Output current is equal to the measured value; error is ignored. ‘Defined value’: User
defined value.
Selection • Min.
• Max.
• Last valid value
• Actual value
• Defined value
148 Endress+Hauser
Micropilot FMR67 HART Operating menu
Failure current
Output current 1 to 2
Endress+Hauser 149
Operating menu Micropilot FMR67 HART
Description Defines the function of the switch output. 'Off' The switch output is always open (non-
conductive) 'On' The switch output is always closed (conductive). 'Diagnostic behavior' The
switch output is normally closed and is only opened if a diagnostic event is present. 'Limit'
The switch output is normally closed and is only opened if a measured variable exceeds a
defined limit. 'Digital output' The switch output is controlled by one of the digital output
blocks of the device.
Selection • Off
• On
• Diagnostic behavior
• Limit
• Digital Output
150 Endress+Hauser
Micropilot FMR67 HART Operating menu
Assign status
Selection • Off
• Digital output AD 1
• Digital output AD 2
• Digital output AD 3
• Digital output AD 4
Additional information The Digital output AD 1/2/3/4 options refer to the Advanced Diagnostic Blocks. A switch
signal generated in these blocks can be transmitted via the switch output.
Assign limit
Selection • Off
• Level linearized
• Distance
• Terminal voltage
• Electronic temperature
• Relative echo amplitude
• Area of incoupling
Description Defines to which behavior of diagnostic events the switch output reacts.
Selection • Alarm
• Alarm or warning
• Warning
Endress+Hauser 151
Operating menu Micropilot FMR67 HART
Switch-on value
Description Defines the switch-on point. The output is closed if the assigned process variable rises
above this point.
Factory setting 0
Additional information The switching behavior depends on the relative position of the Switch-on value and
Switch-off value parameters:
Switch-on value > Switch-off value
– The output is closed if the measured value is larger than Switch-on value.
– The output is opened if the measured value is smaller than Switch-off value.
B
t
D
t
A0015585
A Switch-on value
B Switch-off value
C Output closed (conductive)
D Output opened (non-conductive)
152 Endress+Hauser
Micropilot FMR67 HART Operating menu
A
t
D
t
A0015586
A Switch-on value
B Switch-off value
C Output closed (conductive)
D Output opened (non-conductive)
Switch-on delay
Description Defines the delay applied before the output is switched on.
Switch-off value
Description Defines the switch-off point. The output is opened if the assigned process variable falls
below this point.
Factory setting 0
Additional information The switching behavior depends on the relative position of the Switch-on value and
Switch-off value parameters; description: see the Switch-on value parameter
(→ 152).
Endress+Hauser 153
Operating menu Micropilot FMR67 HART
Switch-off delay
Description Defines the delay applied before the output is switched off.
Failure mode
Additional information
Switch status
Description 'No' The switch output behaves as per its parameter setting. 'Yes' The switching behavior is
inverted as compared to its parameter setting.
Selection • No
• Yes
154 Endress+Hauser
Micropilot FMR67 HART Operating menu
Factory setting No
Endress+Hauser 155
Operating menu Micropilot FMR67 HART
"Display" submenu
The Display submenu is only visible if a display module is connected to the device.
Language
Selection • English
• Deutsch *
• Français *
• Español *
• Italiano *
• Nederlands *
• Portuguesa *
• Polski *
• русский язык (Russian) *
• Svenska *
• Türkçe *
• 中文 (Chinese) *
• 日本語 (Japanese) *
• 한국어 (Korean) *
• Bahasa Indonesia *
• tiếng Việt (Vietnamese) *
• čeština (Czech) *
Factory setting The language selected in feature 500 of the product structure.
If no language has been selected: English
Additional information
Format display
156 Endress+Hauser
Micropilot FMR67 HART Operating menu
Additional information
4841.000
1 Â mm
A0019963
1 Â
93.5 %
1 Â 159.0
mm
A0019964
1 Â 93.5
%
1 Â 159.0
mm
A0019965
1 Â 159.0 mm
V 1 Â 23.5 V
1 Â 93.5
%
A0019966
1 Â 93.5 %
1 Â 159.0 mm
V 1 Â 93.5 V
1 Â 26.3 °C
A0019968
• The Value 1 to 4 display → 158 parameters specify which measured values are
shown on the display and in which order.
• If more measured values are specified than the current display mode permits, the
values alternate on the device display. The display time until the next change is
configured in the Display interval parameter (→ 158).
Endress+Hauser 157
Operating menu Micropilot FMR67 HART
Value 1 to 4 display
Description Select the measured value that is shown on the local display.
Decimal places 1 to 4
Description This selection does not affect the measurement and calculation accuracy of the device.
Selection •x
• x.x
• x.xx
• x.xxx
• x.xxxx
Additional information The setting does not affect the measuring or computational accuracy of the device.
Display interval
Description Set time measured values are shown on display if display alternates between values.
158 Endress+Hauser
Micropilot FMR67 HART Operating menu
User entry 1 to 10 s
Factory setting 5s
Additional information This parameter is only relevant if the number of selected measuring values exceeds the
number of values the selected display format can display simultaneously.
Display damping
Header
Additional information
1 XXXXXXXXX
A0029422
Endress+Hauser 159
Operating menu Micropilot FMR67 HART
Header text
Additional information The number of characters which can be displayed depends on the characters used.
Separator
Selection •.
•,
Factory setting .
Number format
Selection • Decimal
• ft-in-1/16''
Additional information The ft-in-1/16'' option is only valid for distance units.
Description Select number of decimal places for the representation of numbers within the operating
menu.
160 Endress+Hauser
Micropilot FMR67 HART Operating menu
Selection •x
• x.x
• x.xx
• x.xxx
• x.xxxx
Additional information • Is only valid for numbers in the operating menu (e.g. Empty calibration, Full
calibration), but not for the measured value display. The number of decimal places for
the measured value display is defined in the Decimal places 1 to 4 → 158
parameters.
• The setting does not affect the accuracy of the measurement or the calculations.
Backlight
Prerequisite The device has the SD03 local display (with optical keys).
Selection • Disable
• Enable
Contrast display
Description Adjust local display contrast setting to ambient conditions (e.g. lighting or reading angle).
User entry 20 to 80 %
Endress+Hauser 161
Operating menu Micropilot FMR67 HART
The configuration of the device can be saved to the display module at a certain point of
time (backup). The saved configurateion can be restored to the device if required, e.g. in
order to bring the device back into a defined state. The configuration can also be
transferred to a different device of the same type using the display module.
Operating time
Last backup
Description Indicates when the last data backup was saved to the display module.
Configuration management
Description Select action for managing the device data in the display module.
Selection • Cancel
• Execute backup
• Restore
• Duplicate
• Compare
• Clear backup data
162 Endress+Hauser
Micropilot FMR67 HART Operating menu
Backup state
Comparison result
Endress+Hauser 163
Operating menu Micropilot FMR67 HART
164 Endress+Hauser
Micropilot FMR67 HART Operating menu
"Administration" submenu
Factory setting 0
Additional information If the factory setting is not changed or 0 is defined as the access code, the parameters
are not write-protected and the configuration data of the device can then always be
modified. The user is logged on in the Maintenance role.
The write protection affects all parameters marked with the symbol in this
document. On the local display, the symbol in front of a parameter indicates that
the parameter is write-protected.
Once the access code has been defined, write-protected parameters can only be
modified if the access code is entered in the Enter access code parameter
(→ 125).
Please contact your Endress+Hauser Sales Center if you lose your access code.
For display operation: The new access code is only valid after it has been confirmed in
the Confirm access code parameter (→ 167).
Device reset
Description Reset the device configuration - either entirely or in part - to a defined state.
Selection • Cancel
• To factory defaults
• To delivery settings
• Of customer settings
• To transducer defaults
• Restart device
Endress+Hauser 165
Operating menu Micropilot FMR67 HART
166 Endress+Hauser
Micropilot FMR67 HART Operating menu
The Define access code wizard is only available when operating via the local display.
When operating via an operating tool, the Define access code parameter is located
directly in the Administration submenu. The Confirm access code parameter is not
available for operation via operating tool.
Navigation Setup → Advanced setup → Administration → Define access code → Define access
code
Description → 165
Navigation Setup → Advanced setup → Administration → Define access code → Confirm access
code
Factory setting 0
Endress+Hauser 167
Operating menu Micropilot FMR67 HART
Actual diagnostics
Timestamp
Description Displays the timestamp for the currently active diagnostic message.
Previous diagnostics
Description Displays the last diagnostic message which has been active before the current message.
168 Endress+Hauser
Micropilot FMR67 HART Operating menu
Timestamp
Description Displays the time the device has been in operation since the last device restart.
Operating time
Endress+Hauser 169
Operating menu Micropilot FMR67 HART
Diagnostics 1 to 5
Description Display the current diagnostics messages with the highest to fifth-highest priority.
Timestamp 1 to 5
170 Endress+Hauser
Micropilot FMR67 HART Operating menu
Filter options
Description Define which category of event messages is shown in the Events list submenu.
Selection • All
• Failure (F)
• Function check (C)
• Out of specification (S)
• Maintenance required (M)
• Information (I)
Additional information • This parameter is only used for operation via the local display.
• The status signals are categorized according to NAMUR NE 107.
Endress+Hauser 171
Operating menu Micropilot FMR67 HART
Device tag
Serial number
Firmware version
Additional information For firmware versions differing only in the last two digits ("zz") there is no difference
concerning functionality or operation.
Device name
172 Endress+Hauser
Micropilot FMR67 HART Operating menu
Order code
Additional information The order code is generated from the extended roder code, which defines all device
features of the product structure. In contrast, the device features can not be read directly
from the order code.
Additional information The extended order code indicates the version of all the features of the product structure
and thus uniquely identifies the device.
Device revision
Description Shows the device revision with which the device is registered with the HART
Communication Foundation.
Additional information The device revision is used to allocate the correct Device Description file (DD) to the device.
Device ID
Description Shows the device ID for identifying the device in a HART network.
Additional information In addition to the Device type and Manufacturer ID, the Device ID is part of the unique
device identification (Unique ID) which characterizes each HART device unambiguously.
Endress+Hauser 173
Operating menu Micropilot FMR67 HART
Device type
Description Shows the device type with which the measuring device is registered with the HART
Communication Foundation.
Additional information The device type is needed to allocate the suitable Device Description (DD) to the device.
Manufacturer ID
Description Use this function to view the manufacturer ID with which the measuring device is
registered with the HART Communication Foundation.
174 Endress+Hauser
Micropilot FMR67 HART Operating menu
Distance
Description Distance between lower edge of flange or thread and medium surface.
Additional information
A0019485
Level linearized
Additional information The unit is defined by the Unit after linearization parameter → 135.
Output current 1 to 2
Endress+Hauser 175
Operating menu Micropilot FMR67 HART
Measured current 1
Description Shows the current value of the current output which is currently measured.
Terminal voltage 1
Description Shows the current terminal voltage that is applied at the output.
Sensor temperature
176 Endress+Hauser
Micropilot FMR67 HART Operating menu
Assign channel 1 to 4
Selection • Off
• Level linearized
• Distance
• Current output 1
• Measured current
• Current output 2 *
• Terminal voltage
• Electronic temperature
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2
• Analog output adv. diagnostics 3
• Analog output adv. diagnostics 4
Additional information A total of 1000 measured values can be logged. This means:
• 1000 data points if 1 logging channel is used
• 500 data points if 2 logging channels are used
• 333 data points if 3 logging channels are used
• 250 data points if 4 logging channels are used
If the maximum number of data points is reached, the oldest data points in the data log
are cyclically overwritten in such a way that the last 1000, 500, 333 or 250 measured
values are always in the log (ring memory principle).
The logged data are deleted if a new option is selected in this parameter.
Logging interval
Description Define the logging interval tlog for data logging. This value defines the time interval
between the individual data points in the memory.
Endress+Hauser 177
Operating menu Micropilot FMR67 HART
Additional information This parameter defines the interval between the individual data points in the data log, and
thus the maximum loggable process time T log :
• If 1 logging channel is used: T log = 1000 ⋅ t log
• If 2 logging channels are used: T log = 500 ⋅ t log
• If 3 logging channels are used: T log = 333 ⋅ t log
• If 4 logging channels are used: T log = 250 ⋅ t log
Once this time elapses, the oldest data points in the data log are cyclically overwritten such
that a time of T log always remains in the memory (ring memory principle).
The logged data are deleted if this parameter is changed.
Example
When using 1 logging channel
• Tlog = 1000 ⋅ 1 s = 1 000 s ≈ 16.5 min
• Tlog = 1000 ⋅ 10 s = 1 000 s ≈ 2.75 h
• Tlog = 1000 ⋅ 80 s = 80 000 s ≈ 22 h
• Tlog = 1000 ⋅ 3 600 s = 3 600 000 s ≈ 41 d
Selection • Cancel
• Clear data
178 Endress+Hauser
Micropilot FMR67 HART Operating menu
• x-axis: depending on the number of selected channels, 250 to 1000 measured values of
a process variable are displayed.
• y-axis: covers the approximate measured value span and constantly adapts this to the
measurement.
To return to the operating menu, press and simultaneaously.
Endress+Hauser 179
Operating menu Micropilot FMR67 HART
180 Endress+Hauser
Micropilot FMR67 HART Operating menu
‣ Simulation
Endress+Hauser 181
Operating menu Micropilot FMR67 HART
Description of parameters
Selection • Off
• Level
• Level linearized
Additional information • The value of the variable to be simulated is defined in the Process variable value
parameter (→ 182).
• If Assign measurement variable ≠ Off, a simulation is active. This is indicated by a
diagnotic message of the Function check (C) category.
Factory setting 0
Additional information Downstream measured value processing and the signal output use this simulation value. In
this way, users can verify whether the measuring device has been configured correctly.
Selection • Off
• On
Additional information An active simulation is indicated by a diagnostic message of the Function check (C)
category.
182 Endress+Hauser
Micropilot FMR67 HART Operating menu
Additional information The current output assumes the value specified in this parameter. In this way, users can
verify the correct adjustment of the current output and the correct function of connected
control units.
Selection • Off
• On
Switch status
Selection • Open
• Closed
Additional information The switch status assumes the value defined in this parameter. This helps to check correct
operation of connected control units.
Endress+Hauser 183
Operating menu Micropilot FMR67 HART
Selection • Off
• On
Additional information When selecting the On option, the device generates an alarm. This helps to check the
correct output behavior of the device in the case of an alarm.
An active simulation is indicated by the diagnostic message C484 Failure mode
simulation.
Selection • Sensor
• Electronics
• Configuration
• Process
Additional information Only events of the selected category are available in the selcetion list of the Diagnostic
event simulation parameter (→ 184).
When operated via tool, all diagnostic messages are always available in Diagnostic
event simulation. Therefore, Diagnostic event category appears only on the local
display.
Description Select the diagnostic event to be simulated. Note: To terminate the simulation, select 'Off'.
Additional information When operated via the local display, the selection list can be filtered according to the event
categories (Diagnostic event category parameter (→ 184)).
184 Endress+Hauser
Micropilot FMR67 HART Operating menu
Selection • No
• Yes
Factory setting No
Description Indicates the operating time at which the last device check has been performed.
Endress+Hauser 185
Operating menu Micropilot FMR67 HART
186 Endress+Hauser
Micropilot FMR67 HART Index
Index
A Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . 11
Access authorization to parameters Define access code . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Read access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Define access code (Parameter) . . . . . . . . . . . . 165, 167
Write access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Define access code (Wizard) . . . . . . . . . . . . . . . . . . 167
Access code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Incorrect input . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Device alarm simulation (Parameter) . . . . . . . . . . . . 184
Access status display (Parameter) . . . . . . . . . . . . . . 125 Device check (Submenu) . . . . . . . . . . . . . . . . . . . . . 185
Access status tooling (Parameter) . . . . . . . . . . . . . . 124 Device Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Accessories Device ID (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 173
Communication specific . . . . . . . . . . . . . . . . . . . . 95 Device information (Submenu) . . . . . . . . . . . . . . . . 172
Device-specific . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 Device name (Parameter) . . . . . . . . . . . . . . . . . . . . 172
Service specific . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 Device replacement . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Activate table (Parameter) . . . . . . . . . . . . . . . . . . . . 140 Device reset (Parameter) . . . . . . . . . . . . . . . . . . . . . 165
Actual diagnostics (Parameter) . . . . . . . . . . . . . . . . 168 Device revision (Parameter) . . . . . . . . . . . . . . . . . . . 173
Administration (Submenu) . . . . . . . . . . . . . . . . . . . 165 Device tag (Parameter) . . . . . . . . . . . . . . . . . . 115, 172
Advanced setup (Submenu) . . . . . . . . . . . . . . . . . . . 124 Device type (Parameter) . . . . . . . . . . . . . . . . . . . . . 174
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Diagnostic event
Assign channel 1 to 4 (Parameter) . . . . . . . . . . . . . . 177 In the operating tool . . . . . . . . . . . . . . . . . . . . . . . 79
Assign current output (Parameter) . . . . . . . . . . . . . . 146 Diagnostic event category (Parameter) . . . . . . . . . . . 184
Assign diagnostic behavior (Parameter) . . . . . . . . . . 151 Diagnostic event simulation (Parameter) . . . . . . . . . 184
Assign limit (Parameter) . . . . . . . . . . . . . . . . . . . . . 151 Diagnostic events . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Assign measurement variable (Parameter) . . . . . . . . 182 Diagnostic list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Assign status (Parameter) . . . . . . . . . . . . . . . . . . . . 151 Diagnostic list (Submenu) . . . . . . . . . . . . . . . . . . . . 170
Diagnostic message . . . . . . . . . . . . . . . . . . . . . . . . . . 76
B Diagnostics
Backlight (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 161 Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Backup state (Parameter) . . . . . . . . . . . . . . . . . . . . 163 Diagnostics (Menu) . . . . . . . . . . . . . . . . . . . . . . . . . 168
Bin type (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 115 Diagnostics 1 (Parameter) . . . . . . . . . . . . . . . . . . . . 170
Blocking distance (Parameter) . . . . . . . . . . . . . 129, 142 Diagnostics event . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Bluetooth® wireless technology . . . . . . . . . . . . . . . . . 43 Diameter (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 137
DIP switch
C see Write protection switch
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Display (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . . 156
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Display and operating module FHX50 . . . . . . . . . . . . 42
Clear logging data (Parameter) . . . . . . . . . . . . . . . . 178 Display channel 1 to 4 (Submenu) . . . . . . . . . . . . . . 179
Code incorrect (Parameter) . . . . . . . . . . . . . . . . . . . 145 Display damping (Parameter) . . . . . . . . . . . . . . . . . 159
Comparison result (Parameter) . . . . . . . . . . . . . . . . 163 Display interval (Parameter) . . . . . . . . . . . . . . . . . . 158
Configuration backup display (Submenu) . . . . . . . . . 162 Display module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Configuration management (Parameter) . . . . . . . . . 162 Display symbols for submenus . . . . . . . . . . . . . . . . . . 53
Configuration of a level measurement . . . . . . . . . . . . 67 Display symbols for the locking state . . . . . . . . . . . . . 53
Confirm access code (Parameter) . . . . . . . . . . . . . . . 167 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Confirm distance (Parameter) . . . . . . . . . . . . . 119, 122 Distance (Parameter) . . . . . . . . . . . . . . . . 119, 122, 175
Context menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Distance unit (Parameter) . . . . . . . . . . . . . . . . . . . . 115
Contrast display (Parameter) . . . . . . . . . . . . . . . . . . 161 Document
Current output 1 to 2 (Submenu) . . . . . . . . . . . . . . . 146 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Current output 1 to 2 simulation (Parameter) . . . . . . 182 Document function . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Current span (Parameter) . . . . . . . . . . . . . . . . . . . . 147
Customer value (Parameter) . . . . . . . . . . . . . . . . . . 140 E
Electronics housing
D Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Damping output (Parameter) . . . . . . . . . . . . . . . . . . 148 Empty calibration (Parameter) . . . . . . . . . . . . . . . . . 117
Data logging (Submenu) . . . . . . . . . . . . . . . . . . . . . 177 Enter access code (Parameter) . . . . . . . . . . . . . . . . . 125
DD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Envelope curve display . . . . . . . . . . . . . . . . . . . . . . . . 59
Deactivate SIL/WHG (Wizard) . . . . . . . . . . . . . . . . . 145 Event history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Decimal places 1 (Parameter) . . . . . . . . . . . . . . . . . 158 Event level
Decimal places menu (Parameter) . . . . . . . . . . . . . . 160 Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Endress+Hauser 187
Index Micropilot FMR67 HART
K P
Keypad lock Prepare recording map (Parameter) . . . . . . . . . . . . . 122
Disabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Present mapping (Parameter) . . . . . . . . . . . . . . . . . 121
Switching on . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Previous diagnostics (Parameter) . . . . . . . . . . . . . . . 168
Process variable value (Parameter) . . . . . . . . . . . . . . 182
L Product safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Language (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 156 PV (HART device variable) . . . . . . . . . . . . . . . . . . . . . 60
Last backup (Parameter) . . . . . . . . . . . . . . . . . . . . . 162
Last check time (Parameter) . . . . . . . . . . . . . . . . . . 185 R
Level (Parameter) . . . . . . . . . . . . . . . . . . 119, 139, 140 Ramp at echo lost (Parameter) . . . . . . . . . . . . . . . . . 142
Level (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . . . . 126 Read access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Level correction (Parameter) . . . . . . . . . . . . . . . . . . 129 Record map (Parameter) . . . . . . . . . . . . . . . . . 121, 122
Level linearized (Parameter) . . . . . . . . . . . . . . 136, 175 Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . . . 9
Level measurement configuration . . . . . . . . . . . . . . . 67 Remedial measures
Level unit (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 128 Calling up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Linearization (Submenu) . . . . . . . . . . . . . 132, 133, 134 Closing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Linearization type (Parameter) . . . . . . . . . . . . . . . . 134 Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Local display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Repair concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
see Diagnostics message Replacing a device . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
see In alarm condition Requirements for personnel . . . . . . . . . . . . . . . . . . . . 10
188 Endress+Hauser