ALP MANUAL For Sigma
ALP MANUAL For Sigma
www.sigmaelevator.com
1. UNDERSTANDING OF SYSTEM......................................................................................................... 5
-2-
4. ANNOUNCIATOR .............................................................................................................................. 32
-3-
4) RATING OF FUSES .........................................................................................................................44
5) CIRCUIT CHECK..............................................................................................................................44
5.5 VOLTAGE CHECK ...................................................................................................................................45
1) PREPARATION FOR POWER APPLICATION ................................................................................45
2) INPUT VOLTAGE CHECK OF ALP CONTROL PANEL...................................................................45
3) VOLTAGE CHECK AFTER MCCB APPLICATION IN CONTROL PANEL.......................................46
4) C9A CONTACTOR CHECK..............................................................................................................47
5) LED CHECK ON THE PCB ..............................................................................................................48
5.6 ADJUSTMENT..........................................................................................................................................49
1) ADJUSTMENT FOR BATTERY VOLTAGE DETECTION ................................................................49
2) FAILURE DETECTION SETTINGS ..................................................................................................49
5.7 TEST OPERATION ..................................................................................................................................50
1) TEST OPERATION PROCEDURE...................................................................................................50
2) TEST CHARGE OPERATION ..........................................................................................................51
3) RESCUE OPERATION WHEN STOPPING WITHIN DOOR OPENING ZONE ...............................52
4) RESCUE OPERATION WHEN STOPPING WITHOUT DOOR OPENING ZONE ...........................53
5.8 CHECKLIST FOR THE RESCUE OPERATION.......................................................................................54
1) CHECKLIST FOR CONTROL FUNCTIONS
(E/L OPERATION SWITCHES TO RESCUE OPERATION MODE)...........................54
2) CHECKLIST FOR OPERATION FUNCTIONS .................................................................................55
5.9 ACTIONS TO TAKE AFTER COMPLETING TEST OPERATION............................................................56
-4-
1. UNDERSTANDING OF SYSTEM
1.1 OVERVIEW
1) TERMINOLOGY OF DI ALP
• DI: Distributed and Inverter Control Elevator
• ALP: Automatic Landing Device during Power-failure
2) ALP SYSTEM?
The ALP or ARD (Automatic Rescue Device) is a system to rescue passengers trapped in the
car when the electric power failed during the normal operation of an elevator. The ALP system
is largely classified as three different forms. Figure 1 shows the external ALP as a conventional
mode in which the ALP performs a rescue operation by supplying the control power to the E/L
control panel for the operation of main motor, doors and brake.
Figure 1. External type ALP (Conventional mode) Figure 2. Internal type ALP
Figure 2 shows the internal type ALP in which the power supplying devices that the rescue
operation requires are equipped inside the control panel of the elevator, and its control circuit
performs all the necessary functions for the rescue operation. (The battery is installed outside.)
For the elevators of speed of 150(m/min) or higher, the ALP control panel is installed
separately, but its function is so limited that it can only have the power supplying system.
Figure 3 shows the UPS ALP that is more advanced than the internal ALP. The UPS ALP is
equipped with the UPS (Uninterruptible Power Supply) outside, and it has been applied to the
DI elevators (The DI ALP is abbreviated to ALP in the followings.). It is featured that the
interface to the elevator control panel is simple and the separate charge system is not necessary.
-5-
Figure 3. UPS ALP
-6-
1.3 CONFIGURATIONS AND FUNCTIONS OF THE ALP CONTROLLER
ALP functions
Serial
Voltage/Current control
E/L operation control
Parallel
ALP operation speed
control program
communication
ALP operation
control program
program
-7-
1.4 MAIN SPECIFICATIONS AND FUNCTIONS
1) MAIN SPECIFICATIONS
2) MAIN FUNCTIONS
• ELEVATOR CONTROL PANEL
CATEGORIES FUNCTIONS
Rescue operation possible when safety devices are normal
Rescue operation not possible in the on-cage operation
Open doors after stopping automatically at the door opening zone in case
Operating of the power failure
functions Open only doors in case of the power failure at the door opening zone
Return automatically to the normal operation mode when the power is
restored normally
Only use for power failure
Not serving for cage-call
Clear cage-call
Not serving for hall-call
Controlling
Clear hall-call
functions
Turn off up and down lanterns
Turn on the cage direction indicator
Delete load compensation function
Battery
Modes of Initial Power Charge Rescue E/L, ALP
under
operation power-on failure operation operation MCCB off
voltage
Rest
operation g r r r r r
Charge
operation r g r g r r
Rescue
operation r g g g g r
-8-
1.5 FUNCTIONS OF CONTACTORS AND RELAYS
1) OPERATIONS OF MODES
Rest operation O O O
Charge operation O O O O O O
Rescue operation O O O O ⊙
⊙ The setting in case that the power is restored during the rescue operation
2) EXPLANATION OF FUNCTIONS
-9-
2. FUNCTIONS AND FEATURES OF PCB
A B C D E F
By the PCB
C: Control
By the PCB location P: Power
R: I/O control
P: Power electronics
By the operation
O: Operation
If classification by the A: ALP
operation is necessary
within the same PCB
group, the markings of
0 to 9 are used.
- 10 -
2.2 DAC-100 PCB
1) OUTLINE DRAWING OF THE DAC-100 PCB
- 11 -
2) EXPLANATION OF DAC-100 PCB FUNCTIONS
No.
1 APA connector (26P) The signal output connector to the D/A converter for monitoring
2 APB connector (4P) The power source connector receiving P15, N15, P5, and GND
from the DAR-100 PCB
3 APC connector (6P) The serial signal I/O connector to communicate with DI-E/L
4 APA connector (18P) The connector receiving the current and voltage from H.CT and
PT
5 APE connector (16P) The signal I/O connector to take the data out of the DAA-100 PCB
8 APH connector (8P) The signal I/O connector for communication with P.C.
9 CPU The main processor to control the charging device and the UPS.
(TMS320C31PQL)
10 ASIC(CF5900PCM) The ASIC containing the PWM generator, the PWM protector, the
speed detector, the 16 bit timer, and the I/O decoder
11 Detection circuit of The circuit to detect the magnitude and phase of the 3-phase input
input voltage voltage
12 Detection circuit of The circuit to detect the magnitude of the 3-phase input current
input current
13 A/D converting circuit The circuit to convert analog signals into digital signals
14 LCD interface circuit The ancillary circuit to input and output signals to the
announciator
- 12 -
3) LED DISPLAY FUNCTIONS OF THE DAC-100 PCB
* While the ALP control panel stands by, LED1 and LED5 are flickering simultaneously.
- 13 -
○ APB connector: A power input connector for DAC-100 PCB
3 GND
6 GND
9 GND Ground 18
- 14 -
○ APE connector: To be connected to the announciator.
- 15 -
○ APG connector: To be connected to the DAR-100 PCB.
18
19 SEQ_CON
20
21
22
23
24
25 GND Ground
26 GND Ground
- 16 -
○ APH connector: To be connected to the PC
- 17 -
2.3 DAR-100 PCB
1) OUTLINE DRAWING OF THE DAR-100 PCB
- 18 -
2) EXPLANATIONS OF THE PCB FUNCTIONS
No.
2 APR connector (20P) The connector for contactor-drive and contact signal I/O
3 APP connectors (6P) The power supply connector linked to the battery
The connector for the power supplied to DAP-100 PCB
4 APM connector (4P) The connector receiving output voltage from input transformer
(TR2)
5 APS connector (8P) The connector for power supplied to DAC-100 PCB
7 Fuse 3 The fuse for 100V power received from the input transformer
(TR2)
8 Fuse 2 The fuse for 45V power received from the input transformer
(TR2)
9 Power circuit of P5, The circuit to generate 5V, 15V, and –15V from the input direct
P15 and N15 voltage (DC60V)
5V, 15V, -15V: Power for the DRC-100 PCB circuit
10 Power circuit of P24 The circuit to generate 24V, and 12V from DC 60V
and P12 24V: Power for the relay drive
12V: Power for the FET driving signal
11 Power supply circuit When power fails: DC 60V of the battery is supplied to the power
When operation is normal: DC 60V of the power supply is
supplied by rectification of AC45V
When power is loaded: The initial rush current is limited by NTC
12 Contactor drive circuit The circuit to drive the contactors (97SB, 97SBX, 97SD, FAN)
FET: 97SB, 97SBX, 97SD
SSR: Drive the FAN
13 Relay drive circuit The circuit to drive the relays (97B, 35AH, 97CHR) by relay
driving signals from the DAC-100 PCB
14 Surge arrester circuit The circuit to absorb the surge voltage when switching on and off
for the contactor the contactor(97SA), the relay(97SC, 97S), and FAN
- 19 -
3) LED DISPLAY FUNCTIONS OF THE DAR-100 PCB
CONNEC- OPERATING
PIN SIGNALS DIRECTIONS REMARKS
TORS CONDITIONS
1 XR9CHR DAR DAC High Relay signals of charger
operation
2 ZR9B DAC DAR High Driving signal of ALP
safety relay
3 XR9S DAR DAC High Relay for detection signal
of power failure
4 ZR3AH DAC DAR High Driving signal for the relay
to block the 97SA
5 XR9B DAR DAC High Detecting signal of the ALP
safety relay
6 ALP-LIVE
7 XC9B DAR DAC High Detection signal of the
contactor operation to the
A battery
P 8 ZR9CHR DAC DAR High Relay-driving signal of the
K charging device operation
9 XC9A DAR DAC High Detection signal of the main
contactor operation of the E/L
10 ZC9B DAC DAR High Driving signal of the
contactor to the battery
11 XC9X DAR DAC High Detection signal of operation
for the charging device and
the contactor
12 ZC9X DAC DAR High Contactor-driving signal of
the charger operation
13 XC9D DAR DAC High Contactor detection signal for
limiting the rush current
14 ZC9D DAC DAR High Contactor driving signal for
limiting the rush current
- 20 -
CONNEC- OPERATING
PIN SIGNALS DIRECTIONS REMARKS
TORS CONDITIONS
15 XR3AH DAR DAC High Detection signal for the relay
to block the 97SA
16 ZFAN DAC DAR High FAN operation signal
17 RY_OUT DAC DAR High I48A Chip select
A 18 NC
P 19 SEQ-CON DAR DAC Low Connection status check of
the connector
K
20 NC
~
24
25 GND
26 GND
NC means NO CONNECTION.
- 21 -
○ APP connector: To be connected to the DAP-100 PCB and battery
CONNEC- OPERATING
PIN SIGNALS DIRECTIONS REMARKS
TORS CONDITIONS
1 Batt_48V Batt DAR DC48V Input of battery 48V
2 DRV_DCN DAR DAP DCN Supply DCN to the DAP
PCB
A 3 DRV_60V DAR DAP DC60V Supply DC 60V to the DAP
P PCB
P 4 Batt_60V Batt DAR DC60V Input of battery 60V
5 Batt_60V DAR DAP DC60V Supply battery 60V to the
DAP PCB
6 DRV_DCN Batt DAR DCN Input of DCN
CONNEC- OPERATING
PIN SIGNALS DIRECTIONS REMARKS
TORS CONDITIONS
1 AC110_U TR2 DAR AC110V 97SA drive and power-failure
detection
CONNEC- OPERATING
PIN SIGNALS DIRECTIONS REMARKS
TORS CONDITIONS
2 GND GND
3 GND GND
A
4 GND DAR DAC GND
P
5 P24 DAR (MCA/8) 24V
S
6 N15 DAR DAC -15V
8 P5 DAR DAC 5V
- 22 -
2.4 DAP-100 PCB
1) OUTLINE DRAWING OF THE DAP-100 PCB
- 23 -
2) EXPLANATION OF PCB FUNCTIONS
No.
1 ADA connector (20P) The signal I/O connector linked to the DAP-200 PCB
2 APF connector (14P) The signal I/O connector linked to the DAC-100 PCB
3 ADB connector (8P) The connector for the power supplied by DAR-100 PCB
4 P15 power circuit The circuit to generate the phases of (U,V,W,U-,V-,W-) IPM
power 15V from the DAR-100 PCB and AD210AN power
15V to detect the battery power
5 IPM drive circuit The circuit to drive IPM through the photo coupler by using
the PWM signals supplied by the DAC-100 PCB.
6 Battery detection circuit The circuit to detect the battery voltage supplied by DAR-100
- 24 -
4) DEFINITION OF DAP-100 PCB CONNECTOR SIGNALS
○ APF connector: To be connected to the DAC-100 PCB.
• NC means NO CONNECTION.
- 25 -
○ ADB connector: To be connected to the DAR-100 PCB.
OPERATING
PIN SIGNALS REMARKS
CONDITIONS
1 NC
2 NC
3 NC
4 NC
5 Batt_60V DC60V To receive battery 60V from the DAR PCB (APP5)
8 NC
• NC means NO CONNECTION.
- 26 -
3. EXPLANATION OF SYSTEM OPERATIONS
The ALP control panel is composed of the ALP operation control part, the UPS control part, the
charge control part, and the power circuit part.
Outbreak of E/L
power failure panel
ALP
panel
Detection of
power failure
NO
Is it 3 seconds
or longer?
Completion of
YES rescue operation
Display of the
Normal safety rescue operation
circuit
Is power NO
YES Is it at the door restored?
opening zone?
NO YES
- 27 -
If power fails during the normal operation of the elevator, the relay (R9S) of power failure detection in
the DAR-100 PCB is activated. Once the DSP judges that power failure is 3 seconds or longer with
recognition of the signal, it activates the ALP control to be ready for rescue operation. The DSP of the
DAC-100 PCB generates constant AC voltage of constant frequency that is supplied to the elevator
control panel. The E/L control panel activated by the ALP control checks whether or not the safety status
of the elevator is normal. When position of the car is at the door opening zone, passengers can be rescued
by opening the doors. Otherwise, the DSP compares weight of the car with that of the counter weighter
for commanding the DPC-100 PCB to control the speed patterns for rescue operation, in that the elevator
moves downward if the car weighs more, but upward if it weighs same or less. Once the DPC-100 PCB
receives speed patterns, it controls the inverter to drive the motor in rescue operation speed, making the
car stop at the door opening zone to rescue passengers in the car. Once rescue operation is completed, the
E/L control panel sends a signal informing completion of rescue operation to the ALP control panel. The
ALP control panel that received the completion signal ceases the UPS operation, and it displays status of
the ALP control panel and lasts rescue operation until the power is restored. Then, the E/L control panel
returns to the normal status.
Detection of Detection of
battery voltage power failure
NO Is the charging NO
necessary? Is it 3 seconds
or longer?
YES YES
UPS operation
Operation of the
charge device
Completion of
rescue operation
Completion of
charge operation
Rest of the
ALP operation
- 28 -
Figure 6 shows flow chart of the ALP operation. If the ALP operation lasts for 5 minutes after
power is restored, it activates the charge operation to charge the battery. If power fails again
during the charge operation, it ceases the charge operation and performs the rescue operation
again. Once the charge operation is completed, the ALP control panel returns to standby status
until the next event occurs.
- 29 -
If DC 60V of battery is converted into PWM voltage supplied to the main transformer (TR1) by
the inverter, the output voltage (AC380Vrms) of the main transformer flattens to the sinusoidal
wave voltage of the same magnitude as commercial voltage by the filter to be supplied to the
E/L control panel. Features of the UPS control are as follows.
a. It controls the voltage and frequency of the power which is supplied to the E/L control panel.
b. It detects the voltage using the voltage sensor to the adjust the voltage supplied to the E/L
control panel to the commercial voltage, generating voltage command accordingly.
c. It generates the output of the constant voltage and frequency by switching the inverter in a
high speed PWM mode, and also maintains the voltage supplied to the E/L control panel as
the sinusoidal wave voltage to avoid the distortion of voltage for the operation.
- 30 -
Figure 9 shows the charging pattern. The charge control is governed by the same control algorithm as the
PWM voltage typed converter. It has following advantages.
Battery lifetime extends by setting the charge pattern of the battery according to the battery type.
Battery lifetime extends by reducing ripples of the charge current during the battery charging.
The harmonic distortion is reduced by controlling the input current to be a sinusoidal wave through
the high speed PWM switching.
Energy loss is minimized by controlling the input power factor to be “1” while charging.
If the battery voltage is 60V or less, the charging begins by operating the charge device. In case that the
battery voltage is DC 72V or less while charging, the operation is proceeded for three hours in a constant
current mode, otherwise it is proceeded in a constant voltage mode. If the battery voltage is DC 54V or
less, the battery under voltage is displayed 80V or more, it displays a failure by detecting the battery
over-voltage.
- 31 -
4. ANNOUNCIATOR
4.1 OVERVIEW
By arranging a maintenance controller on the board in the form of separated PCB, the necessary
functions for installation and repair, for example, data search, data set, and failure detection, are
provided.
4.2 FUNCTIONS
Display the ALP status
Data set for test & commissioning
Controlling charge operation, UPS operation, rescue operation, etc.
Data read
4.3 CONFIGURATION
Following is a configuration of the DOA-100 PCB.
- 32 -
MAIN MODE RESETTING
MODES KEY I/O
MODE DESCRIPTIONS
INPUT TYPES
- 33 -
4.5 NORMAL MODE
Column
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Row
1 – R E S T M O D E –
2 E R R – N O :
3 M O D – N O :
4 V A L U E :
Column
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Row
1 – C H A R G E M O D E –
2 E R R – N O :
3 M O D – N O :
4 T I M E : 0 : 0 0
4 V A L U E :
- 34 -
Once the display on the 4th row changes, it is possible to output the status description that
needs to be displayed
④ 4th row: displays the charging time
Once “FFFF” is input on the 3rd row, the display of the charging time changes to the “VALUE:”
1 – U P S M O D E –
The 2nd, 3rd, and 4th rows are same as the initial screen of the normal mode.
1 – R E S T M O D E –
4 R E C H A R G E : 0 0 0 0
Numbers on the 11th to 14th columns of the 4th row increase from 0 to 7500, followed to
be changed to the charge mode.
The 2nd and 3rd rows are same as the initial screen of the normal mode.
3 M O D – N O : C 0 0 E –
3 M O D – N O : C 0 7 E –
3 M O D – N O : C 0 8 E –
4 V A L U E :
Check if “VALUE” is displayed on the 1st to 7th columns of the 4th row.
CHANGE THE SCREEN FROM THE CHARGE MODE TO THE DATA READ MODE
In case that the 4th row in the charge mode is displayed as the following, input “FFFF”
on the 3rd row.
4 T I M E : 0 : 0 0
Once “FFFF” is input, the 4th row changes to the data read mode, and the data is
displayed on it.
3 M O D – N O : B 0 0 E
Input “E” followed by the related key numbers to be initial B.
4 V A L U E : 0 7 2
Once the key input is completed, the data are displayed on the 12th to 14th columns of
the 4th row.
3 M O D – N O : F F F F
To release the data read mode, input “FFFF” on the 3rd row.
Once the data read mode is released, the data of the 4th row are not displayed, but the 4th
row screen of the previous mode is displayed.
3 M O D – N O : C 0 1 E
Input “E”, followed by the related key numbers to be initial C on the 3rd row in normal
operation.
Once “E” is input, the screen does not display the code which was entered on the 3rd row,
but wait for the data to be input.
3 M O D – N O : 0 1 E
Input “E” if the data input is completed by inputting the data of two digits.
Once “E” is input, the screen does not display the code which was entered on the 3rd row,
but wait for the key input.
- 36 -
RELEASE SCREEN OF DATA WRITE MODE
3 M O D – N O : F F F F
To release the data write mode, input “FFFF” on the 3rd row.
Once the data write mode is released, the data of the 3rd row is not displayed.
To check if the data was input correctly, switch to the data read mode and input the
related code.
2 E R R – N O :
Unless there is an error, no data are displayed on the 2nd row.
2 E R R – N O : E R R O R
If there is an error, the “ERROR” message is displayed on the 10th to 14th columns of the
2nd row.
2 E R R – N O : E R R 1 0
3 M O D – N O : A
If “A” is input on the 10th column of the 3rd row, the most significant TCD number of
the errors made on the 2nd row is displayed.
If “A” is input again on the same column, the TCD number of the next significant error is
displayed .
2 E R R – N O : E R R 6 0
3 M O D – N O : A A A A
If “A” is displayed on both 10th and 11th columns of the 3rd row, it means that the error
TCD number on the 2nd row has been displayed to the least significant rank.
Once the error TCD number is displayed, input “AAAA” on the 10th to 13th columns of
the 3rd row.
- 37 -
TCD DISPLAY RE-OUTPUT SCREEN
3 M O D – N O : F F F F
Input “FFFF” on the 3rd row to re-output the error TCD number, and the TCD retrieval
screen is displayed on the 3rd row.
3 M O D – N O : D D D D
Input “DDDD” on the 3rd row to release the error TCD number, and the screen is switched
to the normal mode.
- 38 -
5. TEST OPERATION
Commercial
power EMI Filter
MCCB
E/L
E/L
control panel
ALP BKM
control panel
MCCB
Battery
ALP
Power Stack
detection
Power
failure
C9A
If it is necessary to work for the elevator after installing the ALP, make sure to turn off the MCCB
in the E/L control panel. Turning the MCCB of the distribution panel of the building off, the ALP
control panel recognizes this to be a power failure and applies voltage same as a commercial
power (AC380V) to the E/L control panel. This increases a possibility of electric shock.
▷ When turning the E/L MCCB off, power of the ALP control panel is turned off.
▷ Although the MCCB of the ALP control panel is turned off, it does not affect operation
of the elevator.
▷ Although the MCCB of the ALP control panel is turned off, be careful against an electric
shock, since AC380V is applied to the failure detection circuit in the ALP control panel.
▷ In case that the ALP control panel requires a partial repair during normal operation of the
elevator, do not turn off the BKM switch on the input terminal of the transformer (TR2)
which serves for supplying power to the failure detection circuit in the ALP control
panel, because the elevator stops in an emergency mode.
- 39 -
▷ In case that the ALP control panel requires a whole repair and therefore the BKM switch
needs to be off, conduct the repair work while the elevator is not in use after turning off
the MCCB of the E/L control panel.
▷ Although a trouble occurred on the ALP control panel, it does not affect normal
operation of the elevator at all.
▷ In case that rescue operation lasts for 5 minutes, the ALP control panel stops UPS and
displays excess of the rescue operation time (TCD42).
▷ Once the rescue operation is completed, the elevator returns to a rest mode after stopping
the UPS. Following the rest state, the charge operation is automatically performed at 10
minutes after the power returns.
5.3 CHECKING
1) ELEVATOR
① Check if the elevator doors of all the stories are closed and the locking devices are safe and
firm.
② Is there any interference by equipment installed in the hoistway?
③ Is there any problem in the safety system of the elevator?
④ Is the elevator operated normally?
2) CONTROL PANEL
① Is the control panel arranged clearly?
② Are the power lead-in, Wiring & Bolting between the E/L and ALP control panels good?
3) BATTERY
① Check if the case is broken or if anything appears wrong.
- 40 -
② Check clean of terminals after tightening and applying them with grease or Vaseline.
③ Then check if it is covered with a rubber cover.
④ Check if a battery charge indicator is in normal.
⑤ Take a careful look around the battery against fire, static electricity, and electric short
between the terminals.
40Ah
11 ㎾
applicable
13 ~ 15 ㎾
50Ah
Not
18 ~ 22 ㎾ 60Ah
30 ㎾ Not applicable
Battery capacity Number of uses Drawings
40Ah, 12V 5EA (60V) 3×04866A
50Ah, 12V 5EA (60V) 3×04866B
60Ah, 12V 5EA (60V) 3×04866C
- 41 -
4) WIRING CONNECTION BETWEEN E/L CONTROL PANEL AND ALP CONROL
PANEL
MCCB
(Auxiliary
contacts)
Serial
communication
- 42 -
5) CONNECTION CHECK OF PRIMARY TERMINAL OF TRANSFORMERS 1 AND 2
IN ALP CONTROL PANEL
Change position
E/L control panel
3-phase power E/L control panel Connection to the TRANS-1
MCCB
of building Power trans of ALP control panel
Secondary voltage
Primary terminal Primary terminal
of TR1 of TR2
200-240V Available 380V U380,V380,W380 380V, 0V
460-480V
380V None
400V None 400V U400,V400,W400 400V, 0V
440V None 440V U440,V440,W440 440V, 0V
- 43 -
④ Disconnect the power wires connecting the ALP control panel contactors from the battery
terminal boxes.
⑤ Disconnect all the connectors led to the PCB.
⑥ Remove all the fuses out of the fuse holder
⑦ Common both ends of DCN and DCP of the DC link using clips.
⑧ Common input terminals of the power MCCB and I/O terminals of reactors using clips.
⑨ Disconnect the primary and secondary ends of the main transformer (TR1), and common
transformer terminal boxes (U1,V1,W1,U2,V2,W2) using clips.
LG MEASUREMENT
MEASUREMENT POINTS
SPECIFICATIONS RESULTS
EP1(E/L FRAME) <--> EAP1(ALP FRAME) 1MΩ or more
Terminal box (U,V,W) <--> EAP1
Terminal box (R,S,T) <--> EAP1
Transformer terminal box (U1,V1,W1) <--> U2,V2,W2)
Transformer terminal box (U1,V1,W1) <--> EAP1
Transformer terminal box (U2,V2,W2) <--> EAP1
Reactor I/O terminal box <--> EAP1
FUSE HOLDER of DAR-100 PCB <--> EAP1 0.5MΩ or more
97SA Main contacts <--> EAP1
97SB Main contacts <--> EAP1
97SBX Main contacts <--> EAP1
97SD Main contacts <--> EAP1
4) RATING OF FUSES
Check if the rating of fuses 1-3 in the DAR-100 PCB is 125V and 5A.
5) CIRCUIT CHECK
① Check if all the connectors and terminal boxes which are disconnected for an insulation
resistance test are brought back to the previous state.
- 44 -
② Prepare a multi meter.
③ Check the wirings according to the following table.
APD H.CT, PT
APC Serial transfer
APB DAR-100 APS P5, P15, N15 power
DAR-100 APR MT (CTT ASY) CTT contact, driving line
APP DAP-100 ADB Battery power source
APM TR2 AC110V, AC45V
DAP-100 ADA IGBT MIG IGBT driving signal
Change position
E/L control panel
3-phase power E/L control panel Connection to the TRANS-1
MCCB
of building Power trans of ALP control panel
Secondary voltage
Primary terminal Primary terminal
of TR1 of TR2
200-240V Available 380V U380,V380,W380 380V, 0V
460-480V
380V None
400V None 400V U400,V400,W400 400V, 0V
440V None 440V U440,V440,W440 440V, 0V
- 45 -
② Check if the primary voltage of C9A CTT in the ALP control panel is same as the
secondary voltage of MCCB in the E/L control panel shown in Table 1, and also the
primary voltages of TR1 and TR2 in the ALP control panel are same as those of Table 1.
Adjust them if necessary.
RATED MEASURED
No. MEASURING POINTS REMARKS
VOLTAGE VOLTAGE
1 APP.1⊕ – APP.2 DC 48V
2 APP.4⊕ – APP.2 DC 60V
3 APP.3⊕ – APP.2 DC 60V
4 APP.5⊕ – APP.2 DC 60V
5 APM.1 - APM.3 AC 110V
6 APM.2 - APM.4 AC 45V
7 APS.5⊕ – APS.1 DC 24V Not drawn outside
(APS # 2,3,5)
8 APS.6⊕ – APS.2 DC -15V
9 APS.7⊕ – APS.3 DC 15V
10 APS.8⊕ – APS.4 DC 5V
- 46 -
⑩ Record the voltage of the DAR-100 PCB in the following table.
RATED MEASURED
No. MEASURING POINTS REMARKS
VOLTAGE VOLTAGE
1-1 ADB.1⊕ - ADB.2 DC 60V Before correction
2-1 ADB.3⊕ - ADB.2 DC 60V
1-2 ADB.5⊕ - ADB.6 DC 60V After correction
2-2 ADB.7⊕ - ADB.6 DC 60V
3 CH1⊕ - CH2 DC 6V
4 ADA.13⊕ - 14 each ends DC 15V
5 ADA 15⊕ - 16 each ends DC 15V
6 ADA 17⊕ - 18 each ends DC 15V
7 ADA 19⊕ - 20 each ends DC 15V
8 LED5 each ends DC 2V
※ Measure the voltage between CH1 and CH2 by adjusting the variable resistor VR1 so that
ratio of ADB1-ADB2 (before correction, 4P MOLEX) and ADB5-ADB6 (after correction,
8P MOLEX) are to be (10:1)+0.2V.
RATED MEASURED
No. MEASURING POINTS
VOLTAGE VOLTAGE
1 APB.1⊕ - APB.4 DC 15V
2 APB.2⊕ - APB.4 DC 5V
3 APB.3⊕ - APB.4 DC -15V
※ Turn off the MCCB and APY switch of the ALP control panel, and insert the connectors of
APF and ADA in the DAP-100 PCB.
- 47 -
5) LED CHECK ON THE PCB
Turn on the MCCB and APY switch of the ALP control panel.
① DAC-100 PCB
② DAR-100 PCB
③ DAP-100 PCB
- 48 -
5.6 ADJUSTMENT
PROCESSES AND
No. ITEMS SETTINGS
CHECK POINTS
1 Battery over-current 98A Process in the PCB inspection
guideline
2 Battery over-voltage 80V Process in the PCB inspection
guideline
3 Battery under-voltage 54V Program modification
4 Trouble in UPS voltage control Commercial Program modification
voltage±10% Adjust primary tap of transformer
(TR1) according to the voltage
specification
5 IGBT over-current 158 A IGBT equipped internally
6 Protection against IGBT-short- 360A IGBT equipped internally
circuit
7 Protection against over-heating 111°C IGBT equipped internally
8 Excess of the rescue operation 5 minutes Program
time
9 Excess of the charge operation 4 hours Program
time
10 Commercial power under AC280V (75%) Program
voltage
- 49 -
5.7 TEST OPERATION
Building MCCB ON
E/L MCCB ON
ALP PANEL BKM(APY) S/W ON
- 50 -
2) TEST CHARGE OPERATION
- 51 -
3) RESCUE OPERATION WHEN STOPPING WITHIN DOOR OPENING ZONE
- 52 -
4) RESCUE OPERATION WHEN STOPPING WITHOUT DOOR OPENING ZONE
- 53 -
5.8 CHECKLIST FOR THE RESCUE OPERATION
Normal
operation
E/L speed Rescue
operation
- 54 -
2) CHECKLIST FOR OPERATION FUNCTIONS
- 55 -
5.9 ACTIONS TO TAKE AFTER COMPLETING TEST OPERATION
Clear the numbers of times for charge operation and rescue operation from the announciator.
① If the address B16E is pressed, the number of charge operation is displayed on the VALUE
space of the announciator. Also, if the address B17E is pressed, the number of times for
rescue operation is displayed on the VALUE space of the announciator.
② If the address C04E is pressed, “ERASE OK” is displayed on the VALUE space of the
announciator.
③ Turn off/on the MCCB of the ALP control panel, press the address B16E to check if “000”
is displayed on the VALUE space, and also press B17E to check if “000” is displayed.
6. REGULAR INSPECTION
3 ① Check the number of times for rescue operation Refer “※Note 1” below in
from the announciator? (Address: B17E) case that the number of times
for charge operation is “2”
② Check the number of times for charge operation more than that for rescue
from the announciator? (Address: B16E) operation.
- 56 -
7. ALP OPERATION TCD DESCRIPTION
① The trouble codes mentioned in this document are equally applied to the ALP for DI
elevators (60-150 m/min).
② TCD is classified by a function using the numbering system of 10 through 67.
③ When troubles listed in the TCD numbers occurred, the ALP operation is controlled and
managed by Trouble_sum Flag.
0 TROUBLE-10 A1 Not possible for charge and rescue operations R9B off
1 TROUBLE-20 A2 Not possible for charge and rescue operations R9B off
2 TROUBLE-30 B1 Not possible for charge and rescue operations R9B off
- 57 -