x3 Hybrid g4 User Manual en
x3 Hybrid g4 User Manual en
User Manual
5.0kW - 15.0kW
EN
SolaX Power Network Technology (Zhejiang) Co., Ltd. Copyright Declaration
The copy right of this manual belongs to SolaX Power Network Technology(Zhejiang) Co. , Ltd.(SolaX
ADD.: No. 288 Shizhu Road, Tonglu Economic Development Zone, Power Co. , Ltd. ) . Any corporation or individual should not plagiarize, partially or fully copy it
Tonglu City, Zhejiang Province, 310000 P. R. CHINA (including software, etc. ) , and reproduction or distribution of it shall not be allowed in any form or
by any means. All rights reserved. SołaX Power Network Technology (Zhejiang) Co. , Ltd. reserves the
Tel.: + 0571- 5626 0011 right of nal interpretation. The contents are subject to change without prior notice.
E-mail: [email protected]
614.00897.00
Contents
Contents
1 Note on this Manual ................................................. 03
1.1 Scope of Validity .................................................................... 03
1.2 Target Group .......................................................................... 03
1.3 Symbols Used .......................................................................... 03
1.3.1 Important Safety Instructions............................................ 04
1.3.2ExplanationofSymbols...................................................... 09
1.3.3 CE Directives........................................................................ 11
2 Introduction...................................................................... 12
2.1 Basic Features.........................................................................12
2.2 Electrical Block Diagram of The System.........................12
2.3 Work Modes .............................................................................. 15
2.4 Dimension................................................................................17
2.5 Terminals of Inverter .............................................................18
4 Installation .............................................................................. 22
4.1 Check for Transport Damage ...................................................... 22
4.2 Packing List .................................................................................................. 22
4.3 Installation Precautions ..................................................................... 24
4.4 Tool Preparation ...................................................................................... 25
4.5 Installation Site Conditions ............................................................ 27
4.5.1 Installation Carrier Requirements ............................................. 27
4.5.2 Installation Requirements............................................................... 27
4.5.3 Installation Space Requirements................................................. 28
4.6 Mounting ...................................................................................................... 29
01
Contents Notes on this Manual
Caution! Warning!
“Caution” indicates a hazardous situation which, if not Before performing maintenance, cleaning or operation
avoided, could result in minor or moderate injury. on the circuit connected to the inverter, authorized
maintenance personnel must first disconnect the AC
and DC power supplies of the inverter.
Note!
“Note” provides tips that are valuable for the optimal
operation of our product. Warning!
The inverter can not be operated when it is running.
Danger! Warning!
Danger to life due to high voltages in the inverter!
Risk of electric shock!
The personnel responsible for the installation,
electrical connection, debugging, maintenance and
fault handling operation of this product need to be Strictly follow relevant safety specifications for product installation
trained, master the correct operation method, have the and testing. During installation, operation or maintenance, please
corresponding electrician qualification and safety read carefully and follow the instructions and precautions on the
operation knowledge. inverter or user manual. If the operation is incorrect, it may cause
personal and property losses. Please keep the user manual properly
Caution! after use.
When the inverter is working, it is strictly forbidden to
touch the shell. The temperature of the shell is high and This inverter can only use the accessories sold and recommended by
there is a risk of scalding. our company, otherwise it may cause fire, electric shock or
casualties. Without the authorization of our company, you may not
open the inverter cover or replace the inverter parts, otherwise the
Caution!
warranty promise of the inverter will be invalid.
Radiation may be harmful to health!
Do not stay for a long time and keep at least 20 cm away
The use and operation of the inverter must be carried out in
from the inverter.
accordance with the instructions in this manual, otherwise this
protection will fail and the warranty of the inverter will also fail.
Note! During working, the inverter surface temperature may exceed 60 °C ,
Ground PV system. please make sure the inverter cools down before touching, and
Finish PV modules and photovoltaic system grounding make sure children can not touch.
in accordance with local requirements to achieve
optimal protection of systems and personnel. When exposed to sunlight, photovoltaic arrays generate dangerous
high DC voltages. Please follow our instructions, otherwise it will be
life-threatening.
Warning!
Ensure that the input DC voltage is below the inverter
All DC and AC power sources must be disconnected from the
limit. Excessive DC voltage and current may cause
inverter for at least 5 minutes before any wiring or electrical
permanent damage or other losses to the inverter,
operation is performed on the inverter to ensure complete isolation
which is not covered by the warranty.
of the inverter and avoid electric shock.
04 05
Safety Safety
A photovoltaic module used on the inverter must have a IEC61730A If the building installed with external light protection device is
rating, and the total open circuit voltage of the photovoltaic string / far away from the inverter location, in order to protect the
array is lower than the maximum rated DC input voltage of the inverter from electrical and mechanical damage, the inverter
inverter. Any damage caused by photovoltaic over voltage is not should also install an external lightning protection equipment.
covered by warranty.
In order to protect DC system, two-stage surge protection
Installation position should be away from wet environment and equipment is needed between DC cable of inverter and
corrosive substances.
photovoltaic equipment module.
After the inverter and power grid cut off the PV power supply, there
In order to protect the AC system, the level 2 surge protection
will be a certain amount of residual current in a short time, be
cautious or it may lead to serious personal injury and even high risk equipment should be installed at the AC output, located
of death. Use a multimeter (impedance at least1 MΩ) to measure the between the inverter and the grid. Installation requirements
voltage between the UDC and the UDC- to ensure that the inverter must comply with IEC61643-21 standard.
port is discharged below the safe voltage before starting operation
(35 VDC). All DC cables shall be installed in a distance as short as possible,
and the positive and negative cables of the same input need to
Ø Surge protection devices (SPDs) for PV installation be bundled together to avoid causing loops in the system.
Minimum distance installation and binding requirements also
Warning! apply to auxiliary grounding and shielding grounding
Over-voltage protection with surge arresters should be conductors.
provided when the PV power system is installed.
The grid connected inverter is fitted with SPDs in both
Ø Anti-lslanding Effect
PV input side and MAINS side. The islanding effect means that when the power grid is cut off, the
grid-connected power generation system fails to detect the power
Direct or indirect lightning strikes can cause failures. Surge is the outage and still supplies power to the power grid. This is very dangerous
main cause of lightning damage to most devices. Surge voltage may
for the maintenance personnel and the power grid on the transmission
occur at photovoltaic input or AC output, especially in remote
mountain areas where long distance cable is supplied. line.
The inverter’s use active frequency offset method to prevent islanding
Please consult professionals before installing SPDs. effect.
06 07
Safety Safety
www.tuv.com
TUV certified.
ID 1111227431
08 09
Safety Safety
1.3.3 EC Directives
Beware of hot surface. This chapter describes the requirements of the European low
The inverter can become hot during operation. Avoid voltage regulations, including safety instructions and system
contact during operation. licensing conditions, the user must comply with these regulations
when installing, operating, and maintaining the inverter, otherwise
it will cause personal injury or death, and the inverter will cause
Danger of high voltages.
damage.
Danger to life due to high voltages in the inverter!
Please read the manual carefully when operating the inverter .If you
Danger. do not understand "danger", "warning", "caution" and the
Risk of electric shock! description in the manual, please contact the manufacturer or
service agent before installing and operating the inverter.
10 11
Installation Introduction
2 Introduction
Diagram B: N line and PE line separate wiring, M series inverter ;
2.1 Basic Features
(For most countries)
This high-quality inverter can convert solar energy into
alternating current and store energy into batteries. PV 1
The inverter can be used to optimize self-consumption, stored in Inverter PV 2
batteries for future use or fed into the public grid. The way it
CT
works depends on user preferences. It can provide emergency
CT-R Main Breaker/RCD
power during power outages.
BAT Grid EPS(Off-grid) CT-S
CT-T
2.2 Electrical Block Diagram of The System N
X3-Matebox Grid
The inverter has two wiring schemes, one is for M series
inverter connected to X3-Matebox, and the other is for D series E-BAR
inverter.
There are different ways of wiring in different countries, one is to
connect N line with PE line, the other is to separate the line from
Breaker
Breaker
the PE line wiring, see below;
Distribution Box
Diagram A: N line and PE line separate wiring , D series inverter ; Battery
EPS(Off-grid) loads Loads
(For most countries)
Breaker
Distribution Box N
Battery
RCD
EPS(Off-grid) loads Loads
Breaker
Breaker
N-BAR for EPS(Off-grid) loads N-BAR for loads Distribution Box
Battery
EPS(Off-grid) loads Loads
12 13
Introduction Introduction
Breaker
Breaker
• Please control the inverter load and make sure it is Battery min SOC can be set: 10%-100%;
Charge battery to min SOC can be set:10%-100%.
"output value" in "within " EPS(Off-grid) mode, otherwise
the inverter will stop and alarm overload fault". Feed-in priority
The Feed-in priority mode is suitable for areas with
• Please confirm with the grid operator whether there are high feed-in subsidies, but has feed-in power
special regulations for grid connection. limitation.
①When the power of PV is sufficient
①
Active Charging time period: PV power the battery
to the set value, and then power the load, and sell the
③
surplus power to the grid.
If the local grid company limits the grid-connected
②
power of the inverter, the excess energy continues to
charge the battery.
(PV>Battery, PV→Battery→Load→Grid → Battery)
14 15
Introduction Introduction
503mm
that the emergency loads can be used when the
grid is off. Customers no need to worry about the
battery capacity.
16 17
Introduction Technical Data
Max. recommended DC power [W] A:4000/B:4000 A:5000/B:5000 A:8500/B:5000 A:10500/B:6000 A:11000/B:7000 A:11000/B:7000
Max. input current [A] 16/16 16/16 26/16 26/16 26/16 26/16
EPS
Max. short circuit current [A] 20/20 20/20 30/20 30/20 30/20 30/20
Start output voltage [V] 200 200 200 200 200 200
No. of MPP trackers 2 2 2 2 2 2
Strings per MPP tracker A:1/B:1 A:1/B:1 A:2/B:1 A:2/B:1 A:2/B:1 A:2/B:1
I M
J K L
3.2 AC Output/Input(apply to version D/M)
Object Description
A DC switch Model X3-Hybrid-6.0 X3-Hybrid-8.0-M
X3-Hybrid-5.0 X3-Hybrid-6.0-M X3-Hybrid-8.0 X3-Hybrid-10.0-M
X3-Hybrid-10.0 X3-Hybrid-12.0-M
X3-Hybrid-12.0 X3-Hybrid-15.0-M
X3-Hybrid-15.0
X3-Hybrid-5.0-M
B PV connection port AC Output
C Battery connection port Nominal AC power[ W ] 5000 6000 8000 10000 12000 15000(PEA 14000)
Max. apparent AC power [ VA] 5500 6600 8800 11000 13200 15000
D USB port for upgrading
Rated AC voltage [V] 415/240; 400/230; 380/220
E COM port Rated grid frequency [Hz] 50/60
F Battery communication Max. AC current [A] 8.1 9.7 12.9 16.1 19.3 24.1
I Ground connection port Rated AC power [W] 10000 12000 16000 20000 20000 20000
Fans(only for X3-Hybrid-12.0-D/M and X3-Hybrid-15.0-D/M ) Rated grid voltage(range) [V] 415/240; 400/230; 380/220
J
Rated grid frequency [Hz] 50/60
K External monitoring connection port
Max. AC current [A] 16.1 19.3 25.8 32.0 32.0 32.0
CAN1 and CAN2 are for parallel communication / OFF is for
L
external shutdown/ DRM Port(only for Australia)
M EPS(Off-grid) Output(main load connection port)
Warning!
Qualified electrician required for the installation.
18 19
Technical Data Technical Data
Battery type Lithium batteries EPS(Off-grid) rated power[VA] 5000 6000 8000 10000 12000 15000
Battery Full Voltage [V] 180-800 EPS(Off-grid) rated voltage [V] 400V/230VAC
Maximum charge/discharge flow [A] 30A Frequency[ Hz] 50/60
Communication interface CAN/RS485 EPS(Off-grid) rated current [A] 7.2 8.7 11.6 14.5 17.5 21.8
Reverse connection protection Yes EPS(Off-grid) Peak Power [VA] 7500, 60s 9000, 60S 12000, 60S 15000, 60S 15000, 60S 16500, 60S
Switching time [s] <10ms
Total harmonic distortion (THDv) <3 %
3.4 Efficiency, Safety and Protection(apply to version D/M)
Maximum efficiency 98.2% 98.2% 98.2% 98.2% 98.2% 98.2% Dimensions (W/H/D)[mm] 503*503*199
Max. battery charge efficiency Dimensions of Packing (W/H/D)[mm] 560*625*322
(PV to BAT )(@ full load) 98.5% 98.5% 98.5% 98.5% 98.5% 98.5%
Net weight [kg] 30 30 30 30 30 30
Max. battery discharge efficiency Gross weight* [kg] 34 34 34 34 34 34
(BAT to AC)(@ full load) 97.5% 97.5% 97.5% 97.5% 97.5% 97.5%
Heat dissipation treatment Natural Cooling Smart Cooling
Security & Protection <45
Noise emission(typical) [dB] <40
DC SPD Protection Integrated
Storage temperature range [°C] -40~+70
AC SPD Protection Integrated
Operating temperature range[°C] -35~+60 (derating at 45)
Over/under voltage protection YES
Humidity [%] 0%~100%
Grid protection YES
Altitude [m] <3000
DC injection monitoring YES
Ingress Protection IP65
Back feed current monitoring YES
Protective Class I
Residual current detection YES
Cold standby consumption <5W
Anti-islanding protection YES
Over voltage category III(MAINS), II(PV, Battery)
Over load protection YES
Pollution Degree III
Over heat protection YES
Installation mode Wall mounted
Array insulation resistance detection YES
Inverter Topology Non-isolated
Communication interface Meter/ CT, external control RS485, Pocket series, DRM, USB
* The specific gross weight is subject to the actual situation of the whole machine.
20 21
Installation Installation
4 Installation
4.1 Check for Transport Damage Number Quantity Description (for M series)
Ensure that the inverter is in good condition via transportation. If there A 1 the inverter
is any visible damage such as cracks, please contact the dealer B 1 Wall-mount Bracket
immediately. H 5 (Expansion bolt, Gasket, Self-tapping bolt)
I 1 M5 inner hexagon bolt
4.2 Packing List
J 3 Communication line RJ 45 adapter (COM/Meter/BMS)
Open the package and check the materials and accessories L 6 RJ 45 terminals
according to the following list. M Documentations
N 1 Pocket WiFi
O 1 Meter ( optional )
P 1 RJ 45 Terminal adapter
R 1 Ground cable
A B C D Number Quantity Description (for D series)
A 1 the inverter
B 1 Wall-mount Bracket
C 1 Waterproof shield
D 6 PV terminal (positive*2 or 3, negative*2 or 3)
E 6 PV pin angle (positive*2 or 3, negative*2 or 3)
E F G H
F 12 6 mm² European terminals
G 1 OT terminal(inverter grounding)
H 5 (Expansion bolt, Gasket, Self-tapping bolt)
I 1 M5 inner hexagon bolt
J 3 Communication line RJ 45 adapter (COM/Meter/BMS)
I J K L K 2 Battery connection terminals (positive*1, negative*1)
L 6 RJ 45 terminals
M Documentations
N 1 Pocket WiFi
O 1 Meter (optional)
P 1 CT
M N O P Q 1 RJ 45 Terminal adapter
Note:
“L ” The inverter in Australia needs to be connected to DRM, which is 1 more communication line
RJ 45 adapter than that in other countries.
The number of “D” and “E” are different for different power sections. For 5-6kW inverters,
the number of positive and negative PV terminal and PV pin angle is 2, 2, 2 and 2 respectively.
Q R For 8- 15kW inverters, the number of positive and negative PV terminal and PV pin angle is 3,
3, 3 and 3 respectively.
22 23
Installation Installation
Rubber Tape
hammer measure
Hexagon
Crimping
keys
Stay away from Direct Sunlight Rain Exposure Snow Lay up Stay away from Tool
combustibles antenna cables
Euro
terminal
crimping Spirit level
tool
Individual
Protection Dustproof Protective
Tools Cover glasses
24 25
Installation Installation
EPS
(Off-grid) Five-core cable
end wire ≤5°
Cable
Preparation
Grid end
Five-core cable
wire
Battery
Conventional wire
Cable
26 27
Installation Installation
≥300mm First find the expansion screw and the wall bracket in the accessory
bag, as shown below:
For multi-inverter installation scenarios, the inline installation
method is recommended; when the space is insufficient, the It consists of four parts
recommended method of installation in the form of "products"; it is
not recommended to install multiple inverters in stacks. If you
choose stack installation, please refer to the installation separation
distance below.
a) Use a spirit level and a marker to mark drilling holes of the bracket on
the wall.
≥300mm ≥300mm ≥300mm b) Drill holes at marked spots with depth of 65 mm.
≥1000mm ≥1000mm
≥500mm ≥500mm
28 29
Installation Installation
Φ8 Drill
b)
(Depth: 65 mm)
Hammer c)
f)
Inner hexagonal wrench
(Torque:1.2±0.1 N· m)
nut, Gasket,
d)
30 31
Electrical Connections Electrical Connections
5 Electrical Connections
5.1 PV Connection Ø Connection step
The inverter have two PV inputs. Please select photovoltaic modules The PV port wiring of the M series inverter has been completed. For
with good performance and quality assurance. The open circuit voltage speci c installation details, please refer to the X3-Matebox Quick
of the module array should be less than the maximum PV input voltage Installation Guide, the D series needs to be wired according to the
specified by the inverter, and the working voltage should be within the following steps.
MPPT voltage range.
Step 1. Turn off the DC switch, connect the PV module, prepare a 4
Table 1: Maximum input voltage limit(apply to version D/M) mm² PV cable, and find the PV (+) terminal and PV (-) terminal in the
package.
Model X3-Hybrid-5.0 X3-Hybrid-6.0 X3-Hybrid-8.0 X3-Hybrid-10.0 X3-Hybrid-12.0 X3-Hybrid-15.0
Warning!
Positive PV pin
The voltage of photovoltaic modules is very high, and is
dangerous voltage. When wiring, please follow the safe Negative PV pin
Positive terminal
electricity regulations. PV cable PV pin Negative terminal
Step 2. Use a wire stripper to strip the 7mm insulation layer of the wire end.
Note!
Please do not make PV positive or negative ground!
Note! mm
The following PV module requirements need to be applied 7.0
to each input range: Wire stripper
1. Same model
2. Same quantity Step 3. Tighten the cable with the insulation layer stripped and insert it
3. The same array into the metal terminal (see Figure 1), make sure all wires are inserted Into
4. The same angle the metal terminal (see Figure 2).
Notice!
The series inverters support the following PV module
connection modes.
1. Method 1: Multi
+
- PV 11
PV
+
X3 HYD G4
Inverter
-
+
Positive PV pin
PV 22
PV
-
Negative PV pin
2. Method 2: Common Figure 1
- PV 11
PV
+
Inverter
X3 HYD G4
+
PV 22
PV
Positive metal terminal
-
Negative metal terminal
+
Figure 2
- PV 11
PV
+
Inverter
X3 HYD G4
+
PV 22
PV
-
PV Inverter
32 33
Electrical Connections Electrical Connections
Step 4. Tighten the PV pin needle and the wiring harness to make the The following is the location of the inverter's positive and negative
connection tight without looseness. (PV-/PV+) ports.
Note: Before inserting the PV terminal, please turn on the switch of
the PV module and use a multimeter to measure the positive and
negative poles of the PV terminal port to prevent reverse
connection.
Crimping Tool
Multimeter
Step 5. The PV joint is divided into 2 parts - the plug and the fastening DC Voltage
head. Insert the cable through the fastening head and the opposite Range ≥1100 V DC
plug. Note that the red and black lines correspond to differentof
plugs. Finally, force the cable pair into the plug, will a "click" sound
,which indicates that the connection is complete.
Step 6. Tighten the fastening head and into insert the corresponding
positive and negative (PV-/PV+) ports of the inverter.
PV+
Positive terminal
PV-
34 35
Electrical Connections Electrical Connections
5.2 Grid Port and EPS(Off-grid) Output Connection 5.3 EPS(Off-grid) Block Diagram
The inverter is three-phase inverter. Suitable for rated voltage The inverter has an EPS(Off-grid) function. When the grid is connected,
380/400/415V, frequency 50/60Hz. Other technical requests the inverter outputs go through the Grid port, and when the grid is
should comply with the requirement of the local public grid. disconnected, the inverter outputs go through the EPS(Off-grid) port.
The EPS(Off-grid) function can be connected to part of the load, Please
Ø Grid port connection refer to the following diagram for the wiring.
If you want to save installation time, you will need an accessory. If you
Grid Cable and Micro-breaker recommended need a solution, please contact our sales staff.
(apply to version D/M) Ø EPS(Off-grid) wiring diagram
Model X3-Hybrid-5.0 X3-Hybrid-6.0 X3-Hybrid-8.0 X3-Hybrid-10.0 X3-Hybrid-12.0 X3-Hybrid-15.0
Diagram A: N line and PE line separate wiring , D series inverters ;
Cable (copper) 4~6mm² 4~6mm² 4~6mm² 5~6mm² 5~6mm² 5~6mm²
(For most countries)
Micro-Breaker 20A 20A 32A 40A 40A 40A
Breaker
E-BAR Grid
RCD
Breaker
Breaker
Battery
Distribution Box
EPS(Off-grid) loads Loads
Figure: Wrong connection of load and inverter N-BAR for EPS(Off-grid) loads N-BAR for loads
36 37
Electrical Connections Electrical Connections
Diagram B: N line and PE line separate wiring, M series inverters ; Diagram D: N line and PE line together, all load connection EPS(Off-grid)
(For most countries) scheme; ( Applicable to Australia)
PV 1 PV 1
PV 2
Inverter Inverter PV 2
CT CT
CT-R Main Breaker/RCD
RCD CT-R Main Breaker
BAT Grid EPS(Off-grid) CT-S EPS(Off-grid)
CT-T
BAT Grid CT-S
N CT-T
N
X3-Matebox N
E-BAR
E-BAR
E-BAR Grid X3-Matebox Grid
Breaker
Breaker
Breaker
Breaker
N-BAR for EPS(Off-grid) loads N-BAR for loads N-BAR for EPS(Off-grid) loads N-BAR for loads
Diagram C: N line and PE line together, D series inverters; X3-Matebox is a convenient wiring accessory. Please refer to
( Applicable to Australia) X3-Matebox for details. If you need to purchase X3-Matebox, please
contact us.
PV 1
Inverter PV 2
The RCD on the gure represents a leakage protection
CT device with a circuit breaker function.
Breaker RCD CT-R Main Breaker
To use X3-Matebox's Diagram B and Diagram D, you
CT-S
need to set "X3-Matebox" to "Enable" in "Settings";
BAT Grid EPS(Off-grid)
CT-T The Australian customer must shorten the N lines of the
N
Grid and the EPS(Off-grid) in the X3-Matebox.
If your local wiring method does not follow the above
E-BAR Grid operation guide, especially the neutral wire, ground wire,
Breaker
N RCD wire, please contact our company before operation.
RCD
Distribution Box
Breaker
Breaker
Battery
EPS(Off-grid) loads Loads
38 39
Electrical Connections Electrical Connections
Connection requirements
Warning!
Ensure that the EPS(Off-grid) load rated power is within the Note: Check the grid voltage and compare the voltage range (see
EPS(Off-grid) rated output power range, otherwise, the technical data).
inverter will report an "overload" warning. Disconnect the circuit board from all power sources to prevent
electric shock.
When “overload” occurs, adjust the load power to make sure it
is within the EPS(Off-grid) rated output power range, and the The Grid and the EPS(Off-grid) ports of the M series inverter have
inverter will automatically return to normal. been connected, for specific installation details, please refer to the
X3-Matebox Quick Installation Guide. And the D series needs to be
For non-linear loads, ensure that the inrush current power is wired according to the following steps.
within the EPS(Off-grid) rated output power range.
When the configuration current is less than the maximum DC Step 1. Prepare a Grid cable (five-core wire) and an EPS(Off-grid)
input current, the capacity and voltage of lithium and lead cable (four-core wire), and then find the European terminal and
acid will decrease linearly. waterproof cover in the accessory bag.
The following table shows some common loads for your reference. mm m
~60 0m
55 5~6
L1 L1= L1=
5
L1
Note: Please check with the manufacturer for high-power inductive loads.
Power Instance
Common
Content 6 mm² Grid(Five-Core Cable) 6 mm² EPS(Off-grid)(Four-Core Cable)
equipment Equipment
Start Rated Start Rated
Note: The EPS load of the inverter does not support a half-wave load,
and the half-wave load cannot be used here.
40 41
Electrical Connection Electrical Connection
Step 2. First remove the waterproof housing plug, and then the Grid Step 3. Remove the 12mm insulation layer at the end of the wire. Insert
and EPS(Off-grid) cables through the waterproof housing the European-style terminals respectively, and make sure that the stripped
corresponding to the Grid and EPS(Off-grid) ports. ends are inserted into the European-style terminal, and finally use
crimping pliers to press tightly.
Diagonal pliers
L2
L2 =1 2m m
m
12m
L2 L2=
Crimping Tool
Grid
Grid
EPS(Off-grid)
d)
EPS(Off-gri
42 43
Electrical Connection Electrical Connection
Step 4. Find the location of the AC interface on the inverter, insert the Step 6. Tighten the waterproof fastening head.
crimped terminals into the UW10 terminals L1, L2,L3,N, and PE according
to the wire sequence, and use a flat-blade screwdriver to tighten the
screws. (Torque: 1.5±0.1N·m)
Torque screwdriver
( Torque: 1.5±0.1N·m)
Hexagon keys
( Torque: 0.8±0.1N·m)
44 45
Electrical Connection Electrical Connection
Upgrade/Dongle
EPS
Step 3. Tighten the cable with the insulation layer stripped and insert it into
the metal terminal (see Figure 1), make sure all wires are inserted Into the
metal terminal (see Figure 2).
Non-polar
DC MCB
Communication line connection
46 47
Electrical Connection Electrical Connection
Step 4. Tighten the BAT pin needle and the wiring harness to make Step 7. Insert the battery power lines into the corresponding BAT
the connection tight without looseness. port (+), (-) of the inverter.
Crimping Tool
Dongle/Upgrade
Do
BAT+ 5
1 2 3 4 6 7 8
48 49
Electrical Connection Electrical Connection
DRM5 Do not generate power Our company will not be responsible for the impact caused by
the use of other appliances.
DRM6 Do not generate more than 50% of rated power
Do not generate more than 75% of rated power AND Ø Electric meter connection diagram
DRM7
Sink reactive power if capable
Upgrade/Dongle
1 1 2 3 4 5 6 7 8
EPS
Load
Note! in out
Currently only PIN6 (DRM0) and PIN1 (DRM1/5) are functional, other
L1
PIN functions are under development. L2
L3
N
PE
Household Meter
Meter1
Grid (three-phase meter)
out in
If the user has other power generation
equipment (such as inverter) at home and
wants to monitor both, the inverter provides
Meter2 communication function to Other power
Meter2
monitor the power generation equipment. (three-phase meter) generation equipment
For more information, please contact us.
Note: If you want to connect the meter, please ground the GND terminal of the Meter1.
50 51
Electrical Connection Electrical Connection
Ø C T Connection
The current sensor measures the current on the live wire between the Note for CT connection:
inverter and the public grid.
Note!
CT connection diagram • Do not place the CT on the N wire or ground wire.
• Do not put CT on the N line and L line at the same time.
• Do not place the CT on the side where the arrow points to
com
the inverter.
• Do not place the CT on non-insulated wires.
• The cable length between CT and inverter should not
exceed 100 meters.
Upgrade/Dongle
L1 CT-R
L2 CT-S
L3 CT-T 1 2 3 4 5 6 7 8
N
Note:The arrow on the CT 8 CT-R-1 CT-S-1 CT-T-1 485A 485B CT-T-2 CT-S-2 CT-R-2
Meter/CT port is at the
must point at the public bottom of the inverter.
grid.
Public Grid
electricity
CT Note!
Meter/CT
CT/Meter Setting
>Select
CT
52 53
Electrical Connection Electrical Connection
EPS(Off-grid)
PE
Battery
should make 10 inverters maximumly connected in one system and
Critical Load
three-phase
CAN R S T N R S T N
N T S R
+
diagram 2 allows up to 3 inverters to be connected in one system. In
Slave
Inverter
these two systems, one inverter will be set as the “Master inverter”
Grid
PV+ PV-
which will control every other inverters. Diagram 1 system needs to
be equipped with an X3-EPS Parallel Box (G2), and communicate
single-phase
Critical Load
L N
with the "Master Inverter", and all other slave inverters are connected
......
to the "Master Inverter" in parallel via network cable.
CAN CAN PE
... ...
Ø System Diagram
single-phase
Critical Load
-
L N
+
Master
PE
Battery
-
Inverter
Critical Load
three-phase
CAN R S T N R S T N
N T S R
+
CAN R S T N
N
S
T
S
T
R
R
EPS
PV+ PV-
Slave
Inverter
Grid
PV+ PV-
Meter
single-phase
Critical Load
NormalLoad NormalLoad
three-phase single-phase
L N
L N
......
CAN CAN PE
... ...
R S T N
Grid EPS (Off-grid)
R S T N CAN PE
Battery
Meter
single-phase
Critical Load
-
485
L N
+
Master
Inverter
N
S
T
R
CAN R S T N
N
S
T
S
T
R
R
PV+ PV-
Grid
EPS Load
X3-EPS Parallel
COM
Box (G2)
RS T N
Meter
Grid
Diagram 2
NormalLoad NormalLoad
three-phase single-phase
L N
Important Warning!
The hybrid parallel system is extremely complex and a
R S T N
Grid
There are three work modes in parallel system, and your acknowledge
Diagram 1
of different inverter’s work modes will help you understand parallel
system better, therefore please read it carefully before operating.
54 55
Electrical Connection Electrical Connection
Only if no one inverter is set as a “Master”, all inverters are in For diagram 2
Free mode
free mode in the system. Step1: Connect all inverters' communication together by connecting
When one inverter is set as a “Master”, this inverter enters network cables between CAN ports.
Master mode master mode. - Use standard network cables for CAN-CAN connection.
Master mode can be changed to free mode. - Use network cable to connect master inverter CAN2 port and slave 1
Once one inverter is set as a “Master”, all other inverters will inverter CAN1 port, and connect slave 1 inverter CAN2 port and slave2
Slave mode enter slave mode automatically. slave mode can not be inverter CAN1 port.
- Use network cable to connect master inverter meter port and meter.
changed from other modes by LCD setting.
Ø Wiring Operation and LCD Setting Inverter Inverter Inverter
Note: Before operation, please make sure that the inverter slave2 slave1 Master
meets the following three conditions, Meter
CAN1 CAN2 CAN1 CAN2 Meter
1. The software version of all inverters is the same;
2. The power range of all inverter models is the same; network cable network cable
Inverter
Master
Inverter
slave1
...... Inverter
slave8
Inverter
slave9
Meter Meter CAN CAN(2) CAN(1) CAN(2) CAN(1) CAN(2) CAN(1) CAN(2) CAN(1)
network (1) ......
cable network cable n=10
X3- EPS Parallel EPS
Box (G2) COM
Step 3: Turn on the power of the entire system, nd the inverter connected Ø LCD display
to the meter, enter the setting page of the inverter LCD screen, click on the
parallel settings, and select "master control"; then enter the Main display:
"resistance switch" and set it to " ON"; Once inverter enters parallel system, the “today yield” will be replaced by “
Finally, nd the last slave in the parallel system and enter the setting page Inverter Class”, and parallel relevant fault has a higher priority than other
of the inverter LCD screen and set the "resistance switch" to "ON". faults and will be showed rstly on main display.
58 59
Electrical Connection Electrical Connection
Once slave inverter exit from system and be running as an External communication equipment controls the inverter:
independent unit, its all setting will be re-excuted.
The rest of this section covers several important parallel control
functions, and the next page table shows which LCD options are
controlled by master inverter and which can work independently.
Off mode setting:
Off mode can only be set by master inverter ( long press ESC button on
LCD ) .
Date Read
Safety setting:
System safety protection is cancelled by master inverter’s safety. slave
inverter protection mechanism will only be triggered by master
inverter’s instructions.
Inverter communication control external equipment:
Self-use setting:
If system is running as self-use mode, please note the Feedin Power Limit
set of master inverter is for the overall system and the corresponding set
of slave inverter is invalid.
60 61
Electrical Connection Electrical Connection
Torque screwdriver
( Torque: 1.2±0.1N·m)
com
Grid
Upgrade/Dongle
EPS
1 2 3 4 5 6 7 8
Diagonal pliers
1 1 2 3 4 5 6 7 8
m
m
.00
CAN 15
CAN Note!
DRM
Shut down At present, there are only PIN6 (DRM0) and PINI (DRM1 /5), and
oher PIN functions are under development.
62 63
Electrical Connection Electrical Connection
Step 5. Connect the DRM / CAN / OFF communication cable, and Step 6. Lock the cover plate and tighten the fastening head.
insert the cable into the corresponding port.
Upgrade/Dongle
EPS
Upgrade/Dongle
Torque screwdriver
( Torque: 1.2±0.1N·m)
64 65
Electrical Connection Electrical Connection
Step 7: Finally, find the corresponding COM, BMS, Meter, CT, CAN, DRM, Ø METER/CT communication cable
OFF poets on the inverter and insert the communication cable into the
corresponding ports.
METER/CT pin is defined as follow:
1 1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
8 CT-R-1 CT-S-1 CT-T-1 485A 485B CT-T-2 CT-S-2 CT-R-2
1 1 2 3 4 5 6 7 8
Note!
Only one of the Meter and CT connections can be selected.
Meter cable goes to pin terminal 4 and 5; CT-R cable to PIN
Note! Terminal 1 and 8; CT-S cable to PIN Terminal 2 and 7; CT-T cable is
The communication port on the lithium battery must be connected to terminals 3 and 6.
consistent with the definition of pins 4, 5, 7, and 8 above;
A
B
66 67
Electrical Connection Electrical Connection
2) One side of the finished cable, Waterproof connector with RJ45 is Screw waterproof connectors tightly.
inserted into the inverter, and one side of the RJ45 terminal is
inserted into the CT connection.
Upgrade/Dongle
EPS
COM
Upgrade/Dongle
EPS
Distribution box
Note!
When installing, pay attention to water resistance. All the
connected parts of CT must be put into the distribution cabinet.
68 69
Electrical Connection Electrical Connection
Ground wire port of the M series inverter has been connected, and the D
series needs to be wired according to the following steps.
4 mm²
L1
mm
1 +3
=L
L2
Diagonal plier
Crimping Tool
70 71
Electrical Connection Electrical Connection
C
5.7 Monitoring Connection (Accessories)
Step 4. Find the ground connection port on the inverter, and screw The inverter provides a DONGLE port, which can transmit data of the
the ground wire on the inverter with an M5 Hexagon keys. inverter to the monitoring website via Pocket WiFi, Pocket 4G
and Pocket LAN. (If necessary, purchase products from us.)
Upgrade/Dongle
EPS
Cloud
Router
Dongle/Upgra
de
Hexagon keys
Torque: 0.8±0.2N·m
72 73
Electrical Connection Electrical Connection
PV 1
PV 2
Inverter
CT
Breaker CT-R Main Breaker/RCD
Breaker
E-BAR Grid
RCD
Breaker
Breaker
Battery Distribution Box
Please check the Pocket WiFi user manual/Pocket LAN user manual /4G
user manual. N-BAR for EPS(Off-grid) loads N-BAR for loads
74 75
Electrical Connection Electrical Connection
76 77
Firmware Upgrading Firmware Upgrading
6 Firmware Upgrade
Ø Upgrade notes 2) Please contact our service support to obtain the firmware, and store the
firmware in the U disk according to the following path.
Please read the following precautions before upgrading.
Update:
For ARM le: “update \ARM\618.00406.00_HYB_3P_ARM_V1.13_1220.usb”;
Warning!
For DSP le: “update\DSP\618.00405.00_HYB_3P_DSP_V1.14_1215.usb”;
- In order to upgrade the firmware smoothly, if the DSP
and ARM firmware need to be upgraded, please note that
ARM firmware must be upgraded first, then DSP firmware! Ø Upgrade steps
- Please make sure that the category format is correct, do
Step 1. Please save the "Upgrade" firmware in your U disk first, and press
not modify the firmware file name, Otherwise, the inverter
the "Enter" button on the inverter screen for 5 seconds to enter the OFF
may not work!
mode.
Warning!
- For the inverter, ensure that the PV input voltage is
greater than 180V (upgrade on sunny days). please
ensure that the battery SOC is greater than 20% or the
battery input voltage is greater than 180V. Otherwise, it
may cause serious failure during the upgrade process!
Long press for 5
seconds
Caution!
- If the ARM firmware upgrade fails or stops, please do
not unplug the U disk power off the inverter and Step 2. Find the "Upgrade" port of the inverter, unplug the monitoring
restart it. Then repeat the upgrade steps. module (Pocket WiFi/ Pocket 4G/Pocket 4G) by hand, and insert the USB
flash drive.
Caution!
- If the DSP firmware upgrade fails or stops, please check
whether the power is off. If it is normal, plug in the U disk
again and repeat the upgrade.
Ø Upgrade preparation
1) Please check the inverter version and prepare a U disk (USB 2.0/3.0) and
personal computer before upgrading.
Caution!
- Please make sure that the size of the U disk is smaller
than 32G, and the format is FAT 16 or FAT 32.
78 79
Firmware Upgrading Firmware Upgrading
Step 5. For DSP: Please wait for 10 seconds. When "Update" page shown
as below, press down to select "DSP" and then press Enter. Please confirm
the firmware version again and press Enter to upgrade. The upgrade
/Up gra de
takes about 2 minutes.
(i) (j)
/Upgrade
Step 6. After the upgrade is completed, the LCD screen displays" Upgrade
Successful" .
Upgrade(DSP)
Upgrade Successful
Step 3. LCD operation, enter the upgrade interface "update", as shown
below (a): Please press the up and down keys to select ARM, then press
down to set "OK", press the enter key to enter the software version (k)
interface; Step 7. Plug off the U disk, press "Esc" to return to the main interface, and
Upgrade Selection Upgrade(ARM) long press the enter key to exit the mode.
>ARM Cancel
DSP >OK
Caution!
- Please strictly follow each step from step 1-6, don't
miss it.
(a) (b)
- Please confirm the ARM/DSP firmware version on the
USB flash drive.
Step 4. Please confirm the new firmware version again and select the
firmware to upgrade. The upgrade takes about 20 seconds. Tip: If the display screen is stuck on "X3-Hybrid G4" after the upgrade,
(d) When it is completed, the LCD screen returns to the "Update" page. please turn off the photovoltaic power supply and restart, and the inverter
will restart and return to normal. If not,
Update(ARM) Update(ARM) Update
> 618.00406.00_HYB_ >ARM
please contact us for help.
Upgrading---------25%
3P_ARM_V1.13_1220. DSP
usb
(c) (d) (e)
80 81
Setting Setting
Self Use
Work Mode
2 Feed-in priority
Backup mode Date&Time
Forced discharge
Language
Manual Forced charge
EPSmute
Stop Chrg & Dischrg
Self-use mode
PV1 Feed-in Priority
System Status
PV2
Backup mode
3 Battery
Char & Disc period
On-grid
Dry Contact
EPS User settings
User Password
Meter/CT
Safety Code
Parallel Status
Grid Parameters
4
Charger
Export Control
Meter/CT Settings
Name Description On-grid
Self Test
History Data
LCD Display inverter information on the LCD display. EPS(Off-grid) Shadow Fix
Screen 5
Meter/CT-1 Modbus
Blue light: The inverter is in normal state or EPS(Off-grid) mode. Meter-2 External ATS
Blue ashing: The inverter is in the waiting, checking state Error Logs Power Factor
or the system switch is off.
Off: The inverter is in a fault state. Pu Function
FVRT Function
LED Green: The battery communication is normal but the battery
Power limit
Indicator MCB is disconnected, and the battery communication is
settings
6
light normal and working normally. DRM Function
Green ashing: The battery communication is normal and Parallel Setting
in an idle state.
Main Breaker Limit
Off: The battery does not communicate with the inverter.
Phase Unbalanced
Red light on: The inverter is in a fault state.
Advanced settings EPS Setting
Off: The inverter has no error.
As4777 Setting
ESC button: Return from the current interface or function. Reset
Up button: Move the cursor to the upper part or increase the Battery Heating
Key value. Inverter
Advance Password
Function 7
About
Down button: Move the cursor down or decrease the value. Battery
ExternalGen
Internal Code
Enter button: Con rm selection. Pgrid Bias
Note:" "This part of the content cannot be set by the end user. Please contact
the installer or our company if necessary.
82 83
Setting Setting
History Data
Power 0W
Today 0.0KWh
Battery 80% Settings
Normal
About
Ø Menu interface
Ø System ON/OFF
System ON/OFF
Menu Switch
>System ON/OFF
Work Mode >ON<
System Status
84 85
Setting Setting
Work Mode
Feed-in priority enough. The battery will not discharge.
Work Mode (PV< Battery charge, PV + Grid → Battery)
Backup mode Discharge time period: PV+BAT will power the loads together. If the power is
>Work Mode
still not enough, the remaining power will be taken from the grid.
Self Use Feed-in (PV<Load, PV + Battery + Grid → Load)
Manual Press Ent to save priority
③Without PV power
Mode selection, there are 4 working modes to choose from. Active Charging time period: The grid will power the home loads and
also charge the battery;
Name Description (PV=0, Grid → Load + Battery)
Active Discharge time period: The battery will power the home loads
The self-use mode is suitable for areas with low feed-in subsidies rstly. If the battery power is not enough, the remaining power will be
and high electricity prices. taken from the grid. The inverter will enter into the idle mode.
① When the power of PV is sufficient (PV=0, Battery+Grid → Load)
Active Charging or Discharge time period: PV will power the Battery min SOC can be set:10%-100%.;
battery. When the battery is fully charged, PV will power the load, Charge battery to min SOC can be set:10%-100%.
and then sell the surplus power to the grid.( The inverter will limit The Back-up mode is suitable for areas with frequent power outages. Same
the output if Feed-in limit or zero feed-in is needed) working logic with “Self-use” mode. This mode will maintain the battery
(PV>Battery charge, PV →Battery→Load → Grid) capacity at a relatively high level. (Users' setting) to ensure that the
② When the power of PV is insufficient emergency loads can be used when the grid is off. Customers no need to
Backup worry about the battery capacity.
Active Charging time period: PV will power the battery and the
remaining power will be taken from the grid when PV is not mode Battery min SOC can be set:30%-100%.
enough. PV and grid power will charge the battery until it reaches Charge battery to min SOC can be set:30%-100%.
the set value. And then PV will power the load and the remaining The EPS(Off-grid) mode is used when the power grid is off. System will
Self Use power will be taken from the grid when PV is not enough. The provides emergency power through PV and batteries to supply power to
battery will not discharge at this time. the household loads. (Battery is necessary)
(PV<Battery charge, PV + Grid → Battery) ①When the power of PV is sufficient
Active Discharge time period: PV+BAT will power the loads PV will power the loads rstly, and surplus power will charge to the battery.
together. If the power is still not enough, the remaining power (PV>Load , PV → Load → Battery)
will be taken from the grid. ②When the power of PV is insufficient
(PV<Load, PV + Battery + Grid → Load) EPS
③ Without PV power (Off-grid) The remaining power will be taken from the battery.
(PV<Load, PV+Battery → Load → Battery)
Active Charging time period: The grid supplies the loads and also ③Without PV power
can charge the battery; The battery will power the emergency loads until the battery reached the
(PV=0, Grid → Load + Battery) min SOC, then the inverter will enter into the idle mode.
Active Discharge time period: The battery will power the home (PV=0 , Battery → Load)
loads rstly. If the battery power is not enough ,the remaining EPS(off-grid) SOC-min condition is adjustable within the range of
power will be taken from the grid. The inverter will enter into the 1 0%-25%;
idle mode.
Note: in the case of grid connection, all working modes work normally when the battery
(PV=0, Battery+Grid → Load )
Battery min SOC can be set:10%-100%; SOC >5%. When the Min SOC of the system - the actual SOC of the battery > 5%, PV or
Charge battery to min SOC can be set:10%-100%. Grid will force the battery to charge to Min SOC +1%, and then return to the normal
working mode set by the user.
The Feed-in priority mode is suitable for areas with high feed-in Note: when the actual SOC of the battery is ≤ Min SOC, if the mains power is lost,
subsidies, but has feed-in power limitation. the inverter will not enter the EPS (Off-grid) mode. The inverter is in EPS Waiting
①When the power of PV is sufficient
state, at which time the PV will charge the battery. When the battery capacity
Active Charging time period: PV power the battery to the set value,
reaches 31%, the machine will automatically enter EPS (Off-grid) mode.
and then power the load, and sell the surplus power to the grid.
Feed-in Manual mode, there are three options to choose from: forced
If the local grid company limits the grid-connected power of the
priority
inverter, the excess energy continues to charge the battery. charging, forced discharge, stop charging and discharging (grid-
(PV>Battery, PV→Battery→Load→Grid → Battery) connected power).
Active Discharge time period: PV will power the loads rstly, and Work Mode Work Mode Work Mode
surplus power will feed-in to the grid. >Manual >Manual >Manual
(PV<Load, PV → Load → Grid ) Forced Charge Forced Discharge Stop Chrg&Dischrg
86 87
Setting Setting
PV2 b)
System Status
On-grid A On-grid B
Battery c)
Ua 0.0V Ub 0.0V
On-grid d) Ia 0.0A Ib 0.0A
PaOut 0W PbOut 0W
EPS e)
Meter/CT f)
On-grid C Grid Frenquency
Uc 0.0V Fa 0.00Hz
System status contains six content: PV1/PV2/Battery/On-grid Ic 0.0A Fb 0.00Hz
(energy feed into or buy from the grid)and EPS(Off-grid) and so on. PcOut 0W Fc 0.00Hz
Press up and down to select, press "Enter" to con rm the selection,
and press "ESC" to return to the menu.
e ) EPS
a/b ) PV1, PV2 Here you can see the inverter of voltage, current, frequency and
Here you can see the voltage, current and power of the pv1 and Pv2. power.
Photovoltaic panels respectively;
EPS_Spower EPS A
PV1 PV2 PaS 0VA Ua 0.0V
PbS 0VA Ia 0.0A
>U 0.0V >U 0.0V PcS 0VA PaActive 0W
I 0.0A I 0.0A Frequency
P 0W P 0W Freq
EPS B EPS C 0.00Hz
Ub 0.0V Uc 0.0V
c ) Battery Ib 0.0A Ic 0.0A
This status shows the battery condition of the system. Including PbActive 0W PcActive 0W
battery voltage and battery current, Battery power, battery capacity,
battery temperature, BMS connection status. The meaning of the
sign of battery current and power: "+" means charging; "-" means f ) Meter/CT
discharging. Here you can see the data showing the meter or the CT.
Battery Battery
U 400.0V Meter/CT
I -1.0A U 400.0V >Meter/CT1-A -6w
P -400W I -1.0A Meter/CT1-B -6w
SoC 0% P -400W Meter/CT1-C -6w
Cell Temp 20℃ NTC Temp
BMS Connected > Meter2-A -6w
Mete2-B -6w
Meter2-C -6w
88 89
Setting Setting
EPS b)
Error logs
Meter/CT-1 c) >No error
Meter-2 d)
Error Logs e)
Ø User Settings
User settings
Here is a record of the power capacity of the inverter connected to
the grid today and the total. Feed-in Priority e)
90 91
Setting Setting
Here you can set the inverter time, language, working modeSOC, Self-use Mode Self-use Mode
charging and discharging time period and user password.
>Min SOC:
Min SOC
Charge from grid
User Setting 10%
Date & Time
> Language Self-use Mode Self-use Mode
EPS mute
>Charge from grid >Charge battery to
a ) Date time
Enable 10%
This interface is for users to set the system date and time.
92 93
Setting Setting
94 95
Setting Setting
Ø Advance settings
Enter
☆ Country
Safety Code a) >Safety **Previous page
FVRT Function l) >AS4777_2020_A<
Back
Grid Parameters b) Up Down
Power limit m)
Charge c) Country
DRM Function n)
Advanced settings
Export Control d) >AS4777_2020_B<
Parallel Setting o)
Advanced settings
Up Down
Meter/CT Settings e)
Main Breaker Limit p)
f) Country
Self Test Battery Heating q)
>AS4777_2020_C<
Shadow Fix g) EPS(Off-grid) Setting r) Up Down
Modbus h) AS 4777 Setting s) Country
External ATS i) Phase Unbalanced t) >New Zealand<
Power Factor j) Reset u)
Region Australia A Australia B Australia C New Zealand
Pu Function k) Advance Password v) Standarad Setting
AS4777_2020_A AS4777_2020_B AS4777_2020_C New Zealand
Code Name Range
ExternalGen w) OV-G-V 265V 265V 265V 265V 230-300V
Pgrid Bias x) OV-G-V2 275V 275V 275V 275V 1-2S
OV-GV2-T 0.1S 0.1S 0.1S 0.1S 230-300V
All advanced settings can be set here, such as battery, grid, EPS(Off-grid), UN-G-V1 180V 180V 180V 180V 0-0.2S
etc. UNGV1-T 10S 10S 10S 10S 40-230V
"Advanced" setting is generally customization and resetting for battery UN-G-V2 70V 70V 70V 70V 10-11S
UNGV2-T 1.5S 1.5S 1.5S 1.5S 40-230V
and grid. Each part has lower level parts.
OV-G-F1 52HZ 52HZ 55HZ 55HZ 1-2S
Please contact your installer or factory and enter the installer password. OVGF1-T 0.1S 0.1S 0.1S 0.1S 50-55HZ
OV-G-F2 52HZ 52HZ 55HZ 55HZ 0-0.2S
Advanced OVGF2-T 0.1S 0.1S 0.1S 0.1S 50-55HZ
Safety Code OV-GV1-T 1.5S 1.5S 1.5S 1.5S 0-0.2S
UN-G-F1 47HZ 47HZ 45HZ 45HZ 45-50HZ
> Grid Parameters
UNGF1-T 1.5S 1.5S 5S 1.5S 1-6S
UN-G-F2 47HZ 47HZ 45HZ 45HZ 45-50HZ
UNGF2-T 1.5S 1.5S 5S 1.5S 1-6S
a) Safety code Startup-T 60S 60S 60S 60S 15-1000S
User can set safety standard according to different countries and grid tied Restore-T 60S 60S 60S 60S 15-600S
stanndards.There are 8 standards to select. (May be changed or added Recover-VH 253V 253V 253V 253V
without notice) Recover-VL 205V 205V 205V 198V
Recover-FH 50.15Hz 50.15Hz 50.15Hz 50.15Hz
Item Standard Country Recover-FL 47.5Hz 47.5Hz 47.5Hz 47.5Hz
1 VDE 0126 German Start-VH 253V 253V 253V 253V
2 ARN 4015 German Start-VL 205V 205V 205V 198V
3 AS 4777 Australia Start-FH 50.15Hz 50.15Hz 50.15Hz 50.15Hz
4 EN 50549_EU Netherland Start-FL 47.5Hz 47.5Hz 47.5Hz 47.5Hz
5 G98/G99 UK
6 EN 50438_NL Netherland
7 CEI 0-21 Italy
8 IEC61727_In India
96 97
Setting Setting
Reconnection Time of local laws and regulations, which are constantly increasing. Please
OverVoltage_L2 refer to the contents displayed on the inverter screen.
Grid Parameters
Checking Time
UnderVoltage_L2 OFPL_Setting Grid Parameters Grid Parameters Grid Parameters
OverFreq_L2 >OverVoltage_L1 >UnderVoltage_L1 >OverFreq_L1
UFPL_Setting 265.0V 180.0V 52.00Hz
UnderFreq_L2
Local Command: 0/1 Grid Parameters Grid Parameters Grid Parameters
OverFreq_L2 Connect Slope: xx% >UnderFreq_L1 >Vac 10min Avg >OverVoltage_L2
UnderFreq_L2 47.00Hz 258.0V 275.0V
Reconnect Slope: xx%
Tovp_L1 Grid Parameters Grid Parameters Grid Parameters
Vac 10min Time: 603 S
>UnderVoltage_L2 >OverFreq_L2 >UnderFreq_L2
Tuvp_L1 70.0V 52.00Hz 47.00Hz
Tofp_L1 Grid Parameters Grid Parameters Grid Parameters
>Tovp_L1 >Tuvp_L1 >Tofp_L1
OFPL_Setting OFPL_Setting OFPL_Setting 1000ms 10000ms 100ms
OFPL_Curve OFPL_Curve OFPL_RemovePoint(Aus.)
Grid Parameters Grid Parameters Grid Parameters
Symmetric Asymmetry 50.10Hz
>Tufp_L1 >Tovp_L2 >Tuvp_L2
OFPL_Setting OFPL_Setting OFPL_Setting 1000ms 100ms 1000ms
98 99
Setting Setting
100 101
Setting Setting
QuLockSetting QuLockSetting
Power Factor Power Factor
QuLockIn QuLockOut
Mode Select Mode Select
20% 5%
> Under-Excited < > Curve <
k ) PU Function (applicable to specific countries, please refer to local
Power Factor Power Factor grid requirements)
Mode Select The PU function is a volt-watt response mode required by certain
Mode Select
national standards such as AS4777.2. This function can control the
> Q(u) < > Fixed Q Power < active power of the inverter according to the grid voltage.
Selecting "Enable" means that this function is turned on and is the
Mode Comment
default value.
Off -
Select "Disable" to deactivate the function.
Over-Excited PF value
PU Function PU Function PU Function
Under-Excited PF value Response V2 Response V3
>PuFunction
P1_PF
Enable 220.0V 250.0V
P2_PF
P3_PF
PU Function PU Function PU Function
P4_PF 3Tau
Response V4 SetPuPower 1
Power 1
Curve Power 2 265.0V 6~180S 100%
Power 3
PU Function PU Function PU Function
Power 4
PFLockInPoint (EU50549 only) SetPuPower 2 SetPuPower 3 SetPuPower 4
PFLockOutPoint (EU50549 only) 50% 0% 0%
3Tau
PU Function PU Function
SetQuPower1
3Tau_Charge Pu Type
SetQuPower2
10 S Static Dynamics
SetQuPower3
SetQuPower4
l ) FVRT Function(apply to50549)
QuRespondV1( AS4777.2 only)
Here you can set the high and low enable or disable.
Q( u ) QuRespondV2( AS4777.2 only)
QuRespondV3( AS4777.2 only)
FVRT Function
QuRespondV4( AS4777.2 only)
Function Control
K
Disable Enable
3Tau
QuDelayTimer m ) Power limit
QuLockEn
Power limit function, the maximum power of the AC port can be set
Fixed Q Power Q Power
by percentage.
QuLockSetting
QuLockFunction Power Limit
>Proportion
Enable Disable
1.00
102 103
Setting Setting
p/pEmax Setting
> Master > Free
f (P)
capacitive
q ) Battery Heating
0.9 0.95 If the user needs the battery heating function, you can set it to turn on
Lower limit here, and set the time period that needs to be heated, and the two time
curve A curve B periods can be set. (Only for batteries with heating function)
● Reactive power control, reactive power standard curve Q= f(V) Battery Heating Battery Heating
>Func Select: >Heating Period 1:
Q V2s=1.10Vn Start Time
Qmax V1s=1.08Vn=QuVlowRate Enable Disable 00:00
V2i=0.90Vn
V2i=0.92Vn=QuVlowRate
Battery Heating Battery Heating
V1s V2s
>Heating Period 1: >Heating Period 2:
V2i V1i V End Time Start Time
00:00 00:00
-Qmax
Battery Heating
>Heating Period 2:
End Time
00:00
104 105
Setting Setting
Ø About a ) About
Here you can see some basic information of the inverter and battery.
such as the inverter and battery SN number, software version
number, and system run time.
About
Inverter SN >Inverter
Battery
Register SN
DSP
Inverter
ARM Inverter
On-grid Run Time
Inverter Inverter
EPS Run Time
>Inverter SN >Register
Bat_PS1 SN 01234560123456 01234560123456
About Bat_PS2 SN
Battery Inverter Inverter
Bat_PS3 SN
>DSP >ARM
Bat_PS4 SN 2.07 1.03
BatteryM Version
Inverter Inverter
BatteryS Version > EPS(Off-grid) Runtime >On-grid runtime
Inverter code 20.0H 45.9H
Internal Code
BMS Code
108 109
Setting Setting
Battery Ø Information
Battery Battery ☆
Internal Code Internal Code ● Once settings are selected at commissioning they are locked to view
> BMS code
only.
> Inverter code
01 00 01 xx
● In case of a Path Diagram with the mark of “☆”, it indicates that such a
Path Diagram is only applicable to Australia and New Zealand.
110 111
Troubleshooting Troubleshooting
8 Troubleshooting Number
DCI overcurrent protection fault.
8.1 Troubleshooting IE 009 DCI OCP Fault • Wait for a while to check if it's back to normal.
• Or ask the installer for help.
This section contains information and procedures for resolving DCV EPS(Off-grid) overvoltage protection failure.
possible problems with the inverter, and provides you with IE 010 DCV OVP Fault • Wait for a while to check if it's back to normal.
• Or ask the installer for help.
troubleshooting tips to identify and solve most problems that may
occur in the inverter. This section will help you narrow down the Software Detection of Overcurrent Fault.
• Wait for a while to check if it's back to normal.
source of any problems you may encounter. Please read the IE 011 SW OCP Fault
• Shut down photovoltaic, battery and grid connections
troubleshooting steps below. • Or ask the installer for help.
Check the warning or fault information on the system control panel
Overcurrent protection fault.
or the fault code on the inverter information panel. If a message is • Check the impedance of DC input and AC output.
IE 012 RC OCP Fault
displayed, log it before doing anything further. • Wait for a while to check if it's back to normal.
• Or ask the installer for help.
Try the solutions indicated in the table below.
Insulation Fault
IE 013 Isolation Fault • Please check the wire insulation for damage.
Number • Wait for a while to check if it’s back to normal.
• Or ask the installer for help.
Overcurrent fault.
• Wait for a while to check if you're back to normal. Temperature beyond limit
IE 001 TZ Protect Fault • Disconnect PV+ PV- and batteries, reconnect. • Check if ambient temperature exceeds the limit.
IE 014 Temp Over Fault
• Or ask for help from the installer if itcan not return to normal. • Or ask the installer for help.
112 113
Troubleshooting Troubleshooting
Number Number
114 115
Troubleshooting Troubleshooting
Number Number
Battery Unbalanced Failure Battery temperature sensor malfunction
BE 009 BMS_CellImblance • Please contact the battery supplier. BE 026 BMS_TempdiffErr • Please contact the battery supplier.
Battery relay failure ------Is the inverter located in a clean, dry and well-ventilated place?
BE 016 BMS_Relay Fault • Please contact the battery supplier. ------Is the DC input circuit breaker open?
Battery type failure ------Is the specification and length of the cable adequate?
BE 017 BMS_Type_Unmatch • Upgrade the battery BMS software. ------Are the input and output connections and wiring in good
• Please contact the battery supplier.
condition?
Battery version mismatch failure ------Is the configuration set correct for your particular installation?
BE 018 BMS_Ver_ Unmatch • Upgrade the battery BMS software.
• Please contact the battery supplier.
116 117
Troubleshooting Decommissioning
Only qualified people can do the following work. 9.3 Storage and Transportation
In the process of using frequency converter, the manager should check
and maintain the machine regularly. The specific operation is as follows.
Store the inverter in a dry, temperature -40°C~70°C environment.
1. Check whether the heat sink is covered with dirt, clean the machine Pay attention to less than four machines on each stack board
and absorb dust if necessary. This work should be performed from time to during storage and transportation.
time.
2. Check whether the frequency converter indicator is normal, check 9.4 Waste Disposal
whether the frequency converter button is normal, check whether the
frequency converter display is normal. This inspection should be
If it is necessary to scrap the inverter or other related parts, be sure to
conducted at least every 6 months.
send the waste inverter and packaging materials to the designated
3. Check the input and output lines for damage or aging. This inspection location for recycling by the relevant department.
should be conducted at least every 6 months.
118 119
Disclaimer
Warranty
Registration
10 Disclaimer Form
The hybrid inverters are transported, used and operated under
limited condition, such as environmental, electrical etc. Our
company shall not be liable to provide the service, technical support For Customer (Compulsory)
or compensation under conditions listed below, including but not
limited to: Name Country
Phone Number Email
Inverter is damaged or broken by force majeure (such as Address
earthquake, flooding, thunderstorm, lighting, fire hazard, volcanic
eruption etc). State Zip Code
Inverter's warranty is expired and doesn't buy extended warranty. Product Serial Number
Can't provide the inverter's SN, warranty card or invoice.
Inverter is damaged by man-made cause.Inverter is used or Date of Commissioning
operated against any items in local policy. Installation Company Name
Inverter's installation, configuration, commissioning doesn't
follow the requirements mentioned in this manual. Installer Name Electrician License No.
Inverter is installed, refitted or operated in improper ways
mentioned in this manual without authority from us.
For Installer
Inverter is installed, operated under improper environment or
electrical condition mentioned in this manual without authority
from us. Module ( If Any )
Inverter is changed, updated or disassembled on hardware or
Module Brand
software without authority from us.
Obtain the communication protocol from other illegal channels. Module Size(W)
Build monitoring, control system without authority from us.
Connect to other brands batteries without authority from us. Number of String Number of Panel Per String
Our company will keep right to explain all the contents in this user
manual. Battery ( If Any )
Battery Type
Brand
Number of Battery Attached
For more detailed warranty terms, please visit SolaX official website: www.solaxpower.com
to check it.
614.00002.07
120
PLEASE REGISTER THE WARRANTY
IMMEDIATELY AFTER INSTALLATION!
GET YOUR WARRANTY CERTIFICATE
FROM DURACELL!
KEEP YOUR INVERTER ONLINE & WIN
DURACELL POINTS!
1
Open your
camera app
2
Wait for the
camera to
and point recognize
your device the QR code
at the QR
code
3
Click banner
or notification
Notification
Click the notification banner
OK
4Warranty
registration
when it appears page will be
on the screen loaded
automatically